Compact Design
The RSHL Smart boasts of a space saving, IP20
housing that fits in a width of 45mm and can be
mounted on a standard DIN rail. While being very
compact the device also provides for a number of
Smart features.
Space
Optimization
Inventory
Reduction
Diagnostic
Warning
• Its switching system involves moving contacts that are prone to deterioration and have a limited lifespan
• The switch-over from wye to delta generates unwanted current spikes
• It is not always capable of providing smooth mechanical drive motion
• It offers no benefits during stopping
• It takes up precious space in the electrical panel
Peak Current Reduction
By limiting high currents caused during motor
starting, consumers reduce the load on supply
networks. Energy utility companies are encouraging
this practice with advantageous billing schemes.
RSHL can help consumers benefit from these lower
energy cost incentives. The RSHL Smart comes with
a number of preset programs, providing a selection of
different start/stop times, initial voltage, ramp profi-
les, which are conveniently selected to cover the
majority of load applications. In addition the RSHL
Smart can start motors using the Current Limit fun-
ction. In this mode, the user is able to choose from
four different current levels, depending on the type of
load.
Limit Level = I 52.5A (350%)
INominal = 15A
Over-temperature Monitoring
If the motor is equipped with a PTC sensor
(Thermistor), this can be connected directly into
the RSHL Smart, providing a motor
over-temperature alarm function. The 18A
models also provide for a device over-
temperature alarm.
Motor PTC
RSHL MIDI SMART
Motor Reversing
The RSHL offers the possibility to enable and disable
phase sequence monitoring for motor reversing
applications. This allows for the connection of a
reversing solid state relay or contactor between the
mains supply and the softstarter. It also allows auto-
matic softstart with every phase reversal without the
need for extra control of the softstarter.
Applications
The RSHL Smart is a general purpose softstarter.
Typical applications include pumps, compressors,
fans, hydraulic systems, conveyors, grinders, mills,
mixers, lathes, circular saws, machine tools, aera-
tors, granulators, shredders, bucket elevators, pal-
letisers, centrifuges, presses, wire drawing machi-
nes, agitators, industrial dryers and washing
machines, carousels, bottling machines, blowers,
car wash and can making machines.
Delivering Performance
Soft start / Soft stop - the best pro-
tection against motor and equip-
ment wear. Direct start or star delta
start are today’s most common
motor starters. Despite technical
improvements on motors as well
as contactors, jerky starting and
stopping could not be eliminated.
Damage to motor bearings and
gearboxes, premature wear, fre-
quent faults on conveyor belts and
goods which fall over when starting
transport mechanisims are some of
the consequences.
HVAC
Ambient temperatures in different environments are
kept uniform and cool by means of centrifugal or
propeller ventilators.
The control is generally enclosed inside small cabi-
nets and exposed to hot ambient temperatures.
For office/household units safety is an issue and a
Motor Controller with thermal protection and high
operating ambient temperature is the solution.
Compressors
Reciprocating compressors are used for high pres-
sure cleaning of tanks, vessels, sewer lines, boilers
and tubes, steel mill de-scaling and also paint
removal. Motor Controllers will prevent pressure
surges and extend the lifetime of piping systems,
valves and couplings.
Pumps
Pumps are used in an extremely wide variety
of applications. Direct-on-line starting can cause
interference to equipment such as computers and
lighting, located in close proximity to the pumps.
A Carlo Gavazzi Soft Start Motor Controller can
increase pump speed more gently, hence reducing
inrush current. When a pump is stopped suddenly,
the pressure surges and results in fluid hammer.
The Soft Starter eliminates this vibration within
the hydraulic system and reduces down-time and
maintenance costs.
Application Simplified Space Diagnostic
Durability Set-up Optimization Warning
Compact Design
SPACE SAVER! Compact starter solution for induc-
tion motors up to 22kW (400V)
Cost
Saving
Market Applications
Conveyors
Ease of setting makes VariFlex2
versatile for a long list of conveyor
applications. Main Features
Locations: Transportation of bottles • AC variable speed drive for use
in bottling plants, Letter or package with AC induction motors
sorting in postal services, Cement • Input voltage range:
powder conveyors in construction. 1-ph 110VAC, 1-ph 230VAC, Conformity
Fans and HVAC 3-ph 230VAC and 3-ph 480VAC All VariFlex2 are approved
•Single fan and Multi fan for basic • Only 2 physical frame sizes according to the related European
duty assist. • Speed Setting by buttons and North American safety
•Heat ventilation • 2-step speeds setting standard. Conforms to EMI radio
•Air conditioning • Built-in 12VDC for external standard and EMS immunity
•Greenhouse/room application standard EN 61800-3 for industrial
•Compressor/Freezing. • Full motor terminals protection sites. Class A Built-in filter for
Packaging • DIN rail or panel mounting. models with “F” option.
Development of turnkey automation • Breaking transistor built-in
packaging and moulding machinery (only for RVDFB series)
systems. • IP20 and IP65 protection degree
VariFlex2
Market Application
Conveyors
Ease of setting makes VariFlex2 versatile for a long list
of conveyor applications.
Locations: Transportation of bottles in bottling plants
Letter or package sorting in postal services
Cement powder conveyors in construction
Packaging
Development of turnkey automation packaging and
moulding machinery systems.
General purpose
Provides a powerful solution for most
motor applications:
• Automated Bottling Plants
• Lab Coagulation Line
• Air Bag Sealer
• Gas-Fire Boiler
• Paint Mixer
• Tube Straightner
• Car Wash
• Plastic Film Winder
• Winding - Drawing
• Food Mixers
• Olive Pitting
• Milling machine
• String – Synthetic for Tennis Racquets
• Top Rollers for Glass Float Rollers
VariFlex2
Environmental Data
• Operating temperature: -10°C to +40°C (+50°C without sticker) (+14°F to +104°F / +122°F)
Front View Side View Bottom View Front View Side View Bottom View
132/5.12”
140/5.51”
72/2.83” 118/4.65” 118/4.65” 171/6.73”
Technical Specifications
Frame Size Nominal Motor Power Rated Output Output Max. momen-
Voltage AC Supply Rated Weight
Current Voltage and tary Power
Rating Phase Size 1 Size 2 HP kW Capacity kVA Kg/lb
A Frequency Loss Time
(+10% ÷ -15%)
100 - 120VAC
0 ÷ 200Hz
0 ÷ 480V,
3-Phase - RVDFB340150F 2.00 1.50 3.8 2.90 3-phase 2.00 1.62/3.55
- RVDFB340220F 3.00 2.20 5.2 4.00 1.68/3.70
Front View Side View Bottom View Front View Side View Bottom View
204.82/8.06”
295/11.61”
Technical Specifications
Frame Size Nominal Motor Power Rated Output Output Max. momen-
Voltage AC Supply Rated Weight
Current Voltage and tary Power
Rating Phase Size 1 Size 2 HP kW Capacity kVA Kg/lb
A Frequency Loss Time
RVDFA120020FES - 0.25 0.20 1.4 0.53 3.4/7.50
0 ÷ 240V, 0 ÷ 200Hz
(+10% ÷ -15%)
200 - 240VAC
Contactors, Overloads
and Manual Motor Starters
Mini-Contactors and Overloads
• Up to 20 Amps or 7.5HP
Midi-Contactors and Overloads
• Up to 160 Amps or 75HP
Power-Contactors and Overloads
• Up to 900 Amps or 600HP
Manual Motor Starters
• 32, 63 and 100 Amp Frame Sizes
Introduction
CARLO GAVAZZI is proud to present our expanded range of contactors and
overloads, as well as our comprehensive offering of manual motor starters.
The product offering starts with Mini-Contactors in a compact 12 amp frame User Diagnostic
Friendly Warning
size, followed by Midi-Contactors in up to 100 amp frame sizes, and topped off
with the Power-Contactors which offer up to 800 amp frame sizes.
To complement the contactors, Thermal Overloads are offered for each
frame size, available in several setting ranges. Additionally, the Manual Motor Long Term Cost
Reliability Saving
Starters are available in 32, 63 and 100 amp frame sizes.
Definite purpose contactors, electronic overloads, enclosed manual
motor starters and other contactor accessories are also available. For
these and more of our motor control products, such as push buttons, soft
starts, variable frequency drives, see the back cover. Please contact us or
visit our website for more details.
To specify our contactor products, we have also
set up an easy-to-use Product Selection Guide at:
www.GavazziOnline.com/Contactors
CGM Mini-Contactors for use with CC Midi-Contactors for use with CC Power-Contactors
Overloads or Manual Motor Starters Overloads or Manual Motor Starters for use with Overloads
(Up to 20 Amps or 7.5HP) (Up to 160 Amps 75HP) (Up to 900 Amps or 600HP)
Compact in size,
yet powerful in
performance...
CGMS
Screw Clam
CGMC
Connectio
p Cage Clam CGMF
n p
Connectio
n
Fast-on CGMP
Connectio Solder Pin
n
Connectio
n
Solder pin
s
from the b extend
ack
mounting/ for PCB Reversing
electrical
Power Contactor Overload Starte
with Overl r
connectio Contactor
n
CC 150 S A 24 GT 150 oad Start er 50A
ConStactor
with Overl
Magnetic Amperage Size Type Terminal Type Coil Type Coil Voltage Bimetallic Frame Size Class Terminal Type oaRanges
Setting d
Midi -Contactor Midi-Overload (Must match (Use upper
contactor limit in part )
130 - 130A BLANK - S - Screw A - AC type 24 - 24V 150 - 130, 150A BLANK - 10 S - Screw 34 ~ 50A
150 - 150A 3-pole L - Lug (130A) D - DC type & 225 - 185, 225A L - 20 L - Lug (150A 45 ~ 65A
185 - 185A /4 - 4-pole and 150 only AD -AC/DC types 500 - 500V 400 - 265, 330, only) 54 ~ 75A
• Compact size with powerful
225 - 225A
265 - 265A
• cUL, CE and RoHS 400A • Bimetallic overloads
800 - 500, 630,
63 ~ 85A
65 ~ 100A
performance 330 - 330A 800A 80 ~ 105A
400 - 400A
• Approx. 2 ¼ cubic inches
500 - 500A
630 - 630A
Convenience • Manual motor starters
• Side or top mounted auxiliary
85 ~ 125A
95 ~ 130A
110 ~ 150A
(55 cubic mm) 800 - 800A
• Cost effective solution contact(s)
100 ~ 160A
120 ~ 185A
160 ~ 240A
• One frame size for three current • One NO or NC auxiliary contact • Reversing interlock kit (with wires) 200 ~ 330A
ratings (standard)
260 ~ 400A
400 ~ 600A
• Surge absorber unit 520 ~ 800A
• Up to 7.5HP motor rating • DIN rail, back panel or PCB • Separate mounting unitGT150
for
• Up to 20A resistive rating mounting overloads GT225
GT400
• AC or DC control voltage • Light in weight and requires • Direct adaptor bridge for manual
GT800
• Four connection types minimal panel space motor starter and mini-contactor
(shown in the picture above) • Captive screw clamp terminals • Mounting unit for manual motor
(on CGMS type) starter, direct adaptor bridge and
mini-contactor
Ordering Guide
Mini-Contactor Overload
CGM S – 9 A – 120 – 10 CGT – 12 M – 0.16A
Magnetic 3-Pole Application and Amperage Size Coil Type Coil Voltage Built-in Auxiliary Bimetallic Amperage Size Type Setting Ranges
Mini-Contactor Terminal Style Contact Mini-Overload (Use upper limit
Combination in part number)
Non-Reversing 6 - 6A A - AC Coil 24 - 24V 10 - 1 NO 12 - Up to 12A M - Mini 0.1 ~ 0.16A
S - Screw (std.) 9 - 9A D - DC Coil 120 - 120V 01 - 1 NC 0.16 ~ 0.25A
F - Fast On 12 - 12A 0.25 ~ 0.4A
C - Cage Clamp 0.4 ~ 0.63A
P - Solder Pin 480 - 480V 0.63 ~ 1A
Reversing Type 1 ~ 1.6A
U- Screw (standard) See data sheet 1.6 ~ 2.5A
CU - Cage Clamp for full offering 2.5 ~ 4A
FU - Fast On 4 ~ 6A
PU - Solder Pin 5 ~ 8A
6 ~ 9A
7 ~ 10A
9 ~ 13A
Fast-on Optional
CGMF Connection
Types
Cage Clamp
Standard CGMC
Version
with Screw
Clamp
Connection Solder Pin
CGMS CGMP
9 – 13A
See page 4 for all ranges
! ! CGMS Mini-Contactor
&
130 - 130A BLANK - S - Screw A - AC type 24 - 24V 150 - 130, 150A BLANK - 10 S - Screw 34 ~ 50A
150 - 150A 3-pole L - Lug (130A) D - DC type & 225 - 185, 225A L - 20 L - Lug (150A 45 ~ 65A
185 - 185A /4 - 4-pole and 150 only AD -AC/DC types 500 - 500V 400 - 265, 330, only) 54 ~ 75A
225 - 225A 400A 63 ~ 85A
265 - 265A 800 - 500, 630, 65 ~ 100A
330 - 330A 800A 80 ~ 105A
400 - 400A 85 ~ 125A
500 - 500A 95 ~ 130A
630 - 630A 110 ~ 150A
800 - 800A 100 ~ 160A
120 ~ 185A
160 ~ 240A
200 ~ 330A
260 ~ 400A
400 ~ 600A
520 ~ 800A
GT150
GT225
GT400
GT800
Mini-Contactor Overload
CGM S – 9 A – 120 – 10 CGT – 12 M – 0.16A
Magnetic 3-Pole Application and Amperage Size Coil Type Coil Voltage Built-in Auxiliary Bimetallic Amperage Size Type Setting Ranges
Mini-Contactor Terminal Style Contact Mini-Overload (Use upper limit
Combination in part number)
Non-Reversing 6 - 6A A - AC Coil 24 - 24V 10 - 1 NO 12 - Up to 12A M - Mini 0.1 ~ 0.16A
S - Screw (std.) 9 - 9A D - DC Coil 120 - 120V 01 - 1 NC 0.16 ~ 0.25A
F - Fast On 12 - 12A 0.25 ~ 0.4A
C - Cage Clamp 0.4 ~ 0.63A
P - Solder Pin 480 - 480V 0.63 ~ 1A
Reversing Type 1 ~ 1.6A
U- Screw (standard) See data sheet 1.6 ~ 2.5A
CU - Cage Clamp for full offering 2.5 ~ 4A
FU - Fast On 4 ~ 6A
PU - Solder Pin 5 ~ 8A
6 ~ 9A
7 ~ 10A
9 ~ 13A
Ordering Guide
Midi-Contactor Overload
CC 9 S A 120 – GT 32 S 0.16A
Magnetic 3-pole Amperage Size Type Terminal Type Coil Type Coil Voltage AC Coil Auxiliary Bimetallic Frame Size Class Terminal Type Setting Ranges
Midi -Contactor Frequency Contact s Midi-Overload (Must match (Use upper
contactor limit in part )
number)
9 - 9A BLANK - S - Screw A - AC type 24 - 24V BLANK BLANK 32 - 9, 12, 18A BLANK - 10 S - Screw 0.1 ~ 0.16A
12 - 12A 3-pole L - Lug (>50A) D - DC type 120 - 120V -50/60 Hz -Standard 22, 32, 40A L - 20 L - Lug (≥35A) 0.16 ~ 0.25A
18 - 18A /4 - 4-pole & 50Hz - 50Hz only arrangement 65 - 50, 65A 0.25 ~ 0.4A
22 - 22A 600 - 600V 60Hz - 60Hz only NOAUX 75 - 75, 85, 100A 0.4 ~ 0.63A
32 - 32A -No Aux. 0.63 ~ 1A
40 - 40A Contact (>=32A) 1 ~ 1.6A
50 - 50A Preliminary Data 1.6 ~ 2.5A
65 - 65A 2.5 ~ 4A
75 - 75A CGE 22 – 3P – 22AN 4 ~ 6A
85 - 85A 5 ~ 8A
100 - 100A Electronic Frame Size Protection Setting Range 6 ~ 9A
Midi Overload (Use upper 7 ~ 10A
limit in part ) 9 ~ 13A
22 - 9, 12, 18, 22A Direct Mount CGE22 12 ~ 18A
40 - 32, 40A 22 and 40AF 0.3 ~ 1.5AN 16 ~ 22A
80 - 50, 65, 75, 85A 2P - 2-Pole 1 ~ 5AN 18 ~ 25A
3P - 3-Pole 4.4 ~ 22AN 22 ~ 32A
3PR -3-pole 24 ~ 36A
CGE40 28 ~ 40A
Separate Mount 4 ~ 20AN 34 ~ 50A
All CGE sizes 8 ~ 40AN 45 ~ 65A
2S - 2-Pole 54 ~ 75A
3S - 3-Pole CGE80 63 ~ 85A
3SR - 3-Pole 16 ~ 80AN 70 ~ 95A
80 ~ 100A
Through-Hole (Setting Range Guide)
22 and 40AF GT32
2T - 2-Pole GT65
3T - 3-Pole GT95
3TR - 3-Pole
11
For Heavyweight
Applications
up to 900 Amps
Thermal Overloads Bimetallic, 3-Pole Differential GT150 GT225
Range 34 ~ 50A 65 ~ 100A
to to
110 ~ 150A 160 ~ 240A
GT400 GT800
85 ~ 125A 200 ~ 300A
to to
85 ~ 400A 520 ~ 800A
$ AI Insulation Barrier
% GT Thermal Overload
#
^ ^ AR Interlock
$
%
Ordering Guide
Power Contactor Overload
CC 150 S A 24 GT 150 S 50A
Magnetic Amperage Size Type Terminal Type Coil Type Coil Voltage Bimetallic Frame Size Class Terminal Type Setting Ranges
Midi -Contactor Midi-Overload (Must match (Use upper
contactor limit in part )
number)
130 - 130A BLANK - S - Screw A - AC type 24 - 24V 150 - 130, 150A BLANK - 10 S - Screw 34 ~ 50A
150 - 150A 3-pole L - Lug (130A) D - DC type & 225 - 185, 225A L - 20 L - Lug (150A 45 ~ 65A
185 - 185A /4 - 4-pole and 150 only AD -AC/DC types 500 - 500V 400 - 265, 330, only) 54 ~ 75A
225 - 225A 400A 63 ~ 85A
265 - 265A 800 - 500, 630, 65 ~ 100A
330 - 330A 800A 80 ~ 105A
400 - 400A 85 ~ 125A
500 - 500A 95 ~ 130A
630 - 630A 110 ~ 150A
800 - 800A 100 ~ 160A
120 ~ 185A
160 ~ 240A
200 ~ 330A
260 ~ 400A
400 ~ 600A
520 ~ 800A
GT150
GT225
GT400
GT800
Mini-Contactor Overload
CGM S – 9 A – 120 – 10 CGT – 12 M – 0.16A
Magnetic 3-Pole Application and Amperage Size Coil Type Coil Voltage Built-in Auxiliary Bimetallic Amperage Size Type Setting Ranges
Mini-Contactor Terminal Style Contact Mini-Overload (Use upper limit
Combination in part number)
Non-Reversing 6 - 6A A - AC Coil 24 - 24V 10 - 1 NO 12 - Up to 12A M - Mini 0.1 ~ 0.16A
S - Screw (std.) 9 - 9A D - DC Coil 120 - 120V 01 - 1 NC 0.16 ~ 0.25A
F - Fast On 12 - 12A 0.25 ~ 0.4A
C - Cage Clamp 0.4 ~ 0.63A
16 P - Solder Pin To instantly view a data480
sheet
- 480V and specify products, visit www.GavazziOnline.com 0.63 ~ 1A
Reversing Type 1 ~ 1.6A
U- Screw (standard) See data sheet 1.6 ~ 2.5A
CU - Cage Clamp for full offering 2.5 ~ 4A
Manual Motor Starters
GMS 11 Models
High Performance
Manual motor starter includes
Midi-Contactor
short-circuit, overload, phase
Manual
CC
Motor
loss protection
Magnetic 3-pole
Midi -Contactor
9
functions with
Amperage Size Type
S
Terminal Type
A
Coil Type
Starters
high performance and reliability.
And also this manual motor starter,
9 - 9A
12 - 12A
BLANK -
3-pole
S - Screw
L - Lug (>50A)
A - AC type
D - DC type
This isUL508
a global product.
18 - 18A /4 - 4-pole
listed device features a
22 - 22A
32 - 32A
maximum short circuit current rating
40 - 40A
50 - 50A
65 - 65A
of up to 50kA for all frame sizes, at
75 - 75A
85 - 85A
3-phase 480VAC. 100 - 100A
10 13 CC (9~100A) Midi-Contactor
11 16
on
e
releas
TRIP
off
12 13 15
14
45mm Spacing 54mm Spacing 63mm Spacing Jumper 54mm Spacing 63mm Spacing Terminal cover Supply connector
(rated 63A) (rated 63A) (rated 63A) (rated 120A) (rated 120A)
Type MSVGW45-14-2 MSVGW54-14-2 MSVGW63-14-2 MSVGW45-SH MSVCPM25412 MSVCP36312 MSVB54 MSVGWE1-14
Description For 2 GMS-32S/H For 2 GMS-32S/H For 2 GMS-32S/H For connecting For 2 GMS-63 For 2 GMS-63 3 Pole 3 Phase input
+ accessories + accessories GMS-32S + accessories protective cover terminal 63A
(side mnt aux sw) (side mnt W/ GMS-32H (side mnt aux sw) for MSVGW..
undervoltage
or shunt trip)
Type MSVGW45-14-3 MSVGW54-14-3 MSVGW63-14-3 MSVCPM35412 MSVCP36312 MSVTA120 MSVBTC50E
Description For 3 GMS-32S/H For 3 GMS-32S/H For 3 GMS-32S/H For 3 GMS-63 For 3 GMS-63 3 Pole 3 Phase Input
+ accessories + accessories + accessories protective cover terminal 120A
(side mnt aux. sw) (side mnt (side mnt aux. sw) for MSVCP..
undervoltage
or shunt trip)
Type MSVGW45-14-4 MSVGW54-14-4 MSVGW63-14-4 MSVCPM45412 MSVCP46312
Description For 4 GMS-32S/H For 4 GMS-32S/H For 4 GMS-32S/H For 4 GMS-63 For 4 GMS-63
+ accessories + accessories + accessories
(side mnt aux. sw) (side mnt (side mnt aux. sw)
undervoltage
or shunt trip)
Type MSVGW45-14-5 MSVGW54-14-5 MSVGW63-14-5
Description For 5 GMS-32S/H For 5 GMS-32S/H For 5 GMS-32S/H
+ accessories + accessories
(side mnt aux. sw) (side mnt
undervoltage
or shunt trip)
Features:
• Universal mounting plates
• Straight through wiring
• Auxiliary contact block(s) available
• Optional DIN rail mounting
• Optional lug terminals
• Cost effective
• Low coil VA
• Quiet operation
Common Applications
Heating
Ventilation
Air Conditioning
Refrigeration
Lighting
Elevators
Pumps and Compressors
Food and Beverage Industry
Pools and Spas
Welding
CGDP- CGDP- CGDP- CGDP- CGDP- CGDP- CGDP- CGDP- CGDP- CGDP- CGDP- CGDP-
Catalog Number
1020 1520 2020 1025 1525 2025 1030 1530 2030 1040 1540 2040
Number of Poles 1 1+ 2 1 1+ 2 1 1+ 2 1 1+ 2
shunt shunt shunt shunt
Terminal Type Screw Terminals (Standard) or Box Lug (Optional with L Suffix)
Top Cover With Top Cover (Standard) or Without Top Cover (Optional with S Suffix) With Top Cover (Standard)
Rated Insulation Voltage (Ui)UL/IFC 600/660
Rated Operating Voltage (Ue)UL/IFC 600/660
Rated Thermal Current (Ith)UL/IFC 30 35 40 50
Full load amps (FLA) 20 25 30 40
Locked
1 phase Max HP
amps
UL 508 (FLA) 240/277V 3HP/17A 3HP/17A 5HP/28A 7.5HP/40A
Rated 220V 20 25 30 40
1 phase
Max HP
rotor
240/277V 120 150 180 240
ARI 780 amps 480V 100 125 150 200
(LRA)
A 600V 80 100 120 160
Resistive load amps (RES)A 30 35 40 50
1 phase 3 phase Max HP 3 phase Max HP 1 phase Max HP
Dimensions (mm) For Models: CGDP-3020(L)~3040(L) Auxiliary contacts for 3-pole version
Mtg.
Mtg.
CGDPR-3040
rotor
240/277V 120 150 180 240
ARI 780 amps 480V 100 125 150 200
(LRA)
A 600V 80 100 120 160
Resistive load amps (RES)A 30 35 40 50
1 phase 3 phase Max HP 3 phase Max HP 1 phase Max HP
Dimensions (mm) For Models: CGDP-3020(L)~3040(L) Mechanical interlock for 3-pole version
Mtg.
Mtg.
CGDP ■ ■ ■ ■ ■ ■ ■ ■ 5 ■ ■
Series Accessories
CGDP : Non-Reversing Definite Purpose Blank : With Top Cover (Standard)
CGDPR : Reversing Definite Purpose (3 Pole Only) S : Without Top Cover
T : With Anti-dust Plate
Pole Configuration
10 : 1 Pole 15 : 1 Pole + Shunt Auxiliary Contacts
20 : 2 Pole 30 : 3 Pole Blank : Standard (No Aux. Prop)
A : One 3A Aux (Right side x 1)
Amperage Rating B : Two 3A Aux (Both sides x 1)
20: 20 Amps 30: 30 Amps C : Three 3A Aux (Right x 2, Left x 1)
25: 25 Amps 40: 40 Amps Only available on 3-pole models
Installation of Accessories
Assembling a pair of
reversing contactors
with a mechanical Side-mounting auxiliary
interlock contact set available
for 3-poles versions
Hybrid Relays
RMD1H Series:
Compact One Pole up to 20A
Up to 77oF (25oC)
Up to 6 cycles per minute
RMD2/3H Series:
Two and Three Pole up to 40A
For up to 140oF (60oC)
Up to 20 cycles per minute
Making both ends meet...
Using the RMD merges the benefits of the longevity of solid state technology with the
power of electro-mechanical technology and aims to:
Space
Optimization
Diagnostic
Warning
Selection Guide - RMD2 and RMD3: Two and Three Pole Hybrid Relays
Rated Blocking Number of Rated Rated Operational Current at 60o C
Operational Voltage Switched Control
Voltage Poles Voltage
30 Arms 40 Arms
240Vrms 600Vp 2 24 VAC/DC RMD2H24LA30 RMD2H24LA40
(1phase loads)
120 VAC RMD2H24MA30 RMD2H24MA40
(3phase delta)
240 VAC RMD2H24HA30 RMD2H24HA40
240Vrms 600Vp 3 24 VAC/DC RMD3H24LA30 RMD3H24LA40
(3phase delta)
120 VAC RMD3H24MA30 RMD3H24MA40
240 VAC RMD3H24HA30 RMD3H24HA40
480Vrms 600Vp 3 24 VAC/DC RMD3H48LA30 RMD3H48LA40
(3phase star
120 VAC RMD3H48MA30 RMD3H48MA40
+ neutral)
240 VAC RMD3H48HA30 RMD3H48HA40
System Durability
Cost Effective
Further comparison between the starting and 45
20
better package and is suitable where high frequency 15
of switching is needed. 10
5
0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
Number of System Switching Cycles (106)
HVAC
• Baseboard Heaters
Minimal heat emission
• Duct Heaters
Galvanic isolation between input and output connections
• Coffee Machines
Optimal duty cycle
• Pizza Ovens
RMD1H slimline solution
White Goods
Time
Saving
Emergency Systems
Emergency stop devices are generally Short-Handle
connected in the safety circuit of a machine
or plant, and are of particular importance Selector
for their control system. In case of a fault Switches
or accident, the secure function and quick
accessibility of an emergency stop device
can be crucial for saving lives, limiting the
degree of injury to personnel or the extent
of damage to a machine. Long-Handle
Selector
Switches
Product Features
AC and DC Supply Voltage
All illuminated push buttons, short-handle
Mushroom
selector switches and pilot lights have a Push Buttons
wide range of supply voltages: 6, 12, 24, 48
or 110 VAC/DC; 220 VDC; 220 or 380 VAC.
Six Colors
They are available with a various selection
of colors: Red, Green, Yellow, White, Blue Red
and Black.
Emergency Stop
Actions Push Buttons
The switch function can be maintained or
spring return. In a maintained the actuator
stays in thrown position (on-off). In a spring
return the switch must be held in position
and it reverts to its normal position when the I/O Push Buttons
actuating force is removed.
and
Key Switches
Pilot Lights
*
*
*
High Lens
Pilot Light
*
Low Lens
Pilot Light
Teeth Lens
Pilot Light
PB 22S F Standard Flush Push Buttons PB 30F KM4 1R Flush Key-reset Emergency Stop Ø40mm Push Buttons
1
PB 22S IF Standard Flush Illuminated Push Buttons PB 22S SRS Standard Short-handle Selector Switches
PB 22B F Bezel Flush Push Buttons PB 22S ISRS Standard Illuminated1 Short-handle Selector Switches
1
PB 22B IF Bezel Flush Illuminated Push Buttons PB 22B SRS Bezel Short-handle Selector Switches
PB 30F F Flush Push Buttons PB 22B ISRS Bezel Illuminated1 Short-handle Selector Switches
1
PB 30F IF Flush Illuminated Push Buttons PB 30F SRS Flush Short-handle Selector Switches
PB 22S E Standard Extended Push Buttons PB 22S LRS Standard Long-handle Selector Switches
1
PB 22S IE Standard Illuminated Extended Push Buttons PB 22B LRS Bezel Long-handle Selector Switches
PB 22B E Bezel Extended Push Buttons PB 30F LRS Flush Long-handle Selector Switches
1
PB 22B IE Bezel Illuminated Extended Push Buttons PB 22S KRS Standard Key Selector Switches
PB 30F E Flush Extended Push Buttons PB 30F KRS Flush Triangle-Key Selector Switches
1
PB 30F IE Flush Illuminated Extended Push Buttons PB 22S IO 0RG Standard I/O Rectangular Push Buttons
PB 22S M4 Standard Mushroom Ø40mm Push Buttons PB 22S IOL 0RG Standard Illuminated1 Rectangular I/O Push Buttons
1
PB 22S IM4 Standard Illuminated Mushroom Ø40mm Push Buttons PB MB M Metal Holder
PB 30F M4 Flush Mushroom Ø40mm Push Buttons PA LAMP Lamp Element with LED
1 2
PB 30F IM4 Flush Illuminated Mushroom Ø40mm Push Buttons PA2 Contact Block Snap 010/1 100/1 020/1 200/1 110/1
PB 22S M6 Standard Mushroom Ø60mm Push Buttons PA2 Contact Block Slow 010/2 100/2 020/2 200/2 110/2
1
PB 22S IM6 Standard Illuminated Mushroom Ø60mm Push Buttons PL 22 SHL Pilot Light High Lens standard size
PB 22B M6 Bezel Mushroom Ø60mm Push Buttons PL 22 CHL Pilot Light High Lens compact size
1
PB 22B IM6 Bezel Illuminated Mushroom Ø60mm Push Buttons PL 22 SRL Pilot Light Concentric Lens standard size
PB 30F M6 Flush Mushroom Ø60mm Push Buttons PL 22 CRL Pilot Light Concentric Lens compact size
1
PB 30F IM6 Flush Illuminated Mushroom Ø60mm Push Buttons PL 22 SLL Pilot Light Low Lens standard size
PB 22S EM4 1R Standard Red Emergency Stop Ø40mm Push Buttons PL 22 CLL Pilot Light Low Lens compact size
PB 22B EM4 1R Bezel Red Emergency Stop Ø40mm Push Buttons PL 22 STL Pilot Light Teeth Lens standard size
PB 30F EM4 1R Flush Red Emergency Stop Ø40mm Push Buttons PL 22 CTL Pilot Light Teeth Lens compact size
PB 22S EM6 1R Standard Red Emergency Stop Ø60mm Push Buttons PL 22 SFL Flashing Pilot Light
PB 22B EM6 1R Bezel Red Emergency Stop Ø60mm Push Buttons PL 22 STC Pilot Light Two Colours
PB 30F EM6 1R Flush Red Emergency Stop Ø60mm Push Buttons PL 22 SFBZ R Pilot Light Flashing Buzzer
PB 22S KM4 1R Standard Key-reset Emergency Stop Ø40mm Push Buttons PL 22 SBZ K Pilot Light Buzzer
1
= To choose also the lamp element in order to get the lighting function 2
= for example: PA2 110/1 is a contact block with 1NO + 1NC snap action.
Two Pole
Solid State Contactor
Reversing
Solid State Contactor
Three Pole
Solid State Contactor
REC2B
A three-phase contactor with REC2R
two switched poles, while the
other pole connects the mains A three-phase reversing
directly to the motor. This REC3B contactor in which two poles
version can switch motors up to interchange the mains
4kW (5Hp) and is the most A three-phase contactor, in
connection, while the other
compact solid state motor which all three poles are
pole is a direct connection
contactor on the market, which switched. Three pole switching
from the mains to the motor.
employs SCR technology. It is a eliminates any phase imbalance
Motors up to 3kW (3Hp) can
more economical version of the and provides a safer switching
be reversed.
REC3B Series. solution. This option can switch
motors up to 3kW (3Hp)
A Solid State Idea…
• To switch on and off (or reverse) three phase motors with short duty cycles, with the ability to do so more frequently
• To cut down on long term costs related to mechanical contactor replacements and maintenance
• To drastically reduce system downtime, thus maximizing operations efficiency and profitability
• To guarantee repeatable results with each and every switching operation
• To completely eliminate irritating clicking sounds
• To reverse the direction of three-phase motors with a compact solution
• A solid state switch based upon the latest technology and designed using decades of experience
Long Term
Reliability
Space
Optimization
Cost
Saving
User
Friendly
The output semiconductors will switch on instantaneously upon the application of a control input signal. The
solid state switch has an integrated heatsink that is enclosed in the plastic housing of the REC Series. This
eliminates the need for a protective earth (ground) connection, thus making the switch from a mechanical
contactor easier.
Starting and Running Cost Comparison
REC Series vs Mechanical Contactor
Long-Term Reliability
This is always a priority and is mostly needed in
processes where a system failure is costly since the
raw material being worked upon would have to be
scrapped.
Easy to Install
The REC can be mounted on DIN-rail and also
directly to the enclosure back panel though the
mounting bracket.
Accessories
A selection of motor overload relays can also be mounted directly to the electrical connection. The
adaptor can be snapped to the base of the REC Series in order to also provide a reliable and sturdy
mechanical connection between of the REC Series and the motor overload relay.
Electrical Hoists
Compact
Supermarket Checkouts
Economic
Valve Actuators
Reliability
Conveyor System
Durable
Wood Cutters
Palletizers Robust
Precision
CARLO GAVAZZI
A u t o m a t i o n C o m p o n e n t s
Relays
5168 Relay.qk 12/28/03 12:51 Page 2
Monostable or Bistable
Miniature Power Relays
M15
• Miniature size 15 mm high
• PCB mounting Type
• Monostable or bistable versions
• 4 kV / 8 mm insulation
• Switching capacity 8 A / 250 VAC
• DC coils:
2 to 147 VDC monostable version
2.4 to 84.7 VDC bistable version
• 1 normally open contact or
1 change over contact
• General purpose, industrial electronics
• Sealed according to IP 67 standard
• 4 different pin layout configuration
• Low coil power consumption
M25
• Miniature size 15.7 mm high
• PCB mounting Type
• Monostable version
• 5 kV / 10 mm insulation C
• Switching capacity:
12 or 16 A / 250 VAC 1 pole version
8 A / 250 VAC 2 pole version
• DC coils 5 to 110 VDC
• 1 or 2 change over contacts
• General purpose, industrial electronics
• Sealed according to IP 67 standard
• Low coil power consumption
Relay
TYPE M15 - M15 R1/R2 M25 RMI 2-10 /RMI 4-5 RCP
DIMENSIONS
Height - Length - Width 15 x 29 x 10 15.7 x 29 x 12.7 36 x 28 x 21.5 56 x 35.5 x 35.5
CONTACTS
Configuration 1 CO, 1 NA 1 CO, 2 CO 2 CO, 4 CO 2 CO, 3 CO
Material AgCdO AgCdO Silver alloy Silver alloy
Rated current 8A 8 A, 12 A, 16 A 5 A, 10 A 10 A
Max. switching power 2000 VA 2000VA-3000VA-4000VA 300 W-2500 VA (2 poles) 300 W- 2500 VA
- - 150 W-1250 VA (4 poles) -
Max. contact voltage 380 VAC 440 VAC 250 VAC / 30 VDC 380 VAC
Minimum permissible 100 mA at 24 VDC 100 mA at 24 VDC - 100 mA at 24 VDC
load (Typical value) 10 mA at 10 mVDC (Au) - - -
COIL
Rated voltage DC 3 to 110 VDC 5 to 110 VDC 5 to 110 VDC 6 to 110 VDC
3 to 48 VDC (M15 R1) - - -
3 to 24 VDC (M15 R2) - - -
AC - - 6 to 230 VAC 6 to 230 VDC
Consumption DC 100 mW Vmin 0.4 W 0.9 W 1.3 W
AC - - 1.9 VA 2.1 VA
Operating range 0.7 to 1.7 Vn See data sheet 0.7 to 1.7 Vn -
GENERAL DATA
Electrical life (at max.
switching power) 1 x 105 cycles 1 x 105 cycles 1 x 105 ops (1800 ops/h) 1 x 105
Mechanical life 30 x 106 cycles 1 x 107 cycles 1 x 107 ops (18000 ops/h) 1 x 107
Insulation test VAC (1min)
- Contact/coil 4000 VAC 5000 VAC 3750 VAC Vrms 3750 VAC Vrms
- Open contacts 1000 VAC 1000 VAC 750 VAC Vrms 750 VAC Vrms
- Contact different polarity - 2500 VAC (1 pole) 1250 VAC Vrms 1250 VAC Vrms
Protection category IP 67 IP 67 IP 40 IP 40
Operating temperature -40°C to +70°C -40°C to +85°C -55°C to +70°C -40°C to +55°C
Terminal shape PCB PCB Plug-in and PCB Plug-in
Approvals UL, CSA, VDE, IMQ VDE UL, CSA, VDE, IMQ UL, CSA, VDE, IMQ
S, N, D, F
OPTIONS
AgNi, AgSnO2 AgNi, AgSnO2 - -
Gold plated contacts Gold plated contacts
SOCKETS
CARLO GAVAZZI offers a wide range of printed circuit board and modular DIN rail mount sockets for our various
electromechanical relays. The following optional plug-in blocks are also offered for the DIN rail mount sockets:
M 25 A 001 024 16
A = AgCdO (Standard)
S = AgSnO2
C = AgNi10, Au plated > 3.5 micron
G = AgNi10
RMI A 45 230 AC
A = Soldering Terminals
B = PCB Terminals
8 = Eight Pins
11 = Eleven Pins
RG Series
RG Series
Concentrated Power
Carlo Gavazzi introduces the first solid state relay and contactor
in the smallest DIN dimensions of 17.5mm. The RG series offers
solutions in very compact dimensions saving considerable panel
space. The design is in line with European CE marking
directives, the RoHS directive and is also certified by various
international agencies.
The design of the RG series caters for vibrations up to 2g (5g for Apart from certifications in accordance to US and Canadian
some models) and impact resistance of 15/11 g/ms according requirements as per UL 508 and CSA C22.2 No. 14-10
to the Railway Standards IEC/50155 and EN/IEC standards respectively, the RG series conforms to the harmonised
61373:1999. This ensures that the products functionality is not EN standards EN/IEC 60947-4-2 and EN/IEC 60947-4-3
altered in applications where the solid state switch is used in covering resistive and slightly inductive load applications as well
harsh environments subjected to considerable vibrations. as motor switching. The design also conforms to the new solid
state relay standard EN/IEC 62314. Third party independent
The solid state relay series introduced hereafter, can be mounted certification is also attained through VDE Testing Laboratories.
on any heatsinking surface. Distance between SSR heatsink Additionally, some models are certified by Germanischer Lloyd
mounting holes respects same distance as for 'hockey puck' for use in the marine industry.
switches which allows for retrofitting.
2 CARLO GAVAZZI Automation Components. Specifications are subject to change without notice. Illustrations are for example only.
Solutions for your needs
CARLO GAVAZZI Automation Components. Specifications are subject to change without notice. Illustrations are for example only. 3
RG Series
Options
SSR or Contactor Configuration
The output power terminals can be either in a contactor
configuration, the ‘E’ types or in a solid state relay
configuration, the ‘U’ types.
4 CARLO GAVAZZI Automation Components. Specifications are subject to change without notice. Illustrations are for example only.
Applications
HVAC
The RG design does not include any moving parts or
contacts. The power semiconductors switch on and
off according to the logic signal received from the
temperature controller. In contrast with conventional
SSRs, RG can switch up to 20AAC continuously in a
width of only 17.5mm.
Benefits:
• Reduction of panel space makes it easier for
fitting and also retrofitting of SSR
• Silent operation
Benefits:
• Long operating lifetime
• Environmental friendly
• Promotes health safety in food & beverage
environments
Benefits:
• High Process and machine reliability
• Reduced maintenance and downtime costs
CARLO GAVAZZI Automation Components. Specifications are subject to change without notice. Illustrations are for example only. 5
Slimline RG
RGS, RGC, RGH Series
This new range of solid state switches is designed in a modular
fashion offering great flexibility in adapting solutions for the
various installation needs. Various configurations are available
within the three range of families; the RGS, RGC and RGH
series.
The RGC series offers solutions ready for use as the switch is
equipped with an integrated heatsink. Various ratings, specified
at 40°C, are available. The RGH series is based on the RGC
series but offers higher specifications of blocking voltage and I2t
values versus its RGC counterparts.
• Ratings up to 600VAC, 90AAC in 17.5mm width • Ratings up to 600VAC, 20AAC in 17.5mm, 30AAC in 22.5mm,
• Zero Cross or Instant On (Random) Switching 40AAC in 35mm, 60AAC in 70mm up to 85AAC in 70mm
• DC & AC control ranges: 3-32VDC & • Zero Cross or Instant On (Random) Switching
20-275VAC (24-190VDC) • DC & AC control ranges: 3-32VDC & 20–275VAC (24-190VDC)
• Control green LED indication • Control green LED indication
• Integrated varistor • Integrated varistor
• Motor Ratings according to UL508 • Motor Ratings according to UL508
• 100kArms SCCR • 100kArms SCCR
• E type or U type configuration • E type or U type configuration
• Control spring loaded plug available • Control spring loaded plug available
• Optional Over Temperature Protection by adding suffix ‘P’
• 1600Vp blocking voltage and 6600A2s
as I2t for RGH series
6 CARLO GAVAZZI Automation Components. Specifications are subject to change without notice. Illustrations are for example only.
Slimline RG
RGC1D, RGS1D Series
A photovoltaic installation is a long-term investment with a
determined pay-back time. This can only be sustained if
downtimes are kept to a minimum through the use of reliable
equipment. For this reason, Carlo Gavazzi offers 1-phase Solid
State DC Switches which provide a longer operating lifetime
when compared to electromechanical solutions. This is in
addition to the monitoring and smart control systems as well as
surge protectors that Carlo Gavazzi offers.*
* Ask for more information about EOS - Array Control Systems and L-
Guard Series of Surge protectors from a Carlo Gavazzi representative.
Note: cULus is available for RGC1D only. UR and CSA are available for RGS1D only.
CARLO GAVAZZI Automation Components. Specifications are subject to change without notice. Illustrations are for example only. 7
RGC1F
Integrated Fuse Protection
The RGC1F is a series of solid state contactors with integrated
protection by means of an on-board semiconductor fuse. The
fuse is easily accessible through the front panel of the device and
fuse holders utilised accept a wide range of fuses from various
renowned manufacturers. The series consists of two versions, the
RGC1FA and the RGC1FS.
The RGC1FA is a version including just the solid state switch and
the fuse.
Features
• 35mm product width
• Zero cross switching
• Maximum output voltage up to 600VAC
• Current ratings 20AAC, 30AAC, 40AAC @ 40°C
• DC control range: 4 – 32VDC
• Integrated varistor across output for overvoltage protection
• 100kArms short circuit current rating
• Load loss, open fuse, open SSR & shorted SSR detection
with RGC1FS
8 CARLO GAVAZZI Automation Components. Specifications are subject to change without notice. Illustrations are for example only.
RGC1S
Integrated Current Monitoring
The RG Current Sensing (CS) features integrated current
measurement allowing for monitoring of load current variations.
The solid state switch is TEACHed on the load current to be used
as a reference either remotely or locally through a TEACH button
on the front panel.
The RG CS compares the actual load versus the set point and in
case of deviation >16.67% raises an alarm. Apart from the partial
load failure detection, the RG CS monitors for other fault conditions;
switch over temperature, heater loss, switch short or open circuit.
An alarm output signal is present in any fault condition. A red LED
provides a visual indication. The description of the fault is readily
available through the flashing sequence of this LED.
Note: cULus is available for RGC1S series only. UR and CSA apply for the RGS1S series.
Features
• With or without integrated heatsink
(RGC1S, RGS1S respectively)
• 22.5mm width for max. 30AAC up to 85AAC in 70mm @ 40°C
• Up to 6,600A²s for protection by MCB
• Zero cross switching
• Maximum output voltage up to 600VAC
• DC control range of 4 – 32VDC
• Integrated varistor for overvoltage protection
• LEDs for Control, Load and Alarm status indication
• Alarm output signal for switch or load malfunction
Added Benefits Partial Load Failure Detection for Optimal Process Control
Alarm Output
potential difficulties in alignment and avoids any limitations in the
cross sectional area of cables that might be used.
• Self Taught The alarm output, which is normally closed, opens as soon as current
There is no need to calculate the current flowing through the RG CS and deviates from current set point by >16.67%. The RG CS does not
adjust settings accordingly to have a reference set point. This is simply switch off the output when this alarm is raised but operates in
done through a TEACH button or remote signal which when pressed or accordance to demand. The alarm output self recovers when
applied triggers the RG CS to self TEACH on the load current. monitored load current deviation versus set point is <16.67%. A
consistent temperature control process is thus guaranteed. This
• Connectivity alarm indication of a possibly faulty heater or heater malfunction
The RG CS in a 35mm footprint (rating >30AAC) has box clamp advises of needed intervention without affecting the ongoing
power terminals capable of handling 25mm² cables. Cables can be process.
fitted in the clamp and secured, thus reducing installation times. The
control terminals are double box clamps allowing for safe looping.
CARLO GAVAZZI Automation Components. Specifications are subject to change without notice. Illustrations are for example only. 9
Slimline RG
RG Series
Selection Guide - RGS1..E
Rated Output Blocking Connection Control Rated Operational Current @ 40˚C
Voltage Voltage Control/ Power Voltage 25 AAC 50 AAC 75 AAC 90 AAC
230 VAC, ZC 800Vp Screw / Box Clamp 3-32 VDC RGS1A23D20KGU RGS1A23D30KGU
Screw / Box Clamp 20-275 VAC, RGS1A23A20KGU RGS1A23A30KGU
24-190 VDC
600 VAC, ZC 1200Vp Screw / Box Clamp 4-32 VDC RGS1A60D20KGU RGS1A60D30KGU
Screw / Box Clamp 20-275 VAC, RGS1A60A20KGU RGS1A60A30KGU
24-190 VDC
600 VAC, IO 1200Vp Screw / Box Clamp 4-32 VDC RGS1B60D20KGU RGS1B60D30KGU
600VAC, ZC 1600Vp x/Screw 4-32 VDC E-type RGH1A60D15xKE RGH1A60D20xKE RGH1A60D21xKE RGH1A60D31xKE
20 - 275 VAC, E-type RGH1A60A15xKE RGH1A60A20xKE RGH1A60A21xKE RGH1A60A31xKE
24-190 VDC
Rated Output Blocking Connection Control Connection Rated Operational Current @ 40˚C (I t value in brackets)
Voltage Voltage Control/ Power Voltage Type 40 AAC (1800 A s) 40 AAC (6600 A s) 60 AAC (6600 A s)
600VAC, ZC 1600Vp x/Box clamp 4-32 VDC E-type RGH1A60D40KGE RGH1A60D41xGE RGH1A60D60KGE
20 - 275 VAC, E-type RGH1A60A40KGE RGH1A60A41xGE RGH1A60A60KGE
24-190 VDC
x represents the control connection type, x = K for screw control terminals, x = M for spring pluggable control terminal
Note: ZC = Zero Cross Switching, IO = Instant ON Switching
10 CARLO GAVAZZI Automation Components. Specifications are subject to change without notice. Illustrations are for example only.
Selection Guide - RGC1
Rated Output Blocking Rated Operational Control E-type E-type E-type E-type U-type
o
Voltage Voltage Current @ 40 C Voltage Control/ Power Control/ Power Control/ Power Control/ Power Control/ Power
Screw/ Screw Spring/ Screw Screw/ Box Clamp Spring/ Box Clamp Screw/ Box Clamp
x represents the control voltage type; x = D for 3-32VDC, 4-32VDC for 600V versions; x = A for 20-275VAC, 24-190VDC
y represents the control voltage type; y = D for 5-32VDC; y = A for 20-275VAC, 24-190VDC
CARLO GAVAZZI Automation Components. Specifications are subject to change without notice. Illustrations are for example only. 11
Market Applications
Lighting Control
Digital, high precision light dimming systems are
nowadays used in the entertainment industry.
Performances given in theatres, opera houses, TV
studios and concert halls are enhanced by a number
of special effects. RJ1P..MB can link up to a PC
based system to activate and control the intensity
of stage lights.
SWIR* Heaters
Using RJ1P..MB to control SWIR heaters in
thermoformers and drying applications in the printing
and spray painting industries
Diagnostic
Warning
100 mm
Space
Optimization
Cost
m
Saving
0m
12
45 mm
HVAC
In special purpose buildings such as museums and
medical or scientific laboratories, it is fundamental
to maintain the environment under control by con-
tinuously monitoring the current and voltage of
electric heaters used for climate control. RJ1P..MB
can be integrated into the Building Management
System and allows remote communication with a
simple bus cable.
Indications ...
A green LED on the front panel indicates presence of input
power supply by lighting at half intensity and indicates
load activation by lighting to full intensity. A flashing yel-
low LED indicates DATA transmission/reception and a red
LED indicates an alarm condition.
Connection Examples
Lighting Control
Digital, high precision light dimming systems are
nowadays used in the entertainment industry.
Performances given in theatres, opera houses, TV
studios and concert halls are enhanced by a number
of special effects. RJ1P..MB can link up to a PC
based system to activate and control the intensity
of stage lights.
SWIR* Heaters
Using RJ1P..MB to control SWIR heaters in
thermoformers and drying applications in the printing
and spray painting industries
Diagnostic
Warning
100 mm
Space
Optimization
Cost
m
Saving
0m
12
45 mm
HVAC
In special purpose buildings such as museums and
medical or scientific laboratories, it is fundamental
to maintain the environment under control by con-
tinuously monitoring the current and voltage of
electric heaters used for climate control. RJ1P..MB
can be integrated into the Building Management
System and allows remote communication with a
simple bus cable.
Indications ...
A green LED on the front panel indicates presence of input
power supply by lighting at half intensity and indicates
load activation by lighting to full intensity. A flashing yel-
low LED indicates DATA transmission/reception and a red
LED indicates an alarm condition.
Connection Examples
Versatile
The RJ1P is a single package solution that combines the functionality
of several individual products. The innovative element of this design is
that this solid state contactor is based on microprocessor control.
Multi-function Flexible
The user can select one of five The rotary knob has three unused positions.
pre-configured control types: This provides additional modes to be factory
1. Phase Angle Control customized according to specific application
2. Distributed Full Cycle Control requirements that may arise for large OEMs
3. Burst Control (1 second) and end users.
4. Burst Control (3 seconds)
5. Burst Control (10 seconds)
C
Application Space Long Term Diagnostic
Durability Optimization Reliability Warning
Versatile
The RJ1P is a single package solution that combines the functionality
of several individual products. The innovative element of this design is
that this solid state contactor is based on microprocessor control.
Multi-function Flexible
The user can select one of five The rotary knob has three unused positions.
pre-configured control types: This provides additional modes to be factory
1. Phase Angle Control customized according to specific application
2. Distributed Full Cycle Control requirements that may arise for large OEMs
3. Burst Control (1 second) and end users.
4. Burst Control (3 seconds)
5. Burst Control (10 seconds)
C
Application Space Long Term Diagnostic
Durability Optimization Reliability Warning
SOLITRONS
RJ2A
RJ3A
2- and 3-Poles
Switching types
TYPE SELECTION REPRESENTATIONS
Rated operational Control voltage 2-Pole switching / 1-Pole direct 3-Pole switching
Carlo Gavazzi GmbH
voltage 3x25A (MIDI) 3x32A (POWER) 3x20A (MIDI) 3x25A (POWER) 3x32A (MIDI)* Wien - AUSTRIA
220 VACrms 5 - 32 VDC RJ2A22D25 RJ2A22D32 RJ3A22D20 RJ3A22D25 RJ3A22D32EP Tel: +43 1 888 4112 Fax: +43 1 889 10 53
office@carlogavazzi.at
24 - 275 VAC/ RJ2A22A25E RJ2A22A32E RJ3A22A20E RJ3A22A25E RJ3A22A32EP
24 - 190 VDC Carlo Gavazzi NV/SA
600 VACrms 5 - 32 VDC RJ2A60D25 RJ2A60D32 RJ3A60D20 RJ3A60D25 RJ3A60D32EP Vilvoorde - BELGIUM
Tel: +32 2 257 4120 Fax: +32 2 257 41 25
24 - 275 VAC/ RJ2A60A25E RJ2A60A32E RJ3A60A20E RJ3A60A25E RJ3A60A32EP sales@carlogavazzi.be
24 - 190 VDC
Carlo Gavazzi Inc.
* With integrated fan and over-temperature protection
Mississauga, ON - CANADA
Tel: +1 905 542 0979 Fax: +1 905 542 22 48
GENERAL INFO CONNECTIONS Montreal, PQ - CANADA
Tel: +1 514 644 2544 Fax: +1 514 644 2808
gavazzi@carlogavazzi.com
RJ..22 RJ..60
Carlo Gavazzi Handel A/S
Hadsten - DENMARK
Operational voltage range 24 - 280 VAC 40 - 660 VAC Tel: +45 89 60 6100 Fax: +45 86 98 15 30
Blocking voltage 650 Vp 1200 Vp handel@gavazzi.dk
Rated insulation voltage ≥4000 VACrms ≥4000 VACrms
Carlo Gavazzi OY AB
Switching Zero-cross Zero-cross Helsinki - FINLAND
Frequency range 45 - 65 Hz 45 - 65 Hz Tel: +358 9 756 2000 Fax: +358 9 756 20010
myynti@carlogavazzi.fi
Power factor 0.5 @ 230 VACrms 0.5 @ 600 VACrms
Operating temperature -30˚to +70˚C -30˚to +70˚C Carlo Gavazzi Sarl
Roissy - FRANCE
I2t for fusing (t=10ms) 1800 A2s 1800 A2s Tel: +33 1 49 389860 Fax: +33 1 48 63 27 43
Critical dl/dt ≥50 A/µs ≥50 A/µs french.team@carlogavazzi.fr
Critical dV/dt ≥500 V/µs ≥500 V/µs
Carlo Gavazzi GmbH
Internal Varistor Yes Yes Weiterstadt - GERMANY
LED indication Yes Yes Tel: +49 6151 81000 Fax: +49 6151 81 00 40
kontakt@carlogavazzi.de
CE marking Yes Yes
Approvals UL, CSA UL, CSA Carlo Gavazzi UK Ltd
Aldershot - GREAT BRITAIN
Tel: +44 1 252 339600 Fax: +44 1 252 326 799
For further details please view relevant the datasheet on website sales@carlogavazzi.co.uk
www.carlogavazzi.com/ac
Carlo Gavazzi SpA
Lainate (MI) - ITALY
Tel: +39 02 931 761 Fax: +39 02 931 763 01
DERATING CURVE DISSIPATION CURVE info@gavazziacbu.it
28 Carlo Gavazzi BV
26 80 RJ3..25 Beverwijk - NETHERLANDS
24 Tel: +31 251 22 9345 Fax: +31 251 22 60 55
22 RJ3..20 info@carlogavazzi.nl
20 60
18 RJ3..32 RJ2..32 Carlo Gavazzi AS
16 40 Porsgrunn - NORWAY
14 RJ2..32 RJ2..25 Tel: +47 35 93 0800 Fax: +47 35 93 08 01
12 gavazzi@carlogavazzi.no
RJn..25 20
10
8 RJ3..20 Carlo Gavazzi Lda
6 0 Lisboa - PORTUGAL
20 25 30 35 40 45 50 55 60 65 70 0 5 10 15 20 25 30 35 40 Tel: +351 21 361 7060 Fax: +351 21 362 13 73
Ambient temperature (ûC) Load Current per phase (A) carlogavazzi@carlogavazzi.pt
UL and CSA rating are limited to 30A, due to terminal size Carlo Gavazzi SA
Leioa (Bizkaia) - SPAIN
Tel: +34 94 480 4037 Fax: +34 94 480 10 61
APPLICATIONS DIMENSIONS gavazzi@carlogavazzi-sa.es
Carlo Gavazzi AB
Karlstad - SWEDEN
MIDI
Tel: +46 54 85 1125 Fax: +46 54 85 11 77
gavazzi@carlogavazzi.se
Carlo Gavazzi AG
Steinhausen - SWITZERLAND
Tel: +41 41 747 4535 Fax: +41 41 740 45 40
verkauf_vente@carlogavazzi.ch
Switching of motors
Control of heaters
All dimensions in mm
CARLO GAVAZZI
A u t o m a t i o n C o m p o n e n t s
Distributed by:
CARLO GAVAZZI
A u t o m a t i o n C o m p o n e n t s
SOLITRONS
RJ2A
RJ3A
2- and 3-Poles
Switching types
TYPE SELECTION REPRESENTATIONS
Rated operational Control voltage 2-Pole switching / 1-Pole direct 3-Pole switching
Carlo Gavazzi GmbH
voltage 3x25A (MIDI) 3x32A (POWER) 3x20A (MIDI) 3x25A (POWER) 3x32A (MIDI)* Wien - AUSTRIA
220 VACrms 5 - 32 VDC RJ2A22D25 RJ2A22D32 RJ3A22D20 RJ3A22D25 RJ3A22D32EP Tel: +43 1 888 4112 Fax: +43 1 889 10 53
office@carlogavazzi.at
24 - 275 VAC/ RJ2A22A25E RJ2A22A32E RJ3A22A20E RJ3A22A25E RJ3A22A32EP
24 - 190 VDC Carlo Gavazzi NV/SA
600 VACrms 5 - 32 VDC RJ2A60D25 RJ2A60D32 RJ3A60D20 RJ3A60D25 RJ3A60D32EP Vilvoorde - BELGIUM
Tel: +32 2 257 4120 Fax: +32 2 257 41 25
24 - 275 VAC/ RJ2A60A25E RJ2A60A32E RJ3A60A20E RJ3A60A25E RJ3A60A32EP sales@carlogavazzi.be
24 - 190 VDC
Carlo Gavazzi Inc.
* With integrated fan and over-temperature protection
Mississauga, ON - CANADA
Tel: +1 905 542 0979 Fax: +1 905 542 22 48
GENERAL INFO CONNECTIONS Montreal, PQ - CANADA
Tel: +1 514 644 2544 Fax: +1 514 644 2808
gavazzi@carlogavazzi.com
RJ..22 RJ..60
Carlo Gavazzi Handel A/S
Hadsten - DENMARK
Operational voltage range 24 - 280 VAC 40 - 660 VAC Tel: +45 89 60 6100 Fax: +45 86 98 15 30
Blocking voltage 650 Vp 1200 Vp handel@gavazzi.dk
Rated insulation voltage ≥4000 VACrms ≥4000 VACrms
Carlo Gavazzi OY AB
Switching Zero-cross Zero-cross Helsinki - FINLAND
Frequency range 45 - 65 Hz 45 - 65 Hz Tel: +358 9 756 2000 Fax: +358 9 756 20010
myynti@carlogavazzi.fi
Power factor 0.5 @ 230 VACrms 0.5 @ 600 VACrms
Operating temperature -30˚to +70˚C -30˚to +70˚C Carlo Gavazzi Sarl
Roissy - FRANCE
I2t for fusing (t=10ms) 1800 A2s 1800 A2s Tel: +33 1 49 389860 Fax: +33 1 48 63 27 43
Critical dl/dt ≥50 A/µs ≥50 A/µs french.team@carlogavazzi.fr
Critical dV/dt ≥500 V/µs ≥500 V/µs
Carlo Gavazzi GmbH
Internal Varistor Yes Yes Weiterstadt - GERMANY
LED indication Yes Yes Tel: +49 6151 81000 Fax: +49 6151 81 00 40
kontakt@carlogavazzi.de
CE marking Yes Yes
Approvals UL, CSA UL, CSA Carlo Gavazzi UK Ltd
Aldershot - GREAT BRITAIN
Tel: +44 1 252 339600 Fax: +44 1 252 326 799
For further details please view relevant the datasheet on website sales@carlogavazzi.co.uk
www.carlogavazzi.com/ac
Carlo Gavazzi SpA
Lainate (MI) - ITALY
Tel: +39 02 931 761 Fax: +39 02 931 763 01
DERATING CURVE DISSIPATION CURVE info@gavazziacbu.it
28 Carlo Gavazzi BV
26 80 RJ3..25 Beverwijk - NETHERLANDS
24 Tel: +31 251 22 9345 Fax: +31 251 22 60 55
22 RJ3..20 info@carlogavazzi.nl
20 60
18 RJ3..32 RJ2..32 Carlo Gavazzi AS
16 40 Porsgrunn - NORWAY
14 RJ2..32 RJ2..25 Tel: +47 35 93 0800 Fax: +47 35 93 08 01
12 gavazzi@carlogavazzi.no
RJn..25 20
10
8 RJ3..20 Carlo Gavazzi Lda
6 0 Lisboa - PORTUGAL
20 25 30 35 40 45 50 55 60 65 70 0 5 10 15 20 25 30 35 40 Tel: +351 21 361 7060 Fax: +351 21 362 13 73
Ambient temperature (ûC) Load Current per phase (A) carlogavazzi@carlogavazzi.pt
UL and CSA rating are limited to 30A, due to terminal size Carlo Gavazzi SA
Leioa (Bizkaia) - SPAIN
Tel: +34 94 480 4037 Fax: +34 94 480 10 61
APPLICATIONS DIMENSIONS gavazzi@carlogavazzi-sa.es
Carlo Gavazzi AB
Karlstad - SWEDEN
MIDI
Tel: +46 54 85 1125 Fax: +46 54 85 11 77
gavazzi@carlogavazzi.se
Carlo Gavazzi AG
Steinhausen - SWITZERLAND
Tel: +41 41 747 4535 Fax: +41 41 740 45 40
verkauf_vente@carlogavazzi.ch
Switching of motors
Control of heaters
All dimensions in mm
CARLO GAVAZZI
A u t o m a t i o n C o m p o n e n t s
Distributed by:
RJCS
Switching Solutions for ...
Packaging Equipment
Baggers, shrink tunnels, glue sealers
and sanitation packaging....
Packaging Equipment
Baggers, shrink tunnels, glue sealers
and sanitation packaging....
CARLO GAVAZZI
Automation Components
Scroll compressors started via a direct on line (DOL) method Softstarters provide a means of reducing such high values of
normally require about 3 to 4 cycles to start. The starting inrush currents and the associated effects. Through the
current waveform is characterized by a high inrush peak application of a controlled voltage ramp or a current limiting
current, typically 6 to 8 times the rated compressor current, algorithm, a smoother, jerk-free start is achieved. Ramp-up
which gradually decays until the compressor reaches its time is slightly longer when compared to a DOL start, but still
nominal speed/current. Although this high peak only lasts maintained below 600ms so as to comply with
for about 60ms, such a rapid inrush of current may cause recommendations from scroll compressor manufacturers.
undesirable effects on the system and also neighboring Therefore, softstarters eliminate issues related to light
equipment. Such effects include: flickering, voltage disturbances whilst reducing mechanical
stresses on compressor.
• Voltage fluctuations creating disturbances on neighboring
equipment Additionally, softstarters can also provide further cost benefits
• Light flickering to both OEMs and end users. By Limiting starting current to
• Triggering of protection equipment due to high peaks more than 40% with respect to DOL start current (typical for
in starting current softstarters), lower-rating protection systems and cabling may
• Increased compressor noise and vibration during start be used which means less expensive panel designs. End-
• Excessive stresses on compressor hence reducing users, on the other hand, may apply for cheaper contracts
compressor lifetime with utility companies in view of the lower power
requirements.
3 CARLO GAVAZZI Automation Components. Specifications are subject to change without notice. Illustrations are for example only.
Bro_RSBS_RSBT_150611.qxp:PanelBuilderAutomation 6/22/11 9:02 AM Page 4
RSBS and RSBT softstarters have been do not just start and stop the whilst achieving inrush current
specifically designed for soft starting of compressor…. RSBS and RSBT are reductions >50% when compared to
scroll compressors commonly used in equipped with a number of advanced DOL starting.
HVAC applications. These softstarters functions to protect the compressor
A balanced current is ensured thanks softstarter cool in every situation Without the need of any additional
to RSBT’s control over all the 3 phases without the need of any additional sensors, RSBS and RSBT offer a
which results in a better current heatsink. number of built-in diagnostic functions
reduction performance. Conscious of to protect your system against
the space issues in panels, RSBT is With regards to EMC, RSBS and RSBT potentially harmful conditions such as
housed in a slim 45mm housing. are both Class B (residential) wrong phase sequence (RSBT) and
Internal bypassing of semiconductors compliant for emissions. locked-rotor conditions.
on both RSBS and RSBT keeps the
Additionally, alarms may also be
interfaced to an external panel via an
Intelligent Control auxiliary relay. This feature is
particularly helpful when dealing with
RSBS HP is equipped with an scroll compressor is locked, and will service calls from end-users since it
intelligent algorithm designed for high dynamically adjust the current limit provides additional information on the
pressure starting. During every start, automatically during the ramp-up system fault which results in quicker
the RSBS HP will check whether the period. resolution of service calls.
CARLO GAVAZZI Automation Components. Specifications are subject to change without notice. Illustrations are for example only. 4
Bro_RSBS_RSBT_150611.qxp:PanelBuilderAutomation 6/22/11 9:05 AM Page 5
RSBS Series
Soft Starters
RSBS
Housing (H x W x D) 60.4 x 76 x 137.2 mm
Number of Starts per hour @ 40ºC 12 (for RSBS23..A2V.2C24)
10 (for RSBS23..A2V.2C24HP)
Operational Voltage 230 VAC ± 15%
Operational Frequency 50/60Hz ± 5Hz
Rated Operational Current 25/32AAC
Internally bypassed YES
Integrated Starting Capacitor YES
Approvals CE, UL, cUL, EN 60335-2-40
Protection Degree IP20
Integrated protection
against short cycling Yes
RSBS has a number of built-in diagnostic functions to highlight By limiting the starting current to specified limits, RSBS not only
abnormal conditions which could damage the compressor. eliminates the annoying issue of light flickering but most
RSBS alarms include: importantly it increases the compressor’s lifetime by reducing
the mechanical stresses resulting from high starting current.
• Under-voltage protection (in bypass mode)
• Locked rotor protection RSBS is capable of performing up to 12 starts per hour with an
• Ramp-up time > 1second operational temperature range between -20ºC to 65ºC hence
• Welded relay protection guaranteeing reliable operation even in demanding
• Over-current in bypass mode environments.
Alarms are displayed via an easy to interpret LED flashing RSBS also complies with Class B (residential) limits for
sequence for quicker diagnosis of problems by service conducted and radiated emissions which ensures that
personnel. neighbouring equipment is not negatively affected by any
interference generated by the softstarter switching.
Thanks to its compact dimensions RSBS is an easy fit for
panels with space restrictions. RSBS can be panel or DIN
mounted providing additional installation flexibility. Included
in the compact housing of RSBS, there is a starting capacitor
that provides the necessary starting torque for the compressor.
5 CARLO GAVAZZI Automation Components. Specifications are subject to change without notice. Illustrations are for example only.
Bro_RSBS_RSBT_150611.qxp:PanelBuilderAutomation 6/22/11 9:06 AM Page 6
Optimised Performance
RSBS incorporates a firmware which is that starting current never exceeds
specifically designed for single-phase 40AACrms for compressors rated up
scroll compressors. RSBS is a plug’n to 25AAC and 45AACrms for
play softstarter that requires no compressors rated up to 32AAC thus
additional settings by the user, complying with regulatory limits
resulting in quicker installation and established by utility companies.
easier setup.
RSBS HP provides a dynamic current
RSBS works on a current limiting limit that ensures compressor starting
algorithm via an internal current even at higher starting pressures with a
feedback loop. This feature ensures maximum current limit of 80AACrms.
Flexibility
RSBS can be DIN-rail or panel relay output is available for interfacing
mounted for increased flexibility inside of the alarm output to an external
the panel. An optional auxiliary alarm panel.
CARLO GAVAZZI Automation Components. Specifications are subject to change without notice. Illustrations are for example only. 6
Bro_RSBS_RSBT_150611.qxp:PanelBuilderAutomation 6/22/11 9:06 AM Page 7
RSBT Series
Soft Starters
The most compact 15kW softstarter
for scroll compressors and not only that !!!
• Space Conscious
Panel space saving is becoming more of a crucial factor in
HVAC applications specifically heat pumps. RSBT has been
designed in just a 45mm solution, IP20 housing that can
either be DIN or panel mounted. This means that in existing
panel designs, RSBT provides an easy replacement to
contactors.
• Diagnostic Warning
RSBT provides several diagnostic warnings to protect the
system against abnormal conditions including:
RSBT
Housing (H x W x D) 125 x 45 x 81 mm
Number of Starts per hour @ 40ºC 12
Operational Voltage 220/400VAC +/- 15%
Operational Frequency 50/60 Hz +/- 10%
Rated Operational Current 16/25/32AAC
Control Voltage 100 – 400VAC +/-15%
50/60Hz +/-10%
Controlled Phases 3
Internally Bypassed YES
Ramp-up time < 600ms
Approvals CE, UL, cUL, EN 60335-2-40 (LVD)
Protection Degree IP20
7 CARLO GAVAZZI Automation Components. Specifications are subject to change without notice. Illustrations are for example only.
Bro_RSBS_RSBT_150611.qxp:PanelBuilderAutomation 6/22/11 9:07 AM Page 8
Modularity
Thanks to the modular design of the RSBT softstarter series, additional accessories are provided to
enhance the functional capabilites of the RSBT.
CARLO GAVAZZI Automation Components. Specifications are subject to change without notice. Illustrations are for example only. 8
CARLO GAVAZZI
A u t o m a t i o n C o m p o n e n t s
3-Phase
Contact-free Switching
•Fast electronic
switching of 3-phase
loads up to 75A,
600Vrms
•Millions of trouble-
free operations
•Zero-switching
and 4kV isolation
•Touch protection
cover
•Over-temperature
protection alarm
option
•Ideal replacement
of contactors making
frequent switching of
heaters and motors
•Conformance to
IEC61000-4-2, IEC61000-4-3,
IEC61000-4-4, IEC61000-4-5,
IEC61000-4-6, EN55011
Power Thyristor
GENERAL INFO DIMENSIONS REPRESENTATIONS
Features 3-phase switching
73.5 4xM3 6xM5
Carlo Gavazzi GmbH
Load types AC resistive and inductive Wien - AUSTRIA
Control input range 4-32 VDC [RZ3A..D.] Tel: +43 1 888 4112 Fax: +43 1 889 10 53
cg_at@attglobal.net
5 VDC [RZ3A..LD.]
41
24-275 VAC/24-50 VDC [RZ3A..A.] Carlo Gavazzi NV/SA
Vilvoorde - BELGIUM
Input current ≤23 mA [RZ3A..D.] Tel: +32 2 257 4120 Fax: +32 2 257 41 25
≤15 mA [RZ3A..LD.] sales@carlogavazzi.be
≤15 mA [RZ3A..A.] 12 5.3 Carlo Gavazzi Inc.
Rated Operational current Mississauga, ON - CANADA
AC51 @ Ta = 25˚C 25A / 55A / 75A Tel: +1 905 542 0979 Fax: +1 905 542 22 48
A1 A2
Montreal, PQ - CANADA
AC53a @ Ta = 25ºC 5A / 15A / 20A Tel: +1 514 644 2544 Fax: +1 514 644 2808
Heatsink
Min. Operational Current 150, 250, 400 mArms gavazzi@carlogavazzi.com
Compound
L1 L2 L3
T1 T2 T3
Off-state leakage current < 3 mA Carlo Gavazzi Handel A/S
103
92
Operational voltage range 24-440 VAC [RZ3A40..] Hadsten - DENMARK
Tel: +45 89 60 6100 Fax: +45 86 98 15 30
42-660 VAC [RZ3A60..] handel@gavazzi.dk
Non. rep. peak voltage 850 Vp [RZ3A40..] B1 B2
Carlo Gavazzi OY AB
1200 Vp [RZ3A60..]
47.6
Helsinki - FINLAND
Operating temperature -30ºC to +80ºC Tel: +358 9 756 2000 Fax: +358 9 756 20010
myynti@carlogavazzi.fi
Storage temperature -40ºC to +100ºC
Approvals UL, CSA* Relay On LED
Carlo Gavazzi Sarl
Roissy - FRANCE
CE Marking Yes Tel: +33 1 49 389860 Fax: +33 1 48 63 27 43
Over-temperature Alarm Trip LED (suffix “P” option)
Touch Protection IP10 (back-of-hand) french.team@carlogavazzi.fr
For further details please view relevant datasheet on website www.carlogavazzi.com/ac Carlo Gavazzi GmbH
Weiterstadt - GERMANY
Tel: +49 6151 81000 Fax: +49 6151 81 00 40
TYPE SELECTION kontakt@carlogavazzi.de
Carlo Gavazzi AS
Porsgrunn - NORWAY
Tel: +47 35 93 0800 Fax: +47 35 93 08 01
gavazzi@carlogavazzi.no
Carlo Gavazzi SA
Leioa (Bizkaia) - SPAIN
Tel: +34 94 480 4037 Fax: +34 94 480 10 61
CONNECTION DIAGRAMS FAN ACCESSORY gavazzi@carlogavazzi-sa.es
Carlo Gavazzi AB
Karlstad - SWEDEN
Terminal Wiring Tel: +46 54 85 1125 Fax: +46 54 85 11 77
gavazzi@carlogavazzi.se
L1
verkauf_vente@carlogavazzi.ch
L2
sales@carlogavazzi.com
T3
ZC
LEAF RZ3A ENG 11 06/08
A2 (~) (-) L3
Automation Components
range please consult:
B1 (+) www.carlogavazzi.com/ac
**Over-temperature alarm output B1/B2 only with suffix “P” types RZ3A.. on accessory RHS301F230C
Distributed by:
Switching Principles Designed
for Your Application Requirements
Instant-on
Zero Switching Switching Peak Switching DC Switching
Upon application of the control volt- The SSR output is activated imme- The peak switching SSR is The power semiconductor in
age, the SSR’s output is activated at the diately after applying control voltage. designed in a way that the power the DC switching relay operates in
first zero crossing of the line voltage. Consequently, this relay can turn on output is activated at the first peak accordance with the control input.
The response time is less than a half The response time is less than 100
anywhere along the AC sinusoidal volt- of the line voltage upon application
period, i.e. typically less than 8.33 ms.
age curve. Response times can typically of the control voltage. After the ms. DC Switching SSRs are used with
Also offered with an optional system
monitoring function and current sensing be as low as 1 ms. first half period, the Peak Switching resistive and inductive loads for the
function, as shown in the lower right. The SSR is particularly suitable in SSR operates as an ordinary Zero control of DC motors and valves.
Due to the high surge current and applications where a fast response time Switching SSR. The peak of the When switching inductive loads it
blocking voltage capabilities, SSRs of is desired, such as solenoids or coils. inrush current could hereafter be will be necessary to interconnect a
this switching type will also perform reduced during the first half period free wheeling diode surplus voltage
successfully with most inductive and for inductive loads. Ideally suited for parallel to the load as protection.
capacitive loads. They are the most inductive loads with a remnant iron
commonly used SSRs in plastics mold-
core (i.e. transformers).
ing machinery, packaging machines,
soldering equipment and machinery for
the food processing industry.
For resistive loads For resistive loads For resistive and For resistive and
Line Burst Full Cycle
inductive loads inductive loads
Voltage Normal Operation Line Line Load DC DC Relay Shorted Shorted
Relay Relay Voltage Voltage Open Supply Supply Remains Relay Relay
Line voltage loss or
OFF ON Loss Loss Circuit Loss Loss OFF thyristor open circuit
LED Visual Indication
Line Voltage
Analog Full Cycle Heater Break
Control Load Current
Input LED Visual indication
Control Over-temperature /
current over-range
Green LED
Load
LED Visual Indication
Period DC Supply
Current Thyristor short-circuit
Red LED LED Visual Indication
Alarm Ouput Alarm Output LED Indication
Since the 4-20mA or 0-10VDC control With this particular switching prin- = Half LED light intensity
input of the analog relay can be varied, ciple, the SSR provides a number of full The Solitron MIDI current sensing SSR is
cycles, evenly distributed over a fixed The system monitoring (sense) SSR
the output operates in accordance with provides an alarm output in the event a zero switching type which also provides
time period, depending on the control an alarm output when it senses variations
the phase control principle. The relay is input (either 4-20mA or 0-10VDC) of a circuit failure. Internal circuitry
equipped with a built-in synchronization monitors: in the load. Typical conditions that can
— with the low value of the input cor-
circuit in order to achieve phase angle be detected include: heater break, open
responding to zero and the high value of • Line Voltage
control. The output is proportional to circuit, partial heater short circuit, blown
the input to a full output with a period of
the input signal. The transfer function 1.28 seconds. • Load Current fuse, semiconductor short circuit and
faulty power connection. Integral current
is linearized and reproducible. Typical applications include: Analog • Correct Functioning of the SSR
sensing eliminates the need for additional
These SSRs are highly advantageous control of heating elements with manual • SSR Input Status external equipment. “TEACH-IN” set point
in closed loop applications or where soft or automatic controllers with 4-20mA is achieved by pushbutton or remotely
or 0-10VDC control signal. Control of The relay is designed for applica-
starting can limit high inrush currents. tions where immediate fault detection where an HMI is preferred.
heating zones, controlled individually
Ideal for use in switching quartz heaters by a number of temperature controllers is required. An alarm output signal is As shown above, the PNP alarm
or in applications which demand precise with analog output. Analog control of available to determine fault status. output provides a series of pulses which
temperature control. fragile heating elements which are used identify the specific type of fault detected.
for cutting, welding etc., which can Interfacing to a PLC can provide a clear
have their lifetime extended due to the indication of fault. An NPN alarm output
reduced thermal load stress. is also available.
The RJ1P Modbus combines the functionality of Zero Switching, Analog Switching, Analog Full Cycle Switching, System Monitoring
and Current Sensing, with the addition of voltage, current, power and frequency measurements.
Prolonged life expectancy –
Utilizing direct copper bonding
Cutting edge manufacturers of solid state devices have started to change
from their previous production technology - the soldering of power
semiconductors on copper conductors which, in turn, are soldered on
a metallized ceramic disc and finally, to a copper or aluminum base - to
state-of-the-art substrate technology. By looking at the comparison in
the lower corner of this page, you will see - previously, at least four solder
joints between the output chip and the heat sink were required, whereas
the new production means has cut the number of solder joints in half.
This technology makes use of what is called a DCB (direct copper bond-
ing) substrate which, in terms of load change strength, is superior to
all previous techniques. The reduction in the number of required
components with the DCB substrate simplifies the production process
and improves the quality of the product.
The DCB Substrate
Reliability determines the standard conducting paste will not increase the
of power semiconductors thermal resistance - optimum heat
With the DCB substrate, the copper
conductance is a guarantee!
is bonded directly to the ceramic The major benefits to the customer
substrate. In the production process, result from improved heat transfer from
copper conductors with a thickness the chip to the external heat sink and
from a reduction of the mechanical
of 0.3 to 0.5 mm are bonded to
stress in connection with major load
ceramic, at temperatures in excess changes. Due to the direct makeup of
of 1900°F. The temperature is cho- the DCB substrate, an optimum solder
sen such that a joint layer is generat- joint is accomplished. Materials such as
ed between the ceramic surface and beryllium oxide and molybdenum, that
have been used up until now, are no
the copper, the expansion coefficient
longer required. With the conventional Convex
of which is slightly higher than that soldering technique, they were used to Back Plate
of the ceramic substrate. This also compensate for negative thermal and
assures the material expansion electrical characteristics.
coefficient against silicon (the output
chip) is negligible. Hence, thermal Solid state relays make use of
stress or fatigue will not cause new technologies
premature failure of power output
Semiconductor relays combine the Carlo Gavazzi -
semiconductors. the supplier of choice!
advantages of power modules with the
function of separate control. Primarily,
they are used as interface modules With solid state relays for currents in
between controller (logic) and load. As excess of 100 amps and for voltages
a result of their outstanding advantages up to 690 VAC, Carlo Gavazzi offers a
over electromechanical components, variety of solid state switching controls.
they are gaining more and more market For the customer, it is of importance to
share. They take advantage of the fact have knowledge of the manufacturer’s
Chip that new applications demand faster production techniques and internal relay
Solder and more accurate processes, defined design. Only production at a high qual-
Molybdenum switching sequences and more reli- ity level and advanced market-oriented
Solder ability. It is therefore obvious that when product design guarantees successful
Copper
Chip
designing and producing solid state use in the field. This brochure will give
Solder
Solder
relays, no compromises can be made. you a glimpse of our solid state switch-
Double Sided
Carlo Gavazzi produces single and ing relays and contactors, for a more
Ceramics Direct Bonded
CU/Ceramics three phase solid state relays. Only in-depth look, please visit our website at
Solder Solder
DCB substrates with high quality thyris- www.GavazziOnline.com, where you can
SSR Bottom SSR Bottom tors and alternistors are used in their specify products, download data sheets
manufacture. The design of their casing and CAD drawings, and so much more.
and heat sink excels in functionality and Also, as you can see from the back cover
Heat-Sink Heat-Sink
Compound Compound efficiency. The casing carries a slightly of this brochure, in addition to our solid
protruding or convex back plate, assur- state switching controls, Carlo Gavazzi
Heat-Sink Heat-Sink
ing ideal thermal contact to the external offers you a multitude of automation con-
heat sink. Therefore, any excess heat trol components.
Ambient Ambient
PCB, Chassis and DIN Rail Mount SSRs
PCB SSRs
RD Series
RA.S Series
RSCAAM60 Series
RZ3A Series
RMD1 Series
RX1A Series RS1A and RA2A Series
RM1. Series
PCB Mount SSRs RM1E Series Analog Switching SSRs
RP1A Series: Zero switching, up to 10A @ 480VAC • Analog switching thyristor, up to 100A @ 660VAC
RP1B Series: Instant-on switching, up to 10A @ 480VAC • 4-20mA or 0-10VDC control signal
RP1D Series: DC switching, up to 8A @ 60VDC or 1A @ 350VDC • Up to 1400Vp non-repetitive peak voltage
• Green LED status indicator
RMD1 Series Hybrid Relays
• Thyristors initially switch the current, and then after a short • 58.2 x 44.8 x 28.8mm (H x W x D) chassis mount housing
delay, they transfer to an internal electromechanical relay
• Zero switching, up to 20A @ 253VAC RD Series DC Switching SSRs
• DC switching transistor, up to 5A @ 60VDC or 1A @ 350VDC
• Over 5 million operations
• 3-32VDC control voltage
• 4-32VDC or 24-275VAC control voltage
• 58.2 x 45.5 x 30mm (H x W x D) chassis mount housing
• Green LED status indicator
• 81 x 17.5 x 67.2mm (H x W x D) DIN rail mount housing RA2A Series Dual Output SSRs
RX1A Series Fast-Connect Thyrex SSRs • Dual output, zero switching alternistor, up to 40A @ 660VAC
• Quick efficient wiring via fast-connect terminals: • Dual input, 4.5-32VDC control voltage
» Screw terminals or • Up to 1200Vp non-repetitive peak voltage
» Spring terminals or • Fast-on spade terminals
» Fast-on (power) terminals • Two green LED status indicators
• Two 22.5mm wide Thyrex-specific heat sinks • 57.8 x 44.5 x 31.7mm (H x W x D) chassis mount housing
• M4 mounting holes are interchangeable with standard
‘hockey puck’ SSRs, but half the width RA...S Series System Monitoring (Sense) SSRs
• Provides a transistor alarm output upon failure of supply, function
• Zero switching thyristor, up to 50A @ 552VAC
or load
• 4-32VDC or 36-265VAC control voltage
• Zero switching alternistor, up to 110A @ 530VAC
• Up to 1200Vp non-repetitive peak voltage
• 20-32VDC supply voltage with a 4.5-32VDC control voltage
• Green LED status indicator and built-in snubber protection
• Up to 1200Vp non-repetitive peak voltage
• 76 x 22.5 x 56mm (H x W x D) chassis mount housing
• Diagnostic green and red LED status indicators
RS1A Series Zero Switching SSRs • 57.8 x 44.5 x 31.7mm (H x W x D) chassis mount housing
• Economically priced triac (10A) or alternistor (25 and 40A)
• Zero switching, up to 40A @ 530VAC RZ3A 3-Phase Zero Switching SSRs
• 3-32VDC, 18-35VAC/DC, 110, 230 or 400VAC control voltage • Three zero switching alternistors, up to 75A @ 660VAC
• Up to 1200Vp non-repetitive peak voltage • 5VDC, 4-32VDC or 24-50VDC / 24-275VAC control voltage
• Green LED status indicator • Up to 1200Vp non-repetitive peak voltage
• 58.2 x 44.8 x 28.8mm (H x W x D) chassis mount housing • Green LED status indicator, built-in snubber networks, IP20 pro-
tective cover, captive wire clamps and
RM1A Series Zero Switching SSRs • Optional over-temperature protection, transistor alarm output and
• Zero switching thyristor, up to 100A @ 660VAC red LED alarm status indicator
• 3-32VDC, 5-24VAC/DC or 22-48VDC / 20-280VAC control voltage • 73.5 x 103 x 41mm (H x W x D) chassis mount housing
• Instant on switching (RM1B), 3-32VDC control voltage only
• Up to 1400Vp non-repetitive peak voltage RSCAA 3-Phase Analog Switching SSR
• Green LED status indicator and built-in MOV protection
• Phase angle controller for inductive/resistive loads (pumps, fans,
heaters, lights, etc.)
• 58.2 x 44.8 x 28.8mm (H x W x D) chassis mount housing
• Three zero switching alternistors, up to 110A @ 625VAC
RM1C Series Peak Switching SSRs • 10-32VDC supply voltage with a 0 or 4 to 20mA control signal
• Peak switching thyristor, for inductive loads up to 30A @ • Up to 1600Vp non-repetitive peak voltage
660VAC • Red LED status indicators for line and load energization, built-in
• 4.25-32VDC control voltage MOV protection
• Up to 1400Vp non-repetitive peak voltage • Optional over-temperature protection
• Green LED status indicator • 66 x 103 x 73.5mm (H x W x D) chassis mount housing
• 58.2 x 44.8 x 28.8mm (H x W x D) chassis mount housing
Screw Terminals
Fast-on (Power) Terminals
Spring Terminals
For Looping For Ring Terminals Quick Troubleshooting
Faster, More Efficient Panel Building: The revolutionary THYREX fast-connect system allows technical staffs to pre-wire the
cable harness outside of the panel. Base modules can be separately pre-mounted onto their heatsink – an operation requiring
much less expertise. Result: Leaner panel building. Fast assembly: Both power and control terminals plug-on.
Clip-on protection cover is Terminals with support surface IP protected connection of Quick, safe installation which
removable with a screwdriver for connection of cables with wire clamps, cables with ring terminals can easily be tested through
cable shoes or ring terminals up to 5 AWG (16 mm2) the protective cover’s holes
Carlo Gavazzi offers an extensive range of RHS Series heat sinks and other various accessories including:
fork terminals (lug connectors for larger size load wires), thermal paste, MOVs, protective covers, PCB SSR sockets, etc.
SOLITRON Solid State Relays and Contactors
CARLO GAVAZZI’s SOLITRON Series is the result of over two decades experience in designing, manufacturing and
marketing solid state relays. With the SOLITRON family, customers get a product with exceptional features, which
provide unparalleled benefits, resulting in a prolonged application life. It is offered in several switching types, including
dual input/output types, which is unmatched in the industry. They provide a fast switching, long lasting alternative to noisy
electromechanical contactors and environmentally hazardous mercury contactors.
Features
Surface mount technology Direct copper bonding DIN-rail or panel Mounting holes for
provides reliability technology used throughout mounting supports forced air cooling
(Midi & Power only)
Self-lifting Secure looping of cables up to Removeable Use of ring terminals for cables
terminal clamps 2.5mm2 — AWG 12 IP20 cover up to 4mm2 — AWG 10
(Mini only) (Mini only) (Mini only) (Mini only)
Cage-clamp terminals from 45 Choice of two terminal Identification window and LED Optional over-temperature
to 90A guaranteeing secure layouts making it easier to fit indication of input status and alarm signal output
connection of cables up to into existing panel designs optional over-temperature (Midi & Power only)
25mm2 — AWG 3 alarm status
(Midi & Power only)
DIN Rail Mount Solid State Relays/Contactors
RJ2A RJ1A SOLITRON POWER RJ1P
SOLITRON RJD2A Two Pole SOLITRON Analog Switching
MINI RJ2A/RJ3A Three Phase SOLITRON SOLITRON
*All SOLITRONS feature one or more green LED status indicator(s), a built-in protective snubber network and
up to 1200Vp non-repetitive peak voltage ratings.
Packaging Equipment
Baggers, shrink tunnels, glue sealers
and various other types of packaging…
Faston
Screw
Spring
Faster, More Efficient Panel Building
The revolutionary Thyrex fast-connect system
allows technical staffs to pre-wire the cable
harness outside of the panel. Base modules
can be separately pre-mounted onto their
heatsink - an operation requiring much less
expertise. Result: Leaner panel building.
RM RX Thyrex
Mounting: NO Problem!
Compatible: Same mounting hole
spacing as standard hockey puck SSRs
Looping Ring Terminals Quick Troubleshooting
Economical:
Reduces the size and
cost of the enclosure
96mm
78mm
m
6m
m
22.5 80
12
mm 22.5m
m
Compact:
with RHS23A with RHS23B
Smallest footprint available
Heat Sink Heat Sink reaching up to 50 Amps
76mm x 22.5mm x 43mm (H x W x D)
Carlo Gavazzi also offers two DIN-rail
mountable heat sinks for use with the Flexible:
Thyrex, thus simplifying installation and Up to 480 VAC switching
saving panel space. Controlled by AC or DC voltage
Diagnostic
Warning
Communication
Capabilities
Main Features
• AC variable speed drive for use
with AC induction motors
• Sensorless vector control with
high starting torque or V/F control
• Input voltage range:
1-Phase up to 230VAC,
3-Phase up to 480VAC
• Only 2 physical frame sizes
• Speed setting by buttons and knob
• 8-step speeds setting Communication Conformity
• PID function • All parameters accessible both via All VariFlex2 are approved according to
• Built-in 24VDC (60mA) for Keypad and PC the related European and North
external application • RS232 or RS485 MODBus American safety standard. Conforms to
• Full motor terminals protection RTU/ASCII serial communications EMI radio standard and EMS immunity
• I/O expansion (2input / 1output available on all models through an standard EN 61800-3 for the second
insulated) option card environment (Industrial sites).
• DIN rail or panel mounting and • Copy card option for fast and easy
remote Keypad available setup of identical drives
2
VariFlex2
Knob (VR)
Communication and
Configuration
Expansion Port Switches
Remote keypad
Multifunction I/O
Output Terminals
(Motor)
I/O Expansion card
Terminals
for Braking Unit
RS485 Communication device 230VAC or 440VAC
Space Reduction
The RVEF models can be installed side by side
(if the temperature inside the cabinet is below than
50°C / 122°F)
Easy to Install
Easy installation on any kind of DIN rail
and panel mounting
RVEF Drivesoft
Software for your PC or Laptop which allows you
to commission and store parameter settings. Use
with RS232/RS485 communication devices.
VariFlex2
Conveyors
Ease of setting makes VariFlex2 versatile for a long list of
conveyor applications.
Locations: Luggage handling in airports,
Transportation of bottles in bottling plants
Letter or package sorting in postal services
Cement powder conveyors in construction
Booster Pumps
Residential and Commercial mains water pressure regulation
and boosting.
Single Pump and Dual Pump using VariFlex2 for basic duty
assist.
Packaging
Development of turnkey automation packaging and
moulding machinery systems.
General Purpose
Provides a powerful solution for most motor
applications:
• Automated Bottling Plants
• Lab Coagulation Line
• Air Bag Sealer
• Gas - Fire Boiler
• Paint Mixer
• Tube Straightner
• Car Wash
• Plastic Film Winder
• Winding - Drawing
• Food Mixers
• Olive Pitting
• Milling Machine
• Edge bending Woodworking Machine
• String – Synthetic for Tennis Racquets
• Top Rollers for Glass Float Rollers
General Characteristics
• Mounting type: DIN rail and panel mounting clip
• Integrated cooling fan: Yes
• Display: 3 digit / 7 segment
• Keypad / LED: 5 function keys / 1 status LED
• Control mode: Sensorless vector control (starting torque: 100%/3Hz)
• Frequency range: 0~200Hz
• Frequency setting mode: Set directly with keys or the VR on the keypad or the up/down setter or AIN signal
• Output frequency limit function: Respectively setting upper/lower frequency limits and two-stage prohibited
frequencies
• Carrier frequenecy: 4~16Hz (factory setting 10KHz, 10KHz or more derating)
• Other protection function: Over current, over voltage, low voltage, overload, momentary power loss
and restart, stall prevention for acceleration/deceleration/operation, short-
circuit protection for output/grounding fault, reverse restriction, restriction
for direct start after power up and error recovery
Environmental Data
• Operating temperature: -10°C to +50°C (+14°F to +122°F)
• Storage temperature: -20°C to +60°C (-4°F to +140°F) for max. 12 months
• Max. Relative Humidity: 95% (non-condensing)
• Degree of Protection: IP20
Protection Functions
• Over current: Inverter rated current 150%/1min
• Over voltage: 230V class: DC voltage > 400V
460V class: DC voltage > 800V
• Under voltage: 230V class: DC voltage < 190V
460V class: DC voltage < 380V
• Instantaneous power loss restart: Set to enable or disable
• Stall prevention: ACC/DEC/Operation stall prevention and stall prevention level
• Output terminal short circuit: Electronic circuit protection
• Other function: Grounding error, Fault reset limit, directly start at power-on
• EMC: Built-in class B filter according to EN61800-3 first non/limit environment
Max. momentary
Output
1.0s
RVEFA120020 - 0.25 0.20 1.7 0.53 4.3 0.65/1.43
RVEFA120040 - 0.50 0.40 3.1 0.88 5.4 0.67/1.48
2.0s
- RVEFB120220 3.00 2.20 10.5 4.00 21.0 1.05/2.31
RVEFA320020 - 0.25 0.20 1.7 0.53 3.0 0.61/1.34
1.0s
RVEFA320040 - 0.50 0.40 3.1 0.88 4.0 0.61/1.34
200 - 240VAC
(-15% - +10%)
2.0s
- RVEFB320220 3.00 2.20 10.5 4.00 12.2 1.0/2.2
1.0s
- RVEFB340075 1.00 0.75 2.3 1.70 3.0 1.5/3.30
(-15% - +10%)
380 - 480VAC
0 - 200Hz
3 - phase
0 - 480V,
2.0s
- RVEFB340220 3.00 2.20 5.2 4.00 6.6 1.55/3.42
131/5.16”
77/3.03”
118/4.65” 148/5.83”
VariFlex2 - RVCF Series
The VariFlex2 RVCF series is a simple, compact and general purpose AC Semplified
variable speed drive for use with 3-phase AC induction motors. The drive's Set-Up
parameters are logically divided in fifteen different groups for a simple and
immediate setting of the devices according to the needs of the process. The
standard display of the drive can be remoted by the extension cable and put
outside the cabinet where the drive is installed. A full range of product
Communication
spreading from 0.4kW/0.5HP up to 55kW/75HP with single and triphase Capabilities
AC input 230VAC and triphase AC input 480VAC. The VariFlex2 employs
state of the art microprocessor technology which controls all drive functions.
All printed circuit boards are coated and manufactured using surface mount
technology ensuring high quality and reliability.
Main Features
• AC variable speed drive for use
with AC induction motors
• Sensorless vector control or V/F
mode, high starting torque
• Input voltage ranges: 1-ph 230VAC,
3-ph 230VAC, 3-ph 480VAC
• 150%/1Hz (Vector mode) starting
torque
• Simple Built-in PLC function
always available
• PID function available
• Conforms to EMI radio standard
and EMS immunity standard EN Communication
61800-3 for the first environment • All Parameters accessible both Conformity
(Restricted Distribution) via Keypad and PC All VariFlex2 are approved according to
• 6 different physical frame sizes • RS232 or RS485 MODBus the related European and North
• EMC filter internal built-in available RTU/ASCII serial communications American safety standard. Conforms
for same items available on all models through an to EMI radio standard and EMS
• NPN/PNP digital inputs option card immunity standard EN 61800-3 and
• DIN rail or panel mounting and • Memory stick (Copy card) option LVD EN50178.
keypad extension available on for fast and accurate drive to drive LISTED 16KJ
POWER CONV. EQ.
all models parameter transfer and storage E319186
VariFlex2
Market Application
Conveyors
Ease of setting makes VariFlex2 versatile for a long list
of conveyor applications.
Locations:
• Luggage handling in airports
• Transportation of bottles in bottling plants
• Letter or package sorting in postal services
• Cement powder conveyors in construction
Water Treatment
• Residential and Commercial mains water pressure
regulation and boosting
• Waste water management
• High efficiency regulation of water tanks level
• High efficiency pressure regulation of water/fluid pipes
General purpose
Provides a powerful solution for most
motor applications:
• Renewable Energy/Trackers
• Oil Pumps
• Lift, Crane and Elevator
• Wire Drawing machinery
• Metal Sheet machinery
• Textile Complex Machine
• Plastic Machine
• Plastic Secondary Equipments
• Pumping Station
Simple wiring system
It allows to separate power supply cable to the signal cables in the RVCF size “A”, “B” and “C”
Example of size “A”
RVCF Drivesoft
Software for your PC or Laptop which allows you
to commission and store parameter settings.
Use with RS232/RS485 communication devices.
PLC
RVCF series has Built-in simple
PLC function, user can download
Ladder Diagram from
PC (Windows base software) very friendly.
VariFlex2
4 Digit Display Panel Mounting Clip
Keypad
Communication
Port
Optionals
Environmental Data
• Operating temperature: -10°C to +50°C (+14°F to +122°F)
• Storage temperature: -20°C to +60°C (-4°F to +140°F)
• Max. Relative Humidity: 95% (non-condensing)
• Degree of Protection: IP00 or IP20 (Nema 1 by external upper cover only for size “A” and “B”)
Size “A” Size “B” Size “C” Size “D” Size “E” Size “F”
mm/inches Size “A” Size “B” Size “C” Size “D” Size “E” Size “F”
H H 163/6.42 187.1/7.36 260/10.24 360/14.2 553/21.8 653/25.7
W D W 90/3.54 128/5.04 186/7.32 245/9.6 210/8.3 250/9.8
D 147/5.79 148/5.83 195/7.68 265/10.4 269/10.6 308/12.1
Input Current
Rated Output
Nominal
Current
Weight
Frequency
Frame Size Motor
Voltage
Rating
Power
5.6/12.35
- - RVCFC3200750 - - - 10 7.50 35.0 13.3 42.00
2.0s
- - - RVCFD3201100 - - 15 11.0 48.0 20.6 57.0