Sei sulla pagina 1di 11

Level 12

Ward - Top O2 A4 VAC

Outside Diameter (mm) 15 15 15 15 - 15 15 15 15 - 15 22 28 35 -

Pipeline Pressure (kPa) 400 400 400 400 - 400 400 400 400 - 59 59 59 59 -

Measure Length of Pipe 4 10 120 30 - 4 10 120 30 - 4 10 120 30 -


(m)
Nearest Length of Pipe 8 15 122 30 - 8 15 122 30 - 8 15 122 30 -
from Table A1 (m)

Design Flow (L/min) 10 10 58 136 - 20 20 40 72.5 - 40 40 40 40 -

Nearest Flow from Table


A1 (L/min) 579 391 119 263 - 579 391 119 263 - 59 116 71 288 -

Pressure Drop from Table 7 7 7 7 - 7 7 7 7 - 1.3 1.3 1.3 1.3 -


A1 (kPa)
Pressure Drop across the 0.00 0.00 1.64 1.87 - 0.00 0.01 0.78 0.53 - 0.30 0.10 0.41 0.03 -
Pipe (kPa)
Percentage of Pressure 0.00 0.00 0.41 0.47 - 0.88 0.00 0.00 0.19 0.13 - 0.33 0.51 0.17 0.69 0.04 - 1.41
Drop (%)

Ward - Bottom O2 A4 VAC

Outside Diameter (mm) 15 15 15 15 - 15 15 15 15 - 15 22 28 35 -

Pipeline Pressure (kPa) 400 400 400 400 - 400 400 400 400 - 59 59 59 59 -

Measure Length of Pipe 4 10 60 30 - 4 10 60 30 - 4 10 60 30 -


(m)
Nearest Length of Pipe
from Table A1 (m) 8 15 61 30 - 8 15 61 30 - 8 15 61 30 -

Design Flow (L/min) 10 10 82 136 - 20 20 50 72.5 - 40 40 40 40 -

Nearest Flow from Table 579 391 177 263 - 579 391 177 263 - 59 116 106 288 -
A1 (L/min)
Pressure Drop from Table 7 7 7 7 - 7 7 7 7 - 1.3 1.3 1.3 1.3 -
A1 (kPa)
Pressure Drop across the 0.00 0.00 1.48 1.87 - 0.00 0.01 0.55 0.53 - 0.30 0.10 0.18 0.03 -
Pipe (kPa)
Percentage of Pressure 0.00 0.00 0.37 0.47 - 0.84 0.00 0.00 0.14 0.13 - 0.27 0.51 0.17 0.31 0.04 - 1.03
Drop (%)
Level 7 - 11
Ward - Top O2 A4 VAC

Outside Diameter (mm) 15 15 22 22 - 15 15 15 15 - 15 22 35 35 -

Pipeline Pressure (kPa) 400 400 400 400 - 400 400 400 400 - 59 59 59 59 -

Measure Length of Pipe 4 10 120 30 - 4 10 120 30 - 4 10 120 30 -


(m)
Nearest Length of Pipe 8 15 122 30 - 8 15 122 30 - 8 15 122 30 -
from Table A1 (m)

Design Flow (L/min) 20 20 160 292 - 40 40 82.5 137.5 - 80 80 80 80 -

Nearest Flow from Table


A1 (L/min) 579 391 349 349 - 579 391 119 263 - 59 116 130 288 -

Pressure Drop from Table 7 7 7 7 - 7 7 7 7 - 1.3 1.3 1.3 1.3 -


A1 (kPa)
Pressure Drop across the 0.00 0.01 1.45 4.90 - 0.02 0.05 3.31 1.91 - 1.20 0.41 0.48 0.10 -
Pipe (kPa)
Percentage of Pressure 0.00 0.00 0.36 1.23 - 1.59 0.00 0.01 0.83 0.48 - 1.32 2.03 0.70 0.82 0.17 - 3.71
Drop (%)

Ward - Bottom O2 A4 VAC

Outside Diameter (mm) 15 15 15 22 - 15 15 15 15 - 15 22 35 35 -

Pipeline Pressure (kPa) 400 400 400 400 - 400 400 400 400 - 59 59 59 59 -

Measure Length of Pipe 4 10 60 30 - 4 10 60 30 - 4 10 60 30 -


(m)
Nearest Length of Pipe
from Table A1 (m) 8 15 61 30 - 8 15 61 30 - 8 15 61 30 -

Design Flow (L/min) 20 20 136 292 - 40 40 72.5 137.5 - 80 80 80 80 -

Nearest Flow from Table 579 391 177 349 - 579 391 177 263 - 59 116 193 288 -
A1 (L/min)
Pressure Drop from Table 7 7 7 7 - 7 7 7 7 - 1.3 1.3 1.3 1.3 -
A1 (kPa)
Pressure Drop across the 0.00 0.01 4.06 4.90 - 0.02 0.05 1.16 1.91 - 1.20 0.41 0.22 0.10 -
Pipe (kPa)
Percentage of Pressure 0.00 0.00 1.02 1.23 - 2.25 0.00 0.01 0.29 0.48 - 0.78 2.03 0.70 0.37 0.17 - 3.27
Drop (%)
Level 6
Ward - Top O2 A4 VAC

Outside Diameter (mm) 15 15 22 22 - 15 15 22 22 - 15 22 35 42 -

Pipeline Pressure (kPa) 400 400 400 400 - 400 400 400 400 - 59 59 59 59 -

Measure Length of Pipe 4 10 120 30 - 4 10 120 30 - 4 10 120 30 -


(m)
Nearest Length of Pipe 8 15 122 30 - 8 15 122 30 - 8 15 122 30 -
from Table A1 (m)

Design Flow (L/min) 20 20 196 282.5 - 40 40 97.5 857.5 - 80 80 80 200 -

Nearest Flow from Table


A1 (L/min) 579 391 349 768 - 579 391 349 768 - 59 116 130 488 -

Pressure Drop from Table 7 7 7 7 - 7 7 7 7 - 1.3 1.3 1.3 1.3 -


A1 (kPa)
Pressure Drop across the 0.00 0.01 2.17 0.95 - 0.02 0.05 0.54 8.73 - 1.20 0.41 0.48 0.22 -
Pipe (kPa)
Percentage of Pressure 0.00 0.00 0.54 0.24 - 0.78 0.00 0.01 0.13 2.18 - 2.33 2.03 0.70 0.82 0.37 - 3.92
Drop (%)

Ward - Bottom O2 A4 VAC

Outside Diameter (mm) 15 15 22 22 - 15 15 22 22 - 15 22 35 42 -

Pipeline Pressure (kPa) 400 400 400 400 - 400 400 400 400 - 59 59 59 59 -

Measure Length of Pipe 4 10 60 30 - 4 10 60 30 - 4 10 60 30 -


(m)
Nearest Length of Pipe
from Table A1 (m) 8 15 61 30 - 8 15 61 30 - 8 15 61 30 -

Design Flow (L/min) 20 20 196 282.5 - 40 40 97.5 857.5 - 80 80 80 200 -

Nearest Flow from Table 579 391 518 349 - 579 391 518 768 - 59 116 193 488 -
A1 (L/min)
Pressure Drop from Table 7 7 7 7 - 7 7 7 7 - 1.3 1.3 1.3 1.3 -
A1 (kPa)
Pressure Drop across the 0.00 0.01 0.99 4.59 - 0.02 0.05 0.24 8.73 - 1.20 0.41 0.22 0.22 -
Pipe (kPa)
Percentage of Pressure 0.00 0.00 0.25 1.15 - 1.40 0.00 0.01 0.06 2.18 - 2.26 2.03 0.70 0.37 0.37 - 3.47
Drop (%)

Ward - Bottom HDU O2 A4 VAC

Outside Diameter (mm) 15 15 22 - - 15 22 22 - - 15 35 42 - -

Pipeline Pressure (kPa) 400 400 400 - - 400 400 400 - - 59 59 59 - -

Measure Length of Pipe 4 57.5 30 - - 4 57.5 30 - - 4 57.5 30 - -


(m)
Nearest Length of Pipe 8 61 30 - - 8 61 30 - - 8 61 30 - -
from Table A1 (m)

Design Flow (L/min) 10 46 282.5 - - 80 400 857.5 - - 40 120 200 - -

Nearest Flow from Table 579 177 768 - - 579 518 768 - - 59 193 488 - -
A1 (L/min)
Pressure Drop from Table 7 7 7 - - 7 7 7 - - 1.3 1.3 1.3 - -
A1 (kPa)
Pressure Drop across the 0.00 0.45 0.95 - - 0.07 3.93 8.73 - - 0.30 0.47 0.22 - -
Pipe (kPa)
Percentage of Pressure 0.00 0.11 0.24 - - 0.35 0.02 0.98 2.18 - - 3.18 0.51 0.80 0.37 - - 1.68
Drop (%)
Level 5
Dialysis O2 A4 VAC

Outside Diameter (mm) 15 15 15 15 15 15 15 15 15 15 15 28 42 54 54

Pipeline Pressure (kPa) 400 400 400 400 400 400 400 400 400 400 59 59 59 59 59

Measure Length of Pipe


5 12 75 40 10 5 12 75 40 10 5 12 75 40 10
(m)
Nearest Length of Pipe
8 15 91 61 15 8 15 91 61 15 8 15 91 61 15
from Table A1 (m)

Design Flow (L/min) 10 16 35.5 153.5 303.5 20 30 62.5 127.5 217.5 40 80 210 430 710

Nearest Flow from Table


579 391 140 177 391 579 391 140 177 391 59 236 260 674 1480
A1 (L/min)
Pressure Drop from Table
A1 (kPa) 7 7 7 7 7 7 7 7 7 7 1.3 1.3 1.3 1.3 1.3

Pressure Drop across the


Pipe (kPa) 0.00 0.01 0.37 3.45 2.81 0.01 0.03 1.15 2.38 1.44 0.37 0.12 0.70 0.35 0.20

Percentage of Pressure
Drop (%) 0.00 0.00 0.09 0.86 0.70 1.66 0.00 0.01 0.29 0.60 0.36 1.25 0.63 0.20 1.18 0.59 0.34 2.95

Recovery Ward O2 A4 VAC

Outside Diameter (mm) 15 15 15 15 15 15 15 15 15 15 15 28 42 54 54

Pipeline Pressure (kPa) 400 400 400 400 400 400 400 400 400 400 59 59 59 59 59

Measure Length of Pipe 5 15 30 40 10 5 15 30 40 10 5 15 30 40 10


(m)
Nearest Length of Pipe 8 15 30 61 15 8 15 30 61 15 8 15 30 61 15
from Table A1 (m)

Design Flow (L/min) 10 22 118 153.5 303.5 20 25 65 127.5 217.5 40 60 220 430 710

Nearest Flow from Table 579 391 263 177 391 579 391 263 177 391 59 236 488 674 1480
A1 (L/min)
Pressure Drop from Table 7 7 7 7 7 7 7 7 7 7 1.3 1.3 1.3 1.3 1.3
A1 (kPa)
Pressure Drop across the
0.00 0.02 1.41 3.45 2.81 0.01 0.03 0.43 2.38 1.44 0.37 0.08 0.26 0.35 0.20
Pipe (kPa)
Percentage of Pressure
0.00 0.01 0.35 0.86 0.70 1.92 0.00 0.01 0.11 0.60 0.36 1.07 0.63 0.14 0.45 0.59 0.34 2.15
Drop (%)

Operating Theatre O2 A4 VAC N2O A7

Outside Diameter (mm) 15 15 15 15 15 15 15 15 15 15 15 28 42 42 54 15 15 15 15 15 15 22 22 22 22

Pipeline Pressure (kPa) 400 400 400 400 400 400 400 400 400 400 59 59 59 59 59 400 400 400 400 400 700 700 700 700 700

Measure Length of Pipe


5 28 38 15 10 5 28 38 15 10 5 28 38 15 10 5 28 38 15 10 5 28 38 15 10
(m)
Nearest Length of Pipe
8 30 61 15 15 8 30 61 15 15 8 30 61 15 15 8 30 61 15 15 8 30 61 15 15
from Table A1 (m)

Design Flow (L/min) 100 110 120 150 303.5 40 50 60 90 217.5 40 120 160 280 710 15 21 27 45 45 350 525 700 787.5 787.5

Nearest Flow from Table


579 263 177 391 579 579 263 177 391 579 59 159 328 724 1480 579 263 177 391 579 759 1009 682 1488 1488
A1 (L/min)
Pressure Drop from Table
7 7 7 7 7 7 7 7 7 7 1.3 1.3 1.3 1.3 1.3 7 7 7 7 7 7 7 7 7 7
A1 (kPa)
Pressure Drop across the
Pipe (kPa) 0.13 1.14 2.00 1.03 1.28 0.02 0.24 0.50 0.37 0.66 0.37 0.69 0.19 0.19 0.20 0.00 0.04 0.10 0.09 0.03 0.93 1.77 4.59 1.96 1.31

Percentage of Pressure
Drop (%) 0.03 0.29 0.50 0.26 0.32 1.40 0.01 0.06 0.13 0.09 0.16 0.45 0.63 1.17 0.33 0.33 0.34 2.80 0.00 0.01 0.03 0.02 0.01 0.07 0.13 0.25 0.66 0.28 0.19 1.51
Level 4
Opthalmology O2 A4 VAC

Outside Diameter (mm) 15 15 15 - - 15 15 15 - - 15 22 28 - -

Pipeline Pressure (kPa) 400 400 400 - - 400 400 400 - - 59 59 59 - -

Measure Length of Pipe 5 30 22 - - 5 30 22 - - 5 30 22 - -


(m)
Nearest Length of Pipe 8 30 30 - - 8 30 30 - - 8 30 30 - -
from Table A1 (m)

Design Flow (L/min) 10 11.5 27.5 - - 20 22.5 142.5 - - 40 50 130 - -

Nearest Flow from Table


A1 (L/min) 579 263 263 - - 579 263 263 - - 59 78 158 - -

Pressure Drop from Table 7 7 7 - - 7 7 7 - - 1.3 1.3 1.3 - -


A1 (kPa)
Pressure Drop across the 0.00 0.01 0.06 - - 0.01 0.05 1.51 - - 0.37 0.53 0.65 - -
Pipe (kPa)
Percentage of Pressure 0.00 0.00 0.01 - - 0.02 0.00 0.01 0.38 - - 0.39 0.63 0.91 1.09 - - 2.63
Drop (%)

Aesthetics O2 A4 VAC

Outside Diameter (mm) 15 15 15 15 15 15 15 15 15 15 15 22 28 28 28

Pipeline Pressure (kPa) 400 400 400 400 400 400 400 400 400 400 59 59 59 59 59

Measure Length of Pipe 5 13 12 33 10 5 13 12 33 10 5 13 12 33 10


(m)
Nearest Length of Pipe
from Table A1 (m) 8 15 15 61 15 8 15 15 61 15 8 15 15 61 15

Design Flow (L/min) 10 13 16 16 27.5 20 25 30 30 52.5 40 60 80 80 130

Nearest Flow from Table 579 579 579 579 177 579 579 579 579 177 59 116 236 106 236
A1 (L/min)
Pressure Drop from Table 7 7 7 7 7 7 7 7 7 7 1.3 1.3 1.3 1.3 1.3
A1 (kPa)
Pressure Drop across the 0.00 0.00 0.00 0.00 0.11 0.01 0.01 0.02 0.01 0.41 0.37 0.30 0.12 0.40 0.26
Pipe (kPa)
Percentage of Pressure 0.00 0.00 0.00 0.00 0.03 0.03 0.00 0.00 0.00 0.00 0.10 0.11 0.63 0.51 0.20 0.68 0.45 2.47
Drop (%)
Level 3
Chemotherapy O2 A4 VAC

Outside Diameter (mm) 15 15 15 15 15 15 15 15 15 15 15 28 42 54 54

Pipeline Pressure (kPa) 400 400 400 400 400 400 400 400 400 400 59 59 59 59 59

Measure Length of Pipe 5 12.5 97 12 10 5 12.5 97 12 10 5 12.5 97 12 10


(m)
Nearest Length of Pipe 8 15 122 15 15 8 15 122 15 15 8 15 122 15 15
from Table A1 (m)

Design Flow (L/min) 10 16 38.5 56 111 20 30 67.5 100 220 40 80 230 320 720

Nearest Flow from Table


A1 (L/min) 579 391 119 391 391 579 391 119 391 391 59 236 220 1480 1480

Pressure Drop from Table 7 7 7 7 7 7 7 7 7 7 1.3 1.3 1.3 1.3 1.3


A1 (kPa)
Pressure Drop across the 0.00 0.01 0.58 0.11 0.38 0.01 0.03 1.79 0.37 1.48 0.37 0.12 1.13 0.05 0.21
Pipe (kPa)
Percentage of Pressure 0.00 0.00 0.15 0.03 0.09 0.27 0.00 0.01 0.45 0.09 0.37 0.92 0.63 0.21 1.91 0.08 0.35 3.19
Drop (%)

Recovery Ward O2 A4 VAC

Outside Diameter (mm) 15 15 15 15 15 15 15 15 15 15 15 28 42 54 54

Pipeline Pressure (kPa) 400 400 400 400 400 400 400 400 400 400 59 59 59 59 59

Measure Length of Pipe 5 17 58 8 10 5 17 58 8 10 5 17 58 8 10


(m)
Nearest Length of Pipe
from Table A1 (m) 8 30 61 8 15 8 30 61 8 15 8 30 61 8 15

Design Flow (L/min) 10 13 46 63.5 111 20 25 80 112.5 220 40 60 280 370 720

Nearest Flow from Table 579 263 177 579 391 579 263 177 579 391 59 159 328 2191 1480
A1 (L/min)
Pressure Drop from Table 7 7 7 7 7 7 7 7 7 7 1.3 1.3 1.3 1.3 1.3
A1 (kPa)
Pressure Drop across the 0.00 0.01 0.45 0.08 0.38 0.01 0.04 1.36 0.26 1.48 0.37 0.10 0.90 0.04 0.21
Pipe (kPa)
Percentage of Pressure 0.00 0.00 0.11 0.02 0.09 0.23 0.00 0.01 0.34 0.07 0.37 0.79 0.63 0.18 1.53 0.06 0.35 2.75
Drop (%)
Level 2
Internal Med O2 A4 VAC

Outside Diameter (mm) 15 15 15 15 15 15 15 15 15 15 15 28 28 35 35

Pipeline Pressure (kPa) 400 400 400 400 400 400 400 400 400 400 59 59 59 59 59

Measure Length of Pipe 5 60 18 28 15 5 60 18 28 15 5 60 18 28 15


(m)
Nearest Length of Pipe 8 61 30 30 15 8 61 30 30 15 8 61 30 30 15
from Table A1 (m)

Design Flow (L/min) 10 10 21.5 41.5 53 20 20 42.5 82.5 105 40 40 90 170 220

Nearest Flow from Table


A1 (L/min) 579 177 263 263 392 579 177 263 263 392 59 106 159 288 427

Pressure Drop from Table 7 7 7 7 7 7 7 7 7 7 1.3 1.3 1.3 1.3 1.3


A1 (kPa)
Pressure Drop across the 0.00 0.02 0.03 0.16 0.13 0.01 0.09 0.11 0.64 0.50 0.37 0.18 0.25 0.42 0.35
Pipe (kPa)
Percentage of Pressure 0.00 0.01 0.01 0.04 0.03 0.09 0.00 0.02 0.03 0.16 0.13 0.34 0.63 0.31 0.42 0.72 0.58 2.67
Drop (%)

Lab O2 A4 VAC

Outside Diameter (mm) 15 15 15 15 15 15 15 15 15 15 15 22 28 35 35

Pipeline Pressure (kPa) 400 400 400 400 400 400 400 400 400 400 59 59 59 59 59

Measure Length of Pipe 5 17 18 28 15 5 17 18 28 15 5 17 18 28 15


(m)
Nearest Length of Pipe
from Table A1 (m) 8 30 30 30 15 8 30 30 30 15 8 30 30 30 15

Design Flow (L/min) 10 11.5 21.5 41.5 53 20 22.5 42.5 82.5 105 40 50 90 170 220

Nearest Flow from Table 579 263 263 263 391 579 263 263 263 391 59 78 159 288 427
A1 (L/min)
Pressure Drop from Table 7 7 7 7 7 7 7 7 7 7 1.3 1.3 1.3 1.3 1.3
A1 (kPa)
Pressure Drop across the 0.00 0.01 0.03 0.16 0.13 0.01 0.03 0.11 0.64 0.50 0.37 0.30 0.25 0.42 0.35
Pipe (kPa)
Percentage of Pressure 0.00 0.00 0.01 0.04 0.03 0.08 0.00 0.01 0.03 0.16 0.13 0.32 0.63 0.51 0.42 0.72 0.58 2.87
Drop (%)
X-Ray O2 A4 VAC

Outside Diameter (mm) 15 15 15 15 - 15 15 15 15 - 15 22 35 35 -

Pipeline Pressure (kPa) 400 400 400 400 - 400 400 400 400 - 59 59 59 59 -

Measure Length of Pipe 5 30 28 15 - 5 30 28 15 - 5 30 28 15 -


(m)
Nearest Length of Pipe 8 30 30 15 - 8 30 30 15 - 8 30 30 15 -
from Table A1 (m)

Design Flow (L/min) 10 10 41.5 53 - 20 20 82.5 105 - 40 40 170 220 -

Nearest Flow from Table 579 263 263 391 - 579 263 263 391 - 59 78 288 427 -
A1 (L/min)
Pressure Drop from Table
A1 (kPa) 7 7 7 7 - 7 7 7 7 - 1.3 1.3 1.3 1.3 -

Pressure Drop across the 0.00 0.01 0.16 0.13 - 0.01 0.04 0.64 0.50 - 0.37 0.34 0.42 0.35 -
Pipe (kPa)
Percentage of Pressure 0.00 0.00 0.04 0.03 - 0.08 0.00 0.01 0.16 0.13 - 0.30 0.63 0.58 0.72 0.58 - 2.51
Drop (%)

Health Screening O2 A4 VAC

Outside Diameter (mm) 15 15 15 15 - 15 15 15 15 - 15 22 28 35 -

Pipeline Pressure (kPa) 400 400 400 400 - 400 400 400 400 - 59 59 59 59 -

Measure Length of Pipe 5 6 19 15 - 5 6 19 15 - 5 6 19 15 -


(m)
Nearest Length of Pipe 8 8 30 15 - 8 8 30 15 - 8 8 30 15 -
from Table A1 (m)

Design Flow (L/min) 10 10 11.5 53 - 20 20 22.5 105 - 40 40 50 220 -

Nearest Flow from Table 579 579 263 391 - 579 579 263 391 - 59 173 159 427 -
A1 (L/min)
Pressure Drop from Table 7 7 7 7 - 7 7 7 7 - 1.3 1.3 1.3 1.3 -
A1 (kPa)
Pressure Drop across the
Pipe (kPa) 0.00 0.00 0.01 0.13 - 0.01 0.01 0.03 0.50 - 0.37 0.05 0.08 0.35 -

Percentage of Pressure
Drop (%) 0.00 0.00 0.00 0.03 - 0.03 0.00 0.00 0.01 0.13 - 0.14 0.63 0.09 0.14 0.58 - 1.44
Level Basement
Nuclear Medicine O2 A4 VAC

Outside Diameter (mm) 15 15 15 15 15 15 15 15 15 15 15 28 35 35 35

Pipeline Pressure (kPa) 400 400 400 400 400 400 400 400 400 400 59 59 59 59 59

Measure Length of Pipe 5 6 5 56 28 5 6 5 56 28 5 6 5 56 28


(m)
Nearest Length of Pipe 8 8 8 61 30 8 8 8 61 30 8 8 8 61 30
from Table A1 (m)

Design Flow (L/min) 10 10 12 34 68 20 20 30 40 80 40 40 45 50 180

Nearest Flow from Table


A1 (L/min) 579 579 579 177 - 579 579 579 177 177 59 350 637 193 193

Pressure Drop from Table 7 7 7 7 - 7 7 7 7 7 1.3 1.3 1.3 1.3 1.3


A1 (kPa)
Pressure Drop across the 0.00 0.00 0.00 0.24 - 0.01 0.01 0.01 0.33 1.33 0.37 0.01 0.00 0.08 1.06
Pipe (kPa)
Percentage of Pressure 0.00 0.00 0.00 0.06 - 0.06 0.00 0.00 0.00 0.08 0.33 0.42 0.63 0.02 0.01 0.14 1.79 2.59
Drop (%)

Radiotheraphy O2 A4 VAC

Outside Diameter (mm) 15 15 15 15 15 15 15 15 15 15 15 22 22 35 35

Pipeline Pressure (kPa) 400 400 400 400 400 400 400 400 400 400 59 59 59 59 59

Measure Length of Pipe 5 7 5 65 28 5 7 5 65 28 5 7 5 65 28


(m)
Nearest Length of Pipe
from Table A1 (m) 8 8 8 91 30 8 8 8 91 30 8 8 8 91 30

Design Flow (L/min) 10 10 12 34 68 20 20 30 40 80 40 40 45 50 180

Nearest Flow from Table 579 579 579 140 263 579 579 579 140 263 59 173 173 153 193
A1 (L/min)
Pressure Drop from Table 7 7 7 7 7 7 7 7 7 7 1.3 1.3 1.3 1.3 1.3
A1 (kPa)
Pressure Drop across the 0.00 0.00 0.00 0.29 0.44 0.01 0.01 0.01 0.41 0.60 0.37 0.06 0.05 0.10 1.06
Pipe (kPa)
Percentage of Pressure 0.00 0.00 0.00 0.07 0.11 0.18 0.00 0.00 0.00 0.10 0.15 0.26 0.63 0.10 0.09 0.17 1.79 2.79
Drop (%)
Nearest Nearest Pressure
Outside Pipeline Measure Length of Design Flow Flow from Drop from
Diameter Pressure Length of Pipe from (L/min) Table A1 Table A1
(mm) (kPa) Pipe (m) Table A1 (L/min) (kPa)
(m)

15 400 5 8 10 579 7
Pressure Percentage
Drop across of Pressure
the Pipe Drop (%)
(kPa)

0.00 0.00