Surge Protection

EP D TN 24V-230V/16A (/FM)
EnerPro D TN

2-pole EN T3 (VDE category C) Surge Arrester IEC class III

Surge Protective Device for different voltages 24-120V AC and for single phase 230V AC TN- net systems

EP D TN 48V/16A

• Surge Arrester SPD type 3 T3 (IEC SPD class III for up to 16A fuse size
• Unprotected and protected side strictly separated
• Different voltage ranges from nominal 24V AC up to 230V AC
• Longitudinal and transversal surge protection
• No Leakage current to PE! Avoid AC corrosion of grounder
• Line- and function control by LED
• Potential free thermal remote signal contact (/FM) as an option)

Product description
EP D TN 24V-230V (/FM) is a two-pole single phase class III Surge Arrester with LED, which makes a
protection for single phase consumer equipment in the size of only 17.5mm width (1 DIN-module size)
possible.
The green LED indicates whether the operating voltage is available and the protection circuit is in function.
The varistors in the SPD are equipped each with a thermal safety sensor with N.C. contact which cut-off the
varistors from active lines if thermal overloaded by too high leakage current.
The safety cut-off contact operates in such way that it will not influence the active lines and equipment is kept
in function without interruption.
When this safety cut-off contacts response, the green LED will extinguish, and the SPD has to be replaced.
The optional thermal coupled N.C. remote signal contact (/FM) will open too.
The easy to install compact 1 DIN-module robust Polycarbonate housing can be comfortable snapped on a
35mm DIN-rail (size DIN EN 50022).

Application
These SPD serve for the 3rd-stage surge protection of consumer equipment and fulfil IEC class III (EN SPD
type 3 T3 ). Installed at the interface 2-3 acc. to lightning zone conception indicated in IEC 62305 part 1-4
(VDE V 0185 Teil 1.-4).

Protects People and Valuables


Technical data: protection for single phase consumer equipment
Type Art. No. Type Art. No. Remark
EP D TN 24V/16A 38 05 50 EP D TN 120V/16A 38 05 59
EP D TN 24V/16A/FM 38 05 51 EP D TN 120V/16A/FM 38 05 60 with remote contact
EP D TN 48V/16A 38 05 53 EP D TN 230V/16A 38 05 62
EP D TN 48V/16A/FM 38 05 54 EP D TN 230V/16A/FM 38 05 63 with remote contact
EP D TN 60V/16A 38 05 56
EP D TN 60V/16A /FM 38 05 57 with remote contact

EP D TN EP D TN EP D TN EP D TN EP D TN
Type 24V/16A 48V/16A 60V/16A 120V/16A 230V/16A
Protection class (category) acc. to
IEC 61643-1 class III
EN 61643-11 SPD type 3 T3
E DIN VDE 0675-6 11/98-A1 D
Nominal AC voltage 50/60 Hz UN [V] AC 24 48 60 120 230
Rated voltage (max contin. operating voltage) (50/60 Hz) UC [V] 30 60 75 150 255
Max. permissible line fuse In [A] 16 A gL
Protection level at 1 kV/µs UP [kV] ≤ 0,22 ≤ 0,35 ≤ 0,5 ≤ 0,7 ≤ 1,25
Voltage protection level at isn (In ) and 1,2/50µs (UOC 6kV UP [kV] ≤ 1,0 ≤ 1,0 ≤ 1,0 ≤ 1,0 ≤ 1,5
Response time tA [ns] < 25
Nom. discharge current (8/20 µs) 10 times isn [kA] 5
Max. discharge current (8/20 µs) Imax [kA 8
Operating temperature range t [°C] -40 … +80
Min. cross-sectional area 1,5 solid / 1,0 flexible with sleeve
Max. cross-sectional area (DIN 46288) [mm²] 2,5 solid / 1,5 flexible with sleeve
Max. cross-sectional area for remote signal contact FM [mm²] 1,5 solid or flexible with sleeve
Max. switching capacity of remote signal -contact FM [V/A] 1 N.C. 250V / 0.5A AC
Material of Housing / colour Polycarbonate (halogen free) UL94-V0 / yellow
Environment protection category IEC 60529 IP 20
Mounting on 35mm DIN-rail (DIN EN 50022)

Dimensions in mm Diagram
DIN size housing: protected side
1 DIN module (DIN 43880)

unprotected side

LEUTRON GmbH
Telephone +49 711 / 9 47 71-0
EP D TN 24V…230V / 16A (/FM) Subject to technical modifications and
Lightning & Surge Protection
Telefax +49 711 / 9 47 71-70
27.09.2006 .pdf Humboldtstrasse 30-32
delivery possibilities Email: info@leutron.de
© 2006 by LEUTRON GmbH D-70771 Leinfelden-Echterdingen
www.leutron.de
GERMANY