Sei sulla pagina 1di 1

Firestop PU foam PUFS-R

Foams and sealants


One-component PU hand foam for firestop applications, tested
EI 240

BUILDING MATERIALS
Bonds to all standard building
materials such as:
▪ Concrete
▪ Anodised layer
▪ Masonry
▪ Metals
▪ Wood
▪ Gypsum plasterboard
▪ Plastics (not on PE, PP, Teflon,
silicone)
▪ Stone

ADVANTAGES APPLICATIONS FUNCTIONING


▪ Fire resistant up to 240 minutes (EI Tested for: ▪ Surfaces have to be dry, clean and
240) according EN 13501-2:2007 ▪ Filling of vertical and horizontal free of oil, grease or dust.
+ A1:2009. linear joints on walls, or between ▪ Shake the can for at least 20
▪ Meets the requirements of walls and slabs in concrete or seconds before use and screw the
Ministerial Decree 16 February masonry, with thickness and density adaptor with straw onto the valve.
2007 - Classification of fire equal or greater than tested ▪ Moisten the surfaces with a water
resistance of construction products. (autoclaved aerated concrete, sprayer prior to application.
▪ Excellent acoustic and thermal thickness 200 mm and density 550 ▪ Apply bottom up the foam. Fill the
insulation properties. kg/m³) cavities for 65%, as the foam will
▪ Very good bonding properties. Also suitable for: continue to expand slightly.
▪ Excellent stability (no post-expansion ▪ Filling and thermo-acoustic ▪ Repeat shaking regularly during
or shrink after curing). insulating of door and window application. If work in layers repeat
▪ Cured foam can be work (sawed, cut frames subjected to fire risk moistening after each layer.
and polished), then painted and/or ▪ Filling and thermo-acoustic ▪ Clean tools and fresh foam before
plastered. insulating of wall penetrations hardening with cleaner fischer PUR
▪ CFC and H-CFC free propellant. subjected to fire risk or acetone. Cured foam can only be
removed mechanically.
▪ Protect from UV radiation.

TECHNICAL DATA

Firestop PU foam PUFS-R

http://www.fischerfixingsusa.com/ - 09/03/2017 1