Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
om
.c
ia
A2 as
a2 CT
@
M L
b2
B2
M L
ith
c2
C2
M L
M
sm
Neutral C.T
L
rd
TO TRIP
CIRCUIT
}
ha
om
1.1.1 Overcurrent . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.1.2 Earth Fault . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2 Fault Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3 Isolation of Faulty Equipment . . . . . . . . . . . . . . . . . . . . 2
1.4 Protective Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.5 Classes of Protection . . . . . . . . . . . . . . . . . . . . . . . . . 4
.c
1.6 Characteristics of a Good Protection Scheme . . . . . . . . . . . 4
ia
3 Unit protection schemes 7
3.1 Transformer protection . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1.1 The Buchholz relay . . . . . . . . . . . . . . . . . . . . . . 7
as
3.1.2 Explosion Vent . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1.3 Qualitrol Pressure Relief . . . . . . . . . . . . . . . . . . . 8
3.1.4 Continuous Gas Analyser . . . . . . . . . . . . . . . . . . 8
3.1.5 Earth Fault Protection of High Voltage Delta Windings . 10
3.1.6 Differential protection . . . . . . . . . . . . . . . . . . . . 12
@
3.1.7 Differential Protection of a Three Phase Transformer . . . 15
3.1.8 Differential Earth Fault Protection of Star Windings . . . 17
3.2 Busbar protection . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.2.1 Check Zones . . . . . . . . . . . . . . . . . . . . . . . . . 19
ith
4 Non-Unit protection 45
4.1 Overcurrent Relays . . . . . . . . . . . . . . . . . . . . . . . . . . 45
ric
5 Backup Protection 53
om
6 Measuring Voltage and Current 55
6.1 Voltage Transformers . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.2 Current Transformers . . . . . . . . . . . . . . . . . . . . . . . . 55
.c
ia
as
@
ith
sm
rd
ha
ric
List of Figures
1 Photo of Transformer explosive vent . . . . . . . . . . . . . . . . 9
2 Photo of Transformer Qualitrol . . . . . . . . . . . . . . . . . . . 9
om
3 Photo of Transformer Gas Analyser . . . . . . . . . . . . . . . . . 10
4 Delta-Star transformer Protection . . . . . . . . . . . . . . . . . 11
5 Fault is outside area covered by CT’s therefore relay does not
operate (i.e. current from CT – A is cancelled by current from
CT – B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6 Relay operates as fault is between CT’s (i.e. current from CT –
.c
A is NOT cancelled by current from CT – B) . . . . . . . . . . . 13
7 Instantaneous relay . . . . . . . . . . . . . . . . . . . . . . . . . . 13
8 Biased relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
9 Biased type relay . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
ia
10 Protection of single phase of a Transformer . . . . . . . . . . . . 15
11 Transformer Differential Protection . . . . . . . . . . . . . . . . . 16
12 Differential (Restricted) Earth Fault Protection of Transformer -
as
Operation on Fault inside Zone . . . . . . . . . . . . . . . . . . . 18
13 Differential (Restricted) Earth Fault Protection of Transformer –
Operation on Fault outside Zone . . . . . . . . . . . . . . . . . . 18
14 Busbar protection scheme for a single busbar . . . . . . . . . . . 20
@
15 Bus zone protection scheme for a single bus with bus section
circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
16 Bus zone protection for circuit breakers and a half without check
zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
17 Busbar protection scheme for a single bus with a bus section
ith
circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
18 measurement of distance to fault . . . . . . . . . . . . . . . . . . 25
19 distance protection zones . . . . . . . . . . . . . . . . . . . . . . 27
20 Acceleration of Distance measurement . . . . . . . . . . . . . . . 31
sm
30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
31 Earth fault protection on the Delta side of a transformer . . . . . 47
32 Overcurrent and Earth Leakage Relays Connections . . . . . . . 48
33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
ric
34 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
35 Instantaneous relays with Definite Time . . . . . . . . . . . . . . 49
36 Inverse Time relays . . . . . . . . . . . . . . . . . . . . . . . . . . 50
37 Directional relay . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
38 Non-Directional relays applied to parallel feeders . . . . . . . . . 52
39 Directional relays applied to parallel feeders . . . . . . . . . . . . 52
40 Illustration of gross errors in distance measurement with feed in
between relay and fault . . . . . . . . . . . . . . . . . . . . . . . 53
om
.c
ia
as
@
ith
sm
rd
ha
ric
19481 – Demonstrate knowledge of electricity supply protection equipment
Protection 19481
Author - Richard J Smith Creation date - 7 November 2006 Last Updated - 3
May 2007
om
Description This course provides the student with an understanding of elec-
tricity supply protection equipment with emphasis on the equipment provided
at Huntly Power Station. Successful completion of this course will enable the
student to achieve NZQA unit standard 19481 – Demonstrate knowledge of
electrical supply protection equipment.
Pre-Requisites The student have achieved EnChem level 2 and completed his/her
.c
electrical component of their plant training at Huntly or equivalent work expe-
rience.
Completing and Passing the Course The following modules need to be success-
ia
fully completed to pass the course: 1. the 19481 Protection workbook to a
satisfactory level 2. the course evaluation survey
Who should do this Course Genesis staff wishing to complete NZQA National
Cert Electricity Supply (Level 4) will be required to undertake this course.
as
Student Objectives On completing this course, the student will be able to; 1.
Define common terms and abbreviations used in discussing electrical protection.
2. Describe the purpose and classes of protection (range: purpose of protection,
typical causes of faults) 3. Identify the methods of discrimination used to find
@
faults (range: time, current, direction of power flow, distance measurement,
differential relays) 4. State the purpose of voltage and current transformers
5. Identify and describe the types of transformer protection (range: buchholz,
overcurrent, earth fault, differential) 6. Describe the principles of circuit and
ith
1
1 The Need for Protection
If a fault or other abnormal condition occurs in a power system, the faulty
apparatus must be isolated from the rest of the system as quickly as possible to
om
reduce damage both to the faulty equipment and to those parts of the system
carrying the fault current. Protective devices are therefore installed in the
system to detect the presence of a fault and initiate the required action. Isolation
of the affected equipment will then allow continued operation of the remainder
of the system as normal.
.c
1.1 Types of Faults
1.1.1 Overcurrent
ia
When a circuit or piece of equipment is carrying a greater current than it was
designed for, it is said to be overloaded. Most equipment can tolerate some
degree of overloading for a limited time, but protection needs to be provided to
as
limit the overloading to a value that doesn’t damage the equipment. Overcurrent
can be caused by lighting strikes on overhead lines or just attempting to supply
more load than the circuit design load.
the earth voltage near the point of the earth fault can increase to a dangerous
level, and supply to the intended recipient can be interrupted.
Faults and other abnormal conditions may cause changes in the magnitude, di-
rection, phase angle and frequency of circuit currents and voltages. The nature
of these changes depends upon the fault and the position of the fault relative
to the point in the system from which the fault is being observed.
rd
A protective system uses current transformers and voltage transformers (to mea-
sure magnitudes of current and voltage and transform them to values which can
be handled by the relays), relays (to monitor these values and detect an abnor-
mal condition) and a tripping circuit to the circuit breaker.
ha
2
The protective equipment should be simple as possible, but it should also pro-
cess ’discrimination’ in order that it should isolate only the faulty circuit or
apparatus and not operate for other faults outside its zone.
om
1.4 Protective Relays
A relay used for automatic protection may be defined as a mechanical or elec-
trical apparatus triggered by current, voltage, or power which opens or closes
a local circuit when the current has a specified magnitude, or bears a specified
.c
relation to the voltage of the main circuit with which the relay is associated.
The function the relay provides may be classified as follows:
ia
place when the voltage or current falls below a specified value.
• OVER VOLTAGE, and OVER CURRENT, in which operation takes place
as
when the voltage or current rises above a specified value.
• DIRECTIONAL, in which operation takes place when the component of
the current in phase with the voltage, assumes a specified magnitude and
a specified direction in relation to the voltage.
@
• DISTANCE, in which the operation is governed by the ratio of the voltage
to the current, i.e. impedance, or to the component of the current having
some specified phase relation to the voltage.
ith
Relays can be classified, with regard to their timing characteristics, under the
following headings;
• INVERSE TIME, in which the time lag decreases as the value of the
operating current or power increases.
ha
Protective relays must therefore be speedy and selective and this is achieved
by the use of both time and current graded relays and special relays for special
types of fault.
Remember
3
• Relays may require current and/or voltage supplies from CTs and/or VT’s.
• Relays operate on current, voltage, power, or impedance.
• Some relays have a built in, time delay, either definite time or inverse time.
om
1.5 Classes of Protection
Protection systems can be divided into two basic classes:
Unit Protection Unit protection protects a precisely defined area of the pri-
.c
mary system and will respond only to faults within that area.
ia
protection, busbar protection, Buchholz relay, pilot wire, direction
comparison earth fault.
Non-Unit Protection will respond to a fault within an area that is not pre-
as
cisely defined.
• Discrimination
• Stability
• Speed of operation
sm
rd
ha
ric
4
2 Common Terms Related to Protection
Back up Protection This is a second, often slower and cheaper protective
system, that supplements the primary protection should the latter fail to
om
operate for any reason.
CT Current Transformer
Definite Time Relay A relay which operates in a pre-determined time, which
is not affected by fault values. Usually it is operated by the closure of
a contact on another relay, such as an instantaneous over-current relay,
.c
instantaneous earth fault relay, etc.
ia
called “selectivity”
Instantaneous Relay These are relays whose operation is not intentionally
as
delayed. Typical operating times are from about 0.05 to 0.1 second.
Inverse Time (e.g. Overcurrent Relay) These have a time of operation
that decreases as the magnitude of the operating current (or other op-
erating quantity) increases.
@
Non-Unit Protection Protection that will respond to a fault over a wide area
of the system. In general the area will not be precisely defined.
High Speed Tripping This is a relative term but generally implies operation
ith
Relay Pick up Current The value of current at which the relay just operates
and closes its contacts (or voltage for voltage operated relays).
Reliability In the event of a fault in a zone, the protection of that zone must
ha
operate and trip the correct circuit breakers to isolate that zone, and
only that zone, from all live supplies. If it fails to operate, or operates
unnecessarily, the protection system is said to mal-operate. Achieving
reliability requires correct design and installation and regular maintenance
of the protective equipment.
ric
Residual Current The current that results from combining the three currents
in the phases. Paralleling the three secondaries of CT’s on R, Y and B
phases gives an output of the vector sum of the currents in the three phases
- the residual current. This is commonly connected to an earth fault relay.
5
Residual Voltage The vector sum of the voltages to earth of the three phase
conductors. The secondary equivalent is obtained by connecting the three
VT secondaries in series.
om
Restraint A relay may be hindered from operating by some quantity, such as
voltage. it is then said to be given (voltage) restraint. An impedance
relay is restrained by voltage, operated by current. The current tending
to close the contacts, the voltage to open them.
.c
by poor stability.
item[Selectivity or discrimination] The protection in any zone is said to
discriminate or be selective, when it can distinguish between an internal
ia
fault within the zone and an external (through) fault in another zone. The
protection should trip on an internal fault but ignore all external faults
and normal load current. A scheme that lacks discrimination will cause
as
unnecessary disconnection of healthy plant and circuits.
Signal Link A communication link between two substations used for protec-
tion purposes, usually to close (or open) a contact at the remote station.
The link may be by metallic wires (pilots), carrier over pilot wires, power
@
line carrier, radio, etc.
Speed of Operation The longer a fault is allowed to persist, the greater the
damage that may be caused. In the case of a high current fault close to
a generator, synchronisation to the system may be lost. Fast operation
ith
6
3 Unit protection schemes
Unit protection responds only to faults within clearly defined boundaries and
therefore no time delay is necessary for discrimination. This allows fast clearance
om
times which are important for protection of main equipment such as generators
and transformers. Usually the protective scheme consists of two CT’s per phase,
one set at each end of the protective zone. The relay measures the difference
between the secondary currents. If the zone is healthy, there is no difference
between the currents and the relay remains inoperative. If a fault occurs within
the zone (i.e. between the ends), currents from the CTs no longer balance and
.c
the relay operates.
ia
• Differential protection of generators
• Differential protection of transformers
as
• Overall differential protection of generator transformers
• Differential earth fault protection of the star winding of transformers,
including cables
@
• Earth fault protection of transformer delta windings
• Busbar protection
• Pilot wire protection
ith
gas from the transformer. Gas given off can be an early warning of damage
to the transformer and early detection can greatly reduce the cost of repair.
The Buchholz relay has two switches, ”alarm” and ”trip”. The alarm switch is
connected to a float in the top of the relay.
ha
This will operate when a certain amount of gas has accumulated in the re-
lay. The trip switch is connected to a flap in line with the oil pipe, and may
have a float in addition. In the event of major trouble the switch will be ac-
tivated by a sudden rush of gas or oil. Some transformer tap changers have a
ric
Early Buchholz relays used mercury switches; these caused spurious alarms
or trippings in times of earth tremors due to slopping of the mercury. These
alarms or trippings can be prevented by the use of a seismic blocking relay which
7
switches the Buchholz relay out of service when earth tremors are detected. A
seismic blocking relay uses the pendulum principle. When the pendulum moves,
contacts close and the Buchholz trip circuit is temporarily made inoperable.
This relay must he firmly mounted so that movement caused by vehicles etc is
om
not detected. The disadvantage is that at the time of earth tremors this pro-
tection is out of service.
An improved method is the use of a Buchholz relay using reed switches. These
are not affected by movement, as reed switches are closed magnetically. To
prevent the possibility of reed switches closing due to the magnetic field caused
.c
by inrush currents special ”biased reed switches” are used. These have a small
magnet holding the contacts open. This prevents the switch from being closed
by stray magnetic fields. When the switch is moved to its operating magnet,
ia
the switch closes as usual.
The Buchholz alarm which is float operated can be activated by low oil level
allowing air into the relay or by air from the oil in the transformer after filtering
as
has been carried out.
Explosion vents are fitted to all large transformers. This vent is a large diameter
pipe welded to the top of the transformer tank with a down turned bursting
disk or diaphragm. The pipe is usually higher than the conservator tank to
prevent excessive loss of oil, should the disk burst. The explosion vent protects
sm
the transformer case from building up pressure in the case of an internal fault.
When a serious internal fault occurs gas is produced. This quickly builds up
pressure which will operate the Buchbolz trip. Should the pressure not be
sufficiently relieved the bursting disk will shatter and relieve the pressure from
inside the tank case. This is usually obvious by the spillage of oil down the
transformer and over the ground below the vent.
rd
onds.
8
om
.c
ia
as
@
Figure 1: Photo of Transformer explosive vent
ith
sm
rd
ha
ric
9
level in oil.
om
gas detector. Within the gas detector, the gases combine with oxygen from the
ambient air to produce an electrical signal that is measured by an electronic
circuit and converted to ppm. The gas detector is sensitive to the gases that
are the primary indicators of incipient faults in oil-filled transformers (i.e. Hy-
drogen, Carbon monoxide, Ethylene, and Acetylene).
.c
Moisture detection is performed by a thin-film capacitive moisture sensor. The
capacitive value of this sensor varies according to the moisture level and this
value is converted to an electrical signal.
ia
Both the gas detection and moisture level reading are configured to generate
alarms but are not usually connected to transformer trip circuits.
as
@
ith
sm
rd
The delta winding, being insulated from earth, cannot provide an earth re-
turn path for faults anywhere on the system between the generation source and
the HV CT’s.
The earth fault relay can only operate for earth faults on the transformer delta
10
(primary) winding or leads from the transformer to the CT’s.
The protection is therefore a form of unit protection and trips without time
delay.
om
CT’s
A2
R a2
.c
B2
Y b2
ia
C2
B c2
Consider the case of a delta star transformer as shown in Figure 4 supplied from
ith
generation source on the left hand side of RYB, and connected to load a2 b2 c2 .
When the transformer is un-faulted, the currents in each of the leads R,Y,B
at any instant of time return through the other two. The secondary currents
from the CTs circulate round the CT secondaries, but do not pass through the
sm
Faults to earth in the secondary side of the transformer (e.g. feeder faults)
do not operate the HV earth fault relay. An earth fault on secondary terminal
a2 will be balanced on the supply side by primary current in R phase returning
to the source via B phase.
rd
Even with the transformer back livened from the secondary, the earth fault
relay could not pick up for a primary earth fault to the left of the CTs.
ha
Now if there is an earth fault on say the HV A2 terminal, earth fault cur-
rent will flow through Red phase CT and operate the HV earth fault relay.
Thus operation of the relay only occurs for HV faults on the transformer and
connections up to the CT.
ric
Advantages
• Unit protection given for earth faults on HV winding.
• Location of the fault is more easily found than for full differential protec-
tion where LV faults also actuate the relay.
11
• Fast operating, and cheap.
Disadvantages
• Only operates for HV earth faults.
om
• Does not cover HV phase to phase faults, short circuited turns, or LV
faults. (However if the fault is inside the transformer, it is cleared by the
buchholz relay.)
Remember
• Differential earth fault protection of transformer LV star windings also
.c
protects the LV cables if the CT position includes them in the protected
zone.
ia
• Earth fault protection of the delta winding may operate for flashover of
the transformer rod gaps or surge diverters.
as
3.1.6 Differential protection
Circulating Current Differential Protection Figure 5 shows two CT’s, A
and B, protecting the conductor AB with differential protection. An external
load or an external fault is represented at F. Secondary currents flow as shown,
@
and if the CTs have the same ratios and maintain their accuracy, the currents
cancel out to zero and no current flows in the relay.
Fault Current
CT - A CT - B
ith
A B
sm
Fault to earth
(F)
R
rd
Figure 5: Fault is outside area covered by CT’s therefore relay does not operate
(i.e. current from CT – A is cancelled by current from CT – B)
ha
12
Fault to earth
(F)
om
CT - A CT - B
A B
Fault
.c
R
ia
Figure 6: Relay operates as fault is between CT’s (i.e. current from CT – A is
as
NOT cancelled by current from CT – B)
@
Relay
operating
coil Relay Operates
current
ith
Relay Operates
Relay
ha
operating
coil
current
13
Simple Instantaneous Relays Attracted armature type relays can be very
stable in differential circuits where the currents entering and leaving the equip-
ment are identical, i.e. differential protection of busbars and generators, but
not transformers. Simply by connecting a resistance in series with the relay, of
om
a value chosen to simple established rules, it can be assured that the relay will
not operate for faults external to the protected zone.
The CT’s must have the same turn’s ratio, and reasonably similar magneti-
sation characteristics.
.c
Biased Differential Relays These relays are given a restraint against op-
erating which increases with the through current. A common construction is
the induction disc pattern, similar to the inverse over-current relay, with an
ia
operating coil on one electromagnet causing the disc to rotate to close the relay
contacts. Another coil carrying the secondary equivalent of through current
produces a torque on the disc in the opposite direction, tending to prevent
(restrain) relay operation (see Figure 9).
CT
as CT
@
ith
Operating
Restraint
sm
Neglecting initial spring tension then, a 1 amp relay with 20% bias would op-
erate at 0.2 amp with 1 amp through current, and operate at 2 amps with 10
rd
This assists the relay to remain inoperative when the two CTs do not match
correctly in ratio. In particular this occurs with transformer differential pro-
ha
tection, where there are taps on the main transformer. The CT ratios may be
satisfactory for one transformer tap ratio, but not for other taps.
scribed above the currents entering and leaving the equipment are identical
in value if the equipment is healthy. In transformer differential protection, the
input and output currents (primary and secondary) which are compared, have
a known ratio to one another unless there is a short circuit in the transformer.
Figure 10 shows a single phase transformer of ratio 66kV to 11kV (It will have a
turns ratio of 6/1). If 600 amps flow in the 11 000 volt secondary, this must be
14
Transformer
Voltage Source 66kV / 11kV Load
om
CT 100/1 CT 600/1
1 Amp 1 Amp
.c
Relay Operating Winding
ia
Figure 10: Protection of single phase of a Transformer
as
balanced by 1/6 x 600 = 100 amps in the primary winding. Ignoring magnetisa-
tion current (normally very small), the ratio secondary output current/ primary
input current will always be the same as the no load voltage ratio primary volts/
@
secondary volts (6/1 in this case) unless some or all of the transformer turns are
shorted.
Now if CT’s of 100/1 and 600/1 amp ratio are inserted in the primary and
secondary connections as shown and the CT secondaries are connected to a re-
ith
lay, a current of 1 amp will circulate round the CTs, and the current through the
relay operating coil will be zero (or practically so). If the transformer is partly
or wholly short circuited, the balance of currents to the relay is upset, and
the relay operates. Hence faults which occur between the HV and LV current
sm
lation does not conform to the required protection scheme, unwanted tripping
may occur after the load has built up above relay sensitivity.
15
result in different current ratios for the transformer.
om
sation currents are drawn from the supply of a value many times full load of the
bank. These currents on one side of the bank are not matched by corresponding
currents on the output winding and hence, fed only to one side of the relay
appear as a transformer fault. The currents take many seconds to decay to the
normal low value.
.c
These magnetisation inrush currents contain a high proportion of 100 cycle
per second (100 Hz) component which is the second harmonic of the normal 50
Hz supply frequency. Internal transformer fault currents for which the relay is
ia
expected to operate do not contain this second harmonic.
This characteristic is used to make the relay immune to operation from mag-
as
netisation inrush currents. A proportion of relay operating current is passed
through a filter circuit, and the 100 Hz component from it is fed into a sensitive
winding on the relay which hinders it from operating. A timer of approximately
20 seconds is usually employed to ensure inrush currents have stabilised.
@
The connections for the protection of a three phase transformer are shown in
schematic form in Figure 11. Note that this diagram does not show the second
harmonic restraint nor taps on the relay.
ith
R
sm
B
rd
Neutral Point
Bias Coils
ha
Advantages
16
• High speed of operation.
• Protects external leads, cables, and bushings not covered by buchholz.
• Being unit protection - provides discrimination with time delayed non-unit
om
protection elsewhere on the system.
Disadvantages
• Does not detect some incipient faults. (These are detected by the buch-
holz)
.c
• Does not protect the transformer against overheating due to overloads or
external short circuits.
ia
3.1.8 Differential Earth Fault Protection of Star Windings
This protection consists of three phase CTs with secondaries connected in par-
allel to give the earth fault current. This residual current is balanced against
as
the secondary current from the transformer neutral CT and the difference is
applied to the differential relay (see Figure 13).
Thus the scheme detects earth faults between the neutral CT and the phase
@
CT’s, i.e. in the star winding of the transformer, LV bushings, and cable up to
the switchgear containing the CT’s.
Advantages
• Low Cost.
sm
• Fast fault clearance for heavy faults on cables as well as on the transformer.
• In conjunction with buchholz and fast protection of the delta winding, it
virtually provides unit protection of the bank, provided that short circuits
between phases are unlikely on either the HV or LV side, i.e. when cables
rd
are used on the star connected side, and spacings are larger on the other.
Disadvantages
• Does not protect against phase to phase faults or short circuited turns,
ha
• May not detect earth faults at the neutral end of the transformer winding.
Remember
• Unit protection operates for faults within clearly defined boundaries, usu-
ally between two sets of CTs.
17
A2 C.T
om
B2 M L
M L
C2 M L
.c
Neutral C.I
ia
To Trip
Circuit
}
E
as Restricted
E/F relay
@
Figure 12: Differential (Restricted) Earth Fault Protection of Transformer -
Operation on Fault inside Zone
ith
A2
C.T
B2 M L
sm
M L
C2 M L
rd
Neutral C.T
To Trip
ha
Circuit
Restricted
E E/F relay
ric
18
• There will be practically no current in a unit protection relay for an ex-
ternal fault.
• When unit protection operates, it trips without time delay.
om
• In differential protection of transformers:
• CT ratios and interconnections are chosen so that the currents com-
pared in the relay are nearly equal.
• Slight mismatch of currents is permitted by the relay design (bias).
• Transformer magnetisation inrush currents could operate the relay,
.c
but restraint is provided on modern relays by using the 100 Hz con-
tent.
ia
3.2 Busbar protection
Busbar protection is another example of unit protection. The most common
as
relaying principle adopted in the New Zealand transmission system is the high
impedance differential scheme, which is a circulating current scheme.
The basic principle of busbar protection is that for an un-faulted busbar the
total input current is equal to the total output. The sum of the currents is zero
@
for each phase. The relays measuring the summation of the currents receive no
current for un-faulted conditions of the busbar. However when a busbar fault
occurs, the balance is upset, and the relay receives current causing it to operate.
ith
The extent of the busbar and associated equipment protected by busbar pro-
tection (i.e. the ”bus zone”) is dependent upon the position of the busbar
protection C.T’s. The C.T’s may be in the circuit breaker (bulk oil circuit
breakers) or adjacent to the circuit breaker.
sm
zone A2 in a typical three zone scheme. For a bus zone tripping to occur both
differential relays have to respond to a fault e.g. for a fault in zone A1, the zone
A1 differential relay and the check zone differential relay. Detecting the fault
ha
In many cases it is not acceptable to remove the whole bus from service. A
ric
bus coupling CB can be used to sectionise the bus into two sections.
A fault on the bus in zone A1 will be detected in zone A1 and the cheek zone.
CBs 42, 52, 62 and 68 will be tripped via their bus zone relays. This leaves the
other section of the bus in service.
An example of Bus Zone Protection without a check zone is shown in Figure 16.
19
om
.c
ia
as
@
Figure 14: Busbar protection scheme for a single busbar
ith
sm
42 62 72 92
rd
68
52 82
ha
Zone A1 Zone A2
Check Zone
ric
Figure 15: Bus zone protection scheme for a single bus with bus section circuit
breaker
20
om
.c
ia
Zone A
as
112 142 172
Bus B
@
ith
Zone B
Bus B
132 162 192
sm
rd
Figure 16: Bus zone protection for circuit breakers and a half without check
zone
ha
ric
21
In this case a Bus A fault will trip CBs 112, 142 and 172 this will disconnect
Bus A without the loss of any supplies due to the Circuit Breaker and a half
configuration. The check zone is not essential, as in the case of accidental trip-
ping, no supplies are lost.
om
However, a check zone may be included with a circuit breaker and a half scheme,
so always check. The half breakers are not included in either zone and so are
not covered by the bus zone protection.
.c
A fault between 68 and the CT in Figure 17 is in the blind spot of the bus zone
protection.
ia
NOTE: Blind spots only exist where current transformers are separate from
the circuit breakers.
as
This fault in the blind spot will be detected by the busbar protection within
the CT zone (zone of detection) and thus the busbar protection will operate
the zone A1 circuit breakers 42, 52, 62 and 68 in Figure 17. However, the fault
will not be cleared by these trippings (even though the fault current may he
@
significantly reduced).
ith
sm
42 62 72 92
68
52 82
Blind Spot
Zone A1 Zone A
rd
Check Zone
ha
Figure 17: Busbar protection scheme for a single bus with a bus section circuit
breaker
ric
• Tripping the circuit breakers at the remote ends of the circuits associated
with circuit breakers 72, 82 and 92 (no blind spot or CB fall protection
22
fitted). This would be a zone 2 tripping and would not clear the fault for
approximately 0.65 seconds.
or
om
• By tripping circuit breakers 72, 82 and 92 via the zone A2 trip circuitry
(blind spot protection fitted).
Blind spot protection in its simplest form is only a timing relay. A fault
takes place in the blind spot in Figure 17. Zone A1 and the check zone
relays detect this fault. Zone A1 circuit breakers are opened but the fault
.c
is still supplied from zone A2 bus. A timing relay is also activated. After
a short time, approximately 0.15 seconds, zone A1 and check zone relays
are still detecting a fault. As the zone A1 circuit breakers are open the
ia
fault must be in the blind spot and zone A2 is tripped by the timing relay.
This requires a definite time to elapse, but is much faster than a zone 2
tripping from remote stations. The fault in the blind spot did however
as
clear both sections of the bus.
or
• Using CB fail protection
@
The CB fail protection would detect current flowing through the CT ad-
jacent to CB 68, after the CB had opened. This would be taken as a CB
failure and a trip signal sent to CBs 42, 52, 62, 72, 82 and 92, to isolate
CB 68 which had ”failed”.
ith
Blind spot protection is now being removed and replaced with CB failure, as
it completes the same function as blind spot protection, as well as protecting
against failure of a CB to operate.
sm
Blind spots also exist between all other circuit breakers and their CTs. Consider
a fault between 42 and its CT. As this is seen as a bus fault zone A1 will trip.
The fault will still be supplied from the remote end of the circuit which will trip
in zone 2. Other supplies on that bus have been interrupted unnecessarily. Ide-
ally we are only required to trip the circuit on 42, but as the fault was ”behind”
rd
If abnormal voltages are detected on the CT wiring then the protection is dis-
abled for the duration of the fault.
AC wiring supervision flags are self resetting and generally only evident for
a few seconds.
23
3.2.4 DC Supply Failure
In older installations a DC supply failure relay (or trip supply supervision relay)
is used to detect a D.C supply failure to the bus zone protection. One relay per
scheme or one per panel is generally installed.
om
In more modern installations it is incorporated with the bus zone protection
inoperative alarms. A loss of D.C supply to the protection will render the
protection inoperative.
.c
3.2.5 Protection Inoperative Alarm
An alarm is fitted to each separate bus zone to indicate loss of protection. In
Figure 17 these alarms are installed for zones A1 and A2. It is not necessary to
ia
install a separate alarm for the check zone as a fault in the check zone protection
will alarm all zones connected to it. A loss of check zone protection in Figure
17 will alarm both A1 and A2 zones.
When a circuit breaker receives a trip signal, but fails to fully disconnect its
associated faulted primary plant within its normal operating time, CB fail pro-
tection will be activated.
sm
CB fail protection shall be enabled only when the protected circuit breaker
has been called upon to trip by operation of its associated protection systems.
It shall not operate if the circuit breaker fails to open during a routine switching
rd
Remember
• It looks more complicated because there are more than two sets of CTs
for current summations.
• When the current entering the busbar is equal to the current leaving, the
sum of the currents is zero. Hence the sum of secondary currents is also
zero, and the relay is inoperative.
24
• If a fault occurs on the busbar, the balance is upset and the relay operates.
• A second differential relay must also operate for tripping to occur - the
busbar check differential relay.
om
• Circuit supervision relays cut out the protection after a time delay if there
is a slight out of balance of current.
• A check zone is usually included and the check zone and the faulted zone
must detect the fault before a tripping takes place.
.c
• Bus zone protection is most effective when the bus is in several sections
to limit the effect of the tripping.
• Blind spots exist between CBs and CTs. Faults in blind spots usually
ia
remove more equipment than essential from service to clear them.
as
3.3.1 Distance-time and definite distance protection
Distance relays are used to protect transmission lines. As their name implies
they measure the distance from the relaying point to the fault, and trip if the
@
measured distance is less than the relay setting.
Substation Fault
L
ith
V
sm
Fault current flows from the substation around the transmission line loop and
is supplied via current transformers to the relay. The voltage across the loop is
25
measured by the line (or busbar VT) to the relay.
Providing the resistance of the fault is negligible, the measured ratio Line Volts/
Line Current (V/I) is the impedance of the transmission line loop. Also the loop
om
impedance z is proportional to distance L. Hence a measurement can be made
of the distance to the fault.
If the measured impedance is less than the set value, it means that the fault is
closer to the substation than the distance for which the relay is set and therefore
the trip relay will operate.
.c
Discrimination Discrimination is provided by using the stepped time dis-
tance characteristic, as shown in Figure 19. AB and BC are transmission lines
ia
fed from both ends A and C. The relay at A measures the distance to the fault
when the fault current flows out from the busbar A into the line, and has the
time distance characteristic shown above the reference line 00. Thus for all
as
faults within the first 85% (approximately) of line AB, the circuit breaker at A
is tripped instantaneously. For faults further away the relay waits for about 0.5
seconds (zone 2 time), then measures a longer distance zone 2 (say 120% of the
line length) and if the fault is measured within this distance, breaker A trips.
If the fault continues, a greater distance zone 3 is measured and tripped in still
@
longer time (usually 1.2 seconds for zone 3 trippings). In addition a zone 4 may
be fitted that will operate in 4 seconds.
Relay B on the line BC has a similar characteristic with tripping time char-
ith
acteristics shown above the reference line 00. Relays at C on the line CB and
B on the line BA, measure for faults flowing from right to left on the diagram,
and have the characteristics shown below the reference line 00.
Consider now a fault at F. Relay A measures the fault as beyond zone 1 but
before zone 2 time elapses the fault is cleared at B. (Relay B, facing C, measures
sm
Note that zone 1 of each relay is arranged to cover about 85% of a line. This
is because the distance relays have unavoidable errors in measuring distance. A
margin has to be allowed so that faults outside’ the line are not seen as zone 1
rd
faults.
Zone 2 distance covers about 120% (or more) of the line to ensure definite
detection of all faults at the end of the line. Zone 3 provides general back up
ha
26
om
A B C
.c
ia
A – Zone 3
A – Zone 2
A - time to operate
as
A – Zone 1
0 0
@
B– Zone 2 B– Zone 2
ith
B - time to operate
B– Zone 1 B– Zone 1
0 0
sm
C – Zone 3
C – Zone 2
C - time to operate
rd
C – Zone 1
0 0
ha
Figure 19: distance protection zones
ric
27
V 0
i.e. voltage V = 0 therefore Z = = =0
I I
om
phase to phase faults, a voltage in a selected un-faulted phase is used as a ref-
erence of the direction of the fault (towards the line, or reverse direction).
The relay trips in the first two zones for faults out towards the line, but does
not trip for reverse faults (behind the busbars).
.c
The measurement principle used extensively combines directional measurement
and distance measurement in one relay element. (One tripping contact, only
closed when direction is correct, and volts/amps measurements conform to set-
tings).
ia
Starting Relays Starting relays are used to sense a fault on the system, and
start the various relay measurements. If the fault is cleared elsewhere on the
as
system the starting relays reset. (Starting flags do not necessarily mean that a
fault has occurred on that particular transmission line.)
Impedance relays are generally used on each phase, and are given directional
@
phase angle characteristics for better load carrying insensitivity. The starting
relays also select which phases are to be measured, and whether to measure for
faults to earth or to measure phase to phase faults.
Negative sequence current relays are used in some relays to initiate phase to
phase fault measurement, these detect current imbalance in the three phases.
sm
Measurement of Three Phase Faults For three phase faults close to the
protection relay, all voltages fall very low, and in particular, the phase to phase
reference voltage is very low. The reference voltage is the phase to phase volt-
age which is used to enable the relay to determine in which direction the fault
current flows, whether to the line or from the line. Without sufficient reference
voltage the relay is unable to trip.
rd
in the reference winding persists for a few cycles after the reference voltage has
collapsed. Thus with the relay in service, if a three phase fault occurs the relay
can determine the direction of the fault.
However when the VT’s are directly connected to the line, and the line cir-
ric
cuit breaker is open, there is no voltage for the relays to ‘remember’ and the
feature cannot operate. This is overcome by arranging a contact to be closed
for a short time while the main breaker is being closed. If any starting relay op-
erates, the trip circuit is completed through this contact, and the main breaker
is tripped.
28
Other relays at the station, with already livened VT’s will sense the direction
by memory action, and will not trip.
om
secondary voltages is usually fitted on the relay panel, this also disconnects the
D.C supply to the relay, and effectively prevents the distance relay from operat-
ing. When busbar VT’s are utilised, a changeover switch is fitted to select the
voltages from one of the VT’s.
Care has to be exercised that the VT supply to relays is not lost, particularly
.c
when sectionalising a busbar with VT’s on it, or an accidental tripping may
result. Care must also be exercised with busbar VT’s to ensure that the relay
receives the line terminal voltage from a VT directly connected to the line via
ia
the line circuit breaker not through a circuitous route involving line impedances.
In the latter case distance measurement would be incorrect.
29
• Stepped time distance characteristics are used for discrimination.
• The measurement by relays used in New Zealand is inherently directional.
om
generally overcome by use of ”memory” relays.
• Distance relays measure line impedance and so must be supplied with the
line terminal voltage. The line terminal voltage is the same as the busbar
voltage when the line circuit breaker is closed.
.c
In some installations the line terminal voltage for the relay is taken from
a busbar VT (usually on 110kV circuits). In such instances, if the busbar
is to be split, care must be taken that the busbar VT used is directly
ia
connected to the line (through the line CB, and not through a circuitous
route involving line impedances) otherwise distance measurement will be
wrong.
as
• Disconnection of the VT supply to the relay, other than by special means
provided, can result in relay tripping due to load.
tripping at one end of the line in zone 1 accelerates the operation of the zone 2
measurement at the other end of the line (see Figure 20).
Consider a line AB, faulted within 15% of its length from station A. The relay
at station A trips immediately, and sends a signal to station B to change its
distance measurement from 85% of the line length to 120%. The relay at B now
rd
detects the fault and trips without having to wait for zone 2 time to elapse.
One advantage of this carrier signal system is that there is no danger of trip-
ping a remote circuit breaker during communications or protection maintenance.
ha
The same signal as used for accelerated distance protection can be used with
earth fault directional comparison protection. The two protections can be com-
bined and are on most Transpower 220 kV transmission line protection schemes.
ric
The loss of carrier (or other signalling channel) results in the loss of the di-
rectional comparison and the distance protection reverts to plain distance pro-
tection.
30
Normal characteristics of
relay at B
om
Time
Time
0 0
.c
Postion of
Fault Tripping characteristic of
ia
relay at A
A B
as
Figure 20: Acceleration of Distance measurement
This scheme requires careful coordination of relay and carrier signal timings,
ith
but the carrier signal does not have to be sent over a faulted transmission line.
It has been used on the New Zealand grid but is currently out of favour.
rious signal (electrical interference from arcing of isolators etc.) can be avoided
by coding the signal.
This scheme would be used say in tripping a circuit breaker at a remote con-
trolled station if a buchholz relay operated, and there was no local circuit
rd
breaker.
Signalling Systems
• Power Line Carrier Chop System - In this system a ”carrier” signal is sent
ric
31
• Frequency Shift Signalling - Under normal conditions a steady signal
(guard signal) is sent. To transmit a protection signal, the guard sig-
nal is stopped, and replaced by an operate signal of a different frequency.
Hence the name frequency shift. The transmission medium may be carrier
om
or radio.
.c
it sends a trip signal.
ia
is that fault current is fed inwards towards the line from both ends; hence the
relaying condition for tripping is that each protection is both sending and re-
ceiving a trip signal (see Figure 21).
Fault
as
@
RELAY RELAY
Trip Trip
ith
Fault
sm
RELAY RELAY
Trip Block
If the fault is external to the line, the primary fault current flows out of the
protected line at one end. The corresponding relay swings to the ”block” posi-
tion and does not transmit a ”trip” signal, hence neither of the line breakers is
tripped.
ha
This protection can detect earth faults more sensitively than distance protection,
and hence detects faults at towers with relatively high tower footing resistance
to earth.
ric
The same carrier signal can be used for DCEF as for distance protection with
acceleration.
32
3.3.2 Auto Reclose
The majority of faults on transmission lines are transient ones, and when the
line has been disconnected at both ends the arc at the fault de-ionises (cools),
after which the line may be successfully re-livened. When a signal system is used
om
to provide fast tripping at both ends of the line (eliminating any zone 2 delayed
tripping) high speed auto reclose can be used successfully. Thus the carrier is
not used directly for reclosing the breaker at the far end, but it ensures that the
breakers at both ends are tripped before either is reclosed.
.c
If the signalling link (acceleration) is out of service, successful auto-reclose will
still take place for faults within the middle 70% of the line. Faults within 15%
of either end will be cleared from one end in delayed zone 2 time and no reclose
(since reclose is initiated from zone 1 tripping only). The other end will trip in
ia
zone 1 with auto reclose but this will be unsuccessful since the remote CB has
not yet tripped.
as
Early model signalling schemes had circuitry which automatically switched out
auto reclose should the acceleration fail. Later schemes do not have this facility.
this under fault conditions) through pilot circuits of high impedance. This is
impracticable and the provision of long pilot wires of low impedance is also un-
economic. The permissible voltage developed across pilots must also be limited
to practical values.
sm
A method that minimises both the number of pilot cores and the magnitude
of the current circulating in the pilot wires uses a summation transformer to
derive a single phase relay current as shown in Figure 22. Each line CT energises
a different number of turns on the summation transformer primary and so there
is an output current even when the system is healthy and balanced.
rd
Pilot wire protection is very suitable for short lines, provided that satisfactory
pilot wires can be provided. However if the pilot becomes faulty the protection
will either trip or not operate, depending on whether the pilot fault is a short
circuit or an open circuit and on the type of pilot wire protection used (as well
ha
It is of course essential that the pilot wires can withstand the voltages which
develop, including fault conditions. Pilot wire supervision is generally fitted to
check the soundness of pilots under normal conditions but it may not indicate
ric
Taking pilot wire protection out of service has to be done in such a sequence
that neither of the two relays at the two ends of the line may operate. Generally
it necessitates:
33
R
om
B
Summation
Transformer
.c
Output
ia
as
@
Figure 22: Summation Transformer
ith
Since protection is lost if pilot wires become faulty, to increase reliability two
pairs of pilot wires can be provided for each transmission line, over separate
routes so that they are unlikely to fail together.
Advantages
rd
• About the only type of available fast protection for short lines.
Disadvantages
• Needs other protection to cover adjacent busbars, and other blind spots
ric
34
In the experience of electricity distribution in New Zealand, overhead pilots are
subject to short circuits from wind, pole interference by vehicles, animals, de-
bris, kites, rifle fire and lightning.
om
Buried pilots are subject to interference from bulldozers and other digging op-
erations, particularly in city areas. Also rise in earth voltages during faults can
cause insulation breakdown. Altogether the cost of maintenance of pilot wires
has been a great deterrent to using this form of protection.
Remember
.c
• Pilot wire protection is a modified form of differential protection.
ia
• Protection will trip for short or open circuited pilots, depending on type
of protection.
• Pilot wire protection is excellent for short lines, if the reliability of the
as
pilots is good.
• If the protection has to be taken out of service with the transmission line
in service, the correct sequence for operating test switches requires an
operator at each substation.
@
3.3.4 220kV Oil-filled Cable Protection
Where the cables are to be buried an alternative to pilot wire protection could
ith
be using oil filled cables. The oil in the cables is for insulation purposes and is
under pressure.
A low pressure alarm and low pressure trip are also provided to indicate any
damage to the cable (possibly from an external source) and hence remove the
circuit from service.
rd
Additionally a buchholz relay can be fitted at the end of the cable to indicate a
fault within the circuit.
Remember
ha
35
• Directional comparison earth fault protection detects internal line faults
to earth by comparing the direction of current flow.
om
DCEF) is that each relay at the line ends receives and transmits a ”line
faulted” (trip) signal.
• Directional comparison earth fault protection is more sensitive, generally,
than distance protection.
.c
protection.
ia
Generators are an important component of the power system. They are expen-
sive both in terms of initial investment and down time. If they suffer damage
they cannot he quickly repaired. It is therefore economic to provide them with
as
a protection system which reduces the possibility of damage from any internal
fault or other cause.
Breakdown of stator insulation may cause earth faults, phase to phase faults or
three phase faults. Phase to phase faults and three phase faults may or may
sm
not involve earth. However, experience has shown that phase to phase faults
which do not initially involve earth, very rapidly do so. Three phase faults are
amongst the rarest type of fault on a generator. Protection for phase to phase
faults also provides protection for three phase faults.
All generators are provided with two stator protection schemes. These are
rd
stator differential protection and stator earth fault protection. The more recent
installations also include stator inter-turn protection.
ha
earth sometimes directly but most often through a current limiting component.
The current limiting component provides a moderate restraint against the flow
of massive earth fault currents. This has the effect of minimising damage to
the generator winding resulting from an earth fault. This is important since a
severe earth fault inside a generator can cause extensive damage to windings
36
and insulation and possibly cause an internal fire and also It can weld together
sections of iron laminations which could necessitate stator rebuilding.
om
unit system will be considered. This form of connection is commonly found in
thermal generating stations. The generator neutral point is earthed through a
voltage transformer which is arranged to initiate an alarm or to immediately
trip the unit when the voltage between the neutral point and earth exceeds a
pre determined value. Such a system is illustrated in Figure 23.
.c
Generator Transformer Station Busbars
ia
as
Earth Fault Protection Zone
@
To Alarm trip circuit
ith
sm
Also shown by a dotted line in Figure 23 is the earth fault protection zone; the
earth fault protection responds to an earth fault in equipment only within this
area. It is seen that in addition to the generator stator windings, the primary
rd
For an earth fault outside the protection zone, while the generator phase cur-
ha
rents will become unbalanced, no current will flow in the generator neutral
voltage transformer connection because of the delta connection of the primary
windings on the generator and unit auxiliary transformers, and so the earth
fault protection remains inoperative.
ric
It has been pointed out that the earth fault current is limited by the impedance
of the voltage transformer in the generator neutral. The magnitude of the fault
current depends also on the location of the fault with respect to the neutral
point.
37
3.4.2 Stator Differential Protection
This protection, sometimes called circulating current protection, is designed
principally to protect the generator against internal phase to phase faults. De-
pending on the method of neutral earthing, a measure of protection against
om
phase to earth faults may be provided, but in most cases, a separate stator
earth fault protection scheme is necessary. Because of the high current and
possible damage following a phase to phase fault, the differential protection is
designed to clear the fault practically instantaneously.
.c
Generator differential protection is a scheme whereby the current at the neutral
end and the current at the terminal end in each of the three phase windings is
compared. The circuit is arranged so that any inequality between these currents
due to a fault will cause a spill current to flow through the differential relay,
ia
causing it to operate.
In order to measure the current entering and leaving each of the three phase
as
windings, each winding has a CT connected at the neutral end and another at
the terminal end. The secondary windings of these CT’s are interconnected in
such a way that a current normally circulates in the secondary circuit. Hence
the term circulating current protection. Figure 24 shows the usual position of
the differential protection CT’s.
@
Neutral Point
ith
Stator
Stator
Output
sm
Windings
rd
Protection Zone
38
in the secondary circuit, the currents remain balanced and the relay does not
operate.
Neutral Point
om
Neutral Point Single Phase Stator
Winding
I
.c
Current
circulating in
C.T
secondary
circult
ia
as
Differential Relay
(Zero Spill Current under
healthy conditions)
Two other faults, an open circuit and an inter-turn fault in one of the phase
windings, also will not be detected by the normal differential protection scheme.
In the former case, no current flows in the phase winding and in the latter case,
the fault current flows only in the local circuit between the turns involved, and
hence the CT’s at either end of the phase windings will not detect a condition
rd
of unbalance. In both cases, however, a fault to earth will usually develop and
protection will be provided by the normal stator earth fault protection.
It is not usual to provide protection on an A.C generator for external three phase
short circuits. This is because the overcurrent relay required for this protection
normally would not operate in time before the short circuit current fell below
the relay setting.
ric
When considering the protective gear for generators, one must have a broad
knowledge of the characteristics of rotating machines.
Immediately a short circuit occurs on the generator, the short circuit current
rises to between 5 and 10 times full load. The initial stator current rises to a
39
value which is limited only by the sub transient leakage reactance of the ma-
chine which, for all intents and purposes, is equal to the leakage reactance. The
leakage reactance is due to the flux set up by the stator magnetomotive force
which fails to cross the air gap. The increase in stator current which is predom-
om
inantly of a lagging characteristic causes a demagnetising effect by opposing the
air gap flux, but it is an appreciable time before a major change in the air gap
flux can he completed. The net effect is a gradual decrease in the short circuit
current over a period of seconds to a value which can be well below full load of
the machine.
.c
Modern A.C generators are able to withstand the effects of an external short
circuit for a short period, provided the three phase currents are balanced.
ia
Sustained three phase faults external to the machine are not dangerous. The
most likely sequel is loss of synchronism and instability, after the fault has
cleared. No special protective system is installed to guard against this con-
dition. It is the duty of the automatic regulator to deal with the generator
as
stability.
Negative phase sequence currents in the generator stator are caused by un-
rd
by overheating of the rotor body, slot wedges and rotor end winding retaining
rings. The Huntly machines may continue to operate with a maximum negative
phase sequence component of current of only 15% of full load current, a reflec-
tion of the high electrical loading of the machines.
With the increase in size of units the time factor for allowing the negative
40
phase sequence current to flow in the generator has diminished.
om
certain items of plant.
.c
R
ia
as
F
@
B Y
ith
Now if the rotation was reversed so that the phasors rotated in a clockwise
direction, passing F in the sequence, R, B and Y as in Figure 27, we would
sm
have a negative phase sequence system. If we had the three phase cables con-
nected to terminals, you can see that a complete phase reversal from positive
phase sequence (PPS) to negative phase sequence (NPS) is produced, merely by
changing the Y and B connections in the example shown. (Changing any two
phase connections would produce the same result.)
In addition to positive and negative phase sequences, a three phase power system
rd
can produce another phenomenon known as zero phase sequence (ZPS). This can
be displayed vectoriaIly as three phasors rotating together as shown in Figure
28.
Now, different system faults can cause various combinations of positive, nega-
ha
tive and/or zero phase sequences to occur in varying amounts. For example, a
phase to phase fault will create a mixture of PPS and NPS. A phase to earth
fault may cause a combination of PPS, NPS and ZPS. An open circuit phase
connection (such as one phase of a breaker failing to close) may also cause PPS
ric
+ NPS + ZPS.
When ”seen” from an individual generator, the amounts of PPS, NPS and ZPS
will depend upon the load being supplied, the severity of the fault, and amount
of generation on the system and the distance the fault is from the machine (in
other words the impedance to the machine.
41
om
R
.c
F
ia
B
as
Figure 27: Negative sequence rotation
Y
@
ith
sm
Ro
Yo
Bo
rd
ha
ric
42
It is the negative sequence component that has a damaging effect on a turbo-
alternator by producing excessive heat in the rotor. This is explained by refer-
ence to Figure 29 (a) and (b).
om
Stator PPS Field
Rotor
N
.c
Rotor
ia
N
as
Stator
Rotor
N
sm
S
Stator
Figure 29: Effects of PPS and NPS on turbo-alternator (top - Positive phase
sequence; bottom - Negative phase sequence)
rd
field produced by the stator with current drawn from the power system. Under
these conditions there is no relative movement between rotor and stator
Now, let us see what happens when a negative sequence component is intro-
duced from the power system into the stator winding of the machine. The
ric
positive sequence still produces a stator field in the counter clockwise sense.
The steam turbine still drives the rotor in a counter clockwise sense and at the
same speed as the PPS field. The Negative sequence is producing a rotating
field in the opposite direction to the PPS field and the rotor. The relative speed
of NPS field and rotor is twice rotor speed so that currents are induced in the
rotor at twice system frequency (100 Hz on New Zealand system). Because the
43
rotor is designed to operate under static flux conditions, and to give a high me-
chanical strength, it is made from a solid steel forging. This solid forging gives
many paths for the induced currents (at 100Hz) induced by the NPS component.
The end result is rapid heating of the rotor, destruction of the rotor insulation
om
and perhaps bending of the rotor itself. The latter could result in catastrophic
disintegration of the machine since the rotor may weigh many tonnes and is
rotating at 3000 rpm.
Therefore, the modern turbo alternator must be protected from the effects of
negative phase sequence.
.c
3.4.5 Reverse Power Protection
When the prime mover power falls below the level needed to keep a generator
ia
spinning at synchronous speed, power flows in the reverse direction and the
machine becomes a motor. Although this action is wasteful it does not damage
the generator but if the prime mover is a steam turbine, running it with air
as
in its low pressure stages will cause severe overheating and damage might be
caused to the turbine blades. However with the protection systems installed on
Thermal Units the circumstances in which motoring can take place will be most
infrequent in the life of the Unit. This is because for any speculated type of
@
fault the HVCB will be tripped before motoring can take place. The protective
devices which operate should trip the HVCB when the forward power is about
0.5% of the MW power rating.
Steam driven units have a reverse power relay which either gives an alarm,
ith
Damage arises if the protection system fails due to some mal-operation in which
case operator action will be necessary. However, it must be remembered that it
sm
is normal for more than one sensitive relay to be fitted to reduce this risk.
Hydro machines with tail water depression have a reverse power relay to prevent
motoring with a turbine scroll case full of water.
rd
ha
ric
44
4 Non-Unit protection
Non unit Protection will respond to a fault over a wide area of the system. In
general the area will not be precisely defined and will be influenced by factors
om
such as system fault level, system configuration etc. Operation of non unit pro-
tection will provide only a rough indication of the fault location.
Where both unit and non Unit protection have operated the unit protection
.c
flags will provide a more positive indication of fault location than those of the
non unit protection.
If a transformer tripped and the flaggings were on the differential relay, then
ia
the fault must be between the CTs (unit protection). This unit will include
the transformer and usually connecting cables or buswork. A Buchholz trip-
ping would indicate a fault within the transformer. If however, the transformer
as
tripped on overcurrent (non unit protection) the fault would he outside the
transformer. The overcurrent would indicate the transformer was overloaded,
perhaps due to a fault on the system or to excess system loading. The flagging
given do not identify the location of, or reason for the overload.
@
4.1 Overcurrent Relays
Current magnitude is widely used as a means of detecting faults on low voltage
distribution systems, but not so widely on extra high voltage (E.H.V) transmis-
ith
The need for ”selectivity” with overcurrent protection is clear in the simplest
sm
systems. Consider the situation where one incoming feeder set to trip at 400A
gives supply to two outgoing feeders each set to trip at 200A, i.e.
If a fault occurs on feeder C the resultant current will flow through the two
circuit breakers A and C in series. Unless the time delay on A exceeds that on
C by a safe margin both circuit breakers will open. This is not necessary to
clear the fault. A should remain closed to maintain supply to feeder B.
rd
A variety of time characteristics are used with overcurrent relays. Inverse time
current relays offer better selectivity and permit lower time settings where the
level of generation is reasonably constant and the fault current is controlled
ha
by the fault location. Very inverse time characteristics are used where sharper
selectivity is required, for matching the time characteristics of fuses, or for the
protection of power rectifiers.
ric
Overcurrent relays protect against faults between 2 or all 3 phases. These relays
do not necessarily give satisfactory protection for phase to earth faults as the
current magnitude may be restricted by the earth impedance.
45
B
om
200 A
12
.c
400 A
C
200 A
ia
4.2 Earth Fault Relays
Figure 30:
as
@
Most faults within equipment are due to an insulation failure on one phase al-
lowing current to flow to earth, a condition which may lead rapidly to a fault
between phases and possibly to danger to personnel. Earth fault protection is
therefore required to detect a fault to earth and disconnect it from the system
ith
One principle of operation of earth fault protection is based on the fact that
in a balanced circuit currents in the three phases sum up (vectorially) to zero.
sm
When a fault between one phase and earth occurs this balance is upset and the
out of balance (or residual) current is fed to the relay.
Earth fault relays are essentially overcurrent relays which, by virtue of the relay
CT connections, are sensitive only to earth faults. Current settings are much
lower than for overcurrent relays since normally no current flows in the relay.
rd
Earth fault relays are used in unit protection schemes where they will oper-
ate only for faults within a clearly identified part of the system.
ha
Earth fault relays are also used for non unit protection. For example: feeder
protection, LV bus bar and feeder back up protection, HV bus bar and line
back up protection, and Inverse time relays on interconnecting and generator
transformers.
ric
46
The earth fault relay is instantaneous in operating and very low earth fault
settings can usually be obtained. For unearthed windings delta or star the pro-
tection would consist of a single pole instantaneous earth fault relay with or
without a series resistor depending on the type of relay. This is the “plain earth
om
fault” system of protection and is shown in Figure 31.
.c
ia
as
Stabilizing
resistor
@
Over
Current Earth fault Relay
relay
ith
Trip Coil
sm
Most 11kV and 33kV feeders have an earth fault relay operating on the principle
of residual current in the three phases.
The connection of the earth fault relay is similar to that of the star transformer
ha
in Figure 31. In the case of the circuit a CT is not used in the neutral or earth of
the transformer. Without this CT the earth relay will only detect an earth fault
from the CT’s outwards (i.e. away from the transformer). At a substation each
feeder would have protection similar to that in Figure 32. As each responds to
earth faults past the CTs each feeder is easily separately protected.
ric
47
C.T.s
om
.c
Over current Relay coils
ia
Earth Fault
R.Y & B Phases
Relay Coil
4.5 as
Figure 32: Overcurrent and Earth Leakage Relays Connections
CT F
rd
Figure 33:
Remember
ha
48
4.6 Time Graded (Non-Unit) Protection
Time grading is commonly used in protection to selectively trip circuit breakers
when a fault occurs on the system. A simple case is that of instantaneous
overcurrent definite time protection applied to line breakers fed in series (see
om
Figure 34).
A B C D
.c
ia
Figure 34:
as
Instantaneous Relays with Definite Time
@
Operating
Time Relay A Operated
(Sec’s)
ith
1.5 A
1.0 B
sm
0.5 C
Time Graded Protection Figure 34 shows transmission line AD, fed from
end A, supplying power to substations B, C and D in series. Circuit breakers at
A, B and C are fitted with instantaneous overcurrent relays, tripping in definite
times of 1.5, 1.0 and 0.5 seconds. The overcurrent settings are high enough to
carry load currents, but operate for fault currents. The tripping characteristics
ric
When a line fault occurs at F on section CD, relays at A, B and C all carry
the same fault current and pick up. But the time setting of C of 0.5 seconds
is less than B by an adequate margin, and the smallest section of line, CD is
49
Inverse Time Relays
om
Operating
Time Relay A Operated
(Sec’s)
.c
B
ia
Primary Current Fault Current at
“F”
as
Figure 36: Inverse Time relays
@
disconnected. It can be seen that discrimination is thus obtained, and that it
applies for all values of primary currents which could occur.
the earth fault relay at C is given a clearing time for earth faults of 2 seconds.
Earth fault relay B is then set to clear earth faults in 2.5 seconds, and A is set
to clear earth faults in 3 seconds.
ha
The clearing times for earth faults can be, and generally are, quite different
from phase faults clearing times - if C discriminates with B for earth faults, and
C also discriminates with B for phase faults, C discriminates for all types of
faults.
ric
Remember
50
• Time discrimination is commonly used to trip faults from the system se-
lectively.
• Earth fault protection time settings may be completely distinct from phase
om
fault protection (overcurrent) time settings (as well as having different
sensitivities).
.c
locations to provide selectivity and to prevent healthy plant backfeeding the
fault.
ia
Voltage circuit
as Disk (Rotating)
@
Current Circuit
Figure 37: Directional relay
ith
current flow is in the reverse direction the disk rotates in the reverse direction
and the contacts are open and the inverse time relay will not operate.
It can be seen from the diagrams below that if non directional relays are applied
rd
to parallel feeders any faults occurring on the line will inevitably, irrespective
of the relay settings chosen, isolate both lines and completely disrupt supply.
To ensure selective operation (i.e. remove only the faulted feeder) it is usual
to connect relays R3 and R4 such that they only operate for faults occurring
ha
in the line in the direction indicated. They should also operate before the non
directional relays R1 and R2.
Remember
• Overcurrent relay can be fitted with a directional element, so they only
ric
51
om
.c
ia
as
Figure 38: Non-Directional relays applied to parallel feeders
@
ith
sm
R1 (1SEC) R3 (0.5SEC)
rd
ha
R2 (1SEC) R4 (0.5Sec)
ric
52
5 Backup Protection
Even protection with very high reliability can fail to operate, and other inde-
pendent protection is called upon to act. The main protection is called ’primary
om
protection’, and the reserve protection is called ’back up protection’.
Back up protection generally takes the form of another protection nearer the
source than the primary protection. Thus for an 11 kV feeder fitted with over-
current and earth fault protection, the over current and earth fault protection
on the transformer bank acts as back up protection.
.c
Back up protection is generally less sensitive, slower to operate, and does not
provide the selectivity of primary protection. That the back up protection is in-
ferior is generally not given sufficient emphasis. Removal of primary protection
ia
always involves a calculated risk.
Take the case of feeder protection. The back up overcurrent protection, pri-
as
marily for transformer overcurrent protection with high CT ratios, may only
respond for faults on the first 3 or 4 kilometres, and the earth fault protection
may not be able to operate unless contact is made with a well earthed conductor.
@
Distance protection measures a longer distance if it receives only a part of the
line fault current, i.e. if there is other fault currents fed into the line.
A
ith
B 1
10 IA Protected Line
Backup
relay IA
F
sm
IF
9
10 IA
rd
For example Figure 40 shows a back up relay which receives only 1/10 of the
fault current and therefore sees a distance 10 times as great (= 10 AF + AB in
the diagram).
The starting relays at B will probably not respond. The trend in back up
ric
53
• Permission is required from the equipment owner before protection is taken
out of service.
om
also require permission.
• Consider taking the main equipment out of service instead of removing
the protection.
.c
ia
as
@
ith
sm
rd
ha
ric
54
6 Measuring Voltage and Current
6.1 Voltage Transformers
The voltage transformer (VT) is used to step down a given primary voltage, ac-
om
curately to a definite secondary voltage. The usual secondary voltage is 110V.
On 3 phase VT’s the secondaries are usually 63.5V each, star connected to give
a line voltage of 110V. The secondary winding is isolated from the primary
winding. The VT works on a similar principle to power transformers but VT’s
are never used to supply any power load as the current in the transformer would
.c
cause ‘copper losses’ and the secondary voltage would he inaccurate. The VT
is only used to supply relays, meters, potential lamps, master clocks etc.
Oil filled double wound VT’s are used for line voltages up to 110kV. On 220kV
ia
lines and other 110kV equipment CVT’s are used.
Two types of capacitor voltage transformer or CVT are in use. Older CVT’s
as
use a stack of 10 capacitors of equal value connected in series between phase
and earth to act as a voltage divider. A VT is connected across the capacitor at
the earth end of the stack. The primary voltage of the VT is therefore equal to
10% of the phase voltage. That is on a 220kV circuit 12700. The voltage ratio
of the VT is then 12700 to 63.5V.
@
Modern CVT’s are built with the capacitors enclosed in a bushing with the
VT mounted at the base.
ith
On all CVT’s a connecting network is used on the primary of the VT. This
has calibration adjustments to allow for errors in ratio (due to the tolerance of
capacitor values) and phase displacement (due to the phase displacement in the
capacitors).
sm
at one point. For line CTs this is usually in the outdoor junction box at the
star point of the CT connection.
There are two main types of CTs used for two different uses: measuring CT’s
ha
used with instruments and meters, and protective CTs used with protective
relays. Measuring CTS are designed to maintain their specified ratio of trans-
formation up to 150
Protective CTs are designed to maintain their specified ratio to at least 600%,
ric
sometimes 2000% or even 3000% of rated current. These CTs must be accurate
under heavy current fault conditions to operate the relays.
One CT is therefore not suitable for both metering and protection circuits.
Line CTs used on extra high voltage circuits contain several individual CTs
55
within the one enclosure, 5 being typical 2 for metering and 3 for protection.
CTs not in use are short circuited and earthed. Some circuit breakers have CTs
in their bushings. Typical CT secondary currents are 1 or 5 amps. If a line
carries a full load of 1000A, the CT ratio will be 1000:1 or 1000:5, depending
om
on the current required by the metering and protection in use.
NOTE. A CT must not be energised with its secondary open circuited. With
no secondary demagnetising magneto motive force produced, the core usually
saturates and produces a very high voltage, often several thousand volts in the
secondary winding. This can damage insulation and endanger life.
.c
Remember
ia
• CTs are designed for one of two uses.
• CTs secondaries must be earthed at one point for safety.
CT’s.
as
• A ”Current Transformer” or a CB bushing may contain several separate
• VT’s may be a double wound oil filled transformer if the high voltage is
@
110kV or less. At 110kV and above capacitor voltage transformers are
used.
ith
sm
rd
ha
ric
56
A Pre 1985 relay codes
Electrical protection relays are designated by a Standard Code which indicates
the type and duty of the relay. Each relay is prefixed by the number of the circuit
om
breaker which it trips. In the case of the generator protection at Huntly, there
are 3 220kV C.B.’s which are tripped and the number of the Bus ’B’ Selector
breaker is used as the prefix. A letter follows this number to indicate the relay
function in the protection scheme. The letters applicable to the protection
schemes at Huntly are as follows:
A Instantaneous Overcurrent
.c
B Instantaneous Earth Fault
C Definite Time
ia
D Tripping
E Inverse-Time Overcurrent
F Inverse-Time Earth Fault
H Distance
as
@
I Negative Phase Sequence
J Differential
M Temperature (including motor thermal overload)
ith
X Special Functions (low forward power, boiler trip, turbine trip, etc)
In addition, where more than one relay of the same class is associated with the
same circuit breaker, a number suffix is applied. Also the individual phases
ha
Example:-
ric
262 E1 (R) - indicates an inverse-time overcurrent relay, fed from Red phase
and associated with C.B. 262, ie Generator 1 circuit. This relay is in fact the
220kV Generator Transformer 1 inverse time overcurrent relay.
262 E2 (R) - indicates a similar class relay and is the unit transformer high
voltage inverse time overcurrent relay.
57
B Post 1985 relay codes
Since the mid 80’s most plant commissioned in New Zealand has followed the
American National Standards Institute ANSI/IEEE C37.2 code for numbering
om
of electrical protection relays. Each relay is designated by its device function
number, with appropriate suffix letter or letter where necessary which denote
the main device to which the relay is applied or related.
Some of the standard device numbers applicable to the Huntly Unit 5 site are
as follows:
.c
14 underspeed device is a device that functions when the speed of a machine
ia
falls below a predetermined value
21 distance relay is a relay that functions when the circuit admittance, impedance,
as
or reactance increases or decreases beyond a predetermined value
25 synchronizing or synchronism-check device is a device that operates when
two A.C circuits are within the desired limits of frequency, phase angle,
and voltage, to permit or to cause the paralleling of these two circuits
@
27 undervoltage relay is a relay which operates when its input voltage is less
than a predetermined value
28 flame detector is a device that monitors the presence of the pilot or main
ith
41 field circuit breaker is a device that functions to apply or remove the field
excitation of a machine
46 reverse-phase or phase-balance current relay is a relay that functions when
the polyphase currents are of reverse-phase sequence, or when the polyphase
rd
52 A.C circuit breaker is a device that is used to close and interrupt an A.C
power circuit under normal conditions or to interrupt this circuit under
fault or emergency conditions
59 overvoltage relay is a relay which operates when its input voltage is more
than a predetermined value
58
81 frequency relay is a relay that responds to the frequency of an electrical
quantity, operating when the frequency or rate of change of frequency
exceeds or is less than a predetermined value
om
86 lockout relay is a hand or electrically reset auxiliary relay that is operated
upon the occurrence of abnormal conditions to maintain associated equip-
ment or devices inoperative until it is reset
87 differential protective relay is a protective relay that functions on a percent-
age or phase angle or other quantitative difference of two currents, or of
some other electrical quantities
.c
Some of the standard suffix letters that can be applied to device numbers are
as follows:
ia
A Alarm or Auxiliary power
B Battery
D Discharge or DC direct current
as
@
E Exciter
F Feeder
G Generator
ith
M Motor or Metering
N Neutral
R Reactor or rectifier
sm
S Synchronising
T Transformer
Examples:-
rd
59