Sei sulla pagina 1di 92

3URWHFW,7 /LQHGLVWDQFH 5(/


SURWHFWLRQWHUPLQDO
1MRK 506 164-BEN
Page 1
Revision: –
Issued: October 2003
Data subject to change without notice

)HDWXUHV • Open terminal with extensive configuration • Versatile local human-machine interface
possibilities and expandable hardware (LED-HMI)
design to meet specific user requirements
• Extensive self-supervision with internal
• Full scheme phase-to-phase and phase-to- event recorder
earth distance protection with:
• Time synchronization with 1 ms resolution
- general fault criteria, with or without the
• Four independent groups of complete set-
optional phase preference logic for high
ting parameters
impedance earthed networks
• Powerful software PC ‘tool-box’ for moni-
- three to five zones
toring, evalution and user configuration

)XQFWLRQV • Line distance - Two step time delayed directional phase


overcurrent protection (TOC3)
- General fault criteria, impedance and
current based (GFCzi) - Time delayed non-directional residual
overcurrent protection (TEF)
- General fault criteria, impedance and
current based, with phase preference - Time delayed directional residual over-
logic (GFCppl-zi) current protection (TEFdir)
- Distance protection (ZM) - Four step time delayed directional resid-
ual overcurrent protection (EF4)
- Simplified impedance settings (SIS)
- Sensitive directional residual overcur-
- Power swing detection (PSD)
rent protection (WEF1)
- Scheme communication logic (ZCOM)
- Sensitive directional residual power pro-
- Current reversal and weak end infeed tection (WEF2)
logic (ZCAL)
- Scheme communication logic for resid-
- Radial feeder protection (PAP) ual overcurrent protection (EFC)
- Automatic switch onto fault logic (SOTF) - Current reversal and weak end infeed
- Local acceleration logic (ZCLC) logic for residual overcurrent protection
(EFCA)
• Current
- Thermal overload protection (THOL)
- Instantaneous non-directional phase
overcurrent protection (IOCph) - Breaker failure protection (BFP)

- Instantaneous non-directional residual • Voltage


overcurrent protection (IOCr) - Time delayed undervoltage protection
- Definite time non-directional phase (TUV)
overcurrent protection (TOCph) - Time delayed overvoltge protection
- Definite time non-directional residual (TOV)
overcurrent protection (TOCr) - Time delayed residual overvoltage pro-
- Two step time delayed non-directional tection (TOVr)
phase overcurrent protection (TOC2) • Power system supervision
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 2

- Broken conductor check (BRC) - Autorecloser - 1- and/or 3-phase, single


circuit breaker (AR1-1/3)
- Loss of voltage check (LOV)
- Autorecloser - 1- and/or 3-phase, double
- Overload supervision (OVLD)
circuit breakers (AR12-1/3)
- Dead line detection (DLD)
- Autorecloser - 3-phase, single circuit
• System protection and control breaker (AR1-3)
- Pole slip protection (PSP) - Autorecloser- 3-phase, double circuit
- Low active power protection (LAPP) breaker (AR12-3)

- Low active and reactive power protec- • Logic


tion (LARP) - Three pole tripping logic (TR01-3)
- High active power protection (HAPP) - Additional three pole tripping logic
- High active and reactive protection (TR02-3)
(HARP) - Single, two or three pole tripping logic
- Sudden change in phase current protec- (TR01-1/2/3)
tion (SCC1) - Additional single, two or three pole trip-
- Sudden change in residual current pro- ping logic (TR02-1/2/3)
tection (SCRC) - Pole discordance logic (PDc)
- Sudden change in voltage protection - Additional configurable logic blocks
(SCV) (CL2)
- Overvoltage protection (OVP) - Communication channel test logic
- Undercurrent protection (UCP) (CCHT)
- Phase overcurrent protection (OCP) - Binary signal transfer to remote end
(RTC12)
- Residual overcurrent protection (ROCP)
- Multiple command, one fast block with
• Secondary system supervision
16 signals (CM1)
- Current circuit supervision, current
- Multiple command, 79 medium speed
based (CTSU)
blocks each with 16 signals (CM79)
- Fuse failure supervision, negative
• Monitoring
sequence (FUSEns)
- Disturbance recorder (DR)
- Fuse failure supervision, zero sequence
(FUSEzs) - Event recorder (ER)
- Fuse failure supervision, du/dt and di/dt - Fault locator (FLOC)
based (FUSEdb) - Trip value recorder (TVR)
- Voltage transformer supervision (TCT) - Increased accuracy of AC input quatities
• Control (IMA)
- Single command, 16 signals (CD) - Supervision of AC input quantities (DA)
- Synchro-check and energizing-check, - Supervision of mA input quantities (MI)
single circuit breaker (SYN1) • Metering capabilities
- Synchro-check and energizing-check, - Pulse counter logic for metering (PC)
double circuit breakers (SYN12)
- Six event counters (CN)
- Synchro-check with synchronizing and
energizing-check, double circuit breaker • Hardware
(SYNsy1) - 18 LEDs for extended indication capabil-
- Synchro-check with synchronizing and ities
energizing-check, double circuit breaker • Several input/output module options includ-
(SYNsy12) ing measuring mA input module (for trans-
ducers)
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 3

$SSOLFDWLRQ The main purpose of the REL 511 terminal is transmission networks up to the highest volt-
the protection, control and monitoring of age levels. It is suitable for the protection of
overhead lines and cables in high impedance heavily loaded lines and multi-circuit lines,
or solidly grounded distribution and sub- and where the requirement for tripping is one-
transmission networks. Full scheme phase to , two-, and/or three-pole. The terminal may
phase and phase to earth distance protecion is also be used to provide backup protection for
included. The terminal can also be used in power transformers, busbars, etc.

'HVLJQ Type tested software and hardware that com- An extensive library of protection, control
ply with international standards and ABB´s and monitoring functions is available. This
internal design rules together with extensive library of functions, together with the flexible
self monitoring functionality, ensure high hardware design, allows this terminal to be
reliability of the complete terminal configured to each user´s own specific
requirements. This wide application flexibil-
The terminal’s closed and partly welded steel ity makes this product an excellent choice for
case makes it possible to fulfill the stringent both new installations and the refurbishment
EMC requirements. of existing installations.

Serial data communication is via optical con-


nections or galvanic RS485.

3ODWIRUP $SSOLFDWLRQ kits are available for rack, flush, semiflush or


The platform hardware and common software wall mounting.
functions are included in all REx 5xx termi-
nals. It is the foundation on which all termi- All connections are made on the rear of the
nals are built. Application specific modules case. Screw compression type terminal
and functions are added to create a specific blocks are used for electrical connections.
terminal type or family. Serial communication connections are made
by optical fibre connectors type Hewlett
Packard (HFBR) for plastic fibres or bayonet
'HVLJQ type ST for glass fibres.
The REx 5xx platform consists of a case,
hardware modules and a set of common func- A set of hardware modules are always
tions. included in a terminal. Application specific
modules are added to create a specific termi-
The closed and partly welded steel case nal type or family.
makes it possible to fulfill stringent EMC
requirements. Three different sizes of the The common functions provide a terminal
case are available to fulfill the space require- with basic functionality such as self supervi-
ments of different terminals. The degree of sion, I/O-system configurator, real time clock
protection is IP 40 according to IEC 529 for and other functions to support the protection
cases with the widths 1/2x19” and 3/4x19”. and control system of a terminal.
IP 54 can be obtained for the front area in
flush and semiflush applications. Mounting

&RPPRQ 'HVFULSWLRQ self-supervision operates continuously and


IXQFWLRQV Common functions are the software functions includes:
always included in the terminals.
• Normal micro-processor watchdog func-
tion
6HOIVXSHUYLVLRQZLWKLQWHUQDO
HYHQWUHFRUGHU ,17 • Checking of digitized measuring signals
• Checksum verification of PROM contents
$SSOLFDWLRQ and all types of signal communication
Use the local HMI, SMS or SCS to view the
status of the self-supervision function. The
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 4

5HDOWLPHFORFNZLWKH[WHUQDO poses, so that continuous information on


WLPHV\QFKURQL]DWLRQ 7,0( active setting group is available.

$SSOLFDWLRQ &RQILJXUDEOHORJLFEORFNV
Use the time synchronization source selector &/
to select a common source of absolute time
for the terminal when it is a part of a protec- $SSOLFDWLRQ
tion system. This makes comparison of The user can with the available logic function
events and disturbance data between all ter- blocks build logic functions and configure the
minals in a SA system possible. terminal to meet application specific require-
ments.
)XQFWLRQDOLW\
Two main alternatives of external time syn-
Different protection, control, and monitoring
chronization are available. Either the syn-
functions within the REx 5xx terminals are
chronization message is applied via any of quite independent as far as their configuration
the communication ports of the terminal as a
in the terminal is concerned. The user can not
telegram message including date and time, or
change the basic algorithms for different
as a minute pulse, connected to a binary functions. But these functions combined with
input. The minute pulse is used to fine tune
the logic function blocks can be used to cre-
already existing time in the terminals.
ate application specific functionality.
The REx 5xx terminal has its own internal ,QYHUWIXQFWLRQEORFN ,19
clock with date, hour, minute, second and The inverter function block INV has one
millisecond. It has a resolution of 1 ms. input and one output, where the output is in
inverse ratio to the input.
The clock has a built-in calendar that handles
leap years through 2098. Any change 25IXQFWLRQEORFN 25
between summer and winter time must be The OR function is used to form general
handled manually or through external time combinatory expressions with boolean vari-
synchronization. The clock is powered by a ables. The OR function block has six inputs
capacitor, to bridge interruptions in power and two outputs. One of the outputs is
supply without malfunction. inverted.
The internal clock is used for time-tagging $1'IXQFWLRQEORFN $1'
disturbances, events in Substation monitoring The AND function is used to form general
system (SMS) and Substation control system combinatory expressions with boolean vari-
(SCS), and internal events. ables.The AND function block has four
inputs and two outputs. One of the inputs and
)RXUSDUDPHWHUVHWWLQJJURXSV one of the outputs are inverted.
*53 7LPHUIXQFWLRQEORFN 70
The function block TM timer has drop-out
$SSOLFDWLRQ
and pick-up delayed outputs related to the
Use the four sets of settings to optimize the
input signal. The timer has a settable time
terminals operation for different system con- delay (parameter T).
ditions. By creating and switching between
fine tuned setting sets, either from the human- 7LPHUORQJIXFWLRQEORFN 7/
machine interface or configurable binary The function block TL timer with extended
inputs, results in a highly adaptable terminal maximum time delay at pick-up and at drop-
that can cope with a variety of system scenar- out, is identical with the TM timer. The dif-
ios. ference is the longer time delay.
)XQFWLRQDOLW\ 3XOVHWLPHUIXQFWLRQEORFN 73
The GRP function block has four functional The pulse function can be used, for example,
inputs, each corresponding to one of the set- for pulse extensions or limiting of operation
ting groups stored within the terminal. Acti- of outputs. The pulse timer TP has a settable
vation of any of these inputs changes the length.
active setting group. Four functional output
signals are available for configuration pur-
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 5

([WHQGHGOHQJWKSXOVHIXQFWLRQEORFN 74 (YHQWIXQFWLRQ (9
The function block TQ pulse timer with
extended maximum pulse length, is identical $SSOLFDWLRQ
with the TP pulse timer. The difference is the When using a Substation Automation system,
longer pulse length. events can be spontaneously sent or polled
from the terminal to the station level. These
([FOXVLYH25IXQFWLRQEORFN ;25 events are created from any available signal
The exclusive OR function XOR is used to in the terminal that is connected to the event
generate combinatory expressions with bool- function block. The event function block can
ean variables. The function block XOR has also handle double indication, that is nor-
two inputs and two outputs. One of the out- mally used to indicate positions of high-volt-
puts is inverted. The output signal is 1 if the age apparatuses. With this event function
input signals are different and 0 if they are block, data also can be sent to other terminals
equal. over the interbay bus.
6HWUHVHWIXQFWLRQEORFN 65 )XQFWLRQDOLW\
The Set-Reset (SR) function is a flip-flop that As basic, 12 event function blocks EV01-
can set or reset an output from two inputs EV12 running with a fast cyclicity, are avail-
respectively. Each SR function block has two able in REx 5xx. When the function Appara-
outputs, where one is inverted. tus control is used in the terminal, additional
32 event function blocks EV13-EV44, run-
6HWUHVHWZLWKPHPRU\IXQFWLRQEORFN 60 ning with a slower cyclicity, are available.
The Set-Reset function SM is a flip-flop with
memory that can set or reset an output from Each event function block has 16 connecta-
two inputs respectively. Each SM function bles corresponding to 16 inputs INPUT1 to
block has two outputs, where one is inverted. INPUT16. Every input can be given a name
The memory setting controls if the flip-flop with up to 19 characters from the CAP 540
after a power interruption will return the state configuration tool.
it had before or if it will be reset.
The inputs can be used as individual events or
&RQWUROODEOHJDWHIXQFWLRQEORFN *7
can be defined as double indication events.
The GT function block is used for controlling
if a signal should be able to pass from the
The inputs can be set individually, from the
input to the output or not depending on a set-
Parameter Setting Tool (PST) under the
ting.
Mask-Event function, to create an event at
pick-up, drop-out or at both pick-up and
6HWWDEOHWLPHUIXQFWLRQEORFN 76
drop-out of the signal.
The function block TS timer has outputs for
delayed input signal at drop-out and at pick-
The event function blocks EV01-EV06 have
up. The timer has a settable time delay. It also
inputs for information numbers and function
has an Operation setting On, Off that controls
the operation of the timer. type, which are used to define the events
according to the communication standard IEC
0RYHILUVWIXQFWLRQ 02) 60870-5-103.
The Move function block MOF is put first in
the slow logic and is used for signals coming 6XSHUYLVLRQRI$&LQSXW
from fast logic into the slow logic. The MOF TXDQWLWLHV '$
function block is only a temporary storage for
the signals and does not change any value $SSOLFDWLRQ
between input and output. Use the AC monitoring function to provide
three phase or single phase values of voltage
0RYHODVWIXQFWLRQEORFN 02/ and current. At three phase measurement, the
The Move function block MOL is put last in values of apparent power, active power, reac-
the slow logic and is used for signals going tive power, frequency and the RMS voltage
out from the slow logic to the fast logic. The and current for each phase are calculated.
MOL function block is only a temporary stor- Also the average values of currents and volt-
age for the signals and does not change any ages are calculated.
value between input and output.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 6

)XQFWLRQDOLW\ when setting changes are allowed. Unpermit-


Alarm limits can be set and used as triggers, ted or uncoordinated changes by unautho-
e.g. to generate trip signals. rized personnel may influence the security of
people and cause severe damage to primary
The software functions to support presenta- and secondary power circuits.
tion of measured values are always present in
the terminal. In order to retrieve actual val- By adding a key switch connected to a binary
ues, however, the terminal must be equipped input a simple setting change control circuit
with the appropriate hardware measuring can be built simply allowing only authorized
module(s), i.e. Transformer Input Module keyholders to make setting changes from the
(TRM). built-in HMI.

)XQFWLRQDOLW\
6XSHUYLVLRQRIP$LQSXW Activating the setting restriction prevents
TXDQWLWLHV 0, unauthorized personell to purposely or by
mistake change terminal settings or configu-
$SSOLFDWLRQ ration from the local HMI.
Use the DC monitoring function to measure
and process signals from different measuring The function permits remote changes of set-
transducers. Many devices used in process tings and reconfiguration through the serial
control uses low currents, usually in the range communication ports.
4-20 mA or 0-20 mA to represent various
parameters such as frequency, temperature All other functions of the local human-
and DC battery voltage. machine communication remain intact. This
means that an operator can read disturbance
)XQWLRQDOLW\
reports, setting values, the configuration of
Alarm limits can be set and used as triggers,
different logic circuits and other available
e.g. to generate trip signals. information.
The software functions to support presenta-
tion of measured values are always present in %ORFNLQJRIVLJQDOVGXULQJWHVW
the terminal. In order to retrieve actual val- %67
ues, however, the terminal must be equipped
with the mA Input Module (MIM). $SSOLFDWLRQ
The protection and control terminals have a
,2V\VWHPFRQILJXUDWRU ,23 complex configuration with many included
functions. To make the testing procedure eas-
$SSOLFDWLRQ ier, the terminals include the feature to indi-
The I/O system configurator must be used in vidually block a single, several or all
order for the terminal’s software to recognize functions.
added modules and to create internal address
mappings between modules and protections This means that it is possible to see when a
and other functions. function is activated or trips. It also enables
the user to follow the operation of several
related functions to check correct functional-
6HWWLQJUHVWULFWLRQRI+0, ity and to check parts of the configuration etc.
65+
The Release Local for line differential func-
$SSOLFDWLRQ tion is only possible to operate if the terminal
Use the setting restriction function to prevent has been set in test mode from the HMI.
unauthorized setting changes and to control

/LQHGLVWDQFH *HQHUDOIDXOWFULWHULDLPSHG ment criteria. These can be used separately or


DQFHDQGFXUUHQWEDVHG *)& at the same time. Its main purpose is to serve
as an overall fault detection and phase selec-
$SSOLFDWLRQ tion element in all kinds of networks. It is not
The GFC general fault criteria function is an used as a start condition because the distance
independent measuring function. It comprises protection zones utilize full scheme measure-
both impedance and current-based measure- ment.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 7

For the impedance measurement, the shape of tion to be as sensitive as possible to faults
the operating characteristic can be set to pre- with high fault resistances, is achieved by the
vent operation of the impedance measuring inclusion of a facility that allows the resistive
elements for low load impedances, yet at the reach to be limited within the load impedance
same time allow coverage of higher fault area only.
resistances with remote infeed of fault cur-
rent. This makes the GFC function especially Checks based on the level of residual current
suited to cases where the fault resistance to be determine which loops, i.e. phase-to-ground
detected exceeds the minimum expected load or phase-to-phase, are evaluated. Selection of
impedance. the faulted phase(s) is determined by which
of the selected loops operate. Operation of a
The independent measurement of impedance loop occurs when the measured impedance
for each fault loop secures reliable phase within that loop is within the set boundaries
selection and correct operation for complex of the characteristic.
network faults such as simultaneous faults on
parallel circuits, evolving faults, etc. Indepen- For the current-based phase selection, all
dent reactive reach settings for phase-to- three phase currents and the residual current
phase and phase-to-ground measurement are measured continuously, and compared to
secure high selectivity in networks with dif- set values. Assessment of the type of fault is
ferent protective relays used for short-circuit based on the relationship of the measured cur-
and earth-fault protection. rents to the set thresholds.

A possible addition to the GFC function is the The GFC starting condition (STCND) output
optional phase preference logic. Its main pur- will activate the selected loop of the distance
pose is to provide a selective tripping func- protection measuring zone(s) to which it is
tion for cross-country faults in isolated or connected.
high impedance-grounded networks.
The phase preference logic inhibits tripping
)XQFWLRQDOLW\ for single-phase-to-ground faults in isolated
For the impedance-based phase selection, all and high impedance-grounded networks. It
six fault loops are measured separately and does this by blocking forward and reverse
continuously. The reaches are independently operation until two earth-faults are detected
settable in the forward and reverse directions, to be within the non-directional characteris-
and for phase-to-phase and phase-to-ground tic. For such cross-country faults, the logic
faults. The resistive reaches are also indepen- initiates tripping of the preferred fault based
dently settable for phase-to-phase and phase- on the selected phase preference. A number
to-ground faults. Preventing impedance ele- of different phase preference combinations
ment operation due to low load impedances, are available for selection.
but at the same time enabling the GFC func-
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 8

jX
XFW
ZONE 3

ZONE 2

ZONE 1

LA RLoad RF R

XRV
99000189.vsd

ZONE 4

Figure 1: Operating characteristics of the GFC (impedance measuring principle) and zone measuring ele-
ments

Figure 1 presents principally a shaped operate measuring loops as well as in three indepen-
characteristic for an impedance based GFC dent phase-to-earth measuring loops.
function. Different designations have the fol-
lowing meaning: Phase-to-phase distance protection is suitable
as a basic protection function against two-
• XFW: reactive reach in forward direction and three-phase faults in all kinds of net-
• XRV: reactive reach in reverse direction works, regardless of the treatment of the neu-
tral point. Independent setting of the reach in
• RF: resistive reach within the unlimited
the reactive and the resistive direction for
area each zone separately, makes it possible to cre-
• RLoad: resistive reach restricted by the ate fast and selective short circuit protection
minimum load impedance in power systems.
• LA: expected load impedance angle
Phase-to-earth distance protection serves as
basic earth fault protection in networks with
'LVWDQFHSURWHFWLRQ =0 directly or low impedance earthed networks.
Together with an independent phase prefer-
$SSOLFDWLRQ
ence logic, it also serves as selective protec-
The ZM distance protection function provides tion function at cross-country faults in
fast and reliable protection for overhead lines
isolated or resonantly earthed networks.
and power cables in all kinds of power net-
works. For each independent distance protec- Independent reactive reach setting for phase-
tion zone, full scheme design provides
to-phase and for phase-to-earth measurement
continuous measurement of impedance sepa-
secures high selectivity in networks with dif-
rately in three independent phase-to-phase ferent protective relays used for short-circuit
and earth-fault protection.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 9

jX

Xph-e

Xph-ph

Zline

Rph-ph Rph-e
R

98000062.vmf

Where:
Xph-e = reactive reach for ph-e faults
Xph-ph = reactive reach for ph-ph faults
Rph-e = resistive reach for ph-e faults
Rph-ph = resistive reach for ph-ph faults
Zline = line impedance

Figure 2: Schematic presentation of the operating characteristic for one distance protection zone in forward
direction

Distance protection with simplified setting procedures and make the operating character-
parameters is available on request. It uses the istic automatically more adjusted to the needs
same algorithm as the basic distance protec- in combined networks with off-lines and
tion function. Simplified setting parameters cables.
reduce the complexity of necessary setting
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 10

jX

Zline

RFPP RFPE
R

xx00000713.vsd

Where:
X = reactive reach for all kinds of faults
RFPP = resistive reach for phase-to-phase faults
RFPE = resistive reach for phase-to-earth faults
Zline = line impedance

Figure 3: Schematic presentation of the operating characteristic for one distance protection zone in forward
direction with simplified setting parameters

The distance protection zones can operate, delayed zone with time delay set longer than
independently of each other, in directional 100ms.
(forward or reverse) or non-directional mode.
This makes it suitable, together with different Basic distance protection function is gener-
communication schemes, for the protection of ally suitable for use in non-compensated net-
power lines and cables in complex network works.
configurations, such as double-circuit, paral-
lel lines, multiterminal lines, etc. Zone one, )XQFWLRQDOLW\
two and three can issue phase selective sig- Separate digital signal processors calculate
nals, such as start and trip. the impedance as seen for different measuring
loops in different distance protection zones.
The additional distance protection zones four The results are updated each millisecond,
and five have the same basic functionality as separately for all measuring loops and each
zone one to three, but lack the possibility of distance protection zone. Measurement of the
issuing phase selective output signals. impedance for each loop follows the differen-
tial equation, which considers complete line
Distance protection zone five has shorter replica impedance, as presented schemati-
operating time than other zones, but also cally in figure 4.
higher transient overreach. It should gener-
ally be used as a check zone together with the
SOTF switch onto fault function or as a time Xl ∆i ( t )
u ( t ) = ( R l + Rf ) ⋅ i ( t ) + ----- ⋅ -----------
ω ∆t
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 11

influence the operation of the complete mea-


suring zone or only its tripping function by
Rl jXl
the operation of fuse-failure function, power
swing detection function, etc.
i(t)
3RZHUVZLQJGHWHFWLRQ 36'
u(t) Rf
$SSOLFDWLRQ
Power swings in the system arise due to big
changes in load, or changes in power system
configuration due to faults and their clear-
ance. Distance protection detects these power
98000063.vmf
swings as variations with time of the mea-
sured impedance along a locus in the imped-
Where: ance plane. This locus can enter the operate
characteristic of the distance protection and
Rl = line resistance
cause its unwanted operation if no preventive
Rf = fault resistance measures are taken. The main purpose of the
Xl = line reactance PSD power swing detection function is to
detect power swings in power networks and
ω = 2πf
to provide the blocking signal to the distance
f = frequency function to prevent its unwanted operation.
Figure 4: Schematic presentation of impedance )XQFWLRQDOLW\
measuring principle.
The PSD function comprises an inner and an
outer quadrilateral measurement characteris-
Settings of all line parameters, such as posi- tic. Its principle of operation is based on the
tive sequence resistance and reactance as well measurement of the time it takes a power
as zero-sequence resistance and reactance, swing transient impedance to pass through
together with expected fault resistance for the impedance area between the outer and the
phase-to-phase and phase-to-earth faults, are inner characteristics. Power swings are iden-
independent for each zone. The operating tified by transition times longer than timer
characteristic is thus automatically adjusted settings. The impedance measuring principle
to the line characteristic angle, if the simpli- is the same as that used for the distance pro-
fied operating characteristic has not been tection zones. The impedance and the tran-
especially requested. The earth-return com- sient impedance time are measured in all
pensation factor for the earth-fault measure- three phases separately. One-out-of-three or
ment is calculated automatically by the two-out-of-three operating modes can be
terminal itself. selected permanently or adaptively according
to the specific system operating conditions.
Voltage polarization for directional measure-
ment uses continuous calculation and updat- The PSD function detects power swings with
ing of the positive sequence voltage for each a swing period as low as 200 ms (i.e. with a
measuring loop separately. This secures cor- slip frequency as high as 10% of the rated fre-
rect directionality of the protection at differ- quency on a 50 Hz basis). It detects swings
ent evolving faults within the complex under normal system operating conditions, as
network configurations. A memory retaining well as during the dead time of a single-pole
the pre-fault positive-sequence voltage automatic reclosing cycle. Different timers
secures reliable directional operation at close- are used for initial and consecutive swings,
up three-phase faults. securing a high degree of differentiation
between power swing and fault conditions.
The distance protection function blocks are
independent of each other for each zone. It is possible to inhibit the power swing
Each function block comprises a number of detected output on detection of earth fault
different functional inputs and outputs, which current. This can be used to release the opera-
are freely configurable to different external tion of the distance protection function for
functions, logic gates, timers and binary earth faults during power swing conditions.
inputs and outputs. This makes it possible to
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 12

jX
.; ⋅ ; 1,1

; 1,1

Impedance locus at power swing


− .5 ⋅ 51,1 51,1

− 51,1
R
.5 ⋅ 51,1

tP1
− ; 1,1

− .; ⋅ ; 1,1
99000159.vsd

Figure 5: Operating principle and characteristic of the PSD function

6FKHPHFRPPXQLFDWLRQORJLF The type of communication-aided scheme to


=&20 be used can be selected by way of the set-
tings. The ability to select which distance
$SSOLFDWLRQ protection zone is assigned to which input of
It is not possible to set a underreaching dis- the ZCOM logic makes this logic able to sup-
tance protection zone to cover the full length port practically any scheme communication
of the line, and at the same time not to over- requirements regardless of their basic operat-
reach for faults beyond the protected line. To ing principle. The outputs to initiate tripping
avoid overreaching, underreaching distance and sending of the teleprotection signal are
protection zones must always reach short of given in accordance with the type of commu-
the remote end of the line by some safety nication-aided scheme selected and the dis-
margin of 15-20%. The main purpose of the tance protection zone(s) which have operated.
ZCOM scheme communication logic is to
supplement the distance protection function When power line carrier communication
such that fast clearance of faults is also channels are used, unblocking logic is pro-
achieved at the line end for which the faults vided which uses the loss of guard signal.
are on the part of the line not covered by its This logic compensates for the lack of
underreaching zone. To accomplish this, one dependability due to the transmission of the
communication channel, capable of transmit- command signal over the faulted line.
ting an on/off signal, is required in each
direction. &XUUHQWUHYHUVDODQGZHDNHQG
LQIHHGORJLF =&$/
)XQFWLRQDOLW\
The ZCOM function is a logical function
$SSOLFDWLRQ
built-up from logical elements. It is a supple-
In interconnected systems, for parallel line
mentary function to the distance protection, applications, the direction of flow of the fault
requiring for its operation inputs from the dis-
current on the healthy line can change when
tance protection and the teleprotection equip-
the circuit breakers on the faulty line open to
ment. clear the fault. This can lead to unwanted
operation of the distance protection on the
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 13

healthy line when permissive overreach )XQFWLRQDOLW\


schemes are used. The main purpose of the The PAP function performs the phase selec-
ZCAL current reversal logic is to prevent tion using the measured voltages. Each phase
such unwanted operations for this phenome- voltage is compared to the opposite phase-
non. phase voltage. A phase is deemed to have a
fault if its phase voltage drops below a setta-
If the infeed of fault current at the local end ble percentage of the opposite phase-phase
for faults on the protected line is too low to voltage. The phase-phase voltages include
operate the measuring elements, no trip out- memory. This memory function has a settable
put will be issued at the local end and no tele- time constant.
protection signal will be sent to the remote
end. This can lead to time delayed tripping at The PAP function has built-in logic for fast
the remote strong infeed end. The main pur- tripping as well as time delayed tripping. The
pose of the ZCAL weak end infeed logic is to voltage-based phase selection is used for both
enhance the operation of permissive commu- the fast and the delayed tripping. To get fast
nication schemes and to avoid sequential trip- tripping, scheme communication is required.
ping when, for a fault on the line, the initial Delayed tripping does not require scheme
infeed of fault current from one end is too communication. It is possible to permit
weak to operate the measuring elements. delayed tripping only on failure of the com-
munications channel by blocking the delayed
)XQFWLRQDOLW\ tripping logic with a communications channel
The ZCAL function block provides the cur- healthy input signal.
rent reversal and weak end infeed logic func-
tions that supplement the standard scheme On receipt of the communications signal,
communication logic, or the phase segregated phase selective outputs for fast tripping are
scheme communication logic. given based on the phase(s) in which the
phase selection function has operated.
On detection of a current reversal, the current
reversal logic provides an output to block the For delayed tripping, the single-pole and
sending of the teleprotection signal to the three-pole delays are separately and indepen-
remote end, and to block the permissive trip- dently settable. Furthermore, it is possible to
ping at the local end. This blocking condition enable or disable three-pole delayed tripping.
is maintained long enough to ensure that no It is also possible to select either single-pole
unwanted operation will occur as a result of delayed tripping or three-pole delayed trip-
the current reversal. ping for single-phase faults. Three-pole
delayed tripping for single-phase faults is also
On verification of a weak end infeed condi- dependent on the selection to enable or dis-
tion, the weak end infeed logic provides an able three-pole tripping. For single-phase
output for sending the received teleprotection faults, it is possible to include a residual cur-
signal back to the remote sending end, and rent check in the tripping logic. Three-pole
other output(s) for tripping. For terminals tripping is always selected for phase selection
equipped for single-, two-, and three-pole on more than one phase. Three-phase tripping
tripping, outputs for the faulted phase(s) are will also occur if the residual current exceeds
provided. Undervoltage detectors are used to the set level during fuse failure for a time
select the faulted phase (s). longer than the three-pole trip delay time.

The radial feeder protection function also


5DGLDOIHHGHUSURWHFWLRQ 3$3 includes logic which provides outputs that are
specifically intended for starting the auto-
$SSOLFDWLRQ
matic recloser.
The main purpose of the PAP radial feeder
protection function is to provide tripping at
the ends of radial feeders with passive load or $XWRPDWLFVZLWFKRQWRIDXOW
with weak end infeed. To obtain this tripping, ORJLF 627)
the PAP function must be included within the
protection terminal at the load / weak end $SSOLFDWLRQ
infeed end. The main purpose of the SOTF switch-on-to-
fault function is to provide high-speed trip-
ping when energizing a power line on to a
short-circuit fault on the line.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 14

Automatic initiating of the SOTF function until one second after the enabling signal has
using dead line detection can only be used reset. The protection function(s) released for
when the potential transformer is situated on tripping during the activated time can be
the line-side of the circuit breaker. Initiation freely selected from the functions included
using dead line detection is highly recom- within the terminal. Pickup of any one of the
mended for busbar configurations where selected protection functions during the
more than one circuit breaker at one line end enabled condition will result in an immediate
can energize the protected line. trip output from the SOTF function.

Generally, directional or non-directional


overreaching distance protection zones are
/RFDODFFHOHUDWLRQORJLF =&/&
used as the protection functions to be released
$SSOLFDWLRQ
for direct tripping during the activated time. The main purpose of the ZCLC local acceler-
When line-side potential transformers are
ation logic is to achieve fast fault clearance
used, the use of non-directional distance
for faults anywhere on the whole line for
zones secures switch-on-to-fault tripping for those applications where no communication
fault situations there directional information
channel is available.
can not be established, for example, due to
lack of polarizing voltage. Use of non-direc- )XQFWLRQDOLW\
tional distance zones also gives fast fault The ZCLC function is a complementary func-
clearance when energizing a bus from the line tion to the distance protection function.
with a short-circuit fault on the bus.
The local acceleration logic can be enabled
)XQFWLRQDOLW\
for operation in two ways. The first way uses
The SOTF function is a logical function built-
an ‘automatic recloser ready’ signal, either
up from logical elements. It is a complemen-
from the internal recloser, or an external
tary function to the distance protection func- recloser. The second way uses loss of load
tion.
detection. When enabled by either method,
the local acceleration logic will produce an
It is enabled for operation either by the close immediate output on pickup of the function
command to the circuit breaker, by a nor-
selected to the method of acceleration
mally closed auxiliary contact of the circuit
enabled.
breaker, or automatically by the dead line
detection. Once enabled, this remains active

&XUUHQW ,QVWDQWDQHRXVQRQGLUFHWLRQDO filter ensures immunity to disturbances and


SKDVHRYHUFXUUHQWSURWHFWLRQ dc components and minimizes the transient
,2&SK overreach. If any phase current is above the
set value IP>>, the phase overcurrent trip sig-
$SSOLFDWLRQ nal TRP is activated. Separate trip signal for
Different system conditions, such as source the actual phase(s) is also activated. The input
impedance and the position of the faults on signal BLOCK blocks all functions in the
long transmission lines influence the fault current function block.
currents to a great extent. An instantaneous
phase overcurrent protection with short oper- ,QVWDQWDQHRXVQRQGLUHFWLRQDO
ate time and low transient overreach of the UHVLGXDORYHUFXUUHQWSURWHFWLRQ
measuring elements can be used to clear
close-in faults on long power lines, where
,2&U
short fault clearing time is extremely impor-
$SSOLFDWLRQ
tant to maintain system stability.
The instantaneous residual overcurrent pro-
)XQFWLRQDOLW\
tection can be used in a number of applica-
The current measuring element continuously tions. Below some examples of applications
measures the current in all three phases and are given.
compares it to the set operate value IP>>. A
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 15

• Fast back-up earth fault protection for 'HILQLWHWLPHQRQGLUHFWLRQDO


faults close to the line end. UHVLGXDORYHUFXUUHQWSURWHFWLRQ
• Enables fast fault clearance for close in 72&U
earth faults even if the distance protection
or the directional residual current protec- $SSOLFDWLRQ
tion is blocked from the fuse supervision The time delayed residual overcurrent protec-
function tion is intended to be used in solidly and low
resistance earthed systems. The time delayed
)XQFWLRQDOLW\ residual overcurrent protection is suitable as
The current measuring element continuously back-up protection for phase to earth faults,
measures the residual current and compares it normally tripped by operation of the distance
to the set operate value IN>>. A filter ensures protection. The protection function can also
immunity to disturbances and dc components serve as protection for high resistive phase to
and minimizes the transient overreach. If the earth faults.
residual current is above the set value IN>>,
the residual overcurrent trip signal TRN is )XQFWLRQDOLW\
activated. The general trip signal TRIP is The residual current measuring element con-
activated as well. The input signal BLOCK tinuously measures the residual current and
blocks the complete function. compares it with the set operate value IN>. A
filter ensures immunity to disturbances and
'HILQLWHWLPHQRQGLUHFWLRQDO dc components and minimizes the transient
overreach. If the measured current is above
SKDVHRYHUFXUUHQWSURWHFWLRQ the set value IN>, a start signal STN is acti-
72&SK vated. The timer tN is activated and the
residual overcurrent trip signal TRN is acti-
$SSOLFDWLRQ vated after set time. The general trip signal
The time delayed overcurrent protection, TRIP is activated as well. The input signal
TOC, operates at different system conditions BLOCK blocks the function. The input signal
for currents exceeding the preset value and BLKTR blocks both trip signals TRN and
which remains high for longer than the delay TRIP.
time set on the corresponding timer. The
function can also be used for supervision and
fault detector for some other protection func- 7ZRVWHSWLPHGHOD\HGQRQ
tions, to increase the security of a complete GLUHFWLRQDOSKDVHRYHUFXUUHQW
protection system. It can serve as a reserve SURWHFWLRQ 72&
function for the line distance protection, if
activated under fuse failure conditions which $SSOLFDWLRQ
has disabled the operation of the line distance The two current/time stages of overcurrent
protection. protection TOC2 improve the possibility to
get fast operation for nearby faults by using a
)XQFWLRQDOLW\ high set current stage with short time delay.
The current measuring element continuously The low current stage is set with appropriate
measures the current in all three phases and time delay to get selectivity with the adjacent
compares it to the set operate value IP>. A fil- relays in the system. In networks with inverse
ter ensures immunity to disturbances and dc time delayed relays, selectivity is generally
components and minimizes the transient best obtained by using the same type of
overreach. If the current in any of the three inverse time characteristic for all overcurrent
phases is above the set value IP>, a common relays.
start signal STP and a start signal for the
actual phase(s) are activated. The timer tP is )XQFWLRQDOLW\
activated and the phase overcurrent trip signal The current measuring element continuously
TRP is activated after set time. The general measures the current in all phases and com-
trip signal TRIP is activated as well. pares it to the set operate value for the two
current stages. A filter ensures immunity to
The input signal BLOCK blocks the function. disturbances and dc components and mini-
The input signal BLKTR blocks both trip sig- mizes the transient overreach. If the current in
nals TRP and TRIP. any of the three phases is above the set value
I>Low, the start signal for the low current
stage is activated. With setting Characteristic
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 16

= Def, the timer tLow is activated and the trip signal TRLS is activated after set time. If
signal TRLS is activated after set time. If inverse time delay is selected, the timer tMin-
inverse time delay is selected, the timer tMin- Inv starts when the current is above the set
Inv starts when the current is above the set value I>Low. If the current also is above the
value I>Low. If the current also is above the set value I>Inv, the inverse time evaluation
set value I>Inv, the inverse time evaluation starts. When both time circuits operate, the
starts. When both time circuits operate, the definite time circuit tLow is activated and the
definite time circuit tLow is activated and the trip signal TRLS is activated after set time.
trip signal TRLS is activated after the addi-
tional time tLow. If the current is above the If the current is above the set value I>High,
set value I>High, the timer tHigh is activated the timer tHigh is activated and the trip signal
and the trip signal TRHS is activated after set TRHS is activated after set time.The low and
time. the high set current stages can individually be
set directional or non-directional. Directional
The input signal BLOCK blocks all func- information is calculated from positive
tions. Each current stage can also be individu- sequence polarization voltages and the phase
ally blocked. currents. The polarization voltage contains
memory voltage to ensure directional func-
tion at close-in three-phase faults. The direc-
7ZRVWHSWLPHGHOD\HGGLUHF tional element relay characteristic angle
WLRQDOSKDVHRYHUFXUUHQWSUR (RCA) and operate angle are settable in wide
WHFWLRQ 72& ranges.

$SSOLFDWLRQ The input signal BLOCK blocks all func-


The two current/time stages of the TOC3 tions. Trip from each current stage can also be
overcurrent protection, both with optional individually blocked.
directional (Forward release or Reverse
block) or non-directional function, improve
the possibility to obtain selective function of 7LPHGHOD\HGUHVLGXDORYHUFXU
the overcurrent protection relative other UHQWSURWHFWLRQ 7()
relays even in meshed networks. It must be
realized, however, that the setting of a phase $SSOLFDWLRQ
overcurrent protection system in a meshed Use the inverse and definite time delayed
network can be very complicated and a large residual overcurrent functions in solidly
number of fault current calculations are earthed systems to get a sensitive and fast
needed. In some cases, it is not possible to fault clearance of phase to earth faults.
obtain selectivity even when using directional
overcurrent protection. In such cases it is sug- The nondirectional protection can be used
gested to use line differential protection or when high sensitivity for earth fault protec-
distance protection function. tion is required. It offers also a very fast back-
up earth fault protection for the part of a
)XQFWLRQDOLW\ transmission line, closest to the substation
The current measuring element continuously with the protection.
measures the current in all three phases and
compares it to the set operate value for the The nondirectional residual overcurrent pro-
two current stages. A filter ensures immunity tection can be given a relatively low current
to disturbances and dc components and mini- pick-up setting. Thus the protection will be
mizes the transient overreach. If the current in sensitive, in order to detect high resistive
any of the three phases is above the set value phase to earth faults.
I>Low, the start signal for the low current
stage is activated. With setting Characteristic The directional residual overcurrent protec-
= Def, the timer tLow is activated and the trip tion can be used in a number of applications:
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 17

1. Main protection for phase to earth faults )RXUVWHSWLPHGHOD\HGGLUHF


on the radial lines in solidly earthed sys- WLRQDOUHVLGXDORYHUFXUUHQWSUR
tems. Selectivity is achieved by using
time delayed function according to prac-
WHFWLRQ ()
tices in the system (definite time delay or
$SSOLFDWLRQ
some type of inverse time characteristic).
In solidly earthed systems the four step resid-
2. Main protection for phase to earth faults ual overcurrent protection can be used in a
on lines in a meshed solidly earthed sys- similar way as a distance protection. As the
tem. The directional function can be used majority of the faults involve earth connec-
in an permissive overreach communica- tion, the protection will be able to clear most
tion scheme or a blocking scheme. In this of the faults in these systems. All four steps
application the directional residual over- can be non-directional or directional.
current function is used together with the
communication logic for residual overcur- One example of a normal application of the
rent protection. four step residual overcurrent protection can
3. Back-up protection for phase to earth be described as follows: The instantaneous
faults for lines in solidly earthed systems. and directional step 1 will normally cover
By using the directional residual protec- most of the line. The rest of the line is cov-
tion as back-up function, the back-up fault ered by the directional and delayed step 2.
clearance time can be kept relatively short Step 2 will also detect and trip earth faults on
together with the maintained selectivity. the remote busbar. The directional step 3 has
4. Etc. a longer time delay and will act as a selective
protection for earth faults with some degree
)XQFWLRQDOLW\ of fault resistance. The non-directional step 4
The residual overcurrent protection (TEFdir) has the longest delay. This step will detect
measures the residual current of the protected and clear high resistive earth faults as well as
line. This current is compared to the current the majority of series faults.
settings of the function. If the residual current
is larger than the setting value a trip signal The four step residual overcurrent protection
will be sent to the output after a set delay can also be used together with the communi-
time. The time delay can be selected between cation logic for residual overcurrent protec-
the definite or inverse possibility. tion, in order to realize blocking or
permissive overreaching communication
In order to avoid unwanted trip for trans- schemes.
former inrush currents, the function is
blocked if the second harmonic content of the )XQFWLRQDOLW\
residual current is larger than 20% of the The function operates on the basis of the
measured residual current. residual current and voltage measurement.
The function has four steps with individual
As on option the residual overcurrent protec- settings (current, delay, directionality, second
tion can have directional function. The resid- harmonic restrained etc.). Step 1, 2 and 3
ual voltage is used as a polarizing quantity. have independent time delay. The time delay
This voltage is either derived as the vectorial for step 4 can be selected between definite or
sum of inputs U1+U2+U3 or as the input U4. inverse mode of operation.
The fault is defined to be in the forward
direction if the residual current component in For each step the current is compared to the
the characteristic angle 65° (residual current set current of the step. Further the following
lagging the reference voltage, -3U0), is larger quantities are checked to be used as release or
than the set operating current in forward blocking of function from the steps:
direction. The same kind of measurement is
performed also in the reverse direction.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 18

• Direction, forward or reverse direction to filled and the set time delay has elapsed, the
the fault. The residual current component function will give a trip signal.
lagging the reference (-3.U0) voltage 65°
is derived. If this current component is Due to the demands on accuracy and sensitiv-
larger than the directional current setting, ity for this function, special current input
forward direction is detected. transformers must be used.
• The second harmonic of the residual cur-
rent is derived. If this current is larger 6HQVLWLYHGLUHFWLRQDOUHVLGXDO
than 20/32 % of the total residual current, SRZHUSURWHFWLRQ :()
a signal is given that can be used for
blocking of the steps. $SSOLFDWLRQ
In isolated networks or in networks with high
If the conditions for function is fulfilled for a impedance earthing, the phase to earth fault
step, a trip signal is given after the set time current is significantly smaller than the short
delay. circuit currents. In addition to this, the magni-
tude of the fault current is almost independent
6HQVLWLYHGLUHFWLRQDOUHVLGXDO on the fault location in the network.
RYHUFXUUHQWSURWHFWLRQ :()
The protection uses the residual power com-
$SSOLFDWLRQ ponent 3U0 .3I0.cosϕ, where ϕ is the angle
In isolated networks or in networks with high between the residual current and the reference
impedance earthing, the phase to earth fault voltage, compensated with a characteristic
current is significantly smaller than the short angle. The characteristic angle is chosen to -
circuit currents. In addition to this, the magni- 90° in an isolated system. The characteristic
tude of the fault current is almost independent angle is chosen to 0° in compensated systems.
on the fault location in the network.
)XQFWLRQDOLW\
The protection uses the residual current com- The function measures the residual current
ponent 3I0 cosϕ, where ϕ is the angle and voltage. The angle between the residual
between the residual current and the reference voltage and residual current is calculated.
voltage, compensated with a characteristic This angle is used in two functions namely
angle. The characteristic angle is chosen to - first to determine if the fault is in forward or
90° in an isolated system. The characteristic reverse direction, and secondly to calculate
angle is chosen to 0° in compensated systems. the residual power component in the charac-
teristic angle direction.
)XQFWLRQDOLW\
The function measures the residual current The residual voltage (3U0) is compared with
and voltage. The angle between the residual a setting value. The residual current (3I0) is
voltage and residual current (angle between compared to a setting value. The residual
3I0 and -3U0 i.e U0 is 180 degrees adjusted) power component in the characteristic angle
is calculated. This angle is used in two func- direction (SN) is compared to a power refer-
tions namely first to determine if the fault is ence setting. If the power is larger than the
in forward or reverse direction, and secondly setting this is one criterion for function of the
to calculate the residual current component in protection. The voltage and current measure-
the characteristic angle direction. ment are two other criteria that must be ful-
filled for function. The information on power
The residual current component in the charac- is the input to a dependent time delay func-
teristic angle direction is compared with the tion. The function will give a trip signal when
set operating value. If this current component all three criteria for function are fulfilled and
is larger than the setting this is one criterion the time delay has elapsed.
for function of the protection. The residual
voltage is compared to a set operating value. Due to the demands on accuracy and sensitiv-
If the measured voltage is larger than the set- ity for this function, special current input cir-
ting this is another criterion for the operation cuits must be used.
of the protection. If both the criteria are ful-
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 19

6FKHPHFRPPXQLFDWLRQORJLF &XUUHQWUHYHUVDODQGZHDNHQG
IRUUHVLGXDORYHUFXUUHQWSURWHF LQIHHGORJLFIRUUHVLGXDORYHU
WLRQ ()& FXUUHQWSURWHFWLRQ ()&$
$SSOLFDWLRQ $SSOLFDWLRQ
The EFC directional comparison function The EFCA additional communication logic is
contains logic for blocking overreaching and a supplement to the EFC scheme communica-
permissive overreaching schemes. The func- tion logic for the residual overcurrent protec-
tion is applicable together with TEF time tion.
delayed directional residual overcurrent pro-
tection in order to decrease the total operate To achieve fast fault clearing for all earth
time of a complete scheme. faults on the line, the TEF earth-fault protec-
tion function can be supported with logic, that
One communication channel, which can uses communication channels. REx 5xx ter-
transmit an on / off signal, is required in each minals have for this reason available addi-
direction. It is recommended to use the com- tions to scheme communication logic.
plementary additional communication logic
EFCA, if the weak infeed and/or current If parallel lines are connected to common
reversal conditions are expected together with busbars at both terminals, overreaching per-
permissive overreaching scheme. missive communication schemes can trip
unselectively due to fault current reversal.
)XQFWLRQDOLW\ This unwanted tripping affects the healthy
The communication logic for residual over- line when a fault is cleared on the other line.
current protection contains logics for block- This lack of security can result in a total loss
ing overreach and permissive overreach of interconnection between the two buses.To
schemes. avoid this type of disturbance, a fault current-
reversal logic (transient blocking logic) can
In the blocking scheme a signal is sent to the be used.
remote end of the line if the directional ele-
ment, in the directional residual overcurrent Permissive communication schemes for
protection (sending end), detects the fault in residual overcurrent protection, can basically
the reverse direction. If no blocking signal is operate only when the protection in the
received and the directional element, in the remote terminal can detect the fault. The
directional residual overcurrent protection detection requires a sufficient minimum
(receiving end), detects the fault in the for- residual fault current, out from this terminal.
ward direction, a trip signal will be sent after The fault current can be too low due to an
a settable time delay. opened breaker or high positive and/or zero
sequence source impedance behind this ter-
In the permissive overreach scheme a signal minal. To overcome these conditions, weak
is sent to the remote end of the line if the end infeed (WEI) echo logic is used.
directional element, in the directional residual
overcurrent protection (sending end), detects )XQFWLRQDOLW\
the fault in the forward direction. If an accel- The reverse directed signal from the direc-
eration signal is received and the directional tional residual overcurrent function, starts the
element, in the directional residual overcur- operation of a current reversal logic. The out-
rent protection (receiving end), detects the put signal, from the logic, will be activated, if
fault in the forward direction, a trip signal the fault has been detected in reverse direc-
will be sent, normally with no time delay. In tion for more than the tPickUp time set on the
case of risk for fault current reversal or weak corresponding timers. The tDelay timer
end infeed, an additional logic can be used to delays the reset of the output signal. The sig-
take care of this. nal blocks the operation of the overreach per-
missive scheme for residual current, and thus
prevents unwanted operation due to fault cur-
rent reversal.

The weak end infeed logic uses normally a


forward and reverse signal from the direc-
tional residual overcurrent function. The
weak end infeed logic echoes back the
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 20

received permissive signal, if none of the The output signal THOL--TRIP has a dura-
directional measuring elements have been tion of 50 ms. The output signal THOL--
activated during the last 200 ms. Further, it START remains activated as long as the cal-
can be set to give signal to trip the breaker if culated temperature is higher than the set trip
the echo conditions are fulfilled and the resid- value minus a settable temperature difference
ual voltage is above the set operate value for TdReset (hysteresis). The output signal
3U0>. THOL--ALARM has a fixed hysteresis of
5o C.
7KHUPDOSKDVHRYHUORDGSURWHF
WLRQ 7+2/ %UHDNHUIDLOXUHSURWHFWLRQ %)3

$SSOLFWLRQ $SSOLFDWLRQ
Load currents that exceed the permissible In many protection applications local redun-
continuous value may cause damage to the dancy is used. One part of the fault clearance
conductors and isolation due to overheating. system is however never duplicated, namely
The permissible load current will vary with the circuit breaker. Therefore a breaker fail-
the ambient temperature. ure protection can be used.

The THOL thermal overcurrent function The breaker failure protection is initiated by
supervises the phase currents and provides a trip signals from different protection func-
reliable protection against damage caused by tions within or outside the protection termi-
excessive currents. The temperature compen- nal. When a trip signal is sent to the breaker
sation gives a reliable thermal protection even failure protection first, with no or a very short
when the ambient temperature has large vari- delay, a re-trip signal can be sent to the pro-
ations. tected breaker. If fault current is flowing
through the breaker still after a setting time a
)XQFWLRQDOLW\ back-up trip signal is sent to the adjacent
The final temperature rise of an object rela- breakers. This will ensure fault clearance also
tive the ambient temperature is proportional if the circuit breaker is out of order.
to the square of the current. The rate of tem-
perature rise is determined by the magnitude )XQFWLRQDOLW\
of the current and the thermal time constant Breaker failure protection, BFP, provides
of the object. The same time constant deter- backup protection for the primary circuit
mines the rate of temperature decrease when breaker if it fails to clear a system fault. It is
the current is decreased. obtained by checking that fault current per-
sists after a brief time from the operation of
The thermal overload function uses the high- the object protection and issuing then a three
est phase current. The temperature change is phase trip command to the adjacent circuit
continuously calculated and added to the fig- breakers (back-up trip).
ure for the temperature stored in the thermal
memory. When temperature compensation is Correct operation at evolving faults is
used, the ambient temperature is added to the ensured by phase segregated starting com-
calculated temperature rise. If no compensa- mand, phase segregated current check and
tion is used, 20o C is added as a fixed value. phase segregated settable timers.
The calculated temperature of the object is
then compared to the set values for alarm and Additionally, the retrip of the faulty circuit
trip. breaker after a settable time is possible. The
retrip can be controlled by current check or
The information on the ambient temperature carried out as direct retrip.
is received via a transducer input with for
example 0 - 10 mA or 4 - 20 mA.

9ROWDJH 7LPHGHOD\HGXQGHUYROWDJH where reliable detection of low phase volt-


SURWHFWLRQ 789 ages is necessary. The function can also be
used as a supervision and fault detection
$SSOLFDWLRQ function for some other protection functions,
The time delayed undervoltage protection to increase the security of a complete protec-
function, TUV, is applicable in all situations, tion system.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 21

7LPHGHOD\HGRYHUYROWDJH 7LPHGHOD\HGRYHUYROWDJH
SURWHFWLRQ 729 SURWHFWLRQ 729U
$SSOLFDWLRQ $SSOLFDWLRQ
The time delayed phase overvoltage protec- The residual overvoltage protection function
tion is used to protect the electrical equip- is mainly used in distribution networks,
ment and its insulation against overvoltage by mainly as a backup protection for the residual
measuring three phase voltages. In this way, it overcurrent protection in the line feeders, to
prevents the damage to the exposed primary secure the disconnection of earth-faults.
and secondary equipment in the power sys-
tems. )XQFWLRQDOLW\
The residual overvoltage protection function
)XQFWLRQDOLW\ calculates the residual voltage (3U0) from the
The phase overvoltage protection function measuring three phase voltages and initiates
continuously measures the three phase volt- the corresponding output signals if the resid-
ages and initiates the corresponding output ual voltage is larger than the preset value
signals if the measured phase voltages exceed (starting) and remains high longer than the
the preset value (starting) and remain high time delay setting (trip).
longer than the time delay setting on the tim-
ers (trip). This function also detects the
phases which caused the operation.

3RZHUV\VWHP %URNHQFRQGXFWRUFKHFN %5& )XQFWLRQDOLW\


VXSHUYLVLRQ The operation of LOV function is based on
$SSOLFDWLRQ line voltage measurement. The function is
The main purpose of the BRC broken con- provided with a logic, which automatically
ductor check function is the detection of bro- recognises if the line was restored for at least
ken conductors on protected power lines and three seconds before starting the seven sec-
cables (series faults). It is also able to detect onds timer. Additionally, the function is auto-
interruptions in the secondary current cir- matically blocked if only one or two phase
cuits. voltages have been detected low for more
than 10 seconds. The LOV function operates
)XQFWLRQDOLW\ again only if the line has been fully energised.
The BRC function detects a broken conductor
condition by detecting the non symmetry Operation of LOV function is also inhibited
between currents in the three phases. It does by fuse failure and open circuit breaker infor-
this by measuring the difference between the mation signals, by their connection to dedi-
maximum and minimum phase currents, i.e. it cated inputs of the function block.
compares the magnitude of the minimum cur-
rent with that of the maximum current, and The operation of the function is supervised by
gives an output if the minimum current is less the fuse-failure function and the information
than 80% of the maximum current for a set about the closed position of the associated
time interval. At the same time, the highest circuit breaker.
current must be higher than a set percentage
of the terminal rated current.
2YHUORDGVXSHUYLVLRQ 29/'
/RVVRIYROWDJHFKHFN /29 $SSOLFDWLRQ
The overload protection, OVLD, prevents
$SSOLFDWLRQ excessive loading of power transformers,
The loss of voltage detection, LOV, is suit- lines and cables.
able for use in networks with an automatic
restoration function. The LOV function Alternative application is the detection of pri-
issues a three-pole trip command to the cir- mary current transformer overload, as they
cuit breaker, if all three phase voltages fall usually can withstand a very small current
below the set value for a time longer than 7 beyond the rated value.
seconds, and the circuit breaker remains
closed.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 22

)XQFWLRQDOLW\ monitoring functions with the status of the


The function continuously measures the three line, i.e whether or not it is connected to the
phase currents flowing through the terminal. rest of the power system.
If any of the three currents is beyond the pre-
set overcurrent threshold for a time longer )XQFWLRQDOLW\
than the preset value, a trip signal is acti- The dead line detection function continuously
vated. measures all three phase currents and phase
voltages of a protected power line. The line is
declared as dead (not energized) if all three
'HDGOLQHGHWHFWLRQ '/' measured currents and voltages fall below the
preset values for more than 200 ms.
$SSOLFDWLRQ
The main purpose of the dead line detection
is to provide different protection, control and

6\VWHP 3ROHVOLSSURWHFWLRQ 363 degree of differentiation between oscillation


SURWHFWLRQDQG and fault conditions.
$SSOLFDWLRQ
FRQWURO Sudden events in an electrical power system It is possible to inhibit the ocsillation detected
such as large jumps in load, fault occurrence output on detection of earth fault current.
or fault clearance, can cause oscillations This can be used to release the operation of
referred to as power swings. In a recoverable the distance protection function for earth
situation, the power swings will decay and faults during power oscillation conditions.
stable operation will be resumed; in a non-
recoverable situation, the power swings The PSP function has two tripping areas.
become so severe that the synchronism is These are located within the operating area,
lost, a condition referred to as pole slipping. which is located within the inner characteris-
The main purpose of the PSP pole slip protec- tic. On detection of a new oscillation, the
tion is to detect, evaluate, and take the activation of a trip output will depend on the
required action for pole slipping occurrences applied settings. These determine the direc-
in the power system. tion of the transition for which tripping is per-
mitted, whether tripping will occur on entry
)XQFWLRQDOLW\ of the measured impedance into a tripping
The PSP function comprises an inner and an area, or on its exit from the tripping area, and
outer quadrilateral measurement characteris- through which tripping area the transition
tic. It detects oscillations in the power system must be measured for tripping to occur. The
by measuring the time it takes the transient applied settings also determine the number of
impedance to pass through the impedance pole slips required before the trip output is
area between the outer and the inner charac- issued.
teristics. Oscillations are identified by transi-
tion times longer than timer settings. The
impedance measuring principle is the same as /RZDFWLYHSRZHU
that used for the distance protection zones. SURWHFWLRQ /$33
The impedance and the transient impedance
time are measured in all three phases sepa- $SSOLFDWLRQ
rately. One-out-of-three or two-out-of-three The low active power protection function
operating modes can be selected permanently (LAPP) can be used wherever a “low active
or adaptively according to the specific system power” signal is needed. The main applica-
operating conditions. tion is as a local criterion to increase security
when transfer trips are used.
Oscillations with an oscillation period as low
as 200 ms (i.e. with a slip frequency as high In many power systems transfer trips are
as 10% of the rated frequency on a 50 Hz used, i.e. a trip criterion in one substation will
basis) can be detected for normal system be transferred to an adjacent substation via
operating conditions, as well as during the some sort of communication system. For such
dead time of a single-pole automatic reclos- solutions there is always a risk that a false
ing cycle. Different timers are used for initial transfer trip signal is generated in the com-
and consecutive pole slips, securing a high munication system and causes an unwanted
trip. In order to prevent such a scenario a
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 23

local criterion can be added in the substation )XQFWLRQDOLW\


where the trip is intended to take place. Such The low active and reactive power function
a local criterion could be low active power on measures the active and the reactive power
a line, which, in a correct sequence, is discon- separately in each phase. It also determines
nected in the remote end. whether the power flow is towards or from
the relay point as long as the measured cur-
)XQFWLRQDOLW\ rent and voltage are higher than the minimum
The low active power function measures the operating values. The operation becomes
active power separately in each phase. It also automatically nondirectional, if the measured
determines whether the power flow is current decreases under the minimum value
towards or from the relay point as long as the and the measured voltage remains higher.
measured current and voltage are higher than
the minimum operating values. The operation Two operating levels are settable independent
becomes automatically non-directional, if the of each other regarding their operating val-
measured current decreases under the mini- ues, directionality and time delay. It is possi-
mum value and the measured voltage remains ble to use their start and trip signals within
higher. the configuration of a terminal.

Two operating levels are setable independent


of each other regarding their operating val-
+LJKDFWLYHSRZHU
ues, directionality and time delay. It is possi- SURWHFWLRQ +$33
ble to use their start and trip signals within
the configuration of the terminal. $SSOLFDWLRQ
The high active power protection function
(HAPP) can be used wherever a “high active
/RZDFWLYHDQGUHDFWLYH power” signal is needed. There is a number of
SRZHUSURWHFWLRQ /$53 applications for the high active power protec-
tion, wherever active power flow has to be
$SSOLFDWLRQ limited or certain actions have to be taken
The combined low active and reactive power when the active power exceeds specific val-
protection function (LARP) can be used ues. One such example is arming of generator
wherever a “low reactive power” signal is rejection schemes due to certain active power
needed. The main application is as a local cri- transmission levels within a certain corridor.
terion to increase security when transfer trips
are used. The design gives the user a possibil- )XQFWLRQDOLW\
ity to increase the sensitivity for high levels The high active power function measures the
of active power. The tripping criterion is a active power separately in each phase. It also
function of the set value and the actual active determines whether the power flow is
power according to: towards or from the relay point as long as the
measured current and voltage are higher than
the minimum operating values.
Q trip = Q set + α ⋅ P
Two operating levels are setable independent
(Equation 1) of each other regarding their operating val-
In many power systems transfer trips are ues, directionality and time delay. It is possi-
used, i.e. a trip criterion in one substation will ble to use their start and trip signals within
be transferred to an adjacent substation via the configuration of the terminal.
some sort of communication system. For such
solutions there is always a risk that a false
transfer trip signal is generated in the com-
+LJKDFWLYHDQGUHDFWLYH
munication system and causes an unwanted SRZHUSURWHFWLRQ +$53
trip. In order to prevent such a scenario a
local criterion can be added in the substation $SSOLFDWLRQ
where the trip is intended to take place. Such The combined high active and reactive power
a local criterion could be low reactive power protection function (HARP) can be used
on a line, which, in a correct sequence, is dis- wherever a “high reactive power” signal is
connected in the remote end. needed. The design gives the user a possibil-
ity to increase the sensitivity for high levels
of active power. The tripping criterion is a
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 24

function of the set value and the actual active )XQFWLRQDOLW\


power according to: The amplitude of the difference between the
magnitudes of two consecutive cycles is
derived by means of the fourier coefficients
of the fundamental signal.
Q trip = Q set + α ⋅ P
(Equation 2) The integration time is one power system
Typically, high reactive power output from cycle.
generators, connected to transmission grids,
is used as an important signal in system pro- The change in current is compared to a set-
tection schemes to counteract voltage insta- ting value to create the start and, after a time
bility. delay, the trip signal.

)XQFWLRQDOLW\
6XGGHQFKDQJHLQUHVLGXDO
The high active and reactive power function
measures the active and the reactive power FXUUHQWSURWHFWLRQ 6&5&
separately in each phase. It also determines
whether the power flow is towards or from $SSOLFDWLRQ
the relay point as long as the measured cur- The sudden change in residual current protec-
rent and voltage are higher than the minimum tion function (SCRC) can be used wherever a
operating values. sudden change in residual current can be used
to improve the overall functionality of the
The operational characteristic is according to: protection system. The main application is as
a local criterion to increase security when
Q>Qset+tan(k)*abs(P). transfer trips are used.

Two operating levels are settable independent Whenever an earth-fault occurs, or a circuit-
of each other regarding their operating val- breaker get stuck in one phase, a residual cur-
ues, directionality and time delay. It is possi- rent appears, that can be used to increase the
ble to use their start and trip signals within security of transfer trip arrangements.
the configuration of a terminal.
)XQFWLRQDOLW\
The amplitude of the difference between the
6XGGHQFKDQJHLQSKDVH magnitudes of two consecutive cycles is
FXUUHQWSURWHFWLRQ 6&& derived by means of the fourier coefficients
of the fundamental signal.
$SSOLFDWLRQ
The sudden change in current protection The integration time is one power system
function (SCC1) can be used wherever a sud- cycle.
den change in current can be used to improve
the overall functionality of the protection sys- The change in residual current is compared to
tem. The main application is as a local crite- a setting value to create the start and, after a
rion to increase security when transfer trips time delay, the trip signal.
are used.
6XGGHQFKDQJHLQYROWDJH
In many power systems transfer trips are
used, i.e. a trip criterion in one substation will
SURWHFWLRQ 6&9
be transferred to an adjacent substation via
$SSOLFDWLRQ
some sort of communication system. For such
The sudden change in voltage protection
solutions there is always a risk that a false
function (SCV) can be used wherever a sud-
transfer trip signal is generated in the com-
den change in voltage can be used to improve
munication system and causes an unwanted
the overall functionality of the protection sys-
trip. In order to prevent such a scenario a
tem.
local criterion can be added in the substation
where the trip is intended to take place. Such
One application is as a local criterion to
a local criterion could be a sudden change in
increase security when transfer trips are used.
current on a line, which, in a correct
Another application is to recognize network
sequence, is disconnected in the remote end.
topology changes that cause sudden changes
in voltage. Also faults, tap-changer opera-
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 25

tions, shunt device switching, etc., cause sud- criterion to increase security when transfer
den changes in voltage that can be captured trips are used.
by the SCV function.
In many power systems transfer trips are
)XQFWLRQDOLW\ used, i.e. a trip criterion in one substation will
The amplitude of the difference between the be transferred to an adjacent substation via
magnitudes of two consecutive cycles is some sort of communication system. For such
derived by means of the fourier coefficients solutions there is always a risk that a false
of the fundamental signal. transfer trip signal is generated in the com-
munication system and causes an unwanted
The integration time is one power system trip. In order to prevent such a scenario a
cycle. local criterion can be added in the substation
where the trip is intended to take place. Such
The change in voltage is compared to a set- a local criterion could be low current on a
ting value to create a start signal and, after a line, which, in a correct sequence, is discon-
time delay, a trip signal. nected in the remote end.

)XQFWLRQDOLW\
2YHUYROWDJHSURWHFWLRQ When any phase current decreases under the
293 setpoint value, a start signal is issued.
$SSOLFDWLRQ When a start signal is activated and the car-
The overvoltage protection function (OVP) rier received signal is true, a trip signal is
can be used wherever a "high voltage" signal issued after a settable time delay.
is needed. The function can be used for appli-
cations where a high voltage is the result of
an event that has to be indicated, or actions to 3KDVHRYHUFXUUHQW
reduce the time with high voltage levels are SURWHFWLRQ 2&3
required.
$SSOLFDWLRQ
One application example is to take actions to The overcurrent protection function (OCP)
quickly reduce high voltage levels by switch- can be used wherever a "high current" signal
ing out shunt capacitors or switching in shunt is needed. There is a number of applications
reactors, in case of a long transmission con- for the high current protection, wherever cur-
nected in one end only. rent has to be limited, or certain actions have
to be taken when the current exceeds specific
)XQFWLRQDOLW\ values.
The overvoltage protection function (OVP)
measures all three phase voltages on a pro- )XQFWLRQDOLW\
tected power line. The measured voltage sig- The amplitude of the phase currents are cal-
nals are extensively filtered, to secure high culated by means Fourier filtering. When any
accuracy of the measurement. Each of two of the phase currents are larger than the set-
independent voltage measuring stages has its ting values for the high-set step or the low-set
own, independently settable time delay. step, the corresponding start signal will be
activated. At the same time the corresponding
The resetting ratio of the function is settable, timer will be started. After the timer for the
to adjust the operation as much as possible to step has elapsed and there is a CR signal, a
the expected system overvoltage conditions. trip signal will be activated.
This expecially when the big shunt reactors
are used in the network to control the system
overvoltages.
5HVLGXDORYHUFXUUHQW
SURWHFWLRQ 52&3
8QGHUFXUUHQWSURWHFWLRQ $SSOLFDWLRQ
8&3 The residual overcurrent protection function
(ROCP) can be used wherever a high residual
$SSOLFDWLRQ current signal is needed. There is a number of
The undercurrent protection function (UCP) applications for the high residual current pro-
can be used whenever a "low current" signal tection, most of them related to earth faults in
is needed. The main application is as a local low impedance earthed systems. One exam-
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 26

ple is to use the residual overcurrent protec- residual current is larger than the setting
tion as a simple earth fault protection, as a value for the high-set step or the low set step,
back-up for the primary earth fault protection the corresponding start signal will be acti-
included in the line distance protection. vated. At the same time the corresponding
timer will be started. After the timer for the
)XQFWLRQDOLW\ step has elapsed and there is a CR signal, a
The amplitude of the residual current is calcu- trip signal will be activated.
lated by means Fourier filtering. When the

6HFRQGDU\ &XUUHQWFLUFXLWVXSHUYLVLRQ The FUSE function based on the negative


V\VWHP FXUUHQWEDVHG &768 sequence measurement principle is recom-
mended in isolated or high impedance earthed
VXSHUYLVLRQ $SSOLFDWLRQ systems.
Faulty information about current flows in a
protected element might influence the secu- A criterion based on delta current and delta
rity (line differential protection) or depend- voltage measurements can be added to the
ability (line distance protection) of a FUSE function in order to detect a three
complete protection system. phase fuse failure, which in practice is more
associated with voltage transformer switching
The main purpose of the current circuit super- during station operations.
vision function is to detect different faults in
the current secondary circuits and influence )XQFWLRQDOLW\
the operation of corresponding main protec- The FUSE function based on the negative
tion functions. sequence measurement principle continu-
ously measures the negative sequence voltage
The signal can be configured to block differ- and current in all three phases. It operates if
ent protection functions or initiate an alarm. the measured negative sequence voltage
increases over the preset operating value, and
)XQFWLRQDOLW\ if the measured negative sequence current
The function compares the sum of the three remains below the preset operating value.
phase currents from one current transformer
core with a reference zero sequence current The FUSE function based on the zero
from another current transformer core. sequence measurement principle continu-
ously measures the zero sequence current and
The function issues an output signal when the voltage in all three phases. It operates if the
difference is greater than the set value. measured zero sequence voltage increases
over preset operating value, and if the mea-
sured zero sequence current remains below
)XVHIDLOXUHVXSHUYLVLRQ )86( the preset operating value.
$SSOLFDWLRQ The di/dt and du/dt algorithm, detects a fuse
The fuse failure supervision function, FUSE, failure if a sufficient negative change in volt-
continuously supervises the ac voltage cir- age amplitude without a sufficient change in
cuits between the voltage instrument trans- current amplitude is detected in each phase
formers and the terminal. Different output separately. This check is performed if the cir-
signals can be used to block, in case of faults cuit breaker is closed. Information about the
in the ac voltage secondary circuits, the oper- circuit breaker position is brought to the func-
ation of the distance protection and other tion input CBCLOSED through a binary
voltage-dependent functions, such as the syn- input of the terminal.
chro-check function, undervoltage protection,
etc. Three output signals are available. The first
depends directly on the voltage and current
Different measurement principles are avail- measurement. The second depends on the
able for the fuse failure supervision function. operation of the dead line detection function,
to prevent unwanted operation of the distance
The FUSE function based on zero sequence protection if the line has been deenergised
measurement principle, is recommended in and energised under fuse failure conditions.
directly or low impedance earthed systems. The third depends on the loss of all three
measured voltages. A special function input
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 27

serves the connection to the auxiliary contact the measuring voltage from a capacitive volt-
of a miniature circuit breaker, MCB (if used), age transformer.
to secure correct operation of the function on
simultaneous interruption of all three mea- )XQFWLRQDOLW\
sured phase voltages also when the additional The voltage transformer supervision function
delta current and delta voltage algorithm is checks all of the three phase-phase voltages
not present in the function block. and the residual voltage. If the residual volt-
age exceeds the setpoint value and any of the
phase-phase voltages is higher than 80% of
9ROWDJHWUDQVIRUPHUVXSHUYLVLRQ the rated phase-phase voltage the output is
7&7 activated after a settable time delay.
$SSOLFDWLRQ
The main purpose of the voltage transformer
supervision function is to indicate failure in

&RQWURO 6LQJOHFRPPDQGVLJQDOV 6\QFKURFKHFNDQG


&' HQHUJL]LQJFKHFN 6<1
$SSOLFDWLRQ $SSOLFDWLRQ
The terminals may be provided with a func- The main purpose of the synchrocheck func-
tion to receive signals either from a substa- tion is to provide controlled closing of circuit
tion automation system (SMS and/or SCS) or breakers in interconnected networks.
from the local human-machine interface,
HMI. That receiving function block has 16 The main purpose of the energizing check
outputs that can be used, for example, to con- function is to facilitate the controlled recon-
trol high voltage apparatuses in switchyards. nection of a disconnected line or bus to,
For local control functions, the local HMI can respectively, an energized bus or line.
also be used. Together with the configuration
logic circuits, the user can govern pulses or The main purpose of the synchronizing func-
steady output signals for control purposes tion is to provide controlled closing of circuit
within the terminal or via binary outputs. breakers when two asynchronous systems are
going to be connected. It is used for slip fre-
)XQFWLRQDOLW\ quencies that are larger than those for synch-
The single command function consists of a rocheck.
function block CD for 16 binary output sig-
nals. The synchronizing function is only available
together with the synchrocheck and energiz-
The output signals can be of the types Off, ing check functions.
Steady, or Pulse. The setting is done on the
MODE input, common for the whole block, To meet the different application arrange-
from the CAP 531 configuration tool. ments, a number of identical SYN function
blocks may be provided within a single termi-
The outputs can be individually controlled nal. The number of these function blocks that
from the operator station, remote-control may be included within any given terminal
gateway, or from the local HMI. Each output depends on the type of terminal. Therefore,
signal can be given a name with a maximum the specific circuit breaker arrangements that
of 13 characters from the CAP 531 configura- can be catered for, or the number of bays of a
tion tool. specific arrangement that can be catered for,
depends on the type of terminal.
The output signals, here OUT1 to OUT16,
are then available for configuration to built-in )XQFWLRQDOLW\
functions or via the configuration logic cir- The synchrocheck function measures the con-
cuits to the binary outputs of the terminal. ditions across the circuit breaker and com-
pares them to set limits. The output is only
given when all measured conditions are
simultaneously within their set limits.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 28

The energizing check function measures the Especially at higher voltages, the majority of
bus and line voltages and compares them to line faults are single-phase-to-earth. Faults
both high and low threshold detectors. The involving all three phases are rare. The main
output is only given when the actual mea- purpose of the single- and two-pole automatic
sured conditions match the set conditions. reclosing function, operating in conjunction
with a single- and two-pole tripping capabil-
The synchronizing measures the conditions ity, is to limit the effect to the system of faults
across the circuit breaker, and also determines involving less than all three phases. This is
the angle change during the closing delay of particularly valuable for maintaining system
the circuit breaker from the measured slip fre- stability in systems with limited meshing or
quency. The output is only given when all parallel routing.
measured conditions are simultaneously
within their set limits. The issue of the output )XQFWLRQDOLW\
is timed to give closure at the optimal time. The AR function is a logical function built up
from logical elements. It operates in conjunc-
6LQJOHEUHDNHU tion with the trip output signals from the line
For single circuit breaker arrangements, the protection functions, the OK to close output
SYN function blocks have the capability to signals from the synchrocheck and energizing
make the necessary voltage selection. For sin- check function, and binary input signals. The
gle circuit breaker arrangements, selection of binary input signals can be for circuit breaker
the correct voltage is made using auxiliary position/status or from other external protec-
contacts of the bus disconnection. tion functions.

Of the six reclosing programs, one provides


$XWRUHFORVHU $5 for three-pole reclosing only, while the others
provide for single- and two-pole reclosing as
$SSOLFDWLRQ
The majority of power line faults are transient well. For the latter, only the first shot may be
single- or two-pole. All subsequent shots up
in nature, i.e. they do not recur when the line
to the maximum number will be three-pole.
is re-energized following disconnection. The
main purpose of the AR automatic reclosing For some of the programs, depending on the
initial trip, no shot, or only one shot, will be
function is to automatically return power
permitted irrespective of the number of shots
lines to service following their disconnection
for fault conditions. selected.

/RJLF 7ULSSLQJORJLF 75 arrangements that can be catered for, or the


number of bays of a specific arrangement that
$SSOLFDWLRQ can be catered for, depends on the type of ter-
The main purpose of the TR trip logic func- minal.
tion is to serve as a single node through
which all tripping for the entire terminal is )XQFWLRQDOLW\
routed. The minimum duration of a trip output signal
from the TR function is settable.
The main purpose of the single- and two-pole
extension to the basic three-pole tripping The TR function has a single input through
function is to cater for applications where, for which all trip output signals from the protec-
reasons of system stability, single-pole trip- tion functions within the terminal, or from
ping is required for single-phase faults, and/ external protection functions via one or more
or two-pole tripping is required for two-phase of the terminal’s binary inputs, are routed. It
faults, e.g. on double circuit parallel lines. has a single trip output for connection to one
or more of the terminal’s binary outputs, as
To meet the different single, double, 1 and 1/2 well as to other functions within the terminal
or other multiple circuit breaker arrange- requiring this signal.
ments, one or more identical TR function
blocks may be provided within a single termi- The expanded TR function for single- and
nal. The actual number of these TR function two-pole tripping has additional phase segre-
blocks that may be included within any given gated inputs for this, as well as inputs for
terminal depends on the type of terminal. faulted phase selection. The latter inputs
Therefore, the specific circuit breaker enable single- and two-pole tripping for those
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 29

functions which do not have their own phase +LJKVSHHGELQDU\RXWSXW


selection capability, and therefore which have ORJLF +6%2
just a single trip output and not phase segre-
gated trip outputs for routing through the $SSOLFDWLRQ
phase segregated trip inputs of the expanded The time taken for signals to be transferred
TR function. The expanded TR function has from binary inputs to protection functions,
two inputs for these functions, one for imped- and from protection functions to binary out-
ance tripping (e.g. carrier-aided tripping com- puts contributes to the overall tripping time.
mands from the scheme communication The main purpose of the HSBO high speed
logic), and one for earth fault tripping (e.g. binary output logic is to minimize overall
tripping output from a residual overcurrent tripping times by establishing the critical con-
protection). Additional logic secures a three- nections to/from the binary outputs/inputs in
pole final trip command for these protection a more direct way than with the regular I/O
functions in the absence of the required phase connections.
selection signals.
)XQFWLRQDOLW\
The expanded TR function has three trip out- The outputs from the HSBO logic utilize
puts, one per phase, for connection to one or ‘fast’ connections to initiate binary outputs.
more of the terminal’s binary outputs, as well The inputs to the HSBO logic utilize the same
as to other functions within the terminal ‘fast’ connections. Input connections to the
requiring these signals. logic are derived from binary inputs, from
outputs of the high speed distance protection,
The expanded TR function is equipped with and from inputs to the regular trip logic and
logic which secures correct operation for scheme communication logic. The HSBO
evolving faults as well as for reclosing on to scheme communication logic runs in parallel
persistent faults. A special input is also pro- with the regular scheme communication
vided which disables single- and two-pole logic.
tripping, forcing all tripping to be three-pole.
The ‘fast’ connections to and from the HSBO
3ROHGLVFRUGDQFHORJLF 3'F logic comprise so called hard connections in
software. This configuration is made inter-
$SSOLFDWLRQ nally and cannot be altered. The only excep-
Breaker pole position discordance can occur tions are the connections to the binary outputs
on the operation of a breaker with indepen- where limited configuration is possible, and
dent operating gears for the three poles. The required, on the part of the user.
reason may be an interruption in the closing
or trip coil circuit, or a mechanical failure $GGLWLRQDOFRQILJXUDEOH
resulting in a stuck breaker pole. A pole dis- ORJLFEORFNV &/
cordance can be tolerated for a limited time,
for instance during a single-phase trip-reclose $SSOLFDWLRQ
cycle. The pole discordance function detects Additional configurable logic means that an
a breaker pole discordancy not generated by extended number of logic circuits are avail-
auto-reclose cycle and issues a trip signal for able. Also Move function blocks (MOF,
the circuit breaker. MOL), used for synchronization of boolean
signals sent between logics with slow and fast
)XQFWLRQDOLW\
execution, are among the additional config-
The operation of the pole discordance logic,
urable logic circuits.
PD, is based on checking the position of the
breaker auxiliary contacts. Three parallel nor- )XQFWLRQDOLW\
mally open contacts in series with three nor- The functionality of the additional logic func-
mally closed contacts in parallel of the tion blocks are the same as for the basic logic
respective breaker poles form a condition of functions, but with an extended number of
pole discordance, connected to a binary input blocks.
dedicated for the purpose.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 30

&RPPXQLFDWLRQFKDQQHOWHVW (YHQWFRXQWHU &1


ORJLF &&+7
$SSOLFDWLRQ
$SSOLFDWLRQ The function consists of six counters which
Many secondary system applications require are used for storing the number of times each
testing of different functions with confirmed counter has been activated. It is also provided
information about the result of the test. The with a common blocking function for all six
main purpose of the CCHT communication counters, to be used for example at testing.
channel test logic is to perform testing of Every counter can separately be set on or off
communication channels (power line carrier) by a parameter setting.
in applications where continuous monitoring
by some other means is not possible due to )XQFWLRQDOLW\
technical or economic reasons, and to indi- The function block has six inputs for increas-
cate the result of the test. ing the counter values for each of the six
counters respectively. The content of the
)XQFWLRQDOLW\ counters are stepped one step for each posi-
Starting of a communications channel test tive edge of the input respectively.
may be performed manually (by means of an
external pushbutton) or automatically (by The function block also has an input BLOCK.
means of an included timer). When started, At activation of this input all six counters are
the CCHT logic initiates the sending of an blocked.
impulse (carrier send signal) to the remote
end. This action starts the operation of the 0XOWLSOHFRPPDQG &0
applicable external functions. On receipt of
the sent signal at the remote end terminal, a $SSOLFDWLRQ
return signal is immediately sent back to the The terminals may be provided with a func-
initiating end by the identical CCHT logic tion to receive signals either from a substa-
function within that terminal. The initiating tion automation system or from other
end waits for this returned signal. It reports a terminals via the interbay bus. That receiving
successful or an unsuccessful response to the function block has 16 outputs that can be
initiated test based on the receipt or not of used, together with the configuration logic
this signal. An input is provided through circuits, for control purposes within the ter-
which it is possible to abort the test by means minal or via binary outputs. When it is used
of an external signal. to communicate with other terminals, these
terminals must have a corresponding event
%LQDU\VLJQDOWUDQVIHUWRUHPRWH function block to send the information.
HQG 57& )XQFWLRQDOLW\
One multiple command function block CM01
*HQHUDO
with fast execution time also named %LQDU\
In this function, there are two function
VLJQDOLQWHUED\FRPPXQLFDWLRQKLJKVSHHG
blocks, RTC1-, and RTC2-. They are identi-
cal in all aspects. and/or 79 multiple command function blocks
CM02-CM80 with slower execution time are
$SSOLFDWLRQ available in the REx 5xx terminals as options.
The main purpose of the RTC binary signal
transfer to remote end function is the The output signals can be of the types Off,
exchange of communication scheme related Steady, or Pulse. The setting is done on the
signals, trip signals and/or other binary sig- MODE input, common for the whole block,
nals between opposite ends of the line. from the CAP 531 configuration tool.

)XQFWLRQDOLW\ The multiple command function block has 16


The RTC function comprises two identical outputs combined in one block, which can be
function blocks, each able to handle up to 16 controlled from the operator station or from
inputs and 16 outputs, giving a total of 32 sig- other terminals. One common name for the
nals that can be transmitted in each direction. block, with a maximum of 19 characters, is
set from the configuration tool CAP 531.
The updated status of the selected binary sig-
nals is packaged within a data message which The output signals, here OUT1 to OUT16,
is sent once every computation loop. are then available for configuration to built-in
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 31

functions or via the configuration logic cir- The command function also has a supervision
cuits to the binary outputs of the terminal. function, which sets the output VALID to 0 if
the block did not receive data within a config-
ured INTERVAL time.

0RQLWRULQJ 'LVWXUEDQFHUHSRUW '53 state changes from logic one to logic zero
will not be visible in the indications list. Sig-
$SSOLFDWLRQ nals are not time tagged. In order to be listed
Use the disturbance report to provide the net- in the indications list the:
work operator with proper information about
disturbances in the primary network. The 1. signal must be connected to the DRP
function comprises several subfunctions function blocks, (DRP1, DRP2, DRP3).
enabling different types of users to access rel- 2. setting parameter, IndicationMask, for the
evant information in a structured way. input must be set to Show.
Select appropriate binary signals to trigger Output signals of other function blocks of the
the red HMI LED to indicate trips or other configuration will be listed by the signal
important alerts. name listed in the corresponding signal list.
Binary input signals are listed by the name
)XQFWLRQDOLW\ defined in the configuration.
The disturbance report collects data from
each subsystem for up to ten disturbances. The indications can be viewed on the local
The data is stored in nonvolatile memory, HMI and via SMS.
used as a cyclic buffer, always storing the lat-
est occurring disturbances. Data is collected
during an adjustable time frame, the collec- 'LVWXUEDQFHUHFRUGHU '5
tion window. This window allows for data
collection before, during and after the fault. $SSOLFDWLRQ
Use the disturbance recorder to record analog
The collection is started by a trigger. Any and binary signals during fault conditions in
binary input signal or function block output order to analyze disturbances. The analysis
signal can be used as a trigger. The analog may include fault severity, fault duration and
signals can also be set to trigger the data col- protection performance. Replay the recorded
lection. Both over levels and under levels are data in a test set to verify protection perfor-
available. The trigger is common for all sub- mance.
systems, hence it activates them all simulta-
neously. )XQFWLRQDOLW\
The disturbance recorder records both analog
A triggered report cycle is indicated by the and binary signal information and up to ten
yellow HMI LED, which will be lit. Binary disturbances can be recorded.
signals may also be used to activate the red
HMI LED for additional alerting of fault con- Analog and digital signals can be used as trig-
ditions. A disturbance report summary can be gers. A trigger signal does not need to be
viewed on the local HMI. recorded.

A trigger is generated when the analog signal


,QGLFDWLRQV moves under and/or over set limit values. The
trig level is compared to the signal’s average
$SSOLFDWLRQ peak-to-peak value, making the function
Use the indications list to view the state of insensible to DC offset. The trig condition
binary signals during the fault. All binary must occur during at least one full period, that
input signals to the disturbance report func- is, 20 ms for a 50 Hz network.
tion are listed.
The recorder continuously records data in a
)XQFWLRQDOLW\ cyclic buffer capable of storing the amount of
The indications list tracks zero-to-one data generated during the set pre-fault time of
changes of binary signals during the fault the collection window. When triggered, the
period of the collection window. This means pre-fault data is saved and the data for the
that constant logic zero, constant logic one or
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 32

fault and post-fault parts of the collection Reliable information on fault location reduces
window is recorded. the outage time and minimises the need for
patrolling.
The RAM area for temporary storage of
recorded data is divided into subareas, one for The function has limitations for applications
each recording. The size of a subarea depends with series compensated lines.
on the set recording times. There is sufficient
memory for four consecutive recordings with )XQFWLRQDOLW\
a maximum number of analog channels The fault locator can be started by any inter-
recorded and with maximum time settings. nal or external binary signal. Pre-fault and
Should no subarea be free at a new distur- fault phasors of currents and voltages, that
bance, the oldest recording is overwritten. were filtered from disturbance data stored
into digital sample buffers, are then used for
When a recording is completed, the post the distance to fault calculation. The phase
recording process: selective signals from the built-in protection
functions provide the necessary information
• merges the data for analog channels with for the selection of the loop to be used for the
corresponding data for binary signals calculation. It is also possible to use the exter-
stored in an event buffer nal phase selection information.
• compresses the data without loosing any
data accuracy For the distance to fault calculation, a line
modelling algorithm that takes into account
• stores the compressed data in a non-vola- the sources at both ends of the line, is used. In
tile memory this way, the influence of the load current, the
infeed from the remote end and the fault
The disturbance recordings can be viewed via resistance, can be compensated for, resulting
SMS or SCS. in a highly accurate calculation.

(YHQWUHFRUGHU (5 In case of double circuit lines, the influence


of the zero-sequence mutual impedance Zm0
$SSOLFDWLRQ is compensated for by considering the resid-
Use the event recorder to obtain a list of ual current on the parallel line.
binary signal events that occurred during the
disturbance. The function indicates the distance to the
fault as a percentage of the line length, in
)XQFWLRQDOLW\ kilometers or miles as selected.
When a trigger condition for the disturbance
report is activated, the event recorder collects Possibility to make recalculations with
time tagged events from the 48 binary signals changed parameter settings exists.
that are connected to disturbance report and
lists the changes in status in chronological Information on the last ten disturbances is
order. Each list can contain up to 150 time stored.
tagged events that can come from both inter-
nal logic signals and binary input channels
and up to ten disturbances can be recorded.
7ULSYDOXHUHFRUGHU 795
Events are recorded during the total recording
$SSOLFDWLRQ
time which depends on the set recording
Use the trip value recorder to record fault and
times and the actual fault time.
prefault phasor values of voltages and cur-
rents to be used in detailed analysis of the
Events can be viewed via SMS and SCS.
severity of the fault and the phases that are
involved. The recorded values can also be
)DXOWORFDWRU )/2& used to simulate the fault with a test set.

$SSOLFDWLRQ )XQFWLRQDOLW\
An accurate fault locator is an essential com- Pre-fault and fault phasors of currents and
plement to the line protection. The fault loca- voltages are filtered from disturbance data
tor provides distance to fault together with stored in digital sample buffers.
information about the measuring loop that has
been used in the calculation.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 33

When the disturbance report function is trig- ,QFUHDVHGDFFXUDF\RI$&LQSXW


gered, the function looks for non-periodic TXDQWLWLHV ,0$
change in the analog channels. Once the fault
interception is found, the function calculates $SSOLFDWLRQ
the pre-fault RMS values during one period Select the increased accuracy option to
starting 1,5 period before the fault intercep- increase the measuring accuracy of analog
tion. The fault values are calculated starting a input channels, thus also increasing the accu-
few samples after the fault interception and racy of calculated quantities such as fre-
uses samples during 1/2 - 2 periods depend- quency, active and reactive power.
ing on the waveform.
)XQFWLRQDOLW\
If no error sample is found the trigger sample The increased accuracy is reached by a fac-
is used as the start sample for the calcula- tory calibration of the hardware. Calibration
tions. The estimation is based on samples one factors are stored in the terminal. If the trans-
period before the trigger sample. In this case former input module, A/D conversion module
the calculated values are used both as pre- or the main processing module is replaced,
fault and fault values. the terminal must be factory calibrated again
to retain the increased accuracy.
The recording can be viewed on the local
HMI or via SMS.

0HWHULQJ 3XOVHFRXQWHUORJLFIRUPHWHULQJ frequency of up to 40 Hz. The registration of


3& pulses is done for positive transitions (0 to 1)
on any of the 16 binary input channels on the
$SSOLFDWLRQ input module.
The pulse counter logic function counts exter-
nally generated binary pulses, for instance Pulse counter values are read from the opera-
pulses coming from an external energy meter, tor workplace with predefined cyclicity with-
for calculation of energy consumption values. out reset. The integration time period can be
The pulses are captured by the binary input set in the range from 30 seconds to 60 min-
module and then read by the pulse counter utes and is synchronized with absolute system
function. The number of pulses in the counter time.
is then reported via LON to the station con-
trol system or read via SPA from the station The counter value is a 32-bit, signed integer
monitoring system as a service value. with a range 0...+2147483647. The reported
value over the communication bus contains
)XQFWLRQDOLW\ Identity, Value, Time and Pulse Counter
Up to 12 inputs located on binary input mod- Quality.
ules can be used for counting of pulses with a

'DWD 5HPRWHHQGGDWDFRPPXQLFD • V35/36 contra-directional and co-direc-


FRPPXQLFDWLRQ WLRQPRGXOHV tional
• X.21
$SSOLFDWLRQ • RS530/422 contra-directional and co-
The remote terminal communication modules directional
are used for binary signal transfer of up to 32
signals to remote end (RTC), for example for • G.703
distance protections. The following hardware • Short-range galvanic module
modules are available: • Fibre optical communication module
• Short-range fibre optical module

)LEUHRSWLFDOPRGXOH
The fibre optical communication module
DCM-FOM can be used both with multi-
mode and single-mode fibres.The communi-
cation distance can typically be up to 30 km
for single mode fibre and be up to 15 km for
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 34

multi-mode fibre, with high quality fibres 6KRUWUDQJHILEUHRSWLFDOPRGXOH


even longer. This interface can also be used The short-range fibre optical module DCM-
for direct connection to communication SFOM can only be used with multi-mode
equipment of type FOX from ABB. fibre .The communication distance can nor-
mally be up to 5 km. This module can also be
*DOYDQLFLQWHUIDFH used for direct connection to optical/electrical
The galvanic data communication modules communication converters of type 21-15xx
according to V35/36 DCM-V36 contra, and 21-16xx from FIBERDATA
DCM-V36 co, X.21 DCM-X21, RS530/422
DCM-RS 530 contra, DCM-RS 530 co can be Physically the DCM module is inserted in
used for galvanic short range communication slot position S19 for 1/2 19” rack.
covering distances up to 100 m in low noise
environment. Only contra-directional opera- Physically the DCM module is inserted in
tion is recommended in order to get best sys- slot position S29 for 3/4 19” rack.
tem performance. These modules are
designed for 64 kbit/s operation but can also &RGLUHFWLRQDO*JDOYDQLFLQWHUIDFH
be used at 56 kbit/s. The galvanic data communication module
DCM-G.703 according to G.703 is not recom-
6KRUWUDQJHJDOYDQLFPRGXOH mended for distances above 10 m. Special
The short-range galvanic module DCM-SGM attention must be paid to avoid problems due
can be used for communication over galvanic to noise interference. This module is designed
pilot wires and can operate up to distances only for 64 kbit/s operation.
between 0,5 and 4 km depending on pilot
wire cable. Twisted-pair, double-screened &RPPXQLFDWLRQDOWHUQDWLYHV
cable is recommended.
optical fibres
DCM-FOM DCM-FOM
REx 5xx singlemode or singlemode or REx 5xx
multimode multimode

en03000159.vsd

Figure 6: Dedicated link, optical fibre connection

optical fibres

REx 5xx DCM-SFOM DCM-SFOM REx 5xx


multimode multimode

en03000150.vsd

Figure 7: Dedicated link, short range optical fibre connection


3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 35

optical fibres

FOX
REx 5xx DCM-FOM 515/512
to the
MUX other end

other
users

en03000151.vsd

Figure 8: Multiplexed link, optical fibre connection

Galvanic G.703
twisted pair cable with
double screen
optical fibres < 10 m

REx 5xx DCM-FOM FOX 512/515 MUX


to the
other end

other
users

en03000152.vsd

Figure 9: Multiplexed link, fibre optical-galvanic connection with FOX 515

Galvanic V35/V36
twisted pair cable
with double screen
< 100 m

DCM-V36
REx 5xx contra
MUX
to the
other end

other
users

en03000153.vsd

Figure 10:Multiplexed link, galvanic connection, V35/V36 contra directional


3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 36

Galvanic V35/V36
twisted pair cable
with double screen
< 100 m

REx 5xx DCM-V36 co MUX


to the
other end

other
users

en03000154.vsd

Figure 11:Multiplexed link, galvanic connection, V35/V36 co-directional

Galvanic X.21
twisted pair cable
with double screen
< 100 m

REx 5xx DCM-X.21 MUX


to the
other end

other
users

en03000155.vsd

Figure 12:Multiplexed link, galvanic connection, X.21


3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 37

Galvanic RS 530/422
twisted pair cable
with double screen
< 100 m

DCM-RS 530 MUX


REx 5xx
contra
to the
other end

other
users

en03000156.vsd

Figure 13:Multiplexed link, galvanic connection, RS 530/422

Galvanic RS 530/422
twisted pair cable
with double screen
< 100 m

REx 5xx DCM-RS 530 co MUX


to the
other end

other
users

en03000157.vsd

Figure 14:Multiplexed link, galvanic connection, RS 530/422 co-directional

Twisted pair
cable with
double screen

REx 5xx DCM-SGM DCM-SGM REx 5xx

en03000158.vsd

Figure 15:Dedicated link, short range galvanic modem


3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 38

Galvanic G.703
twisted pair cable with
double screen
< 10 m

REx 5xx DCM-G.703


MUX to the
other end

other
users

en03000146.vsd

Figure 16:Multiplexed link, galvanic connection, G.703

Galvanic V35/V36
twisted pair cable with
double screen
optical fibres < 100 m

21-15X V35/V36
REx 5xx DCM-SFOM FIBERDATA
MUX to the
other end

other
users

en03000147.vsd

Figure 17:Multiplexed link, optical fiber - galvanic connection V35/V36 with 21 - 15X
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 39

Galvanic X.21
twisted pair cable with
double screen
optical fibres < 100 m

21-16X X.21
REx 5xx DCM-SFOM FIBERDATA
to the
MUX other end

other
users

en03000148.vsd

Figure 18:Multiplexed link, optical fibre - galvanic connection X.21 with 21-16X

Galvanic G.703
twisted pair cable with
double screen
optical fibres < 10 m

21-16X G.703
REx 5xx DCM-SFOM FIBERDATA
MUX to the
other end

other
users

en03000149.vsd

Figure 19:Multiplexed link, optical fibre - galvanic connection G.703 with 21-16X

6HULDOFRPPXQLFDWLRQ functionalities regarding monitoring and set-


ting of the functions in the terminal.
$SSOLFDWLRQ
One or two optional optical serial interfaces One RS485 interface can be inserted replac-
with LON protocol, SPA protocol or ing one of the optical interfaces. The RS485
IEC 60870-5-103 protocol, for remote com- interface is ordered as terminated for last ter-
munication, enables the terminal to be part of minal in a multidrop connection. The RS485
a Substation Automation (SA) system. These interface is alternatively ordered as untermi-
interfaces with terminal designations X13 and nated for point to point connection, or for
X15 are located at the rear of the terminal. intermediate location in a multidrop connec-
The two interfaces can be configured inde- tion. A selection between SPA and IEC
pendent of each other, each with different 60870-5-103 is made in software at setting of
the terminal.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 40

6HULDOFRPPXQLFDWLRQSURWRFROVSRVVLEOHFRPELQDWLRQVRILQWHUIDFHDQGFRQQHFWRUV
Alt 1 Alt 2 Alt 3
X13 SPA/IEC fibre optic SPA/IEC RS485 SPA fibre optic
X15 LON fibre optic LON fibre optic IEC fibre optic

6HULDOFRPPXQLFDWLRQ63$ )XQFWLRQDOLW\
As an alternative to the SPA communication
$SSOLFDWLRQ the same port can be used for the IEC com-
This communication bus is mainly used for munication.
SMS. It can include different numerical
relays/terminals with remote communication The IEC protocol may be used alternatively
possibilities. Connection to a personal com- on a fibre optic or on an RS485 network. The
puter (PC) can be made directly (if the PC is fibre optic network is point to point only,
located in the substation) or by telephone while the RS485 network may be used by
modem through a telephone network with multiple terminals in a multidrop configura-
CCITT characteristics. tion.

)XQFWLRQDOLW\ The IEC 60870-5-103 protocol implementa-


When communicating with a PC, using the tion in REx 5xx consists of these functions:
rear SPA port, the only hardware needed for a
station monitoring system is: • Event handling
• Report of analog service values (measure-
• Optical fibres ments)
• Opto/electrical converter for the PC • Fault location
• PC • Command handling
-Autorecloser ON/OFF
or
-Teleprotection ON/OFF
• A RS485 network installation according -Protection ON/OFF
to EIA Standard RS485 -LED reset
• PC -Characteristics 1 - 4 (Setting groups)
• File transfer (disturbance files)
Remote communication over the telephone
network also requires a telephone modem. • Time synchronization

The software needed in the PC, either local or The events created in the terminal available
remote, is CAP 540. for the IEC protocol are based on the event
function blocks EV01 - EV06 and distur-
SPA communication is applied when using bance function blocks DRP1 - DRP3. The
the front communication port, but for this commands are represented in a dedicated
purpose, no special serial communication function block ICOM. This block has output
function is required in the terminal. Only the signals according to the IEC protocol for all
software in the PC and a special cable for commands.
front connection is needed.
6HULDOFRPPXQLFDWLRQ/21
6HULDOFRPPXQLFDWLRQ,(&
,(&SURWRFRO $SSOLFDWLRQ
An optical network can be used within the
$SSOLFDWLRQ Substation Automation system. This enables
This communication protocol is mainly used communication with the terminal through the
when a protection terminal communicates LON bus from the operator’s workplace,
with a third party control system. This system from the control center and also from other
must have a program that can interpret the terminals.
IEC 60870-5-103 communication messages.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 41

)XQFWLRQDOLW\ The type of connection is chosen when order-


An optical serial interface with LON protocol ing the terminal.
enables the terminal to be part of a Substation
Control System (SCS) and/or Substation )XQFWLRQDOLW\/21
Monitoring System (SMS). This interface is The serial communication module for LON is
located at the rear of the terminal. The hard- placed in a slot at the rear part of the Main
ware needed for applying LON communica- processing module. The serial communica-
tion depends on the application, but one very tion module can have connectors for:
central unit needed is the LON Star Coupler
and optic fibres connecting the star coupler to • two plastic fibre cables; (Rx, Tx)
the terminals. To communicate with the ter- • two glass fibre cables; (Rx, Tx)
minals from a Personal Computer (PC), the
SMS 510, software or/and the application The type of connection is chosen when order-
library LIB 520 together with MicroSCADA ing the terminal.
is needed.

6HULDOFRPPXQLFDWLRQ
PRGXOHV 6&0 )URQWFRPPXQLFDWLRQ
)XQFWLRQDOLW\63$,(& $SSOLFDWLRQ
The serial communication module for SPA/ The special front connection cable is used to
IEC is placed in a slot at the rear part of the connect a PC COM-port to to the optical con-
main processing module. The serial commu- tact on the left side of the local HMI.
nication module can have connectors for:
)XQFWLRQDOLW\
• two plastic fibre cables; (Rx, Tx) The cable includes an optical contact, an
• two glass fibre cables; (Rx, Tx) opto/electrical converter and an electrical
cable with a standard 9-pole D-sub contact.
• galvanic RS485 This ensures a disturbance immune and safe
communication with the terminal.

xx01000039

Figure 20:Front connection cable


3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 42

+DUGZDUH 0RGXOHV
PRGXOHV
7DEOH %DVLFDOZD\VLQFOXGHGPRGXOHV
0RGXOH 'HVFULSWLRQ
Backplane module (BPM) Carries all internal signals between modules in
a terminal. The size of the module depends on
the size of the case.
Main processing module (MPM) Module for overall application control. All infor-
mation is processed or passed through this
module, such as configuration, settings and
communication. Carries up to 12 digital signal
processors, performing all measuring functions.
Human machine interface (LCD-HMI) The module consist of LED:s, a LCD, push but-
tons and an optical connector for a front con-
nected PC

7DEOH $SSOLFDWLRQVSHFLILFPRGXOHV
0RGXOH 'HVFULSWLRQ
Milliampere input module (MIM) Analog input module with 6 independent, gal-
vanically separated channels.
Binary input module (BIM) Module with 16 optically isolated binary inputs
Binary output module (BOM) Module with 24 single outputs or 12 double-pole
command outputs including supervision func-
tion
Binary I/O module (IOM) Module with 8 optically isolated binary inputs,
10 outputs and 2 fast signalling outputs.
Data communication modules (DCMs) Modules used for digital communication to
remote terminal.
Transformer input module (TRM) Used for galvanic separation of voltage and/or
current process signals and the internal cir-
cuitry.
A/D conversion module (ADM) Used for analog to digital conversion of analog
process signals galvanically separated by the
TRM.
Serial communication module (SCM) Used for SPA/LON/IEC communication
LED module (LED-HMI) Module with 18 user configurable LEDs for indi-
cation purposes

3RZHUVXSSO\PRGXOH 360 )XQFWLRQDOLW\


The power supply modules contain a built-in,
$SSOLFDWLRQ self-regulated DC/DC converter that provides
The power supply module, PSM, with built in full isolation between the terminal and the
binary I/O is used in 1/2 and 3/4 of full width battery system.
19” units. It has four optically isolated binary
inputs and five binary outputs, out of which $'PRGXOH $'0
one binary output is dedicated for internal
fail. )XQFWLRQDOLW\
The inputs of the A/D-conversion module
(ADM) are fed with voltage and current sig-
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 43

nals from the transformer module. The cur- %LQDU\,2FDSDELOLWLHV


rent signals are adapted to the electronic
voltage level with shunts. To gain dynamic $SSOLFDWLRQ
range for the current inputs, two shunts with Input channels with high EMI immunity can
separate A/D channels are used for each input be used as binary input signals to any func-
current. By that a 16-bit dynamic range is tion. Signals can also be used in disturbance
obtained with a 12 bits A/D converter. or event recording. This enables extensive
monitoring and evaluation of the operation of
The input signals passes an anti aliasing filter the terminal and associated electrical circuits.
with a cut-off frequency of 500 Hz.
)XQFWLRQDOLW\
Each input signal (5 voltages and 5 currents) Inputs are designed to allow oxide burn-off
is sampled with a sampling frequency of from connected contacts, and increase the
2 kHz. disturbance immunity during normal protec-
tion operate times. This is achieved with a
The A/D-converted signals are low-pass fil- high peak inrush current while having a low
tered with a cut-off frequency of 250 Hz and steady-state current. Inputs are debounced by
down-sampled to 1 kHz in a digital signal software.
processor (DSP) before transmitted to the
main processing module. Well defined input high and input low volt-
ages ensures normal operation at battery sup-
ply earth faults.
7UDQVIRUPHUPRGXOH 750
The voltage level of the inputs is selected
)XQFWLRQDOLW\
A transformer input module can have up to when ordering.
10 input transformers. The actual number
I/O events are time stamped locally on each
depends on the type of terminal. Terminals
including only current measuring functions module for minimum time deviance and
stored by the event recorder if present.
only have current inputs. Fully equipped the
transformer module consists of:
%LQDU\LQSXWPRGXOH %,0
• Five voltage transformers
• Five current transformers $SSOLFDWLRQ
Use the binary input module, BIM, when a
The inputs are mainly used for: large amount of inputs are needed. The BIM
is available in two versions, one standard and
• Phase currents one with enhanced pulse counting inputs to
be used with the pulse counter function.
• Residual current of the protected line
• Residual current of the parallel circuit (if )XQFWLRQDOLW\
any) for compensation of the effect of the The binary input module, BIM, has 16 opti-
zero sequence mutual impedance on the cally isolated binary inputs.
fault locator measurement or residual cur-
rent of the protected line but from a paral- A signal discriminator detects and blocks
lel core used for CT circuit supervision oscillating signals. When blocked, a hystere-
function or independent earth fault func- sis function may be set to release the input at
tion. a chosen frequency, making it possible to use
• Phase voltages the input for pulse counting. The blocking
frequency may also be set.
• Open delta voltage for the protected line
(for an optional directional earth-fault
protection) %LQDU\RXWSXWPRGXOH %20
• Phase voltage for an optional synchro-
nism and energizing check. $SSOLFDWLRQ
Use the binary output module, BOM, for trip
output or any signalling purpose when a large
amount of outputs is needed.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 44

)XQFWLRQDOLW\ connected in parallel to the standard output


The binary output module, BOM, has 24 soft- relay.
ware supervised output relays, pairwise con-
nected to be used as single-output channels 1RWH7KHPDNLQJFDSDFLW\RIWKHUHHGUHOD\V
with a common connection or as command DUHOLPLWHG
output channels.
P$LQSXWPRGXOH 0,0
$SSOLFDWLRQ
Use the milliampere input module, MIM, to
5
1 interface transducer signals in the +/-20 mA
range from for example temperature and pres-
sure transducers.
5
2 )XQFWLRQDOLW\
The milliampere input module has six input
channels, each with a separate protection and
filter circuit, A/D converter and optically iso-
3 lated connection to the backplane.

The digital filter circuits have individually


xx00000299.vsd
programmable cut-off frequencies, and all
parameters for filtering and calibration are
stored in a nonvolatile memory on the mod-
1 Output connection from relay 1
ule. The calibration circuitry monitors the
2 Common input connection module temperature and commences an auto-
3 Output connection from relay 2 matical calibration procedure if the tempera-
ture drift increase outside the allowed range.
Figure 21:Relay pair example The module uses the serial CAN bus for
backplane communication.
%LQDU\LQSXWRXWSXWPRGXOH
Signal events are time stamped locally for
,20 minimum time deviance and stored by the
event recorder if present.
$SSOLFDWLRQ
Use the binary I/O module, IOM, when few
input and output channels are needed. The ten +XPDQPDFKLQHLQWHUIDFH
output channels are used for trip output or PRGXOH /&'+0,
any signalling purpose. The two high speed
signal output channels are used for applica- $SSOLFDWLRQ
tions where short operating time is essential. The human machine interface is used to mon-
itor and in certain aspects affect the way the
)XQFWLRQDOLW\ product operates. The configuration designer
The binary I/O module, IOM, has eight opti- can add functions for alerting in case of
cally isolated inputs and ten output relays. important events that needs special attention
One of the outputs has a change-over contact. from you as an operator.
The nine remaining output contacts are con-
nected in two groups. One group has five Use the terminals built-in communication
contacts with a common and the other group functionality to establish SMS communica-
has four contacts with a common, to be used tion with a PC with suitable software tool.
as single-output channels. Connect the PC to the optical connector on
the local HMI with the special front commu-
The binary I/O module also has two high nication cable including an opto-electrical
speed output channels where a reed relay is converter for disturbance free and safe com-
munication.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 45

'HVLJQ

5HDG\ 6WDUW 7ULS


5(/9HU
& 4XLW 2
( (QWHUPHQX

C
3
5
E

1. Status indication LEDs


2. LCD display
3. &DQFHO and (QWHU buttons
4. Navigation buttons
5. Optical connector

Figure 22:The LCD-HMI module

The number of buttons used on the HMI tion and control and consists totally of 18
module is reduced to a minimum to allow a LEDs (Light Emitting Diodes). The main
communication as simple as possible for the purpose is to present on site an immediate
user. The buttons normally have more than visual information such as protection indica-
one function, depending on actual dialogue. tions or alarm signals. It is located on the
front of the protection and control terminals.
/(',QGLFDWLRQPRGXOH )XQFWLRQDOLW\
/('+0, The 18 LED indication module is equipped
with 18 LEDs, which can light or flash in
$SSOLFDWLRQ either red, yellow or green color. A descrip-
The LED indication module is an additional tion text can be added for each of the LEDs.
feature for the REx 5xx terminals for protec-
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 46

xx00000406.vsd

1 Three-color LEDs
2 Descriptive label, user exchangeable

Figure 23:The 18 LED indication module (LED-HMI)

The information on the LEDs is stored at loss different sequences; two as follow type and
of the auxiliary power for the terminal, so that four as latch type. Two of the latching types
the latest LED picture appears immediately are intended to be used as a protection indica-
after the terminal has restarted succesfully. tion system, either in collecting or re-starting
mode, with reset functionality. The other two
/('LQGLFDWLRQIXQFWLRQ +/+/(' are intended to be used as a signaling system
Each LED indication on the HMI LED mod- in collecting mode with an acknowledgment
ule can be set individually to operate in six functionality.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 47

+DUGZDUHGHVLJQ /D\RXWVDQGGLPHQVLRQV
'HVLJQ

'LPHQVLRQVFDVHZLWKRXWUHDUFRYHU

E K

D
F
A

C
B
G J
xx02000646.vsd
H
Figure 24:Case without rear cover
xx02000647.vsd

Figure 25:Case without rear cover with 19” rack


mounting kit

&DVHVL]H $ % & ' ( ) * + - .


6U, 1/2 x 19” 223.7 205.7 203.7 - -
6U, 3/4 x 19” 265.9 336 204.1 252.9 318 190.5 316 - 186.6 -
6U, 1/1 x 19” 448.3 430.3 428.3 465.1 482.6

(mm)

The H and K dimensions are defined by the 19” rack mounting kit
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 48

'LPHQVLRQVFDVHZLWKUHDUFRYHU

F
K

E
G
A

C
B D J
H
xx02000648.vsd I
xx02000649.vsd

Figure 26:Case with rear cover Figure 27:Case with rear cover and 19” rack
mounting kit

xx02000650.vsd

Figure 28:Case with rear cover

&DVHVL]H $ % & ' ( ) * + , - .


6U, 1/2 x 19” 223.7 205.7 203.7 - -
6U, 3/4 x 19” 265.9 336 204.1 245.1 255.8 318 190.5 316 - 227.6 -
6U, 1/1 x 19” 448.3 430.3 428.3 465.1 482.6
(mm)

The I and K dimensions are defined by the 19” rack mounting kit.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 49

3DQHOFXWRXWVIRU5([VHULHVVLQJOHFDVH
Flush mounting Semi-flush mounting

C
A

G
E F

D
xx02000666.vsd

xx02000665.vsd

&XWRXWGLPHQVLRQV PP

$ %
&DVHVL]H
6U, 1/2 x 19” 210.1 254.3
6U, 3/4 x 19” 322.4 254.3
6U, 1/1 x 19” 434.7 254.3

C = 4-10 mm
D = 16.5 mm
E = 187.6 mm without rear protection cover, 228.6 mm with rear protection cover
F = 106.5 mm
G = 97.6 mm without rear protection cover, 138.6 mm with rear protection cover
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 50

3DQHOFXWRXWIRU5([VHULHVVLGHE\VLGHFDVHV

D
B
E

F
C
xx02000651.vsd

19"

xx02000652.vsd

Figure 29:Flush mounting of side by side cases

&DVHVL]H &XWRXWGLPHQVLRQV
$ % & ' ( ) *
6U, 3/4 x 19” 326.4 259.3 352.8 190.5 34.4 13.2 ø 6.4
6U, 1/1 x 19” 438.7 259.3 465.1 190.5 34.4 13.2 ø 6.4
(mm)
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 51

'LPHQVLRQVZDOOPRXQWLQJ

80

xx02000653.vsd

B Screws M6 or
E corresponding

C
D

en02000654.vsd

Figure 30:Wall mounting

&DVHVL]H PP $ % & ' (


6U, 1/2 x 19” 292 267.1
6U, 3/4 x 19” 404.3 379.4 272.8 390 247
6U, 1/1 x 19” 516 491.1
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 52

7HUPLQDOGLDJUDP 'UDZLQJV

en03000144.eps

Figure 31:Hardware structure of the 3/4 of full width 19” case

en03000143.eps

Figure 32:Hardware structure of the 1/2 of full width 19” case


3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 53

L1
L2
L3
(MPM) (TRM)
X13:TX SPA / X11:
IEC-870-5-103 (ADM)
1) X13:RX 1
TX OPTION
∩ I1 4
2) HMI HMI
RX 2
X15:TX I2
3) X15:RX LON OPTION 5
3
(PSM) I3 6
X18: INTERNAL 8
INTERNAL 16 FAIL
FAIL I4 7
X18:
15 9
+
I5 10 4)
X12:
1
501.24 U1 2
501.22 6
U2 7
501

12 22 8
14 24 U3 9
X18: 10
11 21 17
+ 5
EL 13 23 4
18
- 3
12
7) 1) COMMUNICATION PORT SPA/IEC 870-5-103
U4 14 5)
2) OPTICAL PORT ON LOCAL HMI.
CONNECTION MADE WITH THE FRONT 16
CONNECTION CABLE FOR PC. U5 6)
18
3) COMMUNICATION PORT LON
4) RESERVED FOR PARALLEL LINE
COMPENSATION OR CTSU ALT WEF 1 and 2
WHEN Ir = 0,1A OR 0,5 A IS SELECTED ON TRM
5) RESERVED FOR DIRECTIONAL EARTH-
FAULT FUNCTION
6) RESERVED FOR REF.VOLTAGE
7) OPTIONAL ON/OFF SWITCH FOR THE DC-
SUPPLY.

xx00000438.vsd

7HFKQLFDOGDWD *HQHUDO
'HILQLWLRQV

5HIHUHQFHYDOXH

The specified value of an influencing factor to which are referred the characteristics of the
equipment.
1RPLQDOUDQJH

The range of values of an influencing quantity (factor) whithin which, under specified condi-
tions, the equipment meets the specified requirements.
2SHUDWLYHUDQJH

The range of values of a given energizing quantity for which the equipment, under specified
conditions, is able to perform its intended functions according to the specified requirements.
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 54

7DEOH &DVH
Material Steel sheet
Front plate Steel sheet profile with cut-out for HMI and for 18 LED when included
Surface treatment Aluzink preplated steel
Finish Light beige (NCS 1704-Y15R)
Degree of protection Front side: IP40, optional IP54 with sealing strip. Rear side: IP20

7DEOH :HLJKW
&DVHVL]H :HLJKW
6U, 1/2 x 19” ≤ 8.5 kg
6U, 3/4 x 19” ≤ 11 kg

7DEOH 3603RZHU6XSSO\0RGXOH
4XDQWLW\ 5DWHGYDOXH 1RPLQDOUDQJH
Auxiliary dc voltage EL = (48 - 250) V +/- 20%

7DEOH 750(QHUJL]LQJTXDQWLWLHVUDWHGYDOXHVDQGOLPLWV
4XDQWLW\ 5DWHGYDOXH 1RPLQDOUDQJH
Current Ir = 1 or 5 A (0.2-30) × Ir

Ir=0.1, 0.5, 1 or 5 A for I5


Operative range (0.004-100) x Ir
Permissive overload 4 × Ir cont.

100 × Ir for 1 s *)
Burden < 0.25 VA at Ir = 1 or 5 A

< 0.02 Va at Ir = 0.1 or 0.5 A


Ac voltage for the terminal Ur = 110 V **) 100/110/115/120 V

Ur = 220 V **) 200/220/230/240 V


Operative range (0.001-1.5) x Ur
Permissive overload 2.3 × Ur phase-earth, cont.

3.0 x Ur phase-earth, for 1 s


Burden < 0.2 VA at Ur
Frequency fr = 50/60 Hz +/-10%
*)
max. 350 A for 1 s when COMBITEST test switch is included.
**) The rated voltage of each individual voltage input U1 to U5 is Ur/√3

7DEOH 7HPSHUDWXUHDQGKXPLGLW\LQIOXHQFH
3DUDPHWHU 5HIHUHQFHYDOXH 1RPLQDOUDQJH ,QIOXHQFH
Ambient temperature +20 °C -10 °C to +55 °C 0.01% / °C

Operative range -25 °C to +55°C


Relative humidity 10%-90% 10%-90% -

Operative range 0%-95%


Storage temperature -40 °C to +70 °C - -
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 55

7DEOH $X[LOLDU\'&VXSSO\YROWDJHLQIOXHQFHRQIXQFWLRQDOLW\GXULQJ
RSHUDWLRQ
'HSHQGHQFHRQ :LWKLQQRPLQDOUDQJH ,QIOXHQFH
Ripple, in DC auxiliary voltage Max 12% 0.01% / %
Interrupted auxiliary DC voltage 48-250 V dc ±20%
Without reset <50 ms
Correct function 0-∞ s
Restart time <180 s

7DEOH )UHTXHQF\LQIOXHQFH
'HSHQGHQFHRQ :LWKLQQRPLQDOUDQJH ,QIOXHQFH
Frequency dependence fr ±10% for 50 Hz ±2.0% / Hz

fr ±10% for 60 Hz
Harmonic frequency dependence 2nd, 3rd and 5th harmonic of fr ±6.0%
(10% content)

7DEOH (OHFWURPDJQHWLFFRPSDWLELOLW\
7HVW 7\SHWHVWYDOXHV 5HIHUHQFHVWDQGDUGV
1 MHz burst disturbance 2.5 kV IEC 60255-22-1, Class III
For short range galvanic modem 2.5kV IEC 60255-22-1, Class III
For galvanic interface
• common mode 1 kV IEC 60255-22-1, Class II
• differential mode 0.5 kV IEC 60255-22-1, Class II
Electrostatic discharge
Direct application Air 8 kV IEC 60255-22-2, Class III

Contact 6 kV
For short range galvanic modem Air 8 kV IEC 60255-22-2, Class III
Contact 6 kV
Fast transient disturbance 4 kV IEC 60255-22-4, Class A
For short range galvanic modem 4 kV IEC 60255-22-4, Class A
For galvanic interface 1 kV IEC 60255-22-4, Class B
Surge immunity test 1-2 kV, 1.2/50µs IEC 60255-22-5

high energy
Power frequency immunity test 150-300 V, IEC 60255-22-7, Class A

50 Hz
Power frequency magnetic field test 1000 A/m, 3s IEC 61000-4-8, Class V
Radiated electromagnetic field distur- 10 V/m, IEC 60255-22-3
bance 80-1000 MHz
Radiated electromagnetic field distur- 10 V/m, IEC 61000-4-3, Class III
bance 80-1000 MHz,
1.4-2.0 GHz
Radiated electromagnetic field distur- 35 V/m IEEE/ANSI C37.90.2
bance
26-1000 MHz
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 56

7HVW 7\SHWHVWYDOXHV 5HIHUHQFHVWDQGDUGV


Conducted electromagnetic field dis- 10 V, 0.15-80 MHz IEC 60255-22-6
turbance
Radiated emission 30-1000 MHz IEC 60255-25
Conducted emission 0.15-30 MHz IEC 60255-25

7DEOH ,QVXODWLRQ
7HVW 7\SHWHVWYDOXHV 5HIHUHQFHVWDQGDUG
Dielectric test 2.0 kVAC, 1 min. IEC 60255-5
Impulse voltage test 5 kV, 1.2/50 µs, 0.5 J
Insulation resistance >100 MΩ at 500 VDC

7DEOH &(FRPSOLDQFH
7HVW $FFRUGLQJWR
Immunity EN 61000-6-2
Emissivity EN 61000-6-4
Low voltage directive EN 50178

7DEOH 0HFKDQLFDOWHVWV
7HVW 7\SHWHVWYDOXHV 5HIHUHQFHVWDQGDUGV
Vibration Class I IEC 60255-21-1
Shock and bump Class I IEC 60255-21-2
Seismic Class I IEC 60255-21-3

7DEOH &DOHQGDUDQGFORFN
3DUDPHWHU 5DQJH
Built-in calender With leap years through 2098

7DEOH ,QWHUQDOHYHQWOLVW
'DWD 9DOXH
Recording manner Continuous, event con-
trolled
List size 40 events, first in-first out
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 57

7DEOH 7,0(7LPHV\QFKURQLVDWLRQ
)XQFWLRQ $FFXUDF\
Time tagging resolution 1 ms
Time tagging error with synchronisation once/60 s ± 1.5 ms
Time tagging error without synchronisation ± 3 ms/min

7DEOH 606FRPPXQLFDWLRQYLDIURQW
)XQFWLRQ 9DOXH
Protocol SPA
Communication speed for the terminals 300, 1200, 2400, 4800, 9600 Bd
Slave number 1 to 899
Change of active group allowed Yes
Change of settings allowed Yes

7DEOH )URQWFRQQHFWLRQFDEOH
)XQFWLRQ 9DOXH
Communication speed for the cable 0.3-115 Kbaud

7DEOH &/&RQILJXUDEOHEORFNVDVEDVLF
8SGDWHUDWH %ORFN $YDLODELOLW\
10 ms AND 30 gates
OR 60 gates
INV 20 inverters
SM 20 flip-flops
GT 5 gates
TS 5 timers

200 ms SR 5 flip-flops
XOR 39 gates

7DEOH $YDLODEOHWLPHUIXQFWLRQEORFNVDVEDVLF
%ORFN $YDLODELOLW\ 6HWWLQJUDQJH $FFXUDF\
TM 10 timers 0.000-60.000 s in ± 0.5% ± 10 ms
steps of 1 ms
TP 10 pulse timers 0.000-60.000 s in ± 0.5% ± 10 ms
steps of 1 ms
TL 10 timers 0.0-90000.0 s in ± 0.5% ± 10 ms
steps of 0.1 s
TQ 10 puls timers 0.0-90000.0 s in ± 0.5% ± 10 ms
steps of 0.1 s
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 58

7DEOH &/$GGLWLRQDOFRQILJXUDEOHORJLFEORFNV
8SGDWHUDWH %ORFN $YDLODELOLW\
200 ms AND 239 gates
OR 159 gates
INV 59 inverters
MOF 3 registers
MOL 3 registers

7DEOH $GGLWLRQDOWLPHUIXQFWLRQEORFNV
%ORFN $YDLODELOLW\ 6HWWLQJUDQJH $FFXUDF\
TP 40 pulse timers 0.000-60.000 s in ± 0.5% ± 10 ms
steps of 1 ms

/LQHGLVWDQFH

7DEOH *)&*HQHUDOIDXOWFULWHULDLPSHGDQFHDQGFXUUHQWEDVHG
)XQFWLRQ 9DOXH
Impedance setting Reactive reach Positive-sequence reac- 0.1-400 ohm/phase in
range at Ir = 1A forward tance steps of 0.01 ohm/phase
Zero-sequence reac- 0.1-1200 ohm/phase in
tance steps of 0.01 ohm /phase
Reactive reach Positive-sequence reac- 0.1-400 ohm/phase in
reverse tance steps of 0.01 ohm/phase
Zero-sequence reac- 0.1-1200 ohm/phase in
tance steps of 0.01 ohm /phase
Resistive reach For phase - phase faults 0.1-400 ohm/loop in steps
(forward & of 0.01 ohm/loop
reverse) For phase - earth faults 0.1-400 ohm/loop in steps
of 0.01 ohm/loop
Load encroachment 0.1-400 ohm/loop in steps
of 0.01 ohm/loop
Safety load impedance 5-45 degrees in steps of 1
angle degrees
Overcurrent set- Phase currents 10-400% of I1b in steps
ting range of 1%
Residual current 10-150% of I4b in steps
of 1%
Timers For phase-to-phase measuring elements 0.000-60.000 s in steps of
1 ms
For phase-to-earth measuring elements 0.000-60.000 s in steps of
1 ms
Static angular Voltage range (0.1-1.1) x Ur +/-5 degrees
accuracy at 0 Current range (0.5-30) x Ir
degrees and 85
degrees
Reset ratio 105% typically
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 59

7DEOH *)&SSO]L3KDVHSUHIHUHQFHORJLF
3DUDPHWHU 6HWWLQJUDQJH
Operate residual current, IN> 20-200% of I4b in steps of 1%
Operate residual voltage, 3U0> 30-70% of U1b in steps of 1%
Voltage phase Phase to phase, UPP< 20-170% of U1b in steps of 1%
selection Phase to earth, UPN< 10-100% of U1b in steps of 1%
Cyclic tripping phase preference L1L3L2, L3L1L2
Non-cyclic tripping phase preference L1L3L2, L1L2L3, L3L2L1,
L3L1L2, L2L1L3, L2L3L1
Non-cyclic blocking phase preference L1L3L2, L1L2L3, L3L2L1,
L3L1L2, L2L1L3, L2L3L1

7DEOH =0=RQHLPSHGDQFHPHDVXULQJHOHPHQWV
)XQFWLRQ 9DOXH
Operate time Typical 28 ms
Min and max Please refer to the separate isoch-
rone diagrams
Min. operate current (10-30) % of I1b in steps of 1 %
Resetting ratio Typical 110 %
Resetting time Typical 40 ms
Output signals start and trip Zone 1-3 Three phase

Single phase and/or three phase


Zone 4, 5 Three phase start and trip

Setting accuracy Included in the measuring accuracy


Number of zones 3, 4 or 5, direction selectable
Impedance set- Reactive Positive-sequence (0.10-400.00) Ω/phase in steps of
ting range at Ir = reach reactance 0.01 Ω
1 A (to be divided Zero sequence (0.10-1200.00) Ω/phase in steps of
by 5 at Ir = 5 A) reactance 0.01 Ω
Resistive Positive-sequence (0.10-400.00) Ω/phase in steps of
reach resistance 0.01 Ω
Zero sequence (0.10-1200.00) Ω/phase in steps of
resistance 0.01 Ω
Fault resis- For phase - phase (0.10-400.00) Ω/loop in steps of
tance faults 0.01 Ω
For phase-earth (0.10-400.00) Ω/loop in steps of
faults 0.01 Ω
Setting range of timers for impedance zones (0.000-60.000) s in steps of 1 ms
Static accuracy at Voltage range (0.1-1.1) x Ur +/- 5 %
0 degrees and 85 Current range (0.5-30) x Ir
degrees
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 60

)XQFWLRQ 9DOXH
Static angular Voltage range (0.1-1,1) x Ur +/- 5 degrees
accuracy at 0 Current range (0.5-30) x Ir
degrees and 85
degrees
Max dynamic overreach at 85 degrees measured with +5%
CVT’s 0.5 < SIR < 30

7DEOH 36'3RZHUVZLQJGHWHFWLRQ
3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\
Impedance setting range Reactive reach, 0.10-400.00 ohm/
at Ir =1A XIN phase in steps of 0.01
ohm/phase
(divide values by 5 for Ir =
5A) Resistive reach, 0.10-400.00 ohm/
RIN phase in steps
of 0.01ohm/phase
Reach multiplication factor, KX 120-200% of XIN in
steps of 1%
Reach multiplication factor, KR 120-200% of RIN in
steps of 1%
Initial PSD timer, tP1 0.000-60.000 s in +/- 0.5 % +/- 10 ms
steps of 1 ms
Fast PSD timer, tP2 0.000-60.000 s in +/- 0.5 % +/- 10 ms
steps of 1 ms
Hold timer tW for activation of fast PSD timer 0.000-60.000 s in +/- 0.5 % +/- 10 ms
steps of 1 ms
Hold timer tH for PSD detected 0.000-60.000 s in +/- 0.5 % +/- 10 ms
steps of 1 ms
Timer tEF overcoming 1ph reclosing dead 0.000-60.000 s in +/- 0.5 % +/- 10 ms
time steps of 1 ms
Timer tR1 to time delay block by the residual 0.000-60.000 s in +/- 0.5 % +/- 10 ms
current steps of 1 ms
Timer tR2 to time delay block at very slow 0.000-60.000 s in +/- 0.5 % +/- 10 ms
swings steps of 1 ms

7DEOH =&206FKHPHFRPPXQLFDWLRQORJLFIRUGLVWDQFHSURWHFWLRQ
3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\
Coordination timer, tCoord 0.000-60.000 s in steps of +/-0.5% +/-10ms
1 ms
Minimum send time, tSendMin 0.000-60.000 s in steps of +/-0.5% +/-10ms
1 ms
Security timer, tSec 0.000-60.000 s in steps of +/-0.5% +/-10ms
1 ms
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 61

7DEOH =&$/&XUUHQWUHYHUVDODQGZHDNHQGLQIHHGORJLF
3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\
Pickup time for current 0.000-60.000 s in steps of ±0.5% ±10ms
reversal, tPickUp 0.001s
Delay time for current 0.000-60.000 s in steps of ±0.5% ±10ms
reversal, tDelay 0.001s
Coordination time for weak 0.000-60.000 s in steps of ±0.5% ±10ms
end infeed logic, tWEI 0.001s
Detection level phase to 10-100% of U1b ±2.5% of Ur
neutral voltage, UPN<
Detection level phase to 20-170% of U1b ±2.5% of Ur at U≤Ur
phase voltage, UPP<
±2.5% of U at U>Ur

7DEOH 3$35DGLDOIHHGHUSURWHFWLRQIXQFWLRQ
3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\
Faulted phase voltage detection level in % of 50-100% of Uref in steps ±2.5% of Ur
cross-polarised phase-phase voltage divided of 1%
by sqrt(3)
Time constant for reference voltages 1-60s in steps of 1s
Residual current detection level 10-150% of I1b in steps ±2.5% of Ir at I ≤ Ir
of 1%
±2.5% of I at I > Ir
Time delay tM for single-pole tripping 0.000-60.000s in steps ±0.5% ±10 ms
of 0.01s
Time delay tT for three-pole tripping 0.000-60.000s in steps ±0.5% ±10 ms
of 0.01s
Time delay tPIR for residual current tripping 0.000-60.000s in steps ±0.5% ±10 ms
(or indication) of 0.01s

7DEOH 627)$XWRPDWLFVZLWFKRQWRIDXOWIXQFWLRQ
3DUDPHWHU 9DOXH $FFXUDF\
Delay following dead line detection input 200 ms +/-0.5% +/-10 ms
before SOTF function is automatically enabled
Time period after circuit breaker closure in 1000 ms +/-0.5% +/-10 ms
which SOTF function is active
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 62

&XUUHQW

7DEOH ,2&,QVWDQWDQHRXVRYHUFXUUHQWSURWHFWLRQ
)XQFWLRQ 6HWWLQJUDQJH 2SHUDWH $FFXUDF\
WLPH
Operate cur- Phase measur- (50-2000)% of - ± 2.5 % of Ir at I ≤Ir
rent I>> ing elements I1b In steps of
± 2.5 % of I at I > Ir
1%
-
Residual measur- (50-2000)% of ± 2.5 % of Ir at I ≤ Ir
ing elements I1b In steps of
± 2.5 % of I at I > Ir
1%
Maximum operate time at I > 10 × Iset Max. 15ms -
Dynamic overreach at τ< 100 ms - < 5%

7DEOH 72&'HILQLWHWLPHQRQGLUHFWLRQDORYHUFXUUHQWSURWHFWLRQ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Operate current Phase measuring ele- (10-400) % of I1b ± 2.5 % of Ir at I ≤ Ir
ments, IP> in steps of 1 % ± 2.5 % of I at I >Ir
Residual measuring (10-150) % of I4b ± 2.5 % of Ir at I ≤ Ir
elements, IN> in steps of 1 % ± 2.5 % of I at I >Ir
Time delay Phase measuring ele- (0.000-60.000) s in ± 0.5 % of t ± 10 ms
ments steps of 1 ms
Residual measuring (0.000-60.000) s in ± 0.5 % of t ± 10 ms
elements steps of 1 ms
Dynamic overreach at τ< 100 ms - <5%

7DEOH 72&7ZRVWHSWLPHGHOD\HGQRQGLUHFWLRQDOSKDVHRYHUFXUUHQW
SURWHFWLRQ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Operate value for low set (5-500)% of I1b in steps of +/- 2.5% of I1r at
function 1%
I ≤ I1r
I > Low
+/- 2.5 % of I at I>I1r
Base current for inverse time (5-500) % of I1b in steps of +/- 2.5 % of I1r at
calculation 1%
I ≤ I1r
I > Inv
+/- 2.5 % of I at I> I1r
Minimum operate time (0.000-60.000)s in steps of +/- 0.5 % +/- 10 ms
1 ms
tMinInv
Definite time delay for low set (0.000-60.000)s in steps of +/- 0.5 % +/- 10 ms
function 1 ms

tLow
Operate value of high set (50-2000)% of I1b in steps of +/- 2.5% of I1r at
function 1%
I ≤ I1r
I > High
+/- 2.5 % of I at I>I1r
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 63

)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\


Definite time delay for high (0.000-60.000) s in steps of +/- 0.5 % +/- 10 ms
set function 1 ms

tHigh
Normal inverse characteristic IEC 60255-3 class 5+/- 60 ms

I = Imeas/Iset
Very inverse characteristic IEC 60255-3 class 7.5+/- 60
13.5
t = ----------- ⋅ k ms
I–1
Extremely inverse character- IEC 60255-3 class 7.5+/- 60
istic ms

Dynamic overreach at τ< 100 ms <5%

7DEOH 72&7ZRVWHSWLPHGHOD\HGGLUHFWLRQDOSKDVHRYHUFXUUHQW
SURWHFWLRQ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Operate value of low set func- (20-2000)% of I1b in steps of 1% ± 2.5 % of Ir at I ≤ Ir
tion, I>Low
± 2.5 % of I at I>Ir
Base current for inverse time (20-500) % of I1b in steps of 1 % ± 2.5 % of Ir at I ≤ Ir
calculation, I>Inv
± 2.5 % of I at I>Ir
Resetting ratio - >95%
Minimum operate time, tMin- (0.000-60.000) s in steps of 1 ms ± 0.5 % ±10 ms
Inv
Definite time delay for low set (0.000-60.000) s in step of 1ms
function, tLow
± 0.5 % ±10 ms
Operate value of high set (20-2000) % of I1b in steps of 1 % ± 2.5 % of Ir at I ≤ Ir
function, I>High
± 2.5 % of I at I>Ir
Definite time delay for high set (0.000-60.000) in steps of 1 ms
function, tHigh
± 0.5 % ±10 ms
Static angular accuracy at 0 Voltage range (0.1-1.1) x Ur ± 5 degrees
degrees and 85 degrees Current range (0.5-30) x Ir
Normal inverse characteristic IEC 60255-3 class 5
+ 60 ms
I = Imeas/Iset

Very inverse characteristic IEC 60255-3 class 7.5


13.5 + 60 ms
I = Imeas/Iset t = ----------- ⋅ k
I–1
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 64

)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\


Extremely inverse characteris- IEC 60255-3 class 7.5
tic + 60 ms

I = Imeas/Iset
RI-inverse characteristic IEC 60256-3 class 5
1 + 60 ms
I = Imeas/Iset t = ------------------------------------ ⋅ k
0.236
0.339 – ---------------
I
Dynamic overreach at τ< 100 ms <5%

7DEOH 7()7LPHGHOD\HGQRQGLUHFWLRQDOUHVLGXDORYHUFXUUHQWSURWHFWLRQ
3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\
Start current, definite time or 5-300% of Ib in steps ± 5% of set value
inverse time delay, IN> of 1%
Operate value Forward IN 5-35% of Ib in steps ± 1.5% of Ir
for directional at ϕ=65 degrees of 1%
current mea- Reverse 60% of the setting for ± 1.5% of Ir
surement forward operation
Characteristic angles 65 degrees lagging ± 5 degrees at 20 V and
Iset=35% of Ir

Definite time delay 0.000 - 60.000 s in ± 0.5 % +/-10 ms


steps of 1ms
Time multiplier for inverse time 0.05-1.10 in steps of According to IEC 60255-3
delay 0.01

k
Normal inverse characteristic IEC 60255-3 class 5 ± 60 ms

I = Imeas/Iset
Very inverse characteristic 13.5 IEC 60255-3 class 7.5 ± 60 ms
t = ----------- ⋅ k
I–1

Extremely inverse characteristic IEC 60255-3 class 7.5 ± 60 ms

Logarithmic characteristic ± 5 % of t at I = (1.3-29) × IN


I
t = 5.8 – 1.35 ⋅ ln -----
IN
Min. operate current for depen- 100-400% of IN in ± 5% of Iset
dent characteristic, IMin steps of 1%
Minimum operate time for depen- 0.000-60.000 s in ± 0.5 % ± 10 ms
dent characteristic, tMin steps of 1 ms
Minimum polarising voltage 1 % of Ur At 50 Hz: 1% of Ur ± 5%

At 60 Hz: 1% of Ur -15% to -5%


Reset time <70 ms -
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 65

7DEOH ())RXUVWHSWLPHGHOD\HGGLUHFWLRQDOUHVLGXDORYHUFXUUHQW
SURWHFWLRQ
3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\
Current level for step 1, IN1> 50 - 2500% of Ib in ± 5 % of Ir at I≤Ir
steps of 1%
± 5% of I at I>Ir
Definite time delay for step 1, t1 0.000 - 60.000 s in ± 0.5 % ±10 ms
steps of 1ms
Current level for step 2, IN2> 20 - 1500 % of Ib in ± 5 % of Ir at I≤Ir
steps of 1%
± 5% of I at I>Ir
Definite time delay for step 2, t2 0.000 - 60.000 s in ± 0.5 % ± 10 ms
steps of 1 ms
Current level for step 3, IN3> 20 - 1500 % of Ib in ± 5 % of Ir at I≤Ir
steps of 1%
± 5% of I at I>Ir
Definite time delay for step 3, t3 0.000 - 60.000 s in +/- 0.5 % ± 10 ms
steps of 1 ms
Current level for step 4 definite time 4 - 440 % of Ib in steps ± 5 % of Ir at I≤Ir
delay or minimum operate current for of 0.1%
± 5% of I at I>Ir
inverse time delay, IN4>
Definite time delay for step 4 or inverse 0.000 - 60.000 s in ± 0.5 % ±10 ms
time additional delay, t4 steps of 1 ms
Base current for inverse time delay, 4 - 110% of Ib in steps ± 5 % of Ir at I≤Ir
IN>Inv of 0.1%
± 5% of I at I>Ir
Time multiplier for inverse time delay 0.05 - 1.10 in steps of -
0.01
Inverse time minimum delay step 4 0.000 - 60.000 s in ± 0.5 % ± 10 ms
steps of 1 ms
Operate value for Forward IN at ϕ= 5-40% of Ib in steps of ± 2.5 % of Ir at I≤Ir
directional current 65° 1%
± 2.5% of I at I>Ir
measurement
Reverse 60% of Forward ± 2.5 % of Ir at I≤Ir

± 2.5% of I at I>Ir
Level of harmonic restrain 20% or 32% ± 5%
Characteristic angle 65° lagging ± 5° at 20 V and Iset=
35 % of Ir
I = Imeas/Iset
Normal inverse characteristic IEC 60255-3 class 5
± 60 ms
I = Imeas/Iset
Very inverse characteristic 13.5 IEC 60255-3 class 7.5
t = ----------- ⋅ k ± 60 ms
I–1
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 66

3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\


Extremely inverse characteristic IEC 60255-3 class 7.5
± 60 ms

Logarithmic characteristic ± 5 % of t at I = (1.3-29)


I
t = 5.8 – 1.35 ⋅ ln ----- × IN
IN

Switch onto fault active time, t4U 0.000 - 60.000 s in ± 0.5 % ± 10 ms


steps of 1 ms

7DEOH :()6HQVLWLYHGLUHFWLRQDOUHVLGXDORYHUFXUUHQWSURWHFWLRQIXQFWLRQ
)XQFWLRQ 9DOXH $FFXUDF\
Operate current, IN> (3.0 - 2000.0 ) % of Ib in ± 2.5% of Ir at I ≤ Ir
steps of 0.1%
± 2.5% of I at I > Ir
Operate voltage, UN> (5.0 - 70.0) % of Ub in steps ± 2.5% of Ur at U ≤ Ur
of 0.1%
± 2.5% of U at U > Ur
Characteristic Angle (-90.0 to +90.0) degrees in
steps of 0.1 degrees
Definite time delay, tTrip (0.000 - 60.000) s in steps of ± 0.5% ± 10 ms
1 ms
Reset ratio > 90% typically

7DEOH :()6HQVLWLYHGLUHFWLRQDOUHVLGXDOSRZHUSURWHFWLRQIXQFWLRQ
)XQFWLRQ 9DOXH $FFXUDF\
Operate current, IN> (5.0 - 400.0) % of Ib in steps ± 2.5% of Ir at I ≤ Ir
of 0.1%
± 2.5% of I at I > Ir
Operate voltage, UN> (1.0-70.0) % of Ub in steps of ± 2.5% of Ur at U ≤ Ur
0.1%
± 2.5% of U at U > Ur
Characteristic angle (-90.0 to +90.0) degrees in
steps of 0.1 degrees
Definite time delay, tTrip (0.000-60.000) s in steps of 1 ± 0.5% ± 10 ms
ms
Inverse characteristic k = (0.0-2.0) in steps of 0.01 IEC 60255-3 class 5 ± 60 ms

S ref Sref = (5.0 - 50.0) % of Sb in


Ti = k steps of 0.1%
S measured

Reset ratio > 90% typically

7DEOH ()&6FKHPHFRPPXQLFDWLRQORJLFIRUUHVLGXDORYHUFXUUHQW
SURWHFWLRQ
3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\
Coordination timer 0.000-60.000 s in steps of 1 ± 0.5% ± 10 ms
ms
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 67

7DEOH ()&$&XUUHQWUHYHUVDODQGZHDNHQGLQIHHGORJLFIRUUHVLGXDO
RYHUFXUUHQWSURWHFWLRQ
3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\
Operate voltage for WEI trip, U> 5-70 % of U1b in steps of 1% ± 5% of set value
Current reversal pickup timer, 0.000-60.000 s in steps of 1 ms ± 0.5% ± 10 ms
tPickUp
Current reversal delay timer, tDelay 0.000-60.000 s in steps of 1 ms ± 0.5% ± 10 ms

7DEOH 7+2/7KHUPDOSKDVHRYHUORDGSURWHFWLRQ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Mode of operation Off / NonComp / Comp

( Function blocked/No temp.


compensation/Temp. comp.)
Base current

IBase (10 - 200 ) % of I1b in steps ± 2.5% of Ir


of 1 %
Temperature rise at IBase

TBase (0 - 100) °C in steps of 1° C ± 1°C


Time constant

tau (1 - 62) min in steps of 1 min ± 1 min


Alarm temperature

TAlarm (50 - 150) °C in steps of 1°C


Trip temperature

TTrip (50 - 150) °C in steps of 1 °C


Temp. difference for reset of
trip
(5 - 30) °C in steps of 1°C
TdReset

7DEOH 7KHUPDORYHUORDGSURWHFWLRQP$LQSXW
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Upper value for mA input

MI11-I_Max -25.00 - 25.00 mA in steps of ± 0.5% of set value


0.01 mA
Lower value for mA input +/- 0.5% of set value

MI11-I_Min -25.00 - 25.00 mA in steps of


0.01 mA
Temp. corresponding to the +/- 1% of set value +/- 1°C
MI11-I_Max setting
-1000 - 1000 °C in steps of 1
MI11-MaxValue °C
Temp. corresponding to the +/- 1% of set value +/- 1°C
MI11-I_Min setting
-1000 - 1000° C in steps of 1
MI11-MinValue °C
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 68

7DEOH %)3%UHDNHUIDLOXUHSURWHFWLRQ
3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\
Operate current, IP> (one 5-200% of I1b in steps of 1% ± 2.5% of Ir at I ≤ Ir
measuring element per ± 2.5% of I at I > Ir
phase)
Retrip time delay t1 0.000-60.000 s in steps of 1 ± 0.5% ± 10 ms
ms
Back-up trip time delay t2 0.000-60.000 s in steps of 1 ± 0.5% ± 10 ms
ms

3DUDPHWHU 9DOXH
Trip operate time Max 18 ms
Operate time for current detection Max 10 ms

9ROWDJH

7DEOH 7897LPHGHOD\HGXQGHUYROWDJHSURWHFWLRQ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Operate voltage, UPE< (10-100) % of U1b in steps of ± 2.5 % of Ur
1%
Time delay (0.000-60.000) s in steps of ± 0.5 % ±10 ms
1ms

7DEOH 7297LPHGHOD\HGRYHUYROWDJHSURWHFWLRQ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Operate voltage Phase measuring (50-170)% of U1b in steps ± 2.5 % of Ur at U ≤
U> elements of 1% Ur

± 2.5 % of U at U >
Ur
Time delay Phase measuring (0.000-60.000) s in steps ± 0.5 % ± 10 ms
elements of 1ms

Operate voltage Residual measur- (5-100)% of U1b in steps ± 2.5 % of Ur at U ≤


U> ing elements of 1% Ur

± 2.5 % of U at U >
Ur
Time delay Residual measur- (0.000-60.000) s in steps ± 0.5 % ± 10 ms
ing elements of 1ms
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 69

3RZHUV\VWHPVXSHUYLVLRQ

7DEOH %5&%URNHQFRQGXFWRUFKHFN
3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\
Minimum level of highest 10-100% of I1b in steps of 1% ± 2.5% of Ir
phase current for operation,
IP>
Output time delay, t 0.000-60.000 s in steps of ± 0.5% ± 10ms
0.001s

7DEOH /29/RVVRIYROWDJHFKHFN
3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\
Operate voltage, UPE< 10-100% of U1b in steps of ± 2.5% of Ur
1%

7DEOH 29/'2YHUORDGVXSHUYLVLRQIXQFWLRQ
3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\
Operate current, IP> 20-300% of I1b in steps of 1% ± 2.5% of Ir at I≤Ir
± 2.5% of I at I>Ir

Time delay, t 0.0-90000.0 s in steps of ± 0.5% ± 10 ms

0.1 s

7DEOH '/''HDGOLQHGHWHFWLRQ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Automatic check of dead Operate phase current, IP< (5-100) % of I1b in ± 2.5 % of Ir
line condition steps of 1%
Operate phase voltage, U< (10-100) % of U1b in ± 2.5 % of Ur
steps of 1%

6\VWHPSURWHFWLRQDQGFRQWURO

7DEOH 3633ROHVOLSSURWHFWLRQIXQFWLRQ
)XQFWLRQ 9DOXH
Reactive and resistive reach for all setting parameters 0.10-400.00 ohm/phase in
at Ir=1 A (for Ir = 5 A, divide values by 5) steps of 0.01ohm/phase
Timers 0.000-60.000s in steps of
0.001s
Counters 0-10 in steps of 1
Reset ratio 105% typically
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 70

7DEOH /$33/RZDFWLYHSRZHUSURWHFWLRQIXQFWLRQ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Power function P< (3.0 - 100.0) % of Sb in steps of 0.1 ± 5 % of Sr
%
Time delay ( 0.000 - 60.000 ) s in steps of 1 ms ± 0.5 % ± 10 ms
Minimum operating current for directional measurement: 5% of Ir
Minimum operating voltage for directional measurement: 10% of Ur

7DEOH /$53/RZDFWLYHDQGUHDFWLYHSRZHUSURWHFWLRQIXQFWLRQ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Power function Q< (3.0 - 100.0) % of Sb in steps of 0.1 % ± 5 % of Sr
Time delay (0.000 - 60.000) s in steps of 1 ms ± 0.5 % ± 10 ms
Minimum operating current for directional measurement: 5% of Ir
Minimum operating voltage for directional measurement: 10% of Ur

7DEOH +$33+LJKDFWLYHSRZHUSURWHFWLRQIXQFWLRQ
)XQFWLRQ 9DOXH $FFXUDF\
Power function P> (3.0 - 200.0) % of Sb in steps of 0.1 % ± 5 % of Sr
Time delay (0.000 - 60.000) s in steps of 1 ms ± 0.5 % ± 10 ms
Minimum operating current for directional measurement: 5% of Ir
Minimum operating voltage for directional measurement: 10% of Ur
Reset ratio > 90% typically

7DEOH +$53+LJKDFWLYHDQGUHDFWLYHSRZHUSURWHFWLRQIXQFWLRQ
)XQFWLRQ 9DOXH $FFXUDF\
Power function Q> (3.0 - 200.0) % of Sb in steps of 0.1 % ± 5 % of Sr
Time delay (0.000 - 60.000) s in steps of 1 ms ± 0.5 % ± 10 ms
Minimum operating current for directional measurement: 5% of Ir
Minimum operating voltage for directional measurement: 10% of Ur
Reset ratio > 90%

7DEOH 6&&6XGGHQFKDQJHLQSKDVHFXUUHQWIXQFWLRQ
3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\
Change in current per power system 20.0-100.0% of Ib in steps of ± 5.0 % of Ir
cycle, DIL> 0.1%
Time delay for start signal, tHStart 0.000-60.000 s in steps of ± 0.5 % ± 10 ms
1 ms
Time delay for trip signal, tHTrip 0.000-60.000 s in steps of ± 0.5 % ± 10 ms
1 ms
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 71

7DEOH 6&5&6XGGHQFKDQJHLQUHVLGXDOFXUUHQWSURWHFWLRQIXQFWLRQ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Change in residual current per 20.0-100.0% of Ib in steps of ± 5.0% of Ir
power system cycle, DIN> 0.1%
Time delay for start signal, tHStart 0.000-60.000 s in steps of 1 ms ± 0.5 % ± 10 ms
Time delay for trip signal, tHTrip 0.000-60.000 s in steps of 1 ms +± 0.5 % ± 10 ms

7DEOH 6&96XGGHQFKDQJHLQYROWDJHSURWHFWLRQIXQFWLRQ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Change in voltage per power system 5.0-100.0% of Ub in steps of ± 0.5 % of Ur
cycle, DUL> 0.1%
Time delay for start signal, tHStart 0.000-60.000 s in steps of 1 ms ± 0.5 % ± 10 ms
Time delay for trip signal, tHTrip 0.000-60.000 s in steps of 1 ms ± 0.5 % ± 10 ms

7DEOH 293$FFXUDWHRYHUYROWDJHSURWHFWLRQIXQFWLRQ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Low-set operating value, ULLow> 80.0-150.0% of Ub in ± 2.5 % of Ur
steps of 0.1%
High-set operating value, ULHigh> 80.0-150.0% of Ub in ± 2.5 % of Ur
steps of 0.1%
Time delayed operation of low-set step, tLow 0.000-60.000 s in ± 0.5 % ± 10 ms
steps of 1 ms
Time delayed operation of high-set step, 0.000-60.000 s in ± 0.5 % ± 10 ms
tHigh steps of 1 ms

7DEOH 8&38QGHUFXUUHQWSURWHFWLRQIXQFWLRQ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Low-set step of undercurrent limit, ILLow< 5.0-100.0% of Ib in ± 2.5 % of Ir
steps of 0.1%
High-set step of undercurrent limit, ILHigh< 5.0-100.0% of Ib in ± 2.5 % of Ir
steps of 0.1%
Time delayed operation of low-set step, tLow 0.000-60.000 s in steps ± 0.5 % ± 10 ms
of 1 ms
Time delayed operation of high-set step, 0.000-60.000 s in steps ± 0.5 % ± 10 ms
tHigh of 1 ms
Reset ratio > 106% typically

7DEOH 2&32YHUFXUUHQWSURWHFWLRQIXQFWLRQ
)XQFWLRQ 9DOXH $FFXUDF\
Low-set operating value, ILLow> 5.0-200.0% of Ib in steps of 0.1% ± 5.0 % of Ir
High-set operating value, ILHigh> 5.0-200.0% of Ib in steps of 0.1% ± 5.0 % of Ir
Time delay of low-set step, tLow 0.000-60.000 s in steps of 1 ms ± 0.5 % ± 10 ms
Time delay of high-set step, tHigh 0.000-60.000 s in steps of 1 ms ± 0.5 % ± 10 ms
Reset ratio > 94% typically
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 72

7DEOH 52&35HVLGXDORYHUFXUUHQWSURWHFWLRQIXQFWLRQ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Residual overcurrent low-set limit, 5.0-100.0% of Ib in steps ± 2.5 % of Ir
INLow> of 0.1%
Residual overcurrent high-set limit, 5.0-100.0% of Ib in steps ± 2.5 % of Ir
INHigh> of 0.1%
Time delayed operation of low-set step, 0.000-60.000 s in steps of ± 0.5 % ± 10 ms
tLow 1 ms
Time delayed operation of high-set step, 0.000-60.000 s in steps of ± 0.5 % ± 10 ms
tHigh 1 ms
Reset ratio > 95% typically

6HFRQGDU\V\VWHPVXSHUYLVLRQ

7DEOH &768&XUUHQWFLUFXLWVXSHUYLVLRQFXUUHQWEDVHG
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Operate current, IMinOp 5-100% of I1b in steps of 1% ± 2.5% of Ir

7DEOH )86(QV)XVHIDLOXUHVXSHUYLVLRQIXQFWLRQQHJDWLYHVHTXHQFH
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Negative-sequence Operate voltage (10 - 50)% of U1b in ± 2.5 % of Ur
quantities: 3U2> steps of 1%
Operate current (10 - 50)% of I1b in ± 2.5 % of Ir
3I2> steps of 1%

7DEOH )86(]V)XVHIDLOXUHVXSHUYLVLRQ]HURVHTXHQFH
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Zero-sequence Operate voltage (10-50)% of U1b in steps of ± 2.5 % of Ur
quantities: 3U0> 1%
Operate current (10-50)% of I1b in steps of 1% ± 2.5 % of Ir
3I0<

7DEOH )86(GE)XVHIDLOXUHVXSHUYLVLRQGXGWDQGGLGWEDVHG
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Operate voltage change level, DU> (50-90)% of U1b in steps of 1% ± 2.5% of Ur
Operate current change level, DI< (10-50)% of I1b in steps of 1% ± 2.5% of Ir

7DEOH 7&79ROWDJHWUDQVIRUPHUVXSHUYLVLRQ
3DUDPHWHU 6HWWLQJ $FFXUDF\
UDQJH
Residual overvoltage limit, UN> 1.0-80.0% of ± 2.5% of Ur
Ub in steps of
0.1%
Time delayed operation for start signal, tDelay 0.000- ± 0.5% ± 10 ms
300.000 s in
steps of 1 ms
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 73

&RQWURO

7DEOH 6<16\QFKURFKHFNZLWKV\QFKURQL]LQJDQGHQHUJL]LQJFKHFN
3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\
Frequency difference limit, 50-500 mHz in steps of 10 mHz ≤20 mHz
FreqDiffSynch

Breaker closing pulse duration,


0.000-60.000 s in steps of 1 ms ± 0.5% ± 10 ms
tPulse

Breaker closing time, tBreaker


0.02-0.50 s in steps of 0.01 s ± 0.5% ± 10 ms

3DUDPHWHU 9DOXH
Bus / line voltage frequency range limit ± 5 Hz from fr

Bus / line voltage frequency rate of change limit <0.21 Hz/s

7DEOH 6<16\QFKURFKHFNDQGHQHUJL]LQJFKHFN
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Synchrocheck:

Frequency difference limit, FreqDiff 50-300 mHz in steps of 10 mHz ≤20 mHz

Voltage difference limit, UDiff 5-50% of U1b in steps of 1% ± 2.5% of Ur

Phase difference limit, PhaseDiff 5-75 degrees in steps of ± 2 degrees


1 degree
Energizing check:

Voltage level high, UHigh 70-100% of U1b in steps of 1% ± 2.5% of Ur

Voltage level low, ULow 10-80% of U1b in steps of 1% ± 2.5% of Ur

Energizing period, automatic reclos- 0.000-60.000 s in steps of 1 ms ± 0.5% ± 10 ms


ing, tAutoEnerg

Energizing period, manual closing,


0.000-60.000 s in steps of 1 ms ± 0.5% ± 10 ms
tManEnerg
Phase shift ϕline - ϕbus 0-360 degrees in steps of
1 degree
Voltage ratio Ubus/Uline 0.20-5.00 in steps of 0.01

7DEOH 6\QFKURFKHFNDQGHQHUJL]LQJFKHFNJHQHUDO
3DUDPHWHU 9DOXH
Synchrocheck:

Bus voltage frequency range limit ± 5 Hz from fr

Operate time 190 ms typically

Energizing check:

Operate time 80 ms typically


3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 74

7DEOH $5$XWRUHFORVHU
3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\
Automatic reclosing open time:
shot 1 - t1 1ph 0.000-60.000 s in steps of ± 0.5% ± 10 ms
1 ms
shot 1 - t1 2ph 0.000-60.000 s in steps of ± 0.5% ± 10 ms
1 ms
shot 1 - t1 3ph 0.000-60.000 s in steps of ± 0.5% ± 10 ms
1 ms
shot 2 - t2 3ph 0.0-9000.0 s in steps of ± 0.5% ± 10 ms
0.1 s
shot 3 - t3 3ph 0.0-9000.0 s in steps of ± 0.5% ± 10 ms
0.1 s
shot 4 - t4 3ph 0.0-9000.0 s in steps of ± 0.5% ± 10 ms
0.1 s
Autorecloser maximum wait time for 0.0-90000.0 s in steps of ± 0.5% ± 10 ms
sync, tSync 0.1 s
Duration of close pulse to circuit 0.000-60.000 s in steps of ± 0.5% ± 10 ms
breaker tPulse 1 ms
Reclaim time, tReclaim 0.0-90000.0 s in steps of ± 0.5% ± 10 ms
0.1 s
Inhibit reset time, tInhibit 0.000-60.000 s in steps of ± 0.5% ± 10 ms
1 ms
Maximum trip pulse duration, tTrip 0.000-60.000 s in steps of ± 0.5% ± 10 ms
(longer trip pulse durations will either 1 ms
extend the dead time or interrupt the
reclosing sequence)
Maximum wait time for release from 0.0-90000.0 s in steps of ± 0.5% ± 10 ms
Master, tWaitForMaster 0.1 s
Maximum wait time between shots, tAu- 0.000-60.000 s in steps of ± 0.5% ± 10 ms
toWait 1 ms
Time delay before indicating reclosing 0.0-90000.0 s in steps of ± 0.5% ± 10 ms
unsuccessful, tUnsuc 0.1 s
Time CB must be closed before AR 0.000-60.000 s in steps of ± 0.5% ± 10 ms
becomes ready for a reclosing cycle, 1 ms
tCBClosed
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 75

7DEOH $5$XWRUHFORVHU
3DUDPHWHU 9DOXH
Reclosing shots 1-4
Programs Three pole trip: 1

Single, two and three pole trip: 6


Number of instances Up to six depending on terminal type
(different terminal types support dif-
ferent CB arrangements and numbers
of bays)
Breaker closed before start 5s

/RJLF

7DEOH 757ULSSLQJORJLF
3DUDPHWHU 9DOXH $FFXUDF\
Setting for the minimum trip 0.000 - 60.000 s in steps of ± 0.5% ± 10 ms
pulse length, tTripMin 1 ms

7DEOH 3'F3ROHGLVFRUGDQFHFRQWDFWEDVHG
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Auxiliary-contact-based (0.000-60.000) s in steps of ± 0.5 % ±10 ms
function - time delay 1 ms

7DEOH &&+7&RPPXQLFDWLRQFKDQQHOWHVWORJLF
3DUDPHWHU 6HWWLQJUDQJH $FFXUDF\
Time interval between auto- 0.0-90000.0 s in steps of 0.1 s ± 0.5% ± 10 ms
matic starts of testing cycle,
tStart
Time interval available for 0.0-90000.0 s in steps of 0.1 s ± 0.5% ± 10 ms
test of the external function
to be registered as suc-
cessful, tWait
Minimum time interval 0.0-90000.0 s in steps of 0.1 s ± 0.5% ± 10 ms
required before repeated
test of the external function,
tCh
Duration of CS output sig- 0.0-90000.0 s in steps of 0.1 s ± 0.5% ± 10 ms
nal, tCS
Duration of CHOK output 0.0-90000.0 s in steps of 0.1 s ± 0.5% ± 10 ms
signal, tChOK
Duration of inhibit condition 0.0-90000.0 s in steps of 0.1 s ± 0.5% ± 10 ms
extension after the BLOCK
input signal resets, tInh
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 76

7DEOH &1(YHQWFRXQWHU
)XQFWLRQ 9DOXH
Counter value 0-10000
Max. count up speed 10 pulses/s

0RQLWRULQJ

7DEOH '53'LVWXUEDQFHUHSRUWVHWWLQJSHUIRUPDQFH
'DWD 6HWWLQJUDQJH
Pre-fault time, tPre 50-300 ms in steps of 10 ms
Post-fault time, tPost 100-5000 ms in steps of 100 ms
Limit time, tLim 500-6000 ms in steps of 100 ms
Number of recorded disturbances Max. 10

7DEOH '5'LVWXUEDQFHUHFRUGHUVHWWLQJSHUIRUPDQFH
)XQFWLRQ 6HWWLQJUDQJH
Overcurrent triggering 0-5000% of Inb in
steps of 1%
Undercurrent triggering 0-200% of Inb in
steps of 1%
Overvoltage triggering 0-200% of Unb in
steps of 1% at 100 V
sec.
Undervoltage triggering 0-110% of Unb in
steps of 1%

7DEOH '5'LVWXUEDQFHUHFRUGHUSHUIRUPDQFH
'DWD 9DOXH
Number of binary signals 48
Number of analog signals 10
Sampling rate 2 kHz
Recording bandwidth 5-250 Hz
Total recording time with ten analog and 48 binary signals recorded. 40 s typically
(The amount of harmonics can affect the maximum storage time)
Voltage channels Dynamic range (0.01-2.00) x Ur at
100/200 V sec.
Resolution 0.1% of Ur
Accuracy at rated U ≤ Ur ± 2.5% of Ur
frequency U > Ur ± 2.5% of U
Current channels Dynamic range Without DC off- (0.01-110.00) × Ir
set
With full DC off- (0.01-60.00) × Ir
set
Resolution 0.5 % of Ir
Accuracy at rated I ≤ Ir ± 2.5 % of Ir
frequency I > Ir ± 2.5 % of I
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 77

7DEOH (5(YHQWUHFRUGHU
)XQFWLRQ 9DOXH
Event buffering capacity Max. number of events/disturbance report 150
Max. number of disturbance reports 10

7DEOH )/2&)DXOWORFDWRU
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Distance to fault Reach for Ir Resistive direc- (0 - 1500) ohm/ ± 2.5 % (typical)
locator =1 A tion phase
Reactive direc- (0 - 1500) ohm/ ± 2.5 % (typical)
tion phase
Phase selection According to
input signals

7DEOH 0HDQYDOXHV $&PRQLWRULQJ


)XQFWLRQ 1RPLQDOUDQJH $FFXUDF\
Frequency (0.95 - 1.05) x fr ± 0.2 Hz
Voltage (RMS) Ph-Ph (0.1 - 1.5) x Ur ± 2.5% of Ur, at U≤ Ur

± 2.5% of U, at U> Ur
Current (RMS) (0.2 - 4) x Ir ± 2.5% of Ir, at I≤ Ir

± 2.5% of I, at I> Ir
Active power*) at |cos ϕ| ≥ 0.9 ± 5.0%
Reactive power*) at |cos ϕ| ≤ 0.8 ± 7.5%
*) Measured at Ur and 20% of Ir
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 78

7DEOH 0,0P$PHDVXULQJIXQFWLRQ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
mA measuring function ± 5, ± 10, +± 20 mA 0-5, ± 0.1 % of set value ± 0.005 mA
0-10, 0-20, 4-20 mA
Max current of transducer (-25.00 to +25.00) mA in steps
to input, I_Max of 0.01
Min current of transducer (-25.00 to +25.00) mA in steps
to input, I_Min of 0.01
High alarm level for input, (-25.00 to +25.00) mA in steps
HiAlarm of 0.01
High warning level for (-25.00 to +25.00) mA in steps
input, HiWarn of 0.01
Low warning level for (-25.00 to +25.00) mA in steps
input, LowWarn of 0.01
Low alarm level for input, (-25.00 to +25.00) mA in steps
LowAlarm of 0.01
Alarm hysteresis for input, (0-20) mA in steps of 1
Hysteresis
Amplitude dead band for (0-20) mA in steps of 1
input, DeadBand
Integrating dead band for (0.00-1000.00) mA in steps of
input, IDeadB 0.01

7DEOH ,0$,QFUHDVHGDFFXUDF\RI$&LQSXWTXDQWLWLHV
)XQFWLRQ 1RPLQDOUDQJH $FFXUDF\
Frequency (0.95 - 1.05) x fr ± 0.2 Hz
Voltage (RMS) Ph-Ph (0.8 - 1.2) x Ur ± 0.25% of Ur, at U≤ Ur

± 0.25% of U, at U> Ur
Current (RMS) (0.2 - 2) x Ir ± 0.25% of Ir, at I≤ Ir

± 0.25% of I, at I> Ir
Active power 0.8 x Ur < U < 1.2 x Ur ± 0.5% of Sr at S ≤Sr

0.2 x Ir < I < 2 x Ir ± 0.5% of S at S > Sr

Reactive power 0.8 x Ur < U < 1.2 x Ur ± 0.5% of Sr at S ≤Sr

0.2 x Ir < I < 2 x Ir ± 0.5% of S at S >Sr

0HWHULQJ

7DEOH 3&3XOVHFRXQWHUORJLFIRUPHWHULQJ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
Input frequency See Binary Input Module (BIM) -
Cycle time for pulse 30 s, 1 min, 1 min 30 s, 2 min, 2 min 30 ± 0,1% of set value
counter s, 3 min, 4 min, 5 min, 6 min, 7 min 30s,
10 min, 12 min, 15 min, 20 min, 30 min,
60 min
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 79

'DWDFRPPXQLFDWLRQ

7DEOH 63$6HULDOFRPPXQLFDWLRQ
)XQFWLRQ 9DOXH
Protocol SPA
Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
Slave number 1 to 899
Remote change of active group allowed yes/no
Remote change of settings allowed yes/no
Connectors and optical fibres glass or plastic

7DEOH /216HULDOFRPPXQLFDWLRQ
)XQFWLRQ 9DOXH
Protocol LON
Communication speed 1.25 Mbit/s
Connectors and optical fibres glass or plastic

7DEOH ,(&6HULDOFRPPXQLFDWLRQ
)XQFWLRQ 9DOXH
Protocol IEC 60870-5-103
Communication speed 9600, 19200 Bd
Connectors and optical fibres glass or plastic

7DEOH 2SWLFDOILEUHFRQQHFWLRQUHTXLUHPHQWVIRU63$,(&
*ODVVILEUH 3ODVWLFILEUH
Cable connector ST connector HFBR, Snap-in connector
Fibre diameter 62.5/125 µm 1 mm

50/125 µm
Max. cable length 500 m 30 m

7DEOH 56FRQQHFWLRQUHTXLUHPHQWVIRU63$,(&
Cable connector Phoenix, MSTB 2.5/6-ST-5.08 1757051
Cable dimension SSTP according to EIA Standard RS485
Max. cable length 100 m

7DEOH /212SWLFDOILEUHFRQQHFWLRQUHTXLUHPHQWVIRU/21EXV
*ODVVILEUH 3ODVWLFILEUH
Cable connector ST-connector HFBR, Snap-in connector
Fibre diameter 62.5/125 µm 1 mm

50/125 µm
Max. cable length 1000 m 30 m
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 80

7DEOH '&0*DOYDQLFGDWDFRPPXQLFDWLRQPRGXOH
,QWHUIDFHW\SH $FFRUGLQJWRVWDQGDUG &RQQHFWRUW\SH
V.36/V11 Co-directional (on request) ITU (CCITT) D-sub 25 pins
V.36/V11 Contra-directional ITU (CCITT) D-sub 25 pins
X.21/X27 ITU (CCITT) D-sub 15 pins
RS 530/RS422 Co-directional (on request) EIA D-sub 25 pins
RS 530/RS422 Contra-directional EIA D-sub 25 pins
G.703 Co-directional ITU (CCITT) Screw
)XQFWLRQ 9DOXH
Data transmission synchronous, full duplex
Transmission type 56 or 64 kbit/s

For G703 only 64 kbit/s

7DEOH '&06*06KRUWUDQJHJDOYDQLFPRGXOH
Data transmission Synchronous, full duplex
Transmission rate 64 kbit/s (256 kBaud; code transparent)
Clock source Internal or derived from received signal
Range max 4 km
Line interface Balanced symmetrical three-state current loop (4 wires)
Connector 5-pin connector with screw connection
Insulation 2,5 kV 1 min. Opto couplers and insulating DC/DC-converter
15 kV with additional insulating transformer

7DEOH '&0)20)LEUHRSWLFDOFRPPXQLFDWLRQPRGXOH
2SWLFDOLQWHUIDFH
Type of fibre Graded-index multimode 50/ Single mode 9/125 µm
125µm or 62,5/125µm
Wave length 1300 nm 1300 nm
Optical transmitter LED LED

injected power -17 dBm -22 dBm


Optical receiver PIN diode PIN diode

sensitivity -38 dBm -38 dBm


Optical budget 21 dB 16 dB
Transmission distance typical 15-20 km a) typical 30-70 km a)
Optical connector Type FC-PC Type FC-PC
Protocol ABB specific ABB specific
Data transmission Synchronous, full duplex Synchronous, full duplex
Transmission rate 64 kbit/s 64 kbit/s
Clock source Internal or derived from Internal or derived from
received signal received signal
a)
depending on optical budget calculation
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 81

7DEOH '&06)206KRUWUDQJHILEUHRSWLFDOPRGXOH
Data transmission Synchronous, full duplex
Transmission rate 64 kbit/s
Clock source Internal or derived from received signal
Optical fibre Graded-index multimode 50/125µm or 62,5/125µm
Wave length 850 nm
Optical connectors ST
Optical budget 15 dB
Transmission distance max 3,5 km
Protocol FIBERDATA specific
Optical connector Type ST

+DUGZDUHPRGXOHV

7DEOH %,0,20360%LQDU\LQSXWV
,QSXWV 5/ 5/ 5/ 5/
Binary inputs BIM: 16, IOM: 8, PSM: 4
Debounce frequency 5 Hz (BIM), 1 Hz (IOM)
Oscillating signal discrimi- Blocking and release settable between 1-40 Hz
nator.*
Binary input voltage RL 24/30 VDC 48/60 VDC 110/125 VDC 220/250 VDC

+/-20% +/-20% +/-20% +/-20%


Power dissipation (max.) 0.05 W/input 0.1 W/input 0.2 W/input 0.4 W/input
*) Only available for BIM

7DEOH %20,20360%LQDU\RXWSXWV
)XQFWLRQRUTXDQWLW\ 7ULSDQG6LJQDO )DVWVLJQDO
UHOD\V UHOD\V
Binary outputs BOM: 24, IOM: 10, IOM: 2
PSM: 4
Max system voltage 250 V AC, DC 250 V AC, DC
Test voltage across open contact, 1 min 1000 V rms 800 V DC

Current carrying Continuous 8A 8A


capacity 1s 10 A 10 A

Making capacity at 0.2 s 30 A 0.4 A


inductive load with L/ 1.0 s 10 A 0.4 A
R>10 ms
Breaking capacity for AC, cos ϕ>0.4 250 V/8.0 A 250 V/8.0 A
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 82

)XQFWLRQRUTXDQWLW\ 7ULSDQG6LJQDO )DVWVLJQDO


UHOD\V UHOD\V
Breaking capacity for DC with L/R<40ms 48 V/1 A 48 V/1 A
110 V/0.4 A 110 V/0.4 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A

Maximum capacitive load - 10 nF

7DEOH 0,0(QHUJL]LQJTXDQWLWLHVUDWHGYDOXHVDQGOLPLWV
4XDQWLW\ 5DWHGYDOXH 1RPLQDO
UDQJH
mA input input range +/- 20 mA -
module input resistance Rin = 194 -
ohm
power consumption each mA-module ≤4W -
each mA-input ≤ 0.1 W -

7DEOH 0,07HPSHUDWXUHGHSHQGHQFH
'HSHQGHQFHRQ :LWKLQQRPLQDOUDQJH ,QIOXHQFH
Ambient temperature, mA-input 2-20 mA -10°C to +55°C 0.02% / °C
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 83

2UGHULQJ *XLGHOLQHV

Carefully read and follow the set of rules to ensure problem-free order management. Be aware
that certain functions can only be ordered in combination with other functions and that some
functions require specific hardware selections.

%DVLFKDUGZDUHDQGIXQFWLRQV
3ODWIRUPDQGEDVLFIXQFWLRQDOLW\
Basic REx 5xx platform and common functions housed in selected casing

0DQXDOVRQ&'
Operator’s manual (English)
Installation and commissioning manual (English)
Technical reference manual (English)
Application manual (English)

%LQDU\,2FDSDELOLWLHV
Binary I/O resided on power supply module 360

0HDVXULQJFDSDELOLWLHV
A/D module $'0
Transformer module 750

/LQHGLVWDQFH
Full-scheme distance protection, 3-zone, phase-to-phase =0S
Full-scheme distance protection, 3-zone, phase-to-earth =0H
Distance protection, zone 4 =0
Distance protection, zone 5 =0

&XUUHQW
Definite time non-directional phase overcurrent protection 72&SK
Definite time non-directional residual overcurrent protection (72&U

/RJLF
High speed binary output logic (HSBO)

0RQLWRULQJ
Supervision of AC input quantities '$
Supervision of mA input quantities 0, (Requires optional mA-transducer module, 0,0)
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 84

3URGXFWVSHFLILFDWLRQ
REL 511 Quantity: 1MRK 002 492-AE

Default:
The terminal is delivered without loaded configuration.

8VHWKHFRQILJXUDWLRQDQGSURJUDPPLQJWRRO &$3 WREXLOGDFRQILJXUDWLRQIURPVWDUWRUWR


PDNHDQH[DPSOHFRQILJXUDWLRQFRPSOHWH

Option:
Customer specific configuration On request

5XOH6HOHFWRQO\RQHDOWHUQDWLYH
Engergizing quantities for binary inputs on 24-30 V 1MRK 002 238-AA
power supply module 48-60 V 1MRK 002 238-BA
110-125 V 1MRK 002 238-CA
220-250 V 1MRK 002 238-DA

1RWH$X[LOLDU\GFYROWDJH(/FRQQHFWHGWRWKHSRZHUVXSSO\PRGXOHLV  9

0HDVXULQJFDSDELOLWLHV
Add measuring capabilities by selecting input energizing options from the following tables.

5XOH6HOHFWRQO\RQHDOWHUQDWLYH,IVHQVLWLYHHDUWKIDXOW
IXQFWLRQDOLW\VKRXOGEHXVHGVHOHFWIURPQH[WWDEOH
Rated measuring input energizing quantities 1 A, 110 V 1MRK 000 157-MB
1 A, 220 V 1MRK 000 157-VB
5 A, 110 V 1MRK 000 157-NB
5 A, 220 V 1MRK 000 157-WB

5XOH6HOHFWRQO\RQHDOWHUQDWLYH$OVRVHOHFWWKHFRUUH
VSRQGLQJVHQVLWLYHHDUWKIDXOWIXQFWLRQ V IURPWKHRSWLRQDO
SURWHFWLRQIXQFWLRQV
Rated measuring input energizing I1-I4 1A 1MRK 000 157-XB
quantities for sensitive earth fault
I5 0.1 A
functions
U1-U5 110 V

I1-I4 5A 1MRK 000 157-RB

I5 0.5 A

U1-U5 110 V
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 85

/LQHGLVWDQFH
5XOH2QH*HQHUDOIDXOWFULWHULDPXVWEHRUGHUHG
General fault criteria, impedance and current based *)&]L 1MRK 001 456-AA
General fault criteria, impedance and current based, with 1MRK 001 456-MA
Phase preference logic *)&SSO]L

/RJLF
5XOH2QHRI 75 RU 75 PXVWEHRUGHUHG
Three pole tripping logic 75 1MRK 001 458-VA
Single, two or three pole tripping logic 75 1MRK 001 458-XA

2SWLRQDOIXQFWLRQV
/LQHGLVWDQFH
Simplified impedance settings 6,6 1MRK 001 459-UA

Power swing detection 36' 1MRK 001 456-LA

Scheme communication logic =&20 1MRK 001 456-NA

5XOH6FKHPHFRPPXQLFDWLRQORJLF =&20 PXVWEH


RUGHUHGLI&XUUHQWUHYHUVDODQGZHHNHQGLQIHHGORJLF
=&$/ LVVHOHFWHG
5XOH&XUUHQWUHYHUVDODQGZHHNHQGLQIHHGORJLF
=&$/ DQG*HQHUDOIDXOWFULWHULD *)& LQFOXGLQJSKDVH
SUHIHUHQFHORJLFFDQQRWEHRUGHUHGWRJHWKHU
Current reversal and weak end infeed logic =&$/ 1MRK 001 455-PA

Radial feeder protection 3$3 1MRK 001 455-SA

Automatic switch onto fault logic 627) 1MRK 001 456-RA

Local acceleration logic =&/& 1MRK 001 456-TA

&XUUHQW
Instantaneous non-directional phase overcurrent protection 1MRK 001 457-AA
,2&SK
Instantaneous non-directional residual overcurrent protec- 1MRK 001 456-VA
tion ,2&U
Two step time delayed non-directional phase overcurrent 1MRK 001 459-LA
protection 72&
Two step time delayed directional phase overcurrent protec- 1MRK 001 457-CA
tion 72&
Time delayed non-directional residual overcurrent protec- 1MRK 001 456-YA
tion 7()
5XOH)RXUVWHSUHVLGXDORYHUFXUUHQWSURWHFWLRQ () RU
'HILQLWHDQGLQYHUVHWLPHGHOD\HGUHVLGXDORYHUFXUUHQW
SURWHFWLRQ 7()GLU FDQRQO\EHVHOHFWHGVHSDUDWHO\
QHYHUWRJHWKHU
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 86

Time delayed directional residual overcurrent protection 1MRK 001 459-ZA


7()GLU
1RWH:KHQ)RXUVWHSUHVLGXDORYHUFXUUHQWSURWHFWLRQ
() LVVHOHFWHG6FKHPHFRPPXQLFDWLRQORJLF ()& 
DQG&XUUHQWUHYHUVDODQGZHDNHQGLQIHHGORJLFIRU
UHVLGXDORYHUFXUUHQWSURWHFWLRQ ()&$ DUHDXWRPDWL
FDOO\DGGHG
Four step time delayed directional residual overcurrent pro- 1MRK 001 459-HA
tection ()
5XOH7KHVHQVLWLYHSURWHFWLRQIXQFWLRQVGHPDQGVWKDW
WKHFRUUHVSRQGLQJUDWHGPHDVXULQJLQSXWHQHUJL]LQJ
TXDQWLWLHVDUHVHOHFWHG
Sensitive directional residual overcurrent protection :() 1MRK 001 457-PA

Sensitive directional residual power protection :() 1MRK 001 459-TA

1RWH,I6FKHPHFRPPXQLFDWLRQORJLF ()& RU&XUUHQW


UHYHUVDODQGZHDNHQGLQIHHGORJLFIRUUHVLGXDORYHUFXU
UHQWSURWHFWLRQ ()&$ LVWREHXVHGRQHGLUHFWLRQDO
HOHPHQW 7()GLU VKRXOGEHVHOHFWHG.
Scheme communication logic for residual overcurrent pro- 1MRK 001 455-UA
tection ()&
Current reversal and weak-end infeed logic for residual 1MRK 001 455-VA
overcurrent protection ()&$
Thermal phase overload protection 7+2/ 1MRK 001 457-DA

Breaker failure protection %)3 1MRK 001 458-AA

9ROWDJH
Time delayed undervoltage protection 789 1MRK 001 457-RA
Time delayed overvoltage protection 729 1MRK 001 457-GA
Time delayed residual overvoltage protection 729U 1MRK 001 459-FA

3RZHUV\VWHPVXSHUYLVLRQ
Broken conductor check %5& 1MRK 001 457-UA
Loss of voltage check /29 1MRK 001 457-VA
Overload supervision 29/' 1MRK 001 457-FA
5XOH,I6ZLWFKRQWRIDXOWORJLF 627) DQGRU)XVHIDLO
XUH )86( DUHVHOHFWHG'HDGOLQHGHWHFWLRQ '/' LV
DXWRPDWLFDOO\LQFOXGHGLQWKHWHUPLQDO
Dead line detection '/' 1MRK 001 455-LA
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 87

6\VWHPSURWHFWLRQDQGFRQWURO
Pole slip protection 363 1MRK 001 457-SA
Low active power protection (LAPP) 1MRK 001 460-AC
Low active and reactive power protection (LARP) 1MRK 001 460-BC
High active power protection (HAPP) 1MRK 001 460-CB
High active and reactive power protection (HARP) 1MRK 001 460-DB
Sudden change in phase current protection (SCC1) 1MRK 001 460-EB
Sudden change in residual voltage protection (SCRC) 1MRK 001 460-FA
Sudden change in voltage protection (SCV) 1MRK 001 460-GB
Overvoltage protection (OVP) 1MRK 001 460-HB
Undercurrent protection (UCP) 1MRK 001 460-KB
Phase overcurrent protection (OCP) 1MRK 001 460-LB
Residual overcurrent protection (ROCP) 1MRK 001 460-MA

6HFRQGDU\V\VWHPVXSHUYLVLRQ
Current circuit supervision, current based &768 1MRK 001 457-XA
5XOH,I )86(GE EDVHGRSWLRQLVVHOHFWHG )86(QV RU
)86(]V RSWLRQPXVWEHRUGHUHG.
Fuse failure supervision, Negative sequence )86(QV 1MRK 001 457-YA
Fuse failure supervision, Zero sequence )86(]V 1MRK 001 457-ZA
Fuse failure supervision, du/dt and di/dt based )86(GE 1MRK 001 459-YA
Voltage transformer supervision 7&7 1MRK 001 455-TA

&RQWURO
Single command, 16 signals &' 1MRK 001 458-EA
Synchrocheck and energizing check, single circuit breaker 1MRK 001 458-GA
6<1
Synchrocheck and energizing check, double circuit break- 1MRK 001 458-FA
ers 6<1
Synchrocheck with synchronizing and energizing check, 1MRK 001 458-KA
single circuit breaker 6<1V\
Synchrocheck with synchronizing and energizing check, 1MRK 001 457-HA
double circuit breaker 6<1V\
Autorecloser - 1- and/or 3-phase, single circuit breaker 1MRK 001 458-LA
$5
Autorecloser - 1- and/or 3-phase, double circuit breakers 1MRK 001 457-KA
$5
Autorecloser - 3-phase, single circuit breaker $5 1MRK 001 458-MA
Autorecloser- 3-phase, double circuit breaker $5 1MRK 001 457-LA
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 88

/RJLF
Additional three pole tripping logic 75 1MRK 001 459-VA
Additional single, two or three pole tripping logic 75 1MRK 001 459-XA

Pole discordance logic (contact based) 3'F 1MRK 001 458-UA
Additional configurable logic blocks &/ 1MRK 001 457-MA
Communication channel test logic &&+7 1MRK 001 459-NA

5XOH,I%LQDU\VLJQDOWUDQVIHUWRUHPRWHHQG 57& LVVHOHFWHG5HPRWHHQGGDWDFRPPX


QLFDWLRQPRGXOHPXVWEHRUGHUHG
Binary signal transfer to remote end 57& 1MRK 001 458-ZA

1RWH7KH/21EDVHGFRPPXQLFDWLRQFDSDELOLW\RSWLRQLVQHFHVVDU\
Multiple command, one fast block with 16 signals (CM1) 1MRK 001 455-RA
Multiple command, 79 medium speed blocks each with 16 1MRK 001 458-YA
signals &0

0RQLWRULQJ
Disturbance recorder '5 1MRK 001 458-NA
Event recorder (5 1MRK 001 459-KA
Fault locator )/2& 1MRK 001 458-RA
Trip value recorder 795 1MRK 001 458-SA
Increased accuracy of AC input quantities ,0$ 1MRK 000 597-PA

0HWHULQJ
1RWH7KHELQDU\LQSXWPRGXOH %,0 ZLWKHQKDQFHGSXOVHFRXQW
LQJFDSDELOLWLHVLVQHHGHGIRUSXOVHFRXQWLQJ
Pulse counter logic for metering 3& 1MRK 001 458-TA
Six event counters &1 1MRK 001 445-CA

6HFRQG+0,ODQJXDJH VWDQGDUG
1RWH2QO\RQHDOWHUQDWLYHLVSRVVLEOH
2nd HMI language, german +0,GH German 1MRK 001 459-AA
2nd HMI language, russian +0,UX Russian 1MRK 001 459-BA
2nd HMI language, french +0,IU French 1MRK 001 459-CA
2nd HMI language, spanish +0,HV Spanish 1MRK 001 459-DA
2nd HMI language, italian +0,LW Italian 1MRK 001 459-EA
Customer specific language Contact your local ABB representative for
availability
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 89

+DUGZDUH
,QGLFDWLRQPRGXOH
18 LED indication module /('+0, 1MRK 000 008-DA

&DVHVL]H
When ordering I/O modules, observe the maximum quantities according to table below.

7DEOH 0D[LPXPKDUGZDUHFRQILJXUDWLRQVIRU,2PRGXOHV
Maximum number of Case size
modules 3/4 x 19” 1/2 x 19”
Note: Standard order 1MRK 000 151-GC 1MRK 000 151-FC
of location for I/O
modules is BIM-BOM-
IOM-MIM-DCM from
right to left as seen
from the rear side of
the terminal
Binary input module 8 3
%,0
Binary output mod-
ules %20 
4 3
Binary input/output
modules ,20
Milliampere input 3 1
module 0,0
Data communication
module for remote ter-
1 1
minal communication
'&0
7RWDOLQFDVH  

%LQDU\LQSXWRXWSXWPRGXOHV
Binary input module %,0 16 inputs
RL24-30 VDC Quantity: 1MRK 000 508-DB
RL48-60 VDC Quantity: 1MRK 000 508-AB
RL110-125 VDC Quantity: 1MRK 000 508-BB
RL220-250 VDC Quantity: 1MRK 000 508-CB

Binary input module with enhanced pulse counting capabilities for the pulse counter logic for
metering %,0 16 inputs

5XOH&DQRQO\EHRUGHUHGWRJHWKHUZLWKWKHSXOVHFRXQWHUORJLFIRUPHWHULQJ 3& RSWLRQDO


IXQFWLRQ
RL24-30 VDC Quantity: 1MRK 000 508-HA
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 90

RL48-60 VDC Quantity: 1MRK 000 508-EA


RL110-125 VDC Quantity: 1MRK 000 508-FA
RL220-250 VDC Quantity: 1MRK 000 508-GA

5XOH7KHQXPEHURIELQDU\RXWSXWPRGXOHV %20 DQGELQDU\,2PRGXOHV ,20 WRJHWKHULQ


DWHUPLQDOPD\QRWH[FHHGDWRWDORI
Binary output module 24 output relays %20 Quantity: 1MRK 000 614-AB

5XOH7KHQXPEHURIELQDU\,2PRGXOHV ,20 DQGELQDU\RXWSXWPRGXOHV %20 WRJHWKHULQD


WHUPLQDOPD\QRWH[FHHGDWRWDORI
Binary input/output module ,20 8 inputs, 10 outputs, 2 high-speed outputs
RL24-30 VDC Quantity: 1MRK 000 173-GB
RL48-60 VDC Quantity: 1MRK 000 173-AC
RL110-125 VDC Quantity: 1MRK 000 173-BC
RL220-250 VDC Quantity: 1MRK 000 173-CC

mA input module 6 channels 0,0 Quantity: 1MRK 000 284-AB

5HPRWHHQGGDWDFRPPXQLFDWLRQPRGXOHV RQO\RQHDOWHUQDWLYHFDQEHVHOHFWHG
Co-directional V.36 galvanic module '&09FR On request

Contra-directional V.36 galvanic module '&09FRQWUD 1MRK 000 185-BA


X.21 galvanic module '&0; 1MRK 000 185-CA
Co-directional RS530 galvanic module '&056FR On request
Contra-directional RS530 galvanic module '&0 1MRK 000 185-EA
56FRQWUD
Fibre optical module '&0)20 1MRK 000 195-AA
Short range galvanic module '&06*0 1MRK 001 370-AA
Short range fibre optical module '&06)20 1MRK 001 370-DA
Co-directional G.703 galvanic module '&0* 1MRK 001 370-CA

6HULDOFRPPXQLFDWLRQPRGXOH
6HULDOFRPPXQLFDWLRQSURWRFROVSRVVLEOHFRPELQDWLRQVRILQWHUIDFHDQGFRQQHFWRUV
Alt 1 Alt 2 Alt 3
X13 SPA/IEC fibre optic SPA/IEC RS485 SPA fibre optic
X15 LON fibre optic LON fibre optic IEC fibre optic

/2&;RQO\RQHDOWHUQDWLYHFDQEHVHOHFWHG
SPA/IEC 60870-5-103 interface 63$,(&SO Plastic fibres 1MRK 000 168-FA
SPA/IEC 60870-5-103 interface 63$,(& Glass fibres 1MRK 000 168-DA
/21JO
SPA/IEC 60870-5-103 interface RS485 gal- RS485 galvanic 1MRK 002 084-BA
vanic,WHUPLQDWHG for termination of last termi-
nal in multi-drop 63$,(&56W
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 91

SPA/IEC 60870-5-103 interface, RS485 gal- RS485 galvanic 1MRK 002 084-CA
vanic, XQWHUPLQDWHG for point-to-point or inter-
mediate location in multi-drop 63$,(&56
XW

/2&;RQO\RQHDOWHUQDWLYHFDQEHVHOHFWHG
LON interface /21SO Plastic fibres 1MRK 000 168-EA
LON interface 63$,(&/21JO Glass fibres 1MRK 000 168-DA
IEC 60870-5-103 interface 63$,(&/21JO Glass fibres 1MRK 000 168-DA
IEC 60870-5-103 interface 63$,(&SO Plastic fibres 1MRK 000 168-FA

7HVWVZLWFK
Test switch module RTXP 24 in RHGS6 case 1MRK 000 371-CA
With internal earthing RK 926 215-BB
With external earthing RK 926 215-BC
On/off switch for the DC-supply 2QRIIVZLWFK RK 795 017-AA

0RXQWLQJGHWDLOVZLWK,3SURWHFWLRQIURPWKHIURQW
19” rack mounting kit ´UDFN 1MRK 000 020-BR
Wall mounting kit :DOO 1MRK 000 020-DA
Flush mounting kit )OXVK 1MRK 000 020-Y
Semiflush mounting kit 6HPLIOXVK 1MRK 000 020-BS
Additional seal for IP54 protection of flush and semiflush 1MKC 980 001-2
mounted terminals ,3

$FFHVVRULHV
3URWHFWLRQFRYHU
Cover for rear area including fixing
screws and assembly instruction 6U, 3/4 x 19” 1MRK 000 020-AB
6U, 1/2 x 19” 1MRK 000 020-AC

0RXQWLQJNLWV
Side-by-side mounting kit 6LGHE\VLGH 1MRK 000 020-Z

&RQYHUWHUV
21-15X: Optical/electrical converter for short range fibre 1MRK 001 295-CA
optical module V.36 (supply 48-110 VDC) ;
21-16X: Optical/electrical converter for short range fibre 1MRK 001 295-DA
optical module X.21/G 703 (supply 48-110 VDC) 
;

.H\VZLWFK
Key switch for restriction of settings via LCD- Quantity: 1MRK 000 611-A
HMI .H\VZLWFK
3URWHFW,7/LQHGLVWDQFHSURWHFWLRQWHUPLQDO 5(/ 
1MRK 506 164-BEN
Page 92

)URQWFRQQHFWLRQFDEOH
Front connection cable between LCD-HMI Quantity: 1MKC 950 001-2
and PC for terminal handling (Opto/9-pole D-
sub) )URQWFRQQHFWLRQFDEOH

0DQXDOV
2QH&'ZLWKDOOVHULHVPDQXDOVLVDOZD\VGHOLYHUHGZLWKHDFKWHUPLQDO

5XOH6SHFLI\WKHQXPEHURIH[WUD&'¶VUHTXHVWHG
User documentation CD-ROM REx 5xx, RET Quantity: 1MRK 002 270-AA
521, RED 521 (DOC-CD)

5XOH6SHFLI\WKHQXPEHURISULQWHGPDQXDOVUHTXHVWHG
Operator’s manual Quantity: 1MRK 506 165-UEN
Technical reference manual Quantity: 1MRK 506 166-UEN
Installation and commissioning manual Quantity: 1MRK 506 167-UEN
Application manual Quantity: 1MRK 506 168-UEN

&XVWRPHUIHHGEDFN
For our reference and statistics we would be pleased to be provided with the following applica-
tion data:

Country: End user:

Station name: Voltage level: kV

5HODWHGGRFXPHQWV

7HFKQLFDORYHUYLHZEURFKXUH

Accessories for REx 5xx*2.3 1MRK 514 009-BEN

CAP 540*1.2 1MRK 511 112-BEN

0DQXIDFWXUHU
$%%$XWRPDWLRQ7HFKQRORJ\3URGXFWV$%
Substation Automation
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
Internet: www.abb.com/substationautomation

Potrebbero piacerti anche