Area coverage per nozzle is 3’(L) x 3’(W) or one (1) no. of nozzle for one (1) no of cooking appliance. Hence, no. of nozzles required = 3 nos. 3 appliance nozzles have been selected.
B. Exhaust Duct Nozzle – [Flow No. = 1]
Perimeter coverage require 1 nozzle per exhaust duct as duct’s limitation as follows: 1 duct nozzles are capable of protecting square or rectangular duct with maximum 50 in. perimeter, with the longest side being a maximum of 16 in. Hence, no of duct nozzle required = 1 (Qty of duct) x 2 nozzles = 2 nozzles 2 duct nozzles have been selected.
C. Plenum Nozzle – [ Flow No. = 1]
Area coverage per nozzle = 10 ft(L) x 4 ft (W) Hence, no of plenum nozzle required = 1 no 1 plenum nozzles have been selected.