PRODUCT DATA SHEET Monitored Pro eConnect® PDU
SPECIFICATIONS
UL, CSA C22.2 (Canada), CE (EU), FCC Part 15, Class A, Design
Certifications:
EN 55022, RoHS Compliant CPI’s Monitored Pro eConnect® Power Distribution Units (PDU) provide reliable
Monitors unit voltage, current, power (kW), power factor and power distribution for evolving enterprise data centers, whether connecting a
energy (kWh) at breaker, ±1% metering accuracy at each
breaker few pieces of equipment, or supporting high-density computing. Monitored Pro
Internal Metering:
Monitors voltage, current, power (kW) and energy (kWh) at each PDUs feature per-outlet monitoring of voltage, current, power (kW) and energy
outlet (kilowatt-hour) levels with a ±1% metering accuracy for each piece of equipment
Liquid Crystal Display (LCD) for easy viewing – screen rotation in the data center.
for viewing at any angle
Allows initial setup of IP and subnet addresses without
computer Each Monitored Pro eConnect PDU features a central LCD display, which provides
Displays total voltage, current and power on single-phase PDUs detailed power usage information for all attached equipment. Additionally, each
Local Display: Displays total voltage, power and line input current on three- PDU comes with the capability for remote monitoring and includes a web-
phase PDUs based interface that provides users with the ability to monitor power usage
Displays voltage, current, power and power factor for each and environmental factors at the outlet, branch circuit and PDU levels, as well
breaker
as allows users to navigate between linked deployments and continuously log
Displays temperature and humidity when optional environmental
probe (P/N 11761-003) is attached to the PDU data and events. This feature also allows users to set thresholds for power,
Displays alarm notifications – Separate LED flashes red on alarm temperature and humidity limits and forwards alarm notifications via email. The
Monitor voltage, current, power (kW), power factor and energy Monitored Pro eConnect PDU is also compatible with most third-party software
(kWh) through 1 GB Ethernet interface using a web browser that accepts SNMP traps.
(HTTP or HTTPS), Telnet or an application that accepts alarms as
SNMP v1, v2c or v3 traps
Monitor temperature and humidity when external environmental Ease of Deployment
Network Monitoring: probes (P/N 11761-003) are attached to the PDU Each PDU has a built-in Ethernet connection, one external connection for two
Monitors door lock/unlock and open/closed status when environmental probes, two connections for linking PDUs together and two
eConnect Electronic Access Control is connected connections for linking two electronic locks on the front and rear of the cabinet.
Set and automatically monitor high and low alarm thresholds for
CPI’s Secure Array™ IP Consolidation allows the use of a single IP address for up
power (excludes line input current), temperature and humidity
Log data and events and receive alarm notifications by email to 32 connected PDUs, significantly reducing operating costs. In addition, CPI’s
Secure Array IP Consolidation provides failover and pass-through capability for an
Use the PDU In/Out connections to link up to 32 PDUs together
using standard RJ45 Cat 5/6 patch cords entire array of connected PDUs. This ensures that functioning PDUs will continue
View all connected PDUs through a single network connection to communicate in the event that a PDU in the array loses connectivity. Elevated
and IP address hot aisle data center temperatures will not affect eConnect PDUs, which have
IP Consolidation Secure Array IP Consolidation: maintains downstream links even been designed to withstand ambient air temperatures up to 149°F (65°C).
(PDU Linking): if one PDU loses power
Supports a backup, second network connection through an
alternate PDU eConnect PDUs with IEC outlets are available with Click Secure Locking Outlets,
Optional alarm notification if IP connection is lost or any of the which prevent accidental disconnections. This patented feature securely fastens
PDU links are dropped straight equipment power cords to the PDU, protecting your power from sudden
Remotely monitor voltage, current, and power (kW) and energy disruptions. Simply insert the equipment plug into locking outlet, easily clicking it
(kWh) at each outlet
Monitored Outlets: into the locked position. To release, lightly squeeze the locking mechanism.
Name outlets to easily identify attached equipment
Create outlet groups to see combined power use
eConnect PDUs are suitable for global use. Most PDUs include an attached 10’L
Temperature: 32°F – 149°F (0°C – 65°C) at Input Power Rating
(kW) (3 m) power cord with an IEC or NEMA style plug rated for 100-125 Volt, 200-240
Operating Conditions: Volt or 380-415 Volt input, and some models have an IEC C20 inlet, allowing the
Relative Humidity: 5% – 95%, non-condensing
Elevation: 0 – 10,000 feet (0 – 3,000 meters) power cords to be ordered separately to match specific site requirements. See
Temperature: -13°F – 149°F (-25°C – 65°C) reverse for product selection, or contact CPI Technical Support for configuration
Storage/NonOperating assistance.
Relative Humidity: 5% – 95%, non-condensing
Conditions
Elevation: 0 – 50,000 feet (0 – 15,000 m)
Includes two tool-less mounting shoulder washers and
installation hardware
COMPATIBLE WITH
The PDU can be installed with the inlet power cord near the top
or bottom of the cabinet • CPI Cabinet Systems
Washers can be installed spaced 64.75” (1645 mm) or 61.25”
• CPI Rack Systems
Installation Hardware: (1556 mm) apart to match most rack/cabinet mounting brackets
The washers can also be offset 2” (51 mm) to provide additional • eConnect Electronic Access Control
space at the top or bottom of the cabinet for the power cord in • Temperature and Humidity Sensors
shorter cabinets
PDUs that are 75”H (1905 mm) must be placed in 45U or taller RELATED PRODUCTS
cabinets • Input Power Cords
Rack/Cabinet Not included with PDU, order separately
• Mounting Brackets
Mounting Brackets Included with most CPI Cabinets, check cabinet specifications
• Power IQ® for eConnect Software
2 Chatsworth Products
PRODUCT DATA SHEET Monitored Pro eConnect® PDU
ORDERING INFORMATION
Monitored Pro Vertical eConnect PDUs
Part Number Input Output Dimensions - in (mm)
Locking Standard Breakers
Amp kW* Plug Outlets H*** W D
Outlet Outlet (Hydraulic Magnetic)
100-240 Volt, Single-Phase Input - Worldwide
L4-1A1A1 P4-1A1A1 16/20 1
3.6**** C20 Inlet** 1 x 2P 20A (24) C13 70.5 (1791) 2.2 (56) 2.2 (56)
L4-1A1C3 P4-1A1C3 16/201 3.6**** C20 Inlet** 1 x 2P 20A (18) C13, (6) C19 70.5 (1791) 2.2 (56) 2.2 (56)
120 Volt, Single-Phase Input - North America Models
N/A P4-1A1A5 20 1.9* C20 Inlet** 1 x 2P 20A (24) 5-20R 70.5 (1791) 2.2 (56) 2.2 (56)
N/A P4-1C0A5 20 1.9* L5-20P 1 x 2P 20A (24) 5-20R 70.5 (1791) 2.2 (56) 2.2 (56)
N/A P4-1D0A5 30 2.8* L5-30P 2 x 2P 20A (24) 5-20R 70.5 (1791) 2.2 (56) 2.2 (56)
208 Volt, Single-Phase Input - North America Models
L4-1E0A1 P4-1E0A1 20 3.3* L6-20P 1 x 2P 20A (24) C13 70.5 (1791) 2.2 (56) 2.2 (56)
L4-1E0C3 P4-1E0C3 20 3.3* L6-20P 1 x 2P 20A (18) C13, (6) C19 70.5 (1791) 2.2 (56) 2.2 (56)
L4-1F0A1 P4-1F0A1 30 4.9* L6-30P 2 x 2P 20A (24) C13 70.5 (1791) 2.2 (56) 2.2 (56)
L4-1F0B1 P4-1F0B1 30 4.9* L6-30P 2 x 2P 20A (36) C13 70.5 (1791) 2.2 (56) 2.2 (56)
L4-1F0C3 P4-1F0C3 30 4.9* L6-30P 2 x 2P 20A (18) C13, (6) C19 70.5 (1791) 2.2 (56) 2.2 (56)
L4-1F0G3 P4-1F0G3 30 4.9* L6-30P 2 x 2P 20A (30) C13, (6) C19 70.5 (1791) 2.2 (56) 2.2 (56)
120/208 Volt, Three-Phase Input - North America Models
N/A P4-1N0A5 20 5.7* L21-20P 3 x 2P 20A (24) 5-20R 70.5 (1791) 2.2 (56) 2.2 (56)
L4-1N0B1 P4-1N0B1 20 5.7* L21-20P 3 x 2P 20A (36) C13 70.5 (1791) 2.2 (56) 2.2 (56)
L4-1N0G3 P4-1N0G3 20 5.7* L21-20P 3 x 2P 20A (30) C13, (6) C19 70.5 (1791) 2.2 (56) 2.2 (56)
N/A P4-1P0A5 30 5.7* L21-30P 3 x 2P 20A (24) 5-20R 70.5 (1791) 2.2 (56) 2.2 (56)
L4-1P0B1 P4-1P0B1 30 8.6* L21-30P 3 x 2P 20A (36) C13 70.5 (1791) 2.2 (56) 2.2 (56)
L4-1P0F3 P4-1P0F3 30 8.6* L21-30P 3 x 2P 20A (24) C13, (12) C19 70.5 (1791) 2.2 (56) 2.2 (56)
L4-1P0G3 P4-1P0G3 30 8.6* L21-30P 3 x 2P 20A (30) C13, (6) C19 70.5 (1791) 2.2 (56) 2.2 (56)
208 Volt, Three-Phase Input- North America Models
N/A P4-1L0B1 20 5.7* L15-20P 3 x 2P 20A (36) C13 70.5 (1791) 2.2 (56) 2.2 (56)
N/A P4-1L0G3 20 5.7* L15-20P 3 x 2P 20A (30) C13, (6) C19 70.5 (1791) 2.2 (56) 2.2 (56)
L4-1M0B1 P4-1M0B1 30 8.6* L15-30P 3 x 2P 20A (36) C13 70.5 (1791) 2.2 (56) 2.2 (56)
L4-1M0F3 P4-1M0F3 30 8.6* L15-30P 3 x 2P 20A (24) C13, (12) C19 70.5 (1791) 2.2 (56) 2.2 (56)
L4-1M0G3 P4-1M0G3 30 8.6* L15-30P 3 x 2P 20A (30) C13, (6) C19 70.5 (1791) 2.2 (56) 2.2 (56)
L4-1T0B1 P4-1T0B1 50 9.9* CS8365C 3 x 2P 20A (36) C13 70.5 (1791) 2.2 (56) 2.2 (56)
L4-1T0F3 P4-1T0F3 50 9.9* CS8365C 3 x 2P 20A (24) C13, (12) C19 70.5 (1791) 2.2 (56) 2.2 (56)
L4-3U0H3 P4-3U0H3 50 14.3* CS8365C 6 x 2P 20A (36) C13, (6) C19 75.0 (1905) 2.7 (69) 2.2 (56)
L4-3U0V3 P4-3U0V3 50 14.3* CS8365C 6 x 2P 20A (12) C13, (18) C19 75.0 (1905) 2.7 (69) 2.2 (56)
L4-3V0F3 N/A 60 17.2* IEC 60A 3P+E 6 x 2P 20A (24) C13, (12) C19 75.0 (1905) 2.7 (69) 2.2 (56)
L4-3V0H3 P4-3V0H3 60 17.2* IEC 60A 3P+E 6 x 2P 20A (36) C13, (6) C19 75.0 (1905) 2.7 (69) 2.2 (56)
L4-3V0V3 P4-3V0V3 60 17.2* IEC 60A 3P+E 6 x 2P 20A (12) C13, (18) C19 75.0 (1905) 2.7 (69) 2.2 (56)
240/415 Volt, Three-Phase Input - North America Models
N/A P4-1Q0B1 20 11.4* L22-20P 3 x 2P 20A (36) C13 70.5 (1791) 2.2 (56) 2.2 (56)
N/A P4-1Q0G3 20 11.4* L22-20P 3 x 2P 20A (30) C13, (6) C19 70.5 (1791) 2.2 (56) 2.2 (56)
L4-2R0F3 P4-2R0F3 30 17.2* L22-30P 6 x 1P 20A (24) C13, (12) C19 72.0 (1829) 2.35 (60) 2.2 (56)
L4-2R0H3 P4-2R0H3 30 17.2* L22-30P 6 x 1P 20A (36) C13, (6) C19 72.0 (1829) 2.35 (60) 2.2 (56)
Notes: Order mounting brackets separately. On Single-Phase PDUs, output voltage equals input voltage. On Three-Phase PDUs, 208 VAC nominal output through C13 and C19 outlets; 120 VAC nominal output
through NEMA 5-20R outlets.
1
Amperage: 20A within North America and 16A Outside of North America.
* For kW column, all values are derated calculations per UL for use in North America. The Input Amp column lists the maximum rated value of the Input Plug/inlet and circuit breaker rating. UL/NEC
regulatory code requires current ratings on product labels to be derated to 80% of the maximum rated values (for example: 20 Amp = 16 Amp on UL product label). For the Input kW column, all values are derated
calculations per UL for use in North America.
** Order power cord separately for PDUs with C20 input.
*** PDUs that are 72”H (1829 mm) must be placed in 44U or taller CPI cabinets. PDUs that are 75”H (1905 mm) must be placed in 45U or taller CPI cabinets.
**** Capacity when used at 230V with a 16A power cord. Actual capacity will vary if connected to lower voltage or to a lower amperage input plug.
3 Chatsworth Products
PRODUCT DATA SHEET Monitored Pro eConnect® PDU
ORDERING INFORMATION
For detailed, model-specific dimensions and technical specification information, download the cut sheet for your selected PDU part number by
entering it into the CPI website search field at the top right corner of our website: www.chatsworth.com
4 Chatsworth Products
PRODUCT DATA SHEET Monitored Pro eConnect® PDU
ACCESSORIES
POWER CORD PLUG TABLE: PDU Input Power Cord, 110-125 VAC,
17763-002 3 (1.4)
IEC C19 Connector to NEMA 5-15P Plug, 8’2”L (2.4 m)
Locking NEMA L5-15P NEMA L5-20P NEMA L6-15P NEMA L6-20P
(Single-Phase) PDU Input Power Cord, 110-125 VAC,
17763-003 3 (1.4)
IEC C19 Connector to NEMA 5-20P Plug, 8’2”L (2.4 m)
PDU Input Power Cord, 200-240 VAC,
17763-004 3 (1.4)
110-125VAC/15A 110-125VAC/20A 200-240VAC/15A 200-240VAC/20A IEC C19 Connector to NEMA 6-15P Plug, 8’2”L (2.4 m)
Straight NEMA 5-15P NEMA 5-20P NEMA 6-15P NEMA 6-20P
Plugs PDU Input Power Cord, 200-240 VAC,
17763-005 3 (1.4)
IEC C19 Connector to NEMA 6-20P Plug, 8’2”L (2.4 m)
PDU Input Power Cord, 110-125 VAC,
17763-006 3 (1.4)
IEC C19 Connector to NEMA L5-15P Plug, 10’L (3 m)
110-125VAC/15A 110-125VAC/20A 200-240VAC/15A 200-240VAC/20A
IEC Plugs PDU Input Power Cord, 110-125 VAC,
17763-007 3 (1.4)
IEC C19 Connector to NEMA L5-20P Plug, 10’L (3 m)
PDU Input Power Cord, 200-240 VAC,
17763-008 3 (1.4)
EC 60320 C-19/C-20 IEC 16A 1P+N+E
IEC C19 Connector to NEMA L6-15P Plug, 10’L (3 m)
110-240VAC/20A 200-240 VAC/16A PDU Input Power Cord, 200-240 VAC,
17763-009 3 (1.4)
IEC C19 Connector to NEMA L6-20P Plug, 10’L (3 m)
Environmental Probe with Temperature and PDU Input Power Cord, 200-240 VAC,
Humidity Sensor 17763-010 3 (1.4)
IEC C19 Connector to IEC 16A 2P+E Plug, 10’L (3 m)
Monitored eConnect PDUs include a single external
connection that can attach up to two Environmental (2) Environmental Probes with
Probes using a splitter. When attached, the PDU will 17761-003 (1) Temperature and (1) Humidity Sensor Kit with splitter 1 (0.5)
report temperature and humidity measurements for each 72"L (1828 mm) x 2”H (50 mm) x 2”W (50 mm)
probe on the local display and remotely through the Environmental Probe with
17761-002 built-in web interface. 17761-001 (1) Temperature and (1) Humidity Sensor 1 (0.5)
• Sold individually or in a kit with two probes and a 72"L (1828 mm) x 1”H (25 mm) x 1”W (25 mm)
splitter
• Each probe is a combination temperature and humidity Environmental Probe Splitter 6”L
17761-002 1 (0.5)
sensor with attached 6'L (1.8 m) cord, allowing the (152 mm) x 2”H (50 mm) x 2”W (50 mm)
sensor to be positioned appropriately within the Note: Splitter is required when attaching two probes together.
cabinet
Additional Accessories
Shipping
Part
Description Weight
Number
lb (kg)
17762-003 Cord Retention Tethers, Pack of 50 1 (0.5)
17762-003 17762-002 17762-002 Ground Wire Kit 1 (0.5)
17762-001 Tool-less Mounting Hardware Kit, Pack of 2 1 (0.5)
Mounting Bracket Kit for F-Series TeraFrame Gen 3
39110-C01 2 (0.9)
Cabinet or GF-Series GlobalFrame Gen 2 Cabinet System
Mounting Bracket Kit for F-Series TeraFrame Gen 2
13780-C01 2 (0.9)
Cabinet System
Mounting Bracket Kit for GF-Series GlobalFrame Gen 1
25140-701 2 (0.9)
39110-C01 13780-C01
Cabinet System
Mounting Bracket Kit for M-Series MegaFrame Cabinet or
13762-701 2 (0.9)
C-Series SlimFrame Cabinet System
35700-701 Mounting Bracket Kit for Rack Systems 2 (0.9)
Note: Each PDU includes Cord Retention Tethers, Ground Wire Kit and Tool-less Mounting Hardware.
They are listed as Service Parts. Mounting Brackets are included with CPI Cabinet Systems.
25140-701 13762-701
5 Chatsworth Products
PRODUCT DATA SHEET Monitored Pro eConnect® PDU
ORDERING INFORMATION
Single-Phase/ Receptacles/
Locking Outlets
NEMA L5-20P NEMA L5-30P NEMA L6-20P NEMA L6-30P NEMA 5-20R IEC C13 IEC C19
110-125 VAC/20A 110-125 VAC/30A 200-240 VAC/20A 200-240 VAC/30A 120 VAC/20A UL: 120/208VAC/15A UL: 120/208VAC/20A
CE: 208VAC/10A CE: 208VAC/16A
Split-Phase/
Locking
Three-Phase/
Locking
NEMA L15-20P NEMA L15-30P NEMA L21-20P NEMA L21-30P NEMA L22-20P NEMA L22-30P 50A CS8365C
208 VAC/20A 208 VAC/30A 120/208 VAC/20A 120/208 VAC/30A 380/415 VAC/20A 380/415 VAC/30A 208 VAC/50A*
Power Inlet
Universal/
Locking
IEC C20 IEC C20 IEC 16A 1P+N+E IEC 32A 1P+N+E IEC 16A 3P+N+E IEC 32A 3P+N+E
110/125 VAC/20A 200/240 VAC/20A 200/240 VAC/16A 200/240 VAC/32A 230/400 VAC/16A 230/400 VAC/32A
* Note: 50A CS8365C is rated for 50A, but maximum input is 35A on three breaker PDUs.
power
Integrate power management, environmental monitoring
and cabinet access control under a single network
connection, one user interface and one user database for
dramatically reduced deployment savings. Fully
compatible with DCIM software. Available on vertical Order Locks and PDUs
Monitored, Monitored Pro, Switched and Switched Pro
eConnect PDUs. preinstalled to your cabinet.
Shipping
Add power. Make it easy.
Part
Description Weight
Number Simplify ordering, shipping and installation by
lb (kg)
requesting eConnect PDUs and eConnect EAC
36650-001 eConnect EAC Smart Card Kit 3 (1.4)
to be installed in CPI's GF-Series GlobalFrame
36652-001 eConnect EAC Sensor Kit 1 (0.5)
or F-Series TeraFrame Cabinets before they leave
36651-001 eConnect EAC Wire Harness Kit 1 (0.5)
the factory. Go to the Product Configurator
36653-001 RF IDeas EAC Smart Card Reader 1 (0.5) to configure a cabinet with locks and PDUs
36654-001 eConnect EAC Smart Cards 1 (0.5) preinstalled.
While every effort has been made to ensure the accuracy of all information, CPI does not accept liability for any errors or omissions
and reserves the right to change information and descriptions of listed services and products.
©2017 Chatsworth Products, Inc. All rights reserved. Chatsworth Products, CPI, CPI Passive Cooling, eConnect, RMR, MegaFrame,
Saf-T-Grip, SeismicFrame, SlimFrame, TeraFrame, GlobalFrame, CUBE-iT PLUS, Evolution, OnTrac, QuadraRack and Velocity are feder-
ally registered trademarks of Chatsworth Products. Simply Efficient, Secure Array, EuroFrame, Clik-Nut and Motive are trademarks of
Chatsworth Products. All other trademarks belong to their respective companies. Rev.11 03/17 MKT-60020-544