Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
F.Q.Yo usef-Zai
D.0’ Kelly
1 Introduction
Abstract: Switching logic is defined for a single-
phase transformer tap changer using thyristor On-load tap changers usually insert resistance or reac-
switching. A laboratory model validates the tance during the switching operation to limit the circu-
theory and shows that tap changing is possible in lating current in the commutating taps. The mechanical
less than one cycle over the whole power-factor operation requires three or four stages and is relatively
spectrum. Waveform sampling and the use of a slow, often many cycles. Solid-state devices are now
microprocessor based control system provides used extensively in the field of power engineering
improved control and additional features such as including motor control, direct-current transmission
data logging etc. Two schemes are considered for etc. Thyristors have been used as an aid to facilitate
the application of thyristor tap changing to three- switching in mechanical tap changers [l, 21. A novel
phase transformers. Economic viability is strongly scheme has been recently described [3] which incorpo-
dependent on the associated power system and its rates a GTO thyristor for the switching duty with a
abnormal operating features, namely system fault fast-acting mechanical selector switch. However, thyris-
currents and especially the degree of exposure of tor switching to eliminate the mechanical moving parts
the transformer to lightning surges. appears to have only been considered or implemented
for specialised applications [4-71. In this paper, the
switching logic requirements together with other neces-
sary operational features are exa,mined for such a tap
List of symbols changer.
i = instantaneous current, A
Il r E r - - i
I = current, RMS A
f = peak current, A
L = inductance, H
n = tap section turns, p.u.
R = resistance, Q
t = time, s
v = instantaneous voltage, V
V = voltage, RMS V
X = reactance, p.u.
a = switching angle, rad
y = overlap angle, rad
6 = extinction angle, rad
$ = power factor angle, rad
CO = supply angular frequency, radls
Suffices
1 = primary winding Fig. 1 Conventional solid-state tap changer
2 = secondary winding
2 Solid-state tap changers
t = tap section
s = supply side The conventional tap changer technique of switching in
sc = short circuit a diverter impedance to limit the circulating current on
tap transition can be used with thyristors as the switch-
0IEE, 1996
ing elements. Fig. 1 shows a typical arrangement. To
ZEE Proceedings online no. 19960578
effect a tap change the thyristor pair X is turned on
Paper first received 20th October 1995 and in revised form 24th April
1996 and the firing circuit to A is turned off. A cycle later,
F.Q. Yousef-Zai is with the Deparhnent of Electrical Engineering, North-
thyristor pair B is turned on and the gate drive to X
West Frontier Province, University of Engineering & Technology, turned off. A tap change is effected in two cycles. The
Peshawa, Pakistan duty on the thyristors can be reduced by arranging the
D. OKelly is with the Department of Electronic & Electrical Engineering, firing circuits for thyristor pairs X and B to be ener-
University of Bradford, West Yorks. BD7 lDP, UK gised at voltage zeros.
IEE Proc.-Electr. Power Appl., Vol. 143, No. 6, November 1996 481
The number of thyristor pairs may be halved by hav- prevent an onerous tap short-circuit current the instant
ing accurately defined switching strategies so that the of switching must be controlled and Figs. 4 and 5 illus-
circulating currents in the tap section are limited to a trate the required switching instant assuming ideal
safe value without the use of a diverter resistance devices and negligible transformer leakage inductance.
(Fig. 2). The main objective of this paper is to examine One thyristor pair (namely, B) is turned on while the
this type of circuit topology. The sections on opera- gate drive for pair A is removed.
tional requirements and the inclusion of measurement
features are equally applicable to both circuit configu- ,(1+n)v
rations. Both schemes probably require a bypass switch
as discussed in Section 6.5. (1-n)v
p
wt
switch
instanti n g # v
I I
-. -. . -. -.-. -.
I I
T2A +J--J -30 0 30
a, deg
v
7 Fig.7 Computed switching characteristics at rated current; switching up
at unity p.$
Fig.6 Typical switching-up sequence with$nite overlap
x,,,, = 0.2p.u.
x,,, = 0.1p.u.
~
____
Xrranff
= 0.05p.u.
negative quantity
I sin(a - 4) = (V/wL:!)[coscy - cos(a r)] (4) +
The load voltage changes from v to (1 - n)v at the initi-
ation of the tap change but this does not affect the cur-
L I I
rent change in thyristor T1A. -30 0 30
Figs. 7-9 show overlap angle characteristics for a a,deg.
range of a and X,, It is assumed that the secondary Fig.9 Computed switching characteristics at rated current; switching at
leakage reactance X2 is half XrrUnsf(in per unit) and the zeiGp$
x,,, = 0.2p.u.
tap section reactance is proportional to the number of
~
?
Q
I
C
;
3
U
0
m
Q
c
0
wt
a ,deg.
Fig.10 Computed switching characteristics ut rated current; peak tap
short-circuit current (1,
= 0)
~ XI,, = 0.2p.u.
____ X*,,.= 0.lp.u.
_ XI,, = 0.05p.~.
Fig.12 Switching down ut unity power factor: switching waveforms
TlA
hf
I I
h( TIC
V I
I
i 1c
C
l0i
T2C
I
Fig.11 Switching down ut unity power factor: equivalent circuit
Fig.13 Switching down at near-unity leading power factor current
equivalent circuit
484 IEE Proc -Electr Power Appl, Vol 143, No 6, November 1996
to prevent reignition of their respective thyristors, see (ii) the value of a is restricted to1 30" which limits the
Fig. 14. If angle aZAis too small, then thyristor T2A maximum voltage at turn-on to 50% of the peak tap-
reignites and a short-duration (safe) tap short circuit section voltage.
occurs as illustrated in Fig. 15. This type of behaviour
increases aIA and reduces the risk of thyristor TIA I
pq Fl
readout
6.1 Single-phase laboratory model [8/ 6. 1. 1 Snubber circuits; The switching angle was
A single-phase model of a five-tap thyristor tap selected to give the lowest possible turn-on voltage con-
changer controlled by a Motorola 68008 microproces- sistent with an appropriate safety margin. Typically,
sor (Fig. 17) was used to test the implementation of the maximum voltage across a device at turn on was
the instrumentation and control features. Three phase- <50% of the peak tap-section power frequency voltage.
locked loops (PLL) were used, namely Each device has to be rated to withstand the total
voltage, current sampling, 64 pulseskycle range of the tap-change section power frequency volt-
age, hence, with five tap sections the peak voltage at
current switching region, 128 pulseskycle turn on is limited to 10% of the peak power-frequency
switching angle, 360 pulses/cycle voltage experienced by the device. This enabled the
thyristors to be operated without snubber circuits. The
dildt in a device is limited by the transformer leakage
reactance and is well within its capability. It is sug-
gested on the basis of these results that a practical
scheme using distribution-size transformers would not
require snubber circuits for the thyristors or at worst a
a b relatively small snubber circuit with a low loss.
leq X
Fi Sectionalised tupping points
0 Sectionulued tupping points with wmding polarity reversed .22 Three-phuse rmg-configuration tup changer schematic diugrum
488 IEE Proc -Electr Power Appi, Vol 143, No 6, November 1996
(i) The thyristor rating is increased: voltage by a factor As with the single-phase scheme described previously
of d3 and current by 1.5. it is advantageous to switch at the lowest value of the
(ii) Three-phase currents must be nearly balanced if instantaneous forward voltage (consistent with safety
onerous tap short-circuit currents are to be avoided. margins) to give the lowest dvldt across the thyristors.
It may result in near-maximum peak values of current
(iii) Secondary windings must be star connected and an being commutated but the winding leakage inductance
earthed star point is not possible. effectively limits the dildt value.
Only a brief treatment of the control features and per- A computer program was written to plot switching
formance are given since the scheme has obvious limi- current and voltage waveshapes [8] and a three-ring
tations. Considering a three-tap scheme as shown in laboratory model was built and tlested. Satisfactory tap
Fig. 22 the corresponding steady-state device currents changing was carried out over a wide power factor
and nonconducting device voltages are shown in Figs. spectrum and experimental results validated the theo-
23 and 24 for a balanced resistive load. retical waveforms. Representative results are given in
An appropriate switching logic is to turn on a device Figs. 25 and 26.
when it is forward biased and there is current flowing However, due to the limitations mentioned previ-
in a device in the same leg. Typically, the device which ously the use of a single-phase tap changer in each limb
is to be turned off has its gate-firing pulse removed is advocated.
some time, say, 2 0 0 before
~ the parallel device is fired.
Table 1 summarises the switching angles for the whole
power factor spectrum for one leg assuming negligible
overlap. The other two legs are switched consecutively
at intervals of one third of a cycle as the load is
assumed to be balanced. The switching angles are read-
ly3
0
I f-c\ vy3 l
overlap angle.
I 'TZ2
ix3 I
0 0
0.020
1x2
0 '
L I vx3 / ! 0.020
L
wt
Fig.23 Three-phase ring-configuration tap changer: steady-state cur- Fig.25 Switching-down voltage and current waveshapes or rmg config-
rents in ring 2 uration three-phase tap changer near-unity power-factor &ad:'co&uted
values
Leading up 30 to (210-x)" + +
down 0 t o 30" where 120" 240"
Lagging up ( 3 0 + ~ t)o 210" 0 <I$ < 30" X= 0
down 210 t o (240+I$)" 30 < I$ < 90"X = e30"
489
Table 2:Case studies
Notes A B C
Transformer rating, MVA 100 5 1
Number of phases 3 3 1
Winding phase voltage, kV RMS 331d3 1 1ld3 3.3
Tapped winding secondary secondary primary
Rated current, kA RMS 1.75 0.26 0.3
with 100% overload, kA RMS 3.5 0.54 0.6
Transformer reactance, per unit 0.15 0.05 0.03
Number of tap sections 16 16 8
Tap voltage, per unit 0.0125 0.0125 0.02
Tap inductance, mH 0.032 0.024 0.01
Number of tap groups 2 2 1
Overvoltage factor 1 4 4 5
M a x i m u m device voltage, kV RMS 0.95 0.64 0.53
Peak voltage on turn on, Vp 84 57 47
Redundancy built in? Yes no no
Bypass switch 2 vacuum vacuum thyristor
switch switch HRC fuse
Transformer efficiency, per unit 0.994 0.99 0.985
Transformer loss on full load, kW 600 50 15
Solid-state loss on full load, kW 3 34 2.6 0.5
Fault MVA 600 70 20
Peak fault current, kAp 4 26.8 9.3 15.5
eq uiva Ie nt ha If cycle, kAp 5 32.8 11.4 19.0
Number of thyristors 252 126 18
Suggested thyristor rating:
current, kA average 6 2.0 0.4 0.4
peak voltage, kVp 7 5.4 4.0 4.0
max dildt, A l p 8 4.7 1.6 2.7
peak voltage on turn on, Vp 9 84 57 47
peak current, kAp 10 33" 12* 19t
max dvldt, vlus 11 ** ** **
1 Overvoltage factor is multiple of peak phase voltage
2 Case C requires HRC fuse co-ordination to limit peak current
3 Solid-state loss is based on (thyristor volt drop = 1.8V)(average full-load current)(number of series
thyristors)
4 Peak fault current = 2.55 (RMS short-circuit current)
5 Equivalent halfcycle = halfcycle of 50Hz sinusoidal current
6 Rounded-up values
7 Rounded-up values: case A assumes redundant thyristor shares any abnormal system overvoltage
8 Based on short-circuit current; thyristor current and voltage ratings are strongly dependent on associ-
ated power system characteristics
9 Rounded-up values; with multiple-tap transitions values are multiplied by number of taps changed
10 * Thyristors may require higher value of average current rating to satisfy peak current requirement;
t either prospective peak value of 19 kA is limited by HRC fuse co-ordination or thyristor average cur-
rent rating is increased
11 ** Safe values may necessitate higher value of peak voltage rating, Section 6.7
Case studies ately rated thyristor pair could be used for the bypass
switch with a series high rupturing capacity (HRC) fuse
Three schemes are considered (Table 2) ranging from a for fault clearance co-ordinated to reduce the actual
single-phase distribution transformer (in which the risk peak fault current below its prospective value.
of failure of a thyristor operating well within its rating
is considered to be negligible) to a large three-phase
transformer with built-in redundancy to give maximum
reliability. It is assumed that both three-phase schemes The switching logic for a transformer solid-state tap
have to handle unbalanced loads and therefore the changer has been developed and applied to a labora-
three-phase scheme considered in Section 8.1 is not tory model giving satisfactory operation over the com-
suitable and each phase must be controlled independ- plete power-factor spectrum under normal operating
ently. conditions. A sampling technique for the measurement
Vacuum switches are used as bypass switches in the of voltage and current values dnd a microprocessor
two larger schemes. At the lowest rating an appropri- based controller were used to implement the required
490 IEE Proc.-Electr. Power Appl., Vol. 143, No 6, November 1996
switching strategies. The combination of power elec- leakage inductance and resistance proportional to the
tronics and microelectronics with a conventional piece number of turns i.e. n(R2 + jX2). The magnetising cur-
of power equipment provides a flexible arrangement rent and the winding resistance R, are relatively small
including not only the main requirement of voltage and may be neglected giving the equivalent circuit of
control but also many additional features such as Fig. 27c. A short-circuit on the secondary winding,
instrumentation, data logging protective aspects, etc. Fig. 27d produces a steady-state current of magnitude
As with all power electronics equipment the power loss
in the semiconductor devices is not insignificant.
+ +
I,, = V,/(X, XI X , ) per unit (5)
Under abnormal system behaviour there may be high A short circuit on the tapped winding Fig. 27e gives a
fault currents or system overvoltages owing to switch- steady-state primary current of
ing operations or lightning surges etc. The viability of a
solid-state tap changer generally capable of handling
+ +
IlSc= V s / [ X s X I ( X a / n ) ]per unit (6)
and a steady-state current in the short-circuited tap of
any or all of these requirements is questionable unless
the very fast response time achieved is mandatory. +
It,, = nIlsc = V , / [ n ( X , X , ) ] per unit (7)
Only if the transformer situation considerably reduces Comparing eqns. 7 and 8 the ralio of the short-circuit
the degree of exposure to high fault currents and, more currents is
especially, steep-fronted surge voltages can the scheme
approach cost effectiveness.
short-circuited tap section - X , XI X ,
-
+ +
Any tap changer scheme must be reliable. The statis- short-circuited secondary + +
n ( X , X I ) X2
(8)
tical risk of a thyristor failure is extremely unlikely Since n is relatively small n(X, -t XI) << X2 and the
owing to the relatively low duty on a device under nor- ratio becomes ( X , + XI +X2)IX2 approximately. This
mal operation compared to its rating. However, if this gives a tap steady-state short-circuit current of approx-
degree of risk is unacceptable built-in redundancy may imately
be included at considerable extra cost. I, = t a p voltage __
-_ ~-nVs --
K
t a p leakage reactance nX2 X z (9)
11 Acknowledgment
It is seen that the steady-state talp short-circuit current
Dr Yousef-Zai is indebted to the Government of Paki- is at least twice the secondary short-circuit current
stan for granting a scholarship and North-West Fron- (assuming, typically, that XI = X2 and with finite sys-
tier Province University of Engineering and tem reactance X,). Additionally, there may be a DC
Technology for study leave to undertake research at component depending on the voltage phase angle at
Bradford University. switching.
12 References
ROBERTS, M.E., and ASHMAN, W.G.: ‘A thyristor-assisted
mechanical on-load tap changer’. IEE Conf. Pub. 53, 1969, pt. 1,
pp. 185-192
COOKE, G.H., and WILLIAMS, K.T.: ‘New thyristor assisted
diverter switch for on-load transformer tap-changer’, ZEE Proc.
B, 1992, 139, (6), pp. 507-511
SHUTTLEWORTH, R., TIAN, X., FAN, C., and POWER, A.:
‘New tap-changing scheme’, ZEE Proc., Electr. Power Appl., 1996,
143, (l), pp. 108-112
MUSGRAVE. G.. and O’KELLY. D.: ‘Imorovement of Dower
system transmission by solid-state ’ techniqces’. IEE Conf: Pub.
123, 1974, pp. 228-233
O’KELLY, D., and MUSGRAVE, G.: ‘Improvement of power
system transient stability limits’, Proc. IEE, 1973, 120, (2), pp.
247-253
GUTH, G., BAKER, R., and EGLIN, P.: ‘Static thyristor-con-
trolled regulating transformer for AC transmission’. IEE Conf.
Pub. 205, 1981, pp. 69-72
ARRILLAGA, J., and DUKE, J.M.: ‘A static alternative to the
transformer on-load tap-changer’, ZEEE Trans., 1980, PAS-99,
(l), pp. 86-91
YOUSEF-ZAI, F.Q.: ‘Fast-acting solid-state transformer tap-
changer’. PhD thesis, University of Bradford, 1990