Abstract—Heat transfer around vertical ground Heat transfer (Different inlet temperature and velocity, different
around vertical ground heat exchangers is a common problem types of soil)
for the design and simulation of ground-coupled heat pump
(GCHP) systems. A serial of calculation models have been found II. METHOD
for ground heat exchangers to predict the temperature
distribution of superficial layers, but most of them still take the A. Simulation models
thermal characteristics of the ground as constant, which have
With the help of CFD-software Fluent [5], we can build and
great effort to the heat transfer efficiency. In this paper we will
propose a combination test and verify and thus provide a proper
simulate the steady-state models flexibly. The software Fluent
way to develop a simplified configuration in CFD software. is based on a finite volume method to convert the governing
equations to solve algebraic equations.
Keywords- Ground source heat pump; Ground heat exchangers; According to the study of Eui-Jong Kim et al [6], there were
simulation; u-pipe about 1,500,000 hexahedron and wedge-shaped volume
elements (fig.1). The bent section of the U-pipe was ignored
I. INTRODUCTION for some reasons below: the major purpose of this paper is the
The temperature at a certain depth underground almost study on the thermal interaction between the temperature
remain constant annually, so it provides a better way that distribution underground and the borehole exchangers, so
compared to the warm air in summer or cold air in winter to comparing to the total pipe, the bent section is too short to have
improve the air-conditioning efficiency. To extract or inject a notable amount in thermal transmissions. Furthermore,
from the superficial layer, an efficient heat-exchanger is because of the irregular volume around the bent pipe, the cells
needful and necessary. Most of heat pump units use vertical will increase dramatically and the whole quality of the mesh
ground heat exchangers which have less ground area went downward consequently.
requirement than horizontal arrangements in residential and
commercial buildings. As a result it is dominant to understand
the way of heat transfer between heat exchangers and the soil
nearby.
Most borehole heat exchanger models recently developed
are based on line source theory or cylinder theory which the
thermal process are usually simulated in 1D or 2D. [1], [2], [3]
and [4] Therefore, the temperature field at certain depth of
underground are not clearly presented. This study concerns the
influence of temperature field at certain depth underground on
the process of heating transfer. The results of the simulation are
compared to laboratory measurements.
The main objectives of this field study are as follows:
x To select a reasonable configuration in Fluent to
predict the temperature field and thus to calculate the
coefficient of heat transmission effectiveness.
x To compare the laboratory measurement with
simulation results on the temperature field and verify
the accuracy of the configuration of simulation.
x Analyze the characters of temperature field at certain
depth of underground at all kinds of combinations. Figure 1
Figure 2
2051
A constant temperature is set at the outside of the pipe wall
which should be an acceptable approximation for a 5m long
borehole at steady-state conditions. Table iii shows all the
boundary conditions necessary in the experiments. To get a
notable temperature distribution, instead of 35oC that is regular
used in construction [8] as the inlet temperature, 40oC, 45oC,
50oC were selected in experiments. The statistical summary of
boundary conditions in experiments is shown in Table iii.
Figure 6
Inlet=50oC depth=4m
From fig.4, fig.5 and fig.6 the distribution present mostly
centrosymmetric. But as it goes closer to the central pipe, the
more asymmetrical the distribution presents. It can be inferred
that the branch of the u-pipe prevent the distribution from
presenting symmetrically. As a result of that the phenomenon
that it looks more circular when it goes further from the central
point.
Figure 4
Inlet=40oC 4m depth Figure 7
Inlet temp=40oC the compare of test result and model
simulation
2052
IV. SUMMARY AND CONCLUSION
In the condition that the movement of fluid in porous of soil
is neglected, the absolute error between laboratorial
measurements and simulation results maintains less than 0.6oC.
The temperature distribution according to the tests and
simulations are roughly central symmetric, and the further
goes to the central, the colder the sensors test. With the rise of
u-pipe inlet temperature, the higher temperature the fixed
sensors will survey; the more overall heat-transmission will
inject into the ground the more time the ground temperature
recover to the oral state required.
On the basis of the conclusion above, we also can roughly
estimate of the porous-underground water situation. There’s
Figure 8 no doubt that the convection and conduction of underground-
Inlet temp=45oC the compare of test result and model water will improve the heat transmission and the temperature
simulation distribution will not exactly be symmetry, but we still need a
systematic, detailed and convictive models and simulations to
tell us in which condition we can neglect the underground
water or have no choice but to count the convective and
conductive heat transmission of porous water in the total
thermal calculation in.