PH-11_66/11KV AL MARKHIYA S/S Metrosil details

Thermal Energy Withstand Thermal Energy Limiting Over Max. Set


Protection Metrosil Model Isc Kr Vk Thermal Rating
Required Absorption Voltage Voltage

REF KA Ip Is V W=4/ ((Isc,max,int)/Kr)Ek J=Pvar x tsc J V V


1000*(4/(22/7))*(31.5/2500/1)*551.03 8837*0.5= 4418.5
11KV Busbar 600-A/S1/256 31.5 2500 1 551.03 53333 1435 185
= 8837 8837*1= 8837

Energy calculation for Metrosil.

Thermal rating of merosil:

Energy dissipated: