Project Title

GC-32-PLQ-S40-1

Circuit Phasing Test

Location Gulf Chlorine W.L.L., - MV Switchgear Room


Cable Route 132/33/11 kV MIB Substation to Gulf Chlorine Substation Date: 24.01.2018
Cable Type 33 kV 1C x 300mm2 CU/XLPE/Pb/HDPE Temperature 28 ºC
Feeder No E50 Length (Red) 2416 m
Equipment Fluke Multimeter, S.No:99190416 Length (Yellow) 2416 m
Calibration Validity:20.05.2018 Length (Blue) 2416 m

Requirement: Phasing corresponds end to end i.e. Local Measurement to match Remote Setti

Phase Remote Settings Local Measurement

Red Earthed Red Earthed


Red Yellow Open Yellow Open
Blue Open Blue Open

Red Open Red Open


Yellow Yellow Earthed Yellow Earthed
Blue Open Blue Open

Red Open Red Open


Blue Yellow Open Yellow Open
Blue Earthed Blue Earthed

Remarks

Tested by:N.Sivakumar Witnessed by: Witnessed by: Witnessed by:


Sign Sign Sign Sign

Date Date Date Date


POWER LINKS QATAR Gulf Chlorine EPE KAHRAMAA
Project Title
GC-32-PLQ-S40-1

DC VOLTAGE TEST ON OUTER SHEATH


Location Gulf Chlorine W.L.L., - MV Switchgear Room
Cable Route 132/33/11 kV MIB Substation to Gulf Chlorine Substation Date: 13/5/2018

Cable Type 33 kV 1C x 300mm2 CU/XLPE/Pb/HDPE Temperature 32 ºC


Feeder No E50 Length (Red) 2416 m
Equipment 0-12KV HVDC Test Kit ,Make: BICOTEST, Length (Yellow) 2416 m
Model No: AXXIS S271T, S.No :39152 Length (Blue) 2416 m
Calibration 15-3-2019

Requirement: No insulation breakdown within 1 minute at test voltage

Red Yellow Blue

Duration 1 min 1 min 1 min

Voltage 12 kV 12 kV 12 kV
Measured
< 0.1 mA < 0.1 mA < 0.1 mA
Current
IR Before HV 271 MΩ 1.71 GΩ 2.90 GΩ

IR After HV 169 MΩ 1.21 GΩ 2.36 GΩ

Result OK OK OK

Remarks

Tested by:N.Sivakumar Witnessed by: Witnessed by: Witnessed by:


Sign Sign Sign Sign

Date Date Date Date

POWER LINKS QATAR Gulf Chlorine EPE KAHRAMAA


Project Title
GC-32-PLQ-S40-1
INSULATION RESISTANCE MEASUREMENT
Location Gulf Chlorine W.L.L., - MV Switchgear Room
Cable Route 132/33/11 kV MIB Substation to Gulf Chlorine Substation Date: 24.01.2018
Cable Type 33 kV 1C x 300mm2 CU/XLPE/Pb/HDPE Temperature 28 ºC
Feeder No E50 Length (Red) 2416 m
Equipment Model: MIT 520, S.No: EN/060406/1124 Length (Yellow) 2416 m
Calibration Validity:07.07.2018 Length (Blue) 2416 m

Requirement: Within parameters

Phase Insulation Resistance 5kV @ 1min

Red 204.0 GΩ

Yellow 234.0 GΩ

Blue 213.0 GΩ

Remarks

Tested by:N.Sivakumar Witnessed by: Witnessed by: Witnessed by:


Sign Sign Sign Sign

Date Date Date Date

POWER LINKS QATAR Gulf Chlorine EPE KAHRAMAA


Project Title
GC-32-PLQ-S40-1

CAPACITANCE MEASUREMENT

Location Gulf Chlorine W.L.L., - MV Switchgear Room


Cable Route 132/33/11 kV MIB Substation to Gulf Chlorine Substation Date: 24.01.2018
Cable Type 33 kV 1C x 300mm2 CU/XLPE/Pb/HDPE Temperature 28 ºC
Feeder No E50 Length (Red) 2416 m
Equipment Model: MIT 520, S.No: EN/060406/1124 Length (Yellow) 2416 m
Calibration Validity:07.07.2018 Length (Blue) 2416 m

Requirement: Similar to but not greater than manufacturer's quoted values

Phase Measured Capacitance Calculated Capacitance

Red 615.00 nF 0.255 µF/kM

Yellow 617.00 nF 0.255 µF/kM

Blue 615.00 nF 0.255 µF/kM

Remarks Theoritical Capacitance value= 0.213 µF/km

Tested by:N.Sivakumar Witnessed by: Witnessed by: Witnessed by:


Sign Sign Sign Sign

Date Date Date Date

POWER LINKS QATAR Gulf Chlorine EPE KAHRAMAA


#REF!

Positive and Negative Sequence Impedance

Cable Route Gasal S/S To RL2 KM S/S Date: 14-10-2010


Cable Type 33kV 1CX400mm2 /XLPE/LEAD/PVC Temperature #REF! ºC
Feeder No 1 Length (Red) 4350 M
Equipment Power Multimeter PMM1 S.N0:200905050024 Length (Yellow) 4350 M
Calibration 19-Sep-11 Length (Blue) 4350 M
Cable Temp Est #REF! ºC
Requirement: Comparable with manufacturer's quoted values

Red Yellow Blue RY


Voltage (V) 121.42 121.37 121.51 ###
Current (A) 100.52 102.23 100.16 ###
Phase 65.55 65.37 66.16 ###
Angle º
S (VA) 12205.14 12407.66 12170.44 r
P (W) 5048.94 5168.02 4924.92 ###
Q (VAR) 11111.94 11280.14 11129.45 ###
F (Hz) 50 50 50 ###
Calculated Values at Test Temperature
Z'1 (μΩ/m) R
R'1 (μΩ/m) i
X'1 (μΩ/m) R
Temperature and Frequency Compensated Values j
Z1 (μΩ/m) #REF! #REF! #REF! X
R1 (μΩ/m) #REF! #REF! #REF! Z
X1 (μΩ/m) 0 0 0 ###
###
Result

Theoretical Values: μΩ/M

Tested by: Witnessed by: Witnessed by: Witnessed by:

#REF! CEGELEC GASAL COMPANY #REF!


Project Title
GC-32-PLQ-S40-1

CONDUCTOR RESISTANCE / CIRCUIT PHASING CHECK


Location Gulf Chlorine W.L.L., - MV Switchgear Room
Cable Route 132/33/11 kV MIB Substation to Gulf Chlorine Substation Date: 24.01.2018
Cable Type 33 kV 1C x 300mm2 CU/XLPE/Pb/HDPE Temperature 28 ºC
Feeder No E50 Length (Red) 2416 m

Equipment Digital Low Resistance Ohm Meter Length (Yellow) 2416 m

Make: Megger, Model:DLRO1, Length (Blue) 2416 m

S.No:6978
Calibration 24-03-2018

Requirement: Comparable with manufacturer's quoted value

Red + Yellow Yellow + Blue Blue + Red

Measured
Resistance 300.6 302.2 303.2
mW
Far-End
Resistance 1.746 2.938 4.365

Rdc20 (Calculated)
Measured
149.214 149.641 149.622
Value in mΩ
Calculated
Value at 20ºC 59.8780 60.0493 60.0417
µΩ/m

Design Value 60 µΩ/m


Design Value = Declared mΩ/mtr X Circuit Length = 60 X 2416 144960 mΩ

Tested by:N.Sivakumar Witnessed by: Witnessed by: Witnessed by:


Sign Sign Sign Sign

Date Date Date Date


POWER LINKS QATAR Gulf Chlorine EPE KAHRAMAA
Project Title
GC-32-PLQ-S40-1
HIGH VOLTAGE FIELD ACCEPTANCE TEST (VLF)

Location: Gulf Chlorine W.L.L., - MV Switchgear Room


132/33/11 kV MIB Substation to Gulf Chlorine Date: 24.01.2018
Cable Route: Substation
Cable Type: 33 kV 1C x 300mm2 CU/XLPE/Pb/HDPE Temperature: 28 °C
Feeder/Cable No: E50 Humidity (% ) : 44%
Phase tested: R Y B Cable Length
Test Equipment: Megger & VLF HV Test System Length (Red) 2416 m
Model: MIT 520 & HV VLF 65 Length (Yellow) 2416 m
S.No: EN/060406/1124 & 156,233 Length (Blue) 2416 m
Calibration certificate validity: 7.7.18 & 7.4.2018

Phase R Y B
Time 60 Mins 60 Mins 60 Mins

Voltage 38kV 38kV 38kV

Frequency (Hz) 0.1Hz 0.1Hz 0.1Hz

Capacitance (nF) 620.0 nF 615 nF 618 nF

Testing Current (mA) 12 mA 13 mA 14 mA

IR Value Before HV 114.0 GΩ 121.0 GΩ 186.0 GΩ

IR Value After HV 98.4 GΩ 116.0 GΩ 141.0 GΩ

REQUIREMENT: Withstand 38 kV @ 60 Mins

REMARKS:

Tested by:N.Sivakumar Witnessed by: Witnessed by: Witnessed by:


Sign Sign Sign Sign

Date Date Date Date


POWER LINKS QATAR
Project Title
GC-32-PLQ-S40-1
Positive/Negative Sequence Impedance Measurement
Location: Gulf Chlorine W.L.L., - MV Switchgear Room
132/33/11 kV MIB Substation to Gulf Chlorine Date: 24.01.2018
Cable Route: Substation

Cable Type: 33 kV 1C x 300mm2 CU/XLPE/Pb/HDPE Temperature 20 ºC

Feeder No: E50


Test Equipment: PQ Clamp Meter Cable Length
Make : Fluke Model 345 - Red Phase: 2416 m
S NO 36580012 - Yellow Phase: 2416 m
Calibration certificate validity: 9/Sep/18 - Blue Phase: 2416 m

Test results Unit RED YELLOW BLUE


Cable Length m 2416 2416 2416
Voltage V 36.38 36.38 36.10
Current A 98.80 94.80 92.60
Power factor Cos θ 0.697 0.658 0.691
Active power W 2269.00 2281.00 2313.00
Reactive power VAr 2594 2609 2413
Frequency Hz 51.8 51,7 51.7

Conductor Temperature θ (°C) 20 25 30 35 40 45 50 90


Temperature Coefficient Kθ 1.237 1.217 1.197 1.178 1.159 1.141 1.123 1

Measured value
Voltage Current U
Z0 = R0 = Zo Cosθ X0 = Z0 Sinθ
U I Cos θ IXL

(V) (A) (Ω /m) (Ω /m) (Ω /m)


Red 36.38 98.80 0.697 0.000152 0.0001062 0.00010929
Yellow 36.38 94.80 0.658 0.000159 0.0001045 0.00011961

Blue 36.10 92.60 0.691 0.000161 0.0001115 0.00011664


Average 36.29 95.40 0.682 0.000158 1.07E-04 1.15E-04
Calculated Values at 90˚C 1.31E-04 1.40E-04 191.7 µΩ/m
* Acceptance Criteria 150 Ω /m

Requirement: ≤

REMARKS:

Tested by:N.Sivakumar Witnessed by: Witnessed by: Witnessed by:


Sign Sign Sign Sign

Date Date Date Date

POWER LINKS QATAR Gulf Chlorine EPE KAHRAMAA


Project Title

ZERO SEQUENCE IMPEDANCE MEASUREMENT


Location: Gulf Chlorine W.L.L., - MV Switchgear Room
132/33/11 kV MIB Substation to Gulf Chlorine Date: 24.01.2018
Cable Route: Substation

Cable Type: 33 kV 1C x 300mm2 CU/XLPE/Pb/HDPE Temperature 28 ºC

Feeder No: E50


Test Equipment: PQ Clamp Meter Cable Length
Make : Fluke Model 345 - Red Phase: 2416 m
S NO 36580012 - Yellow Phase: 2416 m
Calibration certificate validity: 9/Sep/18 - Blue Phase: 2416 m

Test results Unit RED YELLOW BLUE


Cable Length m 2416 2416 2416
Average Cable Length m 2416
Voltage V 18.62
Current A 95.90
Power factor Cos θ 0.908
Active power W 1622.00
Reactive power VAr 747.00
Frequency Hz 51.40
Conductor Temperature θ (°C) 20 25 30 35 40 45 50 90
Temperature Coefficient Kθ 1.237 1.217 1.197 1.178 1.159 1.141 1.123 1
Measured value
Voltage Current 3U
Z0 = R0 = Z0 cosθ X0 = Z0 sinθ
U I Cos θ IXL

(V) (A) (Ω /m) (Ω /m) (Ω /m)

Red 18.62 95.90 0.908 0.00024109 2.19E-04 1.01E-04

Calculated Values at 90˚C 2.66E-04 1.23E-04


* Acceptance Criteria Normal Value = 80 + j12.1 Ω/m
Requirement: ≤

REMARKS:
Tested by:N.Sivakumar Witnessed by: Witnessed by: Witnessed by:
Sign Sign Sign Sign

Date Date Date Date

POWER LINKS QATAR Gulf Chlorine EPE KAHRAMAA


Weight

mm2 Aluminium
Conductor #REF! #REF! kg/km

Diameter under #REF! mm


Inner semi conductor Tjocklek #REF! mm
Densitet 1.13 kg/dm3

Diameter under #REF! mm


Insulation Tjocklek #REF! mm
Densitet 0.92 kg/dm3

Diameter under #REF! mm


Outer semi conductor Tjocklek #REF! mm
Densitet 1.13 kg/dm3

Diameter under #REF! mm


Längdfaktor 1
Bedding Bandbredd #REF! mm
Bandtjocklek #REF! mm Vikt
Bandvikt 130 g/m2

Diameter under #VALUE! mm Vikt


Area #REF! mm2 Antal trådar
Metallic screen (wire) Tråddiameter #REF! mm Area
Stigningsfaktor 12 ggr
Densitet #REF! kg/dm3 Trådlucka

Diameter under #VALUE! mm


Längdfaktor 1
Antal lager 2
Metallic screen (tape) Bandbredd #REF! mm
Bandtjocklek #REF! mm
Lucka #REF! mm
Densitet #REF! kg/dm3 Vikt

Diameter under #REF! mm

Sida 10
Weight

Längdfaktor 1
Metallic laminate Bandbredd #REF! mm
Bandtjocklek #REF! mm Vikt
Bandvikt #REF! g/m2

Diameter under #REF! mm


Leadsheath Tjocklek #REF! mm
Densitet 11.34 kg/dm3

Diameter under #REF! mm


Bedding / inner sheath Tjocklek #REF! mm
Densitet 1 kg/dm3

Diameter under #REF! mm


Antal trådar #REF!
Armour (wire) Tråddiameter #REF! mm Vikt
Stigning #REF! ggr
Densitet #REF! kg/dm3

Diameter under #REF! mm


Längdfaktor 1
Antal lager 2
Armour (tape) Bandbredd #REF! mm Vikt
Bandtjocklek #REF! mm
Lucka #REF! mm
Densitet #REF! kg/dm3

Diameter under #REF! mm


Outer sheath ( PE & PVC ) Tjocklek #REF! mm
Densitet #REF! kg/dm3

Asphalt compound Layer 1 Diameter under #REF!

Asphalt compound Layer 2 Diameter under #REF!

Polypropylene yarns Diameter under #REF!


Tjocklek #REF!

Total cable weight

Sida 11
Weight

Copper
#REF! kg/km #REF! kg/km

#REF! kg/km

#REF! kg/km

#REF! kg/km

#REF! kg/km

#REF! kg/km
#REF!
#REF! #REF! kg/km

#VALUE!

#REF! kg/km #REF! kg/km

Sida 12
Weight

#REF! kg/km #REF! kg/km

#REF! kg/km #REF! kg/km

#REF! kg/km #REF! kg/km

#REF! kg/km #REF! kg/km

#REF! kg/km #REF! kg/km

#REF! kg/km #REF! kg/km

#REF! kg/km #REF! kg/km

#REF! kg/km #REF! kg/km

#REF! kg/km #REF! kg/km

#REF! kg/m

Sida 13

Potrebbero piacerti anche