Sei sulla pagina 1di 4

Issued by Switchgear Contracts Division LARSEN & TOUBRO LIMITED Powai Works, Bombay 400 072.

October-December 1994

Prospect/Retrospect Forthcoming Product

High
Coordination For Performance
MCCB
Motor Protection Larsen & Toubro Limited is shortly
adding a high performance
moulded case circuit breaker
(MCCB) to its existing product
Squirrel cage induction motors are provide reliable coordination with range. Designated as Type DH 100,
the prime movers of Indian industry. downstream equipment. it offers 25kA breaking capacity,
With increasing automation all low let-through energy and allows
around, our dependence on a However, some of the customers termination of both copper and
reliable protection system is have started using Moulded Case aluminium cables of size up to 50
increasing. In the event of a fault, it Circuit Breakers (MCCBs) as a short sq. mm.
is expected that the protective circuit circuit protective device. MCCBs
acts rapidly and clears the fault such have mechanical limitation of It is suitable for operation at 415 V.
that the healthy control devices are minimum operating time. Hence, This MCCB comes with 3 poles and
unaffected and can be put back into let-through energy of MCCBs is different current carrying capacities
operation with minimum downtime. much more as compared to that of of 16, 20, 25, 32, 40, 50, 63, 80 and
fuses. This necessitates detailed 100 amps. Accessories available
To achieve this, detailed study of engineering during system design. are: shunt release, undervoltage
the total system is essential. The Since all switchgear manufacturers release, auxiliary contact block
system designer must ensure do not have complete range of (1 NO + 1 NC), trip alarm contact,
proper coordination among various fuses, contactors, overload relays door interlock and interlock defeat
equipment and cables. The and MCCBs, coordination and facility. To make it convenient to
protective device should operate selection of components becomes use, a rotary operating handle is
quickly so that the energy let complex. Only a manufacturer provided. A red trip push button
through the circuit during the fault is having consistent quality and total helps check the operation of MCCB.
restricted to a level lower than the range of products will be in a
withstand capability of other devices position to offer a reliable Type DH 100 is designed for the
and cables. coordinated system. utilisation Category A, and has a
magnetic threshold capacity of 9
In this issue of L&T Current Trends, times the rated current. During short
In Indian industry, fuses are
we bring you the considerations circuits, it disconnects the supply
predominantly used as short circuit
involved in selecting a suitable short within 10 milliseconds. This MCCB
Protective device. They have a
circuit protective device for a motor conforms to IEC 947-2 and IS
proven track record and they
circuit. 13947 Part 2.
Feature

Short Circuit
Protective Devices
- P. Ramachandran,
Manager, Switchgear Design & Product Development

Industrial processes are becoming Type 1 co-ordination requires that, out to be very expensive. Type 2
progressively sophisticated and the under short-circuit conditions, the co-ordination has a major
cost of downtime is increasing. With contactor or the starter shall cause advantage. After the fault is cleared,
a large number of induction motors no danger to persons or the user needs just to reset the
in use, the protection system for installations and may not be breaker or replace the blown fuse
them has become an important suitable for further service without and check for contact welding. Type
aspect in order to have minimum repair and replacement of parts. 1 co-ordination is cheaper during
downtime of the plants. So installation but Type 2 will prove to
designing a cost effective motor Type 2 co-ordination requires that be economical in the long run.
supply circuit and ensuring its under short-circuit conditions, the
safety under all operating conditions contactor or starter shall cause no Fuses as SCPDs
is of paramount importance. danger to persons or installations
and shall be suitable for further use. Fuses are traditionally used as
Motor circuit designers have a lot to The risk of contact welding is SCPDs because of the low initial
think about in selecting control recognized. capital cost and their capability to
components and in providing interrupt faults faster. Fuses have
adequate protection. The need for These standards replace the three
excellent current limiting
more precise protection is types of co-ordination defined by
characteristics and can be applied
heightened by another factor. There the earlier standards on starters -
safety on systems having high fault
is a trend towards installing motor IEC 292-1: 1969 and IS 8544
levels. They have been the
starters in Motor Control Centres (Part 1): 1977.
undisputed champions in the area
(MCCs). This has led users to size Type 1 co-ordination is easy to of circuit protection for a long time.
motor feeder cables economically. achieve but in the event of a short- Using fuses for short-circuit
When a short-circuit occurs, the circuit, the user has to check all the protection is found to be the easiest
Short Circuit Protective Device starter components and replace and most effective way of achieving
(SCPD) takes a finite time to interrupt them if found necessary. This works Type 2 co-ordination.
the fault. During this time, the current
rises rapidly and certain energy is let
through is higher than the withstand
capacity of the downstream
equipment, it can cause damage to
the equipment. So achieving proper
co-ordination means matching the
characteristics of SCPD and the
downstream equipment including
cables to ensure that the let-through
energy and peak cut-off current do
not rise above the levels that the
circuit can withstand.

Types of Co-ordination
IEC 947-4-1: 1990 and IS 13947
(Part 4/Section 1) : 1993 standards
on starters and contactors define
two types of co-ordination: Type 1 Fig. 1.
and Type 2.

2 L&T Current Trends, October-December 1994


The principle strength of a fuse To meet these stipulated
is its ability to reduce energy requirements, the current limiting
let-through at high fault levels. At MCCB must respond quickly in case
high currents, the fuse element gets of a fault. To achieve high speed
hot and melts (pre-arcing period). contact separation, closely spaced
This is followed by arcing which contact fingers carrying current in
persists until the resistance across opposite directions create a strong
the fuse builds up to a sufficiently magnetic repulsion between the
high value to reduce the current to conductors (see Figure 1). High
zero (arcing period). Both actions speed contact separation is actually
take place very quickly - about 2 produced by electromagnetic
msec for pre-arcing period and 4 repulsion forces generated by the
msec for arcing period - making fault current itself. The higher the
the total operating time of about 6 current, the greater is the force
msec in the event of short circuit. pushing the contacts apart. Although
The combination and high speed rapid contact opening is important,
operation and high arc resistance just opening the contact quickly is
limits the peak fault current and not enough. The next concern is to
reduces the let-through energy. control the arc voltage across the
contacts to ensure proper arc
MCCBs as SCPDs extinction. This is accomplished by
forcing the arc into the arc chute and
• Conventional MCCBs: stretching the arc. The elongated arc
is cooled and broken into segments
MCCBs as SCPDs have been in the arc chute until it is de-ionized
Fig. 2. Current restricting and ceases to conduct current, thus
compared, not always favourably,
with the fuses ever since they were capabilities of current limiting and being extinguished.
introduced. The first generation of conventional MCCBs.
MCCBs had low short-circuit Final requirement for current limiting
cables, resulting in cost efficient
breaking capacity and high operating operation is that the trip mechanism
control system.
time. The breaking capacity offered must operate quickly enough to
by the earlier MCCBs was limited to co-ordinate with the rapidly moving
The standards on circuit breakers
30-35 kA with an operating time of contacts. The mechanism must trip
- IEC 947-2: 1989 and IS 13947
15-20 msec. The traditional MCCB the breaker before the spring loaded
(Part 2): 1993-define current limiting
was a zero-point device, that is to contacts can re-close on the fault.
breaker as the one with a break
say, in the event of a short circuit, it time short enough to prevent the
was unable to clear the fault till it short-circuit current reaching its Figure 2 shows how a typical current
completed the first half-cycle. During prospective peak value. As per UL limiting MCCB restricts the let-
this half-cycle, the entire circuit would standard, a current limiting breaker through energy and peak current
undergo tremendous stress, at times when operating within its current compared to conventional MCCB. On
resulting in damage to the limiting range, limits the let-through a prospective short-circuit current of
downstream equipment. energy to a value less than the 70kA, the installation protected by
energy of 1/2-cycle wave of the the current limiting MCCB would get
Still, MCCBs were considered as symmetrical prospective current. less than 15% of the prospective
SCPPs since they offered features
like remote tripping , remote
signalling, reusability after the
interruption of fault, protection
against single phasing and
undervoltage.

• Current Limiting MCCBs


Introduction of current limiting
MCCBs has resulted in a big
breakthrough in the reduction of let-
through energy in a system and
getting very high breaking capacity
(even of the order of 200 kA).
Current limiting MCCBs can reduce
both the peak fault current and
energy that reach downstream
equipment to a tolerable level. Thus,
motors and cables connected to the
system will not be exposed to high
Let-through energy. With this, the Fig. 3. Selection criteria of MCCB for more protection.
current limiting MCCB helps in
using lower size devices and
3
L&T Currents Trends, October-December 1994
peak current and thermal energy A fuse is better than a current requirement. However, everyone will
compared to that experienced by the limiting MCCB in providing agree that:
installation protected by a protection against the effects of
conventional MCCB. short circuits at very high fault 1. It is possible to achieve Type 2
levels. But in most of the cases, the co-ordination with the help of
MCCB Selection Criteria short-circuit currents are limited by either fuses or MCCBs.
the contactor, relay and cable
In selecting MCCBs for motor 2. MCCBs result in a higher let-
impedance, generally up to 30
protection, the following points are through than a fuse so it may be
times the rated current of the motor.
to be taken care of (Figure 3) : necessary to use a larger
In such events, the MCCB acts
faster than any other type of contactor and/or a CT operated
1. The thermal rating of MCCB relay.
should be greater than or equal protective device available.
to the motor full load current. 3. MCCBs have the advantage
While comparing fuses with MCCBs, that they can be reset, whereas
2. The breaking capacity of the it is essential to compare the blown fuses have to be
MCCB should be greater than systems. MCCB results in a higher replaced, which means keeping
or equal to the prospective fault let-through than a fuse, so it is stock of fuses. In certain
current at its installation point. usually necessary to use a bigger applications, where the cost of
3. The magnetic threshold of the size of contactor and/or a CT downtime is very high, this
MCCB should be selected in operated relay. This occupies larger point is very important.
such a way so as to avoid panel space resulting in increased
nuisance tripping during costs. 4. Though the popularity of
starting of the motor. MCCBs is on the rise, the
Selection of Equipment Indian market is dominated by
4. The best protection can be fuses.
provided by selecting a current The only way to ensure Type 2 Co-
limiting MCCB with only 5. Use of fuses result - in cost
ordination, is to carry out exhaustive
magnetic protection and a savings directly and indirectly -
tests of particular fuse + relay and
suitable thermal overload relay savings through lower initial
MCCB + relay combinations with the
with matching motor costs, usage of lower sized
contactor. While individual
characteristics. contactors and directly
protection devices may perform to a
operated relays, and less panel
5. The thermal characteristics of given set of characteristics, their
space.
MCCB (if provided) should be behaviour in combination affects the
such that it falls above the way the circuit reacts to a fault. 6. To ensure reliable co-
overload relay characteristics Selection of equipment becomes ordination, it is important that
up to the magnetic threshold of very important here. To complicate all protective equipment are
the MCCB. the matter further, in most of the available from a single
cases, not all devices are available manufacturer.
6. The contactor should be able to from a single manufacturer. For
break any currents up to the example, if the fuse/MCCB
magnetic threshold of the breaker. manufacturer does not make relays L&T's Excellent
or contactors, he has to depend on
7. The starter should be able to other makes to offer complete Half-year Results
withstand the let-through protection system. It is likely that
energy of the breaker. Larsen & Toubro Limited has
the relay or the contactor produced excellent results for the
Comparison of Fuses with MCCBs undergoes some design changes half year ended September 30,
which can affect the selection 1994. Sales and service revenues
One constraint against the combination with the fuse/MCCB.
were Rs. 1,450 crores as against
acceptance of MCCB is the initial Thus it is very important that all Rs. 1.242 crores in the
cost when compared to the cost of protective equipment are available corresponding period last year - an
the switch-fuse unit (SFU). But for from a single source to offer proper increase of 17%. Profit before Tax
more complete comparison of co-ordination. Alternatively, such has gone up to RS. 144.6 crores
costs, one must also consider the tests are required to be carried out
from Rs. 112.4 crores - showing
other aspects like ease of periodically.
an increase of 29% due to
maintenance, downtime, simplicity improvement in the operating
of operation, recurring costs, etc. To Conclusion margins. The provision for tax is
sum up, current limiting MCCBs do higher at Rs. 32 crores as against
have a number of practical The argument which centres Rs. 27 crores in the corresponding
advantages over fuses if one around short-circuit protection is the period last year. Profit After Tax has
considers these to be worth the choice between fuses and current gone up substantially from Rs. 85.4
extra cost. These advantages will limiting MCCBs. The reasons being crores to Rs. 112.6 crores - an
have to be weighed against the put forward are both technical and increase of 32%. Based on the
advantages offered by fuses like low commercial. Since each has its own share capital as at September 30,
initial cost, very high breaking merits, there is no clear-cut answer. 1994, the annualised EPS works out
capacity, very low peak cut-off So, the choice depends on the to Rs. 10.62 as against Rs. 8.09 as
current and let-through energy, etc. application and the user at September 30, 1993.
Edited, printed and published by Cerena de Souza for Larsen & Toubro Limited. Published from L&T House, Ballard Estate,
Bombay 400 001 and printed at Vakil & Sons Ltd., 18 Ballard Estate, Bombay 400 001. Associate Editor : Luis S. R. Vas.

Potrebbero piacerti anche