Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Volume batching of cement should be avoided because being a very fine material, its
volume is greatly affected by the way it is filled in the gauge box. It is more accurately
measured by weight. Ordinarily cement is batched by the bag. Each cement bag is packed to
contain a net weight of 50Kg, which is approximately 35 liter in volume. The quantity of
aggregate to be batched with each bag of cement would then be easily measured by using a
measuring box of 35 liter. One such a box would measure internally 40 X 35 X 25 cm.
Water is usually measured by volume in a calibrated tank or by means of flow type water
meters.
Proportions by volume are usually specified in terms of aggregates in a dry-rodded
condition, but the batch quantities must be given in the loose condition. Care must be taken
in the case of wet sand, which might bulk.
Variables in proportioning
In connection with specifying a concrete mix, four variable factors to be considered are
Water-cement ratio.
Cement content or cement-aggregate ratio.
Gradation of the aggregates.
Consistency.
Usually two or three factors are specified, and the others are adjusted to give minimum
workability and economy. Water/cement ratio expresses the dilution of the paste - cement
content varies directly with the amount of paste. Gradation of aggregate is controlled by
varying the amount of given fine and coarse aggregate. Consistency is established by
practical requirements of placing.
In brief, the effort in proportioning is to use a minimum amount of paste (and therefore
cement) that will lubricate the mass while fresh and after hardening will bind the aggregate
particles together and fill the space between them. Any excess of paste involves greater cost,
greater drying shrinkage, greater susceptibility to percolation of water and therefore attack
by aggressive waters and weathering action. This is achieved by minimising the voids by
good gradation.
Page 1
Design Mean Strength
The assumption of a normal distribution of concrete strengths forms the basis of mix design
and statistical quality control procedures for satisfying the strength requirement. For a
normal distribution, the probability of a strength lying outside specified limits either side of
the mean strength can be determined. These limits (fig. below) are usually expressed in
terms of the standard deviation s defined by,
1/ 2
fc c
2
1/ 2 f
f c f cm
2
2
s n N / mm2
n1 n1
Where fc = observed strength
fcm = best estimate of the mean strength
= fc n
n = the number of observations.
Probability values
The probabilities of a strength lying outside the range (f cm s) for different values of are
given in the above table, in which of probabilities of strengths falling below the lower limit
(fcm - s) are also given.
If the specified characteristic strength fcu is the strength below which not more than
1 in 20 of the population of strengths shall fall, it follows that,
fcu = fcm - 1.64s
Or fcm = fcu + 1.64s
Hence if the standard deviation likely to be obtained on site can be assessed, the mean
strength for which the concrete must be designed can be determined.
Table 4.1a: Relative Mixing Water Requirements for Different Consistencies of concrete
Table 4.1b: Approximate Mixing Water Content for the Reference (Plastic) Mix of Table
3.1a for different maximum sizes of Aggregate
$ Water contents of concretes with aggregates sizes greater than 40 mm are not given
For mixes with a slump of less than 30 mm.
Table 4.2. Bulk Volume of Coarse Aggregate per Unit Volume of Concrete.
Page 3
Maximum size of Bulk volume of dry rodded coarse aggregate per unit volume of concrete for
aggregate fineness modulus of sand of: __
(mm)
2.40* 2.60* 2.80* 3.00*
10 0.50 0.48 0.46 0.44
12.5 0.59 0.57 0.55 0.53
20 0.66 0.64 0.62 0.60
25 0.71 0.69 0.67 0.65
40 0.75 0.73 0.71 0.69
50 0.78 0.76 0.74 0.72
70 0.82 0.80 0.78 0.76
150 0.87 0.85 0.83 0.81
Table 4.3. Factors to be applied to the Volume of Coarse Aggregate Calculated on the
basis of Table 3.2. for Mixes of Consistence other than Plastic.
*Measured on standard cylinders. The values given are for maximum size of aggregate of
20 to 25mm.
Page 4
Structures in Severe Exposure, Prescribed by ACI Standard.
Exposure conditions
Type of structure
Structure wet continuously Structure exposed to
or frequently and exposed sea water or
to freezing and thawing* sulphates
Thin sections, such as railings,
kerbs, sills, ledges, ornamental
work, and sections with less
than 25mm cover to the
reinforcement.
0.45 0.40$
All other structures 0.50 0.45$
* Air-entrained concrete should be used under all conditions involving severe exposure.
$
When Type II or Type V cement is used, maximum water/cement ratio may be increased
by 0.05.
Page 5
Table 4.6a
RECOMMENDED SLUMPS FOR VARIOUS TYPES OF CONSTRUCTION (SI)
Types of Construction Slump, mm
Maximum Minimum
Reinforced foundation walls and footings 75 25
Plain footings, caissons, and substructure walls 75 25
Beams and reinforced walls 100 25
Building columns 100 25
Pavements and slabs 75 25
Mass concrete 75 25
Table 4.6b
APPROXIMATE MIXING-WATER AND AIR-CONTENT REQUIREMENTS
Table 4.7
FIRST ESTIMATE OF MASS OF FRESH CONCRETE (SI)
Table 4.8
Page 6
VOLUME OF COARSE AGGREGATE PER UNIT OF VOLUME OF CONCRETE
Table 4.9
ESTIMATED AVERAGE STRENGTHS FOR CONCRETE (MPa)
Table 4.10
MAXIMUM WATER/CEMENT RATIOS FOR CONCRETE
IN SEVERE EXPOSURES
Page 7
Example 4.1 .A trial mix is required for a 150-mm pavement slab being constructed in an
area where exposure to seawater is expected. Strength required is 20 MPa. Trial mix design
strength is 28.5 MPa as previous test result are not available. For the sand, FM = 2.80 and
absorption is 1.2%. The absorption of the coarse aggregate is 1.6%, and its dry-rodded
density is 1730 kg/m3. Fine aggregate is dry and coarse aggregate contains 3.0% water.
Calculate
1. Slump allowed is 25-75 mm (Table 3.1a).
2. Maximum aggregate size is 50 mm (150/3). Size 37.5 mm is chosen, as it is
economically available in the area.
3. Mixing water required is 150 kg/m3 (for 25-50 mm slump). Air content required is
5.5% (Table 3.1b).
4. Maximum W/C is 0.47 for strength and 0.45 for exposure. Use 0.45 (Tables 3.4 and
3.5).
5. Cement content is 150 kg/m3/0.45 = 333 kg/m3.
6. Volume of dry coarse aggregate per volume of concrete is 0.71 (Table 3.3).
7. Materials per m3 (Estimate only as variation in aggregate densities and water
absorption not considered).
Coarse aggregate –0.71 x 1730 = 1228 kg
Water 150 kg
Cement 333 kg
Total 1711 kg
Estimated total mass of concrete is 2350 kg (Table 3.2).
Dry mass of fine aggregate is 2350 kg-1711 kg = 639 kg
Page 8
Cement 9.99 kg
Fine aggregate (SSD): 19.2 + 1.2% x 19.2 (absorption is 1.2%) = 19.2 + 0.23 = 19.43 kg
Coarse aggregate (SSD): 38.0 – 1.4% x 38.0 [excess moisture is total (3.0) – absorbed
(1.6) = 38.0 – 0.53 = 37.47 kg
Mix water; 4.12 – 0.23 + 0.53 = 4.42 kg
Total mass = 71.31 kg
Density was 2340 kg/m3.
Therefore, batch quantities per cubic meter are
Cement: 9.99 x (2340/71.31) = 9.99 x 32.814 = 328 kg/m3
Water: 4.42 x 32.814 = 145 kg/m3
Fine aggregate (SSD): 19.43 x 32.814 = 638 kg/m3
Coarse aggregate (SSD): 37.47 x 32.814 = 1230 kg/m3
Total: 2341 kg/m3
The proportions of cementing materials can also be calculated using the volume occupied
by each component. In the ACI method illustrated in Section 7-6.2, the amount of fine
aggregate required is obtained using the masses of the components. An alternate method
uses the absolute volumes of the components. This method is also included in the CPCA
manual. The following example illustrates the calculations.
Example: 4.2. At step 7 of Example 7-8, these mix quantities were established (as summing
that cementing materials were specified instead of cement): water-150 kg, cementing
materials – 33 kg, and coarse aggregate – 1228 kg. The cm is to include 20% fly ash with
RD – 2.60. Design air content was 5.5%, and the RD values for the fine and coarse
aggregates in the dry (bulk) condition were 2.65 and 2.68 respectively. Calculate the amount
of fine aggregate required. Calculations:
Volumes occupied by the known components in 1 m3 of mix are
A water/cement ratio method of mix design, using the specifications of the Canadian
standards association (CSA) has been described by the Canadian Portland Cement
Association.
1. Exposed concrete must be air entrained and meet the requirements shown in Table 7-
18. The minimum required strength for exposure and the project required strength, if
specified, must both be met. Using the governing value and the overdesign factor
(Section 7-6.1), the mix design strength is selected.
The design (W?CM ratio is found from Table 7-14 for the strength requirement, and
from Table 7-18 for exposure. The lower value is used.
Page 9
2. The maximum aggregate size is chosen. It must not exceed the limits given in step 2
of the ACI method, Section 76.2.
3. Design slump is selected from Table 7-19.
4. Quantities for a trial mix are prepared. About 10.0 kg of cement usually results in a
quantity sufficient for the slump, air, and density tests, and the casting of three
strength cylinders. Extra aggregates, in the saturated, surface-dry condition, are
prepared. (Usually a mass of fine aggregate 5 times the mass of water, and a mass of
5,8, and 10 times for coarse aggregate of maximum size 10,20 and 40 mm
respectively will provide ample quantities.)
5. Cement, including any supplementary materials, and water, including additives, are
mixed. Aggregates are added until the desired slump and a workable mix are
reached. Tests are conducted and the quality of mix, whether it is too harsh or over
sanded (see figure 7-15), is assessed.
Table 7-18
REQUIREMENTS FOR EXPOSED CONCRETE
With the permission of the Canadian Standards Association, material is reproduced from the CSA
Standard CAN/CSA A23.1-M94 (Concrete Materials and Methods of Concrete
Construction/.Methods of Test for Concrete), which is copyrighted by CSA, 178 Rexdale Blvd.,
Rexdale, Ontario, M9W 1R3. While use of this material has been authorized, CSA shall not be
responsible for the manner in which the information is presented, nor for any interpretation
thereof. This CSA material may not be updated to reflect amendments made to the original
content. For up-to-date information, contact CSA.
If the mix is suitable, batch quantities are calculated. Otherwise, changes are made in the
materials and/or proportions and additional trials conducted.
Page 10
Example 4.3 A trial mix is to be prepared for an un reinforced pavement requiring 25 MPa
concrete and subject to freezing and deicing chemicals. Ten kg of cement will be used. The
overdesign factor for these materials has been established as 3.0 MPa.
Table 7-19
SPECIFIED SLUMP
Type of Construction Slump (mm) Allowable Range (mm)
Mass concrete, pavements 40 20 – 60
Structural concrete, slabs on
ground, driveways, walks 80 50 – 110
Tremie concrete 170 140 - 200
With the permission of the Canadian Standards Association, materials is reproduced from the CSA
Standard CAN/CSA A23 1-M94 (Concrete Materials and Methods of Concrete
Construction/Methods of Test for Concrete), which is copyrighted by CSA, 178 Rexdale Blvd.,
Rexdale, Ontario, M9W 1R3. While use of this materials has been authorized, CSA shall not be
responsible for the manner in which the information is presented, nor for any interpretation thereof.
This CSA material may not be updated to reflect amendments made to the original content. For up-
to-date information, contact CSA.
1. The minimum strength required for this exposure (C-2) is 32 MP1. This is greater
than the project-specified strength, and will govern. With the overdesign factor, the
mix design strength is 35 MPa.
From Table 7-14, the maximum W/CM ratio is 0.39. This meets the requirements of
Table 7-18 for this exposure, 0.45, and will be used.
Fig.
Figure 7-15 Harshness of concrete: (a) harsh mix – not enough cement-sand mortar to fill
the spaces between the coarse aggregate particles; (b) good mix-with a light troweling, all
the spaces between the coarse particles are filled (note the good supply of coarse particles at
the edge of the pile); (c) overstanded mix-finishes well but with an excess of mortar, making
it an uneconomical and possibly porous mix.
2. A maximum aggregate size of 40 mm will be used although up to 200/3 = 67 mm
would be acceptable. The required air content is 4-7% (Table 7-18). This will be
used to calculate the amount of air-entrainment chemical to add to the mix water.
3. Required slump is 40 mm, with an allowable range of 20-60 mm (Table 7-19).
4. Quantities for mix:
Cement 10.0 kg
Water (10.0 x 0.39) 3.9 kg
Fine aggregate (SSD) 19.5 kg
Coarse aggregate (SSD) 39.0 kg
5. Actual aggregate quantities used were – fine 19.4k
- coarse 38.5 kg
Total mass of mix = 71.8 kg
Density as measured was 2290 kg/m
Batch quantities:
Cement = 10.0 (kg) x 2290 (kg/m)/71.8 kg = 319 kg/m
Water 3.9 x 2290/71.8 = 124 kg/m
Fine aggregate (SSD) 19.4 x 2290/71.8 = 619 kg/m
Coarse aggregate (SSD) 38.5 x 2290/71.8 = 1228 kg/m
Total 2290 kg/m
Page 11
Note: The Canadian Portland Portland_Cement Association recommends minimum cement
content of 335 kg for this type of exposure.
Research conducted by SHRP has led to a recommendation that a revised method be used to
proportion the trial mix aggregates, in step 6 of the ACI design method.
Computer-generated tables have been used to find the optimum proportions of spheres of
two or three sizes. Voids in the aggregate mixture must be filled with the more expensive
paste fraction. Therefore the aggregate combination with the least volume of voids is the
most economical and densest.
To use the tables, two values for each aggregate are required. The cahract5eristic diameter
D, is found from the diameter at the 63% passing level of a straight-line plot of the grain-
size curve on specified graph. The dry-rodded density and voids content are obtained from a
standard test (AASHTO T19). The dry-packing density PH) is calculated from
PHI = 1 – (% voids/100)
Adjusted quantities
Cement _______ (A)
Water (B1 + excess – required) _______ (B2)
Fine aggregate (C2 – excess + required) _______ (C3)
Coarse aggregate (D2 – excess + required) _______ (D3)
Total _______ (T)
Air-entraining agent _______
Mass per cubic meter
Cement (A/T x ) _______
Water (B2/T x ) _______
Fine aggregate (C3/T x ) _______
Coarse aggregate (C3/T x ) _______
Strength test:
Age in days _______
Failure load _______
Area _______
Strength _______
Purpose: To find the optimum proportions of cement, water, aggregates, and admixtures for
a concrete mixture.
Apparatus:
Mixing pan and tools (or a mechanical mixer)
Balances
Slump cone
Air meter
Volumetric container
Strength-test molds
Procedure:
Page 12
1. Using given or established design criteria, find the estimated quantities per cubic
yard or cubic meter. If supplementary cementing materials are used, the mass of fly
ash or other SCM will also have to be determined. Slump can be found from Table 7
– 12, and amount of mixing water and air from Table 7-13. The W/C or W/Cm ratio
is obtained from Tables 7-14 and 7-15. The volume and mass of coarse aggregate is
calculated from the dry-rodded density and the proportion found in Table 7-16. The
amount of fine aggregate can be found by using the volume method or by using the
estimated total mass of the concrete (Table 7-17).
2. Calculate the amounts required fro a trial mix. A batch of about 0.25 ft 3 or 0.007m3
should be mixed for each standard-strength cylinder to be made.
3. If the aggregates are not in the saturated, surface-dry condition, correct the
calculated batch quantities.
4. Measure out the indicated amounts of each materials, adding the air-entraining
agent, if used, to the water.
5. Dampen the mixing pan (or mixer). Mix the cement and fine aggregates together.
Add the coarse aggregate and mix. Add about 50-75% of the water and mix
thoroughly. Add additional water, mixing constantly, until the desired consistency is
reached. 9This may require more or less water than measured out.) Note the actual
amount of water used an observe the quality of the mix.
6. Conduct a slump test and, if required, an air-content test. 9See sections 7-12.3 and 7-
12.4.)
7. Remix the concrete; place it in the volumetric container in three layers. Rodding
each layer 25 times; level the surface of the concrete flush with the top of the
container; and obtain the mss of the concrete in the container.
8. Remix the concrete and cast the strength-test cylinders. (See section 7-12.5.)
9. Calculations:
a. Find the density of the concrete.
b. Note the actual quantities used and calculate the adjusted amounts if the
aggregates were not in the saturated, surface-dry condition.
c. Calculate the mass per unit volume in 1b/yd 3 or kg/m3, and the actual W/C
ratio.
10. Cap and strength test the cylinders at the specified age. (See Section 7 – 12.6)
Note: For a second trial mix, if required, use the yield quantities for proportions of water
and fine and coarse aggregates, with any adjustments required to improve the workability or
finishing properties. Recalculate the amount of cement needed, used the required W/C
ration and the indicated water content.
Page 13
TRIAL MIX-ACI METHOD DATA SHEET
Page 14
+ excess water ______
- required water ______
Mix water ______ (A4)
Total mix (A4 + B1 + C1 + D1) ______ (T)
Mass per unit volume
Water (A4/T x ) ______
Cement (B1/T x ) ______
Coarse aggregate (C1/T x ) ______
Fine aggregate (D1/T x ) ______
Actual W/C ratio (A4/B1) ______
Strength test:
Age in days ______
Failure load ______
Area ______
Strength ______
PROBLEMS
1. What are the main compounds in Portland cement? Which one is most important for
early strength? For subsequent strength gain?
2. What is meant by hydration of Portland cement? How does hydration affect the
temperature of the material? How Much water is required?
3. Name the types of Portland cement. In what situation would each of these types of
cement be used?
4. The strength of a normal concrete is found to b3 24.7 MPa (3580 psi) at 28 day’s
age. Estimate the strength of this concrete at 6 months if it is moist cured.
5. What is cement clinker?
6. What are the main differences in chemical composition between Type I (10) and
Type III (30) Portland cement? Why are there thee differences?
7. What is meant by water cement ratio? What effect does the value of the water
cement ratio have on the strength of concrete? Why?
8. What is air-entrained concrete? When it is used? Why is it effective? What property
of the mix governs the amount of air required? Why?
9. Estimate the percentage increase in 28-day strength for air-entrained concrete made
with normal cement if the W/C ratio is reduced from 0.63 to 0.55.
Page 15