Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Protection scheme
Submitted to Mr Car.
Submitted by Qaisar.
Dated: 22 Jun. 18
EHV and UHV OH lines are tall structures and have insulators with larger creepage distances
and clearances. Faults on OH lines of these levels, therefore, are rare. Rarest faults of faults are
between phases and involving three phases. Common faults are single phase to ground faults
are mostly due to flashover across insulator due to some surges (BIL are much higher than
typical lightning surge and hence are conducted away by surge arresters… making switching
surges as major cause of flashovers). Types of faults like short circuit condition in power
system network results in severe economic losses and reduces the reliability of the electrical
system. Electrical fault is an abnormal condition, caused by equipment failures such as
transformers and rotating machines and environmental conditions. Theses faults cause
interruption to electric flows, equipment damages and even cause death of humans, birds and
animals.
Types of Faults
Electrical fault is the deviation of voltages and currents from nominal values or states. Under
normal operating conditions, power system equipment or lines carry normal voltages and
currents which results in a safer operation of the system.
But when fault occurs, it causes excessively high currents to flow which causes the damage to
equipment and devices. Fault detection and analysis is necessary to select or design suitable
switchgear equipment, electromechanical relays, circuit breakers and other protection devices.
There are mainly two types of faults in the electrical power system. Those are symmetrical and
unsymmetrical faults.
1. Symmetrical faults
These are very severe faults and occur infrequently in the power systems. These are also called
as balanced faults and are of two types namely line to line to line to ground (L-L-L-G) and line
to line to line (L-L-L).
Only 2-5 percent of system faults are symmetrical faults. If these faults occur, system remains
balanced but results in severe damage to the electrical power system equipment.
2. Unsymmetrical faults
These are very common and less severe than symmetrical faults. There are mainly three types
namely line to ground (L-G), line to line (L-L) and double line to ground (LL-G) faults
Line to ground fault (L-G) is most common fault and 65-70 percent of faults are of this type.
It causes the conductor to make contact with earth or ground. 15 to 20 percent of faults are
double line to ground and causes the two conductors to make contact with ground. Line to line
faults occur when two conductors make contact with each other mainly while swinging of lines
due to winds and 5- 10 percent of the faults are of this type.
These are also called unbalanced faults since their occurrence causes unbalance in the system.
Unbalance of the system means that that impedance values are different in each phase causing
unbalance current to flow in the phases. These are more difficult to analyze and are carried by
per phase basis similar to three phase balanced faults
Factors like de-regulated market environment, economics, right of-way clearance and
environmental requirements have pushed utilities to operate transmission lines close to their
operating limits. Any fault, if not detected and isolated quickly will cascade into a system wide
disturbance causing widespread outages for a tightly interconnected system operating close to
its limits. Transmission protection systems are designed to identify the location of faults and
isolate only the faulted section. The key challenge to the transmission line protection lies in
reliably detecting and isolating faults compromising the security of the system.
As the length of electrical power transmission line is generally long enough and it runs through
open atmosphere, the probability of occurring fault in electrical power transmission line is
much higher than that of electrical power transformers and alternators. That is why a
transmission line requires much more protective schemes than a transformer and an alternator.
Protection of line should have some special features, such as-
During fault, the only circuit breaker closest to the fault point should be tripped.
If the circuit breaker closest to the faulty point, fails to trip, the circuit breaker just next to this
breaker will trip as back up.
The operating time of relay associated with protection of line should be as minimum as possible
in order to prevent unnecessary tripping of circuit breakers associated with other healthy parts
of power system.
These above mentioned requirements cause protection of transmission line much different from
protection of transformer and other equipment of power systems. The main three methods of
transmission line protection are -
Time graded over current protection.
Differential protection.
Distance protection.
At point D the circuit breaker CB-3 is installed with definite time of relay operation
0.5 sec. Successively, at point C another circuit breaker CB-2 is installed with
definite time of relay operation 1 sec. The next circuit breaker CB-1 is installed at
point B which is nearest of the point A. At point B, the relay is set at time of operation
1.5 sec. Now, assume a fault occurs at point F. Due to this fault, the faulty current
flow through all the current transformers or CTs connected in the line. But as the
time of operation of relay at point D is minimum the CB-3, associated with this relay
will trip first to isolate the faulty zone from rest part of the line. In case due to any
reason, CB-3 fails to trip, then next higher timed relay will operate to initiate the
associated CB to trip. In this case, CB-2 will trip. If CB-2 also fails to trip, then next
circuit breaker i.e. CB-1 will trip to isolate major portion of the line.
In the above figure, overall time setting of relay at point D is minimum and
successively this time setting is increased for the relays associated with the points
towards the point A. In case of any fault at point F will obviously trip CB-3 at point
D. In failure of opening CB-3, CB-2 will be operated as overall time setting is higher
in that relay at point C. Although, the time setting of relay nearest to the source is
maximum but still it will trip in shorter period, if major fault occurs near the source,
as the time of operation of relay is inversely proportional to faulty current.
Over Current Protection of Parallel Feeders
For maintaining stability of the system it is required to feed a load from source by
two or more than two feeders in parallel. If fault occurs in any of the feeders, only
that faulty feeder should be isolated from the system in order to maintain continuity
of supply from source to load. This requirement makes the protection of parallel
feeders little bit more complex than simple non direction over current protection of
line as in the case of radial feeders. The protection of parallel feeder requires to use
directional relays and to grade the time setting of relay for selective tripping.
There are two feeders connected in parallel from source to load. Both of the feeders
have non-directional over current relay at source end. These relays should be inverse
time relay. Also both of the feeders have directional relay or reverse power relay at
their load end. The reverse power relays used here should be instantaneous type.
That means these relays should be operated as soon as flow of power in the feeder
is reversed. The normal direction of power is from source to load. Now, suppose a
fault occurs at point F, say the fault current is If. This fault will get two parallel paths
from source, one through circuit breaker A only and other via CB-B, feeder-2, CB-
Q, load bus and CB-P. This is clearly shown in figure below, where IA and IB are
current of fault shared by feeder-1 and feeder-2 respectively.
As per Kirchoff's current law, IA + IB = If.