Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
a r t i c l e i n f o a b s t r a c t
Article history: The paper presents the experimental measurements and numerical simulation of a ground source heat
Received 24 May 2013 exchanger operating at a cold climate for a passive house ventilation system. The investigated passive
Received in revised form 5 August 2013 house is a detached single-family house without a basement, occupied by a four head family, located in the
Accepted 3 September 2013
South of Poland. The measurements cover over one year period and CFD (Computational Fluid Dynamics)
simulations are reported for February when system operates at typical for this period and location cold
Keywords:
climate conditions. The calculations were made with the CFD ANSYS FLUENT software package. The house
Ground source heat exchanger
and its components are fitted with a data acquisition system that is operational from 2011 and records
Passive house ventilation
CFD
139 points at an interval of 1 min. The data reported in the paper were recorded during winter in the
year 2011/2012 by an onside located meteorological station and temperature sensors placed at different
depths in the ground and at the outlet of the ground heat exchanger.
© 2013 Elsevier B.V. All rights reserved.
0378-7788/$ – see front matter © 2013 Elsevier B.V. All rights reserved.
http://dx.doi.org/10.1016/j.enbuild.2013.09.008
A. Flaga-Maryanczyk et al. / Energy and Buildings 68 (2014) 562–570 563
The building meets the strict Passive House standards. Its annual The building has no traditional foundations. The walls are based
maximum space heating demand is below 15 kWh/(m2 a). The on a 0.25 m thick reinforced concrete slab, placed on a 0.4 m thick
blower door test performed before settling gave the result of layer of evenly laid expanded polystyrene. Thermal insulation slabs
0.36 1/h and later, after the house was already occupied, 0.5 1/h. are placed on the layer of compacted gravel and sand which extend
The building also has the typical characteristic of a passive house. below the frost depth (see Fig. 4). Such construction of the foun-
Solar heat gain is increased by placing the windows (with high dations eliminates the heat bridges and heat losses are technically
solar transmittance of glazing) mainly within the south eleva- cut to a minimum.
tion. An exception makes one window on the west elevation, The heat capacity of the applied reinforced concrete slab is the
on which the main entrance doors are also located. All win- highest in the whole building. This heavyweight structure accumu-
dows, except from a glass door leading to a terrace, are fixed, lates more heat from indoor air (when the indoor air temperature
with no possibility of opening. The ventilation of the building rises) or from incident solar radiation than any other building com-
is mechanical. Warm air circulation at low velocity ensures the ponent. When the indoor air temperature drops heat flows back to
proper heat distribution throughout the rooms. The space-heating the indoor air. This causes diminishing the amplitude of air tem-
energy demand of the passive house is covered by the floor heating perature fluctuations in the building. The concrete slab is also very
system and by the warm air of a central mechanical ventilation important for better utilization of transient heat gains. Alongside
system. The thermal energy for heating purposes (floor heat- with the buffer tank it is an additional element for heat accumula-
ing system, air heating coil) as well as for domestic hot water tion in the building.
production is provided by the ground source heat pump (see In the bottom part of the reinforced concrete slab floor heating
Fig. 3). pipes were installed. Such localization enables longer intervals in
floor heating
system
domestic
hot water
T1
heat pump
condenser
T2
M air heating coil
M domestic hot
water tank
domestic cold
water supply
evaporator
(heat pump ground
source heat exchanger)
Fig. 3. The schematic view of the heating and domestic hot water production system in the passive house.
A. Flaga-Maryanczyk et al. / Energy and Buildings 68 (2014) 562–570 565
reinforced slab
floor heating
expanded polystyrene
20+20cm
bedding
compressed sand
heating system supply due to the capability of heat accumulation The data were collected by the recorders and after digital
in the slab. Described construction of the foundations in the passive processing stored in the computer. The measurements started after
house has not been tested so far in Polish conditions. the settlement of the building. Measurement frequency was fixed
The local climate has a significant influence on the microclimate at the level of 1 min. Some results could be observed on line
of the building and the thermal energy demand for heating pur- (internet site: http://www.buduj-pasywnie.pl/dom online). This
poses. Its basic parameters are: temperature and relative humidity, enabled constant monitoring throughout the year and plausibility
solar radiation and wind speed and direction. These parameters are check.
the basic set of boundary conditions for the numerical simulation of Obtained data serve for the research which includes regulat-
the building and its components. They allow defining the real pas- ing the indoor environment, hygrothermal performance of thermal
sivity of the building, because the term “energy demand for space envelope and monitoring of active systems (heating and ventila-
heating” has meaning only in relation to the real local climate. tion) as well as their energy use. The general aim of the whole
In order to make continuous measurements of the needed cli- study is to examine real life performance of one low energy
mate parameters, the local meteorological station was built (Fig. 5). building that was selected from a number of such buildings
The building and associated installations were also provided with that were recently constructed in Poland. All of these buildings
measuring equipment. All measuring instruments used repre- were built with similar technology, with very limited variations
sented physical quantities measured in the form of electrical signals in a layout and installations’ arrangements, so obtained data
(voltage, current, pulse). The list of sensors used for measurements can be considered as representative for this type of construc-
of parameters relevant for the study is presented in Table 1. tion.
Fig. 5. The local meteorological station (a) and the pyranometer for the scattered radiation measurement (b).
566 A. Flaga-Maryanczyk et al. / Energy and Buildings 68 (2014) 562–570
Table 1
The list of sensors used for measurements relevant for the study.
Thermohygrometer LB-710R Temperature and relative humidity of the open air, Temperature: −40. . .85 ◦ C, relative ±0.1 ◦ C, RH: ±2%
meteorological station humidity: 0. . .100%
Thermohygrometer LB-710HS Temperature and relative humidity of indoor air, rooms Temperature: −40. . .85 ◦ C, relative ±0.1 ◦ C, RH: ±2%
humidity: 0. . .100%
Thermoanemometer DeltaOhm Air temperature and air velocity, pipes of GSHE and ventilation Temperature: −10. . .60 ◦ C, air ±0.3 ◦ C
HD2937TC12 ducts velocity: 0.05. . .20 m/s 0.02 m/s ±3%
PT100 sensor Ground temperature, ground −50. . .180 ◦ C ±0.15 ◦ C
Top1068
3. The ground source heat exchanger for the passive house summer (protection from overheating the house) and increas-
ventilation system ing its temperature in winter (preheating), before entering the
house.
The ventilation system of the passive house consist of a ground
source heat exchanger (GSHE), a heat recovery unit and an air
4. CFD simulations
heating coil supplied from a ground source heat pump, what is a
preferable solution for passive houses. In summer-time, the used
For numerical simulations of the ground source heat exchanger
air removed from the building by-passes the heat-recovery unit due
coupled with a ventilation system of the passive house a Computa-
to protection from overheating of the house.
tional Fluid Dynamics (CFD) software package ANSYS FLUENT v.
The schematic view of the ventilation system in the passive
14 was used. ANSYS FLUENT provides comprehensive modeling
house is presented in Fig. 6.
capabilities for a wide range of incompressible and compress-
A ground source heat exchanger reported in this paper, which
ible, laminar and turbulent fluid flow problems. Steady-state or
is a part of the mechanical ventilation system of the passive house
transient analyses can be performed. In ANSYS FLUENT, a broad
described in chapter 2, is an open type, set of buried horizontally
range of mathematical models for transport phenomena (like heat
at depth of 1.5 m PPE plastic pipes. The three 15.85 m long pipes
transfer and chemical reactions) is combined with the ability to
of a diameter 125 mm are connected parallelly along with a mani-
model complex geometries. Examples of ANSYS FLUENT applica-
fold and returning pipes of a diameter 200 mm and total length of
tions include laminar non-Newtonian flows in process equipment;
9.19 m (Fig. 7). The total heat transfer area of this heat exchanger
conjugate heat transfer in turbomachinery and automotive engine
is equal 15.54 m2 . The ground source heat exchanger extends at a
components; pulverized coal combustion in utility boilers; exter-
rectangle of 5.95 m by 5.09 m covering area of 28.78 m2 . Soil slab
nal aerodynamics; flow through compressors, pumps, and fans; and
that was taken in the CFD simulation has 2.0 m depth and is by
multiphase flows in bubble columns and fluidized beds. Robust and
one meter larger then extends of the pipes. The ambient air passes
accurate turbulence models are a vital component of the ANSYS
through tubes buried in the ground, lowering its temperature in
FLUENT suite of models. The turbulence models provided have a
broad range of applicability, and they include the effects of other
physical phenomena, such as buoyancy and compressibility. Par-
air supply exhaust air ticular care has been devoted to addressing issues of near-wall
to the building to ambient accuracy via the use of extended wall functions and zonal models.
Various modes of heat transfer can be modeled, including natu-
ral, forced, and mixed convection with or without conjugate heat
transfer, porous media, etc. [17]. This numerical tool allows simu-
lating the behavior of systems, processes and equipment involving
heating coil supplied
from a heat pump
by-pass
279
at four different depths [K]
278
Temperature of the ground
277
276
275
274 T 10 cm
273
272 T 40 cm
271 T 80 cm
270
269
T 160 cm
2012-02-01
2012-02-02
2012-02-03
2012-02-04
2012-02-05
2012-02-06
2012-02-07
2012-02-08
2012-02-09
2012-02-10
2012-02-11
2012-02-12
2012-02-13
2012-02-14
2012-02-15
2012-02-16
2012-02-17
2012-02-18
2012-02-19
2012-02-20
2012-02-21
2012-02-22
2012-02-23
2012-02-24
2012-02-25
2012-02-26
2012-02-27
2012-02-28
2012-02-29
Date
Fig. 9. Measured temperatures of the ground at four different depths (10 cm, 40 cm, 80 cm and 160 cm).
285
280
275
Temperature [K]
270
T ground 10 cm
265
T ground 40 cm
260
T ground 80 cm
255 T ground 160 cm
250 T air_outside
T gshe_out
245
2012-02-01
2012-02-02
2012-02-03
2012-02-04
2012-02-05
2012-02-06
2012-02-07
2012-02-08
2012-02-09
2012-02-10
2012-02-11
2012-02-12
2012-02-13
2012-02-14
2012-02-15
2012-02-16
2012-02-17
2012-02-18
2012-02-19
2012-02-20
2012-02-21
2012-02-22
2012-02-23
2012-02-24
2012-02-25
2012-02-26
2012-02-27
2012-02-28
2012-02-29
Date
Fig. 10. Measured temperatures of the ground at four different depths (10 cm, 40 cm, 80 cm and 160 cm), of the outside air (TAIR outside ) and at the outlet of the ground source
heat exchanger (TGSHE out ).
568 A. Flaga-Maryanczyk et al. / Energy and Buildings 68 (2014) 562–570
temperature that for each time step was dynamically taken from
measurements. The ground source heat exchanger air inlet temper-
ature was assumed to be equal to outside air temperature measured
at each time step. Flow rate of air was taken from the measured val-
ues. The convergence criteria for numerical simulation at each time
step were continuity, x-velocity, y-velocity, z-velocity, k, epsilon
and the energy. The convergence for all criteria except for the
energy criterion was set at a level of 1E−3. The convergence for the
energy criterion, that was important from energy point of view, was
set at a lower level of 1E−6. The calculation was done at each time
step until all of the convergence criteria were met. Starting point
of temperature distribution in a soil slab was established based Fig. 12. Ground source heat exchanger thermal profile cross-sections.
on a preliminary steady state simulation that was followed by a
dynamic simulation performed for about one week proceeding the
simulation reported in this paper.
The simulations covered one month (February) of system oper- ventilation air intake. The temperature of the fresh, outside air is the
ation in typical for this location cold climate conditions. The data lowest temperature along the whole ground source heat exchanger
used in the simulation were those recorded in the year 2012 by in considered month (February) and thus the impact of the pipe on
a local meteorological station (Fig. 5) and temperature sensors isotherms of the ground is so significant, the biggest in the whole
located at different depths in the ground and at the outlet of the soil slab. Fig. 12a shows the interference of the two utter pipes
ground source heat exchanger coupled with a ventilation system with the one in the centre of the set of three parallel pipes of the
of the passive house. ground source heat exchanger (the first three from the right side of
As expected, despite significant fluctuations in ground tempera- Fig. 12a). The isotherms of the ground for the middle pipe are more
ture at a depth of 10 cm (see Fig. 9), caused by changes in outside air biased than the ones for the outer pipes. The last figure (Fig. 13)
temperature, ground temperature at greater depths was very sta- presents the temperature volume rendering.
ble. The period of cold weather did not cause significant changes in
ground temperature at a depth of heat exchanger location (approx-
imately 140 cm).
Fig. 10 presents juxtaposition of the measured tempera-
tures at different depths in the ground, the temperature of the
outside air and the temperature at the outlet of the ground
source heat exchanger. Analysis of the collected experimental
data show that the ground source heat exchanger success-
fully suppressed the fluctuations of the outside air temperature,
what was significant especially during severe frost in early
February.
The graphical results of performed CFD simulations of the
ground source heat exchanger for the ventilation system of the
passive house are presented in Figs. 11–13. Fig. 11 shows that
the change in temperature of the ventilation air occurs along the
entire length of the tubes of the ground source heat exchanger.
Figs. 12a, b and 13 present the impact of the pipes of the ground
source heat exchanger on the temperature distribution in the soil.
On the right side of Fig. 12b the largest deviation of the isotherms
in the ground can be seen. The blue colored pipe is the place of the Fig. 13. Ground source heat exchanger volume rendering.
A. Flaga-Maryanczyk et al. / Energy and Buildings 68 (2014) 562–570 569
2012-02-01
2012-02-03
2012-02-05
2012-02-07
2012-02-09
2012-02-11
2012-02-13
2012-02-15
2012-02-17
2012-02-19
2012-02-21
2012-02-23
2012-02-25
2012-02-27
2012-02-29
by the RMS error 0.62%) leads to the conclusion that used CFD tool is
suitable for simulation of the ground source heat exchanger operat-
ing at the cold climate for the passive house ventilation system and
Date
the obtained results physically capture the trend of indoor thermal
environment. Fig. 15. Percentage of heat for heating the ventilation air that was provided in
February was the coldest month in the analyzed year. The February by the ground source heat exchanger operating for the passive house
average outdoor temperature was 266 K. The ground source heat ventilation system.
290
285
280
275
Temperature [K]
270
265
260
255 T gshe_out_measured
250 T gshe_out_calculated
245 T air_outside
240
2012-02-02
2012-02-03
2012-02-04
2012-02-05
2012-02-06
2012-02-07
2012-02-08
2012-02-09
2012-02-10
2012-02-11
2012-02-12
2012-02-13
2012-02-14
2012-02-15
2012-02-16
2012-02-17
2012-02-18
2012-02-19
2012-02-20
2012-02-21
2012-02-23
2012-02-24
2012-02-25
2012-02-26
2012-02-27
2012-02-28
2012-02-29
Date
Fig. 14. Experimental data (TGSHE out measured ) and simulation results (TGSHE out calculated ) of the air temperature at the outlet of the ground source heat exchanger. TAIR outside –
represents the temperature of ambient air (before entering the ground source heat exchanger).
570 A. Flaga-Maryanczyk et al. / Energy and Buildings 68 (2014) 562–570
[%]
15%
10%
5%
0%
December January February March April
285
Temperature [K]
280
275
270 T air_outside
265
T gshe_out
260
255
December January February March April
Fig. 16. Percentage of heat for heating the ventilation air that was provided by the ground source heat exchanger operating for the passive house ventilation system (TAIR outside
and TGSHE out are given as mean temperatures in the analyzed month).
6. Conclusions References
In this work the experimental measurements and numerical [1] http://epp.eurostat.ec.europa.eu/statistics explained/index.php/Consumption
of energy
simulations of a ground source heat exchanger operating at a cold [2] http://www.eea.europa.eu/data-and-maps/figures/households-energy-
climate for the passive house ventilation system have been ana- consumption-by-end-uses-4
lyzed. In particular February, as the coldest month in the analyzed [3] V. Badescu, B. Sicre, Renewable energy for passive house heating. Part I. Building
description, Energy and Buildings 35 (2003) 1077–1084.
year, was under detailed investigation. [4] W. Feist, J. Schnieders, V. Dorer, A. Haas, Re-inventing air heating: convenient
The ground source heat exchanger operating for the passive and comfortable within the frame of the Passive House concept, Energy and
house ventilation system at the cold climate enabled to exploit Buildings 37 (2005) 1186–1203.
[5] Passipedia, The Passive House Resource (http://www.passipedia.org/
the heat capacity of the ground for heating means, successfully passipedia en/).
suppressing the fluctuations of the outside air temperature, what [6] Polish Institute of Passive House and Renewable Energy (http://www.pibp.pl/)
was significant especially during severe frost in early February. On (in Polish).
[7] Passive House Institute (http://www.passiv.de/en/index.php).
average, the ground source heat exchanger provided 24% of heat
[8] V. Badescu, Simulation analysis for the active solar heating system of a passive
for heating the ventilation air in February, and since December to house, Applied Thermal Engineering 25 (2005) 2754–2763.
April the mean value of coverage was at the level of 15% of heat for [9] V. Badescu, Economic aspects of using ground thermal energy for passive house
heating the ventilation air in these months. heating, Renewable Energy 32 (2007) 895–903.
[10] K.S. Lee, Underground Thermal Energy Storage, Springer, London, 2013, pp. 16.
The CFD simulations performed for the ground source heat [11] P.S. Doherty, S. Al-Huthaili, S.B. Riffat, N. Abodahab, Ground source heat pump –
exchanger operating for the passive house ventilation system for description and preliminary results of the Eco House system, Applied Thermal
February, based on experimental data showed good correlation Engineering 24 (2004) 2627–2641.
[12] G. Florides, S. Kalogirou, Ground heat exchangers – a review of systems, models
with the measured values. The calculated RMS error is 0.62% which and applications, Renewable Energy 32 (2007) 2461–2478.
means that the difference between calculated and measured values [13] Y. Wu, G. Gan, A. Verhoef, P.L. Vidale, R.G. Gonzalez, Experimental measure-
is 1.7 degree on average. It is satisfactory for this type of simu- ment and numerical simulation of horizontal-coupled slinky ground source
heat exchangers, Applied Thermal Engineering 30 (2010) 2574–2583.
lation that is based on field measurements on a real installation, [14] P.M. Congedo, G. Colangelo, G. Starace, CFD simulations of horizontal ground
especially with the very wide range of temperatures at the ground heat exchangers: a comparison among different configurations, Applied Ther-
source heat exchanger inlet of about 39 K (from 245 K to 284 K) in mal Engineering 33/34 (2012) 24–32.
[15] V. Badescu, Simple and accurate model for the ground heat exchanger of a
analyzed period. passive house, Renewable Energy 32 (2007) 845–855.
The difference between measured and calculated values at the [16] V. Badescu, B. Sicre, Renewable energy for passive house heating. Part II. Model,
level of 1.7 degree on average leads to the conclusion that used CFD Energy Buildings 35 (2003) 1085–1096.
[17] ANSYS FLUENT Theory Guide, ANSYS, Inc. Release 14.0, 2011, November. PA,
tool is suitable for simulations of the ground source heat exchanger
USA (http://www.ansys.com).
operating at the cold climate for the passive house ventilation sys- [18] M. Periasamy, D.B. Sivakumar, T. Senthil Kumar, Dampening flow induced
tem and the obtained results physically capture the trend of indoor vibration due to branching of duct at elbow, International Journal of Computa-
thermal environment. tional Engineering Research 2 (4) (2012) 1001–1004.