Sei sulla pagina 1di 226

Module PIN codes

• DESCRIPTION
Module pin codes are used to control access to the DSE Module itself. Upon leaving the factory, the
module DOES NOT have a PIN code set – The module is fully accessible.

• CONFIGURATION
To set the PIN code, use the module’s PC software.

Details on setting the PIN code within the controller are detailed in the respective PC Software manuals as detailed below:
MODULE RANGE PC SOFTWARE FOR PIN CODE EXAMPLE IMAGE
DSE8700 Series DSE Configuration Suite (SCADA, MAINTENANCE)
DSE8600 Series
DSE7300 Series
DSE7200 Series
DSE6100 Series

DSE7500 Series Link7000Plus (SETUP, COMMS CONFIG, MODULE


SECURITY)

DSE5500 Series Link5000Plus (SETUP, COMMS CONFIG, MODULE


SECURITY)
DSE5300 Series 5xxx for Windows (SETUP, MODULE PIN)
DSE5200 Series 5xxx for Windows (SETUP, MODULE PIN)
Other DSE modules PIN Code Not Available

IF A PIN CODE IS SET YOU CANNOT : IF A PIN CODE IS SET YOU CAN STILL :
Gain access to the front panel editor (FPE) Use the PC software to READ FROM CONTROLLER
Use the PC software to WRITE TO CONTROLLER View SCADA INSTRUMENTATION and STATUS pages
Perform SCADA ‘CONTROL’ operations Control the module operating modes and view the module
instruments on the module fascia
Perform Modbus WRITE operations Perform Modbus READ operations

• IMPORTANT INFORMATION

o Once a PIN code has been set, it can be removed by changing it to “0000”or
changed to another PIN code as desired. You must enter the existing PIN code
first.
o There is no “back door” PIN code and there is no way to remove the PIN code
without knowing the current PIN code. If you lose or forget your PIN code, the
module must be returned to DSE to be reset. There will be a charge for this
service.

056-030 Module PIN codes Issue 2 – A.D.Manton


THIS PAGE IS INTENTIONALLY BLANK

056-030 Module PIN codes Issue 2 – A.D.Manton


DEEP SEA ELECTRONICS PLC
Electronic Engines and DSE Controllers

Document Number 057-004


Author: Ashley Senior

Electronic Engines and DSE Controllers Manual ISSUE 6.3


Electronic Engines and DSE Controllers

DEEP SEA ELECTRONICS PLC


Highfield House
Hunmanby
North Yorkshire
YO14 0PH
ENGLAND

Sales Tel: +44 (0) 1723 890099


Sales Fax: +44 (0) 1723 893303

E-mail : sales@deepseaplc.com
Website : www.deepseaplc.com

Electronic Engines and DSE Controllers


(Previously named CAN AND DSE CONTROLLERS)

© Deep Sea Electronics Plc


All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by
electronic means or other) without the written permission of the copyright holder except in accordance with the provisions of the Copyright,
Designs and Patents Act 1988.
Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to Deep Sea
Electronics Plc at the address above.

The DSE logo is a UK registered trademarks of Deep Sea Electronics PLC.

Any reference to trademarked product names used within this publication is owned by their respective companies.

Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice.

Amendments List
Issue Comments
1 Added DSE7000 Series
2 Updated most engines with more detail
3 Added 3110 controller
4 Added 7500 series
5 Added more ADEC information (Issue 5.1)
6 Changed manual layout and added new information.
6.1 Added ADEM3 wiring amendments.
6.2 Added ECU8 wiring
6.3 Added photo for DDEC, MDEC, EDC4, EEMR3, EMR2, EMR3, S6, CM570 & CM2250

Typeface: The typeface used in this document is Arial. Care should be taken not to mistake the upper case letter I with the numeral 1. The
numeral 1 has a top serif to avoid this confusion.

Highlights an essential element of a procedure to ensure correctness.


NOTE:

Indicates a procedure or practice which, if not strictly observed, could result in damage or destruction of
CAUTION!: equipment.

Indicates a procedure or practice which could result in injury to personnel or loss of life if not followed
WARNING!: correctly.

 Deep Sea Electronics Plc owns the copyright to this manual, which cannot be copied, reproduced or disclosed
to a third party without prior written permission.

SAE Society of Automotive Engineers (USA)

2
Electronic Engines and DSE Controllers

TABLE OF CONTENTS

1 BIBLIOGRAPHY .............................................................................................. 7
1.1 TRAINING GUIDES...................................................................................................................... 7
1.2 MANUALS ................................................................................................................................... 7

2 INTRODUCTION .............................................................................................. 8
2.1 CAN ............................................................................................................................................. 8
2.2 SAE J1939................................................................................................................................... 8
2.3 RS485 .......................................................................................................................................... 8
2.4 TWISTED PAIR CABLING ........................................................................................................... 8
2.5 IMPEDANCE MATCHING ............................................................................................................ 8

3 ELECTRONIC ENGINES AND THE DSE MODULE ........................................ 9


3.1 INSTRUMENTATION ................................................................................................................... 9
3.2 USE OF ENGINE MANUFACTURERS SOFTWARE TOOLS ........................................................ 9
3.3 TURNING ON THE ECU MANUALLY........................................................................................... 9
3.4 ECU TROUBLE CODES AND DIAGNOSTICS............................................................................ 10
3.4.1 SPN/FMI CODES .................................................................................................................................................. 10
3.4.2 CAN ECU WARNING (CAN ECU ERROR) ........................................................................................................ 11
3.4.3 CAN ECU SHUTDOWN (CAN ECU FAIL).......................................................................................................... 11
3.4.4 CAN ECU DATA FAIL ......................................................................................................................................... 11

4 CONNECTIONS ............................................................................................. 12
4.1 OUTPUTS .................................................................................................................................. 12
4.2 CAN / RS485.............................................................................................................................. 12
4.3 DSE CONTROLLER AND CAN FILE COMPATIBILITY .............................................................. 13
4.4 TYPICAL CONNECTIONS ......................................................................................................... 14
4.5 ECU POWER AND ECU STOP OUTPUTS ................................................................................. 14
4.5.1 CAN ECU POWER ............................................................................................................................................... 14
4.5.2 CAN ECU STOP ................................................................................................................................................... 14
4.6 REMOTE SPEED CONTROL ..................................................................................................... 14
4.6.1 DSE53XX SERIES................................................................................................................................................ 14
4.6.2 DSE55XX SERIES................................................................................................................................................ 14
4.6.3 DSE7XXX AND DSE8XXX SERIES .................................................................................................................... 14

5 CATERPILLAR .............................................................................................. 15
6 CUMMINS....................................................................................................... 16
6.1 CM570 ....................................................................................................................................... 17
6.1.1 ECU FUNCTIONALITY ........................................................................................................................................ 17
6.1.2 ECU WIRING ........................................................................................................................................................ 17
6.1.2.1 CAN CONFIGURATION.................................................................................................................................................... 18
6.1.2.2 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 18
6.1.2.3 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 18
6.2 CM850 ....................................................................................................................................... 19
6.2.1 ECU FUNCTIONALITY ........................................................................................................................................ 19
6.2.2 ECU WIRING ........................................................................................................................................................ 19
6.2.2.1 CAN CONFIGURATION.................................................................................................................................................... 20
6.2.2.2 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 20
6.2.2.3 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 20
6.3 CM2250 ..................................................................................................................................... 21
6.3.1 ECU FUNCTIONALITY ........................................................................................................................................ 21
6.3.2 ECU WIRING ........................................................................................................................................................ 21
6.3.3 CAN CONFIGURATION....................................................................................................................................... 22
6.3.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 22
6.3.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 22
6.4 GCS ........................................................................................................................................... 23
6.4.1 ECU FUNCTIONALITY ........................................................................................................................................ 23
6.4.2 ECU WIRING ........................................................................................................................................................ 23
6.4.3 CAN CONFIGURATION....................................................................................................................................... 24
6.4.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 24
6.4.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 24
6.5 ISB ............................................................................................................................................ 25
6.5.1 ECU FUNCTIONALITY ........................................................................................................................................ 25
6.5.2 ECU WIRING ........................................................................................................................................................ 25
6.5.3 CAN CONFIGURATION....................................................................................................................................... 26
6.5.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 26
6.5.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 26

7 DETROIT ........................................................................................................ 27
7.1 DDEC III/IV................................................................................................................................. 28
7.1.1 ECU FUNCTIONALITY ........................................................................................................................................ 28
3
Electronic Engines and DSE Controllers

7.1.2 ECU WIRING ........................................................................................................................................................ 28


7.1.3 CAN CONFIGURATION....................................................................................................................................... 29
7.1.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 29
7.1.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 29

8 DEUTZ............................................................................................................ 30
8.1 EMR2......................................................................................................................................... 31
8.1.1 ECU FUNCTIONALITY ........................................................................................................................................ 31
8.1.2 ECU WIRING ........................................................................................................................................................ 31
8.1.3 CAN CONFIGURATION....................................................................................................................................... 32
8.1.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 32
8.1.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 32
8.2 EMR 3........................................................................................................................................ 33
8.2.1 ECU FUNCTIONALITY ........................................................................................................................................ 33
8.2.2 ECU WIRING ........................................................................................................................................................ 33
8.2.3 CAN CONFIGURATION....................................................................................................................................... 34
8.2.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 34
8.2.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 34

9 FIAT POWERTRAIN ...................................................................................... 35


10 FORD .......................................................................................................... 36
10.1 GCP ........................................................................................................................................... 37
10.1.1 ECU FUNCTIONALITY.................................................................................................................................... 37
10.1.2 ECU WIRING.................................................................................................................................................... 37
10.1.3 CAN CONFIGURATION .................................................................................................................................. 38
10.1.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 38
10.1.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 38

11 GM ............................................................................................................... 39
11.1 PSI ............................................................................................................................................. 40
11.1.1 ECU FUNCTIONALITY.................................................................................................................................... 40
11.1.2 ECU WIRING.................................................................................................................................................... 40
11.1.3 CAN CONFIGURATION .................................................................................................................................. 41
11.1.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 41
11.1.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 41

12 ISUZU .......................................................................................................... 42
12.1 4H .............................................................................................................................................. 43
12.1.1 ECU FUNCTIONALITY.................................................................................................................................... 43
12.1.2 ECU WIRING.................................................................................................................................................... 43
12.1.3 CAN CONFIGURATION .................................................................................................................................. 44
12.1.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 44
12.1.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 44

13 IVECO ......................................................................................................... 45
13.1 EDC62 ....................................................................................................................................... 46
13.1.1 ECU FUNCTIONALITY.................................................................................................................................... 46
13.1.2 ECU WIRING.................................................................................................................................................... 46
13.1.3 CAN CONFIGURATION .................................................................................................................................. 47
13.1.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 47
13.1.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 47
13.2 EDC7C1 ..................................................................................................................................... 48
13.2.1 ECU FUNCTIONALITY.................................................................................................................................... 48
13.2.2 ECU WIRING.................................................................................................................................................... 48
13.2.3 CAN CONFIGURATION .................................................................................................................................. 49
13.2.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 49
13.2.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 49
13.3 EDC7UC31 ................................................................................................................................ 50
13.3.1 ECU FUNCTIONALITY.................................................................................................................................... 50
13.3.2 ECU WIRING.................................................................................................................................................... 50
13.3.3 CAN CONFIGURATION .................................................................................................................................. 51
13.3.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 51
13.3.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 51
13.4 T3 .............................................................................................................................................. 52
13.4.1 ECU FUNCTIONALITY.................................................................................................................................... 52
13.4.2 ECU WIRING.................................................................................................................................................... 52
13.4.3 CAN CONFIGURATION .................................................................................................................................. 53
13.4.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 53
13.4.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 53

14 JOHN DEERE ............................................................................................. 54


14.1 JDEC ......................................................................................................................................... 55
14.1.1 ECU FUNCTIONALITY.................................................................................................................................... 55
14.1.2 ECU WIRING.................................................................................................................................................... 55
14.1.3 CAN CONFIGURATION .................................................................................................................................. 56
14.1.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 56
14.1.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 56

4
Electronic Engines and DSE Controllers

15 MTU ............................................................................................................. 57
15.1 ADEC......................................................................................................................................... 58
15.1.1 ECU FUNCTIONALITY.................................................................................................................................... 58
15.1.2 ECU WIRING.................................................................................................................................................... 58
15.1.3 CAN CONFIGURATION .................................................................................................................................. 59
15.1.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 59
15.1.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 59
15.2 MDEC ........................................................................................................................................ 60
15.2.1 ECU FUNCTIONALITY.................................................................................................................................... 60
15.2.2 ECU WIRING.................................................................................................................................................... 60
15.2.3 CAN CONFIGURATION .................................................................................................................................. 61
15.2.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 61
15.2.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 61
15.3 ECU8 ......................................................................................................................................... 62
15.3.1 ECU FUNCTIONALITY.................................................................................................................................... 62
15.3.2 ECU WIRING.................................................................................................................................................... 62
15.3.3 CAN CONFIGURATION .................................................................................................................................. 63
15.3.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 63
15.3.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 63

16 PERKINS ..................................................................................................... 64
16.1 1300........................................................................................................................................... 65
16.1.1 ECU FUNCTIONALITY.................................................................................................................................... 65
16.1.2 ECU WIRING.................................................................................................................................................... 65
16.1.3 CAN CONFIGURATION .................................................................................................................................. 66
16.1.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 66
16.1.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 66
16.2 ADEM3 ...................................................................................................................................... 67
16.2.1 ECU FUNCTIONALITY.................................................................................................................................... 67
16.2.2 ECU WIRING.................................................................................................................................................... 67
16.2.3 CAN CONFIGURATION .................................................................................................................................. 68
16.2.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 68
16.2.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 68
16.3 ADEM4 ...................................................................................................................................... 69
16.3.1 ECU FUNCTIONALITY.................................................................................................................................... 69
16.3.2 ECU WIRING.................................................................................................................................................... 69
16.3.3 CAN CONFIGURATION .................................................................................................................................. 70
16.3.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 70
16.3.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 70

17 SCANIA ....................................................................................................... 71
17.1 S6 .............................................................................................................................................. 72
17.1.1 ECU FUNCTIONALITY.................................................................................................................................... 72
17.1.2 ECU WIRING.................................................................................................................................................... 72
17.1.3 CAN CONFIGURATION .................................................................................................................................. 73
17.1.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 73
17.1.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 73

18 SISU ............................................................................................................ 74
18.1 EEM3 ......................................................................................................................................... 75
18.1.1 ECU FUNCTIONALITY.................................................................................................................................... 75
18.1.2 ECU WIRING.................................................................................................................................................... 75
18.1.3 CAN CONFIGURATION .................................................................................................................................. 76
18.1.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 76
18.1.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 76

19 VOLVO ........................................................................................................ 77
19.1 EDC3 ......................................................................................................................................... 78
19.1.1 ECU FUNCTIONALITY.................................................................................................................................... 78
19.1.2 ECU WIRING.................................................................................................................................................... 78
19.1.3 CAN CONFIGURATION .................................................................................................................................. 79
19.1.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 79
19.1.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 79
19.2 EDC4 ......................................................................................................................................... 80
19.2.1 ECU FUNCTIONALITY.................................................................................................................................... 80
19.2.2 ECU WIRING.................................................................................................................................................... 80
19.2.3 CAN CONFIGURATION .................................................................................................................................. 81
19.2.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 81
19.2.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 81
19.3 EMS2/B ..................................................................................................................................... 82
19.3.1 ECU FUNCTIONALITY.................................................................................................................................... 82
19.3.2 ECU WIRING.................................................................................................................................................... 82
19.3.3 CAN CONFIGURATION .................................................................................................................................. 83
19.3.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 83
19.3.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 83

20 YANMAR ..................................................................................................... 84
20.1 ECO ........................................................................................................................................... 85
20.1.1 ECU FUNCTIONALITY.................................................................................................................................... 85
5
Electronic Engines and DSE Controllers

20.1.2 ECU WIRING.................................................................................................................................................... 85


20.1.3 CAN CONFIGURATION .................................................................................................................................. 86
20.1.3.1 DSE CONFIGURATION SUITE SOFTWARE .................................................................................................................. 86
20.1.3.2 DSE5XXX/75XX PC SOFTWARE .................................................................................................................................... 86

6
Bibliography

1 BIBLIOGRAPHY
This document refers to and is referred to by the following DSE publications which can be obtained from the DSE website
www.deepseaplc.com

1.1 TRAINING GUIDES


Training Guides are produced to give ‘handout’ sheets on specific subjects during training sessions.

DSE PART DESCRIPTION


056-023 Adding New CAN Files

1.2 MANUALS
DSE PART DESCRIPTION
057-086 31xx Series Operators Manual
057-087 31xx Series Configuration Suite Software Manual
057-111 44xx Mk2 Series Operators Manual
057-093 44xx Series Configuration Suite Software Manual
057-013 5310 Operators Manual
057-014 5320 Operators Manual
057-006 52/xx53xx Series Configuration Suite Software Manual
057-015 5510 Operators Manual
057-016 5520 Operators Manual
057-007 55xx Series Configuration Suite Software Manual
057-112 60xx Series Operators Manual
057-114 60xx Series Configuration Suite Software Manual
057-095 61xx Series Operators Manual
057-096 61xx Series Configuration Suite Software Manual
057-113 71xx Series Operators Manual
057-117 71xx Series Configuration Suite Software Manual
057-074 72/73xx Series Operators Manual
057-077 72/73xx Series Configuration Suite Software Manual
057-088 7510 Operators Manual
057-089 7520 Operators Manual
057-078 75xx Series Configuration Suite Software Manual
057-115 8610 Operators Manual
057-119 86xx Series Configuration Suite Software Manual
057-124 8710 Operators Manual
057-127 87xx Series Configuration Suite Software Manual

7
Introduction

2 INTRODUCTION
2.1 CAN
Controller Area Network (CAN) is a serial bus standard, originally developed in the 1980s by Robert Bosch GmbH, for connecting electronic
control units (ECUs). CAN was specifically designed to be robust in noisy environments. It can be even more robust against noise if twisted
pair wire is used. Although initially created for automotive purposes, nowadays it is used in many embedded control applications (e.g.,
generator sets) that may be subject to noise.

2.2 SAE J1939


SAE J1939 is the Vehicle Network Communication standard using CAN for communication and diagnostics by the heavy duty truck industry.
As generator engines are usually based upon truck engines, this standard has also been adopted by the majority of (but not all) Generator
Engine Manufacturers.
For instance MTU engines use CAN but have not adopted J1939. However DSE controllers are also compatible with and officially certified for
use with MTU engines.

2.3 RS485
RS485 is a serial bus standard for connecting multiple devices to the same bus.
This connection standard is used by Cummins on some engine ranges rather than the CAN standard adopted by other genset manufacturers.
However DSE 5300 Series controllers are also compatible with the Cummins RS485 enabled engines.

2.4 TWISTED PAIR CABLING


Twisted pair (TP) cabling is a common form of wiring in which
two conductors are wound around each other for the purposes of
canceling out electromagnetic interference (known as crosstalk).
The number of twists in the cable per meter make up part of the
specification for a given type of cable. The greater the number of
twists, the more crosstalk is reduced.

Twisting wires decreases interference because:


The loop area between the wires (which determines the magnetic
coupling into the signal) is reduced as much as physically
possible.
The directions of current generated by a uniform coupled
magnetic field is reversed for every twist, canceling each other
out.

The characteristic impedance of a twisted pair cable is around 100Ω making it suitable for both CAN or RS485 use. Screened,
Shielded Twisted Pair is particularly suitable as the screening and shield offer even more protection.

If incorrect cable type is used it will lead to data transmission errors in the future, potentially after commissioning and the engineer has
left site!

Ω impedance cable suitable for CAN or RS485 use (DSE part number
NOTE:-DSE stock and supply Belden cable 9841 which is a high quality 120Ω
016-030)

2.5 IMPEDANCE MATCHING


When sending power down a transmission line, it is desirable that all the power is absorbed by the load and none of it is reflected back to the
source. This can be ensured by making the source and load impedances equal in which case the line is said to be matched.
CAN and RS485 specifies 120Ω cable be used with 120Ω termination resistors at each end to match impedances. The termination resistor is
fitted internally into the DSE CAN interface controller so is not required externally. Ensure that the DSE controller is the ‘last’ device on the
communications link where more than one device is connected to the engine ECU’s CAN connector.

If the cable impedance and/or termination resistors are not correctly fitted, this can cause some of the received signal to be ‘reflected’ back to
the transmitting module. This reflection will ‘collide’ with further data transmissions, causing data transmission errors.

Ω termination resistor internally so must be fitted externally.


NOTE:-The DSE RS485 interface does not include the 120Ω
The RS485 interface is NOT used for CAN engines.

8
Electronic Engines and DSE Controllers

3 ELECTRONIC ENGINES AND THE DSE MODULE


3.1 INSTRUMENTATION
As the Engine ECU is connected to measurement sensors
on the engine, this instrumentation is available to be read
into the DSE controller.
All DSE electronic engine enabled controllers will read
engine oil pressure, engine coolant temperature and
engine speed from the engine ECU.
In addition to this, DSE44xx, DSE5xxx, DSE6xxx, DSE7xxx
and DSE8xxx controllers will display “enhanced engine
ECU instrumentation” when it is supported by the engine
ECU.
This information can also be viewed using the Engine
instrumentation pages of the configuration software.

When the ECU is not powered it is not possible to read the


diagnostic trouble codes or instrumentation. See the
section entitled Turning on the ECU manually.

NOTE:- 3110 controllers do not support SCADA monitoring by PC software.

NOTE:- When connected to an active ECU supporting the instrument, the instrument’s value are shown on the DSE module’s screen and also on
the PC remote instrumentation page.
When the ECU is not powered, engine ECU instrumentation will indicate # # #
When instrument has an errors (for instance sensor errors), x x x is displayed.
Unsupported instruments have blank values (no indication).

NOTE:- Some engine ECUs do not support all of the ‘enhanced engine ECU instrumentation’. The unsupported displays will appear blank on the
module display.

3.2 USE OF ENGINE MANUFACTURERS SOFTWARE TOOLS


Occasionally it is necessary to connect the engine manufacturers software tools to the engine ECU in order to make changes to the engine
configuration.
The ECU may need to be powered up to perform this operation and as the ECU is normally only powered when the engine is running, it must
be turned on manually as described in the following section.

NOTE:- If the manufacturers software tool connects to the same CAN interface as the DSE module, ensure the DSE module is the ‘last’ device on
the CAN interface.
If the tool does not operate when connected to the same CAN interface as the DSE module, you are referred to your engine manufacturer.

3.3 TURNING ON THE ECU MANUALLY


When the ECU is not powered it is not possible to read the diagnostic trouble codes or instrumentation. Additionally, it is not possible to use
the engine manufacturers configuration tools. As the ECU is unpowered when the engine is not running, it must be turned on manually as
follows :

• Select STOP mode on the DSE controller.

• Press and hold the START button to power the ECU. As the controller is in STOP mode, the engine will not be started.
• Continue to hold the start button for as long as you need the ECU to be powered.
• The ECU will remain powered until a few seconds after the START button is released.

This is also useful if the engine manufacturer’s tools need to be connected to the engine, for instance to configure the engine as the ECU
needs to be powered up to perform this operation.

NOTE:-DSE3110 does not include the ECU OVERRIDE function.

NOTE:-When the ECU is not powered, engine ECU instrumentation will indicate ### on the display of the DSE controller.

NOTE:-When it is required for the DSE controller to change ECU settings (ie when the Alternative Frequency setting is changed) the settings will
the sent to the ECU the next time the ECU is turned on. “Setting ECU” will appear on the DSE display while this adjustment takes place.

9
Electronic Engines and DSE Controllers

3.4 ECU TROUBLE CODES AND DIAGNOSTICS

NOTE:-DSE3110 controllers display only the common Check Engine indicator – Contact your engine supplier for details.

3.4.1 SPN/FMI CODES


If the engine ECU detects a fault with the engine, it will communicate this problem to the DSE controller in the form of a “trouble code”. There
are two levels to these trouble codes

1. SPN = Suspect Parameter Number. This indicates what is wrong (i.e. Engine temperature).
2. FMI = Failure Mode Indicator. This indicates the type of failure (i.e. High).

Example taken from Volvo Penta Engine Documentation :

SPN 100, FMI 1 = Means Oil Pressure Sensor - Value below Normal
SPN 100, FMI 3 = Means Oil Pressure Sensor - Short Circuit
SPN 100, FMI 5 = Means Oil Pressure Sensor - Open Circuit

The DSE controller will display these codes in text format :

Alarm 1/1
Low Oil Pressure

Shutdown

Where an ‘unknown’ code is sent by the ECU, the DSE controller will display the SPN/FMI code number allowing the user to cross reference
this information with the fault codes supplied by the engine manufacturer.

The DSE fault text display replaces the flashing “twinkle code” lamp available on some trouble code display systems giving a much more user
friendly interface to the engine ECU.

Each alarm can be one of two types, ECU ERROR or ECU FAIL. These are detailed in the following sections.

With DSE7000 Series controllers, these alarms are named CAN ECU WARNING and CAN ECU SHUTDOWN.

NOTE:-DSE3110 controllers display only the common Check Engine indicator – Contact your engine supplier for details.

10
Electronic Engines and DSE Controllers

3.4.2 CAN ECU WARNING (CAN ECU ERROR)

NOTE:-DSE3110 controllers display only the common Check Engine indicator – Contact your engine supplier for details.

This is a “warning” type alarm (Sometimes called the yellow lamp alarm by engine manufacturers) – the engine ECU does not shutdown the
engine, it continues to run. The DSE controller takes no action other than to generate a warning alarm and to indicate the alarm via the
fascia display.

Alarm 1/1 Alarm 1/1


CAN ECU Warning The display will alternate between the Water Level Low
text display and the manufacturers
error codes.
Warning xxx,xxx,xxx

3.4.3 CAN ECU SHUTDOWN (CAN ECU FAIL)

NOTE:-DSE3110 controllers display only the common Check Engine indicator – Contact your engine supplier for details.

This is a “shutdown” type alarm (Sometimes called the red lamp alarm by engine manufacturers) – the engine has been shutdown by the
ECU. The DSE controller performs the relevant shutdown procedure for the ECU as dictated by the CAN file selection, generates a
shutdown alarm and indicates the alarm via the fascia display.

Alarm 1/1 Alarm 1/1


CAN ECU Shutdown The display will alternate between the Fuel Pressure Low
text display and the manufacturers
error codes.
Shutdown xxx,xxx,xxx

NOTE: - If the CAN message is a manufacturers specific code, it may not be displayed as text. If this is the case, the display will show the generic
manufacturers code only, which must be cross-referenced with the engine manufacturer’s literature. Please contact the engine manufacturer for
further assistance.

The above displays show a standard J1939 based system. Other manufacturers systems supported by the module work in a similar way though the
exact detail may vary from those illustrated.

Example
Alarm 1/1
CAN ECU Shutdown

xxx,xxx,xxx
To reset latched warning faults on the engine ECU, press the DSE controller mute button.

To reset latched shutdown faults on the engine ECU, press the DSE controller stop/reset button.

3.4.4 CAN ECU DATA FAIL


As the engine ECU CAN link is used to provide engine protection, it is a matter of safety that the CAN link remains intact.
If the link is not operative during normal running, an engine shutdown will occur and ‘Can data fail’ is shown on the module’s display :

Alarm 1/1
CAN ECU Data Fail

Shutdown

As the CAN link is not operative, shutdown of the engine cannot be made using a CAN message (!).
In this case, the only method of shutdown is via the ECU STOP output.

NOTE:-The check for data on the ECU link takes place after the DSE controller’s safety delay timer.

NOTE:-DSE3110 controllers display only the common Check Engine indicator – Contact your engine supplier for details.

11
DSE Module Connection

4 CONNECTIONS
As the connections to DSE controllers are similar across the DSE range the engine ECU connections are
common for all controllers. The following table details the differences between the different ranges.

4.1 OUTPUTS
Fuel Start Auxiliary Output 1 Auxiliary Output 2
3110 Use output A (terminal 3) Use output B (terminal 4) 5 (C) 6 (D)
44xx 3 4 6 7
53xx 4 5 6 7
55xx 4 5 6 7
60xx 4 5 8 (C) 9 (D)
61xx 4 5 8 (C) 9 (D)
71xx 4 5 8 (E) 9 (F)
72xx 4 5 8 (E) 9 (F)
73xx 4 5 8 (E) 9 (F)
75xx 4 5 8 (E) 9 (F)
86xx 4 5 8 (E) 9 (F)
87xx 4 5 8 (E) 9 (F)

4.2 CAN / RS485


CAN SCR CAN H CAN L RS485 SCR RS485 B RS485 A
3110 N/A 10 11 N/A N/A N/A
44xx 14 12 13 N/A N/A N/A
53xx 20 21 22 23 24 25
55xx 23 24 25 29 30 31
60xx 18 16 17 N/A N/A N/A
61xx 18 16 17 N/A N/A N/A
71xx 27 25 26 N/A N/A N/A
72xx 27 25 26 SCR B A
73xx 27 25 26 SCR B A
75xx 27 25 26 SCR B A
86xx 27 25 26 SCR B A
87xx 27 25 26 SCR B A

NOTE:- The CAN and RS485 specifications, require that a 120Ω Ω terminator is fitted to each end of the communications link. This termination
resistor is fitted internally into the DSE CAN interface so is not required externally. Ensure that the DSE controller is the ‘last’ device on the
communications link where more than one device is connected to the engine ECU’s CAN connector.
However, the DSE RS485 interface does not include the 120Ω Ω termination resistor internally, this is supplied loose with the RS485 enabled controller.

NOTE:- DSE31xx Series fuel/start outputs are rated at 2A DC. DSE31xx auxiliary outputs are rated at 2A DC.

NOTE:- DSE44xx Series fuel/start outputs are rated at 2A DC. DSE44xx auxiliary outputs are rated at 2A DC.

NOTE:- DSE5xxx Series fuel/start outputs are rated at 15A DC. DSE5xxx auxiliary outputs are rated at 5A DC.

NOTE:- DSE6xxx Series fuel/start outputs are rated at 2A DC. DSE6xxx auxiliary outputs are rated at 2A DC.

NOTE:- DSE7xxx Series fuel/start outputs are rated at 15A DC. DSE7xxx auxiliary outputs are rated at 2A DC.

NOTE:- DSE8xxx Series fuel/start outputs are rated at 15A DC. DSE7xxx auxiliary outputs are rated at 2A DC.

12
DSE Module Connection

4.3 DSE CONTROLLER AND CAN FILE COMPATIBILITY

NOTE:-If a DSE module does not have the CAN file you require, please contact DSE Technical Support for more information.

CUMMINS CUMMINS CUMMINS CUMMINS CUMMINS CUMMINS CUMMINS DEUTZ DEUTZ ECONTROLS GENERIC GENERIC GM
CM570 CM850 CM2250 ISB QSK QST QSX EMR2 EMR3 GCP J1939 PLUS PSI
3110             
44xx             
53xx             
55xx             
60xx             
61xx             
71xx             
72xx             
73xx             
75xx             
86xx             
87xx             

JOHN JOHN
ISUZU IVECO IVECO IVECO IVECO DEERE DEERE MTU MTU MTU MTU MTU MTU MTU
4H EDC62 EDC7C1 EDC7UC31 T3 JDEC PUMP ADEC ECU8 MDEC201 MDEC302 MDEC303 MDEC304 MDEC506
3110              
44xx              
53xx              
55xx              
60xx              
61xx              
71xx              
72xx              
73xx              
75xx              
86xx              
87xx              

PERKINS PERKINS PERKINS PERKINS SCANIA SISU VOLVO VOLVO VOLVO VOLVO YANMAR
1100 1300 ADEM3 ADEM4 S6 EEM3 EDC3 EDC4 EMS2 EMS2B ECO
3110           
44xx           
53xx           
55xx           
60xx           
61xx           
71xx           
72xx           
73xx           
75xx           
86xx           
87xx           

13
DSE Module Connection

4.4 TYPICAL CONNECTIONS


Connections between the DSE controller and the engine system are similar for all engine types and includes connection to the Engine ECU
link and in some engine types, ancilliary control is also required.
Engine ECU link
DSE ECU
Controller

FUEL / CAN
ECU POWER

Engine

CRANK

NOTE:- RUN/POWER and CRANK are not required with all engine types. See specific connection lists elsewhere in this manual for further
details.

4.5 ECU POWER AND ECU STOP OUTPUTS


DSE controllers have configurable output sources specifically
designed to control the engine ECU. These are labelled CAN
ECU Power and ECU Stop in the DSE configuration software.

The exact timing/sequence of their operation varies slightly


depending upon the configuration of “Electronic Engine type” but
essentially their functions are as follows:

4.5.1 CAN ECU POWER


Normally used to turn on the ECU (sometimes via an external slave relay).
Some engine ECUs are permanently powered in which case the ECU Power output is used to give input to a Run (or similarly named) input
on the ECU.

4.5.2 CAN ECU STOP


Used to give input to a Stop (or similarly named) input on the ECU. This is used as a backup stop system should the ECU Data link fail. In this
instance, it’s not possible to stop the engine using a data command as the link is not operative. As a backup, the STOP signal is given to the
engine via a separate hardwired connection.

CAUTION!: Check the current rating of the ECU terminals that CAN ECU POWER and CAN ECU STOP signals are connected to and ensure the DSE
output rating is not exceeded.

4.6 REMOTE SPEED CONTROL


4.6.1 DSE53XX SERIES
As the DSE module’s analogue inputs for oil pressure and coolant temperature are not used when the module is configured for use with an
electronic engine, it is possible to use the coolant temperature input as engine speed control by connecting a potentiometer. Contact Deep
Sea Electronics Technical Support Department for further details and to confirm the list of engines that support this feature.

4.6.2 DSE55XX SERIES


Version 10 and later DSE5510/5520 controllers have a configurable speed parameter that can be adjusted when the engine is running. Refer
to the relevant operator and PC software configuration manual for further details on enabling and utilising this function.

4.6.3 DSE7XXX AND DSE8XXX SERIES


The DSE7XXX and DSE8XXX controllers have a configurable speed parameter that can be adjusted when the engine is running. Refer to the
relevant operator and PC software configuration manual for further details on enabling and utilising this function.

14
Caterpillar and DSE Controllers

5 CATERPILLAR
Engines in the Caterpillar range are split into subgroups depending upon the type of engine governing are employed. These different systems
are fully compatible with the DSE Controllers when configured correctly and can allow engine control and diagnostics via the J1939 link.

NOTE:-Caterpillar engines use the ADEM3 and ADEM4 ECUs which are also found on the Perkins range of engines. Please refer to the section
entitled ‘Perkins’ else where in this manual for more information.

15
Cummins and DSE Controllers

6 CUMMINS
Engines in the Cummins range are split into subgroups depending upon the type of engine governing are employed. These different systems
are fully compatible with the DSE Controllers when configured correctly and can allow engine control and diagnostics via the J1939 link.
We have collated the following data for the electronically governed engines.

16
Cummins and DSE Controllers

6.1 CM570

CM570 Mounted on the engine J1939 Data link connector

6.1.1 ECU FUNCTIONALITY


CM570 FUNCTIONALITY CM570 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0xDC
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, CCVS
Inlet Temperature  Proprietary msg GAP,GCP,EG
Exhaust Temperature  Notes
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  Legend
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

6.1.2 ECU WIRING


CUMMINS CM570 ‘6 PIN
DSE TERMINAL POWER CONNECTOR’
DESCRIPTION TERMINALS NOTES

NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
Fuel Relay
H
Output
CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
Connect directly to engine starter solenoid.
Start Relay
-
Output CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.

CUMMINS ‘DATA LINK


DSE TERMINAL CONNECTOR’
DESCRIPTION TERMINALS NOTES
CANbus
C Screen for the J1939 cable. Connect at Cummins ECU end only.
common
J1939 + Use only screened 120Ω impedance cable approved specifically for use in
CANbus H A
CANbus applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in
CANbus L B
CANbus applications.

17
Cummins and DSE Controllers

6.1.2.1 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

6.1.2.2 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for the


Cummins CM570 or Cummins ISB CAN file
depending which is available.

Using the Cummins CM570 CAN file will require a


SW1 setting of 5.0 and an SW2 setting of 4.0. This
setting is only applicable with DSE Load Share
Controllers and will need fine tuning during the DSE
Four Steps to Successful Synchronisation
Commissioning steps.

6.1.2.3 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


either the Cummins-CM570 or Cummins ISB
CAN file depending which is available.

Using the Cummins-CM570 CAN file will


require a SW1 setting of 5.0 and an SW2
setting of 2.0. This setting is only applicable
with DSE Load Share Controllers and will
need fine tuning during the DSE Four Steps
to Successful Synchronisation
Commissioning steps

18
Cummins and DSE Controllers

6.2 CM850

6.2.1 ECU FUNCTIONALITY


CM850 FUNCTIONALITY CM850 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0xDC
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, CCVS
Inlet Temperature  Proprietary msg GAP, GCP, EG
Exhaust Temperature  Notes
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  Legend
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

6.2.2 ECU WIRING


CUMMINS CM850 50 PIN
DSE TERMINAL CONNECTOR
DESCRIPTION TERMINALS NOTES

NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
Fuel Relay
39
Output
CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
Connect directly to engine starter solenoid.
Start Relay
-
Output CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.

CUMMINS CM850 9 PIN


DSE TERMINAL CONNECTOR
DESCRIPTION TERMINALS NOTES
CANbus
E Screen for the J1939 cable. Connect at Cummins ECU end only.
common
J1939 + Use only screened 120Ω impedance cable approved specifically for use in
CANbus H C
CANbus applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in
CANbus L D
CANbus applications.

19
Cummins and DSE Controllers

6.2.2.1 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

6.2.2.2 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for the


Cummins CM850 CAN file.

Using the Cummins CM850 CAN file will require a


SW1 setting of 5.0 and an SW2 setting of 4.0.
This setting is only applicable with DSE Load
Share Controllers and will need fine tuning during
the DSE Four Steps to Successful
Synchronisation Commissioning steps.

6.2.2.3 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the Cummins-CM850 CAN file.

Using the Cummins-CM850 CAN file will


require a SW1 setting of 5.0 and an SW2
setting of 2.0. This setting is only applicable
with DSE Load Share Controllers and will
need fine tuning during the DSE Four Steps
to Successful Synchronisation
Commissioning steps

20
Cummins and DSE Controllers

6.3 CM2250

6.3.1 ECU FUNCTIONALITY


CM2250 FUNCTIONALITY CM2250 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0xDC
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, CCVS
Inlet Temperature  Proprietary msg GAP, GCP, EG
Exhaust Temperature  Notes
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  Legend
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

6.3.2 ECU WIRING

NOTE:- DSE currently do not have any wiring information for this ECU. Please contact the engine supplier for more information.

21
Cummins and DSE Controllers

6.3.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

6.3.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Cummins CM2250 CAN file.

Using the Cummins CM2250 CAN file will


require a SW1 setting of 5.0 and an SW2
setting of 4.0. This setting is only applicable
with DSE Load Share Controllers and will
need fine tuning during the DSE Four Steps
to Successful Synchronisation
Commissioning steps.

6.3.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the Cummins-CM2250 CAN file.

Using the Cummins-CM570 CAN file will


require a SW1 setting of 5.0 and an SW2
setting of 2.0. This setting is only applicable
with DSE Load Share Controllers and will
need fine tuning during the DSE Four Steps
to Successful Synchronisation
Commissioning steps

22
Cummins and DSE Controllers

6.4 GCS

6.4.1 ECU FUNCTIONALITY


GCS FUNCTIONALITY GCS FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method N/A
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address N/A
Number of Starts DSE ECU Power &delay
Oil Temperature  (Not available on QSK) ECU Stop
Coolant Pressure  (Not available on QSX) J1939 msg N/A
Inlet Temperature  Proprietary msg N/A
Exhaust Temperature  Notes
Fuel Temperature  (Not available on QSX) DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  Legend
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

6.4.2 ECU WIRING


CUMMINS ‘D PIN
DSE TERMINAL CONNECTOR 6’
DESCRIPTION TERMINALS NOTES
External relay used to close terminal 5 to terminal 8.

Fuel Relay NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
5,8
Output
CAUTION!:- An external slave relay will be needed. Check the current consumption and
specify relay accordingly.
Connect directly to engine starter solenoid.
Start Relay
-
Output CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
RS485 - Use only screened 120Ω impedance cable approved specifically for use in
RS485 A 18
CANbus applications.
RS485 + Use only screened 120Ω impedance cable approved specifically for use in
RS485 B 21
CANbus applications.
19, 22 Link 19 and 22 together to enable Cummins ECU 120Ω termination resistor.

NOTE:- Newer variants of these engines may be fitted with the CM850 ECU (as fitted to the QSL11 engines). Contact Cummins for further
information.

NOTE:- The GCS uses a MOBUS RS485 protocol and consequently a DSE controller with MODBUS engine control must be used with these
controllers (DSE53XX (RS485 version), DSE55XX (RS485 version), DSE73XX, DSE75XX and DSE8XXX).

23
Cummins and DSE Controllers

6.4.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

6.4.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

NOTE:- The GCS uses a MOBUS RS485 protocol and consequently a DSE controller with MODBUS engine control must be used with either of
these controllers DSE73XX, DSE75XX and DSE8XXX.

Using the Cummins QSK engine select the


Cummins QSK CAN File. Selecting the
incorrect CAN file will result in
instrumentation not being display

Using the Cummins QST engine select the


Cummins QST CAN File. Selecting the
incorrect CAN file will result in
instrumentation not being display

Using the Cummins QSX engine select the


Cummins QSX CAN File. Selecting the
incorrect CAN file will result in
instrumentation not being display

The Cummins GCM ECU uses MODBUS


communication over RS485 rather then
J1939 over CAN. The user can select if they
wish to use the DSE module’s RS485 port
or the DSEnet port if either or is in use.

6.4.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

NOTE:- The GCS uses a MOBUS RS485 protocol and consequently a DSE controller with MODBUS engine control must be used with either of
these controllers DSE53XX (RS485 version) and DSE55XX (RS485 version).

Using the Cummins QSK engine select the


Cummins-QSK-Modbus CAN File.
Selecting the incorrect CAN file will result in
instrumentation not being display

Using the Cummins QST engine select the


Cummins-QST-Mobus CAN File. Selecting
the incorrect CAN file will result in
instrumentation not being display

Using the Cummins QSX engine select the


Cummins-QSX-Modbus CAN File.
Selecting the incorrect CAN file will result in
instrumentation not being display.

24
Cummins and DSE Controllers

6.5 ISB

6.5.1 ECU FUNCTIONALITY


ISB FUNCTIONALITY ISB FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0x2B
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST
Inlet Temperature  Proprietary msg None
Exhaust Temperature  Notes
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  Legend
   
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

6.5.2 ECU WIRING


CUMMINS ISB
DSE TERMINAL ‘CONNECTOR B’
DESCRIPTION TERMINALS NOTES
Key switch input
Fuel Relay
39
Output CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
Connect directly to engine starter solenoid.
Start Relay
-
Output CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
Using PC software configure ‘Auxiliary Output 1’ to be ‘ECU POWER’
External relay used to close terminal 1, 7, 12 and 13 to DC battery supply.
Auxiliary
1, 7, 12, 13
Output 1 CAUTION!:- An external slave relay will be needed. Check the current consumption and
specify relay accordingly.

DSE CUMMINS ISB ‘9 PIN


TERMINAL DEUTSCH CONNECTOR’
DESCRIPTION TERMINALS NOTES
CANbus
SAE J1939 shield Screen for the J1939 cable. Connect at one end only.
common
J1939 + Use only screened 120Ω impedance cable approved specifically for use in
CANbus H SAE J1939 signal
CANbus applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in
CANbus L SAE J1939 return
CANbus applications.

25
Cummins and DSE Controllers

6.5.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

6.5.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Cummins ISB CAN file.

6.5.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the Cummins ISB CAN file.

26
Detroit and DSE Controllers

7 DETROIT
Engines in the Detroit range are fitted with only one type of engine governing. This system is fully compatible with the DSE Controllers when
configured correctly and can allow engine control and diagnostics via the J1939 link.
We have collated the following data for the electronically governed engines.

27
Detroit and DSE Controllers

7.1 DDEC III/IV

7.1.1 ECU FUNCTIONALITY


DDEC III/IV FUNCTIONALITY DDEC III/IV FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage  Speed Control 
Engine Hours  Source address 0x2B
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, TSC1
Inlet Temperature  Proprietary msg None
Exhaust Temperature  Notes OEM DTC lookup table
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  LEGEND
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

7.1.2 ECU WIRING


DSE TERMINAL DETROIT
DESCRIPTION CONNECTOR NOTES

NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
Fuel Relay Output -
CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.
Connect directly to engine starter solenoid.

Start Relay Output - CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.
CANbus common - Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus H 12
applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus L 13
applications.

28
Detroit and DSE Controllers

7.1.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

7.1.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Generic J1939 CAN file.

7.1.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the Generic J1939 CAN file.

29
Deutz and DSE Controllers

8 DEUTZ
Engines in the Deutz range are split into subgroups depending upon the type of engine governing are employed. These different systems are
fully compatible with the DSE Controllers when configured correctly and can allow engine control and diagnostics via the J1939 link.
We have collated the following data for the electronically governed engines.

30
Deutz and DSE Controllers

8.1 EMR2

8.1.1 ECU FUNCTIONALITY


EMR2 FUNCTIONALITY EMR2 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 1
MODBUS Oil Pressure  DM1 Ignored 91
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0x2B, 0x11
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg TSC1
Inlet Temperature  Proprietary msg Volvo_STP
Exhaust Temperature  Notes Uses CM1, as EMR3
Fuel Temperature  DTC Ignore 91, 6771, 6279
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  Legend
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

8.1.2 ECU WIRING


DEUTZ ‘VEHICLE SIDE
DSE TERMINAL (F) CONNECTOR’
DESCRIPTION TERMINALS NOTES

NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
Fuel Relay
14
Output
CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
Connect directly to engine starter solenoid.
Start Relay
-
Output CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
1 Connects directly to battery negative
CANbus
- Screen for the J1939 cable. Connect at one end only.
common
J1939 + Use only screened 120Ω impedance cable approved specifically for use in
CANbus H 12
CANbus applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in
CANbus L 13
CANbus applications.

NOTE:-It may be necessary to enable the Deutz ECU for CAN control. Using the Deutz service tool software, change parameter 4400 on Page 6 to
‘1’.
Once this is done, depending upon the Deutz ECU configuration the engine speed may change. If this occurs, terminals 17 & 18 of the Deutz ECU
should be linked.

31
Deutz and DSE Controllers

8.1.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

8.1.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Deutz EMR2 or Volvo EDC4 CAN file
depending which is available.

8.1.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


either the Deutz-EMR2 or VolvoEDC4 CAN
file depending which is available.

32
Deutz and DSE Controllers

8.2 EMR 3

Deutz EMR3-E Deutz EMR3-S

8.2.1 ECU FUNCTIONALITY


EMR3 FUNCTIONALITY EMR3 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 1
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0x03
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, TSC1
Inlet Temperature  Proprietary msg Volvo_Stop
Exhaust Temperature  Notes
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  Legend
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

8.2.2 ECU WIRING


DEUTZ EMR3-E
‘DIAGNOSTIC
DSE TERMINAL CONNECTOR’
DESCRIPTION TERMINAL NOTES
Connect to terminal 15

Fuel Relay NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
Key switch
Output
CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.
Connect directly to engine starter solenoid.
Start Relay
-
Output CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.
CANbus common - Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus H M
applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus L F
applications.

33
Deutz and DSE Controllers

8.2.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

8.2.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Deutz EMR3 CAN file.

8.2.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the Deutz-EMR3 CAN file.

34
Fiat Powertrain and DSE Controllers

9 FIAT POWERTRAIN
Engines in the Fiat Powertrain range are split into subgroups depending upon the type of engine governing are employed. These different
systems are fully compatible with the DSE Controllers when configured correctly and can allow engine control and diagnostics via the J1939
link.

NOTE:-Fiat Powertrain was original named Iveco. Please refer to the section ‘Iveco’ elsewhere in this manual for more information.

35
Ford and DSE Controllers

10 FORD
Engines in the Ford range are fitted with only one type of engine governing. This system is fully compatible with the DSE Controllers when
configured correctly and can allow engine control and diagnostics via the J1939 link.
We have collated the following data for the electronically governed engines.

36
Ford and DSE Controllers

10.1 GCP
Space Reserved for Photo of ECU

10.1.1 ECU FUNCTIONALITY


GCP FUNCTIONALITY GCP FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0xEA
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, TSC1
Inlet Temperature  Proprietary msg None
Exhaust Temperature  Notes OEM DTC lookup table
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  LEGEND
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

10.1.2 ECU WIRING


FORD ’42 PIN
DSE TERMINAL CONNECTOR’
DESCRIPTION TERMINALS NOTES

NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
Fuel Relay Output 1
CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.
Connect directly to engine starter solenoid.

Start Relay Output 2 CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.
CANbus common - Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus H 28
applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus L 29
applications.

37
Ford and DSE Controllers

10.1.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

10.1.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Econtrols GCP CAN file.

10.1.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

NOTE:- The Econtrols ECP CAN file is not currently available for the DSE5xxx and DSE75xxx range of modules. Please contact the DSE Technical
Support Department for more information.

38
GM and DSE Controllers

11 GM
Engines in the GM range are fitted with only one type of engine governing. This system is fully compatible with the DSE Controllers when
configured correctly and can allow engine control and diagnostics via the J1939 link.
We have collated the following data for the electronically governed engines.

39
GM and DSE Controllers

11.1 PSI

11.1.1 ECU FUNCTIONALITY


PSI FUNCTIONALITY PSI FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0xEA
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, TSC1
Inlet Temperature  Proprietary msg None
Exhaust Temperature  Notes OEM DTC lookup table
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  LEGEND
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

11.1.2 ECU WIRING

NOTE:- DSE currently do not have any wiring information for this ECU. Please contact the engine supplier for more information.

40
GM and DSE Controllers

11.1.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

11.1.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the GM PSI CAN file.

Using the GM PSI CAN file will require a


SW1 setting of 5.0 and an SW2 setting of
4.0. This setting is only applicable with DSE
Load Share Controllers and will need fine
tuning during the DSE Four Steps to
Successful Synchronisation Commissioning
steps.

11.1.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

NOTE:- The GM PSI CAN file is not currently available for the DSE5xxx and DSE75xxx range of modules. Please contact the DSE Technical Support
Department for more information.

41
Isuzu and DSE Controllers

12 ISUZU
Engines in the Isuzu range are fitted with only one type of engine governing. This system is fully compatible with the DSE Controllers when
configured correctly and can allow engine control and diagnostics via the J1939 link.
We have collated the following data for the electronically governed engines.

42
Isuzu and DSE Controllers

12.1 4H
Space Reserved for Photo of ECU

12.1.1 ECU FUNCTIONALITY


4H FUNCTIONALITY 4H FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 1
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours DSE Source address 0x11, 0xE4
Number of Starts DSE ECU Power &delay
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, RQST CI, SHUTDN, TSC1
Inlet Temperature  Proprietary msg None
Exhaust Temperature  Notes
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  LEGEND
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

12.1.2 ECU WIRING


ISUZU ‘V
DSE TERMINAL CONNECTOR’
DESCRIPTION TERMINAL NOTES

NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
Fuel Relay Output 24
CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.

Start Relay Output 26 CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.
CANbus common - Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus H 18
applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus L 37
applications.

43
Isuzu and DSE Controllers

12.1.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

12.1.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Isuzu 4H CAN file.

Using the Isuzu 4H CAN file will require a


SW1 setting of 5.0 and an SW2 setting of
4.0. This setting is only applicable with DSE
Load Share Controllers and will need fine
tuning during the DSE Four Steps to
Successful Synchronisation Commissioning
steps.

12.1.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the Isuzu-ECM CAN file.

Using the Isuzu-ECM CAN file will require a


SW1 setting of 5.0 and an SW2 setting of
2.0. This setting is only applicable with DSE
Load Share Controllers and will need fine
tuning during the DSE Four Steps to
Successful Synchronisation Commissioning
steps

44
Iveco and DSE Controllers

13 IVECO
Engines in the Iveco range are split into subgroups depending upon the type of engine governing are employed. These different systems are
fully compatible with the DSE Controllers when configured correctly and can allow engine control and diagnostics via the J1939 link.
We have collated the following data for the electronically governed engines.

45
Iveco and DSE Controllers

13.1 EDC62

Iveco EDC62 mounted on the engine EDC62 interface board

13.1.1 ECU FUNCTIONALITY


EDC62 FUNCTIONALITY EDC62 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure DSE Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours DSE Source address 0x03
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, TSC1
Inlet Temperature  Proprietary msg Iveco_EDC2BC
Exhaust Temperature  Notes No oil pressure via CAN
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  LEGEND
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

13.1.2 ECU WIRING


EDC62
INTERFACE ‘J3
DSE TERMINAL CONNECTOR’
DESCRIPTION TERMINALS NOTES

NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
Fuel Relay Output 9
CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.

Start Relay Output 6 CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.

EDC62
INTERFACE ‘J7
DSE TERMINAL CONNECTOR’
DESCRIPTION TERMINALS NOTES
CANbus common - Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus H 5
applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus L 2
applications.

46
Iveco and DSE Controllers

13.1.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

13.1.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Iveco EDC62 CAN file.

13.1.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the Iveco-EDC62 CAN file.

47
Iveco and DSE Controllers

13.2 EDC7C1

13.2.1 ECU FUNCTIONALITY


EDC7C1 FUNCTIONALITY EDC7C1 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0x03
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, TSC1
Inlet Temperature  Proprietary msg Iveco_EDC2BC
Exhaust Temperature  Notes
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  LEGEND
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

13.2.2 ECU WIRING


EDC7UC31
INTERFACE ‘J3
DSE TERMINAL CONNECTOR’
DESCRIPTION TERMINALS NOTES

NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
Fuel Relay Output 9
CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.

Start Relay Output 6 CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.

EDC7UC31
INTERFACE ‘J7
DSE TERMINAL CONNECTOR’
DESCRIPTION TERMINALS NOTES
CANbus common - Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus H 5
applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus L 2
applications.

48
Iveco and DSE Controllers

13.2.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

13.2.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Iveco EDC7C1 CAN file.

13.2.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the Iveco-EDC7C1 CAN file.

49
Iveco and DSE Controllers

13.3 EDC7UC31

13.3.1 ECU FUNCTIONALITY


EDC7UC31 FUNCTIONALITY EDC7UC31 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0x27
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, TSC1
Inlet Temperature  Proprietary msg Iveco_EDC2BC
Exhaust Temperature  Notes
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  LEGEND
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

13.3.2 ECU WIRING


EDC7UC31
INTERFACE ‘J3
DSE TERMINAL CONNECTOR’
DESCRIPTION TERMINALS NOTES

NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
Fuel Relay Output 9
CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.

Start Relay Output 6 CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.

EDC7UC31
INTERFACE ‘J7
DSE TERMINAL CONNECTOR’
DESCRIPTION TERMINALS NOTES
CANbus common - Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus H 5
applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus L 2
applications.

50
Iveco and DSE Controllers

13.3.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

13.3.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Iveco EDC7UC31 CAN file.

13.3.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

NOTE:- The Iveco EDC7UC31 CAN file is not currently available for the DSE5xxx and DSE75xxx range of modules. Please contact the DSE Technical
Support Department for more information.

51
Iveco and DSE Controllers

13.4 T3
Space Reserved for Photo of ECU

13.4.1 ECU FUNCTIONALITY


T3 FUNCTIONALITY T3 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours DSE Source address 0x03
Number of Starts DSE ECU Power delay
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, TSC1
Inlet Temperature  Proprietary msg Iveco_ENG_CNTRL
Proprietary messages for oil pressure and coolant
Exhaust Temperature  Notes temperature
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  LEGEND
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

13.4.2 ECU WIRING


DSE TERMINAL IVECO T3
DESCRIPTION CONNECTIONS NOTES

NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
Ignition Switch
Fuel Relay Output
Terminal
CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.
Connect directly to engine starter solenoid.

Start Relay Output - CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.
CANbus common - Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus H 31
applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus L 32
applications.

NOTE: Some Iveco engines have been reported to not show the 'Hours Run' Instrumentation when used with the Generic can config.

NOTE: The start input on some ECUs will not start the engine, direct wiring to the starter motor needs to be made.

52
Iveco and DSE Controllers

13.4.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

13.4.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Iveco T3 CAN file.

13.4.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the Iveco-Tier3 CAN file.

53
John Deere and DSE Controllers

14 JOHN DEERE
Engines in the John Deere range are fitted with only one type of engine governing. This system is fully compatible with the DSE Controllers
when configured correctly and can allow engine control and diagnostics via the J1939 link.
We have collated the following data for the electronically governed engines.

54
John Deere and DSE Controllers

14.1 JDEC

14.1.1 ECU FUNCTIONALITY


JDEC FUNCTIONALITY JDEC FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours DSE Source address 0x03
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, TSC3
Inlet Temperature  Proprietary msg None
Exhaust Temperature  Notes
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  LEGEND
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

14.1.2 ECU WIRING


JOHN DEERE 21-PIN
DSE TERMINAL DEUTSCH CONNECTOR
DESCRIPTION TERMINAL NOTES
Terminal J on the John Deere connection is the ignition

Fuel Relay Output J CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
Terminal D on the John Deere connection is the start input

Start Relay Output D CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
Using PC software select the relevant engine and configure ‘Auxiliary Output 1’ to be
‘ECU POWER’.
Auxiliary
G
Output 1 CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
CANbus common - Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in
CANbus H 1 (Hi)
CANbus applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in
CANbus L 2 (Lo)
CANbus applications.

NOTE:- The JDEC ECU must be configured to enable Torque Speed Control on TSC source 1 to source address 3 and the Governor set to ‘Single
Governor’ Isochronous governing selected.

55
John Deere and DSE Controllers

14.1.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

14.1.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the John Deere CAN file.

The DSE controller must be configured for


the John Deere Pump CAN file to disable
speed control.

Using the John Deere CAN file will require


a SW1 setting of 5.0 and an SW2 setting of
4.0. This setting is only applicable with DSE
Load Share Controllers and will need fine
tuning during the DSE Four Steps to
Successful Synchronisation Commissioning
steps.

14.1.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the John Deere CAN file.

Using the John Deere CAN file will require


a SW1 setting of 5.0 and an SW2 setting of
2.0. This setting is only applicable with DSE
Load Share Controllers and will need fine
tuning during the DSE Four Steps to
Successful Synchronisation Commissioning
steps

56
MTU and DSE Controllers

15 MTU
Engines in the MTU range are split into subgroups depending upon the type of engine governing are employed. These different systems are
fully compatible with the DSE Controllers when configured correctly and can allow engine control and diagnostics via the J1939 link.
We have collated the following data for the electronically governed engines.

57
MTU and DSE Controllers

15.1 ADEC

ADEC ECU Mounted on the engine SAM module mounted in the customer panel

15.1.1 ECU FUNCTIONALITY


ADEC FUNCTIONALITY ADEC FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0x1
Number of Starts DSE ECU Power &delay
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg OHECS, RQST, EBC1, CCVS, TSC1
Inlet Temperature  Proprietary msg mtu_LS, mtu_SDS, mtu_CONT
Exhaust Temperature  Notes ECU permanently powered.
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  LEGEND
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

15.1.2 ECU WIRING


DSE TERMINAL MTU ADEC MTU SAM
DESCRIPTION TERMINAL TERMINAL NOTES
Start input of ADEC (DI 7).
Fuel Relay Output X1 37 - Connect X1 22 to GND
This terminal is optional. Start command is also sent by CAN message.
Stop input of ADEC (DI 1).
Start Relay Output X1 43 -
Connect X1 28 to GND
CANbus common - X23 3 Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in
CANbus H 1 (Hi) X23 2
CANbus applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in
CANbus L 2 (Lo) X23 1
CANbus applications.

NOTE:- The ADEC ECU is designed to be permanently powered via the emergency stop button on the control panel.

NOTE:- Cranking of the engine is managed by the ADEC controller following instruction from the DSE controller.

NOTE:-The ADEC ECU has to be used with in conjunction with the MTU SAM display module.

58
MTU and DSE Controllers

15.1.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

15.1.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the MTU ADEC CAN file.

15.1.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the mtu-ADEC CAN file.

59
MTU and DSE Controllers

15.2 MDEC

15.2.1 ECU FUNCTIONALITY


MDEC FUNCTIONALITY MDEC FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method N/A
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start  (Not available when using MTU MDEC 303)
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch
Battery Voltage DSE Idle Mode
Charge Alternator Voltage  Speed Control 
Engine Hours  Source address N/A
Number of Starts DSE ECU Power &delay
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg N/A
Inlet Temperature  Proprietary msg N/A
Exhaust Temperature  Notes ECU permanently powered.
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  LEGEND
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

15.2.2 ECU WIRING


MTU MDEC X1
DSE TERMINAL CONNECTER
DESCRIPTION TERMINAL NOTES
Fuel Relay Output BE9 Start input of MDEC
Start Relay Output BE1 Run input of MDEC
CANbus common E Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus H G
applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus L F
applications.

NOTE:-The MDEC ECU is designed to be permanently powered however the DSE controller can be configured to switch the ECU power by
configuring an Auxiliary output to be “ECU power”. This output should be used to control the ECU power relay and will turn off the MDEC ECU when

the DSE controller is placed into STOP/RESET mode. Note that using this method, the MDEC ECU takes approximately 30 seconds to power up

once the DSE controller is taken out of STOP/RESET mode.

NOTE:-Cranking of the engine is managed by the MDEC controller following instruction from the DSE controller.

NOTE:-The MTU engine can be used with or without the MTU PIM display module. Ensure that MTU are informed prior to the despatch of your
engine whether or not you intend to fit the PIM module and also that you require CAN for connection to the DSE controller. This will ensure that you
receive the engine with the relevant options enabled. Incorrectly set options for PIM and secondary CAN controller may lead to “CAN 1 NODE LOST
180” errors displayed by the DSE module (and MTU PIM module)

NOTE:-DSE55xx, DSE75xx and DSE8xxx can perform synchronising and loadsharing using CAN instructions to the engine ECU when using the
MTU-MDEC-304 configuration file in conjunction with compatible MDEC controllers. If in doubt about the MDEC version you have, you are referred to
MTU.

NOTE:-MDEC Speed control is configurable. Ensure it is set to receive speed control signals via the CAN interface.

60
MTU and DSE Controllers

15.2.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

15.2.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

Using the MTU MDEC303 CAN file with a version 304


MDEC a warning error code “SD CAN SPEED DEMAND
250” will be displayed on the DSE controller (and MTU
PIM module). Speed control is not available using the
MTU MDEC303 CAN file. If in doubt about the MDEC
version you have, you are referred to MTU.

When using the MTU MDEC304 CAN file, speed control


is available. If in doubt about the MDEC version you have,
you are referred to MTU.

When using the MTU MDEC504 CAN file, speed control


is available. If in doubt about the MDEC version you have,
you are referred to MTU.

Using the MTU MDEC304 CAN file and above will require
a SW1 setting of 5.0 and an SW2 setting of 4.0. This
setting is only applicable with DSE Load Share
Controllers and will need fine tuning during the DSE Four
Steps to Successful Synchronisation Commissioning
steps.

15.2.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

Using the mtu-MDEC-303 CAN file with a version 304


MDEC, a warning error code “SD CAN SPEED
DEMAND 250” will be displayed on the DSE controller
(and MTU PIM module). Speed control is not available
using the mtu-MDEC-303 CAN file

When using the mtu-MDEC-304 CAN file, speed control


is available.

NOTE:- The mtu-MDEC-506 CAN file is not currently available for the DSE5xxx and DSE75xxx range of modules. Please contact the DSE Technical
Support Department for more information.

Using the MTU MDEC304 CAN file and above


will require a SW1 setting of 5.0 and an SW2
setting of 4.0. This setting is only applicable with
DSE Load Share Controllers and will need fine
tuning during the DSE Four Steps to Successful
Synchronisation Commissioning steps.

Ensure crank disconnect on Charge Alternator


Voltage is disabled (not checked).

61
MTU and DSE Controllers

15.3 ECU8

ECU8 Mounted on the engine Smart Connect module mounted in the customer panel

15.3.1 ECU FUNCTIONALITY


ECU8 FUNCTIONALITY ECU8 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method N/A
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0x01
Number of Starts DSE ECU Power &delay
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg OHECS, RQST, EBC1, CCVS, TSC1
Inlet Temperature  Proprietary msg mtu_LS, mtu_SDS, mtu_CONT
Exhaust Temperature  Notes
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  LEGEND
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

15.3.2 ECU WIRING


ECU8
DSE TERMINAL ‘X1 CONNECTOR’
DESCRIPTION TERMINAL NOTES
External relay used to close terminal 31 to terminal 32.

Fuel Relay NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
31, 32
Output
CAUTION!:- An external slave relay will be needed. Check the current consumption and
specify relay accordingly.

SMART CONNECT
DSE TERMINAL ‘X4 CONNECTOR’
DESCRIPTION TERMINAL NOTES
CANbus common 3 Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in
CANbus H 1
CANbus applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in
CANbus L 2
CANbus applications.

62
MTU and DSE Controllers

15.3.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

15.3.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for the


MTU ECU8 CAN file.

Using the MTU ECU8 CAN file will require a SW1


setting of 5.0 and an SW2 setting of 4.0. This
setting is only applicable with DSE Load Share
Controllers and will need fine tuning during the
DSE Four Steps to Successful Synchronisation
Commissioning steps.

15.3.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

NOTE:- The MTU ECU8 CAN file is not currently available for the DSE5xxx and DSE75xxx range of modules. Please contact the DSE Technical
Support Department for more information.

63
Perkins and DSE Controllers

16 PERKINS
Engines in the Perkins range are split into subgroups depending upon the type of engine governing are employed. These different systems
are fully compatible with the DSE Controllers when configured correctly and can allow engine control and diagnostics via the J1939 link.
We have collated the following data for the electronically governed engines.

64
Perkins and DSE Controllers

16.1 1300

16.1.1 ECU FUNCTIONALITY


1300 FUNCTIONALITY 1300 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine Speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours DSE Source address 0x11
Number of Starts DSE ECU Power &delay
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg None
Inlet Temperature  Proprietary msg Perkins_A
Exhaust Temperature  Notes
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  Legend
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

16.1.2 ECU WIRING

NOTE:- DSE currently do not have any wiring information for this ECU. Please contact the engine supplier for more information.

65
Perkins and DSE Controllers

16.1.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

16.1.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Perkins 1300 CAN file.

16.1.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

NOTE:- The Perkins 1300 CAN file is not currently available for the DSE5xxx and DSE75xxx range of modules. Please contact the DSE Technical
Support Department for more information.

66
Perkins and DSE Controllers

16.2 ADEM3

16.2.1 ECU FUNCTIONALITY


ADEM3 FUNCTIONALITY ADEM3 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine Speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0x11
Number of Starts DSE ECU Power &delay
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, TC1, ETC3
Inlet Temperature  Proprietary msg None
Exhaust Temperature  Notes
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  Legend
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

16.2.2 ECU WIRING


DSE TERMINAL PERKINS ‘J1 CONNECTOR’
DESCRIPTION TERMINAL NOTES

NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
Fuel Relay
70
Output
CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
Connect directly to engine starter solenoid.
Start Relay
-
Output CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
CANbus common 42 Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in
CANbus H 50
CANbus applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in
CANbus L 34
CANbus applications.

NOTE:- According to Perkins, warning lamps or equivalent must be connected to Perkins customer interface connector terminals 28, 29, 30 & 31.
Failure to connect to these terminals will result in “open circuit” alarms from the ECU. Perkins have advised that a suitable equivalent for the warning
Ω 5W resistor. Be aware that outputs on terminals 10,19 & 20 are battery positive outputs. The outputs on terminals 28, 29, 30 & 31 are
lamp is a 220Ω
battery negative outputs.

67
Perkins and DSE Controllers

16.2.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

16.2.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Perkins ADEM3 CAN file.

16.2.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the Perkins CAN file.

68
Perkins and DSE Controllers

16.3 ADEM4

16.3.1 ECU FUNCTIONALITY


ADEM4 FUNCTIONALITY ADEM4 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine Speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0x11
Number of Starts DSE ECU Power &delay2
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, TC1, ETC3
Inlet Temperature  Proprietary msg None
Exhaust Temperature  Notes ECU permanently powered
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  Legend
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

16.3.2 ECU WIRING


PERKINS
‘COMMUNICATION
INTERFACE CONNECTOR
DSE TERMINAL (DEUTSCH HD16-9-96S)’
DESCRIPTION TERMINAL NOTES

NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
Fuel Relay Output Unknown
CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.

Start Relay Output Unknown CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
CANbus common C Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in
CANbus H G
CANbus applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in
CANbus L F
CANbus applications.

69
Perkins and DSE Controllers

16.3.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

16.3.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Perkins ADEM4 CAN file.

Using the Perkins ADEM4 CAN file will


require a SW1 setting of 5.0 and an SW2
setting of 4.0. This setting is only applicable
with DSE Load Share Controllers and will
need fine tuning during the DSE Four Steps
to Successful Synchronisation
Commissioning steps.

16.3.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the Perkins_ADEM_4 CAN file.

Using the Perkins_ADEM_4 CAN file will


require a SW1 setting of 5.0 and an SW2
setting of 2.0. This setting is only applicable
with DSE Load Share Controllers and will
need fine tuning during the DSE Four Steps
to Successful Synchronisation
Commissioning steps

70
Scania and DSE Controllers

17 SCANIA
Engines in the Scania range are fitted with the S6 type of engine governing. The Scania diagnostics system is known as Keyword 2000™ and
is fully compatible with the DSE Controllers when configured correctly. It can allow engine control and diagnostics via the J1939 link.
We have collated the following data for the electronically governed engines below.

71
Scania and DSE Controllers

17.1 S6

17.1.1 ECU FUNCTIONALITY


S6 FUNCTIONALITY S6 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0x27, 0xFB
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg CCVS, KW2000
Inlet Temperature  Proprietary msg Scania_TSC, Scania_DLN1
Exhaust Temperature  Notes
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  Legend
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

17.1.2 ECU WIRING


DSE TERMINAL SCANIA ‘EMS B1
DESCRIPTION CONNECTOR’ TERMINAL NOTES
Ignition U15

Fuel Relay NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
3
Output
CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
Connect directly to engine starter solenoid.

NOTE:- Not required on ‘later’ Scania S6 engines as cranking is performed by the S6 ECU.
Start Relay
- Contact Scania for more information.
Output
CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
CANbus common - Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in
CANbus H 9
CANbus applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in
CANbus L 10
CANbus applications.

NOTE:- DSE55xx, DSE75xx and DSE8xxx can perform synchronising and load sharing using CAN instructions to the engine ECU.

72
Scania and DSE Controllers

17.1.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

17.1.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for the


Scania S6 CAN file. The Scania Co-ordinator
device must not be connected to the engine
with this CAN file.

Using the Scania S6 CAN file will require a


SW1 setting of 5.0 and an SW2 setting of 4.0.
This setting is only applicable with DSE Load
Share Controllers and will need fine tuning
during the DSE Four Steps to Successful
Synchronisation Commissioning steps.

17.1.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the Scania-kw2000 CAN file when the
Co-ordinator device is fitted to the engine.

The DSE controller must be configured for


the Scania-kw2k-coo CAN file when the
Co-ordinator device is not fitted to the
engine. The DSE controller will perform
some additional functions normally
performed by the Co-ordinator.

Using the Scania-kw2000 or Scania-kw2k-


coo CAN file will require a SW1 setting of
5.0 and an SW2 setting of 2.0. This setting
is only applicable with DSE Load Share
Controllers and will need fine tuning during
the DSE Four Steps to Successful
Synchronisation Commissioning steps.

73
Sisu and DSE Controllers

18 SISU
Engines in the Sisu range are fitted with only one type of engine governing. This system is fully compatible with the DSE Controllers when
configured correctly and can allow engine control and diagnostics via the J1939 link.
We have collated the following data for the electronically governed engines.

74
Sisu and DSE Controllers

18.1 EEM3

18.1.1 ECU FUNCTIONALITY


EEM3 FUNCTIONALITY EEM3 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0x03, 0x11, 0x27
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, TSC1, OHECS, GPM24, DM3
Inlet Temperature  Proprietary msg None
Exhaust Temperature  Notes OEM DTCs messages included
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  LEGEND
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

18.1.2 ECU WIRING


DSE TERMINAL SISU ‘EEM3 CONNECTOR’
DESCRIPTION TERMINAL NOTES

NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
Fuel Relay
5
Output
CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
CANbus common - Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in
CANbus H 30
CANbus applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in
CANbus L 31
CANbus applications.

75
Sisu and DSE Controllers

18.1.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

18.1.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Sisu EEM3 CAN file.

Using the Sisu EEM3 CAN file will require a


SW1 setting of 5.0 and an SW2 setting of
4.0. This setting is only applicable with DSE
Load Share Controllers and will need fine
tuning during the DSE Four Steps to
Successful Synchronisation Commissioning
steps.

18.1.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the Sisu-EEM3 CAN file..

Using the Sisu-EEM3 CAN file will require a


SW1 setting of 5.0 and an SW2 setting of
2.0. This setting is only applicable with DSE
Load Share Controllers and will need fine
tuning during the DSE Four Steps to
Successful Synchronisation Commissioning
steps

76
Volvo and DSE Controllers

19 VOLVO
Engines in the Volvo Penta range are split into subgroups depending upon the type of engine governing are employed. These different
systems are fully compatible with the DSE Controllers when configured correctly and can allow engine control and diagnostics via the J1939
link.
We have collated the following data for the electronically governed engines.

77
Volvo and DSE Controllers

19.1 EDC3

19.1.1 ECU FUNCTIONALITY


EDC3 FUNCTIONALITY EDC3 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage  Speed Control 
Engine Hours  Source address 0x11, 0x2B
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop Pulse
Coolant Pressure  J1939 msg RQST, TSC1
Inlet Temperature  Proprietary msg Volvo_VP_Status
Exhaust Temperature  Notes Uses CM1
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  Legend
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

19.1.2 ECU WIRING


VOLVO TAD12 ‘STAND
DSE TERMINAL ALONE CONNECTOR’
DESCRIPTION TERMINAL NOTES

Fuel Relay
H CAUTION!:- An external slave relay may be needed. Check the current consumption does not
Output
exceed the DSE unit’s output specification.

Start Relay
E CAUTION!:- An external slave relay may be needed. Check the current consumption does not
Output
exceed the DSE unit’s output specification.
Using PC software configure ‘Auxiliary Output 1’ to be ‘ECU POWER’
Auxiliary
P
Output 1 NOTE:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.
CANbus common - Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus H 1 (Hi)
applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus L 2 (Lo)
applications.

NOTE:- Should the TAD12 ECU detect an engine fault not monitored by the DSE Module, an ‘external reset’ must be provided to reset the ECU.
Volvo specify that the reset is performed using external pushbuttons to give an input to TAD12 Standalone connector terminal J (diagnostics), P
(power) and H(stop).
According to Volvo, the reset sequence is:
1. Press and hold down the diagnostic button (terminal J) and apply power to H (stop)
2. Apply power to P (but don’t start the engine).
3. Hold these inputs for three seconds.
4. Release the diagnostic button (terminal J).
5. Remove power from H (stop).
6. Remove power from P (power).

78
Volvo and DSE Controllers

19.1.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

19.1.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Volvo EDC4 CAN file.

19.1.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


either the Volvo or Volvo-EDC3 CAN file
depending which is available.

79
Volvo and DSE Controllers

19.2 EDC4

19.2.1 ECU FUNCTIONALITY


EDC4 FUNCTIONALITY EDC4 FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 1
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage DSE Speed Control 
Engine Hours  Source address 0x03
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, TSC1
Inlet Temperature  Proprietary msg Volvo_EngineStopRequest
Exhaust Temperature  Notes Uses CM1
Fuel Temperature  DTC Ignore 91, 743, 677, 6279
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  Legend
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

19.2.2 ECU WIRING


VOLVO EDC4
DSE TERMINAL CONNECTOR
DESCRIPTION TERMINAL NOTES

NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
Fuel Relay
14
Output
CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.
Connect directly to engine starter solenoid.
Start Relay
-
Output CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.
1 Connects directly to battery negative
CANbus common - Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus H 12
applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus L 13
applications.

80
Volvo and DSE Controllers

19.2.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

19.2.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Volvo EDC4 CAN file.

19.2.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the VolvoEDC4 CAN file.

81
Volvo and DSE Controllers

19.3 EMS2/B

19.3.1 ECU FUNCTIONALITY


EMS2/B FUNCTIONALITY EMS2/B FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure  Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage  Speed Control 
Engine Hours  Source address 0x11, 0x2B
Number of Starts DSE ECU Power
Oil Temperature  ECU Stop Pulse
Coolant Pressure  J1939 msg RQST, TSC1
Inlet Temperature  Proprietary msg Volvo_VP_Status
Exhaust Temperature  Notes
Fuel Temperature  DTC Ignore 608
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  LEGEND
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

19.3.2 ECU WIRING


VOLVO EMS2/B
DSE TERMINAL CONNECTOR
DESCRIPTION TERMINAL NOTES
Using PC software select the relevant engine and configure ‘Auxiliary Output 1’ to be ‘ECU
POWER’
Auxiliary
5
Output 1 CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.
Using PC software select the relevant engine and configure ‘Auxiliary Output 2’ to be ‘ECU
STOP
Auxiliary
6
Output 2 ’ CAUTION!:- An external slave relay may be needed. Check the current consumption does not
exceed the DSE unit’s output specification.
CANbus common - Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus H 1 (Hi)
applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in CANbus
CANbus L 2 (Lo)
applications.

NOTE:- Speed control via CAN is not possible if the Volvo CIU is fitted to the engine or with Variable Speed (VE) engines.

NOTE:- Cranking of the engine is managed by the EMS2 controller following instruction from the DSE controller.

NOTE:- DSE55xx, DSE75xx and DSE8xxx can perform synchronising and load sharing using CAN instructions to the engine ECU.

82
Volvo and DSE Controllers

19.3.3 CAN CONFIGURATION


EMS2 and EMS2b are different versions of the same ECU. EMS2b is a later version with some issues with the original EMS2 diagnostic
reporting having been addressed. As Volvo EMS2/EMS2b has speed control via CAN, you must set the SW1 and SW2 if using a DSE Load
Share controller. Information regarding these configuration parameters can be found in the products software manual, please refer to section
entitled ‘Bibliography’ for more details.

19.3.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

Using the Volvo EMS2b CAN file with an


Volvo EMS2 engine will result in an alarm
being continuously present.

Using the Volvo EMS2 CAN file with an


Volvo EMS2b engine will result in some
alarms not being annunciated on the DSE
controller.

If the Volvo CIU IS fitted, you must use the


Volvo EDC3 CAN file instead of the Volvo
EMS2 file. In this situation speed control by
CAN is NOT possible.

Using the Volvo EMS2/b CAN file will


require a SW1 setting of 5.0 and an SW2
setting of 4.0. This setting is only applicable
with DSE Load Share Controllers and will
need fine tuning during the DSE Four Steps
to Successful Synchronisation
Commissioning steps.

19.3.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

Using the Volvo-EMS2b CAN file with an


Volvo EMS2 engine will result in an alarm
being continuously present.

Using the Volvo-EMS2 CAN file with an


Volvo EMS2b engine will result in some
alarms not being annunciated on the DSE
controller.

If the Volvo CIU IS fitted, you must use the


Volvo CAN file instead of the Volvo EMS2
file. In this situation speed control by CAN is
NOT possible.

Using the Volvo-EMS2/b CAN file will


require a SW1 setting of 5.0 and an SW2
setting of 2.0. This setting is only applicable
with DSE Load Share Controllers and will
need fine tuning during the DSE Four Steps
to Successful Synchronisation
Commissioning steps

83
Yanmar and DSE Controllers

20 YANMAR
Engines in the Yanmar range are fitted with only one type of engine governing. This system is fully compatible with the DSE Controllers when
configured correctly and can allow engine control and diagnostics via the J1939 link.
We have collated the following data for the electronically governed engines.

84
Yanmar and DSE Controllers

20.1 ECO
Space Reserved for Photo of ECU

20.1.1 ECU FUNCTIONALITY


ECO FUNCTIONALITY ECO FUNCTIONALITY
MODBUS Engine Hours  DM1 Conv. Method 4
MODBUS Oil Pressure  DM1 Ignored
MODBUS Coolant Temperature  DM1 Amber 
MODBUS Engine RPM  DM1 Red 
MODBUS Charge Alt  DM1 Protect 
MODBUS Speed Feed  DM1 Malfunction 
Engine speed  Start 
Oil Pressure DSE Stop 
Coolant Temperature  1500/1800 switch 
Battery Voltage DSE Idle Mode 
Charge Alternator Voltage  Speed Control 
Engine Hours  Source address 0x11
Number of Starts  ECU Power
Oil Temperature  ECU Stop
Coolant Pressure  J1939 msg RQST, TSC1
Inlet Temperature  Proprietary msg Yanmar_OLS, Yanmar_EC, Yanmar_STP
Exhaust Temperature  Notes
Fuel Temperature  DTC Ignore
Turbo Pressure 
Fuel Pressure 
Fuel Consumption  LEGEND
Fuel Used   Function supported
Atmospheric Pressure   Not supported
Water in Fuel  DSE DSE controller measures/calculates the value

20.1.2 ECU WIRING


DSE TERMINAL ECO
DESCRIPTION KEYSWITCH TERMINAL NOTES

NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
Fuel Relay
4
Output
CAUTION!:- An external slave relay may be needed. Check the current consumption
does not exceed the DSE unit’s output specification.

Start Relay
3 CAUTION!:- An external slave relay may be needed. Check the current consumption
Output
does not exceed the DSE unit’s output specification.

DSE TERMINAL ECO


DESCRIPTION ‘R1 CONNECTOR’ TERMINAL NOTES
CANbus common C Screen for the J1939 cable. Connect at one end only.
J1939 + Use only screened 120Ω impedance cable approved specifically for use in
CANbus H A
CANbus applications.
J1939 – Use only screened 120Ω impedance cable approved specifically for use in
CANbus L B
CANbus applications.

85
Yanmar and DSE Controllers

20.1.3 CAN CONFIGURATION


Information regarding these configuration parameters can be found in the products software manual, please refer to section entitled
‘Bibliography’ for more details.

20.1.3.1 DSE CONFIGURATION SUITE SOFTWARE


These settings are only applicable to DSE controllers which use the DSE Configuration Suite Software. This comprises of the DSE31xx,
DSE44xx, DSE6xxx, DSE71xx, DSE72xx, DSE73xx and DSE8xxx series of controllers.

The DSE controller must be configured for


the Yanmar ECO CAN file.

20.1.3.2 DSE5XXX/75XX PC SOFTWARE


These settings are only applicable to DSE controllers which use the DSE5xxx and DSE75xx PC Software. This comprises the DSE5xxx and
DSE75xx series of controllers.

The DSE controller must be configured for


the Yanmar-ECO CAN file.

86
This Page is Intentionally Left Blank

87
This Page is Intentionally Left Blank

88
paul

DEEP SEA ELECTRONICS PLC


PLC PROGRAMMING GUIDE FOR DSE
CONTROLLERS
Document Number: 057-175
Author: Anthony Manton

PLC Programming Guide for DSE Controllers ISSUE 1


PLC Programming Guide for DSE Controllers

Deep Sea Electronics Plc


Highfield House
Hunmanby
North Yorkshire
YO14 0PH
ENGLAND

Sales Tel: +44 (0) 1723 890099


Sales Fax: +44 (0) 1723 893303

E-mail: sales@deepseaplc.com
Website: www.deepseaplc.com

PLC Programming Guide for DSE Controllers

© Deep Sea Electronics Plc


All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written permission of
the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents
Act 1988.
Applications for the copyright holder’s written permission to reproduce any part of this publication
must be addressed to Deep Sea Electronics Plc at the address above.

Any reference to trademarked product names used within this publication is owned by their respective
companies.

Deep Sea Electronics Plc reserves the right to change the contents of this document without prior
notice.

Amendments Since Last Publication

Amd. No. Comments


1 First release

Typeface : The typeface used in this document is Arial. Care must be taken not to mistake the upper
case letter I with the numeral 1. The numeral 1 has a top serif to avoid this confusion.

2
PLC Programming Guide for DSE Controllers

Table of Contents
1 BIBLIOGRAPHY .................................................................................................. 4
2 INTERNAL PLC DESCRIPTION .......................................................................... 4
2.1 DSE CONTROLLER COMPATIBILITY ............................................................................... 5
2.2 FUNCTIONS, FLAGS AND MATHS.................................................................................... 6
2.2.1 PLC FUNCTIONS......................................................................................................... 6
2.2.2 FLAGS ......................................................................................................................... 6
2.2.3 PLC MATHEMATICS.................................................................................................... 6
2.2.3.1 USER REGISTERS ............................................................................................................... 6
2.2.3.2 USER STORES..................................................................................................................... 6

3 ACCESSING THE PLC EDITOR ......................................................................... 7


3.1 PLC LOGIC......................................................................................................................... 8
3.1.1 CONDITIONS............................................................................................................... 9
3.1.1.1 TEST FLAG .......................................................................................................................... 9
3.1.1.2 TEST INSTRUMENTATION VALUE ...................................................................................... 9
3.1.1.3 TEST CALCULATED VALUE................................................................................................11
3.1.1.4 TEST COUNTER .................................................................................................................12
3.1.1.6 TEST TIME AND DATE ........................................................................................................12
3.1.1.7 TEST BUTTON PRESS ........................................................................................................13
3.1.2 ACTIONS ................................................................................................................... 14
3.1.3 TRIGGER TYPE......................................................................................................... 14
3.1.3.1 CONTROLLING USER PLC FLAGS .....................................................................................15
3.1.3.2 COUNTER CONTROL..........................................................................................................15
3.1.3.3 MATHEMATICAL .................................................................................................................16
3.1.3.4 COPY ..................................................................................................................................16
3.1.3.5 CLOCK ADJUST ..................................................................................................................17
3.1.3.6 TIMER .................................................................................................................................17
3.1.3.7 FUNCTION ..........................................................................................................................18
3.1.3.8 OVERRIDE GENCOMM .......................................................................................................19
3.1.3.9 ALARM RESET ....................................................................................................................19
3.1.4 TOOLS ....................................................................................................................... 20
3.1.4.1 COUNTERS .........................................................................................................................20
3.1.4.2 TIMERS ...............................................................................................................................20
3.1.4.3 REGISTERS ........................................................................................................................21
3.1.4.4 STORES ..............................................................................................................................21
3.1.4.5 ADD LABEL .........................................................................................................................21
3.1.4.6 IMPORT RUNG(S) ...............................................................................................................22
3.1.4.7 SEARCH FOR USAGE .........................................................................................................22
3.1.4.8 MEMORY STATUS ..............................................................................................................22

4 MODULE DISPLAY ........................................................................................... 23


5 HOW TO CREATE A PLC PROGRAM.............................................................. 24
5.1 DESIGNING THE PROGRAM ........................................................................................... 24
5.2 USING THE PLC EDITOR TO MAKE AN EXAMPLE PROGRAM ..................................... 24
6 TESTING AND DIAGNOSING A PLC PROGRAM ............................................ 28

3
Introduction

1 BIBLIOGRAPHY
This document refers to and is referred to by the following DSE publications, obtained from the DSE
website www.deepseaplc.com.

DSE Part Description


057-051 DSE Configuration Suite PC Software Installation & Operation Manual
057-157 DSE335 Configuration Suite PC Software Manual
057-077 DSE7200 and DSE7300 Series Configuration Suite PC Software Manual
057-160 DSE7410 and DSE7420 Configuration Suite PC Software Manual
057-119 DSE8600 Series Configuration Suite PC Software Manual
057-127 DSE8700 Series Configuration Suite PC Software Manual
057-164 DSE8810 Configuration Suite PC Software Manual
057-174 DSE8860 Configuration Suite PC Software Manual
057-203 DSEE800 Configuration Suite PC Software Manual

2 INTERNAL PLC DESCRIPTION


The internal PLC allows the system designer to add functionality to the DSE controller where such
functions do not already exist. It also allows the designer to take existing functions within the
controller and tailor them to suit the application requirements.

The main point to remember with the PLC is that the designer is not changing existing functions within
the DSE controller, rather they are using them in differing ways to help ensure that DSE’s high level of
protection and safety cannot be bypassed with the PLC. However, great care must still be taken to
ensure the PLC program operates as required by the designer.

For example, the DSE8610 controller contains synchronising and load sharing functions, with
protections provided by the MultiSet Communications (MSC) link. It would be inappropriate to allow
designers to bypass these protections. However to allow customisation, DSE have provided digital
input functions to alter the process while maintaining all necessary protections. These input functions
are also accessible via PLC Functions, described in the section entitled PLC functions elsewhere in
this document.

NOTE: It is the responsibility of the PLC programmer to ensure that the PLC program
operates exactly as intended. DSE cannot be held responsible for any issues arising from
unintended actions of the PLC program.

4
Introduction

2.1 DSE CONTROLLER COMPATIBILITY


At the time of writing, the following controllers include the internal PLC with the following features:

Feature DSE335 DSE72xx DSE73xx DSE74xx DSEE800 DSE86xx DSE87xx DSE88xx


Number Of Nodes 50 100 100 200 400 400 200 200
Counters 10 10 10 10 20 20 10 10
Timers 10 10 10 10 20 20 10 10
Plc Functions 20 20 20 20 20 20 20 20
User Plc Flags 20 20 20 40 40 40 40 40
Flag Test
Flag Set, Reset, Drive, Toggle
Calendar Test
Instrumentation Test
Button Press Test
Import / Export Rungs
Alarm Reset
Label Space 1024 2048 2048 2048 2048 2048
Editable Timer And Counter Names
PLC SCADA
Override Gencomm
Registers 20
Stores 8
Module Display of Counters & Timers
Module Display of Register & Stores
Front Panel Editing of Counter and Timer
Set Points
Front Panel Editing of Registers
Front Panel Editing of Stores
Maths Functions
Clock Adjust (+/- 1hr)

5
2.2 FUNCTIONS, FLAGS AND MATHS
The PLC operates using key components – Functions, Flags and Maths. Almost every PLC program
consists of checking Flags and activating Functions or setting user Flags. Additionally more complex
programs may include some mathematical operations.

2.2.1 PLC FUNCTIONS

PLC functions can be considered as Virtual Inputs. For example, a PLC Function is configured in
exactly the same way as a Digital Input. The difference is that the PLC Function is activated by the
PLC and does not require hard wiring. In addition it does not ‘use up’ one of the module’s hardware
inputs.

2.2.2 FLAGS

Flags can be considered as Status Items within the DSE controller. Any operating state or alarm that
occurs can be detected by the PLC program. Decisions can then be made as to what action to
perform upon particular conditions.

It is also possible to create ‘user flags’ to store the result of a condition or set of conditions. These are
known as “PLC Output Flags”.

Module outputs can then be set to operate upon the PLC Output Flags or upon the module’s inbuilt
Flags.

These Flags are often called Output Sources.

2.2.3 PLC MATHEMATICS

PLC mathematics allows the user to manipulate instrumentation values with mathematical functions,
placing values and results into the module’s Registers or Stores for access later either by the PLC
itself or via the controller’s display.

2.2.3.1 USER REGISTERS

Values placed in the User Registers are lost when the module DC power is removed and after
configuration upload from the DSE Configuration Suite PC Software.

User Registers are able to be viewed in the module instrumentation screens after selection using the
DSE Configuration Suite PC Software. Refer to the section entitled Module Display elsewhere in this
document for further details.

2.2.3.2 USER STORES

Values placed in the User Stores are maintained, even when the module DC power is removed.
The values are stored in Non-Volatile (N.V.) memory. To minimise the number of writes to the N.V.
memory (extending its life), the values are stored at intervals of one minute since the last write to the
N.V. memory and then only if the value has changed.

User Stores are able to be viewed and edited in the module instrumentation screens after selection
using the DSE Configuration Suite PC Software. Refer to the section entitled Module Display
elsewhere in this document for further details.

6
Accessing the PLC Editor

3 ACCESSING THE PLC EDITOR


To access the internal PLC, the DSE Configuration Suite PC Software must be installed and a
Configuration from a supported controller must be opened. For details of this refer to DSE Publication
057-051 DSE Configuration Suite PC Software Installation & Operation Manual available from
www.deepseaplc.com.

The internal PLC editor is


accessed via the Advanced
section of the configuration
in the DSE Configuration
Suite PC Software.

The PLC menu consists of


the PLC Logic page where
the main programming takes
place, and the configuration
of the PLC Functions and
display of Registers and
Stores on the module’s
display.

These menu options are


described in the following
sections.

7
Accessing the PLC Editor

3.1 PLC LOGIC


Icons for testing Conditions

Icons for Actions

Icons for Tools

PLC ladder program area

To create a program, click and drag the icons from the Condition and Actions toolbar onto the
program area.

The PLC program is evaluated every 100 ms (10 times per second).
The evaluation time of each rung is indeterminate as each rung consists of a variety of functions,
each one with a variable execution time.

Actions are ‘queued’ by the PLC during the evaluation of the rungs, then executed in order at the
completion of the program, before the cycle begins again.
This means that the order of the items in the PLC may change the way the program operates.

8
Accessing the PLC Editor

3.1.1 CONDITIONS

Items on the Conditions toolbar allow for a variety of conditions to be tested (checked). Not all items
are available with all controllers.

Test Flag Test Calculated Test Timer Test Button


Value Press

Test
Instrumentation
Test Test Date and
Value
Counter Time

3.1.1.1 TEST FLAG

A Flag is an internal state of the controller. Some examples of flags include operating mode and
current alarm conditions. The list of testable flags varies depending upon the controller being
configured and is the same list for configuring the module’s output relays. A full list along with
descriptions is contained within the relevant DSE Configuration Suite PC Software Manual.

3.1.1.2 TEST INSTRUMENTATION VALUE

Allows the controller’s instrumentation to be tested in a number of ways.

Selection Mathematical Symbol


Less than < (Or Value is Under Range)
At most <= (Or Value is Under Range)
Equal to =
At least >= (Or Value is Over Range or at another Sentinel Value)
More than > (Or Value is Over Range or at another Sentinel Value)
Between >= AND <= (And Value is not at a Sentinel Value)

The list of testable flags varies depending upon the controller. A full list of module instrumentation is
contained within the relevant Operator Manual.

Not all instrumentation can be read from all controllers. These include :

• Instruments that are not supported by the controller. For example “Mains Voltage” is only
available in controllers with Mains Sensing.
• Instruments not configured in the controller. For example the Fuel Level Input may be
configured to be “not used”.
• Instruments that are under range or over range. For example if the Coolant Temperature is
below the measurable range of the temperature sensor being used.
• Instruments that are in a fault condition. For example the Oil Pressure Sensor may be “open
circuit”.
• Instruments whose condition cannot be determined. For example Power Factor is not
measurable when there is no load applied to the generator.

In these circumstances the module returns a sentinel value as listed overleaf. The actual value
returned for a given state varies depending upon the size and type of instrument being read.

NOTE: It is the responsibility of the PLC programmer to ensure that the PLC program
operates exactly as intended. DSE cannot be held responsible for any issues arising from
unintended actions of the PLC program.

9
Accessing the PLC Editor

Sentinel Values for Instrumentation

Size of register Sentinel Values Sentinel Values Description


(Hexadecimal) (Decimal)
16 bit unsigned, any scale 0xFFFF 65535 Unimplemented
0xFFFE 65534 Over measurable range
0xFFFD 65533 Under measurable range
0xFFFC 65532 Transducer fault
0xFFFB 65531 Bad data
0xFFFA 65530 High digital input
0xFFF9 65529 Low digital input
0xFFF8 65528 Reserved
16 bit signed, any scale 0x7FFF 32767 Unimplemented
0x7FFE 32766 Over measurable range
0x7FFD 32765 Under measurable range
0x7FFC 32764 Transducer fault
0x7FFB 32756 Bad data
0x7FFA 32763 High digital input
0x7FF9 32762 Low digital input
0x7FF8 32761 Reserved
32 bit unsigned, any scale 0xFFFFFFFF 4294967295 Unimplemented
0xFFFFFFFE 4294967294 Over measurable range
0xFFFFFFFD 4294967293 Under measurable range
0xFFFFFFFC 4294967292 Transducer fault
0xFFFFFFFB 4294967291 Bad data
0xFFFFFFFA 4294967290 High digital input
0xFFFFFFF9 4294967289 Low digital input
0xFFFFFFF8 4294967288 Reserved
32 bit signed, any scale 0x7FFFFFFF 2147483647 Unimplemented
0x7FFFFFFE 2147483646 Over measurable range
0x7FFFFFFD 2147483645 Under measurable range
0x7FFFFFFC 2147483644 Transducer fault
0x7FFFFFFB 2147483643 Bad data
0x7FFFFFFA 2147483642 High digital input
0x7FFFFFF9 2147483641 Low digital input
0x7FFFFFF8 2147483640 Reserved

10
Accessing the PLC Editor

3.1.1.3 TEST CALCULATED VALUE

NOTE: On some controllers, Calculated Values are available in the Test Instrumention
section.

Calculated values are predefined by DSE and are included to provide additional ways of testing of the
controller’s instrumentation.

Selection Description
Average An average of the instrumentation
Difference The difference between the maximum and the minimum
Maximum The highest instrumentation value
Minimum The lowest instrumentation value
Minimum Index Indicates the lowest of the three phases (L1=1, L2=2, L3=3)
Maximum Index Indicates the highest of the three phases (L1=1, L2=2, L3=3)

Example:

L1 = 230 V AC
L2 = 233 V AC
L3 = 224 V AC

Results of the Calculated Values operators are as follows:


Average Difference Maximum Minimum Minimum Index Maximum Index
233 224 3 2
229 9
Maximum Minimum L3 is the minimum L2 is the maximum of
((230+233+224)/3) (233-224)
Value Value of the three phases the three phases

11
Accessing the PLC Editor

3.1.1.4 TEST COUNTER

Allows a counter to be tested to see if it has reached the configurable limit.

State Value When Tested


Not Active False
Active, not reached limit False
Active, reached or past limit True

3.1.1.5 TEST TIMER

Allows a timer to be tested to see if it has reached the configurable limit.

State Value When Tested


Not Active False
Active, not reached limit False
Active, reached or past limit True

3.1.1.6 TEST TIME AND DATE

Test Time and Date are a collection of tests that allows an action based upon a specific time, date or
time and date.

Icon Name Description


Time of Day Allows testing for a specific time ie 10:32 am
Day of Week Allows testing for a specific day(s) ie Tuesday
Day of Month Allows testing for a specific date(s) in the month ie 25th
Week in Month Allows testing for a specific week(s) in the month ie Week 3
Month Allows testing to a specific month(s) ie September

It is also possible to combine two or more of these tests to make a more specific test.

For example:

+ + allows a test for a specifc time, day and month, for instance 10:32am on any Tuesday in
September.

12
Accessing the PLC Editor

3.1.1.7 TEST BUTTON PRESS

Allows the PLC program to check if any of the control buttons are being pressed on the controller.

Depending upon controller type this allows testing for the following button presses:

DSEGenset Range DSEATS Range


Stop/Reset Start Inhibit
Manual Manual
Auto Auto
Test Mode
Start Mute
Mains Information
Gen S1
Mute S2

Example: Testing for multilple button presses.

This example drives PLC Flag 1 when the Test button OR Start button is pressed:

This example drives PLC Flag 1 when the Test button AND Start button is pressed:

13
Accessing the PLC Editor

3.1.2 ACTIONS

The action toolbar contains the icons that allow the PLC to perform certain actions. These are
described in the following sections.

Methods of Mathematical Timer PLC Function Alarm Reset


Controlling User
Flags

Counter Control Copy Clock Override


adjust Gencomm

3.1.3 TRIGGER TYPE

Some Actions are ‘edge triggered’. This means the action takes place when the preceeding
Condition(s) change. If a Condition remains unchanged, the Action is not repeated.

Some Actions are ‘level triggered’. This means the action takes place if the Condition(s) are true and
continues to be actioned until the Condition(s) become false.

Action Type Trigger Type


Set Flag Edge
Drive Flag Edge
Reset Flag Edge
Toggle Flag Edge
Increment Counter Edge
Decrement Counter Edge
Zero Counter Edge
Mathematical Level
Copy Level
Clock Adjust Edge
Timer Level
Plc Function Level
Gencomm Override Level
Alarm Reset Level

14
Accessing the PLC Editor

3.1.3.1 CONTROLLING USER PLC FLAGS

Four different ways of controlling the User Settable PLC Flags are possible.

Icon Name Description


Set Flag Sets a Flag. The flag remains set until another a Reset or Toggle action
changes it. Removal of the condition that activated the Set command has
no effect on the state of a flag.
This is useful for ‘remembering’ that a condition has occurred.
Reset Flag If a flag is in a Set position, this action resets the flag.
Toggle Flag Changes the state of a flag. If the flag is currently set, it resets it.
If the flag is currently reset, it sets it.
Drive Flag This action makes the flag state follow the condition that preceeds it.
For example if the condition is true, the flag is set. If the condition is
subsequently removed, the flag is automatically reset.

3.1.3.2 COUNTER CONTROL

Actions to control user counters.

Icon Name Description


Increment Adds one to the specified counter until the counter reaches its configured
counter counter limit.
Decrement Subtracts one from the specified counter (unless the counter is already
counter zero (0)).
Zero counter Sets the specified counter to Zero.

15
Accessing the PLC Editor

3.1.3.3 MATHEMATICAL

Actions to allow mathematical functions to be performed and the results placed in a Register or Store.

Item Description
Operation Addition: Value1 + Value 2
Value 1 Subtraction: Value 1 – Value 2
Value 2 Multiply: Value 1 * Value 2
Divide: Value 1 / Value 2 (remainder is lost)
Remainder: The remainder of Value 1 / Value 2
Magnitude: The value with its ‘sign’ removed. For example both 6 and -6 give a
value of 6.
Minimum: The lowest of Value 1 and Value 2. For example Value 1 = 5, Value
2 = 7. The Minimum is 5.
Maximum: The highest of Value 1 and Value 2. For example Value 1=5, Value
2 = 7. The Maximum is 7.
Target The location where the result of the mathematical operation is to be placed.

Register: Values placed in the User Registers are lost when the module DC
power is removed.
Store: Values placed in the User Stores are maintained, even when the module
DC power is removed.

For further details of Registers and Stores, see the section entitled PLC Maths
elsewhere in this document.

3.1.3.4 COPY

Allows a value to be copied or placed into a Register or Store.

Item Description
Value Fixed Value: Enter the value manually.
Calculated Value: Select the calculated instrumentation value from a list of
prefined options.
Instrumentation Value: Select one of the modules instrumentation items.
Register: Select one of the Registers.
Store: Select one of the Stores.
Target The location where the Value is to be placed.

Register: Values placed in the Registers are lost when the module DC power is
removed.
Store: Values placed in the Stores are maintained, even when the module DC
power is removed.

For further details of Registers and Stores, see the section entitled PLC Maths
elsewhere in this document.

16
Accessing the PLC Editor

3.1.3.5 CLOCK ADJUST

Included to ease Daylight Saving adjustments, this allows one hour to be added to or subtracted from
the module’s internal clock.

Example:
Showing the addition of one hour on the fourth Sunday in March at 1 am. Addtionally this is setting a
User Store to the value of 1. This allows us to check in the PLC SCADA or in the module
instrumention if DST is active:

Example:
Showing the subtraction of one hour on the fourth Sunday in October at 2 am. We additionally check
the status of DST (Store 1) to ensure the clock is not continually adjusted one hour later!

3.1.3.6 TIMER

Allows a timer to be started.


When the condition leading to the timer becomes true, the timer is started and runs until the
configurable timer limit is reached. If the condition becomes false, the timer is stopped and the current
time is ‘lost’. The timer begins from zero if it is restarted.

If it is required to restart a timer, it’s condition must be made false, then true again in order to re-
enable the timer. This restarts the timer from zero.

17
Accessing the PLC Editor

3.1.3.7 FUNCTION

PLC functions can be considered as Virtual Inputs. For example a PLC Function is configured in
exactly the same way and has the same selections as a Module Digital Input. The difference is that
the PLC Function is activated by the PLC and does not require hard wiring.

Item Description
Function User Configured: Allows the user to configure the Function to perform
an alarm or status indication.
Digital Input Selection List: Allows the user to select from a predefined
selection list. Refer to the DSE Configuration Suite PC Software Manual
for the host controller in use for a full description of possible selections.
Polarity Close to Activate: The Function is ‘normally inactive’ and must be
driven in the PLC in order to activate it.
Open to Activate: The Function is ‘normally active’ and must driven in
the PLC in order to de-activate it.
Action Electrical Trip: When activated, an electrical trip alarm is generated, the
(Only applicable when load switch is opened (if closed) and the generator placed into the
function is set to “User cooling run before stopping.
Configured”) Indication: No alarm condition is generated and the set continues to
run. This is often used to create status indications or be monitored by the
user’s PLC logic.
Warning: When activated, a warning alarm is generated but the set
remains running.
Shutdown: When activated, a shutdown alarm is generated, the load
switch (if closed) is immediately opened and the set is immediately
stopped.

Example using a function to prevent starting the generator upon a mains failure during the whole of
Sunday. This uses PLC Function 1, configured to “Auto Start Inhibit”.

18
Accessing the PLC Editor

3.1.3.8 OVERRIDE GENCOMM

Using an external PLC that has a Modbus master serial port, it is possible to write values to the DSE
controllers to change certain parameters. The protocol used for this is called Gencomm.
Using the DSE internal PLC, it is possible to change these same values using the Override Gencomm
action.
Depending upon controller type, the parameters that can be changed vary. Some controllers have no
adjustable parameters using this function.

Example 1: Using Override Gencomm, the Run Priority of the set can be changed.
Example 2: Using Override Gencomm, the amount of power the generator is producing can be
changed.

3.1.3.9 ALARM RESET

This action allows individual alarms to be reset. An alarm can only be reset if the condition that
generated the alarm is no longer present.

To perform an action that resets ALL alarms, it’s more appropriate to drive a PLC Function that has
been configured to Alarm Reset.

19
Accessing the PLC Editor

3.1.4 TOOLS
Setup Import PLC Search for Counter /
Timers Rung(s) Timer usage
Setup
Counters

Setup Setup
Registers Stores Add a Label

3.1.4.1 COUNTERS

Click to Click and


Rename the Drag to Set
Counter the Counter
(DSE8xxx Limit
series only)

Scroll down
to access all
the counters.

3.1.4.2 TIMERS

Click to Click and


Rename the drag to set
Timer the Timer
(DSE8xxx
series only)
Limit

Scroll down
to access all
the timers.

20
Accessing the PLC Editor

3.1.4.3 REGISTERS

Allows the user registers to be named for easier referencing and display on the module screen.

Click to
rename the
Register

3.1.4.4 STORES

Allows the user registers to be named for easier referencing and display on the module screen.

Click to
Rename the
Stores

3.1.4.5 ADD LABEL

Clicking Add Label generates a blank label in the PLC Ladder. This allows the designer to place notes
in the PLC Ladder.

Delete the Click and drag to move the Type the Label here
Label Label to another location in
the ladder.

21
Accessing the PLC Editor

3.1.4.6 IMPORT RUNG(S)

Allows the designer to import a PLC program containing one or more rungs into the current program.
This is useful for reusing functions created in other configurations.
Care must be taken when using this function as Flags, Registers, Stores, Counters, Timers and PLC
Functions may be called that are already in use in the current program.

3.1.4.7 SEARCH FOR USAGE

Shows a list of currently used Functions, Counters, Timers, Registers and Stores. This makes it
easier when adding additional counters and timers by allowing the designer to see which ones are
already in use.

3.1.4.8 MEMORY STATUS

The PLC memory status is contained at the bottom of the PLC Logic page. The amount of available
memory differs between controller ranges.

The amount of memory blocks used in The amount of labels used by Counters,
the ladder program. Timers, Registers, Stores and user placed
Labels.

22
Module Display

4 MODULE DISPLAY

NOTE: This section is not available on all controllers. See the section entitled DSE
Controller Compatibility elsewhere in this document.

This section allows the user to select up to eight items from the complete list of Counters, Timers,
Registers or Stores for display on the host module’s instrumentation display.

The Module Display page is


located under Advanced | PLC in
the module Configuration.

Select which of the Counters,


Timers, Registers and Stores are
to be show on the controller’s
display.

After selection for display on the host controller, Counters, Timers, Registers and Stores are able to
be viewed and/or edited as below on the controller display.

Parameter View Edit


Counter Value
Counter Limit
Timer Value
Timer Limit
Register
Store

NOTE: All Stores are able to be edited in the SCADA | PLC | PLC Stores section of the
DSE Configuration Suite PC Software regardless of their selection in the Module Display |
Displayed Pages section of the configuration. For details of this, refer to the relevant control
DSE Configuration Suite PC Software Manual as listed in the Bibliography section of this
manual.

23
Designing the PLC Program

5 HOW TO CREATE A PLC PROGRAM


5.1 DESIGNING THE PROGRAM
The fundamental issue in creating a PLC program is knowing exactly what is required!
It is usually best to start with a written description. As the DSE PLC is based around the internal
system of inputs and outputs, keep these functions in mind when designing the solution.

5.2 USING THE PLC EDITOR TO MAKE AN EXAMPLE PROGRAM


For example, if a function is required to silence the controller’s alarm 30 seconds after it begins, the
designer must consider how to determine if the alarm is active and then how to perform the silencing
function.

Looking through the list of Flags we find Audible Alarm. This flag is set whenever the controller’s
internal audible alarm is active.

Therefore, in the PLC Logic screen we can ‘drag’ the (Flag Test) icon to the Program Area. The
following options box appears:

Parameter Description
Condition Type The type of condition to check for. This is automatically set when the icon is
dragged from the Condition toolbar but can be changed if the wrong one is
inadvertently selected.
Polarity Normally Open: Tests if the condition is True.
Normally Closed: Tests if the condition is False.
Source Contains the list of available Flags.
This list differs between controller types. A full list of sources is included in the
relevant controller’s Configuration Suite manual.
OK Click to add the condition to the PLC program.
Cancel Click to cancel and return to the editor without adding the condition.

In our example we select Flag Test, Normally Open, Audible Alarm and click .

Our example program is now as below. If it isn’t, then go back and check what went wrong.

24
Designing the PLC Program

The next thing we need to do is set a timer that expires in 30 seconds after the audible alarm begins.

Drag the (Delay) icon from the Action Toolbar and drop it just to the right of the black line to the
right of the Audible Alarm symbol that has just been placed.

As the mouse button is released, the following settings box appears :

Parameter Description
Action Type The type of action to perform. This is automatically set when the icon is dragged
from the Action toolbar but can be changed if the wrong one is inadvertently
selected.
Timer # The number of the timer to be operated.

Next click , the Timer Limit settings box appears.

For our example,set Timer limit 1 to 30s:


and click .

Now the program looks like this:

This program now checks for an audible alarm and start a timer that runs for 30 seconds (so long as
the audible alarm remains active). Next we need to configure what happens when the timer expires.

We need a new Condition: (Timer Test). Drag this from the Condition Toolbar into the empty
space below the first PLC rung. The details window appears. Make selections as shown below. This
checks to see if Timer # 1 has expired.

25
Designing the PLC Program

Our program is now as shown below:

We have now just one more item to add to the PLC Ladder.
When the 30 second timer expires, we want it to silence the audible alarm. This is achieved using a
PLC Function. Drag the (Trigger Function) icon and drop it to the right of the Timer Limit 1 condition.

Parameter Description
Action Type The type of action to perform. This is automatically set when the icon is dragged
from the Action toolbar but can be changed if the wrong one is inadvertently
selected.
Function # The number of the Function to be operated.

For our example, select Function # 1.

Our program is now as shown below:

This program now checks for an audible alarm and start a timer that runs for 30 seconds (so long as
the audible alarm remains active).
When the timer expires, Function 1 is triggered.

Finally we have to configure what Function 1 is used for.

Select PLC Functions 1-4 from the Configuration Editor:

26
Designing the PLC Program

The PLC Functions editor is displayed.


PLC Functions have exactly the same choices as module digital inputs.

Configures when the Example of a user configured


input is active: input.
Never, always,
active from starting, Close or open to activate.
active from the end
of the safety timer.
Select the type of alarm
required.
This is the text
that is displayed Click and drag to change the setting.
on the module This is used to give a delay on
screen when the acceptance of the input. Useful for
alarm is triggered. liquid level switches or to mask short
term operations of the external
switch device.

For our example PLC program, we need to select Alarm Mute, a predefined function that silences the
alarm:
Function. The possible
As this example selections differ with
shows a predefined each controller range.
function, these These are listed in the
parameters are relevant Configuration
greyed out as they Suite Software
are not applicable manual.

Finally. We have a program that now checks for an audible alarm and starts a timer that runs for 30
seconds (so long as the audible alarm remains active).
When the timer expires, Alarm Mute (Function 1) is triggered silencing the alarm. If another alarm
occurs, the audible alarm restarts, starting our 30 second timer again.

Remember to click (Save) to save a copy of the configuration file. The PLC program is contained
within the configuration file.
Also remember to click (Write to module) to upload the configuration file to the connected controller.

27
Testing and Diagnosing the PLC Program

6 TESTING AND DIAGNOSING A PLC PROGRAM


Many PLC programs are very simple, having only one or two rungs (lines) in the ladder. Often, the
easiest way to test these is to simply use the module and test that the actions are as required.
However sometimes this leads to us finding that the PLC program is not acting as required. This is
usually caused by an error in the design of the program.
DSE have provided a diagnostic monitor in the SCADA section of the Configuration Suite Software to
aid the fault finding process. This is not available in all controllers with PLC functionality.

Select PLC in the SCADA section of the Config


Suite when connected to the module containing
the PLC ladder to be viewed / diagnosed.
The message:

is shown until the entire PLC ladder has been


downloaded for viewing from the connected
controller.

Conditions highlighted in green show ACTIVE


(true) conditions.
Conditions with no highlight are INACTIVE (false)
‘Clear’ means that the flag is not set.
‘Set’ means that the flag is set.
See below for further details.

Timers and Counter shows their current value.

Note that depending upon update time of the


SCADA screen, this may not be in ‘real time’.
Fast connection methods such as USB or direct
Ethernet connection (no internet) give much quicker
update rates.

Example showing SCADA display of Flag Testing:

PLC SCADA symbol


when PLC Output Flag 1 is
PLC Editor Symbol Description
Active (True) Inactive (False)

Test PLC flag 1 (normally open)

Test PLC flag 1 (normally closed)

28
This Page is Intentionally Blank

29
This Page is Intentionally Blank

30
®

DSE

DSEE800 ENVIRONMENTAL TESTING STANDARDS

ELECTRO MAGNETIC COMPATIBILITY


ENGINE CONTROLLER BS EN 61000-6-2
EMC Generic Immunity Standard for the
Industrial Environment
BS EN 61000-6-4
FEATURES EMC Generic Emission Standard for the
Industrial Environment

ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
The DSEE800 is an easy to use With the built in PLC editor the Using the DSE Configuration Suite including Electrical Business Equipment
engine controller designed to controller is fully flexible and can be PC Software the controller is easy
provide flexible control with built in adjusted to meet many different to use and configure which allows TEMPERATURE
BS EN 60068
monitoring and protection. The needs, providing the user with the alteration of operating parameters, Ab/Ae Cold Test -30oC
DSEE800 is compatible with both ability to achieve special operating sequences, timers and alarms. BS EN 60068-2-2
electronic and non-electronic diesel modes which are unique to their Bb/Be Dry Heat +70oC
engines and fully configurable for a machine and application. A range VIBRATION
wide range of applications such as of comprehensive communication BS EN 60068-2-6
engine driven pumps, and system expansion options Ten sweeps in each of three major axes
5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
compressors, hydraulic power ensures that the user can extend
packs and off highway machinery. the input and output capability and HUMIDITY
communicate with other devices or BS EN 60068-2-30
Db Damp Heat Cyclic 20/55oC @ 95% RH
Control of the application can be systems offering further advanced 48 Hours
achieved both automatically and and high level use in very BS EN 60068-2-78
Cab Damp Heat Static 40oC @ 93% RH
manually with engine start, speed demanding applications. On board 48 Hours
and clutch control all built in. The event, data logging and trending
monitoring and configuration of makes it possible to determine SHOCK
BS EN 60068-2-27
system variables allows the preventative maintenance and Three shocks in each of three major axes
controller to start and stop the improved performance criteria for 15gn in 11mS
engine, increase and decrease the machine.
DEGREES OF PROTECTION
engine speed as the output PROVIDED BY ENCLOSURES
demands and program ramping for BS EN 60529
IP65 - Front of module when installed into the
loading/unloading of the engine. control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY


OF ENGINE APPLICATIONS

DSENET® RS232 AND USB USB CONFIGURABLE DC OUTPUTS RATIO-METRIC EMERGENCY DC POWER
EXPANSION RS485 PORT HOST INPUTS INPUTS STOP SUPPLY 8-35V

DSEE800

VOLT FREE PWM OUTPUTS FUEL & START CHARGE ELECTRONIC MAGNETIC
OUTPUTS ALTERNATOR ENGINES PICK-UP
OUTPUTS

ISSUE 1
®

DSE

DSEE800
SPECIFICATION

DC SUPPLY
CONTINUOUS VOTLAGE RATING
ENGINE CONTROLLER 8 V to 35 V continuous

CRANKING DROPUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
FEATURES supply recovers to 5 V. This is achieved
without the need for internal batteries.

MAXIMUM OPERATING CURRENT


510 mA at 12 V, 238 mA at 24 V

MAXIMUM STANDBY CURRENT


226 mA at 12 V, 107 mA at 24 V

MAXIMUM OFF MODE CURRENT


180 mA at 12 V, 86 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V

INPUTS
DIGITAL INPUTS A to K
Configurable as:
Positive switching
Negative switching

RATIOMETRIC INPUT A
Configurable as:
Negative switching digital input
0 V to 10 V
4 mA to 20 mA
0 Ω to 480 Ω

RATIOMETRIC INPUTS B to L
KEY FEATURES • CAN, Magnetic Pick-up or KEY BENEFITS Configurable as:
Negative switching digital input
• Built-in governor control tachometer speed sensing • 132 x 64 pixel ratio display for 0 V to 10 V
• Automatic speed control • Fuel usage monitor and low fuel clarity 4 mA to 20 mA
0 Ω to 1920 Ω
• Manual speed control via push alarms • Real-time clock provides
buttons, digital input or analogue • Charge alternator failure alarm accurate event logging OUTPUTS
input • Manual fuel pump control • Set maintenance periods can be DC OUTPUT A (FUEL) & B (START)
10 A short term,
• Automatic speed ramping • “Protections disabled” feature configured to maintain optimum 5 A continuous at supply voltage
• Flexible automatic start control • LED and LCD alarm indication engine performance
• Clutch control • USB connectivity • Ethernet communications VOLT-FREE OUTPUTS C & D
5 A DC at 35 V DC
• 4-Line back-lit LCD text display • Backed up real time clock provides built in advanced 8 A AC at 250 V AC
• Multiple display languages • Fully configurable via DSE remote monitoring.
DC OUTPUTS E, F, G & H
• Five key menu navigation Configuration Suite PC software • Can be integrated into remote 2 A DC at supply voltage
• Front panel editing with PIN • Configurable display languages monitoring systems
protection • Remote SCADA monitoring via • Increased input and output PWM OUTPUTS I, J, K & L
4 A at supply voltage
• Customisable status screens DSE Configuration Suite PC expansion capability via DSENet® 20 Hz to 250 Hz
• Power save off mode software • Licence-free PC software
• Configurable digital inputs (11) • User selectable RS232, RS485 & • IP65 rating (with supplied gasket) PULSE PICK-UP
VOLTAGE RANGE
• Configurable ratiometric Ethernet communications offers increased resistance to ±0.5 V to 60 V RMS
inputs (12) • Modbus RTU & TCP support water ingress Fully isolated
• Configurable DC outputs (4) • User configurable MODBUS • Advanced PLC editor allows user
FREQUENCY RANGE
• Configurable volt-free outputs (2) pages configurable functions to meet 10,000 Hz (max)
• Configurable PWM outputs (4) • Advanced SMS control and fault application requirements.
BUILT-IN GOVERNOR CONTROL
• Configurable timers and alarms messaging (additional GSM MINIMUM LOAD IMPEDANCE
• 3 configurable maintenance modem required) 1000 Ω
alarms • Start & stop capability via SMS Fully isolated
• Multiple date and time engine messaging GAIN VOLTAGE
scheduler • Additional display screens to 0 V to 10 V DC
• Configurable event log (250) help with modem diagnostics
OFFSET VOLTAGE
• CAN engine support • DSENet® expansion compatible ±10 V DC
• Advanced Integral PLC editor • Data logging and trending
DIMENSIONS
OVERALL
240 mm x 172 mm x 57 mm
9.4” x 6.8” x 2.2”
RELATED MATERIALS
PANEL CUTOUT
TITLE PART NO’S 220 mm x 160 mm
DSEE800 Installation Instructions 053-090 8.7” x 6.3”
DSEE800 Operator Manual 057-202
DSEE800 PC Configuration Suite Manual 057-203 MAXIMUM PANEL THICKNESS
8 mm
0.3”
DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA
Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA OPERATING TEMPERATURE RANGE
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708 -40 °C to +80 °C
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com
STORAGE TEMPERATURE RANGE
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 -40 °C to +85 °C
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457
055-168/09/13 US (3)
053-090
TYPICAL WIRING DIAGRAM DEEP SEA ELECTRONICS ISSUE 1
A larger diagram is available in the operators manual.
Part No 057-202 D S EE 8 0 0 I NST AL L AT I O N I NST R UCT I O NS

ACCESSING THE FRONT PANEL CONFIGURATION EDITOR


• Ensure the engine is at rest and the module is in STOP mode by pressing the Stop/Reset
button.

• Press and hold the the (stop) button and (tick) button together.
• If a module security PIN has been set, the PIN number request is then shown .

• Press (tick), the first ‘#’ changes to ‘0’. Press (up) or (down) to adjust it to the correct
value.
• Press (right) when the first digit is correctly entered. The digit you have just entered will now
show ‘#’ for security.

• The other digits of the PIN number. You can press (left) if you need to move back to adjust
one of the previous digits.

• When (tick) is pressed after editing the final PIN digit, the PIN is checked for validity. If the
number is not correct, you must re-enter the PIN.
• If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is
displayed.

• To edit the parameter, press (tick) to enter edit mode. The parameter begins to flash to indicate
that you are editing the value.
• Press the up or down buttons to change the parameter to the required value.
• Press (tick) to save the value. The parameter ceases flashing to indicate that it has been saved.

• To exit the editor at any time, press and hold the (stop) to eixit without saving changes or
(tick) button to save changes and exit.

EDITING A PARAMETER

• Enter the editor as described above.

• Press the (up) (down) and (right) to cycle to the section you wish to view/change.
Then press (up) or (down) to cycle to the parameter within the section you have chosen.

• To edit the parameter, press (tick) to enter edit mode. The parameter begins to flash to indicate
that you are editing the value.
• Press the up or down buttons to change the parameter to the required value.

• Press (tick) to save the value. The parameter ceases flashing to indicate that it has been saved.

• To exit the editor at any time, press and hold the (stop) or (tick) button.

NOTE: When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure
security.
NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to
ensure security.
NOTE: More comprehensive module configuration is possible using the PC configuration software. Please
contact us for further details
NOTE: The contents of the tables overleaf may differ depending on the actual module configuration.
ADJUSTABLE PARAMETERS - Front Panel Configuration Editor. ACCESSING THE “MAINTENANCE” EDITOR
Section Parameter As Shown On Display Values

Display Contrast 0 % Description Action Activation


Language English, others. Press (up) or (down) buttons together.
Current Date and Time Date hh:mm USB Stick Removal Request
Engine Oil Pressure Low shutdown 0 bar Override Starting Alarms Request Press
Oil Pressure Low Pre-Alarm
Coolant Temp High Pre-Alarm
0 bar
0 ºC
Press ,(up) or (down) (right) to cycle to Clear AMF Alarm
Manual Fuel Pump
Clear
Inactive
Coolant Temp High Shutdown 0 ºC the Parameter you wish to action. Min / Max Session Reset Request Button
Start Delay Off load 0 s Cancel Telemetry Request
Start Delay on load 0 s
Start Delay Telemetry 0 s
Pre Heat Timer 0 s
Crank Duration 0 s To exit the editor at any time, press and hold the (tick) button.
Crank rest Time 0 s
Safety On Delay 0 s
Smoke Limiting 0 s
Smoke limiting off 0 s
Warm Up Time 0 s
Cool Down Time 0 s
Under Speed Shutdown Inactive ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
Under Speed Warning Inactive
Over Speed Shutdown Inactive
Over Speed Warning Inactive
Over Speed Shutdown 0 RPM
Speed Overshoot 0% • The ‘running’or editor can be entered while the engine is running. All protections remain active if the engine is
Fail To Stop Delay 0 s running while the running editor is entered.
Battery Under Volts Warning Active
Battery Under Volts Warning Delay 0 m
Battery Under Volts Warning 0 v • Press and hold the (tick) button to enter the running editor.
Battery Over Volts Warning Active
Battery Over Volts Warning Delay 0 m
Battery Over Volts Warning 0 v
Charge Alternator Failure Warning Active
Charge Alternator Failure Warning 0 V ADJUSTABLE PARAMETERS - Running Configuration Editor
Charge Alternator Warning Delay 0 s
Charge Alternator Failure Shutdown Inactive
Priming Delay 0 s • Enter the editor as described above.
Clutch Engage Speed 8
Clutch Disengage Speed 0
Idle Speed 0.00
Warming Speed 0.00
• Press the (up) or (down) buttons to cycle to the section you wish to view / change.
Cooldown Speed 0.00
Starting 0.00
Min Speed 0.00
On Load Speed 0.00 • To Edit the parameter press the (tick) button to enter edit mode. The parameter begins to flash to indicate that
Max Speed 0.00
you are editing the value.
Auto Adjustable Speed Inactive
Cool Down at Idle 0 s
LCD Page Timer 5m
Timers
Scroll Delay
Engine Pre Heat Timer
2s
0s
• Press the (up) or (down) buttons to change the parameter to the required value.
Engine Crank Duration 10s
Engine Crank Rest Time 10s
Engine Safety On Delay 10s • Press the (tick) button to save the value. The parameter ceases flashing to indicate that it has been saved.
Engine Smoke Limiting 0s
Engine Smoke Limiting Off 0s
Engine Warm Up Time 0s
Engine Cool Down Time 1m • Press and hold (tick) button to exit the “Running Configuration Editor”.
Engine Speed Overshoot Delay 0s
Engine Failed To Stop Delay 30s
Battery Under Voltage Warning Delay 1m
Battery Over Voltage Warning Delay 1m
Return Delay 30s Section Parameter Values
Under Voltage Pre-Alarm 196v Display Contrast 0%
Nominal Voltage 230v Language English (United Kingdon), Other
Schedule Schedule Inactive
Schedule On Load Active , Inactive (Only Available When Scheduler Is Active) b SectiT
Schedule Period Weekly, Monthly (Only Available When Scheduler Is Active) o

Schedule Time & Date Selection (1-16) Press to begin editing then or when
selecting the different parameters in the scheduler.

Deep Sea Electronics Plc. Deep Sea Electronics Inc.


Tel:+44 (0)1723 890099 Phone: +1 (815) 316-8706 DIMENSIONS AND MOUNTING
Fax: +44 (0)1723 893303 Fax: +1 (815) 316- 8708 For flat surface mounting in a Type 1 enclosure to meet UL requirements
Email: support@deepseaplc.com TOLL FREE (USA) : Tel: 1 866 636 9703
Web: www.deepseaplc.com Email: dsesales@deepseausa.com DIMENSIONS PANEL CUTOUT:
240.0 mm x 181.1 mm x 41.7 mm (9.4” x 7.1” x 1.6”) 220 mm x 160 mm (8.7” x 6.3”)
Web: www.deepseausa.com
DEEP SEA ELECTRONICS PLC
DSEE800 Operator Manual

Document Number: 057-202


Author: Ashley Senior

DSEE800 Operator Manual ISSUE 2


DSEE800 Operator Manual

DEEP SEA ELECTRONICS PLC


Highfield House
Hunmanby
North Yorkshire
YO14 0PH
ENGLAND

Sales Tel: +44 (0) 1723 890099


Sales Fax: +44 (0) 1723 893303

E-mail: sales@deepseaplc.com
Website: www.deepseaplc.com

DSEE800 Operator Manual

© Deep Sea Electronics Plc


All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written permission
of the copyright holder except in accordance with the provisions of the Copyright, Designs and
Patents Act 1988.
Applications for the copyright holder’s written permission to reproduce any part of this publication
should be addressed to Deep Sea Electronics Plc at the address above.

The DSE logo is a UK registered trademarks of Deep Sea Electronics PLC.

Any reference to trademarked product names used within this publication is owned by their
respective companies.

Deep Sea Electronics Plc reserves the right to change the contents of this document without prior
notice.

Amendments List

Minimum Module Minimum Configuration


Issue Comments
Version Required Suite Version Required
1 Initial release V 1.0.0 2013.21 V 1.93.3
Updated for V1.2.12, and Tier IV engine DPF
parameters added.
2 V 1.2.12 2015.15 V1.242.5
FPE and Running Configuration Editor edited to
match the latest updates in the controller.

Typeface: The typeface used in this document is Arial. Care should be taken not to mistake the upper case letter I with the numeral 1. The
numeral 1 has a top serif to avoid this confusion.

Clarification of notation used within this publication.

NOTE Highlights an essential element of a procedure to ensure correctness.

Indicates a procedure or practice, which, if not strictly observed, could


CAUTION! result in damage or destruction of equipment.
Indicates a procedure or practice, which could result in injury to
WARNING! personnel or loss of life if not followed correctly.

2
DSEE800 Operator Manual

TABLE OF CONTENTS

Section Page
1 BIBLIOGRAPHY .............................................................................................. 6
1.1 INSTALLATION INSTRUCTIONS .................................................................................. 6
1.2 TRAINING GUIDES ........................................................................................................ 6
1.3 MANUALS ...................................................................................................................... 6
2 INTRODUCTION .............................................................................................. 7
3 SPECIFICATION .............................................................................................. 8
3.1 SHORT NAMES.............................................................................................................. 8
3.2 OPERATING TEMPERATURE ....................................................................................... 8
3.3 TERMINAL SPECIFICATION ......................................................................................... 9
3.4 POWER SUPPLY REQUIREMENTS .............................................................................. 9
3.4.1 MODULE SUPPLY INSTRUMENTATION DISPLAY ................................................ 9
3.5 INPUTS......................................................................................................................... 10
3.5.1 DIGITAL INPUTS ................................................................................................... 10
3.5.2 RATIOMETRIC INPUTS......................................................................................... 10
3.5.2.1 DIGITAL INPUT CONFIGURATION ................................................................ 10
3.5.2.2 RESISTIVE INPUT CONFIGURATION ........................................................... 10
3.5.2.3 0-10V INPUT CONFIGURATION .................................................................... 11
3.5.2.4 4-20MA INPUT CONFIGURATION................................................................. 11
3.5.3 CHARGE FAIL INPUT ............................................................................................ 11
3.5.4 PULSE PICKUP ..................................................................................................... 12
3.6 OUTPUTS..................................................................................................................... 12
3.6.1 DC OUTPUTS A & B (FUEL & START) .................................................................. 12
3.6.2 CONFIGURABLE VOLT-FREE OUTPUTS C & D .................................................. 12
3.6.3 CONFIGURABLE DC OUTPUTS E, F, G & H ........................................................ 12
3.6.4 CONFIGURABLE PWM OUTPUTS I, J, K & L ....................................................... 13
3.6.4.1 PWM OUTPUT CONFIGURATION ................................................................. 13
3.6.4.2 DC OUTPUT CONFIGURATION ..................................................................... 13
3.6.5 GOVERNOR CONTROL OUTPUT ......................................................................... 13
3.7 COMMUNICATION PORTS .......................................................................................... 14
3.8 COMMUNICATION PORT USAGE .............................................................................. 15
3.8.1 USB CONNECTION ............................................................................................... 15
3.8.1.1 USB SLAVE PORT (CONFIGURATION) ......................................................... 15
3.8.1.2 USB HOST PORT (USB STORAGE DEVICE CONNECTION) ........................ 15
3.8.2 RS232 PORT ......................................................................................................... 16
3.8.2.1 RECOMMENDED PC RS232 SERIAL PORT ADD-ONS ................................. 17
3.8.2.2 RECOMMENDED EXTERNAL MODEMS ....................................................... 17
3.8.2.3 RS485 PORT .................................................................................................. 18
3.8.2.4 RECOMMENDED PC RS485 SERIAL PORT ADD-ONS ................................. 19
3.8.3 ETHERNET PORT ................................................................................................. 20
3.8.3.1 DIRECT PC CONNECTION ............................................................................ 21
3.8.3.2 CONNECTION TO BASIC ETHERNET ........................................................... 22
3.8.3.3 CONNECTION TO COMPANY INFRASTRUCTURE ETHERNET ................... 23
3.8.3.4 CONNECTION TO THE INTERNET ................................................................ 24
3.8.3.5 FIREWALL CONFIGURATION FOR INTERNET ACCESS ............................. 25
3.8.4 CAN PORT ........................................................................................................... 26
3.8.5 DSENET® (EXPANSION MODULES) ................................................................... 27
3.9 SOUNDER .................................................................................................................... 28
3.9.1 ADDING AN EXTERNAL SOUNDER ..................................................................... 28
3.10 ACCUMULATED INSTRUMENTATION .................................................................... 28
3.11 DIMENSIONS AND MOUNTING ............................................................................... 29
3.11.1 DIMENSIONS ........................................................................................................ 29
3.11.2 PANEL CUTOUT.................................................................................................... 29
3.11.3 WEIGHT ................................................................................................................ 29

3
DSEE800 Operator Manual

3.11.4 FIXING CLIPS ........................................................................................................ 30


3.11.5 CABLE TIE FIXING POINTS .................................................................................. 31
3.11.6 SILICON SEALING GASKET ................................................................................. 31
3.11.7 APPLICABLE STANDARDS ................................................................................... 32
3.11.8 ENCLOSURE CLASSIFICATIONS ......................................................................... 33
3.11.8.1 IP CLASSIFICATIONS .................................................................................... 33
3.11.8.2 NEMA CLASSIFICATIONS ............................................................................. 34
4 INSTALLATION ............................................................................................. 35
4.1 TERMINAL DESCRIPTION .......................................................................................... 36
4.1.1 DC SUPPLIES, E-STOP INPUT, DC OUTPUTS & CHARGE FAIL INPUT ............. 36
4.1.2 PWM OUTPUTS & SUPPLY .................................................................................. 37
4.1.3 PULSE PICKUP, CAN, DSENET, MSC & GOVERNOR ......................................... 38
4.1.4 VOLT-FREE OUTPUTS C & D ............................................................................... 39
4.1.5 RATIOMETRIC INPUTS A TO I ............................................................................. 39
4.1.6 RATIOMETRIC INPUTS J TO L ............................................................................. 40
4.1.7 DIGITAL INPUTS A TO K ...................................................................................... 40
4.1.8 USB SLAVE (PC CONFIGURATION) CONNECTOR ............................................. 41
4.1.9 USB HOST (DATA LOGGING) CONNECTOR ....................................................... 41
4.1.10 RS232 CONNECTOR ............................................................................................ 42
4.1.11 RS485 CONNECTOR ............................................................................................ 43
4.1.12 ETHERNET CONNECTOR .................................................................................... 44
4.2 TYPICAL WIRING DIAGRAM ....................................................................................... 45
4.2.1 DSEE800 TYPICAL WIRING DIAGRAM ................................................................ 46
4.3 EARTH SYSTEMS........................................................................................................ 47
4.3.1 NEGATIVE EARTH ................................................................................................ 47
4.3.2 POSITIVE EARTH ................................................................................................. 47
4.3.3 FLOATING EARTH ................................................................................................ 47
4.4 TYPICAL ARRANGEMENT OF DSENET® .................................................................. 48
5 DESCRIPTION OF CONTROLS .................................................................... 49
5.1 CONTROL PUSH-BUTTONS ....................................................................................... 50
5.2 VIEWING THE INSTRUMENT PAGES ......................................................................... 53
5.2.1 STATUS ................................................................................................................. 54
5.2.1.1 ENGINE LOCKED OUT .................................................................................. 54
5.2.2 ENGINE ................................................................................................................. 55
5.2.3 RATIOMETRIC INPUTS......................................................................................... 55
5.2.4 ALARMS ................................................................................................................ 56
5.2.4.1 CAN ERROR MESSAGES .............................................................................. 56
5.2.5 EVENT LOG .......................................................................................................... 57
5.2.6 SERIAL PORT ....................................................................................................... 58
5.2.6.1 RS232 SERIAL PORT ..................................................................................... 58
5.2.6.2 RS485 SERIAL PORT ..................................................................................... 62
5.2.7 ABOUT .................................................................................................................. 63
5.2.7.1 MODULE INFORMATION ............................................................................... 63
5.2.7.2 ETHERNET ..................................................................................................... 64
5.2.7.3 DATA LOGGING ............................................................................................. 65
5.2.7.4 LCD ................................................................................................................. 66
5.3 USER CONFIGURABLE INDICATORS ........................................................................ 67
6 OPERATION .................................................................................................. 68
6.1 QUICKSTART GUIDE .................................................................................................. 68
6.1.1 STARTING THE ENGINE ...................................................................................... 68
6.1.2 STOPPING THE ENGINE ...................................................................................... 69
6.2 OFF MODE ................................................................................................................... 70
6.3 MANUAL MODE ........................................................................................................... 71
6.3.1 STARTING SEQUENCE ........................................................................................ 71
6.3.2 ENGINE RUNNING ................................................................................................ 72
6.3.3 STOPPING SEQUENCE ........................................................................................ 72
6.4 AUTOMATIC MODE .................................................................................................... 73

4
DSEE800 Operator Manual

6.4.1 WAITING IN AUTO MODE..................................................................................... 73


6.4.2 STARTING SEQUENCE ........................................................................................ 73
6.4.3 ENGINE RUNNING ................................................................................................ 74
6.4.4 STOPPING SEQUENCE ........................................................................................ 74
6.5 STOP/RESET MODE.................................................................................................... 75
6.6 SCHEDULER ................................................................................................................ 76
6.6.1 OFF MODE ............................................................................................................ 76
6.6.2 MANUAL MODE..................................................................................................... 76
6.6.3 AUTO MODE ......................................................................................................... 76
6.6.4 STOP/RESET MODE ............................................................................................. 76
7 PROTECTIONS ............................................................................................. 77
7.1 CAN ERROR MESSAGES ............................................................................................ 77
7.2 PROTECTIONS DISABLED ......................................................................................... 78
7.2.1 INDICATION AND WARNING ALARMS................................................................. 78
7.2.2 SHUTDOWN AND CONTROLLED SHUTDOWN ALARMS.................................... 78
7.3 INDICATIONS ............................................................................................................... 79
7.4 WARNING ALARMS ..................................................................................................... 80
7.5 CONTROLLED SHUTDOWN ALARMS ........................................................................ 82
7.6 SHUTDOWN ALARMS ................................................................................................. 84
7.7 MAINTENANCE ALARM .............................................................................................. 86

8 FRONT PANEL CONFIGURATION ............................................................... 87


8.1 MAIN CONFIGURATION EDITOR ................................................................................ 88
8.1.1 ACESSING THE MAIN CONFIGURATION EDITOR .............................................. 88
8.1.2 ENTERING PIN...................................................................................................... 88
8.1.3 EDITING A PARAMETER ...................................................................................... 89
8.1.4 EXITING THE MAIN CONFIGURATION EDITOR .................................................. 89
8.1.5 AVAILABLE PARAMETERS TO BE EDITED ......................................................... 90
8.2 ‘RUNNING’ CONFIGURATION EDITOR ...................................................................... 92
8.2.1 ACESSING THE ‘RUNNING’ CONFIGURATION EDITOR ..................................... 92
8.2.2 ENTERING PIN...................................................................................................... 92
8.2.3 EDITING A PARAMETER ...................................................................................... 92
8.2.4 EXITING THE ‘RUNNING’ CONFIGURATION EDITOR ......................................... 93
8.2.5 AVAILABLE PARAMETERS TO BE EDITED ......................................................... 93
9 COMMISSIONING .......................................................................................... 94
10 FAULT FINDING ......................................................................................... 95
10.1 STARTING ................................................................................................................ 95
10.2 LOADING .................................................................................................................. 95
10.3 ALARMS ................................................................................................................... 96
10.4 COMMUNICATIONS ................................................................................................. 96
10.5 MISCELLANEOUS .................................................................................................... 96
11 MAINTENANCE, SPARES, REPAIR AND SERVICING ............................. 97
11.1 PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE ............................ 97
11.1.1 INDIVIDUAL PLUGS .............................................................................................. 97
11.2 PURCHASING ADDITIONAL FIXING CLIPS FROM DSE......................................... 97
11.3 PURCHASING ADDITIONAL SEALING GASKET FROM DSE................................. 97

12 WARRANTY................................................................................................ 98
13 DISPOSAL .................................................................................................. 98
13.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT)........................... 98

5
Bibliography

1 BIBLIOGRAPHY
This document refers to and is referred to by the following DSE publications which can be obtained
from the DSE website: www.deepseaplc.com

1.1 INSTALLATION INSTRUCTIONS


Installation instructions are supplied with the product in the box and are intended as a ‘quick start’
guide only.

DSE Part Description


053-090 DSEE800 Installation Instructions

1.2 TRAINING GUIDES


Training Guides are produced to give ‘handout’ sheets on specific subjects during training sessions

DSE Part Description


056-029 Smoke Limiting
056-030 Module PIN Codes

1.3 MANUALS
Product manuals are downloaded from the DSE website: www.deepseaplc.com

DSE Part Description


057-004 Electronic Engines and DSE Wiring Guide
057-203 DSEE800 Configuration Suite PC Software Manual

6
Introduction

2 INTRODUCTION
This document details the installation and operation requirements of the DSEE800 module, part of
the DSEGenset® range of products.

The manual forms part of the product and should be kept for the entire life of the product. If the
product is passed or supplied to another party, ensure that this document is passed to them for
reference purposes.
This is not a controlled document. You will not be automatically informed of updates. Any future
updates of this document will be included on the DSE website at www.deepseaplc.com

The DSEExxx series is designed to provide differing levels of functionality across a common
platform. This allows the engine OEM greater flexibility in the choice of controller to use for a specific
application.

The DSEE800 module has been designed to allow the operator to start and stop the engine, control
engine speed manually or automatically and if required, transfer the load to engine either manually or
automatically.

The user also has the facility to view the system operating parameters via the LCD display.

The DSEE800 module monitors the engine, indicating the operational status and fault conditions,
automatically shutting down the engine and giving a true first up fault condition of an engine failure
by the LCD display.

The powerful ARM microprocessor contained within the module allows for incorporation of a range of
complex features:

• Icon based LCD display


• USB Communications
• Engine parameter monitoring.
• Fully configurable inputs for use as alarms or a range of different functions.
• Engine ECU interface to electronic engines.

Using a PC and the DSE Configuration Suite software allows alteration of selected operational
sequences, timers, alarms and operational sequences. Additionally, the module’s integral front panel
configuration editor allows adjustment of this information.

A robust plastic case designed for front panel mounting houses the module. Connections are via
locking plug and sockets.

Access to critical operational sequences and timers for use by qualified engineers, can be protected
by a security code. Module access can also be protected by PIN code. Selected parameters can be
changed from the module’s front panel.

The module is housed in a robust plastic case suitable for panel mounting. Connections to the
module are via locking plug and sockets.

7
Specification

3 SPECIFICATION
3.1 SHORT NAMES

Short Name Description


DSEE000, DSEExxx All modules in the DSEExxx range.
DSEE800 DSEE800 module/controller

3.2 OPERATING TEMPERATURE

Module Description
DSEE800 -30ºC to +70ºC (-40ºC to +70ºC when display heater in use)

8
Specification

3.3 TERMINAL SPECIFICATION

NOTE: For purchasing additional connector plugs from DSE, please see the section
entitled Maintenance, Spares, Repair and Servicing elsewhere in this document.

Two part connector.


• Male part fitted to
module
• Female part supplied in
Connection Type
module packing case -
Screw terminal, rising
clamp, no internal Example showing cable entry and screw
spring. terminals of a 10 way connector
Minimum Cable Size 0.5 mm² (AWG 24)
Maximum Cable Size 2.5 mm² (AWG 10)

3.4 POWER SUPPLY REQUIREMENTS

Minimum Supply Voltage 5 V continuous


Able to survive 0 V for 100 ms providing the supply was at least 10 V
Cranking Dropouts
before the dropout and recovers to 5 V afterwards.
Maximum Supply Voltage 35 V continuous (60 V protection)
Reverse Polarity Protection -35 V continuous
510 mA at 12 V
Maximum Operating Current
238 mA at 24 V
226 mA at 12 V
Maximum Standby Current
107 mA at 24 V
Maximum Current When In 180 mA at 12 V
Off Mode 86 mA at 24 V

3.4.1 MODULE SUPPLY INSTRUMENTATION DISPLAY

Range 0 V-70 V DC (note Maximum continuous operating voltage of 35 V DC)


Resolution 0.1 V
Accuracy 1% full scale (±0.7 V)

9
Specification

3.5 INPUTS

3.5.1 DIGITAL INPUTS

11 configurable digital inputs


Number
(23 when ratiometric inputs are configured as digital inputs)
Configuration Negative or positive switching activation via PC Software
When configured to negative switching, connect the input terminal
to the plant supply negative terminal
Switching Activation
When configured to positive switching, connect the input terminal to
a positive source with respect to the plant supply negative terminal
When configured to negative switching, below 4 V guarantees an
active condition
Level Threshold
When configured to positive switching, above 5.0 V guarantees an
active condition
Maximum Input Voltage +60 V DC with respect to plant supply negative
Minimum Input Voltage -24 V DC with respect to plant supply negative
Contact Wetting Current 6 mA typical
12 V typical when configured to negative switching
Open Circuit Voltage
0 V typical when configured to positive switching

3.5.2 RATIOMETRIC INPUTS

3.5.2.1 DIGITAL INPUT CONFIGURATION

Number 12 configurable ratiometric inputs


Negative Switching Activation Connect the input terminal to the plant supply negative terminal
Low Level Threshold 2.1 V minimum
High Level Threshold 6.6 V maximum
Maximum Input Voltage +60 V DC with respect to plant supply negative
Minimum Input Voltage -24 V DC with respect to plant supply negative
Contact Wetting Current 6 mA typical
Open Circuit Voltage 12 V typical

3.5.2.2 RESISTIVE INPUT CONFIGURATION

Number 12 configurable ratiometric inputs


Resistance measurement by measuring voltage across sensor with
Measurement Type
a fixed current applied
Arrangement Differential resistance measurement input
Measurement Current 11 mA ±10%
Full Scale 480 Ω
Over Range / Fail 540 Ω
Resolution 1%
Accuracy +/-2% of full scale resistance (±9.6 Ω) excluding transducer error
Max Common Mode Voltage ±2 V
0% to 250%, -200 °C to 1300 °C (-328 °F to 2372 °F) or
Display Range 0 bar to 17.2 bar (0 PSI to 250 PSI) subject to limits of the sensor
and sensor configuration

10
Specification

3.5.2.3 0-10V INPUT CONFIGURATION

Number 12 configurable ratiometric inputs


Full Scale 0 V to 10 V
Resolution 1%
Accuracy +/-2% of full scale voltage (±0.2 V) excluding transducer error
Max Common Mode Voltage ±2 V
0% to 250%, -200 °C to 1300 °C (-328 °F to 2372 °F) or
Display Range 0 bar to 17.2 bar (0 PSI to 250 PSI) subject to limits of the sensor
and sensor configuration

3.5.2.4 4-20MA INPUT CONFIGURATION

Number 12 configurable ratiometric inputs


Full Scale 0 mA to 20 mA
Resolution 1%
Accuracy +/-2% of full scale resistance (±0.4 mA) excluding transducer error
Max Common Mode Voltage ±2 V
00% to 250%, -200 °C to 1300 °C (-328 °F to 2372 °F) or
Display Range 0 bar to 17.2 bar (0 PSI to 250 PSI) subject to limits of the sensor
and sensor configuration

3.5.3 CHARGE FAIL INPUT

Minimum Voltage 0V
Maximum Voltage 35 V (plant supply)
Resolution 0.2 V
Accuracy ±1% of max measured voltage
Excitation Active circuit constant power output
Output Power 2.5 W nominal at 12 V and 24 V
Current At 12V 210 mA
Current At 24V 105 mA

The charge fail input is actually a combined input and output. Whenever the engine is required to
run, the terminal provides excitation current to the charge alternator field winding.

When the charge alternator is correctly charging the battery, the voltage of the terminal is close to
the plant battery supply voltage. In a failed charge situation, the voltage of this terminal is pulled
down to a low voltage. It is this drop in voltage that triggers the charge failure alarm. The level at
which this operates and whether this triggers a warning or shutdown alarm is configurable using the
DSE Configuration Suite Software.

11
Specification

3.5.4 PULSE PICKUP

Type Differential input


Minimum Voltage 0.5 V RMS
Max Common Mode Voltage ±2 V
Clamped to ±70 V by transient suppressers, dissipation not to
Maximum Voltage
exceed 1 W.
Maximum Frequency 10,000 Hz
Resolution 6.25 RPM
Accuracy ±25 RPM
Pulse Per Revolution 0.1 to 500.0

NOTE: DSE stock pickup devices available in two body thread lengths:
DSE Part number 020-012 - Magnetic Pickup probe 5/8 UNF 2½” thread length
DSE Part number 020-013 - Magnetic Pickup probe 5/8 UNF 4” thread length

Magnetic Pickup devices can often be ‘shared’ between two or more devices. For example, one
device can often supply the signal to both the DSE module and the engine governor. The possibility
of this depends upon the amount of current that the magnetic pickup can supply.

3.6 OUTPUTS

3.6.1 DC OUTPUTS A & B (FUEL & START)

Arrangement Supplied from Emergency Stop terminal 3


Normally used as Fuel & Start outputs.
Type Fully configurable for other purposes if the module is configured to control an
electronic engine.
Rating 10 A resistive for 10 seconds, 5 A resistive continuous at plant supply.

3.6.2 CONFIGURABLE VOLT-FREE OUTPUTS C & D

Type Normally open


5 A at 35 V DC
Rating
8 A resistive at 250 V AC

3.6.3 CONFIGURABLE DC OUTPUTS E, F, G & H

Arrangement Supplied from DC supply terminal 2


Type Fully configurable
Rating 2 A resistive continuous at plant supply

12
Specification

3.6.4 CONFIGURABLE PWM OUTPUTS I, J, K & L

3.6.4.1 PWM OUTPUT CONFIGURATION

Number 4 configurable outputs


Arrangement Supplied from dedicated input supply
Average Current Rating 4A
Peak Current Rating 6A
Voltage Rating Dedicated input supply
Minimum Frequency 20 Hz
Maximum Frequency 250 Hz
Minimum Load Impedance 3 Ω at 12 V, 6 Ω at 24 V
Resolution 0.5% of range selection
Accuracy +/-1% of range selection

3.6.4.2 DC OUTPUT CONFIGURATION

Number 4 configurable outputs


Arrangement Supplied from dedicated input supply
Type Fully configurable
Rating 4 A resistive continuous at dedicated input supply

3.6.5 GOVERNOR CONTROL OUTPUT

Arrangement Supplied from DC supply terminal 2


Type Isolated DC output, voltage controlled
Voltage Range -5 V to +10 V DC
Max Common Mode Voltage ±1 kV
Resolution Less than 1 mV
Accuracy ± 5%
Minimum Load 500 Ω

13
Specification

3.7 COMMUNICATION PORTS

Type B USB 2.0


USB Slave Port For connection to PC running DSE Configuration Suite
Max distance 6 m (20 feet)
Type A USB 2.0
USB Host Port Capability to add a maximum of 16 GB USB storage device for
data recording only
RS232 and RS485 are both fitted but and provide independent
Serial Communication
operation
Non – isolated
Max Baud rate 115K baud subject to configuration
RS232 Serial Port
TX, RX, RTS, CTS, DSR, DTR, DCD
Male 9 way D type connector
Max distance 15 m (50 feet)
Isolated
Data connection 2 wire + common
Half Duplex
RS485 Serial Port Data direction control for Transmit (by s/w protocol)
Max Baud Rate 115K baud subject to configuration
External termination required (120 Ω)
Max common mode offset 70 V (on board protection transorb)
Max distance 1.2 km (¾ mile)
RJ45 Ethernet connection for TCP/IP
Auto detecting 10/100 Mbit Ethernet port
Ethernet Port
Auto MDIX to remove need for crossover cables
Max distance 100m (328 feet) between routers
Engine CAN Port
Standard implementation of ‘Slow mode’, up to 250K bits/s
Non-Isolated.
Internal Termination provided (120 Ω)
CAN Port Max distance 40 m (133 feet)

NOTE: For additional length, the DSE124 CAN Extender


is available. Please refer to DSE Publication: 057-116
DSE124 Operator Manual for more information.
Non-isolated
Data connection 2 wire + common
Half Duplex
DSENet (Expansion Comms) Data direction control for Transmit (by s/w protocol)
Port Baud Rate 115K
Internal termination fitted (120 Ω)
Max common mode offset ±5 V
Max distance 1.2 km (¾ mile)

14
Specification

3.8 COMMUNICATION PORT USAGE

3.8.1 USB CONNECTION

3.8.1.1 USB SLAVE PORT (CONFIGURATION)

The USB port is provided to give a simple means of connection between a PC and the controller.
Using the DSE Configuration Suite Software, the operator is then able to control the module, starting
or stopping the engine, selecting operating modes, etc.

Additionally, the various operating parameters (such as coolant temperature, oil pressure, etc.) of the
engine are available to be viewed or changed.

To connect a module to a PC by USB, the following items are required:

• DSEE800 Controller

• DSE Configuration Suite PC Software


(Supplied on configuration suite software CD or available
from www.deepseaplc.com).

• USB cable Type A to Type B.


(This is the same cable as often used between a PC and a
USB printer)

NOTE: DSE stock 2 m (6.5 feet) USB type A to type B cable, DSE Part Number: 016-125.
Alternatively they are purchased from any PC or IT store.

NOTE: The DC supply must be connected to the module for configuration by PC.

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

3.8.1.2 USB HOST PORT (USB STORAGE DEVICE CONNECTION)

USB Type A connection for an of external USB storage device of maximum 16 GB for
instrumentation data logging.

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

15
Specification

3.8.2 RS232 PORT

The RS232 port on the controller supports the Modbus RTU protocol and is for connection to a single
Modbus master device only.

The MODBUS register table for the controller is available upon request from the DSE Technical
Support Department.

RS232 is for short distance communication (max 15m) and is typically used to connect the controller
to a telephone or GSM modem for more remote communications.

The various operating parameters (such as coolant temperature, oil pressure, etc.) of the remote
engine are viewed or changed.

NOTE: For a single module to PC connection and distances up to 6 m (20 feet) the USB
connection method is more suitable and provides for a lower cost alternative to RS485 (which
is more suited to longer distance connections).

Many PCs are not fitted with an internal RS232 serial port. DSE DOES NOT recommend the use of
USB to RS232 convertors but can recommend PC add-ons to provide the computer with an RS232
port.

16
Specification

3.8.2.1 RECOMMENDED PC RS232 SERIAL PORT ADD-ONS

Remember to check these parts are suitable for your PC. Consult your PC supplier for further advice.

• Brainboxes PM143 PCMCIA RS232 card (for laptop PCs)

• Brainboxes VX-001 Express Card RS232 (for laptops and nettops PCs)

• Brainboxes UC246 PCI RS232 card (for desktop PCs)

• Brainboxes PX-246 PCI Express 1 Port RS232 1 x 9 Pin (for desktop


PCs)

Supplier:
Brainboxes
Tel: +44 (0)151 220 2500
Web: http://www.brainboxes.com
Email: Sales: sales@brainboxes.com

NOTE: DSE have no business tie to Brainboxes. Over many years, our own engineers
have used these products and are happy to recommend them.

3.8.2.2 RECOMMENDED EXTERNAL MODEMS

• Multitech Global Modem – MultiModem ZBA (PSTN)


DSE Part Number 020-252
(Contact DSE Sales for details of localisation kits for these modems)

• Sierra Fastrak Xtend GSM modem kit (PSU, Antenna and modem)*
DSE Part number 0830-001-01

NOTE: For GSM modems a SIM card is required, supplied by your GSM network provider:

For SMS only, a ‘normal’ voice SIM card is required. This enables the controller to send SMS
messages to designated mobile phones upon status and alarm conditions.

For a data connection to a PC running DSE Configuration Suite Software, a ‘special’ CSD
(Circuit Switched Data) SIM card is required that enables the modem to answer an incoming
data call. Many ‘pay as you go’ services do not provide a CSD (Circuit Switched Data) SIM
card.

17
Specification

3.8.2.3 RS485 PORT

The RS485 port on the controller supports the Modbus RTU protocol and is for connection to a single
Modbus master device only.

The DSE MODBUS register table for the controller is available upon request from the DSE Technical
Support Department.

RS485 is used for point-to-point cable connection of more than one device (maximum 32 devices)
and allows for connection to PCs, PLCs and Building Management Systems (to name just a few
devices).

One advantage of the RS485 interface is the large distance specification (1.2 km when using Belden
9841 (or equivalent) cable. This allows for a large distance between the module and a PC running the
DSE Configuration Suite software. The operator is then able to control the module, starting or
stopping the engine, selecting operating modes, etc.

The various operating parameters (such as coolant temperature, oil pressure, etc.) of the remote
engine are viewed or changed.

NOTE: For a single module to PC connection and distances up to 6 m (20 feet) the USB
connection method is more suitable and provides for a lower cost alternative to RS485 (which
is more suited to longer distance connections).

Many PCs are not fitted with an internal RS485 serial port. DSE DOES NOT recommend the use of
USB to RS485 convertors but can recommend PC add-ons to provide the computer with an
RS485port.

18
Specification

3.8.2.4 RECOMMENDED PC RS485 SERIAL PORT ADD-ONS

Remember to check these parts are suitable for your PC. Consult your PC supplier for further advice.

• Brainboxes PM154 PCMCIA RS485 card (for laptops PCs)


Set to ‘Half Duplex, Autogating” with ‘CTS True’ set to ‘enabled’

• Brainboxes VX-023 ExpressCard 1 Port RS422/485 (for laptops and


nettop PCs)

• Brainboxes UC320 PCI Velocity RS485 card (for desktop PCs)


Set to ‘Half Duplex, Autogating” with ‘CTS True’ set to ‘enabled’

• Brainboxes PX-324 PCI Express 1 Port RS422/485 (for desktop PCs)

Supplier:
Brainboxes
Tel: +44 (0)151 220 2500
Web: http://www.brainboxes.com
Email: Sales: sales@brainboxes.com

NOTE: DSE have no business tie to Brainboxes. Over many years, our own engineers
have used these products and are happy to recommend them.

19
Specification

3.8.3 ETHERNET PORT

The Ethernet port on the controller supports the Modbus TCP protocol and is for connection for up to
five Modbus master devices.

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

The DSE MODBUS register table for the controller is available upon request from the DSE Technical
Support Department.

Ethernet is used for point-to-point cable connection of more than one device and allows for
connection to PCs, PLCs and Building Management Systems (to name just a few devices).

One advantage of the Ethernet interface is the ability to interface into an existing LAN (Local Area
Network) connection for remote connection via an internet connection. This allows for a large
distance between the module and a PC running the DSE Configuration Suite software. The operator
is then able to control the module, starting or stopping the engine, selecting operating modes, etc.

The various operating parameters (such as coolant temperature, oil pressure, etc.) of the remote
engine are viewed or changed.

NOTE: For a single module to PC connection and distances up to 6 m (20 feet) the USB
connection method is more suitable and provides for a lower cost alternative to Ethernet
(which is more suited to longer distance connections).

NOTE: DSE stock 2 m (6.5 feet) Ethernet Cable, DSE Part Number: 016-137. Alternatively
they can be purchased from any PC or IT store.

20
Specification

3.8.3.1 DIRECT PC CONNECTION

Requirements
• Crossover Ethernet cable (see Below)
• PC with Ethernet port

Crossover
Network Cable

For the advanced


Crossover Cable Wiring Detail Engineer, a crossover
cable is a CAT5 cable
Two pairs crossed, two pairs uncrossed with one end terminated
10baseT/100baseT crossover as T568A and the other
end terminated as T568B.
Pin Connection 1 (T568A) Connection 2 (T568B)
white/green white/orange
1
stripe stripe
2 green solid orange solid
white/orange white/green
3
stripe stripe
4 blue solid blue solid
white/blue white/blue
5
stripe stripe
6 orange solid green solid
white/brown white/brown
7
stripe stripe
8 brown solid brown solid

NOTE: This cable can be purchased from any PC or IT store.

21
Specification

3.8.3.2 CONNECTION TO BASIC ETHERNET

Requirements
• Ethernet cable (see below)
• Working Ethernet (company or home network)
• PC with Ethernet port

Ethernet Cable

Ethernet Router
or ADSL Router

For the advanced


Ethernet Cable Wiring Detail
Engineer, this cable has
both ends terminated as
10baseT/100baseT
T568A or T568B.
Pin Connection 1 (T568A) Connection 2 (T568A)
white/green white/green
1
stripe stripe
2 green solid green solid
white/orange white/orange
3
stripe stripe
4 blue solid blue solid
white/blue white/blue
5
stripe stripe
6 orange solid orange solid
white/brown white/brown
7
stripe stripe
8 brown solid brown solid

NOTE: DSE stock 2 m (6.5 feet) Ethernet Cable, DSE Part Number: 016-137. Alternatively
they can be purchased from any PC or IT store.

22
Specification

3.8.3.3 CONNECTION TO COMPANY INFRASTRUCTURE ETHERNET

Requirements
• DSE module with the ability to connect to Ethernet
• Ethernet cable (see below)
• Working Ethernet (company or home network)
• PC with Ethernet port
PC Network
Ethernet Router Wall
or ADSL Router Connection
Sockets
Ethernet Cable

For the advanced


Ethernet Cable Wiring Detail Engineer, this cable has
both ends terminated as
10baseT/100baseT T568A or T568B.

Pin Connection 1 (T568A) Connection 2 (T568A)


white/green white/green
1
stripe stripe
2 green solid green solid
white/orange white/orange
3
stripe stripe
4 blue solid blue solid
white/blue white/blue
5
stripe stripe
6 orange solid orange solid
white/brown white/brown
7
stripe stripe
8 brown solid brown solid

NOTE: DSE stock 2 m (6.5 feet) Ethernet Cable, DSE Part Number: 016-137. Alternatively
they can be purchased from any PC or IT store.

23
Specification

3.8.3.4 CONNECTION TO THE INTERNET

Requirements
• Ethernet cable (see below)
• Working Ethernet (company or home network)
• Working Internet connection (ADSL or DSL recommended)

DSL or ADSL
Router
INTERNET Ethernet
Cable

The DSL/ADSL
router routes
external network
traffic
DSL or ADSL
Router

Optional ‘Local’
Site PC
PC Remote From
Generator Site

For the advanced


Ethernet Cable Wiring Detail Engineer, this cable has
both ends terminated as
10baseT/100baseT T568A or T568B.

Pin Connection 1 (T568A) Connection 2 (T568A)


white/green white/green
1
stripe stripe
2 green solid green solid
white/orange white/orange
3
stripe stripe
4 blue solid blue solid
white/blue white/blue
5
stripe stripe
6 orange solid orange solid
white/brown white/brown
7
stripe stripe
8 brown solid brown solid

NOTE: DSE stock 2 m (6.5 feet) Ethernet Cable, DSE Part Number: 016-137. Alternatively
they can be purchased from any PC or IT store.

24
Specification

3.8.3.5 FIREWALL CONFIGURATION FOR INTERNET ACCESS

As modem/routers differ enormously in their configuration, it is not possible for DSE to give a
complete guide to their use with the module. However it is possible to give a description of the
requirements in generic terms. For details of how to achieve the connection to your modem/router
you are referred to the supplier of your modem/router equipment.

The module makes its data available over Modbus TCP and as such communicates over the
Ethernet using a Port configured via the DSE Configuration Suite software.

You must configure your modem/router to allow inbound traffic on this port. For more information you
are referred to your WAN interface device (modem/router) manufacturer.

It is also important to note that if the port assigned (setting from software “Modbus Port Number”) is
already in use on the LAN, the module cannot be used and another port must be used.

Outgoing Firewall Rule

As the module makes its user interface available to standard web browsers, all communication uses
the chosen port. It is usual for a firewall to make the same port outgoing open for communication.

Incoming Traffic (Virtual Server)

Network Address and Port Translation (NAPT) allows a single device, such as the modem/router
gateway, to act as an agent between the Internet (or "public external network") and a local (or
"internal private") network. This means that only a single, unique IP address is required to represent
an entire group of computers.

For our application, this means that the WAN IP address of the modem/router is the IP address we
need to access the site from an external (internet) location.

When the requests reach the modem/router, we want this passed to a ‘virtual server’ for handling, in
our case this is the module.

Result: Traffic arriving from the WAN (internet) on port xxx is automatically sent to IP address set
within the configuration software on the LAN for handling.

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

25
Specification

3.8.4 CAN PORT

Modules are fitted with the CAN interface as standard and are capable of
receiving engine data from engine CAN controllers compliant with the
CAN standard.
CAN enabled engine controllers monitor the engine’s operating
parameters such as engine speed, oil pressure, engine temperature
(among others) in order to closely monitor and control the engine. The industry standard
communications interface (CAN) transports data gathered by the engine controller interface. This
allows engine controllers to access these engine parameters with no physical connection to the
sensor device.

NOTE: For further details on connection to electronic engines, refer to DSE Publication:
057-004 Electronic Engines And DSE Wiring

26
Specification

3.8.5 DSENET® (EXPANSION MODULES)

DSENet® is the interconnection cable between the host controller and the expansion module(s) and
must not be connect to any device other than DSE equipment designed for connection to the
DSENet®

Cable Type Two core screened and shielded twisted pair


120 Ω
Cable Characteristics
Low capacitance
Belden 9841
Recommended Cable
Belden 9271
1200 m (¾ mile) when using Belden 9841 or direct equivalent.
Maximum Cable Length
600 m (656 yards) when using Belden 9271 or direct equivalent.
DSENet® Topology “Daisy Chain” Bus with no stubs (spurs)
120 Ω. Fitted internally to host controller. Must be fitted externally to the
DSENet® Termination
‘last’ expansion module.
Total 20 devices made up of DSE2130 (up to 4), DSE2131 (up to 4),
DSE2133 (up to 4), DSE2152 (up to 4), DSE2157 (up to 10), DSE2548
(up to 10)

This gives the possibility of :


Maximum 32 additional 0-10 V or 4-20 mA outputs (DSE2152)
Maximum Expansion
Maximum 80 additional relay outputs (DSE2157)
Modules
Maximum 80 additional LED indicators
Maximum 24 additional RTD or thermocouple inputs (DSE2133).
Maximum 32 additional inputs (Can be configured as either digital, or
resistive when using DSE2130)
Maximum 40 additional ratiometric inputs (All can be configured as
either digital, resistive, 0-10 V or 4-20 mA when using DSE2131)

NOTE: As a termination resistor is internally fitted to the controller, the controller must
be the ‘first’ unit on the DSENet link. A termination resistor MUST be fitted to the ‘last’ unit on
the DSENet® link. For connection details, refer to section entitled Typical Wiring Diagram
elsewhere in this document.

NOTE: DSEE800 module does not support the DSE2510 or DSE2520 display modules.

27
Specification

3.9 SOUNDER
The module features an internal sounder to draw attention to warning, shutdown and Controlled
Shutdown alarms.

Sounder Level 64 db at 1 m

3.9.1 ADDING AN EXTERNAL SOUNDER

Should an external alarm or indicator be required, this can be achieved by using the DSE
Configuration Suite PC software to configure an auxiliary output for “Audible Alarm”, and by
configuring an auxiliary input for “Alarm Mute” (if required).

The audible alarm output activates and de-activates at the same time as the module’s internal
sounder. The Alarm mute input and internal Lamp Test / Alarm Mute button activate ‘in parallel’
with each other. Either signal mutes the internal sounder and audible alarm output.

Example of configuration to achieve external sounder with external alarm mute button:

3.10 ACCUMULATED INSTRUMENTATION

NOTE: When an accumulated instrumentation value exceeds the maximum number as


listed below, it resets and begins counting from zero again.

Maximum 99999 hrs 59 minutes


Engine Hours Run
(Approximately 11 years and 4 months)

Accumulated Power 999999 kWh / kVArh / kVAh

The number of logged Engine Hours and Number of Starts can be set/reset using the DSE
Configuration Suite PC software. Depending upon module configuration, this may have been PIN
locked by your engine supplier

28
Specification

3.11 DIMENSIONS AND MOUNTING

3.11.1 DIMENSIONS
240 mm x 181 mm x 42 mm
(9.4” x 7.1” x 1.6”)

3.11.2 PANEL CUTOUT


220 mm x 160 mm
(8.7” x 6.3”)

3.11.3 WEIGHT
0.7 kg
(1.4 lb)

29
Specification

3.11.4 FIXING CLIPS

The module is held into the panel fascia using the supplied fixing clips.
• Withdraw the fixing clip screw (turn anticlockwise) until only the pointed end is protruding
from the clip.
• Insert the three ‘prongs’ of the fixing clip into the slots in the side of the module case.
• Pull the fixing clip backwards (towards the back of the module) ensuring all three prongs of
the clip are inside their allotted slots.
• Turn the fixing clip screws clockwise until they make contact with the panel fascia.
• Turn the screws a little more to secure the module into the panel fascia. Care should be
taken not to over tighten the fixing clip screws.

Fixing Clip

Fixing Clip Fitted


To Module

NOTE: In conditions of excessive vibration, mount the module on suitable anti-vibration


mountings.

30
Specification

3.11.5 CABLE TIE FIXING POINTS

Integral cable tie fixing points are included on the rear of the module’s case to aid wiring. This
additionally provides strain relief to the cable loom by removing the weight of the loom from the
screw connectors, thus reducing the chance of future connection failures.

Care should be taken not to over tighten the cable tie (for instance with cable tie tools) to prevent the
risk of damage to the module case.

Cable Tie Fixing Point With Cable And Tie In Place

3.11.6 SILICON SEALING GASKET

NOTE: For purchasing an additional silicon gasket from DSE, please see the section
entitled Maintenance, Spares, Repair and Servicing elsewhere in this document.

The optional silicon gasket provides improved sealing between module and the panel fascia.
The gasket is fitted to the module before installation into the panel fascia.
Take care to ensure the gasket is correctly fitted to the module to maintain the integrity of the seal.

Sealing Gasket Gasket Fitted


To Module

31
Specification

3.11.7 APPLICABLE STANDARDS

BS 4884-1 This document conforms to BS4884-1 1992 Specification for


presentation of essential information.
BS 4884-2 This document conforms to BS4884-2 1993 Guide to content
BS 4884-3 This document conforms to BS4884-3 1993 Guide to presentation
BS EN 60068-2-1 -30 °C (-22 °F)
(Minimum temperature) (-40ºC (-40 °F) when display heater in use)
BS EN 60068-2-2
+70 °C (158 °F)
(Maximum temperature)
BS EN 60950 Safety of information technology equipment, including electrical
business equipment
BS EN 61000-6-2 EMC Generic Immunity Standard (Industrial)
BS EN 61000-6-4 EMC Generic Emission Standard (Industrial)
BS EN 60529 IP65 (front of module when installed into the control panel with the
(Degrees of protection optional sealing gasket)
provided by enclosures) IP42 (front of module when installed into the control panel WITHOUT
being sealed to the panel)
UL508 12 (Front of module when installed into the control panel with the
NEMA rating optional sealing gasket).
(Approximate) 2 (Front of module when installed into the control panel WITHOUT being
sealed to the panel)
IEEE C37.2 Under the scope of IEEE 37.2, function numbers can also be used to
(Standard Electrical represent functions in microprocessor devices and software programs.
Power System Device The controller is device number 11L-8000 (Multifunction device
Function Numbers and protecting Line (engine) –module).
Contact Designations)
As the module is configurable by the engine OEM, the functions covered
by the module vary. Under the module’s factory configuration, the device
numbers included within the module are :

2 – Time Delay Starting Or Closing Relay


5 – Stopping Device
6 – Starting Circuit Breaker
11 – Multifunction Device
12 – Overspeed Device
14 – Underspeed Device
18 – Accelerating or Decelerating Device
19 – Starting-to-running transition contactor
26 – Apparatus Thermal Device
27DC – DC Undervoltage Relay
29 – Isolating Contactor Or Switch
30 – Annunciator Relay
54 – Turning Gear Engaging Device
59DC – DC Overvoltage Relay
62 – Time Delay Stopping Or Opening Relay
63 – Pressure Switch
71 – Level Switch
74 – Alarm Relay
83 – Automatic Selective Control Or Transfer Relay
86 – Lockout Relay

In line with our policy of continual development, Deep Sea Electronics, reserve the right to change
specification without notice.

32
Specification

3.11.8 ENCLOSURE CLASSIFICATIONS

3.11.8.1 IP CLASSIFICATIONS

The modules specification under BS EN 60529 Degrees of protection provided by enclosures

IP65 (Front of module when module is installed into the control panel with the optional sealing gasket).
IP42 (Front of module when module is installed into the control panel WITHOUT being sealed to the panel)

First Digit Second Digit


Protection against contact and ingress of solid objects Protection against ingress of water

0 No protection 0 No protection

1 Protected against ingress solid objects with a diameter 1 Protection against dripping water falling vertically. No
of more than 50 mm. No protection against deliberate harmful effect must be produced (vertically falling drops).
access, e.g. with a hand, but large surfaces of the body
are prevented from approach.

2 Protected against penetration by solid objects with a 2 Protection against dripping water falling vertically. There
diameter of more than 12 mm. Fingers or similar objects must be no harmful effect when the equipment
prevented from approach. (enclosure) is tilted at an angle up to 15° from it s normal
position (drops falling at an angle).

3 Protected against ingress of solid objects with a 3 Protection against water falling at any angle up to 60°
diameter of more than 2.5 mm. Tools, wires etc. with a from the vertical. There must be no harmful effect (spray
thickness of more than 2.5 mm are prevented from water).
approach.

4 Protected against ingress of solid objects with a 4 Protection against water splashed against the equipment
diameter of more than 1 mm. Tools, wires etc. with a (enclosure) from any direction. There must be no harmful
thickness of more than 1 mm are prevented from effect (splashing water).
approach.

5 Protected against harmful dust deposits. Ingress of dust 5 Protection against water projected from a nozzle against
is not totally prevented but the dust must not enter in the equipment (enclosure) from any direction. There must
sufficient quantity to interface with satisfactory operation be no harmful effect (water jet).
of the equipment. Complete protection against contact.

6 Protection against ingress of dust (dust tight). Complete 6 Protection against heavy seas or powerful water jets.
protection against contact. Water must not enter the equipment (enclosure) in
harmful quantities (splashing over).

33
Specification

3.11.8.2 NEMA CLASSIFICATIONS

THE MODULES NEMA RATING (APPROXIMATE)

12 (Front of module when module is installed into the control panel with the optional sealing gasket).
2 (Front of module when module is installed into the control panel WITHOUT being sealed to the panel)

NOTE: There is no direct equivalence between IP / NEMA ratings. IP figures shown are
approximate only.

1 Provides a degree of protection against contact with the enclosure equipment and against a limited amount of falling dirt.

IP30

2 Provides a degree of protection against limited amounts of falling water and dirt.

IP31

3 Provides a degree of protection against windblown dust, rain and sleet; undamaged by the formation of ice on the
enclosure.
IP64

3R Provides a degree of protection against rain and sleet:; undamaged by the formation of ice on the enclosure.

IP32

4 (X) Provides a degree of protection against splashing water, windblown dust and rain, hose directed water; undamaged by the
formation of ice on the enclosure. (Resist corrosion).
IP66

12/12K Provides a degree of protection against dust, falling dirt and dripping non corrosive liquids.

IP65

13 Provides a degree of protection against dust and spraying of water, oil and non corrosive coolants.

IP65

34
Installation

4 INSTALLATION
The module is designed to be mounted on the panel fascia. To aid user connection, icons are used
on the rear of the module to help identify terminal functions. An example of this is shown below.

NOTE: Availability of some terminals depends upon module version. Full details are given
in the section entitled Terminal Description elsewhere in this manual.

NOTE: For dimension and mounting details, see the section entitled Specification,
Dimension and Mounting elsewhere in this document.

Terminals RS232 Serial Terminals Terminals Terminals Ethernet


32-45 Port Number 36-47 48-51 52-62 Port

RS485 Terminals Terminals Terminals USB Host Port USB Slave Port
Port 1-11 12-17 18-31 (Data Logging) (PC Configuration)

35
Installation

4.1 TERMINAL DESCRIPTION

4.1.1 DC SUPPLIES, E-STOP INPUT, DC OUTPUTS & CHARGE FAIL INPUT

Pin Cable
Description Notes
No Size
DC Plant Supply Input 2.5 mm²
1 Connect to ground where applicable
(Negative) AWG 13
DC Plant Supply Input 2.5 mm²
2 Supplies the module and DC Outputs A, B, E, F, G & H
(Positive) AWG 13
2.5 mm²
3 Emergency Stop Input Plant Supply Positive. Also supplies DC Outputs A & B.
AWG 13
Plant Supply Positive from terminal 2.
2.5 mm²
4 DC Output A (FUEL) 10 A for 10 seconds, 5 A resistive continuous
AWG 13
Fixed as FUEL relay if electronic engine is not configured.
Plant Supply Positive from terminal 2.
2.5 mm²
5 DC Output B (START) 10 A for 10 seconds, 5 A resistive continuous
AWG 13
Fixed as START relay if electronic engine is not configured.
Do not connect to ground (battery negative).
2.5 mm²
6 Charge Fail / Excite If charge alternator is not fitted, leave this terminal
AWG 13
disconnected.
1.0 mm²
7 Display Heater Supply Supplies the module’s display heater only
AWG 18
1.0 mm²
8 Configurable DC Output E 2 A DC output from terminal 2
AWG 18
1.0 mm²
9 Configurable DC Output F 2 A DC output from terminal 2
AWG 18
1.0 mm²
10 Configurable DC Output G 2 A DC output from terminal 2
AWG 18
1.0 mm²
11 Configurable DC Output H 2 A DC output from terminal 2
AWG 18

NOTE: When the module is configured for operation with an electronic engine, FUEL and
START output requirements may be different. For further details on connection to electronic
engines, refer to DSE Publication: 057-004 Electronic Engines And DSE Wiring

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

36
Installation

4.1.2 PWM OUTPUTS & SUPPLY

Pin Cable
Description Notes
No Size
PWM Supply Input 1.0 mm²
12 Connect to ground where applicable
(Negative) AWG 18

PWM Supply Input 1.0 mm²


13 Supplies the module’s PWM Outputs I, J, K & L
(Positive) AWG 18
2.5 mm²
14 Configurable PWM Output I 4 A PWM output supplied from terminal 13.
AWG 13
2.5 mm²
15 Configurable PWM Output J 4 A PWM output supplied from terminal 13.
AWG 13
2.5 mm²
16 Configurable PWM Output K 4 A PWM output supplied from terminal 13.
AWG 13
2.5 mm²
17 Configurable PWM Output L 4 A PWM output supplied from terminal 13.
AWG 13

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

37
Installation

4.1.3 PULSE PICKUP, CAN, DSENET, MSC & GOVERNOR

Pin Cable
Description Notes
No Size
0.5 mm² Connect to magnetic pickup device or charge alternator
18 Pulse Pickup Positive
AWG 20 tachometer output
0.5 mm² Connect to magnetic pickup device or charge alternator
29 Pulse Pickup Negative
AWG 20 tachometer output

20 Pulse Pickup Screen Shield Connect to ground at one end only

0.5 mm²
21 CAN Port H Use only 120 Ω CAN and RS485 approved cable
AWG 20
0.5 mm²
22 CAN Port L Use only 120 Ω CAN and RS485 approved cable
AWG 20

23 CAN Port Screen Shield Use only 120 Ω CAN and RS485 approved cable

0.5 mm²
24 DSENet Expansion B Use only 120 Ω CAN and RS485 approved cable
AWG 20
0.5 mm²
25 DSENet Expansion A Use only 120 Ω CAN and RS485 approved cable
AWG 20

26 DSENet Expansion Screen Shield Use only 120 Ω CAN and RS485 approved cable

0.5 mm²
27 MSC H Use only 120 Ω CAN and RS485 approved cable
AWG 20
0.5 mm²
28 MSC L Use only 120 Ω CAN and RS485 approved cable
AWG 20

29 MSC Screen Shield Use only 120 Ω CAN and RS485 approved cable

0.5 mm²
30 Governor Output B Connect to voltage or wiper input of governor speed input
AWG 20
0.5 mm²
31 Governor Output A Connect to 0 V reference of governor speed input
AWG 20

NOTE: For further details on connection to electronic engines, refer to DSE Publication:
057-004 Electronic Engines And DSE Wiring Guide

NOTE: Screened 120 Ω impedance cable specified for use with CAN must be used for the
CAN link.
DSE stock and supply Belden cable 9841 which is a high quality 120 Ω impedance cable
suitable for CAN use (DSE part number 016-030)

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

38
Installation

4.1.4 VOLT-FREE OUTPUTS C & D

Pin Cable
Description Notes
No Size
32 Configurable 0.5 mm²
33 Normally Open Volt-Free Output C AWG 20

34 Configurable 0.5 mm²


35 Normally Open Volt-Free Output D AWG 20

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

4.1.5 RATIOMETRIC INPUTS A TO I

Pin Cable
Description Notes
No Size
Oil Pressure Input 0.5 mm²
36 Connect to oil pressure sensor
(Ratiometric Input A) AWG 20
0.5 mm²
37 Configurable Ratiometric Input B Connect to coolant temperature sensor
AWG 20
0.5 mm²
38 Configurable Ratiometric Input C Connect to fuel level sensor
AWG 20
0.5 mm²
39 Ratiometric Input A, B & C Common Return feed for ratiometric input A, B & C
AWG 20
0.5 mm²
40 Configurable Ratiometric Input D
AWG 20
0.5 mm²
41 Configurable Ratiometric Input E
AWG 20
0.5 mm²
42 Configurable Ratiometric Input F
AWG 20
0.5 mm²
43 Ratiometric Input D, E & F Common Return feed for ratiometric input D, E & F
AWG 20
0.5 mm²
44 Configurable Ratiometric Input G
AWG 20
0.5 mm²
45 Configurable Ratiometric Input H
AWG 20
0.5 mm²
46 Configurable Ratiometric Input I
AWG 20
0.5 mm²
47 Ratiometric Input G, H & I Common Return feed for ratiometric input G, H & I
AWG 20

NOTE: It is VERY important that terminal 39, 43 & 47 (sensor commons) are soundly
connected to an earth point on the ENGINE BLOCK when inputs are in use, not within the
control panel, and must be a sound electrical connection to the sensor bodies. This
connection MUST NOT be used to provide an earth connection for other terminals or devices.
The simplest way to achieve this is to run a SEPARATE earth connection from the system
earth star point, to terminals 39, 43 & 47 directly, and not use this earth for other connections.

NOTE: If you use PTFE insulating tape on the sensor thread when using earth return
sensors, ensure you do not insulate the entire thread, as this prevents the sensor body from
being earthed via the engine block.

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

39
Installation

4.1.6 RATIOMETRIC INPUTS J TO L

Pin Cable
Description Notes
No Size
0.5 mm²
48 Configurable Ratiometric Input J
AWG 20
0.5 mm²
49 Configurable Ratiometric Input K
AWG 20
0.5 mm²
50 Configurable Ratiometric Input L
AWG 20
0.5 mm²
51 Ratiometric Input J, K & L Common Return feed for ratiometric input J, K & L
AWG 20

NOTE: It is VERY important that terminal 51 (sensor common) is soundly connected to an


earth point on the ENGINE BLOCK when inputs are in use, not within the control panel, and
must be a sound electrical connection to the sensor bodies. This connection MUST NOT be
used to provide an earth connection for other terminals or devices. The simplest way to
achieve this is to run a SEPARATE earth connection from the system earth star point, to
terminal 51 directly, and not use this earth for other connections.

NOTE: If you use PTFE insulating tape on the sensor thread when using earth return
sensors, ensure you do not insulate the entire thread, as this prevents the sensor body from
being earthed via the engine block.

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

4.1.7 DIGITAL INPUTS A TO K

Pin Cable
Description Notes
No Size
0.5 mm²
52 Configurable Digital Input A
AWG 20
0.5 mm² Configurable as positive or negative switching in a group of three
53 Configurable Digital Input B
AWG 20 (A, B & C)
0.5 mm²
54 Configurable Digital Input C
AWG 20
0.5 mm²
55 Configurable Digital Input D
AWG 20
0.5 mm² Configurable as positive or negative switching in a group of three
56 Configurable Digital Input E
AWG 20 (D, E & F)
0.5 mm²
57 Configurable Digital Input F
AWG 20
0.5 mm²
58 Configurable Digital Input G
AWG 20
0.5 mm²
59 Configurable Digital Input H
AWG 20
0.5 mm² Configurable as positive or negative switching in a group of five
60 Configurable Digital Input I
AWG 20 (G, H, I, J & K)
0.5 mm²
61 Configurable Digital Input J
AWG 20
0.5 mm²
62 Configurable Digital Input K
AWG 20

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

40
Installation

4.1.8 USB SLAVE (PC CONFIGURATION) CONNECTOR

Cable
Description Notes
Size

Socket for connection to PC with DSE 0.5 mm² This is a standard USB type A
Configuration Suite Software AWG 20 to type B connector.

NOTE: The USB connection cable between the PC and the module must not be extended
beyond 6 m (20 feet). For distances over 6 m, it is possible to use a third party USB extender.
Typically, they extend USB up to 50 m (164 yards). The supply and support of this type of
equipment is outside the scope of Deep Sea Electronics PLC.

CAUTION!: Care must be taken not to overload the PCs USB system by connecting more
than the recommended number of USB devices to the PC. For further information, consult
your PC supplier.

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

4.1.9 USB HOST (DATA LOGGING) CONNECTOR

Storage
Description Notes
Size

Socket for connection to USB storage Maximum USB storage device must be formatted as FAT, not
device for data logging 16 GB FAT32.

NOTE: For further details on how to add and remove a USB storage device, refer to
section entitled Data Logging Pages elsewhere in this document.

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

41
Installation

4.1.10 RS232 CONNECTOR

Description Notes
Socket for connection to a modem or PC
Supports Modbus RTU protocol or external modem
with DSE Configuration Suite Software

View looking into the male connector on the module

PIN No Notes
1 Received Line Signal Detector (Data Carrier Detect)
2 Received Data
3 Transmit Data
4 Data Terminal Ready
5 Signal Ground
6 Data Set Ready
7 Request To Send
8 Clear To Send
9 Ring Indicator

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

42
Installation

4.1.11 RS485 CONNECTOR

Description Cable Notes


Socket for connection to PC with DSE Belden
Supports Modbus RTU protocol
Configuration Suite Software 9841

PIN No Notes
A (-) Connect to RXD- and TXD-
B (+) Connect to RXD+ and TXD+
SCR Signal Ground

NOTE: A 120 Ω termination resistor must be fitted across terminals A and B if the DSE
module is the first or last device on the R485 link.

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

43
Installation

4.1.12 ETHERNET CONNECTOR

Description Cable Notes


Socket for connection to PC or network Ethernet
Supports Modbus TCP protocol
with DSE Configuration Suite Software Cable

View looking into the female connector on the module

PIN No Notes
1 TXD+
2 TXD-
3 RXD+
4 Do not connect
5 Do not connect
6 RXD-
7 Do not connect
8 Do not connect

NOTE: For further details on how utilise an Ethernet connection, refer to section entitled
Communication Port Usage elsewhere in this document.

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

44
Installation

4.2 TYPICAL WIRING DIAGRAM


As every system has different requirements, these diagrams show only a TYPICAL system and do
not intend to show a complete system.

Engine manufacturers and panel builders may use these diagrams as a starting point; however, you
are referred to the completed system diagram provided by your system manufacturer for complete
wiring detail.

Further wiring suggestions are available in the following DSE publications, available at
www.deepseaplc.com to website members.

DSE Part Description


057-004 Electronic Engines and DSE Wiring

45
Installation

4.2.1 DSEE800 TYPICAL WIRING DIAGRAM

46
Installation

4.3 EARTH SYSTEMS

4.3.1 NEGATIVE EARTH

The typical wiring diagrams located within this document show connections for a negative earth
system (the battery negative connects to Earth)

4.3.2 POSITIVE EARTH

When using a DSE module with a Positive Earth System (the battery positive connects to Earth), the
following points must be followed:

• Follow the typical wiring diagram as normal for all sections EXCEPT the earth points
• All points shown as Earth on the typical wiring diagram should connect to BATTERY
NEGATIVE (not earth).

4.3.3 FLOATING EARTH

Where neither the battery positive nor battery negative terminals are connected to earth the following
points must to be followed

• Follow the typical wiring diagram as normal for all sections EXCEPT the earth points
• All points shown as Earth on the typical wiring diagram should connect to BATTERY
NEGATIVE (not earth).

47
Installation

4.4 TYPICAL ARRANGEMENT OF DSENET®


Twenty (20) devices can be connected to the DSENet®, made up of the following devices :

Device Maximum Number Supported


DSE2130 Input Expansion 4
DSE2131 Ratiometric Input Expansion 4
DSE2133 RTD/Thermocouple Intput Expansion 4
DSE2152 Analogue Output Expansion 4
DSE2157 Relay Output Expansion 10
DSE2548 LED Expansion 10

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

48
Description Of Controls

5 DESCRIPTION OF CONTROLS

NOTE: The following descriptions detail the sequences followed by a module containing
the standard ‘factory configuration’. Always refer to your configuration source for the exact
sequences and timers observed by any particular module in the field.

Control of the module is via push buttons mounted on the front of the module with Off Mode ,
Manual Mode , Auto Mode , Alarm Mute/Lamp Test , Start , Stop/Reset Mode ,
Increase Engine Speed and Decrease Engine Speed functions. For normal operation,
these are the only controls which need to be operated. Details of their operation are provided later in
this document.

CAUTION: The module may instruct an engine start event due to external influences.
Therefore, it is possible for the engine to start at any time without warning. Prior to
performing any maintenance on the system, it is recommended that steps are taken to remove
the battery and isolate supplies.

Menu Module
Navigation Display Four user
configurable
status
indication
LEDs

Decrease Increase
Engine Speed Engine Speed
(Manual Mode (Manual Mode
Only) Only)

Off Manual Auto Alarm Mute Start Stop /


Mode Mode Mode & Lamp Test Reset Mode

49
Description Of Controls

5.1 CONTROL PUSH-BUTTONS

Icon Description
Off Mode

This button is only active in the Stop/Reset Mode .

Pressing the Off Mode button reduces the module’s power consumption by
turning off the modules display.

Pressing the Off Mode button again to reawaken the module. The module
awakens in Stop/Reset Mode .

For further details, see section entitled ‘Operation’ elsewhere in this manual.

Manual Mode

This button places the module into its Manual Mode . Once in
Manual Mode , the module responds to the Start button to start the
engine. The module monitors the engine speed and once the configured value has
been met, the engine is automatically placed on load (‘Clutch Control’ becomes
active (if used)). The engine remains on load until Stop/Reset Mode or
Auto Mode are selected or the engine speed decreases below the configured
value.

Also in Manual Mode , the module responds to the


Increase Engine Speed and Decrease Engine Speed buttons after the
engine’s priming stage. The engine speed can be increased and decreased within
the boundaries configured in the module’s configuration.

For further details, see section entitled ‘Operation’ elsewhere in this manual.

Auto Mode

This button places the module into its Auto Mode . This mode allows the
module to control the function of the engine automatically. The module monitors
the remote start input and once a start request is made, the set is automatically
started and placed on load (‘Clutch Control’ becomes active (if used)).

Upon removal of the starting signal, the module removes the load from the engine
and shut the set down observing the stop delay timer and cooling timer as
necessary (‘Clutch Control’ become inactive (if used)). The module then waits for
next start event.

Also in Auto Mode , the module responds to the Increase Engine Speed
and Decrease Engine Speed buttons after the engine’s priming stage if the
module is configured automatic speed control is configured to ‘Fixed Speed’. The
engine speed can be increased and decreased within the boundaries configured in
the module’s configuration.

For further details, see section entitled ‘Operation’ elsewhere in this manual.

50
Description Of Controls

Icon Description
Alarm Mute / Lamp Test

This button de-activates the audible alarm output (if configured) and illuminates all
of the LEDs on the module’s facia.

Start

This button is only active in the Stop/Reset Mode and Manual Mode .

Pressing the Start button in Stop/Reset Mode powers the ECU but does
not start the engine. This can be used to check the status of the CAN
communication and to prime the fuel system.

Pressing the Start button in Manual Mode starts the engine.

For further details, see section entitled ‘Operation’ elsewhere in this manual.

Stop / Reset Mode

This button places the module into its Stop/Reset Mode . This clears any
alarm conditions for which the triggering criteria have been removed. If the engine
is running and the module is put into Stop/Reset Mode , the module
automatically instructs the engine to unload (‘Clutch Control’ become inactive (if
used). The fuel supply de-energises and the engine comes to a standstill. Should
any form of remote start signal be present while operating in this mode, a start
does not occur.

For further details, see section entitled ‘Operation’ elsewhere in this manual.

51
Description Of Controls

Icon Description
Decrease Engine Speed

This button is only active in the Auto Mode (if speed control is configured to
‘Fixed Speed’) or Manual Mode .

Pressing the Decrease Engine Speed button decreases the engine’s speed
within the configured boundaries.

For further details, see section entitled ‘Operation’ elsewhere in this manual.

Increase Engine Speed

This button is only active in the Auto Mode (if speed control is configured to
‘Fixed Speed’) or Manual Mode .

Pressing the Increase Engine Speed button increases the engine’s speed
within the configured boundaries.

For further details, see section entitled ‘Operation’ elsewhere in this manual.

Navigation Keys

Used for navigating the instrumentation, event log and configuration screens.

For further details, please see section entitled ‘Operation’ elsewhere in this
manual.

52
Description Of Controls

5.2 VIEWING THE INSTRUMENT PAGES


It is possible to scroll to display the different pages of information by repeatedly operating the

Next & Previous Page buttons. If you want to view one of the
instrument pages towards the end of
the list, it may be quicker to scroll left
through the pages rather than right!
Example

Further presses of the Next Page


Ratiometric
Status Engine Button returns the display to the Status
Inputs
page.

The complete order and contents of each information page are given in the following sections

Once selected, the page remains on the LCD display until the user selects a different page, or after
an extended period of inactivity (LCD Page Timer), the module reverts to the status display.

If no buttons are pressed upon entering an instrumentation page, the instruments displayed are
automatically subject to the setting of the LCD Scroll Timer.

The LCD Page and LCD Scroll timers are configurable using the DSE Configuration Suite Software
or by using the Front Panel Editor.

The screenshot shows the


factory settings for the timers,
taken from the DSE
Configuration Suite Software.

Alternatively, to scroll manually through all instruments on the currently selected page, press the

Instrumentation Scroll buttons. The ‘auto scroll’ is disabled.

If you want to view one of the


instruments towards the end of the list,
it may be quicker to scroll up through
the instruments rather than down!

To re-enable ‘auto scroll’ press the Instrumentation Scroll buttons to scroll to the ‘title’ of the
instrumentation page (ie Engine). A short time later (the duration of the LCD Scroll Timer), the
instrumentation display begins to auto scroll.

When scrolling manually, the display automatically returns to the Status page if no buttons are
pressed for the duration of the configurable LCD Page Timer.

If an alarm becomes active while viewing the status page, the display shows the Alarms page to draw
the operator’s attention to the alarm condition.

53
Description Of Controls

5.2.1 STATUS

This is the ‘home’ page, the page that is displayed when no other page has been selected, and the
page that is automatically displayed after a period of inactivity (LCD Page Timer) of the module
control buttons.

This page changes with the action of the controller, when the engine is running, that target speed is
be displayed.

Status 22:31 Factory setting of Status screen showing engine stopped...


Engine at Rest

Stop Mode

Safety on Delay 00:04 ...and engine running


Target speed is given as a % of the
full scale of the governor output.
Target Speed 30% E.g. 30% of 10 V (full scale) = 3 V

The contents of this display may vary depending upon configuration by the engine manufacturer or
supplier.

The display above is achieved with the factory settings, shown below in the DSE Configuration suite
software:

‘Stop Mode’ etc is


displayed on the
Home Page

With a summary of the


instrumentation shown
when the engine is running.

Other pages can be


configured to be shown,
automatically scrolling
when the set is running.

NOTE: The following sections detail instrumentation pages, accessible using the

Next & Previous Page buttons, regardless of what pages are configured to be displayed
on the ‘status’ screen.

5.2.1.1 ENGINE LOCKED OUT

Status 22:31 Engine Locked Out indicates that the engine cannot be started due
Engine Locked Out to an active Shutdown or Controlled Shutdown on the module.

Stop Mode Press the Next or Previous Page button to scroll to the
alarms page to investigate. Press the Stop/Reset Mode button
to clear the alarm, if the fault does not clear the fault is still active.

54
Description Of Controls

5.2.2 ENGINE

Contains instrumentation gathered about the engine itself, some of which may be obtained using the
CAN or other electronic engine link.

• Engine Speed
• Oil Pressure
• Coolant Temperature
• Engine Battery Volts
• Engine Run Time
• Engine Fuel Level
• Oil Temperature*
• Coolant Pressure*
• Inlet Temperature*
• Exhaust Temperature*
• Fuel Temperature*
• Turbo Pressure*
• Fuel Pressure*
• Fuel Consumption*
• Fuel Used*
• Fuel Level*
• Auxiliary Sensors (If fitted and configured)
• Engine Maintenance Due (If configured)
• Engine ECU Link*
• Tier 4 Engine Information*

NOTE*: For further details of support engine, refer to DSE Publication: 057-004
Electronic Engines and DSE Wiring Guide.

Depending upon configuration and instrument function, some of the instrumentation items may
include a tick icon beside them. This denotes a further function is available, for further details
refer to section entitled Operation elsewhere in this document.

Example:

The tick icon denotes that manual fuel


pump control is enabled in this system.

Press and hold the Tick button to start


the fuel transfer pump, release to stop the
pump. This is detailed further in the section
entitled ‘operation’ elsewhere in this document.

5.2.3 RATIOMETRIC INPUTS


Contains values of ratiometric inputs measured from the module’s ratiometric input terminals.

• Ratiometric Inputs A to L (Only appears if configured)

55
Description Of Controls

5.2.4 ALARMS

When an alarm is active, the Internal Audible Alarm sounds and the Common Alarm LED, if
configured, illuminates.
The audible alarm is silenced by pressing the Alarm Mute / Lamp Test button.

The LCD display jumps from the ‘Information page’ to display the Alarm Page

Number of active alarms. This is


alarm 1 of a total of 2 active alarms
1/2 Alarm
Low Oil Pressure The cause of alarm, e.g. Low Oil Pressure

Warning The type of alarm, e.g. Warning

The LCD displays multiple alarms such as “Coolant Temperature High”, “Emergency Stop” and “Low
Coolant Warning”. These automatically scroll in the order that they occurred.

In the event of an alarm, the LCD displays the appropriate text. If an additional alarm then occurs,
the module displays the appropriate text.

Example:

1/2 Alarm 2/2 Alarm


Low Oil Pressure Coolant Temperature High

Warning Shutdown

5.2.4.1 CAN ERROR MESSAGES

When connected to a suitable CAN engine, the controller displays alarm status messages from the
ECU.

1/1 Alarm
Type of alarm that is
ECU Amber triggered in the DSE
module, e.g. Warning
Warning

Press the Next Page button to access the list of current active Engine DTCs (Diagnostic
Trouble Codes) from the ECU.

Engine DTCs
The code is interpreted by the module and shows on the display as a
Water Level Low text message. Additionally, the manufacturer’s fault code is shown
below.
Xxx,xxx,xxx

NOTE: For details on these code meanings, refer to the ECU instructions provided by the
engine manufacturer, or contact the engine manufacturer for further assistance.

NOTE: For further details on operation of electronic engines, refer to


DSE Publication: 057-004 Electronic Engines And DSE Wiring Guide

56
Description Of Controls

5.2.5 EVENT LOG

The module maintains a log of past alarms and/or selected status changes.
The log size has been increased in the module over past module updates and is always subject to
change. At the time of writing, the modules log is capable of storing the last 250 log entries.

Under default factory settings, the event log is configured to include all possible options; however,
this is configurable by the system designer using the DSE Configuration Suite software.

Example showing the possible


configuration of the modules event
log (DSE Configuration Suite
Software). This also shows the
factory settings of the module.

When the event log is full, any subsequent event overwrites the oldest entry. Hence, the event log
always contains the most recent events. The module logs the event type, along with the date and
time (or engine running hours if configured to do so). If the module is configured and connected to a
modem, an SMS message is sent on any logged event.

To view the event log, repeatedly press the Next or Previous Page buttons until the LCD
screen displays the Event Log page.

1 Event
This is event 1
Oil Pressure Low
Shutdown
12 Sep 2007, 08:25:46

Press the Scroll Down button to view the next most recent event.

Continuing to press the Scroll Down button cycles through the past events after which, the
display shows the most recent alarm and the cycle begins again.

To exit the event log and return to viewing the instruments, press the Next or Previous Page
buttons to select the next instrumentation page.

57
Description Of Controls

5.2.6 SERIAL PORT

5.2.6.1 RS232 SERIAL PORT

This section is included to give information about the RS232 serial port and external modem (if
connected).

The items displayed on this page change depending upon configuration of the module. You are
referred to your system supplier for further details.

NOTE: Factory Default settings are for the RS232 port to be enabled with no modem
connected, operating at 19200 baud, Modbus slave address 10.

Module Connected To an RS232 Telephone Modem

When the module is powered up, it sends ‘initialisation strings’ to the connected modem. It is
important therefore that the modem is already powered, or is powered up at the same time as the
module. At regular intervals after power up, the modem is reset, and reinitialised, to ensure the
modem does not ‘hang up’.

If the module does not correctly communicate with the modem, “Modem initialising’ appears on the
Serial Port instrument screen as shown overleaf.

If the module is set for “incoming calls” or for “incoming and outgoing calls”, once the modem is
dialled, it answers after two rings (using the factory setting ‘initialisation strings). Once the call is
established, all data is passed between the dialling PC and the module.

If the module is set for “outgoing calls” or for “incoming and outgoing calls”, then the module dials out
whenever an alarm is generated.

NOTE: Not all alarms generate a dial out command; this is dependant upon module
configuration of the event log. Any event configured to be recorded in the event log causes
the modem to dial out to a PC.

Press the Scroll Down button view the modem


status....

Indicates that the RS232 port is


configured for modem use. It displays
‘RS232’ if no modem is configured.

58
Description Of Controls

Module Connected To an RS232 GSM Modem

When the module is powered up, it sends ‘initialisation strings’ to the connected modem. It is
important therefore that the modem is already powered, or is powered up at the same time as the
module. At regular intervals after power up, the modem is reset, and reinitialised, to ensure the
modem does not ‘hang up’.

If the module does not correctly communicate with the modem, “Modem initialising’ appears on the
Serial Port instrument screen as shown overleaf.

If the module is set for “incoming calls” or for “incoming and outgoing calls”, once the modem is
dialled, it answers after two rings (using the factory setting ‘initialisation strings). Once the call is
established, all data is passed between the dialling PC and the module.

If the module is set for “outgoing calls” or for “incoming and outgoing calls”, then the module dials out
whenever an alarm is generated.

NOTE: Not all alarms generate a dial out command; this is dependant upon module
configuration of the event log. Any event configured to be recorded in the event log causes
the modem to dial out to a PC.

Many GSM modems are fitted with a status LED to show operator cell status and ringing indicator.
These are a useful troubleshooting tool.

In the case of GSM connection problems, try calling the DATA number of the SIMCARD with an
ordinary telephone. There should be two rings, followed by the modem answering the call and then
‘squealing’. If this does not happen, you should check all modem connections and double check with
the SIM provider that it is a DATA SIM and can operate as a data modem. DATA is NOT the same as
FAX or GPRS and is often called Circuit Switched Data (CSD) by the SIM provider.

Press the Scroll Down button view the modem GSM


status....

Currently connected GSM


operator and signal strength.

NOTE: In the case of GSM modems, it is important that a DATA ENABLED SIM is used.
This is often a different number than the ‘voice number’ and is often called Circuit Switched
Data (CSD) by the SIM provider.

If the GSM modem is not purchased from DSE, ensure that it has been correctly set to operate at
9600 baud.

59
Description Of Controls

Modem Initialisation Sequence

1) The modem attempts to communicate to the module

2) If the Modem and module communicate successfully:

3) In case of communication failure between the modem and module, the modem is automatically
reset and initialisation is attempted once more:

In the case of a module that is unable to communicate with the modem, the display continuously
cycles between ‘Modem Reset’ and ‘Modem Initialising’ as the module resets the modem and
attempts to communicate with it again, this continues until correct communication is established
with the modem. In this instance, you should check connections and verify the modem operation.

Module Modem Diagnostics

Modem diagnostic screens are included; press the Scroll Down button when viewing the
RS232 Serial Port instruments to cycle to the available screens. If you are experiencing modem
communication problems, this information aids troubleshooting.

Shows the state of the modem communication lines. These can help
Serial Port diagnose connection problems.
RTS DTR Example:
CTS DCD
DSR RTS A dark background shows the line is active.
RTS A grey background shows that the line is toggling high and low
RTS No background indicates that the line is inactive

Line Description
RTS Request to Send Flow Control
CTS Clear to Send Flow Control
DSR Data Set Ready Ready to Communicate
DTR Data Terminal Ready Ready to Communicate
DCD Data Carrier Detect Modem is Connected

Modem Commands
Rx: OK Shows the last command sent to the
Tx: AT+IPR=9600 modem and the result of the command.
Rx: OK

60
Description Of Controls

Module RS232 Port Configured For Connection to A Modbus Master

The modules operate as a modbus RTU slave device. In a modbus system, there is only one Master,
typically a PLC, HMI system or PC SCADA system.

This master requests for information from the modbus slave (The module) and may (in control
systems) also send request to change operating modes etc. Unless the Master makes a request, the
slave is ‘quiet’ on the data link.

The factory settings are for the module to


communicate at 19200 baud, modbus slave
address 10.

To use the RS232 port, ensure that ‘port usage’ is


correctly set using the DSE Configuration Suite
Software.

‘Master inactivity timeout’ should be set to at


least twice the value of the system scan time. For
example if a modbus master PLC requests data
from the module once per second, the timeout
should be set to at least 2 seconds

The DSE MODBUS document containing register mappings inside the DSE module is available upon
request from support@deepseaplc.com. Email your request along with the serial number of your
DSE module to ensure the correct information is sent to you.

61
Description Of Controls

5.2.6.2 RS485 SERIAL PORT

This section is included to give information about the currently selected serial port

The items displayed on this page change depending upon configuration of the module. You are
referred to your system supplier for further details.

NOTE: Factory Default settings are for the RS485 port to operate at 19200 baud, modbus
slave address 10.

Module RS485 Port Configured For Connection to A Modbus Master

The modules operate as a modbus RTU slave device.


In a modbus system, there is only one Master, typically a PLC,
HMI system or PC SCADA system.

This master requests for information from the modbus slave


(The module) and may (in control systems) also send request
to change operating modes etc. Unless the Master makes a request, the slave is ‘quiet’ on the data
link.

The factory settings are for the module to


communicate at 19200 baud, modbus slave
address 10.

‘Master inactivity timeout’ should be set to at


least twice the value of the system scan time.
For example if a modbus master PLC requests
data from the module once per second, the
timeout should be set to at least 2 seconds.

The DSE MODBUS document containing register mappings inside the DSE module is available upon
request from support@deepseaplc.com. Email your request along with the serial number of your
DSE module to ensure the correct information is sent to you.

Typical Requests (Using Pseudo Code)

BatteryVoltage=ReadRegister(10,0405,1): reads register (hex) 0405 as a single register (battery


volts) from slave address 10.

WriteRegister(10,1008,2,35701, 65535-35701): Puts the module into AUTO mode by writing to


(hex) register 1008, the values 35701 (auto mode) and register 1009 the value 65535-35701 (the
bitwise opposite of auto mode)

Shutdown=(ReadRegister(10,0306,1) >> 12) & 1): reads (hex) 0306 and looks at bit 13
(shutdown alarm present)

Warning=(ReadRegister(10,0306,1) >> 11) & 1): reads (hex) 0306 and looks at bit 12
(Warning alarm present)

ControlledShutdown=(ReadRegister(10,0306,1) >> 10) & 1): reads (hex) 0306 and looks at
bit 11 (Controlled Shutdown alarm present)

ControlMode=ReadRegister(10,0304,2): reads (hex) register 0304 (control mode).

62
Description Of Controls

5.2.7 ABOUT

5.2.7.1 MODULE INFORMATION

Contains important information about the module and the firmware versions. This information may be
asked for when contacting DSE Technical Support Department for advice.

About • Variant (E800)


Variant E800 • Application Version – The version of the module’s
Application V1.2.12 main firmware file (Updatable using the Firmware
USB ID BC614E Update Wizard in the DSE Configuration Suite
Software).
• USB ID – Unique identifier for PC USB connection

Press the Scroll Down button to access more information about the module.

About • Bootloader - Firmware Update bootloader


Bootloader V1.3.2 software version
Analogue V1.0.13 • Analogue – Analogue measurements software
Engine V1.24 version
• Engine – Engine type file version.

63
Description Of Controls

5.2.7.2 ETHERNET

Whilst in the ‘ABOUT’ section, press the Scroll Down button to access more information
about the network settings.

Network settings change be configured using DSE Configuration Suite Software. The module must
be rebooted for the changes to take effect.

Network • IP Address – The configured network IP


IP Address address of the module
192.168.50.76 • DHCP – Dynamic Host Configuration
DHCP Disabled Protocol (DHCP) has been enabled or
disabled in the modules configuration.

Press the Scroll Down button to access more information about the network settings.

Network
Subnet Mask • Subnet Mask – The configured network subnet
255.255.255.0 mask of the module.

Network
• Gateway Address – The configured network
Gateway Address
gateway address of the module.
192.168.49.76

Network
DNS Address • DNS Address – The configured network
DNS address of the module.
192.168.88.99

Network
• MAC Address – The MAC address of the
MAC Address module, this cannot be changed and is
E8.A4.C1.0.A.C2 unique to every Ethernet device.

DHCP
Host • DHCP – The DHCP settings of module if configured.
Domain
Vender

MODBUS Over IP
• TCP Port – The MODBUS TCP communication
TCP Port 502 port number.
Pref IP 192.168.20.11 • Pref IP – The preferred connection IP address. The
module can support up to 4 MODBUS TCP
masters. If there is an additional request from
another master with this IP address, it will be
allowed to be the fifth MODBUS TCP master.

64
Description Of Controls

5.2.7.3 DATA LOGGING

Whilst in the ‘ABOUT’ section, press Scroll Down button to access more information about
the data logging settings.

Location of logged data. Displays either internal


module memory or external USB memory.
Data Logging
Log to internal memory
If data logging is active or inactive
Logging active
No USB drive present
If external USB storage
device is disconnected

Inserting a USB storage device to the USB host connector on the rear of the module displays the
following change to the page.

Data Logging
Log to USB drive If external USB storage
Logging active device is connected
Do not remove USB drive

NOTE: Removal of the USB drive should only be carried out using the following method.

Press and hold the Tick button until “Ok to remove USB drive” is displayed.

Data Logging
Log to USB drive
Logging active
Ok to remove USB drive

It is now safe to remove the USB drive.


This ensures the logging data file saves to memory complete and does not become corrupt.

Press Scroll Down button to view the next page.

Data Logging Remaining time available


Time remaining for logging information.
xxxx h xx m xxxx hours xx minutes

Press Scroll Down button to view the next page.

Data Logging Memory space remaining, this


Memory remaining depends what size memory drive is
xxxx fitted (Max 16GB) or allocated internal
(2MB) memory left available.

65
Description Of Controls

5.2.7.4 LCD

Whilst in the ‘ABOUT’ section, press Scroll Down button to access more information about
the LCD Temperature.

LCD
LCD Temperature Temperature of LCD display measured in °C.
34 Display heater (if used) turns on at -20 °C and off at -10 °C

66
Description Of Controls

5.3 USER CONFIGURABLE INDICATORS


These LEDs are configured by the user to indicate any one of 100+ different functions based
around the following:-

• Indications - Monitoring of a digital input and indicating associated functioning user’s equipment -
Such as Battery Charger On or Louvres Open, etc.

• Warnings, Controlled Shutdowns & Shutdowns Alarms - Specific indication of a particular


warning or shutdown condition, backed up by LCD indication - Such as Low Oil Pressure
Shutdown, Low Coolant level, etc.

• Status Indications - Indication of specific functions or sequences derived from the modules
operating state - Such as Safety On, Pre-heating, Panel Locked, etc.

User configurable LEDs

67
Operation

6 OPERATION

NOTE: The following descriptions detail the sequences followed by a module containing
the standard ‘factory configuration’. Always refer to your configuration source for the exact
sequences and timers observed by any particular module in the field.

6.1 QUICKSTART GUIDE


This section provides a quick start guide to the module’s operation.

6.1.1 STARTING THE ENGINE

Press the Manual


Mode button... ...followed by
the Start button

68
Operation

6.1.2 STOPPING THE ENGINE

Select Stop/Reset
mode. The engine is
stopped

69
Operation

6.2 OFF MODE

NOTE: If a digital input configured to panel lock is active, changing module modes is not
possible. Viewing the instruments and event logs is NOT affected by panel lock.

Off Mode is activated by pressing the Stop/Reset Mode button followed by the Off Mode
button.
The LED above the Off Mode button illuminates to indicate that the controller is in the Off Mode.

In Off Mode , the engine does not start manually or automatically.

Press the Off Mode button again to awaken the module. The module awakens in the
Stop/Reset Mode .

70
Operation

6.3 MANUAL MODE

NOTE: If a digital input configured to panel lock is active, changing module modes is not
possible. Viewing the instruments and event logs is NOT affected by panel lock.

Manual Mode is activated by pressing the Manual Mode button.


The LED above the Manual Mode button illuminates to indicate Manual Mode operations.

In Manual Mode , the set does not start automatically.


To begin the starting sequence, press the Start button.

6.3.1 STARTING SEQUENCE

NOTE: There is no start delay in this mode of operation.

The fuel relay is energised and the engine is cranked.

NOTE: If the unit has been configured for CAN, compatible ECU’s receives the start
command via CAN.

If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the
crank rest duration after which the next start attempt is made. Should this sequence continue beyond
the set number of attempts, the start sequence is terminated and the display shows the Fail to Start
alarm.

The starter motor is disengaged when the engine fires. Speed detection is derived from the Pulse
Pickup Terminals which are measured from a Magnetic Pickup mounted on the flywheel, charge
alternator tachometer output or from the CANbus link to the engine ECU depending on module
configuration.

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

Additionally, rising oil pressure can be used to disconnect the starter motor (but cannot detect
underspeed or overspeed).

After the starter motor has disengaged, the Safety On Delay timer activates, allowing Oil Pressure,
High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to
stabilise without triggering the fault.

71
Operation

6.3.2 ENGINE RUNNING

Once the engine is running and all starting timers have expired, the engine is seen as available.

In Manual Mode , the Clutch Control output (if configured) activates automatically if the engine
speed has increased above the configured engage value.

NOTE: The Clutch Control remains inactive until the Oil Pressure has risen. This prevents
excessive wear on the engine.

Once the engine has been placed on load, it is not automatically removed. To manually remove the
load either:

• Press the Auto Mode button to return to automatic mode. The set observes all
Auto Mode start requests and stopping timers before beginning the Auto Mode Stopping
Sequence.
• Press the Stop/Reset Mode button to remove load and stop the engine.

6.3.3 STOPPING SEQUENCE

In Manual Mode the set continues to run until either:

• The Stop/Reset Mode button is pressed – The Clutch Control output is de-activated
immediately and the engine immediately stops.
• The Auto Mode button is pressed. The set observes all Auto Mode start requests
and stopping timers before beginning the Auto Mode Stopping Sequence.

72
Operation

6.4 AUTOMATIC MODE

NOTE: If a digital input configured to external panel lock is active, changing module
modes is not possible. Viewing the instruments and event logs is NOT affected by panel lock.

Auto Mode is activated by pressing the Auto Mode button.


The LED above the Auto Mode button illuminates to indicate Auto Mode operations.

Auto Mode allows the engine to operate fully automatically, starting and stopping as required
with no user intervention.

6.4.1 WAITING IN AUTO MODE

If a starting request is made, the starting sequence begins.


Starting requests are from the following sources:

• Activation of an auxiliary input that has been configured to Remote Start.


• Activation of the inbuilt exercise scheduler.

6.4.2 STARTING SEQUENCE

To allow for ‘false’ start requests, the start delay timer begins.

Should all start requests be removed during the start delay timer, the unit returns to a stand-by state.

If a start request is still present at the end of the start delay timer, the fuel relay is energised and the
engine is cranked.

NOTE: If the unit has been configured for CAN, compatible ECU’s receive the start
command via CAN and transmit the engine speed to the DSE controller.

If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the
crank rest duration after which the next start attempt is made. Should this sequence continue beyond
the set number of attempts, the start sequence is terminated and the display shows the Fail to Start
alarm.

The starter motor is disengaged when the engine fires. Speed detection is derived from the Pulse
Pickup Terminals which are measured from a Magnetic Pickup mounted on the flywheel, charge
alternator tachometer output or from the CANbus link to the engine ECU depending on module
configuration.

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

Additionally, rising oil pressure can be used to disconnect the starter motor (but cannot detect
underspeed or overspeed).

After the starter motor has disengaged, the Safety On Delay timer activates, allowing Oil Pressure,
High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to
stabilise without triggering the fault.

73
Operation

6.4.3 ENGINE RUNNING

Once the engine is running and all starting timers have expired, the engine is seen as available.

The Clutch Control output (if configured) activates automatically if configured to do so.

NOTE: The Clutch Control remains inactive until the Oil Pressure has risen. This prevents
excessive wear on the engine.

If all start requests are removed, the stopping sequence begins.

6.4.4 STOPPING SEQUENCE

The Return Delay timer operates to ensure that the starting request has been permanently removed
and isn’t just a short term removal. Should another start request be made during the cooling down
period, the engine returns on load.

If there are no starting requests at the end of the Return Delay timer, the Clutch Control output (if
configured) de-activates and the Cooling Down Timer is initiated.

The Cooling Down Timer allows the engine to run off load and cool sufficiently before being stopped.
This is particularly important where turbo chargers are fitted.

After the Cooling Down timer has expired, the set is stopped.

74
Operation

6.5 STOP/RESET MODE

NOTE: If a digital input configured to panel lock is active, changing module modes is not
possible. Viewing the instruments and event logs is NOT affected by panel lock.

Stop/Reset Mode is activated by pressing the Stop/Reset Mode button.


The LED above the Stop/Reset Mode button illuminates to indicate Stop/Reset Mode
operations.

In Stop/Reset Mode , the module removes the engine from load (if necessary) before stopping if
it is already running.

If the engine does not stop when requested, the Fail To Stop Alarm is activated (subject to the
setting of the Fail to Stop timer). To detect the engine at rest the following must occur :

• Engine speed is zero as detected by the CANbus ECU or Pulse Pickup Input
• Charge Alternator Voltage must be zero.
• Oil pressure sensor must indicate low oil pressure

When the engine has stopped, it is possible to send configuration files to the module from DSE
Configuration Suite PC software and to enter the Front Panel Editor to change parameters.

Any latched alarms that have been cleared are reset when Stop/Reset Mode is entered.

The engine is not started when in Stop/Reset Mode . If remote start signals are given, the input is
ignored until Auto Mode is entered.

When left in Stop/Reset Mode with no presses of the fascia buttons and configured for Sleep
Mode, the module enters Sleep Mode. To ‘wake’ the module, press any fascia control buttons.

Sleep Mode in the


DSE Configuration
Suite Software

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

75
Operation

6.6 SCHEDULER
The controller contains an inbuilt exercise run scheduler, capable of automatically starting and
stopping the set. Up to 16 scheduled start/stop sequences can be configured to repeat on a 7-day or
28-day cycle.

Scheduled runs may be on load or off load depending upon module configuration.

Example

Screen capture from DSE


Configuration Suite Software
showing the configuration of
the Exercise Scheduler.

In this example the set starts


on Monday in the Second
Week of each month at 09:00
am and runs for 5 hours, then
Wednesday in the Third Week
of each month at 13:30 pm and
runs for 30 minutes.

6.6.1 OFF MODE

• Scheduled runs do not occur when the module is in Off Mode .

6.6.2 MANUAL MODE

• Scheduled runs do not occur when the module is in Manual Mode waiting for a start
request.

6.6.3 AUTO MODE

• Scheduled runs operate ONLY if the module is in Auto Mode with no Shutdown or
Controlled Shutdown alarm present.
• If the module is in Off Mode , Stop/Reset Mode or Manual Mode when a
scheduled run begins, the engine is not started. However, if the module is moved into
Auto Mode during a scheduled run, the engine is called to start.
• Depending upon configuration by the system designer, an external input can be used to
inhibit a scheduled run.
• If the engine is running OFF LOAD in Auto Mode and a scheduled run configured to ‘On
Load’ begins, the engine is placed ON LOAD for the duration of the Schedule.

6.6.4 STOP/RESET MODE

• Scheduled runs do not occur when the module is in Stop/Reset Mode .

76
Protections

7 PROTECTIONS
When an alarm is active, the Internal Audible Alarm sounds and the Common Alarm LED if
configured illuminates.
The audible alarm is silenced by pressing the Alarm Mute / Lamp Test button.

The LCD display jumps from the ‘Information page’ to display the Alarm Page

Number of active alarms.


This is alarm 1 of a total of 2 active
1/2 Alarm
Low Oil Pressure The cause of alarm, e.g. Low Oil Pressure

Warning The type of alarm, e.g. Warning

The LCD displays multiple alarms such as “Coolant Temperature High”, “Emergency Stop” and “Low
Coolant Warning”. These automatically scroll in the order that they occurred.

In the event of an alarm, the LCD displays the appropriate text. If an additional alarm then occurs,
the module displays the appropriate text.

Example:

1/2 Alarm 2/2 Alarm


Low Oil Pressure Coolant Temperature High

Warning Shutdown

7.1 CAN ERROR MESSAGES


When connected to a suitable CAN engine, the controller displays alarm status messages from the
ECU.

1/1 Alarm
Type of alarm that is
ECU Amber triggered in the DSE
module, e.g. Warning
Warning

Press the Next Page button to access the list of current active Engine DTCs (Diagnostic
Trouble Codes) from the ECU.

Engine DTCs
The code is interpreted by the module and shows on the display as a
Water Level Low text message. Additionally, the manufacturer’s fault code is shown
below.
Xxx,xxx,xxx

NOTE: For details on these code meanings, refer to the ECU instructions provided by the
engine manufacturer, or contact the engine manufacturer for further assistance.

NOTE: For further details on operation of electronic engines, refer to


DSE Publication: 057-004 Electronic Engines And DSE Wiring Guide

77
Protections

7.2 PROTECTIONS DISABLED


User configuration is possible to prevent Shutdown & Controlled Shutdown alarms from stopping the
engine. Under such conditions, Protections Disabled appears on the module display to inform the
operator of this status.

This feature is provided to assist the system designer in meeting specifications for “Warning Only”,
“Protections Disabled”, “Run to Destruction”, “War Mode” or other similar wording.

When configuring this feature in the PC software, the system designer chooses to make the feature
either permanently active, or only active upon operation of an external switch. The system designer
provides this switch (not DSE) so its location varies depending upon manufacturer, however it
normally takes the form of a key operated switch to prevent inadvertent activation. Depending upon
configuration, a warning alarm may be generated when the switch is operated.

The feature is configurable in the PC configuration software for the module. Writing a configuration to
the controller that has “Protections Disabled” configured, results in a warning message appearing on
the PC screen for the user to acknowledge before the controller’s configuration is changed. This
prevents inadvertent activation of the feature.

NOTE: For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

7.2.1 INDICATION AND WARNING ALARMS

Under Indication or Warning alarms:

• The module operation is unaffected by the Protections Disabled feature. See sections
entitled Indications and Warning Alarms elsewhere in this document.

7.2.2 SHUTDOWN AND CONTROLLED SHUTDOWN ALARMS

NOTE: The Emergency Stop input and Engine Overspeed Shutdown alarms continue to
operate even when Protections Disabled has been activated.

Under Shutdown or Controlled Shutdown alarm conditions (excluding Emergency Stop and
Overspeed):

• The alarm is displayed on the screen as detailed in the section entitled Shutdown Alarms or
Controlled Shutdown Alarms elsewhere in this document.
• The set continues to run.
• The Clutch Control maintains active (it is not opened if already closed)
• Shutdown Blocked also appears on the LCD screen to inform the operator that the
Protections Disabled feature has blocked the shutdown of the engine under the normally
critical fault.
• The ‘shutdown’ alarm is logged by the controllers Event Log (if configured to log shutdown
alarms) and logs that the Shutdown was prevented.

78
Protections

7.3 INDICATIONS
Indications are non-critical and often status conditions. They do not appear on the LCD of the module
as a text message. However, an output or LED indicator is configured to draw the operator’s attention
to the event.

Example

• Input configured for


indication.

• The LCD text does not


appear on the module
display but can be added
in the configuration to
remind the system
designer what the input is
used for.

• As the input is configured


to Indication there is no
alarm generated.

• LED Indicator to make


LED1 illuminate when
Digital Input A is active.

• The Insert Card Text


allows the system
designer to print an insert
card detailing the LED
function.

• Sample showing
operation of the LED.

79
Protections

7.4 WARNING ALARMS


Warnings are non-critical alarm conditions and do not affect the operation of the engine system, they
serve to draw the operators attention to an undesirable condition.

Example

1/2 Alarm
High Coolant Temperature

Warning

In the event of an alarm the LCD jumps to the alarms page, and scroll through all active alarms.

By default, warning alarms are self-resetting when the fault condition is removed. However enabling
‘all warnings are latched’ causes warning alarms to latch until reset manually. This is enabled using
the DSE Configuration Suite in conjunction with a compatible PC.

If the module is configured for CAN and receives an “error” message from the ECU, ‘CAN ECU
Amber” is shown on the module’s display as a warning alarm.

Display Reason
If a ratiometric input has been configured to a digital input
Ratiometric Input A to L Digital Input and has been configured as a warning the appropriate
LCD message is displayed.
The module detects that the value of the ratiometric input
Ratiometric Input A to L High
has increased pre-alarm setting.
The module detects that the value of the ratiometric input
Ratiometric Input A to L Low
has fallen below pre-alarm setting.
The module detects that the engine ECU has detected the
Charge Air Temperature Charge Air Temperature has exceeded the pre-alarm trip
level.
The module detects the auxiliary charge alternator voltage
Charge Alternator Failure from the W/L terminal has fallen below the pre-alarm
level.
Coolant Temperature Sender Open The module detects that the circuit to the coolant
Circuit temperature sensor has been broken.
If a digital input has been configured as a warning the
Digital Input A to K
appropriate LCD message is displayed.
The module detects that the engine ECU has detected that
ECU After Treatment
the after treatment is currently in progress.
The module detects that the engine ECU has detected a
ECU Amber
fault causing an Amber alarm.
The module detects that the engine ECU has detected a
ECU Protect
fault causing a Protect alarm.
The module detects that the engine ECU has detected a
ECU Malfunction
fault causing a Malfunction alarm.
The module detects that the engine ECU has detected a
ECU Red
fault causing a Red alarm.
The module detects that the engine ECU has detected that
ECU Water In Fuel
there is water in the fuel.
The Engine DC supply has risen above the high volts
Battery High Voltage
setting level for the duration of the high battery volts timer
The Engine DC supply has fallen below the low volts
Battery Low Voltage
setting level for the duration of the low battery volts timer

Alarms continued overleaf...

80
Protections

Display Reason
Indicates that the engine maintenance alarm has
Engine Maintenance Alarm 1, 2 & 3 triggered. A visit is required by the engine service
company.
Indicates the amount of fuel measured by the fuel level
Fuel Usage sensor is in excess of the Fuel Usage alarm settings. This
often indicates a fuel leak or potential fuel theft.
The module detects that the engine coolant temperature
High Coolant Temperature has exceeded the high engine temperature pre-alarm trip
setting after the Safety On timer has expired.
The module detects that the engine coolant temperature
Low Coolant Temperature has fallen below the high engine temperature pre-alarm
setting level.
The level detected by the fuel level sensor is below the
Low Fuel Level
low fuel level setting.
The module detects that the engine oil pressure has fallen
Low Oil Pressure below the low oil pressure pre-alarm setting level after the
Safety On timer has expired.
The speed signal from the pulse input is not being
Loss Of Speed Sensing
received by the DSE controller.
The module detects that the circuit to the MPU has been
Pulse Pickup Open Circuit
broken.
The module detects that the engine speed has risen above
Overspeed
the overspeed pre alarm setting.
The module detects that the engine speed has fallen
Underspeed
below the underspeed pre alarm setting.

81
Protections

7.5 CONTROLLED SHUTDOWN ALARMS

NOTE: Shutdown and Controlled Shutdown alarms can be disabled by user


configuration. See the section entitled Protections Disabled elsewhere in this document.

Controlled Shutdowns are latching and stop engine but in a controlled manner. On initiation of the
Controlled Shutdown condition the module de-energises all the ‘Clutch Control’ output to remove
the load from the engine. Once this has occurred the module starts the Cooling Down Timer and
allows the engine to cool off-load before shutting it down. The alarm must be accepted and cleared,
and the fault removed to reset the module.

Example

1/2 Alarm
High Coolant Temperature

Controlled Shutdown

In the event of an alarm the LCD jumps to the alarms page, and scroll through all active alarms.

Controlled Shutdowns are latching alarms and to remove the fault, press the Stop/Reset Mode
button on the module.

NOTE: The alarm condition must be rectified before a reset takes place. If the alarm
condition remains, it is not possible to reset the unit (The exception to this is the Low Oil
Pressure alarm and similar ‘active from safety on’ alarms, as the oil pressure is low with the
engine at rest).

Display Reason
If a ratiometric input has been configured to a digital input and has
Ratiometric Input A to L
been configured as a warning the appropriate LCD message is
Digital Input
displayed.
The module detects that the value of the ratiometric input has
Ratiometric Input A to L High
increased pre-alarm setting.
The module detects that the value of the ratiometric input has fallen
Ratiometric Input A to L Low
below pre-alarm setting.
The module detects that the engine ECU has detected the Charge Air
Charge Air Temperature
Temperature has exceed the trip level.
If a digital input has been configured as an controlled shutdown, the
Digital Input A to K
appropriate LCD message is displayed.
The module detects that the engine ECU has detected that the after
ECU After Treatment
treatment is currently in progress.
The module detects that the engine ECU has detected a fault causing
ECU Amber
an Amber alarm.
The module detects that the engine ECU has detected a fault causing
ECU Protect
a Protect alarm.
The module detects that the engine ECU has detected a fault causing
ECU Malfunction
a Malfunction alarm.
The module detects that the engine ECU has detected a fault causing
ECU Red
a Red alarm.
The module detects that the engine ECU has detected that there is
ECU Water In Fuel
water in the fuel.

Alarms continued overleaf...

82
Protections

Display Reason
Indicates the amount of fuel measured by the fuel level
Fuel Usage sensor is in excess of the Fuel Usage alarm settings.
This often indicates a fuel leak or potential fuel theft.
The module detects that the engine coolant
temperature has exceeded the high engine temperature
High Coolant Temperature
trip alarm setting level after the Safety On timer has
expired.
The level detected by the fuel level sensor is below the
Low Fuel Level
low fuel level trip setting.

83
Protections

7.6 SHUTDOWN ALARMS

NOTE: Shutdown and Controlled Shutdown alarms can be disabled by user


configuration. See the section entitled Protections Disabled elsewhere in this document.

Shutdown alarms are latching and immediately stop the engine. On Initiation of the Shutdown
condition the module de-energises all the ‘Clutch Control’ output to remove the load from the
engine. Once this has occurred, the module shuts the engine down immediately to prevent further
damage. The alarm must be accepted and cleared, and the fault removed to reset the module.

Example

1/2 Alarm
Low Oil Pressure

Shutdown

In the event of an alarm the LCD jumps to the alarms page, and scroll through all active alarms.

Shutdowns are latching alarms and to remove the fault, press the Stop/Reset Mode button on
the module.

If the module is configured for CAN and receives an “error” message from the ECU, ‘CAN ECU Red”
is shown on the module’s display as a s alarm.

NOTE: The alarm condition must be rectified before a reset takes place. If the alarm
condition remains, it is not be possible to reset the unit (The exception to this is the Low Oil
Pressure alarm and similar ‘active from safety on’ alarms, as the oil pressure is low with the
engine at rest).

Display Reason
Air Flap Closed Alarm The module detects the air flap has closed.
If a ratiometric input has been configured to a digital
Ratiometric Input A to L Digital Input input and has been configured as a warning the
appropriate LCD message as displayed.
The module detects that the value of the ratiometric
Ratiometric Input A to L High
input has increased pre-alarm setting.
The module detects that the value of the ratiometric
Ratiometric Input A to L Low
input has fallen below pre-alarm setting.
The module detects it has lost its calibration and should
Memory Corruption
be sent back to DSE for repair.
The module detects the auxiliary charge alternator
Charge Alternator Failure voltage from the W/L terminal has fallen below the trip
level.
The module detects that the engine ECU has detected
Charge Air Temperature
the Charge Air Temperature has exceed the trip level.
The module detects that the circuit to the coolant
Coolant Temperature Sender Open Circuit
temperature sensor has been broken.
The module detects that the emergency stop has been
Emergency Stop
pressed from the emergency stop terminal
If a digital input has been configured as an shutdown
Digital Input A to K
alarm, the appropriate LCD message as displayed.

Alarms continued overleaf...

84
Protections

Display Reason
The module detects that the engine ECU has detected that
ECU After Treatment
the after treatment is currently in progress.
The module detects that the engine ECU has detected a
ECU Amber
fault causing an Amber alarm.
The module detects that the engine ECU has detected a
ECU Protect
fault causing a Protect alarm.
The module detects that the engine ECU has detected a
ECU Malfunction
fault causing a Malfunction alarm.
The module detects that the engine ECU has detected a
ECU Red
fault causing a Red alarm.
The module detects that the engine ECU has detected that
ECU Water In Fuel
there is water in the fuel.
Indicates that the engine maintenance alarm has triggered.
Engine Maintenance Alarm 1, 2 & 3
A visit is required by the engine service company.
The module has detected that the engine has failed to start
Fail to Start
after the configured number of start attempts.
Indicates the amount of fuel measured by the fuel level
Fuel Usage sensor is in excess of the Fuel Usage alarm settings. This
often indicates a fuel leak or potential fuel theft.
The level detected by the fuel level sensor is below the low
Low Fuel Level
fuel level setting.
The module detects that the engine oil pressure has fallen
Low Oil Pressure below the low oil pressure alarm trip setting level after the
Safety On timer has expired.
The module detects that the circuit to the oil pressure sensor
Oil Pressure Sender Open Circuit
has been broken.
The speed signal from the pulse pickup is not being
Loss Of Speed Sensing
received by the DSE controller.
The module detects that the circuit to the MPU has been
Pulse Pickup Open Circuit
broken.
The engine speed has risen above the overspeed alarm trip
Overspeed
setting
The engine speed has fallen below the underspeed alarm
Underspeed
trip setting

85
Protections

7.7 MAINTENANCE ALARM


Depending upon module configuration one or more levels of engine maintenance alarm may occur
based upon a configurable schedule.

Example 1

Screen capture from DSE


Configuration Suite Software showing
the configuration of the Maintenance
Alarm for 1, 2 and 3.

When activated, the maintenance


alarm is either a Warning (set
continues to run) or Shutdown
(running the set is not possible).

Resetting the maintenance alarm is


normally actioned by the site service
engineer after performing the required
maintenance.
The method of reset is either by:

• Activating an input that has been


configured to Reset Maintenance
Alarm 1, 2 or 3.

• Pressing the maintenance reset


button in the DSE Configuration
Suite, Maintenance section.

Example 2

Screen capture from DSE


Configuration Suite Software showing
the configuration of a digital input for
Reset Maintenance Alarm 1.

Example 3

Screen capture from DSE Configuration Suite


Software showing the Maintenance Alarm
Reset ‘button’ in the DSE Configuration Suite
SCADA | MAINTENANCE section.

86
Front Panel Configuration

8 FRONT PANEL CONFIGURATION


This configuration mode allows the operator to fully configure the module through its display without
the use of the DSE Configuration Suite PC Software.

Use the module’s facia buttons to traverse the menu and make value changes to the parameters:

Previous Parameter

Previous Section Next Section

Next Parameter Edit


Parameter

87
Front Panel Configuration

8.1 MAIN CONFIGURATION EDITOR

8.1.1 ACESSING THE MAIN CONFIGURATION EDITOR

NOTE: More comprehensive module configuration is possible via PC configuration


software. For further details of module configuration, refer to DSE Publication: 057-203
DSEE800 Configuration Software Manual.

• Ensure the engine is at rest and the module by pressing the Stop/Reset Mode button.

• Press the Stop/Reset Mode and Tick buttons together to enter the front panel
configuration editor.

8.1.2 ENTERING PIN

• If a module security PIN has been set, the PIN request is then shown.

• Press the Tick button, the first ‘#’ changes to ‘0’. Press the Instrumentation Scroll

buttons to adjust it to the correct value.

• Press the Next Page button when the first digit is correctly entered. The digit you have
just entered now shows as ‘#’ for security.

• Press the Previous Page button to move back to adjust one of the previous digits.

• After editing the final PIN digit, press the Tick button. The PIN is then checked for
validity. If the number is not correct, the PIN must re-entered.

• If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is
displayed.

NOTE: The PIN is not set by DSE when the module leaves the factory. If the module has a
PIN code set, this has been affected by your engine supplier who should be contacted if you
require the code. If the code has been ‘lost’ or ‘forgotten’, the module must be returned to
the DSE factory to have the module’s code removed. A charge is made for this procedure.
NB - This procedure cannot be performed away from the DSE factory.

NOTE: The PIN is automatically reset when the editor is exited (manually or
automatically) to ensure security.

88
Front Panel Configuration

8.1.3 EDITING A PARAMETER

• Press the Next or Previous Page buttons to cycle to the section which is required to be

edited. Press the Instrumentation Scroll buttons to cycle to the parameter within the
section chosen to be edited.

• Press the Tick button to edit the parameter. The parameter begins to flash to indicate
that the parameter is being edited.

• Press the Instrumentation Scroll buttons to adjust the parameter to the required value.

• Press the Tick button to stop editing the paramter. The parameter ceases flashing to
indicate that it the parameter is no longer being edited.

NOTE: Pressing and holding the Instrumentation Scroll buttons gives an auto-
repeat functionality. Values can be changed quickly by holding the navigation buttons for a
prolonged period of time.

8.1.4 EXITING THE MAIN CONFIGURATION EDITOR

• Press and hold the Stop/Reset Mode button to exit the editor without saving changes.

• Press and hold the Tick button to exit the editor and save the changes.

NOTE: The editor automatically exits after 5 minutes of inactivity to ensure security.

89
Front Panel Configuration

8.1.5 AVAILABLE PARAMETERS TO BE EDITED

Section Parameter As Shown On Display Values


Display Contrast 0%
Language English, others.
Current Date and Time Date hh:mm
Engine Oil Pressure Low shutdown 0 bar
Oil Pressure Low Pre-Alarm 0 bar
Coolant Temp High Pre-Alarm 0 ºC
Coolant Temp High Trip 0 ºC
Coolant Temp High Shutdown 0 ºC
Start Delay Off load 0s
Start Delay on load 0s
Start Delay Telemetry 0s
Pre Heat Timer 0s
Crank Duration 0s
Crank rest Time 0s
Safety On Delay 0s
Smoke Limiting 0s
Smoke limiting off 0s
Warm Up Time 0s
Cool Down Time 0s
Under Speed Shutdown Inactive
Under Speed Warning Inactive
Over Speed Shutdown Inactive
Over Speed Warning Inactive
Over Speed Shutdown 0 RPM
Speed Overshoot Delay 0s
Speed Overshoot 0%
Fail To Stop Delay 0s
Battery Under Volts Warning Active
Battery Under Volts Warning Delay 0m
Battery Under Volts Warning 0V
Battery Over Volts Warning Active
Battery Over Volts Warning Delay 0m
Battery Over Volts Warning 0V
Charge Alternator Failure Warning Active
Charge Alternator Failure Warning 0V
Charge Alternator Warning Delay 0s
Charge Alternator Failure Shutdown Inactive
Priming Delay 0s
Clutch Engage Speed 0 RPM
Clutch Disengage Speed 0 RPM
Idle Speed 0.00
Warming Speed 0.00
Cooldown Speed 0.00
Starting 0.00
Priming Speed 0.00
Min Speed 0.00
Default Running Speed 0.00
Max Speed 0.00

Parameters continue overleaf...

90
Front Panel Configuration

Section Parameter As Shown On Display Values


Reset Default Speed On Start-Up Inactive
Auto Adjustable Speed Inactive
Engine Cool Down at Idle 0s
Delayed Engine Start 0s
Delayed Engine Stop 0s
Engine Speed Transient Delay 0.0 s
Selectable Speed Transfer Time 0.0 s
DPF Auto Regen Inhibit Inactive
Timers LCD Page Timer 1s
Scroll Delay 1s
Engine Pre Heat Timer 0s
Engine Crank Duration 3s
Engine Crank Rest Time 3s
Engine Safety On Delay 5s
Engine Smoke Limiting 0s
Engine Smoke Limiting Off 0s
Engine Warm Up Time 0s
Engine Cool Down Time 0s
Engine Speed Overshoot Delay 0s
Engine Failed To Stop Delay 10 s
Battery Under Voltage Warning Delay 0s
Battery Over Voltage Warning Delay 0s
Return Delay 0s
Schedule Schedule Inactive
Active , Inactive (Only Available
Schedule On Load
When Scheduler Is Active)
Weekly, Monthly (Only Available
Schedule Period
When Scheduler Is Active)
Press to begin editing, then or
Schedule Time & Date Selection (1-16) when selecting the different
parameters in the scheduler.

91
Front Panel Configuration

8.2 ‘RUNNING’ CONFIGURATION EDITOR

8.2.1 ACESSING THE ‘RUNNING’ CONFIGURATION EDITOR

• The ‘running’ editor can be entered whilst the engine is running. All protections remain active if
the engine is running while the running editor is entered

• Press and hold the Tick button to enter the ‘running’ configuration editor.

8.2.2 ENTERING PIN

• Even if a module security PIN has been set, the PIN is not requested whilst entering the ‘running’
editor.

NOTE: The PIN is not set by DSE when the module leaves the factory. If the module has a
PIN code set, this has been affected by your engine supplier who should be contacted if you
require the code. If the code has been ‘lost’ or ‘forgotten’, the module must be returned to
the DSE factory to have the module’s code removed. A charge is made for this procedure.
NB - This procedure cannot be performed away from the DSE factory.

NOTE: The PIN is automatically reset when the editor is exited (manually or
automatically) to ensure security.

8.2.3 EDITING A PARAMETER

• Press the Instrumentation Scroll buttons to cycle to the parameter to be edited.

• Press the Tick button to edit the parameter. The parameter begins to flash to indicate
that the parameter is being edited.

• Press the Instrumentation Scroll buttons to adjust the parameter to the required value.

• Press the Tick button to stop editing the paramter. The parameter ceases flashing to
indicate that the parameter is no longer being edited.

NOTE: Pressing and holding the Instrumentation Scroll buttons gives an auto-
repeat functionality. Values can be changed quickly by holding the navigation buttons for a
prolonged period of time.

92
Front Panel Configuration

8.2.4 EXITING THE ‘RUNNING’ CONFIGURATION EDITOR

• Press and hold the Stop/Reset Mode button to exit the editor without saving changes.

• Press and hold the Tick button to exit the editor and save the changes.

NOTE: The editor automatically exits after 5 minutes of inactivity to ensure security.

8.2.5 AVAILABLE PARAMETERS TO BE EDITED

Section Parameter Values


Display Contrast 0%
Language English (United Kingdom), Other
Engine DPF Auto Regen Inhibit Inactive
DPF Manual Regen Inactive
DPF Manual Regen Cancel Inactive

93
Commissioning

9 COMMISSIONING
Before the system is started, it is recommended that the following checks are made:

• The unit is adequately cooled and all the wiring to the module is of a standard and rating
compatible with the system. Check all mechanical parts are fitted correctly and that all electrical
connections (including earths) are sound.

• The unit DC supply is fused and connected to the battery and that it is of the correct polarity.

• The Emergency Stop input is wired to an external normally closed switch connected to DC
positive.

NOTE: If Emergency Stop feature is not required, link the input to the DC Positive.

• To check the start cycle operation, take appropriate measures to prevent the engine from starting
(disable the operation of the fuel solenoid). After a visual inspection to ensure it is safe to
proceed, connect the battery supply. Press the Manual Mode button followed by the Start
button the unit start sequence commences.

• The starter engages and operates for the pre-set crank period. After the starter motor has
attempted to start the engine for the pre-set number of attempts, the LCD displays ‘Failed to
start. Press the Stop/Reset Mode button to reset the unit.

• Restore the engine to operational status (reconnect the fuel solenoid). Press the
Manual Mode button followed by the Start button. This time the engine should start and
the starter motor should disengage automatically. If not then check that the engine is fully
operational (fuel available, etc.) and that the fuel solenoid is operating. The engine should now
run up to operating speed. If not, and an alarm is present, check the alarm condition for validity,
then check input wiring. The engine should continue to run for an indefinite period. It is possible
at this time to view the engine parameters - refer to the ‘Description of Controls’ section of this
manual.

• Press the Auto Mode button, the engine runs for the pre-set cooling down period, then stop.
The engine should stay in the standby mode. If not check that there is not a signal present on the
Remote Start Input.

• Initiate an automatic start by supplying the remote start signal (if configured). The start sequence
commences and the engine runs up to operational speed. Once the engine is available the
Clutch Control output activates (if configured). If not, check the wiring to the clutch control
mechanism. Check the Warming timer has timed out.

• Remove the remote start signal. The return sequence begins. After the pre-set time, the engine is
unloaded. The engine then runs for the pre-set cooling down period, then shutdown into its
standby mode.

• Set the modules internal clock/calendar to ensure correct operation of the scheduler and event
logging functions. For details of this procedure see section entitled Front Panel Configuration

• If, despite repeated checking of the connections between the controller and the customer’s
system, satisfactory operation cannot be achieved, then the customer is requested to the DSE
Technical Support Department

94
Fault Finding

10 FAULT FINDING
10.1 STARTING

Symptom Possible Remedy


Unit is inoperative Check the battery and wiring to the unit. Check the DC supply.
Check the DC fuse.
Read/Write configuration
does not operate
Unit shuts down Check DC supply voltage is not above 35 Volts or below 9 Volts
Check the operating temperature is not above 70°C. Check the DC
fuse.
Fail to Start is activated after Check wiring of fuel solenoid. Check fuel. Check battery supply.
pre-set number of attempts to Check battery supply is present on the Fuel output of the module.
start Check the speed-sensing signal is present on the module’s inputs.
Refer to engine manual.
Continuous starting of engine Check that there is no signal present on the “Remote Start” input.
when in the Check configured polarity is correct.
Auto Mode
Engine fails to start on receipt Check Start Delay timer has timed out.
of Remote Start signal.
Check signal is on “Remote Start” input. Confirm correct
configuration of input is configured to be used as “Remote Start”.

Check that the oil pressure switch or sensor is indicating low oil
pressure to the controller. Depending upon configuration, then set
does not start if oil pressure is not low.
Pre-heat inoperative Check wiring to engine heater plugs. Check battery supply. Check
battery supply is present on the Pre-heat output of module. Check
pre-heat configuration is correct.
Starter motor inoperative Check wiring to starter solenoid. Check battery supply. Check battery
supply is present on the Starter output of module. Ensure oil
pressure switch or sensor is indicating the “low oil pressure” state to
the controller.

10.2 LOADING

Symptom Possible Remedy


Engine runs but does not take Check Warm up timer has timed out.
load Check connections to the clutch control mechanism.
Incorrect reading on Engine Check engine is operating correctly.
gauges
Check that sensor is compatible with the module and that the
Fail to stop alarm when module configuration is suited to the sensor.
engine is at rest

95
Fault Finding

10.3 ALARMS

Symptom Possible Remedy


Low oil Pressure fault Check engine oil pressure. Check oil pressure switch/sensor and
operates after engine has wiring. Check configured polarity (if applicable) is correct (i.e.
fired Normally Open or Normally Closed) or that sensor is compatible with
the module and is correctly configured.
High engine temperature fault Check engine temperature. Check switch/sensor and wiring. Check
operates after engine has configured polarity (if applicable) is correct (i.e. Normally Open or
fired. Normally Closed) or that sensor is compatible with the module.
Shutdown fault operates Check relevant switch and wiring of fault indicated on LCD display.
Check configuration of input.
Controlled Shutdown fault Check relevant switch and wiring of fault indicated on LCD display.
operates Check configuration of input.
Warning fault operates Check relevant switch and wiring of fault indicated on LCD display.
Check configuration of input.
CAN ECU WARNING This indicates a fault condition detected by the engine ECU and
CAN ECU SHUTDOWN transmitted to the DSE controller.
CAN DATA FAIL Indicates failure of the CAN data link to the engine ECU.
Check all wiring and termination resistors (if required).
Incorrect reading on Engine Check engine is operating correctly. Check sensor and wiring paying
gauges particular attention to the wiring to terminal 10 (refer to appendix).

Fail to stop alarm when Check that sensor is compatible with the module and that the
engine is at rest module configuration is suited to the sensor.

10.4 COMMUNICATIONS

Symptom Possible Remedy


CAN DATA FAIL Indicates failure of the CAN data link to the engine ECU.
Check all wiring and termination resistors (if required).

10.5 MISCELLANEOUS

Symptom Possible Remedy


Module appears to ‘revert’ to When editing a configuration using the PC software it is vital that the
an earlier configuration configuration is first ‘read’ from the controller before editing it. This
edited configuration must then be “written” back to the controller for
the changes to take effect.

When editing a configuration using the fascia editor, be sure to press

the Tick button to save the change before moving to another


item or exiting the fascia editor

NOTE: The above fault finding is provided as a guide check-list only. As the module is
configured to provide a wide range of different features, always refer to the source of your
module configuration if in doubt.

96
Maintenance, Spares, Repairs and Servicing

11 MAINTENANCE, SPARES, REPAIR AND SERVICING


The controller is Fit and Forget. As such, there are no user serviceable parts within the controller.
In the case of malfunction, you should contact your original equipment manufacturer (OEM).

11.1 PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE


If you require additional plugs from DSE, please contact our Sales department using the part
numbers below.

11.1.1 INDIVIDUAL PLUGS

Module Terminal Designation Plug Description Part No.


1-11 11 way 5.08 mm 007-451

12-17 6 way 5.08 mm 007-446

18-31 14 way 5.08 mm 007-428


32-35 4 way 5.08 mm 007-444
36-47 12 way 5.08 mm 007-109
51-55 4 way 5.08 mm 007-444
60-65 11 way 5.08 mm 007-451
RS485 3 way 5.08 mm 007-174
PC Configuration interface lead
016-125
(USB type A – USB type B)

11.2 PURCHASING ADDITIONAL FIXING CLIPS FROM DSE

Item Description Part No.

Module Fixing Clips (Packet Of 4) 020-294

11.3 PURCHASING ADDITIONAL SEALING GASKET FROM DSE

Item Description Part No.

Module Silicon Sealing Gasket 020-507

97
Warranty & Disposal

12 WARRANTY
DSE provides limited warranty to the equipment purchaser at the point of sale. For full details of any
applicable warranty, you are referred to your original equipment supplier (OEM).

13 DISPOSAL
13.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT)
Directive 2002/96/EC
If you use electrical and electronic equipment you must store, collect, treat, recycle and
dispose of WEEE separately from your other waste.

98
This Page is Intentionally Left Blank

99
This Page is Intentionally Left Blank

100
Module Configuration
This document details the different connection methods used between DSE controllers and the PC and also shows
the different configuration methods possible across the DSE range.

• Configuration by Windows PC
Direct USB Connection
Uses USB Type A to Type B lead (The same as typically used on a USB printer).

Module range Front panel config PC config PC Software


8700 series Selected items 
8600 series Selected items 
7300 series Selected items 
7200 series Selected items 
7100 series  All items  DSE Configuration
6100 series  All items  Suite
6000 series  All items 
4400 series  All items 
3100 series  All items 
332/333 series ATS Selected items 

813 interface

Module range External switch configuration PC config PC Software


103 MKII Selected items depending  DSE Configuration
402 MKII upon module configuration  Suite

810 interface

Available in USB (recommended) or RS232 (for legacy PC support) versions.

Module range Front panel config PC config PC Software


7500 series Selected items 
5500 series Selected items 
5300 series Selected items  5xxx for Windows
5200 series Selected items 
5100 series MKII*  All items 
710/720   7xx for Windows
55x series   P810 for Windows
*5110 MK 1 controller is not PC configurable, front fascia configuration only.

056-017 PC Configuration Interfacing Issue 5 - ADM


808 interface
Available only for RS232 ports. If your PC does not have an RS232 port, you will need to add a PCI (desktop PCs) or
PCMCIA (laptop PCs) card, available from all good PC stockists. DSE do not recommend the use of RS232 to USB
convertors.

Module range Front panel config PC config PC Software


51x / 52x / 530 / 54x / 560   P808 for Windows

• Front panel configuration


o Modules with front panel configuration are supplied with installation instructions giving
details of installation and configuration. Alternatively this information is contained on the
DSE website at www.deepseaplc.com. Registration is not required for access to these
documents.

• Useful part numbers


DSE Part Number Description
0806-001-15 DSE Configuration Suite Software CD and DSE USB controller drivers
DSE Software CD (contains 700 series PC software, P810 software, P810 USB
0806-001-03
drivers, P808 software, 5000 series software, legacy 606 software)
0810-001-03 P810 interface (RS232) with 0806-001-03 Software CD included
0810-002-00 P810 interface (USB) with 0806-001-03 Software CD included
0813-01 813 interface (USB) for use with DSE103MKII, DSE402MKII
016-125 USB Type A to Type B lead for DSE USB controllers

• Software on the web


o All DSE software is available at www.deepseaplc.com to registered members.
Registration and download is free of charge.

056-017 PC Configuration Interfacing Issue 5 - ADM

Potrebbero piacerti anche