Sei sulla pagina 1di 11

Solid-state on-load transformer tap changer

F.Q.Yo usef-Zai
D.0’ Kelly

Indexing terms: Tap changing, Thyristors, Transformers

1 Introduction
Abstract: Switching logic is defined for a single-
phase transformer tap changer using thyristor On-load tap changers usually insert resistance or reac-
switching. A laboratory model validates the tance during the switching operation to limit the circu-
theory and shows that tap changing is possible in lating current in the commutating taps. The mechanical
less than one cycle over the whole power-factor operation requires three or four stages and is relatively
spectrum. Waveform sampling and the use of a slow, often many cycles. Solid-state devices are now
microprocessor based control system provides used extensively in the field of power engineering
improved control and additional features such as including motor control, direct-current transmission
data logging etc. Two schemes are considered for etc. Thyristors have been used as an aid to facilitate
the application of thyristor tap changing to three- switching in mechanical tap changers [l, 21. A novel
phase transformers. Economic viability is strongly scheme has been recently described [3] which incorpo-
dependent on the associated power system and its rates a GTO thyristor for the switching duty with a
abnormal operating features, namely system fault fast-acting mechanical selector switch. However, thyris-
currents and especially the degree of exposure of tor switching to eliminate the mechanical moving parts
the transformer to lightning surges. appears to have only been considered or implemented
for specialised applications [4-71. In this paper, the
switching logic requirements together with other neces-
sary operational features are exa,mined for such a tap
List of symbols changer.
i = instantaneous current, A

Il r E r - - i
I = current, RMS A
f = peak current, A
L = inductance, H
n = tap section turns, p.u.
R = resistance, Q
t = time, s
v = instantaneous voltage, V
V = voltage, RMS V
X = reactance, p.u.
a = switching angle, rad
y = overlap angle, rad
6 = extinction angle, rad
$ = power factor angle, rad
CO = supply angular frequency, radls

Suffices
1 = primary winding Fig. 1 Conventional solid-state tap changer
2 = secondary winding
2 Solid-state tap changers
t = tap section
s = supply side The conventional tap changer technique of switching in
sc = short circuit a diverter impedance to limit the circulating current on
tap transition can be used with thyristors as the switch-
0IEE, 1996
ing elements. Fig. 1 shows a typical arrangement. To
ZEE Proceedings online no. 19960578
effect a tap change the thyristor pair X is turned on
Paper first received 20th October 1995 and in revised form 24th April
1996 and the firing circuit to A is turned off. A cycle later,
F.Q. Yousef-Zai is with the Deparhnent of Electrical Engineering, North-
thyristor pair B is turned on and the gate drive to X
West Frontier Province, University of Engineering & Technology, turned off. A tap change is effected in two cycles. The
Peshawa, Pakistan duty on the thyristors can be reduced by arranging the
D. OKelly is with the Department of Electronic & Electrical Engineering, firing circuits for thyristor pairs X and B to be ener-
University of Bradford, West Yorks. BD7 lDP, UK gised at voltage zeros.
IEE Proc.-Electr. Power Appl., Vol. 143, No. 6, November 1996 481
The number of thyristor pairs may be halved by hav- prevent an onerous tap short-circuit current the instant
ing accurately defined switching strategies so that the of switching must be controlled and Figs. 4 and 5 illus-
circulating currents in the tap section are limited to a trate the required switching instant assuming ideal
safe value without the use of a diverter resistance devices and negligible transformer leakage inductance.
(Fig. 2). The main objective of this paper is to examine One thyristor pair (namely, B) is turned on while the
this type of circuit topology. The sections on opera- gate drive for pair A is removed.
tional requirements and the inclusion of measurement
features are equally applicable to both circuit configu- ,(1+n)v
rations. Both schemes probably require a bypass switch
as discussed in Section 6.5. (1-n)v

Fig.4 Safe switching region with lagging~$ load


Fig.2 Solid-state tap changer without diverter resistance

'r I oad Fig.5 Safe switching region with leadingp.$ load


Zero overlap, ideal devices

The switching device logic is straightforward:


Fig.3 Equivalent circuit for tap changer
Three tapping points shown, winding resistance neglected switching up instant: v and i have values of like
polarity
3 Principle of operation
switching down instant: v and i have values of
The equivalent circuit corresponding to the tapped sec- unlike polarity.
ondary side of the transformer is shown in Fig. 3. Only It is seen that as the power factor approaches unity the
three taps are shown to illustrate the switching proce- available safe switching period tends to zero for either
dure. Consider current to be flowing in thyristor pair switching down with forward power flow or switching
A. The secondary voltage is either increased by switch- up with reverse power flow.
ing up (thyristor pair B turned on) or switching down
(by turning on thyristor pair C). A tap change is 4 Switching logic
achieved by simply turning on the appropriate thyris-
tor-pair (viz.say B) while turning off thyristor pair A. 4. I Influence of overlap angle
However, with a random instant of switching a trans- In practice the secondary winding has leakage imped-
former tap may be short circuited for nearly one cycle. ance which delays commutation from one thyristor pair
The value of this short-circuit current may exceed that to the next thyristor pair during a switching operation.
due to a short circuit on the whole secondary winding, The commutation period or overlap angle is a function
see the Appendix, and with repeated tap changes the of the leakage impedance, tap-winding voltage and
possible damage to the windings or devices by these load current. The leakage impedance is approximately
high short-circuit currents is clearly unacceptable. To n(R2 + jwL2), see the Appendix.
482 IEE Pvoc -Electr Power Appl , Vol 143, No 6, November 1996
about the voltage zero since it 11s shown later that the
duty on the device is minimised using this switching

p
wt

switch
instanti n g # v

I I

-. -. . -. -.-. -.
I I
T2A +J--J -30 0 30
a, deg

v
7 Fig.7 Computed switching characteristics at rated current; switching up
at unity p.$
Fig.6 Typical switching-up sequence with$nite overlap
x,,,, = 0.2p.u.
x,,, = 0.1p.u.
~

____
Xrranff
= 0.05p.u.

Fig. 6 illustrates a typical switching-up sequence


with finite overlap. Neglecting thyristor volt drop the
relationship between overlap angle y, switching angle a
and load phase angle $I is given by eqn. 1. The load
current i is not affected by the tap-change voltage until
commutation is completed and the load voltage then
suddenly rises to (1 + n)v. The switching angle a is con-
strained as follows:
lagging power factor: Q s a < n - y, where Q is a posi-
tive quantity
leading power factor: 0 s a < (n + Q - y), where Q is a
negative quantity
isin(y+a-#) = (nQ/nzz)[sin(aty- K)-sin(a -I()expp]
(1)
where 2, = [R22+ (oL~)~]'" a, deg.
Fig.8 Computed switching chavucteristics at rated current; switching
B = -YR2/(WL2) down at unity p$
XI,,, = 0.2p.u.
K = tan-'(oL2/R2)
~

____ XI,,, = O.lp.u.


Xrram,= 0.05p.u.
With negligible resistance eqn. 1 becomes
+
i sin(y a! - 4) = ( n V / n w ~ a ) [ c a!o s- cos(a! y)] (2) + 30r
Defining I and V to be the RMS values of current and
voltage
+
sin(y cy - 4) = (V/wL2)[cosa - cos(a y)] +
(3)
For a switching-down sequence from, say, A to C the
current in T1A changes from I sin(a - $I) to zero and
with negligible resistance the relationship for y is now
given by eqn. 4. The switching angle a is constrained
as follows:
lagging power factor: 0 5 a < Q - y where Q is a posi-
tive quantity
leading power factor: (n + Q) s a < (n y) where 4 is a ~

negative quantity
I sin(a - 4) = (V/wL:!)[coscy - cos(a r)] (4) +
The load voltage changes from v to (1 - n)v at the initi-
ation of the tap change but this does not affect the cur-
L I I
rent change in thyristor T1A. -30 0 30
Figs. 7-9 show overlap angle characteristics for a a,deg.
range of a and X,, It is assumed that the secondary Fig.9 Computed switching characteristics at rated current; switching at
leakage reactance X2 is half XrrUnsf(in per unit) and the zeiGp$
x,,, = 0.2p.u.
tap section reactance is proportional to the number of
~

__-- x,,, = 0.1p.u.


turns. The firing angle a is limited to a value 2 30" x,,,, = 0.05p.u
IEE Proc-Electr. Power Appl., Vol. 143, No. 6, November 1996 483
range. With a zero power factor lagging load (Fig. 9) 4.3 Switching at near-unity power factor
the value of a is positive for switching down and nega- current
tive for switching up. The characteristics in Figs. 8 and It is seen from Figs. 4-6 that an onerous duty is switch-
9 show that with a negative value of a there is a limit- ing down a near-unity power factor load current (or,
ing value of a above which commutation would be alternatively, switching up a near-unity power factor
incomplete at the voltage zero. For example in Fig. 8 reverse current). A solution is to define the instant of
with X,,,,, = 0.01 the values of la1 and y are identical tap changing or switching (i.e. removing the gate drive
at 4.4". The safety margin between T l A ceasing to con- from one thyristor pair, say A, and turning on an adja-
duct and experiencing a positive forward voltage is cent thyristor pair, say C) to be at an angle (n - a) or
defined as angle 6 and in common with power electron- the equivalent value (-a) prior to voltage zero. The tap
ics terminology is called extinction angle. is short circuited for a small period but since the tap
voltage is relatively small during this period, the peak
4.2 Tap short circuit value of circulating current is not large. Fig. 10 shows
Referring to Fig. 6 if 6 is too small and T1A reignites the peak tap short-circuit current characteristics in
there is a commutation failure. Since both T2A and terms of a for transformer reactances of 0.05, 0.10 and
T2B have been turned on together, the tap is short 0.20 per unit. A short-circuit current of one per unit in
circuited. Short-circuit current flows through T1A and Fig. 10 corresponds to the peak value of rated current.
T2B for nearly a whole cycle (owing to its DC compo- Figs. 11 and 12 illustrate the switching-down of a
nent) and gives a peak current of nearly twice the unity power factor load. There is little danger of a pro-
steady-state value. The short circuit on the tap could be longed short circuit on the tap due to thyristor T2A
prevented by turning on T2B some time after TlA. starting to conduct. This device has not conducted for
However, this method was rejected since it introduces nearly a halfcycle and the safety margin for the
an extra control parameter for each thyristor pair and removal of the firing signal is 6,. The duty is similar
the possibility of maloperation (in particular if all the on switching up a unity power factor load with reverse
devices are instantaneously in the nonconducting state power flow.
then load blocking occurs and the devices are subjected The most onerous duty is switching down a near-
to the full transformer secondary voltage). unity leading power factor load current as shown in
Fig. 13. The transition occurs without a tap short cir-
cuit if both extinction angles 61, and are sufficient

?
Q
I
C
;
3
U

0
m
Q
c
0

wt

a ,deg.
Fig.10 Computed switching characteristics ut rated current; peak tap
short-circuit current (1,
= 0)
~ XI,, = 0.2p.u.
____ X*,,.= 0.lp.u.
_ XI,, = 0.05p.~.
Fig.12 Switching down ut unity power factor: switching waveforms

TlA
hf
I I

h( TIC
V I
I
i 1c
C
l0i
T2C

I
Fig.11 Switching down ut unity power factor: equivalent circuit
Fig.13 Switching down at near-unity leading power factor current
equivalent circuit

484 IEE Proc -Electr Power Appl, Vol 143, No 6, November 1996
to prevent reignition of their respective thyristors, see (ii) the value of a is restricted to1 30" which limits the
Fig. 14. If angle aZAis too small, then thyristor T2A maximum voltage at turn-on to 50% of the peak tap-
reignites and a short-duration (safe) tap short circuit section voltage.
occurs as illustrated in Fig. 15. This type of behaviour
increases aIA and reduces the risk of thyristor TIA I

restriking. Angle al, must always be large enough to


prevent TIA being turned-on since this results in an
onerous tap short-circuit current. This switching duty
also applies to switching up a near-unity lagging power
factor current with power flow in the reverse direction.

4.4 Optimum switching angle


From the previous Sections it is seen that a wide range
of switching angle a is possible for a large part of the
power factor spectrum. However, only a limited range
of a is possible if Fig.16 Typical switching-up characteristicfor a
~ limits of safe operation
(i) discontinuities in its value (as @ changes) are to be -.-. -.- suggested nominal value
avoided and

Fig. 16 shows a typical optimised characteristic for a


with a transformer leakage reactance of 0.1 per unit
and load currents up to rated value. It has the follow-
ing features:
maximum tap-section circulating current X- 2p.u.
maximum device current 2- 2p.u.
minimum extinction angle = 4" == 22Op.s
maximum range of switching angle a = +30"
The switching-down characteristic is similar to Fig. 16
with 4 altered by 180".

5 Control and instrumentation

In the preceding Section the basic switching require-


ments for a solid-state tap changer are defined assum-
ing a steady-state load current. In practice, many other
aspects have to be considered. Typical operational
requirements are summarised here, with their imple-
mentation described in Section 6:
Fig. 14 Switching down at near-unity leadingpowerfactor current: T2A (i) The system must be capable of handling transients
does not reignite
on transformer energisation.
(ii) Measurement of current and phase angle to define
the switching angle a.
(iii) Voltage measurement and switching logic to give
the required voltage control features.
(iv) Tap changing must be inhibited if it is unsafe
owing to either a DC component in the load current
(following transformer energisation) or a sudden
change of load current.
(v) Rapid detection of a system fault and action initi-
ated to limit thyristor duty.
(vi) Instrumentation for voltage, current, power and
energy measurement.
(vii) The ability to withstand lightning surges and
switching overvoltages.

6 Implementation of switching and operational


features

The use of a microprocessor based control system is


invaluable in providing a range of flexible features.
Fig.15 Switching down at near-unity leading power factor current: T2A Furthermore, sampling techniques facilitate the switch-
reignites, ,S is too small ing requirements and data evaluation.
IEE Proc-Electr. Power Appl., Vol. 143, No. 6, November 1996 485
I II,

pq Fl
readout

Fig. 17 Laboratory model of microprocessor-controlledtup changer


A DC offset, sudden current change, fault detector unit
B Microprocessor M68020, inputioutput board, coprocessor M68221
C Power factor measurement
D PLL, 64 samples per cycle
E PLL, 128 samples per cycle
F PLL, 360 samples per cycle
G Zero-crossing detector

6.1 Single-phase laboratory model [8/ 6. 1. 1 Snubber circuits; The switching angle was
A single-phase model of a five-tap thyristor tap selected to give the lowest possible turn-on voltage con-
changer controlled by a Motorola 68008 microproces- sistent with an appropriate safety margin. Typically,
sor (Fig. 17) was used to test the implementation of the maximum voltage across a device at turn on was
the instrumentation and control features. Three phase- <50% of the peak tap-section power frequency voltage.
locked loops (PLL) were used, namely Each device has to be rated to withstand the total
voltage, current sampling, 64 pulseskycle range of the tap-change section power frequency volt-
age, hence, with five tap sections the peak voltage at
current switching region, 128 pulseskycle turn on is limited to 10% of the peak power-frequency
switching angle, 360 pulses/cycle voltage experienced by the device. This enabled the
thyristors to be operated without snubber circuits. The
dildt in a device is limited by the transformer leakage
reactance and is well within its capability. It is sug-
gested on the basis of these results that a practical
scheme using distribution-size transformers would not
require snubber circuits for the thyristors or at worst a
a b relatively small snubber circuit with a low loss.

6.2 Switching logic


Voltage and current zero crossover points were used to
initiate and stop a counter defining angle @.The value
of $ and the current magnitude (Section 6.3) were then
applied to look-up tables to define the appropriate
value of a as discussed in Section 4.
d The secondary voltage was measured and conven-
tional tap-changer control used to maintain a near-con-
stant secondary voltage without hunting. An additional
feature (if required) was the switching of two or more
taps at the same time to handle large sudden changes
of primary voltage. However, this increases the switch-
-,-- ----- ing duty on a thyristor. Fig. 18 shows typical current
--
e waveforms during a tap transition.
Fig. 1S Typical measured current switching waveforms on tup changing If the load current is very small, say, less than 0.003
a Switching down a = 0" lagging p.f.
b Switching up a = -15" lagging p.f. per unit, the measurement of (9 is not easy. Since the
c Switching down a = -10" unity p.f. overlap angle on tap changing is now very small, it is
d Switching up a = -5" unity p.f.
e Switching down a = -10" leading p.f. quite safe to use a fixed angle of a which depends on
f Switching up a = 0" leading p.f. X,,,,, Typically a = -10" for X,,,,, = 0.1p.u.
486 IEE Proc -Elect? Power A p p l , Val 143 No 6, November 1996
The switching logic could be readily arranged (if detected in a fraction of a cycle. Typically, a fault was
required) to include specific secondary voltage/load indicated by four successive current samples (at 64
current characteristics, e.g. near-constant voltage at a pulses/cycle) exceeding a specified value of 3 p.u.
remote load. Both the detection and the multiple tap transition of
fault currents were successfully irnplemented in the lab-
6.3 Voltage and current measurements oratory model.
Current and voltage sampling at 64 sampleslcycle was For transformers operating at relatively low system
used to determine the power and RMS values of V and voltages there is the possibility of using a thyristor with
I. Stored values of power at 10s intervals enabled the an appropriate snubber circuit as the bypass switch.
daily (or more) energy consumption to be monitored.
The DC component of a cycle was found and if greater 6.7 Overvoltage considerations
than a preset ratio then tap transition was inhibited. Probably the most onerous duty on the thyristor bank
The sampling frequency in the region of voltage zero is the overvoltage owing to steep-fronted lightning
was doubled to 128 samples per cycle. Corresponding surges being propagated into the transformer. The ini-
samples of current in the previous cycle and the present tial voltage distribution across a transformer winding is
cycle were compared to indicate a change of slope very dependent upon the inherent capacitance distribu-
which would affect the angle at current zero and hence tion. Usually the turns at the low potential or earthy
change the effective power factor. Tap transition was end of the winding are subject to the least onerous duty
inhibited if these measurements showed that the change and hence the tapped winding should be connected
of angle at which current zero would occur could lead here.
to a possible ‘unsafe’ switching condition i.e. a large The design must ensure that the thyristor overvolt-
circulating current. ages are limited to a safe value. 1 t may be necessary to
limit the magnitude by, say, zinc oxide nonlinear resist-
6.4 Overload condition ances and the critical dvldt by swamping the inherent
The metered value of current indicates any overload capacitance of the tapped winding by a capacitor. The
condition. It is suggested that the energy history of the difficulty of quantifying this duty and the expense of
transformer (Section 6.3), together with a knowledge of the protective elements suggests that the only viable
the transformer thermal time constant could be used to application of a solid-state tap changer is when the
give a measure of the overload capability at any time. location of the transformer and its associated feeders
attenuate the magnitude and especially the wavefront
6.5 Transformer energisation steepness of any incoming surges to a moderately safe
One thyristor pair must be gated to ensure that on value.
transformer energisation the thyristor bank does not Overvoltages due to switching operations in the sys-
experience full secondary voltage. However, even in tem are usually in the kilohertz frequency range and
this state on energising the transformer onto a static the maximum value is usually defined as a multiple of
load the voltage duty on the thyristors may be very the peak phase voltage. Conselquently, the thyristor
onerous before current is established in the thyristor. It dvldt rating is usually adequate when the voltage rating
is considered necessary to have a bypass device across is sufficient.
the thyristor pair connected to the midpoint of the
tapped section, as shown in Figs. 1 and 2. After an 6.8 Thyristor failure and redundancy
appropriate time following transformer energisation, With the solid-state tap changer schemes considered
this thyristor pair would be turned on and the bypass above the failure of a thyristor is serious. Unless reme-
switch opened. The bypass switch could be, say, a vac- dial action is taken the failed thyristor will produce a
uum switch and the additional advantages of this short circuit on the tapped winding sections which
scheme are: the control circuitry could be energised could lead to further thyristor failures.
from the transformer, and the thyristor duty could be The statistical risk of such a failure is low since the
reduced on a system fault, see Section 6.6. normal duty on a thyristor is well below its rating, par-
ticularly when the devices are rated to withstand system
6.6 System faults overvoltage as discussed in Section 6.7. If this risk is
The short-time rating of thyristors usually prevents (in unacceptable, redundancy may be included by replac-
terms of cost effectiveness) a thyristor pair from han- ing each thyristor with a pair of series thyristors of the
dling a system short-circuit current for the total fault same rating. In the event of a thyristor failure the thyr-
duration or as required by relevant specifications. On istor in series continues to perform the required switch-
fault incidence the vacuum switch used for the starting ing duty. Grading or damping resistors could be used
up procedure (Section 6.5) could be used to bypass the to share the duty on the two series thyristors. A frac-
thyristor bank, the gate drives of the conducting thyris- tion of the voltages across these resistors could be used
tor pair being turned off on switch closure. If the to monitor the healthy (or otherwise) state of a thyris-
switch closure time is several cycles, continuous tap tor.
changing could be arranged to limit the conducting However, in addition to doubling the number of
period to less than one cycle for each thyristor pair. devices, firing circuits etc., a further disadvantage is the
The switching logic is relatively simple, successive thyr- doubling of the on-state device losses. The extra cost of
istor pairs being switched at a quarter of a cycle after such a scheme would be considerable.
each current zero. The low secondary voltage ensures a
relatively low value of any circulating current which 7 Multitap considerations
may be produced during this period. Even with the
fault current in a thyristor limited to less than one cycle The voltage rating of the thyristors in the schemes con-
the thyristor rating may be dictated by the fault level. sidered above (Figs. 1 and 2) is dependent on the
The current sampling technique enables a fault to be number of taps. Above, say, six taps it is appropriate
IEE Proc -Electr Power Appl, Vol 143, No 6, November 1996 487
to consider ways of reducing the thyristor duty. Qne are turned on and Y is turned off. Again, a disadvan-
method which halves the voltage rating is to split the tage of the scheme is that two thyristors are always
thyristors into two sections as shown in Fig. 19. Con- conducting. Otherwise, the scheme is attractive as the
trol of the extra thyristor pairs Z and Y is relatively tapped winding now requires only half the tappings
simple. Normally, either Z or Y are continuously con- points and the number of thyristor pairs is nearly
ducting. On tap-changing from T7 to T8 the gate halved. However, in some tap positions there is an
drives of thyristor-pairs T7 and Y are removed and additional winding resistance loss owing to the extra
thyristor pairs T8 and Z are turned on consistent with secondary turns in circuit. Bypass switches are included
the appropriate firing logic described previously. The in Figs. 19 and 20.
main disadvantage of the scheme is that the thyristor
losses are doubled since two thyristors are always con- er
ducting. Also the voltage ratings of thyristor pairs Y
and 2. are required to be nearly twice that for the tap- Each phase of a three-phase tap changer may be con-
ping-point thyristors depending on voltage grading. trolled independently as described with some reduction
However, this could be reduced by firing the gate of of the electronic circuitry by multiplexing e.g. the wave-
thyristor T7 when Y has been turned off to define the form sampling circuit. With balanced loading at all
voltage across thyristor pair Y. times the control is considerably simplified. One phase
More than two sections could be used without is controlled, as described, with the firing angles for the
increasing the thyristor losses: the rating of the thyris- other two phases delayed 120" and 240", respectively.
tor pairs connected to the load would have to be
appropriately increased. 8.1 Three-phase ring configuration tap
An alternative arrangement shown in Fig. 20 changer
reverses the winding polarity. With thyristor pair X An alternative arrangement is shown in Fig. 21, which
energised the tap voltages reduce the output voltage. reduces the number of thyristors required by a half.
When the thyristor pairs T7 and X are conducting (i.e. However, there are several disadvantages with this
midpoint voltage) the tap voltage may be reversed by arrangement :
firing thyristor pair Y then turning off thyristor pairs
T7 and X. A halfcycle later thyristor pairs T1 and Y

Fig.21 Three-phase ring-configuration tap changer

leq X
Fi Sectionalised tupping points

0 Sectionulued tupping points with wmding polarity reversed .22 Three-phuse rmg-configuration tup changer schematic diugrum

488 IEE Proc -Electr Power Appi, Vol 143, No 6, November 1996
(i) The thyristor rating is increased: voltage by a factor As with the single-phase scheme described previously
of d3 and current by 1.5. it is advantageous to switch at the lowest value of the
(ii) Three-phase currents must be nearly balanced if instantaneous forward voltage (consistent with safety
onerous tap short-circuit currents are to be avoided. margins) to give the lowest dvldt across the thyristors.
It may result in near-maximum peak values of current
(iii) Secondary windings must be star connected and an being commutated but the winding leakage inductance
earthed star point is not possible. effectively limits the dildt value.
Only a brief treatment of the control features and per- A computer program was written to plot switching
formance are given since the scheme has obvious limi- current and voltage waveshapes [8] and a three-ring
tations. Considering a three-tap scheme as shown in laboratory model was built and tlested. Satisfactory tap
Fig. 22 the corresponding steady-state device currents changing was carried out over a wide power factor
and nonconducting device voltages are shown in Figs. spectrum and experimental results validated the theo-
23 and 24 for a balanced resistive load. retical waveforms. Representative results are given in
An appropriate switching logic is to turn on a device Figs. 25 and 26.
when it is forward biased and there is current flowing However, due to the limitations mentioned previ-
in a device in the same leg. Typically, the device which ously the use of a single-phase tap changer in each limb
is to be turned off has its gate-firing pulse removed is advocated.
some time, say, 2 0 0 before
~ the parallel device is fired.
Table 1 summarises the switching angles for the whole
power factor spectrum for one leg assuming negligible
overlap. The other two legs are switched consecutively
at intervals of one third of a cycle as the load is
assumed to be balanced. The switching angles are read-
ly3
0
I f-c\ vy3 l

ily modified to include the effect of finite values of 'Y2


0
L
I
A
0.020
,
1
0.020

overlap angle.

I 'TZ2

ix3 I

0 0
0.020
1x2
0 '
L I vx3 / ! 0.020
L

wt
Fig.23 Three-phase ring-configuration tap changer: steady-state cur- Fig.25 Switching-down voltage and current waveshapes or rmg config-
rents in ring 2 uration three-phase tap changer near-unity power-factor &ad:'co&uted
values

Fig.26 Switching-down voltage and current waveshapesfor ring-confg-


Fig.24 Three-phase ring-configuration tap changer: steady-state volt- uration three-phase tap changer near-unity power-factor load: measured
ages across nonconducting devices in leg X results

Leading up 30 to (210-x)" + +
down 0 t o 30" where 120" 240"
Lagging up ( 3 0 + ~ t)o 210" 0 <I$ < 30" X= 0
down 210 t o (240+I$)" 30 < I$ < 90"X = e30"

489
Table 2:Case studies
Notes A B C
Transformer rating, MVA 100 5 1
Number of phases 3 3 1
Winding phase voltage, kV RMS 331d3 1 1ld3 3.3
Tapped winding secondary secondary primary
Rated current, kA RMS 1.75 0.26 0.3
with 100% overload, kA RMS 3.5 0.54 0.6
Transformer reactance, per unit 0.15 0.05 0.03
Number of tap sections 16 16 8
Tap voltage, per unit 0.0125 0.0125 0.02
Tap inductance, mH 0.032 0.024 0.01
Number of tap groups 2 2 1
Overvoltage factor 1 4 4 5
M a x i m u m device voltage, kV RMS 0.95 0.64 0.53
Peak voltage on turn on, Vp 84 57 47
Redundancy built in? Yes no no
Bypass switch 2 vacuum vacuum thyristor
switch switch HRC fuse
Transformer efficiency, per unit 0.994 0.99 0.985
Transformer loss on full load, kW 600 50 15
Solid-state loss on full load, kW 3 34 2.6 0.5
Fault MVA 600 70 20
Peak fault current, kAp 4 26.8 9.3 15.5
eq uiva Ie nt ha If cycle, kAp 5 32.8 11.4 19.0
Number of thyristors 252 126 18
Suggested thyristor rating:
current, kA average 6 2.0 0.4 0.4
peak voltage, kVp 7 5.4 4.0 4.0
max dildt, A l p 8 4.7 1.6 2.7
peak voltage on turn on, Vp 9 84 57 47
peak current, kAp 10 33" 12* 19t
max dvldt, vlus 11 ** ** **
1 Overvoltage factor is multiple of peak phase voltage
2 Case C requires HRC fuse co-ordination to limit peak current
3 Solid-state loss is based on (thyristor volt drop = 1.8V)(average full-load current)(number of series
thyristors)
4 Peak fault current = 2.55 (RMS short-circuit current)
5 Equivalent halfcycle = halfcycle of 50Hz sinusoidal current
6 Rounded-up values
7 Rounded-up values: case A assumes redundant thyristor shares any abnormal system overvoltage
8 Based on short-circuit current; thyristor current and voltage ratings are strongly dependent on associ-
ated power system characteristics
9 Rounded-up values; with multiple-tap transitions values are multiplied by number of taps changed
10 * Thyristors may require higher value of average current rating to satisfy peak current requirement;
t either prospective peak value of 19 kA is limited by HRC fuse co-ordination or thyristor average cur-
rent rating is increased
11 ** Safe values may necessitate higher value of peak voltage rating, Section 6.7

Case studies ately rated thyristor pair could be used for the bypass
switch with a series high rupturing capacity (HRC) fuse
Three schemes are considered (Table 2) ranging from a for fault clearance co-ordinated to reduce the actual
single-phase distribution transformer (in which the risk peak fault current below its prospective value.
of failure of a thyristor operating well within its rating
is considered to be negligible) to a large three-phase
transformer with built-in redundancy to give maximum
reliability. It is assumed that both three-phase schemes The switching logic for a transformer solid-state tap
have to handle unbalanced loads and therefore the changer has been developed and applied to a labora-
three-phase scheme considered in Section 8.1 is not tory model giving satisfactory operation over the com-
suitable and each phase must be controlled independ- plete power-factor spectrum under normal operating
ently. conditions. A sampling technique for the measurement
Vacuum switches are used as bypass switches in the of voltage and current values dnd a microprocessor
two larger schemes. At the lowest rating an appropri- based controller were used to implement the required
490 IEE Proc.-Electr. Power Appl., Vol. 143, No 6, November 1996
switching strategies. The combination of power elec- leakage inductance and resistance proportional to the
tronics and microelectronics with a conventional piece number of turns i.e. n(R2 + jX2). The magnetising cur-
of power equipment provides a flexible arrangement rent and the winding resistance R, are relatively small
including not only the main requirement of voltage and may be neglected giving the equivalent circuit of
control but also many additional features such as Fig. 27c. A short-circuit on the secondary winding,
instrumentation, data logging protective aspects, etc. Fig. 27d produces a steady-state current of magnitude
As with all power electronics equipment the power loss
in the semiconductor devices is not insignificant.
+ +
I,, = V,/(X, XI X , ) per unit (5)
Under abnormal system behaviour there may be high A short circuit on the tapped winding Fig. 27e gives a
fault currents or system overvoltages owing to switch- steady-state primary current of
ing operations or lightning surges etc. The viability of a
solid-state tap changer generally capable of handling
+ +
IlSc= V s / [ X s X I ( X a / n ) ]per unit (6)
and a steady-state current in the short-circuited tap of
any or all of these requirements is questionable unless
the very fast response time achieved is mandatory. +
It,, = nIlsc = V , / [ n ( X , X , ) ] per unit (7)
Only if the transformer situation considerably reduces Comparing eqns. 7 and 8 the ralio of the short-circuit
the degree of exposure to high fault currents and, more currents is
especially, steep-fronted surge voltages can the scheme
approach cost effectiveness.
short-circuited tap section - X , XI X ,
-
+ +
Any tap changer scheme must be reliable. The statis- short-circuited secondary + +
n ( X , X I ) X2
(8)
tical risk of a thyristor failure is extremely unlikely Since n is relatively small n(X, -t XI) << X2 and the
owing to the relatively low duty on a device under nor- ratio becomes ( X , + XI +X2)IX2 approximately. This
mal operation compared to its rating. However, if this gives a tap steady-state short-circuit current of approx-
degree of risk is unacceptable built-in redundancy may imately
be included at considerable extra cost. I, = t a p voltage __
-_ ~-nVs --
K
t a p leakage reactance nX2 X z (9)
11 Acknowledgment
It is seen that the steady-state talp short-circuit current
Dr Yousef-Zai is indebted to the Government of Paki- is at least twice the secondary short-circuit current
stan for granting a scholarship and North-West Fron- (assuming, typically, that XI = X2 and with finite sys-
tier Province University of Engineering and tem reactance X,). Additionally, there may be a DC
Technology for study leave to undertake research at component depending on the voltage phase angle at
Bradford University. switching.

12 References
ROBERTS, M.E., and ASHMAN, W.G.: ‘A thyristor-assisted
mechanical on-load tap changer’. IEE Conf. Pub. 53, 1969, pt. 1,
pp. 185-192
COOKE, G.H., and WILLIAMS, K.T.: ‘New thyristor assisted
diverter switch for on-load transformer tap-changer’, ZEE Proc.
B, 1992, 139, (6), pp. 507-511
SHUTTLEWORTH, R., TIAN, X., FAN, C., and POWER, A.:
‘New tap-changing scheme’, ZEE Proc., Electr. Power Appl., 1996,
143, (l), pp. 108-112
MUSGRAVE. G.. and O’KELLY. D.: ‘Imorovement of Dower
system transmission by solid-state ’ techniqces’. IEE Conf: Pub.
123, 1974, pp. 228-233
O’KELLY, D., and MUSGRAVE, G.: ‘Improvement of power
system transient stability limits’, Proc. IEE, 1973, 120, (2), pp.
247-253
GUTH, G., BAKER, R., and EGLIN, P.: ‘Static thyristor-con-
trolled regulating transformer for AC transmission’. IEE Conf.
Pub. 205, 1981, pp. 69-72
ARRILLAGA, J., and DUKE, J.M.: ‘A static alternative to the
transformer on-load tap-changer’, ZEEE Trans., 1980, PAS-99,
(l), pp. 86-91
YOUSEF-ZAI, F.Q.: ‘Fast-acting solid-state transformer tap-
changer’. PhD thesis, University of Bradford, 1990

13 Appendix. System and transformer tap short


circuits I
e
vs
e
Consider a transformer Fig. 27a with a leakage flux Fig.27 Short-circuit Considerations
a Transformer schematic
path as shown in Fig. 27b. It is reasonable to assume b Leakage flux path
that the leakage flux linkage is proportional to turns. c Equivalent circuit, p.u. values
d Secondary short circuit
Hence the tapped portion of the secondary winding has e Tap short circuit

ProcElectr. Power Appl., Vol. 143, No. 6, November 1996 49 1

Potrebbero piacerti anche