16kV Substation
Parameters Setting for Electric Protection Page |1

1 Introduction

This report gives the functional settings of the protection relays necessary for the operation of the
protection system and for selective clearance of faults.

This report includes the protective functions for the following components:

∂ PT
∂ Incoming Feeder
∂ Pump Feeder
∂ Transformer Feeder
∂ Capacitor Feeder
∂ Bus Coupler

Protection devices are mounted in the cubicles

1910-AH-001 PT -F511/7SJ661

1910-AH-002 INCOMING FEEDER (1000kW) -F511/7SJ661

1910-AH-003 1# PUMP FEEDER (355kW) -F511/7SJ661

1910-AH-007 TRANSFORMER FEEDER (200kVA) -F511/7SJ661

1910-AH-008 CAPACITOR FEEDER (300kVAR) -F511/7SJ661

1920-AH-001 CAPACITOR FEEDER (900kVAR) -F511/7SJ661

1920-AH-002 TRANSFORMER FEEDER (1600kVA) -F511/7SJ661

1920-AH-005 1# INCOMING FEEDER (5800kW) -F511/7SJ661

1920-AH-000 BUS COUPLER -F511/7SJ661

The settings were made with reference to

∂ The single line diagram:


SHOUGANG HIERRO PERU S.A.A.DWG
∂ Data, curves and characteristics of transformers
∂ Relay instruction manuals

For complete settings of the digital protection devices refer to the DIGSI printout of each relay.

Some data were not known during creating this calculation study. Therefore these data and setting
values are marked with single question mark ”?”. These setting values have to be established by
testing at site through the commissioning staff.

For values marked with double question marks ”??” further information is necessary from
CUSTOMER / MANUFACTURER in order to allow correct setting of these parameters.

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection Page |2

The pre-selected values for these settings are common values from other comparable power
plants.

All settings have to be checked and if necessary revised during commissioning at site.

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection Page |3

2 Technical Data

2.1 Busbar

2.1.1 Busbar Data

Rated voltage Un 4.16 kV


Rated current In 2000A
Rated frequency fn 60 Hz
Max. through fault current Issc 40kA

2.1.2 Current Transformer (1910-ER-100)

Rated
Ratio
Index Class output Remarks Function Destination
(A/A)
(VA)

AH-001 PT 27/59 -F511

AH-002 150/1 5P20 10 Incoming Feeder 50/51 -F511

100/1 5P20 10 1# Pump Feeder 50/51,46,49,27/59 -F511


AH-003
100/1 10P10 2.5 1# Pump Feeder 50N/51N -F511

100/1 5P20 10 Transformer Feeder 50/51 -F511


AH-007
100/1 10P10 2.5 Transformer Feeder 50N/51N -F511
50/51
100/1 5P20 10 Capacitor Feeder -F511
AH-008 27/59
100/1 10P10 2.5 Capacitor Feeder 50N/51N -F511

2.1.3 Current Transformer (1920-ER-100)

Rated
Ratio
Index Class output Remarks Function Destination
(A/A)
(VA)
50/51
250/1 5P20 10 Capacitor Feeder -F511
27/59
AH-001
100/1 10P10 2.5 Capacitor Feeder 50N/51N -F511

500/1 5P20 10 Transformer Feeder 50/51 -F511


AH-002
100/1 10P10 2.5 Transformer Feeder 50N/51N -F511

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection Page |4

AH-005 2000/1 5P20 10 Incoming Feeder 50/51 -F511

1000/1 5P20 10 Bus Coupler 50/51N -F511


AH-000

2.1.3 Voltage Transformer

Rated
Core Upr Class output Use Function Destination
(VA)

4.16kV /
3P 100 0.1/ √3 27/59 -F511
√3
4.16kV /
0.5 90 0.1/ √3 Measurement
√3

2.2 Transformer (T)

2.2.1 Transformer Data

Winding Primary Secondary


Rated voltage Un 4.16 kV 0.48 kV
Rated apparent power Sn 200kVA 200kVA
Rated current In
Impedance Voltage uk 4%
Control range of OLTC + +2 * 2.5%
Control range of OLTC - -2 * 2.5%

Vector group Dyn5


Maximum over-excitation (10sec) (U/f)max
Permissive over-excitation capability time t (U/f)max
Permissive overload Imax/IN
Thermal time constant τ

2.2.2 Transformer Data

Winding Primary Secondary


Rated voltage Un 4.16 kV 0.48 kV
Rated apparent power Sn 1600kVA 1600kVA
Rated current In
Impedance Voltage uk 6%
Control range of OLTC + +2 * 2.5%
Control range of OLTC - -2 * 2.5%

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection Page |5

Vector group Dyn5


Maximum over-excitation (10sec) (U/f)max
Permissive over-excitation capability time t (U/f)max
Permissive overload Imax/IN
Thermal time constant τ

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection Page |6

3 Setting for AH001 PT Feeder

3.1 Parameter Setting -F511 7SJ661

3.1.1 Busbar Data

Rated voltage Un 4.16 kV


Rated current In 2000A
Rated frequency fn 60 Hz
Max. through fault current Issc 40kA

3.1.2 Undervoltage Protection 27

1) . 27-1 Pickup Value:

U ; Pickup < 0.9 ≥ U N


< 0.9 ≥ 100 < 90V
2) 27-2 Pickup Value:

U ;; Pickup < 0.85 ≥ U N


< 0.85 ≥ 100 < 85V

DAdr parameter name parameter value unit


5101 Undervoltage Protection Alarm Only [12700]
5001 Overvoltage Protection Alarm Only [12700]
Under Voltage
5102 U< Pickup 90 V
5106 T U< Time Delay 1.5 sec
5110 U<< Pickup 85 V
5112 T U<< Time Delay 0.5 sec
5113A Dropout Ratio U< 1.2
5114A Dropout Ratio U<< 1.2
5120A Current Supervision OFF [23]

3.1.3 Overvoltage Protection 59

1) . 59-1 Pickup Value:

U = Pickup < 1.05 ≥ U N


< 1.05 ≥ 100 < 105V

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection Page |7

2) 59-2 Pickup Value:

U == Pickup < 110 ≥ U N


< 110 ≥ 100 < 110V

DAdr parameter name parameter value unit


5101 Undervoltage Protection Alarm Only [12700]
5001 Overvoltage Protection Alarm Only [12700]
Over Voltage
5002 U> Pickup 105 V
5004 T U> Time Delay 0.5 sec
5005 U>> Pickup 110 V
5007 T U>> Time Delay 0.5 sec
5017A Dropout Ratio U> 0.95
5018A Dropout Ratio U>> 0.95

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection Page |8

4 Setting for 1910-AH-002 Incoming Feeder

4.1 Parameter Setting -F511 7SJ661

4.1.1 Line Data

Un=4.16kV

fn=60Hz

Sn=1000kW

4.1.1 Overcurrent protection (50/51)


I>> coordinate with Transformer feeder:

I == < K ≥ I ==transformer < 1.2 ≥ 832.8 A < 1.2 ≥ 209 < 999.3 A

The secondary setting:

I == 999.3
I == < < ≥ 1A < 6.66 A
nCT 150

Backup protection for the subordinate busbar

KK 1.2 1000
I= < ≥ Ifh. max < ≥ < 196 A
Kf 0.85 3 ≥U N

The secondary setting:

I = 196
I= < < ≥ 1A < 1.3 A
nCT 150

DMT
Ph
Fundamental component
1219A I>>> measurement of [30708]
1216A I>>> active Always [30721]
1217 I>>> Pickup oo A
1218 T I>>> Time Delay 0 sec
1220A I>> measurement of Fundamental component
1214A I>> active Always [12882]

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection Page |9

1202 I>> Pickup 6.66 A


1203 T I>> Time Delay 0 sec
1221A I> measurement of Fundamental component
1204 I> Pickup 1.3 A
1205 T I> Time Delay 0.5 sec

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 10

5 Setting for 1910-AH003 Pump Feeder

5.1 Parameter Setting -F511 7SJ661

5.1.1 Pump Data

355kW

5.1.1 Overcurrent protection (50/51)

PN 355
Ie < < < 58 A
3 ≥ U N ≥ cos Ε 3 ≥ 4.16 ≥ 0.85

High current:(Always enable)

I == < (10.5 , 12) ≥ I e < 11≥ 58 < 638 A

The secondary setting:

I == 638
I == < < ≥ 1A < 6.4 A
nCT 100

Low Current:(Enable when motor finished the starting)

I = < (7.8 , 8) ≥ I e < 8 ≥ 58 A < 464 A

The secondary setting:

I= 464
I= < < ≥ 1A < 4.6 A
nCT 100

DAdr parameter name parameter value unit


DMT Ph
1219A I>>> measurement of Fundamental component [30708]
1216A I>>> active Always [30721]
1217 I>>> Pickup oo A
1218 T I>>> Time Delay 0 sec
1220A I>> measurement of Fundamental component [30708]
1214A I>> active Always [12882]
1202 I>> Pickup 6.4 A
1203 T I>> Time Delay 0 sec

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 11

1221A I> measurement of Fundamental component [30708]


1204 I> Pickup 4.6 A
1205 T I> Time Delay 0 sec

5.1.2 Earth Fault Overcurrent protection (50/51N)

I E = < (0.05 , 0.1) ≥ I e < 0.1 ≥ 58 < 5.8 A

The secondary setting:

I E = 5.8
I E= < < ≥ 1A < 0.06 A
nCT 100

DMT E
1319A IE>>> measurement of Fundamental component [30708]
1316A IE>>> active Always [30722]
1317 IE>>> Pickup oo A
1318 T IE>>> Time Delay 0 sec
1320A IE>> measurement of Fundamental component [30708]
1314A IE>> active Always [12884]
1302 IE>> Pickup oo A
1303 T IE>> Time Delay 0 sec
1321A IE> measurement of Fundamental component [30708]
1304 IE> Pickup 0.06 A
1305 T IE> Time Delay 0.5 sec

5.1.3 Negative sequence protection (46)

I 2== < (0.4 , 0.6) ≥ I e < 0.4 ≥ 58 < 23 A

The secondary setting:

I 2== 23
I 2== < < ≥ 1A < 0.23 A
nCT 100
I2> Alarm

I 2= < (0.1) ≥ I e < 0.1 ≥ 58 < 5.8 A

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 12

I2> The secondary setting:

I 2== 5.8
I 2== < < ≥ 1A < 0.06 A
nCT 100

Unbalance Load (Negative


4001 Sequence) ON [22]
4012A Dropout Time Delay DMT 0 sec
DMT
4002 I2> Pickup 0.23 A
4003 T I2> Time Delay 3 sec
4004 I2>> Pickup 0.06 A
4005 T I2>> Time Delay 10 sec

5.1.4 Thermal Over Load Protection (49)

1) 4202 Parameter K-factor indicates the maximum continuous permissible phase


current.

I_max-current: 1.15In

In 58
K Factor < 1.15 ≥ < 1.15 ≥ < 0.66
Ipn 100
2) Threshold thermal warn:
2
1 ∑ I ⌡ 1
σ <  1s  < ≥ 1002 < 166 min?
60  I maX  60

3) Current warning value is calculated as below,


I_warning current: 1.15In

In 58
I warning < K ≥ < 1.15 ≥ < 0.66 A
Ipn 100
4) The customer can check the motor manufacturing data, then set parameter Thermal
time constant.

4201 Thermal overload protection ON [22]


Therm Over Load
4202 K-Factor 0.66
4203 Time Constant 166 min
4204 Thermal Alarm Stage 90 %

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 13

4205 Current Overload Alarm Setpoint 0.66 A


4207A Kt-FACTOR when motor stops 7
4208A Emergency time 100 sec

5.1.5 Undervoltage Protection 27

1) . 27-1 Pickup Value (Alarm):

U ; Pickup < 0.6 ≥ U N


< 0.6 ≥ 100 < 60V
2) 27-2 Pickup Value(Trip):

U ;; Pickup < (0.45 , 0.5) ≥ U N


< 0.45 ≥ 100 < 45V

DAdr parameter name parameter value unit


5101 Undervoltage Protection Alarm Only [12700]
Under Voltage
5102 U< Pickup 60 V
5106 T U< Time Delay 0.5 sec
5110 U<< Pickup 45 V
5112 T U<< Time Delay 9 sec
5113A Dropout Ratio U< 1.2
5114A Dropout Ratio U<< 1.2
5120A Current Supervision OFF [23]

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 14

6 Setting for 1910-AH007 Transformer Feeder

6.1 Parameter Setting -F511 7SJ661

6.1.1 Transformer Data

Winding Primary Secondary


Rated voltage Un 4.16 kV 0.48 kV
Rated apparent power Sn 200kVA 200kVA
Rated current In
Impedance Voltage uk 4%
Control range of OLTC + +2 * 2.5%
Control range of OLTC - -2 * 2.5%

Vector group Dyn5


Maximum over-excitation (10sec) (U/f)max
Permissive over-excitation capability time t (U/f)max
Permissive overload Imax/IN
Thermal time constant τ

6.1.1 Overcurrent protection (50/51)

1 SN 1 200
I 3 pole max < ≥ < ≥ < 694 A
uk 3 ≥ U N 1 0.04 3 ≥ 4.16

With a safety factor of 20% this gives the primary setting:

I == < 1.2 ≥ I 3 pole max < 1.2 ≥ 694 < 832.8 A

The secondary setting:

I == 832.8
I == < < ≥ 1A < 8.3 A
nCT 100

Backup protection for the subordinate busbar

KK 1.3 SN 200
I= < ≥ Ifh. max < ≥ A < 1.3 ≥ < 36 A
Kf 1 3 ≥U N1 3 ≥ 4.16

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 15

The secondary setting:

I= 36
I= < < ≥ 1A < 0.36 A
nCT 100

DAdr parameter name parameter value unit


DMT Ph
1219A I>>> measurement of Fundamental component [30708]
1216A I>>> active Always [30721]
1217 I>>> Pickup oo A
1218 T I>>> Time Delay 0 sec
1220A I>> measurement of Fundamental component [30708]
1214A I>> active Always [12882]
1202 I>> Pickup 8.3 A
1203 T I>> Time Delay 0 sec
1221A I> measurement of Fundamental component [30708]
1204 I> Pickup 0.36 A
1205 T I> Time Delay 0.5 sec

6.1.2 Earth Fault Overcurrent protection (50/51N)

SN 200
I E = < 0.3 ≥ Ifh. max < 0.3 ≥ < 0.3 ≥ < 8.32 A
3 ≥ U N1 3 ≥ 4.16
The secondary setting:

I E = 8.32
I E= < < ≥ 1A < 0.08 A
nCT 100

DMT E
1319A IE>>> measurement of Fundamental component [30708]
1316A IE>>> active Always [30722]
1317 IE>>> Pickup oo A
1318 T IE>>> Time Delay 0 sec
1320A IE>> measurement of Fundamental component [30708]
1314A IE>> active Always [12884]
1302 IE>> Pickup oo A
1303 T IE>> Time Delay 0 sec
1321A IE> measurement of Fundamental component [30708]
1304 IE> Pickup 0.08 A
1305 T IE> Time Delay 0.5 sec

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 16

7 Setting for 1910-AH008 Capacitor Feeder

7.1 Parameter Setting -F511 7SJ661

7.1.1 Capacitor Data

400kvar

7.1.1 Overcurrent protection (50/51)

PN 400
Ie < < < 55.5 A
3 ≥U N 3 ≥ 4.16

I == < (4 , 5) ≥ I e < 4 ≥ 55.5 < 222 A

The secondary setting:

I == 222
I == < < ≥ 1A < 2.2 A
nCT 100

Backup protection for the max overload current

I = < K K ≥ I e < 1.5 ≥ 55.5 A < 83.2 A

The secondary setting:

I = 83.2
I= < < ≥ 1A < 0.83 A
nCT 100

DAdr parameter name parameter value unit


DMT Ph
1219A I>>> measurement of Fundamental component [30708]
1216A I>>> active Always [30721]
1217 I>>> Pickup oo A
1218 T I>>> Time Delay 0 sec
1220A I>> measurement of Fundamental component [30708]
1214A I>> active Always [12882]
1202 I>> Pickup 2.2 A
1203 T I>> Time Delay 0 sec
1221A I> measurement of Fundamental component [30708]

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 17

1204 I> Pickup 0.83 A


1205 T I> Time Delay 0.3 sec

7.1.2 Earth Fault Overcurrent protection (50/51N)

I E = < (0.1 , 0.2) ≥ I e < 0.1 ≥ 55.5 < 5.55 A

The secondary setting:

I E = 5.55
I E= < < ≥ 1A < 0.05 A
nCT 100

DMT E
1319A IE>>> measurement of Fundamental component [30708]
1316A IE>>> active Always [30722]
1317 IE>>> Pickup oo A
1318 T IE>>> Time Delay 0 sec
1320A IE>> measurement of Fundamental component [30708]
1314A IE>> active Always [12884]
1302 IE>> Pickup oo A
1303 T IE>> Time Delay 0 sec
1321A IE> measurement of Fundamental component [30708]
1304 IE> Pickup 0.05 A
1305 T IE> Time Delay 0.6 sec

7.1.3 Undervoltage Protection 27

1) . 27-1 Pickup Value (Alarm):

U ; Pickup < 0.6 ≥ U N


< 0.6 ≥ 100 < 60V
2) 27-2 Pickup Value(Trip):

U ;; Pickup < (0.2 , 0.5) ≥ U N


< 0.4 ≥ 100 < 40V

DAdr parameter name parameter value unit


5101 Undervoltage Protection Alarm Only [12700]
5001 Overvoltage Protection Alarm Only [12700]
Under Voltage
5102 U< Pickup 60 V

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 18

5106 T U< Time Delay 0.5 sec


5110 U<< Pickup 40 V
5112 T U<< Time Delay 0.5 sec
5113A Dropout Ratio U< 1.2
5114A Dropout Ratio U<< 1.2
5120A Current Supervision ON [23]

7.1.3 Overvoltage Protection 59

1) . 59-1 Pickup Value(Alarm):

U = Pickup < 1.05 ≥ U N


< 1.05 ≥ 100 < 105V
2) 59-2 Pickup Value(Trip):

U == Pickup < 110 ≥ U N


< 110 ≥ 100 < 110V

DAdr parameter name parameter value unit


5101 Undervoltage Protection Alarm Only [12700]
5001 Overvoltage Protection Alarm Only [12700]
Over Voltage
5002 U> Pickup 105 V
5004 T U> Time Delay 1 sec
5005 U>> Pickup 110 V
5007 T U>> Time Delay 5 sec
5017A Dropout Ratio U> 0.95
5018A Dropout Ratio U>> 0.95

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 19

8 Setting for 1920-AH001 Capacitor Feeder

8.1 Parameter Setting -F511 7SJ661

8.1.1 Capacitor Data

1155kvar

8.1.1 Overcurrent protection (50/51)

PN 1155
Ie < < < 160 A
3 ≥U N 3 ≥ 4.16

I == < (4 , 5) ≥ I e < 4 ≥ 160 < 641A

The secondary setting:

I == 641
I == < < ≥ 1A < 2.5 A
nCT 250

Backup protection for the max overload current

I = < K K ≥ I e < 1.5 ≥ 160 A < 240 A

The secondary setting:

I= 240
I= < < ≥ 1A < 0.96 A
nCT 250

DAdr parameter name parameter value unit


DMT Ph
1219A I>>> measurement of Fundamental component [30708]
1216A I>>> active Always [30721]
1217 I>>> Pickup oo A
1218 T I>>> Time Delay 0 sec
1220A I>> measurement of Fundamental component [30708]
1214A I>> active Always [12882]
1202 I>> Pickup 2.5 A
1203 T I>> Time Delay 0 sec
1221A I> measurement of Fundamental component [30708]

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 20

1204 I> Pickup 0.96 A


1205 T I> Time Delay 0.3 sec

8.1.2 Earth Fault Overcurrent protection (50/51N)

I E = < (0.1 , 0.2) ≥ I e < 0.1 ≥ 160 < 16 A

The secondary setting:

I E = 16
I E= < < ≥ 1A < 0.16 A
nCT 100

DMT E
1319A IE>>> measurement of Fundamental component [30708]
1316A IE>>> active Always [30722]
1317 IE>>> Pickup oo A
1318 T IE>>> Time Delay 0 sec
1320A IE>> measurement of Fundamental component [30708]
1314A IE>> active Always [12884]
1302 IE>> Pickup oo A
1303 T IE>> Time Delay 0 sec
1321A IE> measurement of Fundamental component [30708]
1304 IE> Pickup 0.16 A
1305 T IE> Time Delay 0.6 sec

8.1.3 Undervoltage Protection 27

1) . 27-1 Pickup Value (Alarm):

U ; Pickup < 0.6 ≥ U N


< 0.6 ≥ 100 < 60V
2) 27-2 Pickup Value(Trip):

U ;; Pickup < (0.2 , 0.5) ≥ U N


< 0.4 ≥ 100 < 40V

DAdr parameter name parameter value unit


5101 Undervoltage Protection Alarm Only [12700]
5001 Overvoltage Protection Alarm Only [12700]
Under Voltage
5102 U< Pickup 60 V

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 21

5106 T U< Time Delay 0.5 sec


5110 U<< Pickup 40 V
5112 T U<< Time Delay 0.5 sec
5113A Dropout Ratio U< 1.2
5114A Dropout Ratio U<< 1.2
5120A Current Supervision ON [23]

8.1.3 Overvoltage Protection 59

1) . 59-1 Pickup Value(Alarm):

U = Pickup < 1.05 ≥ U N


< 1.05 ≥ 100 < 105V
2) 59-2 Pickup Value(Trip):

U == Pickup < 110 ≥ U N


< 110 ≥ 100 < 110V

DAdr parameter name parameter value unit


5101 Undervoltage Protection Alarm Only [12700]
5001 Overvoltage Protection Alarm Only [12700]
Over Voltage
5002 U> Pickup 105 V
5004 T U> Time Delay 1 sec
5005 U>> Pickup 110 V
5007 T U>> Time Delay 5 sec
5017A Dropout Ratio U> 0.95
5018A Dropout Ratio U>> 0.95

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 22

9 Setting for 1920-AH002 Transformer Feeder

9.1 Parameter Setting -F511 7SJ661

9.1.1 Transformer Data

Winding Primary Secondary


Rated voltage Un 4.16 kV 0.48 kV
Rated apparent power Sn 1600kVA 1600kVA
Rated current In
Impedance Voltage uk 6%
Control range of OLTC + +2 * 2.5%
Control range of OLTC - -2 * 2.5%

Vector group Dyn5


Maximum over-excitation (10sec) (U/f)max
Permissive over-excitation capability time t (U/f)max
Permissive overload Imax/IN
Thermal time constant τ

9.1.1 Overcurrent protection (50/51)

1 SN 1 1600
I 3 pole max < ≥ < ≥ < 3701A
uk 3 ≥ U N 1 0.06 3 ≥ 4.16

With a safety factor of 20% this gives the primary setting:

I == < 1.2 ≥ I 3 pole max < 1.2 ≥ 3701 < 4441A

The secondary setting:

I == 4441
I == < < ≥ 1A < 8.9 A
nCT 500

Backup protection for the subordinate busbar

KK 1.3 SN 1600
I= < ≥ Ifh. max < ≥ A < 1.3 ≥ < 288 A
Kf 1 3 ≥U N1 3 ≥ 4.16

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 23

The secondary setting:

I= 288
I= < < ≥ 1A < 0.57 A
nCT 500

DAdr parameter name parameter value unit


DMT Ph
1219A I>>> measurement of Fundamental component [30708]
1216A I>>> active Always [30721]
1217 I>>> Pickup oo A
1218 T I>>> Time Delay 0 sec
1220A I>> measurement of Fundamental component [30708]
1214A I>> active Always [12882]
1202 I>> Pickup 8.9 A
1203 T I>> Time Delay 0 sec
1221A I> measurement of Fundamental component [30708]
1204 I> Pickup 0.57 A
1205 T I> Time Delay 0.5 sec

9.1.2 Earth Fault Overcurrent protection (50/51N)

SN 1600
I E = < 0.3 ≥ Ifh. max < 0.3 ≥ < 0.3 ≥ < 66.6 A
3 ≥ U N1 3 ≥ 4.16
The secondary setting:

I E = 66.6
I E= < < ≥ 1A < 0.66 A
nCT 100

DMT E
1319A IE>>> measurement of Fundamental component [30708]
1316A IE>>> active Always [30722]
1317 IE>>> Pickup oo A
1318 T IE>>> Time Delay 0 sec
1320A IE>> measurement of Fundamental component [30708]
1314A IE>> active Always [12884]
1302 IE>> Pickup oo A
1303 T IE>> Time Delay 0 sec
1321A IE> measurement of Fundamental component [30708]
1304 IE> Pickup 0.66 A
1305 T IE> Time Delay 0.5 sec

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 24

10 Setting for 1920-AH000 Bus Coupler

10.1 Parameter Setting -F511 7SJ661

10.1.1 Bus coupler Data

10.1.1 Overcurrent protection (50/51)

I == < 1.1≥ I ==transformer < 1.1≥ 8.9 A < 9.79 A

Backup protection

I = < K K ≥ I =l < 1.1 ≥ 0.96 A < 1.05 A

t = < tl ∗ Χt < 0.5 ∗ 0.3 < 0.8s

DAdr parameter name parameter value unit


DMT Ph
1219A I>>> measurement of Fundamental component [30708]
1216A I>>> active Always [30721]
1217 I>>> Pickup oo A
1218 T I>>> Time Delay 0 sec
1220A I>> measurement of Fundamental component [30708]
1214A I>> active Always [12882]
1202 I>> Pickup 9.79 A
1203 T I>> Time Delay 0 sec
1221A I> measurement of Fundamental component [30708]
1204 I> Pickup 1.05 A
1205 T I> Time Delay 0.8 sec

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 25

11 Setting for 1920-AH-005 Incoming Feeder

11.1 Parameter Setting -F511 7SJ661

11.1.1 Line Data

Un=4.16kV

fn=60Hz

Sn=5800kW

11.1.1 Overcurrent protection (50/51)


I>> coordinate with Transformer feeder:

I == < K ≥ I ==transformer < 1.2 ≥ 4441A < 5329 A

The secondary setting:

I == 5329
I == < < ≥ 1A < 2.66 A
nCT 2000

Backup protection for the subordinate busbar

KK 1.2 5800
I= < ≥ Ifh. max < ≥ < 1136 A
Kf 0.85 3 ≥U N

The secondary setting:

I = 1136
I= < < ≥ 1A < 0.57 A
nCT 2000

DMT
Ph
Fundamental component
1219A I>>> measurement of [30708]
1216A I>>> active Always [30721]
1217 I>>> Pickup oo A
1218 T I>>> Time Delay 0 sec
1220A I>> measurement of Fundamental component
1214A I>> active Always [12882]

Unrestricted
Pure 4.16kV Substation
Parameters Setting for Electric Protection P a g e | 26

1202 I>> Pickup 2.66 A


1203 T I>> Time Delay 0 sec
1221A I> measurement of Fundamental component
1204 I> Pickup 0.57 A
1205 T I> Time Delay 1.2 sec