Sei sulla pagina 1di 8

Switchgear Identification: E02+RE02 132KV THURDIBUORO LINE

RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.895.701
Functions Tested: 25-51P-50G Type : Multifunctional Protection

SUMMARY OF WIRED CONTACT OUTPUTS


Contact
Description State Tested
ID

F3 OPEN PHASE A TC1 NO OK

F4 OPEN PHASE B TC1 NO OK

F5 OPEN PHASE C TC1 NO OK

F6 BLOCK AR NO OK

F7 SYNC OK NO OK

F8 CB MANUAL CLOSE NO OK

G3 CB CLOSE COMMAND NO OK

G4 PROT GEN TRIP NO OK

H3 OPEN DS1 NO OK

H4 CLOSE DS1 NO OK

H6 OPEN DS2 NO OK

H7 CLOSE DS2 NO OK

J3 OPEN LINE DS NO OK

J4 CLOSE LINE DS NO OK

2
Switchgear Identification: E02+RE02 132KV THURDIBUORO LINE
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.895.701
Functions Tested: 25-51P-50G Type : Multifunctional Protection

SUMMARY OF WIRED CONTACT INPUTS


Contact ID Description Tested Remarks

F_CC1 (F1) CB 3P-Cose Posit OK

F_CC2 (F2) CB PHA Open OK

F_CC3 (F3) CB PHB Open OK

F_CC4 (F4) CB PHC Open OK

F_CC5 (F5) CB AL SF6 0.51MP OK

F_CC6 (F6) CB Op Lockout SF OK

F_CC7 (F7) SPARE OK

F_CC8 (F8) CB Closing LocDV OK


F_CC9 (F9)
CB Pole Discrep OK
F_CC10 (F10)
CB Prot Mot Swi OK
F_CC11 (F11)
CB Exc Mot run OK
F_CC12 (F12)
CB Heating fail OK

F_CC13 (F13) CB in remote OK

F_CC14 (F14) CB in local OK

G_CC1 (G1) Line DS Mot trip OK

G_CC2 (G2) Line DS remote OK

G_CC3 (G3) Line DS local OK

G_CC4 (G4) Line DS Closed OK

G_CC5 (G5) Line DS Open OK

G_CC6 (G6) ES Open OK

G_CC7 (G7) ES Closed OK

G_CC8 (G8) DSES MCB heat FA OK

G_CC9 (G9) DS1 Mot Prot TRP OK

3
Switchgear Identification: E02+RE02 132KV THURDIBUORO LINE
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.895.701
Functions Tested: 25-51P-50G Type : Multifunctional Protection

G_CC10 (G10) DS1 In Remote OK

G_CC11 (G11) DS1 In Local OK

G_CC12 (G12) DS1 Closed OK

G_CC13 (G13) DS1 Open OK

G_CC14 (G14) DS1 MCB Heat FA OK

H_CC1(H01) DS2 Mot Prot TRP OK

H_CC2 (H02) DS2 In Remote OK

H_CC3 (H03) DS2 In Local OK

H_CC4 (H04) DS2 Closed OK

H_CC5 (H05) DS2 Open OK

H_CC6 (H06) DS2 MCB Heat FA OK

H_CC7 (H07) SPARE OK

H_CC8 (H08) BCPU VT SupplyFA OK

H_CC9 (H09) Block CB Close OK

H_CC10 (H10) SPARE OK

H_CC11 (H11) TC 1 FAIL OK

H_CC12 (H12) TC 2 FAIL OK

H_CC13 (H13) MCB DISCN SUP T) OK

H_CC14 (H14) V METER FAIL OK

H_CC15 (H15) VT REF SINCRO F OK

H_CC16 (H16) SPARE OK

J_CC1 (J01) SYNC Overide OUT OK

J_CC2 (J02) SYNC Overide IN OK

J_CC3 (J03) ILOCK Overide SW OK

4
Switchgear Identification: E02+RE02 132KV THURDIBUORO LINE
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.895.701
Functions Tested: 25-51P-50G Type : Multifunctional Protection

UNBALANCED SYSTEM TO IDENTIFY PHASES (Read values on Primary values)

Phase VOLTAGE INJECTION ACTUAL VALUE CURRENT INJECTION ACTUAL VALUE

V Mag V Angle V Mag V Angle I Mag I Angle I Mag I Angle

A 20 V 0º 24.081KV 0.0º 1A 0º 0.598KA 359.759º

B 40 V -120º 47.924KV 119.615º 2A -120º 1.198KA 119.425º

C 60 V -240º 71.869KV 239.318º 3A 120º 1.801KA 239.057º

VOLTAGE INJECTION ACTUAL VALUE CURRENT INJECTION (G) ACTUAL VALUE

V Mag V Angle I Mag I Angle I Mag I Angle

AUX 63.5V 76.036KV 1A 0.598KA

BALANCED V&I SYSTEM (Read values on Primary values)

Phase VOLTAGE INJECTION ACTUAL VALUE CURRENT INJECTION ACTUAL VALUE

V Mag V Angle V Mag V Angle I Mag I Angle I Mag I Angle

A 63,5 V 0º 76.186KV 0.0º 1A 0º 0.598KA 359.482º

B 63,5 V -120º 76.044KV 119.507º 1A -120º 0.598KA 119.099º

C 63,5 V -240º 76.062KV 239.112º 1A 120º 0.600KA 238.463º

5
Switchgear Identification: E02+RE02 132KV THURDIBUORO LINE
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.895.701
Functions Tested: 25-51P-50G Type : Multifunctional Protection

51P – PHASE TIME OVERCURRENT-


CURRENT INJECTION SETTING VALUE TESTED VALUE CONCLUSION

I Mag I Angle PKP TIME PKP TIME RESULT DATE


(OK/NOT OK)

A 1.5A 0º 0.96A 3.63s OK


IEC CURVE A
B 1.5A -120º 0.96A TDM:0.38 0.96A 3.65s OK 13/3/17
(3.59s)
C 1.5A 120º 0.96A 3.64s OK

CONTACT
OUTPUTS G04 OK 13/3/17
ACTIVATED

LED LED 1 13/3/17

51G– GROUND TIME OVERCURRENT-


CURRENT INJECTION SETTING VALUE TESTED VALUE CONCLUSION

I Mag I Angle PKP TIME PKP TIME RESULT DATE


(OK/NOT OK)

G 0.21A 0º NO PKP - OK
0.22A 3s 13/3/17
G 0.23A 0º 0.22 3.045s OK

CONTACT
OUTPUTS G04 OK 13/3/17
ACTIVATED

LED LED 2 OK 13/3/17

6
Switchgear Identification: E02+RE02 132KV THURDIBUORO LINE
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.895.701
Functions Tested: 25-51P-50G Type : Multifunctional Protection

25 – SYNCHROCHECK-

SYNC SETTING VALUE TESTED VALUE RESULT DATE


(OK/NOT OK)

Voltage Difference 6.35V 6.5V OK 13/3/17

Phase Angle Difference 20º 21º OK 13/3/17

Frequency Slip 20 mHz 20Hz OK 13/3/17

CONTACT OUTPUTS
F07 OK 13/3/17
ACTIVATED

REMARKS:

GE Digital Energy Customer


INSPECTORS Representative
Representative

NAME EDER LAFRAGUA

SIGNATURE

DATE 23/3/2017