Sei sulla pagina 1di 6

Name of the project : Cadbury 'Nilgiri' Project

Name of the Client : Cadbury India Limited


Location of the project : Sri City, Naidupeta, Near Nellore, Andhra Pra
BOQ for Building Management System

S.No Description of Item / Work. Unit Qty Supply


Rate

Notes:
Read all the Quantities as Supply, Installation, testing &
Commissioning.
Verify all the quantities given in BOQ in conjunction with
Scope of work, Technical Specification, Data Sheets and
schematic / layout drawings provided along with Tender.

BMS
Server / Work Station (with latest configuration available in the
1 Lot 1
market)
2 Color Laserjet Printer (A4 size) Lot 1
PLC main rack in the BMS room, to be linked with the field racks &
server / workstation using LAN.PLC Main racks consisting of all
3 required accessories like Power supply units, terminal blocks, relays, Nos 1
MCBs, etc needs to be considered. MOC of panel as given in the
standard documents.
a CONTROL LOGIX CHASSIS 10 SLOT Nos 1
b POWER SUPPLY MODULE Nos 1
c CPU MODULE Nos 1
d ETHERNET MODULE Nos 2

PLC field I/O racks consisting of total I/Os as given in the I/O list
(560DI, 113DO, 130AI, 64AO & 4080 soft inputs) depending on the
field requirement. All racks interlinked over LAN using Ethernet IP
4 for interface with the any of the field systems. All required Nos 5
accessories like Power supply units, terminal blocks, relays, MCBs,
etc needs to be considered. MOC of panel as given in the standard
documents.
a POWER SUPPLY MODULE Nos 21
b FLEX I/O ETHERNET MODULE Nos 21
c 32 Channel DIGITAL INPUT MODULE Nos 14
d 16 Channel DIGITAL OUTPUT MODULE Nos 4
e 8 Channel ANALOG INPUT MODULE Nos 27
f 4 Channel ANALOG OUTPUT MODULE Nos 0
g FLEX TERM BASE Nos 45
h MODBUS RTU RS485 COMMUNICATION MODULE Nos 0

Programming Software RS Logix 5000 for PLC system with required


5 Lot 1
supporting licence
FT View studio SCADA Software for BMS with 6000 tags along with
6 Lot 1
required supporting Licenses.
Developing suitable logic software in the main PLC system as
7 required for fully functional integrated system. Lot 1
Developing suitable SCADA software as required for fully functional
8 system with required MMI screens, alarm / events reports, trends, Lot 1
etc
9 CABLES with required cable glands, laying accessories, tags, etc.
a 1 Pair x 1 sq mm Armoured sheilded Cable Mtrs 10000
b 2 Pair x 1 sq mm Armoured sheilded cable Mtrs 17500
c 3 Pair x 1 sq mm Armoured sheilded cable Mtrs 4500
d 3 C x 1.5 Armoured cable Mtrs 500

Cable Trays with required laying accessories, bends, supports,


10 cable clamps, etc.
a SS mesh type Cable Trays (50 mm X 50 mm) Mtrs 400
b SS mesh type Cable Trays (150 mm X 50 mm) Mtrs 200
c SS mesh type Cable Trays (300 mm X 50 mm) Mtrs 200
d GI Cable Trays (50 mm X 50 mm) Mtrs 500
e GI Cable Trays (150 mm X 50 mm) Mtrs 2500
f GI Cable Trays (300 mm X 50 mm) Mtrs 1700
g 25mm G.I. Conduits Mtrs 1500

11 Soft integration with following sub-systems


a AHUs Variable frequency drive - Ethernet IP LS 1
b Chiller Plant Manager - Ethernet IP LS 1
c Room parameter display - / Ethernet IP LS 1
d Energy meters - Ethernet IP LS 1
e DG - MODBUS RTU / Ethernet IP LS 1
f DG Load Management - Ethernet IP LS 1
g UPS - MODBUS RTU / Ethernet IP LS 1
h Switchgear Realy module - / Ethernet IP LS 1
i Boiler - Ethernet IP LS 1
j CDA -Ethernet IP LS 1
k LNG - Ethernet IP LS 1
l PCW -Ethernet IP LS 1
m HWS -Ethernet IP LS 1
n WWMS -Ethernet IP LS 1
o HSD system - / Ethernet IP LS 1
p Process SCADA System for Utility Metering and monitoring. LS 1

12 Hooter for Ahu's trip condition Nos 1


13 Room Temperature (PT 1000) & Rh (0-10vdc) sensor Nos 8
14 Room Pressure sensor (4-20 mA) Nos 8
15 Room temperature , RH & Pressure value show in display panel Nos 8
16 SS I/O Box 500x500x300 Nos 16
Alarm notification by e-mail: Web-Module will be sent to one or
17 Nos 1
more e-mail receiver alarm notification.
18 PanelView 1000 with SS enclosure Nos 1
19 Ethernet SW 5700 Nos 1
20

Additional BOQ items if any as required by the vendor to complete


the work as defined in the scope documents
ect
d
Near Nellore, Andhra Pradesh

Excise duty or
Installation Supply Installation Custom duty CST Amount
VAT Amount
Rate Amount Amount Amount
Total Total Supply +
Total Supply Total Supply +
Installation Installation
Amount Service Tax Installation
Amount Amount Remarks
(Including all Amount Amount (Ecl.
(Including all (Including all
taxes) Taxes)
taxes) taxes)