Sei sulla pagina 1di 28

Medium Voltage Distribution

Application Catalogue
A tool for all MV equipment designers

May 2008
Application Catalogue Contents
A tool for all MV equipment
designers

Presentation
General 4

User guide 5

Selection tables 6

Application
Substation feeder 10

Substation incomer 12

Bus tie 14

Bus riser 16

Busbar VT’s 17

Transformer feeder 18

Transformer incomer 22

Motor feeder 24

Generator incomer 26

DEAI06EN.indd 3
Presentation General

The Medium Voltage Application Catalogue is a tool for all Medium Voltage
equipment designers.

Purpose
b To help you produce Medium Voltage switchgear assemblies which include
Schneider Electric components
b To help you specify s tandard solutions.

How?
By offering you standard applications for the protection of different Medium
Voltage network configurations.
By providing you with a guarantee of the full protection chain composed
of different Schneider Electric components.

b With specification of the equipment required for each standard application


b  And the complete wiring diagram of the Medium Voltage equipment
for each application.

4 DEAI06EN.indd
Presentation User guide

Step 1: Selection table


Using the selection table, you select your application from the different
standard applications offered:

b Based on the network component to be protected:


substation incomer or feeder, transformer, motor or generator 
b Based on the formulated protection, metering and monitoring

requirements
The application chosen from the selection table is detailed in the application
pages.

Step 2: Application page


Each standard application is presented in a page which includes:

b  A single-line diagram of the application, with the different components


to be combined:
v Switching device

v Measurement sensors

v Protection unit

v Details of the functions offered by the protection unit:

v Protection functions

v Monitoring and control functions

b Optional functions available

b Reference of the complete wiring diagram for the application.

Step 3: Wiring diagrams


 A diagram library on CD-ROM contains the wiring diagrams,
in AutoCad format, of all the standard applications offered.

Each diagram:
b Corresponds to a standard application

b Contains all the information required for the complete wiring, power 

and control current, of the Medium Voltage equipment


b May be easily adapted by you to match the options you choose

and your particular needs.

DEAI06EN.indd 5
Presentation Selection tables

Application Line or substation


Feeder Incomer  
Protection and control type S1 S2 S2 S2 S3 S3 S3 S4
Page No. 10 11 11 11 12 12 12 13
Sepam series 20 S20 S20
Sepam series 40 S40 S41 S42 S40 S41 S42
NEX 17.5 kV diagram 5130… 7350 7356 7358 7360 7357 7359 7361
NEX 24 kV diagram 5130… 7373 7378 7379 7374
Protection function ANSI code
Phase overcurrent 50/51 b b b b b b b b

Voltage-restrained phase overcurrent 50V/51V


Earth fault, 50N/51N
b b b b b b b b
sensitive earth fault 50G/51G
Breaker failure 50BF b b b b b b

Negative sequence/unbalance 46 b b b b b b b b

Directional phase overcurrent 67 b (1) b

Directional earth fault 67N/67NC b b b b

Directional active overpower 32P b (1) b (1) b b

Directional reactive overpower 32Q/40


Thermal overload 49RMS
Phase undercurrent 37
Excessive starting time, locked rotor 48/51LR/14
Starts per hour 66
Positive sequence undervoltage 27D
Remanent undervoltage 27R
Undervoltage 27/27S b b b b b b

Overvoltage 59 b b b b b b

Neutral voltage displacement 59N b (1) b (1) b (1) b b b

Negative sequence overvoltage 47 b (1) b (1) b (1) b b b

Overfrequency 81H b (1) b (1) b (1) b b b

Underfrequency 81L b (1) b (1) b (1) b b b

Rate of change of frequency 81R


Recloser (4 cycles) 79 v v v v v

Temperature monitoring (8 to 16 RTDs, 2 set points per RTD) 38/49T


Thermostat/Buchholz/DGPT
Measurement and diagnostic
Phase current I1; I2; I3 RMS, residual current I0 b b b b b b b b

 Average current I1; I2; I3; peak demand current IM1, IM2, IM3 b b b b b b b b

Voltage U21; U32; U13; V1; V2; V3; residual voltage V0 b b b b b b

Positive sequence voltage Vd/rotation direction; neg. seq. voltage Vi (only S40) b b b b b b

Frequency b b b b b b

 Active; reactive and apparent power P. Q. S


Peak demand power PM. QM b b b b b b
Power factor 
Calculated active and reactive energy ( +/-W.h. +/- var.h) b b b b b b

 Active and reactive energy by pulse counting ( +/-W.h. +/- var.h) v (1) v (1) v (1) v (1) v (1) v (1)

Temperature
Network and machine diagnosis
Tripping context b b b b b b

Tripping current Trip1; Trip2; Trip3; Trip0 b b b b b b b b

Unbalance ratio/negative sequence current Ii b b b b b b b b

Phase displacement ϕ0; ϕ1; ϕ2; ϕ3 b b b b b b

Disturbance recording b b b b b b b b

Thermal capacity used


Remaining operating time before overload tripping
Waiting time after overload tripping
Running hours counter/operating time
Start current and time
Start inhibit time delay, number of starts before inhibition

b  Standard
v  According to parameter setting and MES module or MET module
(1) Not used in schematic diagram

6 DEAI06EN.indd
Bus tie Bus riser Busbar VT’s Transformer Motor Generator  
Feeder Incomer Feeder Incomer  
S5 S6 B2 B1 B1 T1 T2 T3 T3 T6 T4 T4 T5 T5 M1 M2 G1
14 15 16 17 17 18 19 20 20 21 22 22 23 23 24 25 26
S20 B22 B21 B22 T20 T20 M20
S40 T40 T42 T40 T40 T42 T40 T42 M41 G40
7354 7355 7351 7352 7362 7365 7363 7366 7364 7367 7353 7368 7369
7372 7377 7371 7370 7375 7376 7380 7382 7381 7383

b b b b b b b b b b b b b b

b b b b b b b b b b b b b b

b b b b b b b b b b b

b b b b b b b b b b b b

b (1) b b

b b b b

b b

b b

b b b b b b b b b b b b

b b

b b

b b

b b b b

b b b b

b b b b b b b b b b b b b

b b b b b b b b b b b b b

b (1) b b b b (1) b (1) b (1) b (1) b (1) b (1) b (1) b b

b (1) b (1) b b (1) b (1) b (1) b (1) b (1) b (1) b (1) b (1) b b

b (1) b b b b (1) b (1) b (1) b (1) b (1) b (1) b (1) b (1) b

b (1) b b b b (1) b (1) b (1) b (1) b (1) b (1) b (1) b (1) b

v v v v v v v

v v v v v

b b b b b b b b b b b b b b

b b b b b b b b b b b b b b

b b b b b b b b b b b b b

b b b b b b b b b b b b b

b b b b b b b b b b b b b

b b b b b b b b b b

b b b b b b b b b b

v (1) v (1) v (1) v (1) v (1) v (1) v (1) v (1) v (1) v (1)

v v v (1) v (1) v (1) v (1) v (1) v (1) v v v v

b b b b b b b b b b

b b b b b b b b b b b b b b

b b b b b b b b b b b b b b

b b b b b b b b b b

b b b b b b b b b b b b b b b b b

b b b b b b b b b b b b

b b b b b b b b b b b b

b b b b b b b b b b b b

b b b b b b b b b b b b

b b

b b

DEAI06EN.indd 7
Presentation Selection tables (cont.)

Application Line or substation


Feeder Incomer  
Protection and control type S1 S2 S2 S2 S3 S3 S3 S4
Page No. 10 11 11 11 12 12 12 13
Sepam series 20 S20 S20
Sepam series 40 S40 S41 S42 S40 S41 S42
NEX 17.5 kV diagram 5130… 7350 7356 7358 7360 7357 7359 7361
NEX 24 kV diagram 5130… 7373 7378 7379 7374
Switchgear diagnostic ANSI code
Cumulative breaking current b b b b b b b b

Trip circuit supervision v v v v v v v v

Number of operations, operating time, charging time v v v v v v v v

CT/VT supervision 60FL b b b b b b

Control and monitoring


Circuit breaker/contactor control 94/69 v v v v v v v v

Latching/acknowledgment 86 b b b b b b b b

Logic discrimination 68 v v v v v v v v

Switching of groups of settings b (1) b (1) b (1) b (1) b (1) b (1) b (1) b (1)

Logic equation editor  b b b b b b

Optional features
8 temperature sensor inputs - MET148-2 module v v v v v v v v

1 low level analog output - MSA141 module v v v v v v v v

Logic inputs/outputs - MES114 (10I/4O) module v v v v v v v v

RS485 interface - ACE949-2 (2-wire) or ACE959 (4-wire) module b b b b b b b b

Test bo x b b b b b b b b

Local remote/switch b b b b b b b b

CT’s option
LPCT sensors b b b b b b b b

Core balance CT v v v v v v v v

b  Standard
v  According to parameter setting and MES module or MET module
(1) Not used in schematic diagram

8 DEAI06EN.indd
Bus tie Bus riser Busbar VT’s Transformer Motor Generator  
Feeder Incomer Feeder Incomer  
S5 S6 B2 B1 B1 T1 T2 T3 T3 T6 T4 T4 T5 T5 M1 M2 G1
14 15 16 17 17 18 19 20 20 21 22 22 23 23 24 25 26
S20 B22 B21 B22 T20 T20 M20
S40 T40 T42 T40 T40 T42 T40 T42 M41 G40
7354 7355 7351 7352 7362 7365 7363 7366 7364 7367 7353 7368 7369
7372 7377 7371 7370 7375 7376 7380 7382 7381 7383

b b b b b b b b b b b b b b

v v v (1) v (1) v (1) v v v v v v v v v v v v

v v v v v v v v v v v v v v

b b b b b b b b b b

v v v (1) v (1) v (1) v v v v v v v v v v v v

b b b b b b b b b b b b b b b b b

v v v v v v v v v v v v v v

b (1) b (1) b (1) b (1) b (1) b (1) b (1) b (1) b (1) b (1) b (1) b (1) b (1) b (1)

b b b b b b b b b b

v v (1) v (1) v (1) v v (1) v (1) v v v v v

v v v v v v v v v v v v v v v v v

v v v v v v v v v v v v v v v v v

v v v v v v v v v v v v v v v v v

b b b b b b b b b b b b b b b b b

b b b b b b b b b b b b b b

b b b b b b b b b b b b b b

b b b b b b b b b b b b

DEAI06EN.indd 9
Application Substation feeder S1

b  Protection against phase to phase Protection


and phase to earth short circuits Sepam S20
b  Detecting of unbalanced power supplied  b 50/51: overcurrent - IDMT, DT (4 settings)

b 50N/51N: earth fault - IDMT, DT (4 settings)


b  Recloser 
b 46: negative sequence overcurrent.
b  It suited for integration into a supervisory 

system using Modbus serial interface.


Several standard options are available
to ensure maximum flexibility and cost 
effectiveness in meeting the requirements
Measurement and diagnostic
Sepam S20, LCD display LED (Light Emitting Diode)
of different systems. b Phase current: I1, I2, I3 RMS

b Residual current: I0

b  Average currents: I1, I2, I3

b Peak demand phase currents

   0
   8
b Tripping currents: I1, I2, I3, I0
   3
b Unbalance ratio/negative sequence current Ii
   6
   5
   E
   D
b Disturbance recording.

Trip/close(1) CT’s option


b CLP1: LPCT sensors 100 A to 1250 A

b Core balance CT: CSH120 or CSH200.


50/51  A 86
50N/51N MD 74
46 30
79(1)
68
Control
Sepam S20 Basic MES114 module
apparatus (10 I/4 O)
Cumulative breaking current b b

Trip CB output (O1) b b

Closing lockout (O2) b b


 Analog Output Logic discrimination block send (O3) b b

Watch dog (O4) b b


Remote UMI
CB control (86) b b

CB open/closed status indication b


Modbus RS485
Number of operations, operating time b
Substation feeder S1 Logic discrimination block receive b

External tripping b

Trip circuit supervision (74) b

Fault and alarm contact (O11(2) to O14) b

Recloser 4 cycles (79) b

(1) Close by communication and recloser  External network time synchronization b


(2) O11 reserved for closing order 
External trip b

Local/remote control selection b

Inhibition recloser  b

Optional features
b Communication interface module, 2 wires (ACE949-2) Modbus

b Communication interface module, 4 wires (ACE959) Modbus

b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module

b Remote advanced UMI (type DSM303)

b Test box

b Local/remote switch

b Logic inputs and outputs module MES114 (10I/4O).

10 DEAI06EN.indd
Application Substation feeder S2

b  Protection against phase to phase Measurement and diagnostic


and phase to earth short circuits Sepam S40/S41/S42, LCD display LED (Light Emitting Diode)
b  Detecting of unbalanced power supplied  b Phase current: I1, I2, I3 RMS

b Residual current: I0
b  Recloser 
b  Average currents: I1, I2, I3
b  It suited for integration into a supervisory 
b Peak demand phase currents
system using Modbus serial interface. b Line voltage: U21, U32, U13

Several standard options are available b Phase to neutral voltage: V1, V2, V3

b Residual voltage: V0
to ensure maximum flexibility and cost 
b Positive sequence voltage/rotation direction
effectiveness in meeting the requirements b Frequency
of different systems. b  Active, reactive and apparent power: P, Q, S

b Peak demand power PM, QM and power factor 

b  Active and reactive energy

b Tripping currents: I1, I2, I3, I0

b Unbalance ratio/negative sequence current Ii


   5
   8
   3
   6
   5
To Busbar VT’s b Phase displacement
   E
   D
b Disturbance recording

b Tripping context.
50/51 A 94
CT’s option
50N/51N V 69
b CLP1: LPCT sensors 100 A to 1250 A
50BF F 86
Open/close b Core balance CT: CSH120 or CSH200.
46 MD 74
trip
KW 30
67N/67NC(1) KVAR 68
KVA 60LF
27/27S PF 79
59 KW.h
Control
KVar.h Sepam S40/S41/S42 Basic MES114 module
apparatus (10 I/4 O)
Cumulative breaking current b b

Trip CB output (O1) b b

Closing lockout (O2) b b

Logic discrimination block send (O3) b b

 Analog Output Watch dog (O4) b b

CB control (86) b b
Remote UMI CB open/closed status indication b

Modbus RS485 Number of operations, operating time b

Trip circuit supervision (74) b

Substation feeder S2  Logic discrimination block receive Bl1 b

CB closing order  b

Fault and alarm contact (O11(2) to O14) b

Recloser 4 cycles (79) b

Protection CB opening order  b

Sepam S40/S41/S42 Inhibit closing b

b 50/51: overcurrent - IDMT, DT (4 s ettings) External tripping b

b 50N/51N: earth fault - IDMT, DT (4 settings) Local/remote control selection b


b 50BF: breaker failure
Inhibition recloser  b
b 46: negative sequence overcurrent - IDMT,

DT (2 settings) External network time synchronization b

b 67N/67NC: directional earth fault (1) - IDMT,

DT (2 settings) Optional features


b 27/27S: undervoltage (2 settings) b Communication interface module, 2 wires (ACE949-2) Modbus

b 59: overvoltage (2 settings). b Communication interface module, 4 wires (ACE959) Modbus

b Logic inputs and outputs module MES114 (10I/4O)

b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module

b Remote advanced UMI (type DSM303)

(1) On Sepam S41 and S42  b Test box

(2) O11 reserved for closing order  b Local/remote switch.

DEAI06EN.indd 11
Application Substation incomer S3

b  Protection against phase to phase Measurement and diagnostic


and phase to earth short circuits Sepam S40/S41/S42, LCD display LED (Light Emitting Diode)
b  Detecting of unbalanced power supplied  b Phase current: I1, I2, I3 RMS

b Residual current: I0
b  It suited for integration into a supervisory 
b  Average currents: I1, I2, I3
system using Modbus serial interface. b Peak demand phase currents
Several standard options are available b Line voltage: U21, U32, U13

to ensure maximum flexibility and cost  b Phase to neutral voltage : V1, V2, V3

b Residual voltage: V0
effectiveness in meeting the requirements
b Positive sequence voltage/rotation direction
of different systems. b Frequency

b  Active, reactive and apparent power: P, Q, S

b Peak demand power PM, QM and power factor 

b  Active and reactive energy

b Tripping currents: I1, I2, I3, I0

b Unbalance ratio/negative sequence current Ii


   6
   8
   3
   6
   5
Modbus RS485 b Phase displacement
   E
   D
b Disturbance recording

Remote UMI b Tripping context.

 Analog Output CT’s option


b CLP1: LPCT sensors 100 A to 1250 A

b Core balance CT: CSH120 or CSH200.

50/51 A 94
50N/51N V 69
50BF F 86
46 MD 74
Control
67(1) KW 30
67N/67NC(2) KVAR 68 Sepam S40/S41/S42 Basic MES114 module
32P KVA 60LF apparatus (10 I/4 O)
27/27S PF Cumulative breaking current b b
59 KW.h Trip CB output (O1) b b
59N KVar.h
Closing lockout (O2) b b
47
Open/close 81H Logic discrimination block send (O3) b b

trip 81L Watch dog (O4) b b

CB control (86) b b

CB open/closed status indication b

Number of operations, operating time b


Substation incomer S3
Trip circuit supervision (74) b

Logic discrimination block receive Bl1 b

CB closing order  b

Protection Fault and alarm contact (O11(3) to O14) b

Sepam S40/S41/S42 CB opening order  b

b 50/51: overcurrent - IDMT, DT (4 settings) Inhibit closing b


b 50N/51N: earth fault - IDMT, DT (4 settings)
External tripping b
b 50BF: breaker failure
Local/remote control selection b
b 46: negative sequence overcurrent - IDMT,

DT (2 settings) External network time synchronization b

b 67: directional phase overcurrent (1) - IDMT,

DT (2 settings) Optional features


b 67N/67NC: directional earth fault (2) - IDMT, b Communication interface module, 2 wires (ACE949-2) Modbus

DT (2 settings) b Communication interface module, 4 wires (ACE959) Modbus

b 32P: directional active overpower (2) b Logic inputs and outputs module MES114 (10I/4O)

b 27/27S: undervoltage (2 settings) b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module

b 59: overvoltage (2 settings) b Remote advanced UMI (type DSM303)

b 59N: neutral voltage displacement (2 settings) b Test box

b 47: negative sequence overvoltage b Local/remote switch.

b 81H: overfrequency (2 settings)

b 81L: underfrequency (4 settings).

(1) On Sepam S42 only 


(2) On Sepam S41 and S42 
(3) O11 reserved for closing order 

12 DEAI06EN.indd
Application Substation incomer S4

b  Protection against phase to phase Protection


and phase to earth short circuits Sepam S20
b  Detecting of unbalanced power supplied  b 50/51: overcurrent - IDMT, DT (4 s ettings)

b 50N/51N: earth fault - IDMT, DT (4 settings)


b  It suited for integration into a supervisory 
b 46: negative sequence overcurrent.
system using Modbus serial interface.
Several standard options are available
to ensure maximum flexibility and cost 
effectiveness in meeting the requirements
of different systems.
Measurement and diagnostic
Sepam S20, LCD display LED (Light Emitting Diode)
b Phase current: I1, I2, I3 RMS

b Residual current: I0

b  Average currents: I1, I2, I3

b Peak demand phase currents

   1 b Tripping currents: I1, I2, I3, I0


   8
   3
   6
   5
Modbus RS485 b Unbalance ratio/negative sequence current Ii
   E
   D
b Disturbance recording.
Remote UMI CT’s option
 Analog Output b CLP1: LPCT sensors 100 A to 1250 A

b Core balance CT: CSH120 or CSH200.

50/51 A
50N/51N
86
MD 74 Control
30 Sepam S20 Basic MES114 module
68 apparatus (10 I/4 O)
Cumulative breaking current b b

Trip CB output (O1) b b

Closing lockout (O2) b b

Logic discrimination block send (O3) b b

Open/close Watch dog (O4) b b


trip
CB control (86) b b

CB open/closed status indication b

Number of operations, operating time b

Substation incomer S4 Logic discrimination block receive b

External tripping b

Trip circuit supervision (74) b

Fault and alarm contact (O11(2) to O14) b

(1) Close by communication and recloser  External network time synchronization b


(2) O11 reserved for closing order  External trip b

Local/remote control selection b

Inhibition recloser  b

Optional features
b Communication interface module, 2 wires (ACE949-2) Modbus

b Communication interface module, 4 wires (ACE959) Modbus

b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module

b Remote advanced UMI (type DSM303)

b Test box

b Local/remote switch

b Logic inputs and outputs module MES114 (10I/4O).

DEAI06EN.indd 13
Application Bus tie S5

b  Protection against phase to phase Protection


and phase to earth short circuits Sepam S20
b  Detecting of unbalanced power supplied  b 50/51: overcurrent - IDMT, DT (4 settings)

b 50N/51N: earth fault - IDMT, DT (4 settings)


b  It suited for integration into a supervisory 
b 46: negative sequence overcurrent.
system using Modbus serial interface.
Several standard options are available
to ensure maximum flexibility and cost 
effectiveness in meeting the requirements
of different systems.
Measurement and diagnostic
Sepam S20, LCD display LED (Light Emitting Diode)
b Phase current: I1, I2, I3 RMS

b Residual current: I0

b  Average currents: I1, I2, I3

b Peak demand phase currents

   2
   8
b Tripping currents: I1, I2, I3, I0
   3
b Unbalance ratio/negative sequence current Ii
   6
   5
   E
   D
b Disturbance recording.

Trip/close(1) CT’s option


b CLP1: LPCT sensors 100 A to 1250 A

b Core balance CT: CSH120 or CSH200.


50/51 A 86
50N/51N MD 74
30

68 Control
Sepam S20 Basic MES114 module
apparatus (10 I/4 O)
Cumulative breaking current b b

Trip CB output (O1) b b

Closing lockout (O2) b b


Analog Output Logic discrimination block send (O3) b b

Watch dog (O4) b b


Remote UMI
CB control (86) b b

CB open/closed status indication b


Modbus RS485
Number of operations, operating time b
Bus tie S5  Logic discrimination block receive b

External tripping b

Trip circuit supervision (74) b

Fault and alarm contact (O11(2) to O14) b

(1) Close by communication and recloser  External network time synchronization b

(2) O11 reserved for closing order  External trip b

Local/remote control selection b

Inhibition recloser  b

Optional features
b Communication interface module, 2 wires (ACE949-2) Modbus

b Communication interface module, 4 wires (ACE959) Modbus

b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module

b Remote advanced UMI (type DSM303)

b Test box

b Local/remote switch

b Logic inputs and outputs module MES114 (10I/4O).

14 DEAI06EN.indd
Application Bus tie S6

b  Protection against phase to phase Protection


and phase to earth short circuits Sepam S40
b  Detecting of unbalanced power supplied  b 50/51: overcurrent - IDMT, DT (4 s ettings)

b 50N/51N: earth fault - IDMT, DT (4 settings)


b  Recloser 
b 50BF: breaker failure
b  It suited for integration into a supervisory 
b 46: negative sequence overcurrent - IDMT, DT (2 settings).
system using Modbus serial interface.
Several standard options are available
to ensure maximum flexibility and cost 
effectiveness in meeting the requirements Measurement and diagnostic
of different systems. Sepam S40, LCD display LED (Light Emitting Diode)
b Phase current: I1, I2, I3 RMS

b Residual current: I0

b  Average currents: I1, I2, I3

   3 b Peak demand phase currents


   8
   3
   6
   5
To Busbar VT’s b Line voltage: U21, U32, U13
   E
   D
b Phase to neutral voltage: V1, V2, V3

b Residual voltage: V0
50/51 A 94
b Positive sequence voltage/rotation direction
50N/51N V 69
b Frequency
50BF F 86
Open/close b  Active, reactive and apparent power: P, Q, S
(1) 46 MD 74
trip b Peak demand power PM, QM and power factor 
KW 30
b  Active and reactive energy
KVAR 68
b Tripping currents: I1, I2, I3, I0
KVA 60LF
b Unbalance ratio/negative sequence current Ii
PF
b Phase displacement
KW.h
b Disturbance recording
KVar.h
b Tripping context.

CT’s option
b CLP1: LPCT sensors 100 A to 1250 A

b Core balance CT: CSH120 or CSH200.

 Analog Output

Remote UMI Control


Sepam S40 Basic MES114 module
Modbus RS485 apparatus (10 I/4 O)
Bus tie S6  Cumulative breaking current b b

Trip CB output (O1) b b

Closing lockout (O2) b b

Logic discrimination block send (O3) b b

Watch dog (O4) b b

CB control (86) b b

CB open/closed status indication b

Number of operations, operating time b

Trip circuit supervision (74) b

Logic discrimination block receive Bl1 b

CB closing order  b

Fault and alarm contact (O11(2) to O14) b

CB opening order  b

Inhibit closing b

(1) Close by communication External tripping b


(2) O11 reserved for closing order  Local/remote control selection b

Inhibition recloser  b

External network time synchronization b

Optional features
b Communication interface module, 2 wires (ACE949-2) Modbus

b Communication interface module, 4 wires (ACE959) Modbus

b Logic inputs and outputs module MES114 (10I/4O)

b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module

b Remote advanced UMI (type DSM303)

b Test box

b Local/remote switch.

DEAI06EN.indd 15
Application Bus riser B2

b  Detecting of variation in network voltage Protection


or frequency  Sepam B22
b  It suited for integration into a supervisory  b 27D/47: positive sequence undervoltage (2 sets)

b 27R: remanent undervoltage


system using Modbus serial interface.
b 27: phase to phase undervoltage (2 sets)
Several standard options are available b 27S: phase to neutral undervoltage
to ensure maximum flexibility and cost  b 59: phase to phase overvoltage (2 sets)

effectiveness in meeting the requirements b 59N: neutral voltage displacement (2 sets)

b 81H: overfrequency
of different systems.
b 81L: underfrequency (2 sets)

b 81R: rate of change of frequency (B22 only).

   4
   8
Measurement and diagnostic
   3
   6
   5
   E
Sepam B22, LCD display LED (Light Emitting Diode)
   D
b Line voltage: U21, U32, U13

b Phase to neutral voltage: V1, V2, V3

b Residual voltage: V0

b Positive sequence voltage/rotation direction


27D/47 V 86
b Frequency
27R F 30
b Disturbance recording.
27
27S
59
59N
81L
81H Control
81R (B22) Sepam B22 Basic MES114 module
apparatus (10 I/4 O)
 Analog Output Trip CB output (O1) b b

Closing lockout (O2) b b


Remote UMI
Logic discrimination block send (O3) b b

Watch dog (O4) b b


Modbus RS485
Fault and alarm contact (O11 to O14) b b

Bus riser B2  External network time synchronization b

Optional features
b Communication interface module, 2 wires (ACE949-2) Modbus

b Communication interface module, 4 wires (ACE959) Modbus

b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module

b Remote advanced UMI (type DSM303)

b Test box

b Logic inputs and outputs module MES114 (10I/4O).

16 DEAI06EN.indd
Application Busbar VT’s B1

b  Detecting of variation in network voltage Protection


or frequency  Sepam B21/B22
b  It suited for integration into a supervisory  b 27D/47: positive sequence undervoltage (2 sets)

b 27R: remanent undervoltage


system using Modbus serial interface.
b 27: phase to phase undervoltage (2 sets)
Several standard options are available b 27S: phase to neutral undervoltage
to ensure maximum flexibility and cost  b 59: phase to phase overvoltage (2 sets)

effectiveness in meeting the requirements b 59N: neutral voltage displacement (2 sets)

b 81H: overfrequency
of different systems.
b 81L: underfrequency (2 sets)

b 81R: rate of change of frequency (B22 only).

   7
   8
Measurement and diagnostic
   3
   6
   5
   E
Sepam B21/B22, LCD display LED (Light Emitting Diode)
   D
b Line voltage: U21, U32, U13

b Phase to neutral voltage: V1, V2, V3

b Residual voltage: V0

b Positive sequence voltage/rotation direction


27D/47 V 86
b Frequency
27R F 30
b Disturbance recording.
27
27S
59
59N
81L
81H Control
81R (B22) Sepam B21/B22 Basic MES114 module
apparatus (10 I/4 O)
 Analog Output Trip CB output (O1) b b

Closing lockout (O2) b b


Remote UMI
Logic discrimination block send (O3) b b

Watch dog (O4) b b


Modbus RS485
Fault and alarm contact (O11 to O14) b b

Busbar VT’s B1 External network time synchronization b

Optional features
b Communication interface module, 2 wires (ACE949-2) Modbus

b Communication interface module, 4 wires (ACE959) Modbus

b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module

b Remote advanced UMI (type DSM303)

b Test box

b Logic inputs and outputs module MES114 (10I/4O).

DEAI06EN.indd 17
Application Transformer feeder T1

b  Protection against internal faults and  Protection


overload protection Sepam T20
b  It also monitors the winding temperature b 50/51: overcurrent - IDMT, DT (4 settings)

b 50N/51N: earth fault - IDMT, DT (4 settings)


by probes providing local and remote
b 46: negative sequence overcurrent
indication of operation b 49RMS: thermal overload (2 settings)
b  It suited for integration into a supervisory  b 38/49T: temperature monitoring (2 settings/probe).

system using Modbus serial interface.


Several standard options are available
to ensure maximum flexibility and cost 
effectiveness in meeting the requirements Measurement and diagnostic
of different systems. Sepam T20, LCD display LED (Light Emitting Diode)
b Phase current: I1, I2, I3 RMS

b Residual current: I0

   8
   8
b  Average currents: I1, I2, I3
   3
b Peak demand phase currents
   6
   5
   E
   D
b Temperature measurement

b Tripping currents: I1, I2, I3, I0


Trip/close(1)
b Unbalance ratio/negative sequence current Ii

b Disturbance recording
50/51  A 86 b Running hours counter/operating time
50N/51N MD 74 b Thermal capacity used
49RMS Temp 30 b Remaining operating time before overload trip
38/49T 68 b Waiting time after overload tripping.

CT’s option
  p
   i b CLP1: LPCT sensors 100 A to 1250 A
  r
   t
  r b Core balance CT: CSH120 or CSH200.
  e
   t
  n
   I

Temp Sensor 
Control
Sepam T20 Basic MES114 module
 Analog Output apparatus (10 I/4 O)
Remote UMI Cumulative breaking current b b

Trip CB output (O1) b b

Modbus RS485 Closing lockout (O2) b b

Logic discrimination block send (O3) b b


Transformer feeder T1
Watch dog (O4) b b

CB control (86) b b

CB open/closed status indication b

Number of operations, operating time b

Logic discrimination block receive b

External tripping b

(1) Close by communication Trip circuit supervision (74) b


(2) O11 reserved for closing order  Fault and alarm contact (O11(2) to O14) b

Local/remote control selection b

Inhibition thermal overload b

Optional features
b Communication interface module, 2 wires (ACE949-2) Modbus

b Communication interface module, 4 wires (ACE959) Modbus

b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module

b 8 temperature sensor inputs (38/49T) MET148-2 module

b Logic inputs and outputs module MES114 (10I/4O)

b Remote advanced UMI (type DSM303)

b Test box

b Local/remote switch.

18 DEAI06EN.indd
Application Transformer feeder T2

b  Protection against internal faults and  Protection


overload protection Sepam T20
b  It also monitors the winding temperature b 50/51: overcurrent - IDMT, DT (4 s ettings)

b 50N/51N: earth fault - IDMT, DT (4 settings)


and Buchholz providing local and remote
b 46: negative sequence overcurrent
indication of operation b 49RMS: thermal overload (2 settings)
b  It suited for integration into a supervisory  b Thermostat/Buchholz.

system using Modbus serial interface.


Several standard options are available
to ensure maximum flexibility and cost 
effectiveness in meeting the requirements Measurement and diagnostic
of different systems. Sepam T20, LCD display LED (Light Emitting Diode)
b Phase current: I1, I2, I3 RMS

b Residual current: I0

   9
   8
b  Average currents: I1, I2, I3
   3
b Peak demand phase currents
   6
   5
   E
   D
b Tripping currents: I1, I2, I3, I0

b Unbalance ratio/negative sequence current Ii


Trip/close(1)
b Disturbance recording

b Running hours counter/operating time


50/51  A 86 b Thermal capacity used
50N/51N MD 74 b Remaining operating time before overload trip
49RMS 30 b Waiting time after overload tripping.
Thermos 68 CT’s option
Buchholz b CLP1: LPCT sensors 100 A to 1250 A

  p
   i b Core balance CT: CSH120 or CSH200.
  r
   t
  r
  e
   t
  n
   I

Control
Sepam T20 Basic MES114 module
apparatus (10 I/4 O)
 Analog Output Cumulative breaking current b b

Trip CB output (O1) b b

Remote UMI Closing lockout (O2) b b

Logic discrimination block send (O3) b b


Modbus RS485
Watch dog (O4) b b

Transformer feeder T2  CB control (86) b b

CB open/closed status indication b

Number of operations, operating time b

Logic discrimination block receive b

External tripping b

Trip circuit supervision (74) b

Fault and alarm contact (O11(2) to O14) b

External tripping (Buchholz) b

External tripping (Winding temperature) b

(1) Close by communication Buchholz alarm b


(2) O11 reserved for closing order  Winding temperature alarm b

Local/remote control selection b

Inhibition thermal overload b

Optional features
b Communication interface module, 2 wires (ACE949-2) Modbus

b Communication interface module, 4 wires (ACE959) Modbus

b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module

b Logic inputs and outputs module MES114 (10I/4O)

b Remote advanced UMI (type DSM303)

b Test box

b Local/remote switch.

DEAI06EN.indd 19
Application Transformer feeder T3

b  Protection against internal faults and  Measurement and diagnostic


overload protection Sepam T40 or T42, LCD display LED (Light Emitting Diode)
b  It also monitors pressure device providing  b Phase current: I1, I2, I3 RMS

b Residual current: I0
local and remote indication of operation
b  Average currents: I1, I2, I3
b  It suited for integration into a supervisory 
b Peak demand phase currents
system using Modbus serial interface. b Line voltage: U21, U32, U13

Several standard options are available b Phase to neutral voltage: V1, V2, V3

b Residual voltage: V0
to ensure maximum flexibility and cost 
b Positive sequence voltage/rotation direction
effectiveness in meeting the requirements b Frequency
of different systems. b  Active, reactive and apparent power: P, Q, S

b Peak demand power PM, QM and power factor 

b  Active and reactive energy

b Tripping currents: I1, I2, I3, I0

b Unbalance ratio/negative sequence current Ii


   0
   9
   3
   6
   5
To Busbar VT’s b Phase displacement
   E
   D
b Disturbance recording

b Running hours counter/Operating time


50/51 A 94 b Thermal capacity used
50N/51N V 69 b Remaining operating time before overload trip
50BF F 86 b Waiting time after overload tripping
Open/close
46 MD 74 b Tripping context.
trip
KW 30
CT’s option
67N/67NC(1) KVAR 68
b CLP1: LPCT sensors 100 A to 1250 A
49RMS KVA 60LF
b Core balance CT: CSH120 or CSH200.
27/27S PF
59 KW.h
KVar.h   p
   i
  r
DGPT2    t
  r
  e
   t
  n
Control
   I

Sepam T40 or T42 Basic MES114 module


apparatus (10 I/4 O)
Cumulative breaking current b b

Trip CB output (O1) b b

Closing lockout (O2) b b

 Analog Output Logic discrimination block send (O3) b b

Watch dog (O4) b b


Remote UMI CB control (86) b b

Modbus RS485 CB open/closed status indication b

Number of operations, operating time b


Transformer feeder T3
Trip circuit supervision (74) b

Logic discrimination block receive BI1 b

Protection CB closing order b

Sepam T40 or T42 Fault and alarm contact (O11(2) to O14) b

b 50/51: overcurrent - IDMT, DT (4 settings) CB opening order b

b 50N/51N: earth fault - IDMT, DT (4 settings) Pressure alarm b


b 50BF: breaker failure
Pressure tripping b
b 46: negative sequence overcurrent - IDMT,
Thermostat alarm b
DT (2 settings)
b 67: directional phase overcurrent (1) - IDMT,
Thermostat tripping b

DT (2 settings) External network time synchronization b

b 67N/67NC: directional earth fault (1) - IDMT,

DT (2 settings) Optional features


b 49RMS: thermal overload (2 settings) b Communication interface module, 2 wires (ACE949-2) Modbus
b 27/27S: undervoltage (2 settings) b Communication interface module, 4 wires (ACE959) Modbus
b 59: overvoltage (2 settings) b Logic inputs and outputs module MES114 (10I/4O)
b 59N: neutral voltage displacement (2 settings). b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module

b Remote advanced UMI (type DSM303)

b Test box

b Local/remote switch.
(1) On Sepam T42 only 
(2) O11 reserved for closing order 

20 DEAI06EN.indd
Application Transformer feeder T6

 Protection against internal faults and 


b  Measurement and diagnostic
overload protection Sepam T40, LCD display LED (Light Emitting Diode)
b  It also monitors the windings by probes b Phase current: I1, I2, I3 RMS

b Residual current: I0
 providing device local and remote indication
b  Average currents: I1, I2, I3
of operation b Peak demand phase currents
b  It suited for integration into a supervisory  b Line voltage: U21, U32, U13

system using Modbus serial interface. b Phase to neutral voltage: V1, V2, V3

b Residual voltage: V0
Several standard options are available
b Positive sequence voltage/rotation direction
to ensure maximum flexibility and cost  b Frequency
effectiveness in meeting the requirements b  Active, reactive and apparent power: P, Q, S

of different systems. b Peak demand power PM, QM and power factor 

b  Active and reactive energy

b Tripping currents: I1, I2, I3, I0

b Unbalance ratio/negative sequence current Ii


   0
   9
   3
   6
   5
To Busbar VT’s b Phase displacement
   E
   D
b Disturbance recording

b Running hours counter/operating time


50/51 A 94 b Thermal capacity used
50N/51N V 69 b Remaining operating time before overload trip
50BF F 86 b Waiting time after overload tripping
Open/close
46 MD 74 b Tripping context.
trip
KW 30
CT’s option
67N/67NC(1) KVAR 68
b CLP1: LPCT sensors 100 A to 1250 A
49RMS KVA 60LF
b Core balance CT: CSH120 or CSH200.
27/27S PF
59 KW.h
KVar.h   p
   i
  r
DGPT2    t
  r
  e
   t
  n
Control
   I

Sepam T40 Basic MES114 module


apparatus (10 I/4 O)
Cumulative breaking current b b

Trip CB output (O1) b b

Closing lockout (O2) b b

 Analog Output Logic discrimination block send (O3) b b

Watch dog (O4) b b


Remote UMI CB control (86) b b

Modbus RS485 CB open/closed status indication b

Number of operations, operating time b


Transformer feeder T6 
Trip circuit supervision (74) b

Logic discrimination block receive BI1 b

Protection CB closing order b

Sepam T40 Fault and alarm contact (O11(2) to O14) b

b 50/51: overcurrent - IDMT, DT (4 s ettings) CB opening order b

b 50N/51N: earth fault - IDMT, DT (4 settings) Pressure alarm b


b 50BF: breaker failure
Pressure tripping b
b 46: negative sequence overcurrent - IDMT,
Thermostat alarm b
DT (2 settings)
b 67: directional phase overcurrent (1) - IDMT,
Thermostat tripping b

DT (2 settings) External network time synchronization b

b 67N/67NC: directional earth fault (1) - IDMT,

DT (2 settings) Optional features


b 49RMS: thermal overload (2 settings) b Communication interface module, 2 wires (ACE949-2) Modbus
b 27/27S: undervoltage (2 settings) b Communication interface module, 4 wires (ACE959) Modbus
b 59: overvoltage (2 settings) b Logic inputs and outputs module MES114 (10I/4O)
b 59N: neutral voltage displacement (2 settings) b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
b 38/49T: temperature monitoring. b 8 temperature sensor inputs (38/49T) MET148-2 module

b Remote advanced UMI user machine interface (type DS M303)

b Test box
(1) On Sepam T42 only  b Local/remote switch.
(2) O11 reserved for closing order 

DEAI06EN.indd 21
Application Transformer incomer T4

b  Protection against internal faults and  Measurement and diagnostic


overload protection Sepam T40 or T42, LCD display LED (Light Emitting Diode)
b  It also monitors the winding temperature b Phase current: I1, I2, I3 RMS

b Residual current: I0
and Buchholz device providing local and 
b  Average currents: I1, I2, I3
remote indication of operation b Peak demand phase currents
b  It suited for integration into a supervisory  b Line voltage: U21, U32, U13

system using Modbus serial interface. b Phase to neutral voltage: V1, V2, V3

b Residual voltage: V0
Several standard options are available
b Positive sequence voltage/rotation direction
to ensure maximum flexibility and cost  b Frequency
effectiveness in meeting the requirements b  Active, reactive and apparent power: P, Q, S

of different systems. b Peak demand power PM, QM and power factor 

b  Active and reactive energy

b Tripping currents: I1, I2, I3, I0

b Unbalance ratio/negative sequence current Ii


   1
   9
   3
   6
   5
Modbus RS485 b Phase displacement
   E
   D
b Disturbance recording
Remote UMI b Running hours counter/Operating time

 Analog Output b Thermal capacity used

b Remaining operating time before overload trip

b Waiting time after overload tripping

b Tripping context.

CT’s option
50/51 A 94 b CLP1: LPCT sensors 100 A to 1250 A
  p
   i
50N/51N V 69   r
   t b Core balance CT: CSH120 or CSH200.
50BF F 86   r
  e
   t
46 MD 74   n
   I
67(1) KW 30
67N/67NC(1) KVAR 68
49RMS KVA 60LF Control
27/27S PF
59 KW.h Sepam T40 or T42 Basic MES114 module
59N KVar.h apparatus (10 I/4 O)
Thermost Cumulative breaking current b b

Open/close Buchholz Trip CB output (O1) b b


trip Closing lockout (O2) b b

Logic discrimination block send (O3) b b

Watch dog (O4) b b

CB control (86) b b
Transformer feeder T4
CB open/closed status indication b

Number of operations, operating time b

Trip circuit supervision (74) b

Logic discrimination block receive BI1 b

Protection CB closing order b

Sepam T40 or T42 Fault and alarm contact (O11(2) to O14) b

b 50/51: overcurrent - IDMT, DT (4 settings) CB opening order b

b 50N/51N: earth fault - IDMT, DT (4 settings) Buchholz alarm b


b 50BF: breaker failure
Buchholz tripping b
b 46: negative sequence overcurrent - IDMT,
Thermostat alarm b
DT (2 settings)
b 67: directional phase overcurrent (1) - IDMT,
Thermostat tripping b

DT (2 settings) External network time synchronization b

b 67N/67NC: directional earth fault (1) - IDMT,

DT (2 settings) Optional features


b 49RMS: thermal overload (2 settings) b Communication interface module, 2 wires (ACE949-2) Modbus
b 27/27S: undervoltage (2 settings) b Communication interface module, 4 wires (ACE959) Modbus
b 59: overvoltage (2 settings) b Logic inputs and outputs module MES114 (10I/4O)
b 59N: neutral voltage displacement (2 settings). b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module

b Remote advanced UMI user machine interface (type DS M303)

b Test box

b Local/remote switch.
(1) On Sepam T42 only 
(2) O11 reserved for closing order 

22 DEAI06EN.indd
Application Transformer incomer T5

 Protection against internal faults and 


b  Measurement and diagnostic
overload protection Sepam T40 or T42, LCD display LED (Light Emitting Diode)
b  It also monitors the winding by probes b Phase current: I1, I2, I3 RMS

b Residual current: I0
 providing device local and remote indication
b  Average currents: I1, I2, I3
of operation b Peak demand phase currents
b  It suited for integration into a supervisory  b Line voltage: U21, U32, U13

system using Modbus serial interface. b Phase to neutral voltage: V1, V2, V3

b Residual voltage: V0
Several standard options are available
b Positive sequence voltage/rotation direction
to ensure maximum flexibility and cost  b Frequency
effectiveness in meeting the requirements b  Active, reactive and apparent power: P, Q, S

of different systems. b Peak demand power PM, QM and power factor 

b  Active and reactive energy

b Tripping currents: I1, I2, I3, I0

b Unbalance ratio/negative sequence current Ii


   2
   9
   3
   6
   5
Modbus RS485 b Phase displacement
   E
   D
b Disturbance recording

Remote UMI b Running hours counter/operating time

b Thermal capacity used


 Analog Output b Remaining operating time before overload trip

Temp Sensor  b Waiting time after overload tripping

b Tripping context.

CT’s option
b CLP1: LPCT sensors 100 A to 1250 A
50/51 A 94
  p
   i b Core balance CT: CSH120 or CSH200.
50N/51N V 69   r
   t
50BF F 86   r
  e
   t
46 MD 74   n
   I
67(1) KW 30
67N/67NC(1) KVAR 68
49RMS KVA 60LF
Control
27/27S PF Sepam T40 or T42 Basic MES114 module
59 KW.h apparatus (10 I/4 O)
59N KVar.h Cumulative breaking current b b
38/49T Temp
Trip CB output (O1) b b
Open/close
trip Closing lockout (O2) b b

Logic discrimination block send (O3) b b

Watch dog (O4) b b

CB control (86) b b

Transformer feeder T5  CB open/closed status indication b

Number of operations, operating time b

Trip circuit supervision (74) b

Logic discrimination block receive BI1 b

Protection CB closing order b

Sepam T40 or T42 Fault and alarm contact (O11(1) to O14) b

b 50/51: overcurrent - IDMT, DT (4 s ettings) CB opening order b

b 50N/51N: earth fault - IDMT, DT (4 settings) Inhibit closing b


b 50BF: breaker failure
External tripping b
b 46: negative sequence overcurrent - IDMT,
Local/remote control selection b
DT (2 settings)
b 67: directional phase overcurrent - IDMT,
Inhibition thermal overload b

DT (2 settings) External network time synchronization b

b 67N/67NC: directional earth fault - IDMT,

DT (2 settings) Optional features


b 49RMS: thermal overload (2 settings) b Communication interface module, 2 wires (ACE949-2) Modbus
b 27/27S: undervoltage (2 settings) b Communication interface module, 4 wires (ACE959) Modbus
b 59: overvoltage (2 settings) b Logic inputs and outputs module MES114 (10I/4O)
b 59N: neutral voltage displacement (2 settings) b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
b 38/49T: temperature monitoring. b 8 temperature sensor inputs (38/49T) MET148-2 module

b Remote advanced UMI user machine interface (type DS M303)

b Test box

b Local/remote switch.
(1) O11 reserved for closing order 

DEAI06EN.indd 23
Application Motor feeder M1

 Protection against internal faults and 


b  Protection
loads faults Sepam M20
b  Monitoring of motor starting conditions b 50/51: overcurrent - IDMT, DT (4 settings)

b 50N/51N: earth fault - IDMT, DT (4 settings)


and winding temperature by probes
b 46: negative sequence overcurrent
 providing local and remote indication of  b 49RMS: thermal overload (2 settings)
operation b 37: undercurrent

b  It suited for integration into a supervisory  b 48/51LR: exces. start. time, locked rotor 

b 66: starts per hour 


system using Modbus serial interface.
b 38/49T: temperature monitoring.
Several standard options are available
to ensure maximum flexibility and cost 
effectiveness in meeting the requirements
of different systems.
Measurement and diagnostic
   3
   9
Sepam M20, LCD display LED (Light Emitting Diode)
   3
b Phase current: I1, I2, I3 RMS
   6
   5
   E
   D
b Residual current: I0

b  Average currents: I1, I2, I3


Trip/close(1)
b Peak demand phase currents

b Temperature measurement
50/51  A 86 b Tripping currents: I1, I2, I3, I0
50N/51N MD 74 b Unbalance ratio/negative sequence current Ii
49RMS Temp 30 b Disturbance recording
46 68 b Running hours counter/operating time
37 b Thermal capacity used
48/51LR/14 b Remaining operating time before overload trip
66 b Waiting time after overload tripping
38/49T b Starting current and time/overload

b Start inhibit time delay/numb. start before inhibition.

CT’s option
b CLP1: LPCT sensors 100 A to 1250 A

b Core balance CT: CSH120 or CSH200.

M Temp Sensor 
 Analog Output
Remote UMI
Control
Modbus RS485 Sepam M20 Basic MES114 module
apparatus (10 I/4 O)
Motor feeder M1
Cumulative breaking current b b

Trip CB output (O1) b b

Closing lockout (O2) b b

Logic discrimination block send (O3) b b

Watch dog (O4) b b

CB control (86) b b

CB open/closed status indication b

Number of operations, operating time b

External trip b

Trip circuit supervision (74) b

Fault and alarm contact (O11(2) to O14) b

Motor reacceleration b

(1) Close by communication Motor shaft rotation b

(2) O11 reserved for closing order  Local/remote control selection b

Inhibition thermal overload b

External network time synchronization b

Optional features
b Communication interface module, 2 wires (ACE949-2) Modbus

b Communication interface module, 4 wires (ACE959) Modbus

b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module

b 8 temperature sensor inputs (38/49T) MET148-2 module

b Remote advanced UMI (type DSM303)

b Test box

b Local/remote switch

b Logic inputs and outputs module MES114 (10I/4O).

24 DEAI06EN.indd
Application Motor feeder M2

b  Protection against internal faults, network  Measurement and diagnostic


related and loads faults Sepam M41, LCD display LED (Light Emitting Diode)
b  Monitoring of motor starting conditions b Phase current: I1, I2, I3 RMS

b Residual current: I0
and the winding temperature
b  Average currents: I1, I2, I3
b  It suited for integration into a supervisory 
b Peak demand phase currents
system using Modbus serial interface. b Line voltage: U21, U32, U13

Several standard options are available b Phase to neutral voltage: V1, V2, V3

b Residual voltage: V0
to ensure maximum flexibility and cost 
b Positive sequence voltage/rotation direction
effectiveness in meeting the requirements b Frequency
of different systems. b  Active, reactive and apparent power: P, Q, S

b Peak demand power PM, QM and power factor 

b  Active and reactive energy


   4 b Tripping currents: I1, I2, I3, I0
   9
   3
   6 To Busbar VT’s
   5
   E b Unbalance ratio/negative sequence current Ii
   D
b Phase displacement

b Disturbance recording
50/51 A 94
b Running hours counter/operating time
50N/51N V 69
b Thermal capacity used
50BF F 86
b Remaining operating time before overload trip
46 MD 74
b Waiting time after overload tripping
Open/close 67N/67NC KW 30
b Starting current and time
trip 32P KVAR 68
b Start inhibit time delay/number of start before inhibition
32Q/40 KVA 60LF
b Tripping context.
49RMS PF
37 KW.h CT’s option
48/51LR/14 KVar.h b CLP1: LPCT sensors 100 A to 1250 A

66 Temp b Core balance CT: CSH120 or CSH200.

27D
27R
27/27S
59
59N Control
47
Sepam M41 Basic MES114 module
38/49T
apparatus (10 I/4 O)
Temp Sensor  Cumulative breaking current b b
M
Trip CB output (O1) b b
 Analog Output Closing lockout (O2) b b

Remote UMI Logic discrimination block send (O3) b b

Watch dog (O4) b b

Modbus RS485 CB control (86) b b

CB open/closed status indication b


Motor feeder M2 
Number of operations, operating time b

Trip circuit supervision (74) b

Motor rotation detection b


Protection CB closing order  b
Sepam M41
Fault and alarm contact (O11(1) to O14) b
b 50/51: overcurrent - IDMT, DT (4 s ettings)
CB opening order b
b 50N/51N: earth fault - IDMT, DT (4 settings)

b 50BF: breaker failure Inhibit closing b

b 46: negative sequence overcurrent External tripping b

b 67N/67NC: directional earth fault - IDMT, Local/remote control selection b


DT (2 settings)
Inhibition thermal overload b
b 32P: directional active overpower 
External network time synchronization b
b 32Q/40: directional reactive overpower 

b 49RMS: thermal overload (2 settings)

b 37: phase undercurrent Optional features


b 48/51LR/14: exces. start. time, locked rotor  b Communication interface module, 2 wires (ACE949-2) Modbus

b 66: starts per hour  b Communication interface module, 4 wires (ACE959) Modbus

b 27D: positive sequence undervoltage (2 settings) b Logic inputs and outputs module MES114 (10I/4O)

b 27R: remanent undervoltage b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module

b 27/27S: undervoltage (2 settings) b 8/16 temperature sensors inputs MET148-2 module

b 59: overvoltage (2 settings) b Remote advanced UMI (type DSM303)

b 59N: neutral voltage displacement (2 settings) b Test box

b 47: negative sequence overvoltage b Local/remote switch.

b 38/49T: temperature monitoring.

(1) O11 reserved for closing order 

DEAI06EN.indd 25
Application Generator incomer G1

b  Protection against faults, network and  Measurement and diagnostic


loads faults Sepam G40, LCD display LED (Light Emitting Diode)
b  Monitoring of winding temperature b Phase current: I1, I2, I3 RMS

b Residual current: I0
b  It suited for integration into a supervisory 
b  Average currents: I1, I2, I3
system using Modbus serial interface. b Peak demand phase currents
Several standard options are available b Line voltage: U21, U32, U13

to ensure maximum flexibility and cost  b Phase to neutral voltage: V1, V2, V3

b Residual voltage: V0
effectiveness in meeting the requirements
b Positive sequence voltage/rotation direction
of different systems. b Frequency

b  Active, reactive and apparent power: P, Q, S

b Peak demand power PM, QM and power factor 

b  Active and reactive energy


   5
   9 b Tripping currents: I1, I2, I3, I0
   3
   6 50/51 A 94
   5
   E b Unbalance ratio/negative sequence current Ii
   D 50V/51V V 69
b Phase displacement
50G/51G F 86
b Disturbance recording
50BF MD 74
b Running hours counter/operating time
Open/close 46 KW 30
b Thermal capacity used
trip   32P KVAR 68
b Remaining operating time before overload trip
32Q/40 KVA 60LF
b Waiting time after overload tripping
49RMS PF
b Tripping context.
27/27S KW.h
59 KVar.h CT’s option
59N Temp b CLP1: LPCT sensors 100 A to 1250 A

47 b Core balance CT: CSH120 or CSH200.

81H
81L
38/49T

Control
Sepam G40 Basic MES114 module
apparatus (10 I/4 O)
G Temp Sensor  Cumulative breaking current b b

 Analog Output Trip CB output (O1) b b

Closing lockout (O2) b b


Remote UMI
Logic discrimination block send (O3) b b

Watch dog (O4) b b


Modbus RS485
CB control (86) b b

Generator incomer G1 CB open/closed status indication b

Number of operations, operating time b

Trip circuit supervision (74) b

Logic discrimination block receive Bl1 b


Protection CB closing order  b

Sepam G40 Fault and alarm contact (O11(1) to O14) b


b 50/51: overcurrent - IDMT, DT (4 settings)
CB opening order b
b 50G/51G: earth fault - IDMT, DT (4 settings)
Inhibit closing b
b 50BF: breaker failure

b 46: negative sequence overcurrent External tripping b

b 32P: directional active overpower  Local/remote control selection b

b 32Q/40: directional reactive overpower  Inhibition thermal overload b


b 49RMS: thermal overload
External network time synchronization b
b 27/27S: undervoltage (2 settings)

b 59: overvoltage (2 settings)


Optional features
b 59N: neutral voltage displacement (2 settings)
b Communication interface module, 2 wires (ACE949-2) Modbus
b 47: negative sequence overvoltage
b Communication interface module, 4 wires (ACE959) Modbus
b 81H: overfrequency (2 settings)
b Logic inputs and outputs module MES114 (10I/4O)
b 81L: underfrequency (4 settings)
b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
b 38/49T: temperature monitoring.
b 8/16 temperature sensors inputs MET148-2 module

b Remote advanced UMI (type DSM303)

b Test box

b Local/remote switch.

(1) O11 reserved for closing order 

26 DEAI06EN.indd
   d
  e
  v
  r
  e
  s
  e
  r
  s
   t
   h
  g
   i
  r
   l
   l
   A
  -
   S
   A
   S
  s
  e
   i
  r
   t
  s
  u
   d
  n
   I
  c
   i
  r
   t
  c
  e
   l
   E
  r
  e
   d
   i
  e
  n
   h
  c
   S
   ©
      9
      4
      2
      0
      6
      9
 .
      T
      R
      A

Schneider Electric Industries SAS  As standards, specifications and designs change from time to time, please ask for confirmation
89, boulevard Franklin Roosevelt of the information given in this publication.
F-92505 Rueil-Malmaison Cedex
Tel.: +33 (0 )1 41 29 85 00 This document has been printed
www.schneider-electric.com on ecological paper 

Publishing: Schneider Electric Industries SAS


Production: Graphème
Printing:

DEAI06EN 05-2008

Potrebbero piacerti anche