3-5T, 15-25Ton Pkgd Elec/Elec Rooftop - Foundation - (BPGDE)

66 RT Almacen Lurin Foundation 20tn

Tag BPGDE-A-1, Model number EAC240

Tonnage 20 Ton Refrigeration systems Not Used


option
Refrig charge 13.2 lb Refrig charge (HFC-410A) - 7.1 lb
(HFC-410A) - ckt 1 ckt 2

Airflow configuration Convertible Design Airflow 7400 cfm


Tonnage 20 Ton Unit function Cooling
Voltage 208-230/60/3 Design ESP 1.000 in H2O

Cooling Leaving Unit DB 57.84 F Cooling Leaving Unit WB 56.68 F


Cooling Entering Dry 80.00 F Cooling Entering Wet Bulb 67.00 F
Bulb
Gross Total Capacity 248.73 MBh Gross Sensible Capacity 190.25 MBh
Gross Latent Capacity 58.48 MBh Ambient Temp 95.00 F
Net Total Capacity 239.18 MBh Net Sensible Capacity 180.70 MBh

MCA 117.00 A MOP 150.00 A


Compressor 1 RLA 46.50 A Compressor 2 RLA 27.00 A
Electric Heat FLA Voltage 208-230/60/3

Heating capacity Without heat Heating EAT


Heating LAT Heating Temp Rise

Field Supplied Drive Kit None MCA (230 w/ Elec Heat) 0.00 A

Required
Electric Heat Static Press 0.000 in H2O MOP (230 w/Elec Heat) 0.00 A

Add
Component SP Add 0.000 in H2O Total Static Pressure 1.000 in H2O

Indoor Mtr. Operating 3.03 bhp Condenser Fan FLA 5.00 A

Power
Indoor RPM 831 rpm Evaporator Fan FLA 16.70 A
Indoor Motor Power 2.26 kW Outdoor Motor Power 1.69 kW
Electric Heat FLA (230 V) Compressor Power 19.75 kW

Supply Standard drive motor System Power 23.69 kW

fan/drive/type/motor
Exhaust fan power 0.56 kW EER @ AHRI Conditions 10.0 EER
IEER Rating 10.80