Sei sulla pagina 1di 6

UJC-S

UNDERGROUND JUNCTION CHAMBER


CATALOGUE 2018
UJC-S UNDERGROUND
JUNCTION CHAMBER

APPLICATION TECHNICAL CHARACTERISTICS Up to 42 kV


For onshore renewable power • Burial type 316 stainless steel 1250 Amps
parks, the underground junction housing.
chamber will be used as a • Robust design with IP68 degree of
connecting point for cable-jointing protection (IEC60529/AS60529).
and branching applications. • Suitable for voltage up to 42 kV
• Suitable for cable up to 1200 mm2

DESIGNED,
MANUFACTURED
& TESTED IN
AUSTRALIA

DESIGN
Underground junction chamber
comprising:
1. Burial type stainless steel metal
housing. 2 3 4

2. Cable gland plate upper.


3. Cable glands.
4. Lid.
5. Cable gland plate tower.
6. Cable seals arrangement, up
to 4 rails for max. 12 single
core cables with outer cable
2
diameter 34 to 80 mm.

Voltage Outer dimensions Outer cable dia


Underground (mm)
Um of cabinet with base Installation
Junction Chamber
(kV) (w x d x h)(mm) min max

UJC-S 42 1527 x 805 x 358 Burial type 34 80


BENEFITS
• The chamber design is specifically
designed to be installed in
1
underground conditions.
• High reliability of installation. 2
3
• Good test and demarcation point.
• Caters for installation of monitoring
4
equipment.
• Reduction of land footprint.
• Joining/branching of cables with
different cross-sections. 1527

DIMENSIONS/FEATURES 5
1. Mounting Brackets
2. Lifting Lugs 3
3. Gland Plates
6
4. Interface with protection caps 1
5. Earth System (standard only
bottom bar supplied)
6. Compression Gland 358 805

ARRANGEMENTS
Possibility to add surge arresters to
Junction chamber can be equipped
protect equipment from high voltage
with different connectors. See
surges. See catalogue pages for
catalogue pages for more details.
more details.

ENCLOSURES

Junction frame type Cable sizes OD (Ø mm)


UJC-C-M400J2-T1 34-55

UJC-C-M400J2-T2 55-80
MOUNTING FRAME - SLED

UJC-F-1-C-T1 Mounting frame with 6 cable cleats

CLEATS

MOUNTING
FRAME

ACCESSORIES
To terminate 1 open end of the screended two-way interface C junctions.

Conductor size (mm2) Current capacity


Connector type Accessories
min max (Amps)
M480TB/G + BIPA Bushing extender + Bipa and cap 35 300 630

M484TB/G + BIPA Bushing extender + Bipa and cap 35 630 1250

M489TB/G + BIPA Bushing extender + Bipa and cap 630 1200 1250

Connector for
cable sizes up
to 300 mm2

Connector housing
(K)(M)(P)480TB/G

Connector for
cable sizes up
to 630 mm2

Stud+nut Conductor Basic insulating plug Cable reducer


+washer lug with shear (K)(M)(P)800BIPA
Connector housing
off bolts + rubber cap
(K)(M)(P)484TB/G

Connector for
cable sizes up
to 1200 mm2

Connector housing
(K)(M)(P)489TB/G
Nexans Australmold
Building 2/ 69 Dalton Road, Thomastown, Vic, 3074 - Australia
Phone: +61 3 9205 8400
Email: sales@australmold.com.au
Web: www.australmold.com.au

Catalogue also available on Website and Mobile Apps

Find out more about Nexans Power Accessories.


01/2018