Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
LOCATION: Elgin, IL
4. Sprinkler Constant K:
Other __________________________
5. Piping Constant C:
a. Underground: 140
b. Overhead: 120
b. The sprinkler spacing coverage shall not exceed the listing per sprinkler. Greater sprinkler
spacing coverage is allowed if the sprinkler is U.L. listed for greater coverage.
b. q1 is 18 gpm minimum for one calculated sprinkler, 13 gpm minimum if two sprinklers are
calculated, or the flow is based on the U.L. listing of the sprinkler being used.
d. Listed for 13 gpm minimum. Verify that the listed gpm is equal to the q1 in the calculations.
e. q1 = 13 gpm.
2
⎛ q1 ⎞
a. Pt1 = ⎜ ⎟
⎝K⎠
2
⎛ 13 ⎞
b. Pt1 = ⎜ ⎟ = 11.11 – 11.40 psi minimum.
⎝ 3.9 ⎠
c. Verify that Pt1 is equal to or greater than the minimum operating pressure of the sprinkler’s
U.L listing.
11. Check to see if the pipe sizes Ps in the calculations match the pipe sizes on the drawing. Yes
12. Check the friction losses through the sprinkler piping psi/ft.
a. Do the friction losses (psi/ft) match the friction loss tables? Yes
14. Check the elevation loss Pe = 8 ft. x .434 = 3.5 psi loss.
a. qd = 5.0 gpm.