Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
© OMICRON Slide 2
Safety Instruction
> The CMC test set can output life-hazardous voltages and
currents.
> Throughout the presentation and user manuals, this symbol
indicates special safety-relevant notes/directions linked to the
possibility of touching live voltages and/or currents. Please
thoroughly read and follow those directions to avoid life
hazardous situations.
> This symbol indicates potential hazards by electrical
voltages/currents caused by, for example, wrong connections,
short-circuits, technically inadequate or faulty equipment or by
disregarding the safety notes which written on the user manuals.
> Note: before you use your CMC devices, please read through
the Section Safety Instructions on the CMC user manual!
© OMICRON Slide 3
Agenda
© OMICRON Slide 4
Distance Protection Principles
© OMICRON Slide 6
Principle and Background
> The principle of distance protection involves the ratio between the
measured voltage and the measured current at the relaying point. The
calculation of the apparent impedance is compared with the reference
(reach impedance). If the measured impedance is less than the reference
impedance, it is assessed that fault occurs within the protected line. Testing
the impedance characteristic (R/X) is the way to prove the operation of the
relay whether it ready to operate or not.
© OMICRON Slide 8
The Principle of Distance Relay
Z2= ZA+50%×ZB
Z1= 80 ~ 85%×ZA
0
ZS IRelay
ZA ZB ZC
VRelay
ZRelay
© OMICRON Slide 9
Example 1
ZS ZL X
185 585 ZL
IRelay = 4.678-16.24 kA
1000 kV
Load (R) ZRelay
200
VRelay = 98.40-2.54 kV
ZRelay = 21.0313.69 R
ZS = Source Impedance
ZL = Protected Line Impedance
© OMICRON Slide 10
Example 2: Fault 50% of Protected Line
ZS 0.5ZL 0.5ZL X
185 2.585 2.585 ZL
1000 kV IRelay = ? ZRelay ?
Load (R)
VRelay = ? 200
ZRelay = ?
© OMICRON Slide 11
Example 2: Fault 50% of Protected Line
ZS 0.5ZL 0.5ZL X
185 2.585 2.585 ZL
> 1000
Example
kV
2: Fault 50% of Protected Line
IRelay = 28.57 -85 kA
Load (R)
VRelay = 71.430 kV 200 ZRelay
ZRelay = 2.585
Load (R)
VRelay = 83.330 kV
> Example 3: Fault 200
100% of Protected
Line
ZRelay = 5.085 ZRelay
© OMICRON Slide 12
Example 4:
Fault 50% of Protected Line with Arc Resistance
ZS 0.5ZL 0.5ZL
185 2.585 2.585
1000 kV
IRelay = 28.57-85 kA
VRelay = 71.430 kV X
ZL
ZRelay = 2.585
ZRelay
IRelay = 26.94-70.18 kA
VRelay = 74.27-5.32 kV
ZRelay = 2.75764.858
R
© OMICRON Slide 13
ZS 0.5ZL 0.5ZL
Calculations 185 2.585 2.585
1000 kV
RF RLoad
10 200
© OMICRON Slide 14
Impedance Characteristic
> A zone characteristics can consist of any number and combination of line,
circle or arc elements.
> MHO
> Polygon
© OMICRON Slide 15
Impedance Characteristic
X X
R R
© OMICRON Slide 16
Impedance Characteristic
X X
R R
© OMICRON Slide 17
Impedance Characteristic
X X
R R
© OMICRON Slide 18
Example
© OMICRON Slide 19
Fault Calculation
© OMICRON Slide 21
Loop Impedance (ZLoop)
> Phase–Phase Fault:
IFault ZL
Test Impedance 2
ZL VFault = VA-VB, VB-VC or VC-VA
ZS
V =V IFault = IA-IB, IB-IC or IC-IA
Fault Ph-Ph
ZL
2
21 1
, 2
Phase-Phase Fault
> 3 Phase Fault:
ZL
Test Impedance 1
ZS ZL ZL VFault = VAN = VBN = VCN
IFault = IA = IB = IC
ZL
IFault N
21
VFault = VPh-N
,
3 Phase Fault
© OMICRON Slide 22
Loop Impedance (ZLoop) Z1 I0
Z1 I0
ZS
Phase-Ground Z1 I0
ZL V0
ZE = kLZL 3I0
ZN
V0/3I0 = (Z1/3)ZN
> We can calculate the ground return impedance Z0 = Z1 3ZN
by using the sequence component method ZN = (Z0Z1)/3
(the result is grounding factor). And then, we ZN = (1/3) [(Z0/Z1) 1]Z1
can use this factor to eliminate the ground Z1 = ZL
ZN = ZE
return impedance and comparing with the
kL = (1/3) [(Z0/Z1) 1]
reference to make decision.
> Grounding factor (EF compensation factor)
© OMICRON Slide 23
Obtain the Parameters for Distance Protection
© OMICRON Slide 24
Eliminate Ground Return Impedance
IFault ZLoop = ZFault = [ VFault / IFault ] = (1 kL)ZL
ZL
> Type A
1
VFault = VPh-E ZE = kLZL , 1
, 1 1
© OMICRON Slide 25
Calculation with Type A
IPh ZL
VPh-E ZE RF
X
RF/(1kL) .. (calculate)
RF (system)
ZL
© OMICRON Slide 26
Calculation with Type A
IPh
kL = 130 ZE = kL×ZL = 5115
ZL 585 Case #1 Without ARC Resitance (RF)
VPh-E ZRelay = (ZL + ZE) / (1 + kL)
RF 30 = (9.66100 ) / (1.9315) = 585
RF =3
Case #2 With ARC Resitance (RF)
Z’Relay = (ZL + RF + ZE) / (1 + kL)
= (9.6082.08 ) / (1.9315) = 4.9767.08
RF =3
VFault = VPh-E = IFault × Z’Relay = 9.604182.084 kV
R
© OMICRON Slide 27
Calculation with Type A Case #1 IPh
ZL 585
9.6593100 kV 10 kA VPh-E
ZE 5115
9.66100 X
ZL, Relay =585
kL =130
1+kL = 1.9315
585
585 0
© OMICRON Slide 28
Calculation with Type A Case #2 IPh
ZL 585
9.6082.08 kV 10 kA VPh-E
RF 30
ZE 5115
9.6082.08 X
ZL, Relay =4.9785
kL =130
1+kL = 1.9315
4.9767.08
585 1.55-15.05
© OMICRON Slide 29
Calculation with Type B
IPh ZL
VPh-E ZE RF
X
RF/(1Kr) .. (calculate)
XL RF (system)
ZL
R
RL
© OMICRON Slide 30
IPh
Calculation with Type B Case #1
ZL 585
ZE 5115
4.9804 0.4358
585 0
© OMICRON Slide 31
IPh
Calculation with Type B Case #2
ZL 585
585 0.7795
RL, Relay
© OMICRON Slide 32
Calculation with Type C
IPh ZL
VPh-E ZE RF
(RL RE RF – RE) = RL RF
( XL XE )/(1 Kx) = XL (Kx = XE/XL)
X
RF
XL RF (system)
ZL
R
RL
© OMICRON Slide 33
IPh
Calculation with Type C Case #1
ZL 585
VPh-E
9.6593100 kV 10 kA
ZE 5115
4.9804 0.4358
585 0 R
RL, Relay
© OMICRON Slide 34
IPh
Calculation with Type C Case #2
ZL 585
VPh-E
RF 30
9.6082.08 kV 10 kA
ZE 5115
9.6082.08 X
XL, Relay ZL, Relay =6.0555.4
4.9804 3.4359
585 3
RL, Relay
© OMICRON Slide 35
Summary on Grounding Factors
Format Contents Example
5115
Magnitude / Angle 130
585
Magnitude / Angle 130
0
Magnitude / Angle 3.89822.631
1
1 0 0 1 0
> Conversion 1 3 1
3 1 3 1 1
tan
tan
tan
© OMICRON Slide 36
Define grounding factor in TU
Elimination Method
Type A
Type B
Type C
© OMICRON Slide 37
Example: Loop impedance, Fault current & voltage
X Phase-Phase Fault
575 ZLoop = 2×ZTest = 2×575 = 1075
Test Model Constant Test Current
ITest = IFault = 1-45A
VTest= VFault = ITest×ZLoop=1-45A×1075= 1030V
VTest = VL1-E – VL2-E = 1030 V, ITest = IL1 = 1-45 A
R
30°
75°
© OMICRON Slide 38
IFault = 1-45A under Phase to Phase fault
30°
75°
© OMICRON Slide 39
Example: Loop impedance, Fault current & voltage
Phase-Ground Fault
1
> Type A , 1
> Type B , 1 1
> Type C , 1
VL3-E
X
575
VFault=VL1-E
30
R
VL2-E
IFault=IL1
© OMICRON Slide 40
Test Point 1, Type A
6.34350 V
X
575 1-81.79 A
Constant Test Current
6.343581.79
1+kL=1.26876.79
R
575
© OMICRON Slide 41
Test Point 1, Type B
1-81.79 A
Constant Test Current
j6.279 0.9059
6.343581.79
j4.83 1.2941
575
© OMICRON Slide 42
Test Point 1, Type C
j6.279 0.9059
6.343581.79
j4.83 1.2941
575
© OMICRON Slide 43
Test Point 2, Type A (ARC Only)
3.80610 V
X
1-6.79 A
Constant Test Current
3.8061∠6.79
30
1+kL=1.26876.79
R
30
© OMICRON Slide 44
Test Point 2, Type B (ARC Only)
10 A
Constant Test Current
j0 2.1
2.10
j0 3
30
© OMICRON Slide 45
Test Point 2, Type C (ARC Only)
> RE= 0
10A
Constant Test Current
j0 3
30
j0 3
30
© OMICRON Slide 46
Summary on Phase-Ground Fault
ARC only
© OMICRON Slide 47
Polarization
> The Phase Angle is well known operating principle for distance relays. It use the
phaser information which contained in the input signal to build up the impedance
characteristic and making the decision whether fault occurs inside the protected zone
or not.
> The concept is the angle of two quantity will be compared (S1 and S2), if it smaller
than 90 degree that means the location of fault is inside the protected zone.
ZL (measurement)
ZR S2=ZR+ZL
R
S1=ZR-ZL
X ZR (reference) ZL
ZR
S2=ZR+ZL
ZL (measurement) S1=ZR-ZL
R
© OMICRON Slide 50
Circle Characteristic
X ZR (reference) ZL
ZL (measurement) ZR S2=ZR+ZL
S1=ZR-ZL
R
X ZL
ZR (reference)
ZR S2=ZR+ZL
ZL (measurement) S1=ZR-ZL
R
© OMICRON Slide 51
Phase Angle Comparator (Circle Characteristic)
> ZR is the relay setting, IFault and VFault are the measured values
> When the relay get the quantity of fault voltage and fault current, the
operating quantity S1 and polarizing quantity S2 are build up.
> The relay decides whether fault occur inside the protected zone or not.
© OMICRON Slide 52
Mho Characteristic
X ZR (reference)
ZR
S1= ZR-ZL
X ZR (reference)
ZR
ZR-ZL
ZL (measurement)
Angle between ZR-ZL and ZL > 90 deg
R
© OMICRON Slide 53
Mho Characteristic ZL
ZR (reference)
X
ZR-ZL ZR
X ZR (reference) ZL
ZR
ZR-ZL
ZL
© OMICRON Slide 54
Phase Angle Comparator (Mho Characteristic)
> ZR is the relay setting, IFault and VFault are the measured values
© OMICRON Slide 55
Phase Angle Comparator (Mho with Offset)
X
ZR1 (FWD) ZR1
ZR1-ZL
ZR2 ZL
R ZL-ZR2
ZL
ZL (measurement)
ZR2 ZL-ZR2
R
ZR1
ZL
ZL
ZR2
R ZL-ZR2
> Where ZR1 is the relay setting for forward direction, ZR2 for reverse direction
> IFault and VFault are the measured results at the relay location
© OMICRON Slide 58
Voltage Memory & Cross-Polarised
> Using Memory Voltage Relay include another circuit which used to
remember the prefault voltage. When bolted fault occur the circuit will hold
the prefault voltage for some period which long enough for the relay to
make decision as to whether the fault is in forward or reverse direction .
> Using Cross-Polarized The other phase which not is the faulty phase will
be added to polarizing quantity.
© OMICRON Slide 59
Memory Voltage & Dynamic effect during fault
X
ZR tX (statedy state characteristic)
R
tX
t3
t2
t1 Dynamic
t0 (initial characteristic)
ZS
© OMICRON Slide 60
Cross Polarised Voltage
VCA
VC
VA
VBC VC VAB
VB
VAB
© OMICRON Slide 61
Cross Polarised Voltage
> 1 ; 2
> k = Percentage of Cross Polarizing Voltage
> VP = Cross Polarizing Voltage
IX IX
VFault
IZR IZR
VFault kVP
IR IR
© OMICRON Slide 62
Cross Polarised Voltage
IX X
Self-Polarized
ZR
IZR
VFault kVP
VFault
IR R
IZS
[k/(1k)]ZS
ZS
If k<1 Partially Crossed Polarized
© OMICRON Slide 63
Updates about IEC 60255 standard
© OMICRON Slide 65
How to Compare the Different Characteristics?
© OMICRON Slide 66
Overvoltage during fault?
Test Point
© OMICRON Slide 67
Limitations
© OMICRON Slide 68
IEC 60255-121:2014
> Additionally:
> “static accuracy tests” to ensure basic functionality
© OMICRON Slide 69
IEC 60255-121:2014
> 121 describes the “functional standard for the distance protection”
© OMICRON Slide 70
Key Concepts in IEC 60255-121
© OMICRON Slide 71
Key Concepts in IEC 60255-121
IMPORTANT:
> The test results are documented and compared, but not assessed!
© OMICRON Slide 72
Accuracy Tests under Steady State Conditions
© OMICRON Slide 73
Overview of Dynamic Performance Tests
Section Result
12 SIR diagrams short line
6.3.2 Operate time and transient overreach (TO)
12 SIR diagrams long line
short & long line
Total 3584 shots
6.3.3 Operate time and transient overreach
12 SIR diagrams
short line with CVT
6.3.4 Transient overreach tests (Search Test) TO for L1N, L23 & SIR: 10, 50
© OMICRON Slide 74
Dynamic Performance Verification (Section 6.3.2)
Relay
© OMICRON Slide 75
Number of Fault Injections
© OMICRON Slide 76
Examples from IEC 60255-121
© OMICRON Slide 77
Dynamic Performance Transient Oscillation Tests
© OMICRON Slide 78
Double Infeed and Parallel Line
© OMICRON Slide 79
IEC 60255-121 Measuring relays and protection equipment
Part 121: Functional requirements for distance protection
Country Vote
Austria Yes
Brazil Yes
Canada Yes
China Yes
Czech Republic Yes
Finland Yes
France Yes
Germany Yes
Hungary Yes
India Yes
Ireland Yes
Italy Yes
Japan Yes
Korea, Republic of Yes
Qatar Yes
Russian Federation Yes
Serbia Yes
Sweden Yes
Switzerland Yes
United States of America Yes
© OMICRON Slide 80
Old vs. New: compare typical trip time
© OMICRON Slide 81
Line/ground Impedance Test
CPC 100 + CP CU1 Functional Tests
with Service Settings
Distance Relay Type Tests Test Universe
according to IEC 60255‐121:2014
RelaySimTest Lab Package
System Simulation Tests
On site verification
for the Protected Line
Test Universe
RelaySimTest
Maintenance
Test Universe
© OMICRON Slide 82
Summary on Testing
Slide: 86
© OMICRON Slide 86
Draw the Impedance Zone Characteristic
Radius
© OMICRON Slide 87
Draw the Impedance Zone Characteristic
> Mho
© OMICRON Slide 88
Draw the Impedance Zone Characteristic
© OMICRON Slide 89
Draw the Impedance Zone Characteristic
> Type: Starting
Starting Zone
Starting Contact
Tripping Zone
Trip Contact
Extended Zone
Trip Contact
© OMICRON Slide 90
We test (almost) all relays
© OMICRON Slide 91
OCC PTL OMICRON-XRIO Converter
© OMICRON Slide 92
Advanced Distance Module
© OMICRON Slide 94
Time Measurement
© OMICRON Slide 95
Check Test
> The aim of the Check test is to check reaches and trip times of the
individual zones above and below the reach.
> To do so, two shots per zone are placed
© OMICRON Slide 96
Search Test
> The aim of the Search test is to determine the exact reach of the individual
zones by applying several shots along a search line. The number of shots is
calculated automatically using the search resolution.
© OMICRON Slide 97
Testing with Nominal Characteristic
> When performing a search test of known nominal characteristics, the initial
shots to search for the zone reaches are placed on the tolerance limits of
the zone reaches.
resolution = 1% or 50mΩ
Zone2
tol- tol+
resolution
© OMICRON Slide 98
Testing with Nominal Characteristic
Impedance View
Z/t Diagram
© OMICRON Slide 99
Testing with Nominal Characteristic
5
2
3
6
7
1 4
Impedance View
Z/t Diagram
Search Sequence
1 2 3
© OMICRON Slide 2
Time grading for relay A
© OMICRON Slide 3
Settings of the System Under Test Menu in
RelaySimTest
Z1`PL = Impedance of the Protected Line from the relay to the fault location
Z1``PL = Impedance of the Protected Line from the fault location to busbar B
VF = Voltage drop over the fault resistance
21A 21B
> The instantaneous zone (Zone1) should cover 100% of protected line.
> Zone1 cannot be set to cover 100% of protected line.
E.g. Fault occur on Line2 Sub.B at 5.0
> VFault,Prim = 20 kV; IFault,Prim = 3.9 kA; CT – 1000/1; PT – 110kV/110V
> Z = VSec/ISec = 20 V/ 3.9 A = 5.12 > 5.0 (Beyond Sub.B)
Relay at Sub.A sees the fault on Line 2
Solutions: Solution B
> A. Test and Calibrate the CT and PT CPC100 + CP CU1
> B. Line impedance test
> C. Test the relay performance
> D. Set the reach of zone1 to protect only 80% -
90% of protected line
Solution C
CMC356+Test Universe
Zone1 of 21B
21B
Line1 Line2
21A
Zone1 of 21A
> Solution D: Set the reach of zone1 to 80% -90% of protected line
> Further Challange: There is no protection zone at the end of the protected
line on bothe sides, about 10-20% of the line.
> Further Solution: Adding the delay zone (zone2) which cover the protected
line (about 120% of protected line), But the tripping time of this zone will be
delayed about 250-400 ms to coordinate with other protection.
Zone2 + Delay
21B
Zone1 of 21B
Line1 Line2
Zone1 of 21A
21A
Zone2 + Delay
Basic Scheme
© OMICRON Slide 122
Zone Extension Scheme
Sub. A Sub. B
Zone2 + delay
Extension Zone1
Protected Line (Line1) Line2
Zone1 Extension
Zone2 + delay
21A 21B
Enable Z1X Enable Z1X
Z1X Z1X
Trip Trip
Zone1 Zone1
> Remark: In practical this scheme will be used with the radial distribution
feeder which there is no communication available. Usually, the scheme will
be operated with the Auto-Recloser to activate the Extension Zone (Z1X)
> To improve the situation of delay time when fault occurs at the end of protected
line the scheme below are introduced
Without Communication
> Zone Extension Scheme
> Loss of Load Logic
> Switch On To Fault Logic (SOTF)
Modules suggested:
> QuickCMC: Freely control tool
> State Sequencer: Complex sequence and logic verification
> NetSim: Network simulation tool
> RelaySimTest: Advanced module for network simulation
Zone1
Zone2 + delay
21A 21B
Communication
21A 21B
> Logic Diagram Communication
Zone1 Zone1
TZ2 Trip Trip TZ2
Zone2 Zone2
Zone1 Zone1
Trip Trip
Zone2 TZ2 TZ2 Zone2
Tx Tx
TD Rx Rx TD
Zone1
Zone1 Zone1
Trip Trip
Zone2 TZ2 TZ2 Zone2
Tx Tx
TD Rx Rx TD
Comm. Equipment Comm. Equipment
© OMICRON Slide 129
Cross Fault on Parallel Line
> Parallel lines tripped CB at one end but the CB at other end is still closed
> Relay C and D at the healthy line detect the short current reversal situation
> Relay C and D shall be blocked from operation
A B
Fault Trips Trips
C. D.
Relay B
Fault Relay C
A. B.
Current Reversal
CB Open
Relay D
21A2 21B2
Line2
Sub. A Sub. B
Protected Line
21A1 21B1
Communication
21A1 21B1
> Zone2 is detected and waiting > Reverse zone is detected
for the delay time to trip circuit > Receive carrier signal from 21A1
breaker.
> Carrier signal is sent to 21B1 > 21B1 Blocked
21A2 21B2
Line2
Sub. A Sub. B
Protected Line
21A1 21B1
Communication
21A1
21B1
> Reverse zone is detected
> Zone2 is detected
> Receive carrier signal from 21B1
> Carrier signal is sent to 21A1
> 21A1 Blocked
© OMICRON Slide 133
Current Reversal (Fault on Parallel Line)
Zone1 Zone1
Trip Trip
Zone2 TZ2 TZ2 Zone2
Block Block
Tx Tx
TD Rx Rx TD
Comm. Equipment Comm. Equipment
0 1 0 0
Zone1 Zone1
1 0
0 Trip Trip 0
1 0
Zone2 TZ2 TZ2 Zone2
1 0
0 1 1 0 0 1
1 0
Block 1 0 0 Block
1 0 0
0 1 0 1
Tx Tx
TD 0 Rx 1 Rx 1 TD
Comm. Equipment Comm. Equipment
1
Reverse. Zone Dropoff Time (for holding the signal block)
1
1 1
0 Block Trip & Block Carrier Send
Zone2 1
© OMICRON Slide 2
Time grading
© OMICRON Slide 3
Settings of the System Under Test Menu in
RelaySimTest
3. If the healthy phases have no current, the loss of load accelerated trip logic
understands the remote side has tripped the CB (without communication). It will
enable Relay 21A to trip the circuit breakers without waiting for Zone2 to time out.
Zone2
Trip
Zone1
Zone2 TZ2
Zone2 TZ2
> Limitations:
> 1. This logic can be used only with three pole circuit breaker model.
> 2. It becomes inoperative with three phase fault.
21A 21B
Start energizing
> This SOTF logic will be used to discriminate between the normal fault
condition and fault which occurs during the energization process.
Time Window
Dead to Live Line Logic
SOTF
Close Command Zone2
Trip
Zone1
Zone2 TZ2
© OMICRON Slide 152
Fuse Failure (Voltage Transformer Supervision or VTS)
> Due to protection of IVT/CVT from the short circuit in the secondary side,
we need to add the protection equipment such as fuse or MCB. This causes
unwanted trips of distance protection in case fuse broken or MCB tripped,
because the voltage become zero. So that, the distance function will be
blocked to avoid maloperation.
> Using Zero or Negative sequence, or Supervision circuits.
Ia = Ib = Ic I0 = 0, I2 = 0
Va Vb ,Vc V0 0 , V2 0
w Close Command
Dead to live
without trouble
Zone1
Sub. A Zone2 + delay
21A 21B
Zone1 Zone1
Trip Trip
Zone2 TZ2 TZ2 Zone2
Tx Tx
Rx Rx
TD TD
Zone1
Trip
TZ2 Zone2
Signal From
Remote End Under Voltage U<
Tx
Rx
TD
Zone1 Zone1
Trip Trip
Zone2 TZ2 TZ2 Zone2
Tx Tx
Rx Rx
E1 E2
ZS1 ZL ZS2
I
System A System B
Magnitude Difference
E1 E2
ZS1 ZL ZS2
I
System A System B
Phase Difference
66.40 V
21 ZL
E2
Angle Diff = 30 Angle Diff = 50 Angle Diff = 100
Power = 229.6 watt Power = 368.0 watt Power = 549.8 watt
VRelay = 66.6375.978 V VRelay = 64.2129.732 V VRelay = 55.17916.25 V
IRelay = 3.4580.997 A IRelay = 5.64610.997 A IRelay = 10.23435.99 A
ZRelay = 19.0994.98 ZRelay = 11.3731.265 ZRelay = 5.39219.74
IRelay
D
> When a generator has fallen out of step, the locus is continously run
through in one direction (the frequency of two system are difference – slip
frequency). This ia called asynchronous power swing.
> If such power swing happens, actions are needed.
Current
System Fault:
> The power swing is not
the fault in the protected
line, so that the distance
protection should be
prevented to allow the
Voltage
other protection to trip
selectively.
Current
© OMICRON Slide 164
The Locus of Impedance under Power Swing
E1 E2
ZS1 ZL ZS2
21
E1 < E2
© OMICRON Slide 165
Power Swing and Mho X
ZS2 ZS2
ZL ZL
R R
ZS1 ZS1
> The detecting function measures the positive sequence impedance of the
network.
> A real fault on the line changes the impedance very quickly. The locus runs
from load point to the protected zone in a few milliseconds
> In the case of power swings, impedance variations do not occur
instantaneously.
> Rate of Change of Impedance (dZ/dt) is the way to sense the power swing.
> Detecting Methods:
> Using two impedance zone (inner and outter zone). The relay can identify
the nature of the power swing according to the transition time from the outer
zone to the inner zone. If toutter–inner > tsetting,
> Continuous monitor the rate of change of impedance, by sampling.
> A lot of other methods
Fault Cond.
T
> Once a power swing is detected, how a distance relay should perform?
> Block the the protected zone in case of synchronous power swing
> Send trip command when Asynchronous power swing is detected
> Release blocking function when fault occurs during power swing.
Fault Cond.
7.722
T=200 ms
Detection
Unstable
Detection
Unstable
Q&A