SHORT-CIRCUIT REPORT

3-Phase fault at bus: Bus3

Nominal kV = 230.000
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 2.005 kA Method C
Steady State = 0.780 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus3 Total 0.00 0.381 -0.997 2.6 1.067

Bus1 Bus3 47.00 0.190 -0.498 2.6 0.533

Bus2 Bus3 47.00 0.190 -0.498 2.6 0.533

Bus2 Bus1 47.00 0.000 0.000 999.9 0.000

Bus4 Bus1 66.00 0.190 -0.498 2.6 0.533

Bus5 Bus2 66.00 0.190 -0.498 2.6 0.533

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 1.054 1.148 0.454

0.02 1.056 1.065 0.137

0.03 1.055 1.056 0.041

0.04 1.051 1.051 0.012

0.05 1.045 1.045 0.004

0.06 1.047 1.047 0.001

0.07 1.049 1.049 0.000

0.08 1.050 1.050 0.000

0.09 1.050 1.050 0.000

0.10 1.051 1.051 0.000

0.15 1.051 1.051 0.000

0.20 1.049 1.049 0.000

0.25 1.045 1.045 0.000

0.30 1.038 1.038 0.000