Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
1 Scope............................................................. 2
2 Conflicts and Deviations................................. 2
3 References..................................................... 2
4 Information Required with Quotation.............. 5
5 Definitions....................................................... 6
6 Service Conditions.......................................... 8
7 General........................................................... 9
8 Corrosion Protection..................................... 11
9 Labeling/Listing/Certification......................... 11
10 Rating........................................................... 12
11 Structure....................................................... 13
12 Enclosures.................................................... 14
13 Wireways/Raceways..................................... 17
14 Conductors/Cables....................................... 18
15 Switching and Distribution Devices.............. 22
16 Protection, Control and Metering.................. 29
17 Utilities.......................................................... 36
18 Grounding (Earthing).................................... 37
19 Interlocks...................................................... 37
20 Nameplates and Marking.............................. 38
21 Testing.......................................................... 38
22 Shipping........................................................ 39
1 Scope
1.1. Outdoor, maximum 600A rated switchracks which are either completely or
partially field assembled or whether it is installed as a fully assembled unit.
The switchrack may be comprised of factory-built assemblies (FBAs) built to
either IEC or NA based Standards, or a mixture of both. Individual FBAs built
utilizing a mixture of standards is unacceptable.
2.1 If there are any conflicts between this Specification and associated purchasing,
project or engineering documents, this specification shall take precedence.
2.2 Direct all requests to deviate from this Specification in writing to the Company
or Buyer Representative, who shall follow internal company waiver procedure.
3 References
The following is a summary of all the documents which have been mentioned within
this Specification. The specific part(s) of these documents which are applicable have
been identified throughout this Specification.
Page 2 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
Page 3 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
Page 4 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
Underwriters Laboratories
UL 98 Enclosed and Dead-Front Switches
UL 198C High-Interrupting-Capacity Fuses, Current-Limiting
Types
UL 198D Class K Fuses
UL 198E Class R Fuses
UL 363 Knife Switches
UL 489 Molded-Case Circuit Breakers and Circuit-Breaker
Enclosures
UL 508 Industrial Control Equipment
UL 845 Motor Control Centers
UL 886 Outlet Boxes and Fittings for Use in Hazardous Areas
The following is a list of the information which shall be supplied with the Quotation:
Page 5 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
the subject tests were performed. If requested, the Supplier shall provide the
Buyer with all the necessary detailed testing information suitable for
independent verification of the test data. This request may be made at any time
prior to, or after, the award of the Purchase Order.
4.2 User's List of the same or similar equipment which has been in service for a
minimum of two (2) years. List should indicate:
a) User company name.
b) Installation site.
c) Date of installation.
4.3 A detailed listing of all deviations from this standard with an explanation against
each item. In addition, written certification shall be provided that the proposed
equipment shall fully comply with all other items within this Standard.
4.4 The items listed in 4.1 to 4.3 above are necessary to complete the technical
evaluation of the Quotation. Failure to provide this information will result in the
automatic disqualification of the Quotation. This list is in addition to the
information requested within the Quotation Request or the Purchase Order
documents.
5 Definitions
Conductor: All material, devices and parts which are expected to carry current as part
of their normal function (e.g., cable, bus, relay contacts, terminal block studs, etc.).
Enclosure: The case or housing surrounding electrical devices to protect these devices
from the environment, from physical damage, or to prevent personnel from accessing
the devices. This definition does not include raceway/wireway fittings (i.e., unions
couplings, reducers, elbows, conduit bodies, etc.) which are considered an integral part
Page 6 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
Main Circuit: Per the IEC 60050 definition, is all the conductive parts of an assembly
included in a circuit which is intended to transmit electrical energy to the connected
load.
Commentary Notes:
1) Note that per the IEC 60050 definition, “main circuit” includes the controlgear neutral
conductor system.
2) For example, when “main circuit circuit breaker” is used, it means a circuit breaker which
is connected to the main circuit.
Mechanical Connectors: Connectors which are attached onto the conductor using,
generally, a standard, non-proprietary tool. The process is reversible and the connector
can be removed from the conductor without cutting the conductor or the connector.
Raceways: Enclosed channels for housing and protecting electric wires and cable.
This term includes rigid and flexible conduit.
Service Connection Equipment: The electrical devices which carry the entire current
load for the switchrack. This includes, for example, the service entrance terminations,
main incoming disconnector (if used) and the enclosure which is used to distribute the
main circuit to the individual FBAs.
Specification: The main body (i.e., sections 1 to 22) and does not include the
information contained within the Data Schedules.
Page 7 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
Switching Assembly: Is the assembly of switching devices and associated control and
auxiliary equipment which controls or distributes power to a single load, or group of
loads via a single circuit (e.g., a motor starter is a switching assembly).
Wireways: Troughs, channels, etc., with or without hinged or removable covers, for
housing and protecting electric wires and cable.
6 Service Conditions
6.1 General
The switchrack will be installed outdoors and shall be suitable for continuous
operation under the following service conditions:
a) Ambient air temperature:
i) A maximum of 50°C.
ii) A minimum of 0°C, unless a lower temperature is specified within
Data Schedule 1.
iii) Average temperature, measured over a period of 1 month, is a
maximum of 45°C.
Commentary 6.1.1 a):
Page 8 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
7 General
7.3 This specification shall take precedence over any referenced third party
document.
Page 9 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
7.6 The switchrack structure, and devices mounted on the switchrack may be of
dissimilar metals. However, all devices and structural members shall be suitably
protected against galvanic action where dissimilar metals are in contact.
7.7 All conduit and cable gland connections shall be threaded. All threading of
conduit and cable gland connections shall be tapered (NPT) in accordance with
ANSI/ASME B1.20.1. Metric to NPT conversion fittings shall not be used.
7.8 Conduit or cable shall terminate into hubs. Enclosures, devices, switching
assemblies, FBAs, etc., without built-in hubs shall be provided with conduit hub
fittings. Conduit hub fittings shall have an equal, or better, environmental rating
as the device into which it is installed and shall meet the requirements of
Section 13.2. Hubs shall be threaded in accordance with paragraph 7.5.
7.9 Oil immersed switching devices shall not be used in any circuits.
7.11 Controllers for fire pump motors shall meet the additional requirements
presented within NFPA 20.
7.12 Incoming power to the switchrack shall be distributed in a radial, star type
fashion from the dedicated enclosure indicated within Section 11.
(NA Supplement)
7.NA1 Clearance and creepage distances and spacings shall meet the requirements of
NEMA ICS 1. For the application of these standards, the following shall also
be assumed per NEMA ICS 1, Annex A:
a) Group A “General Industrial Control.”
b) Category III “Distribution Level” Overvoltage Category.
Page 10 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
(IEC Supplement)
7.IEC1 Clearance and creepage distances and spacings shall meet the requirements of
IEC 60947-1. For the application of these standards, the following shall also
be assumed:
a) Material Group I
b) Pollution Degree 4.
8 Corrosion Protection
8.1 Corrosion primary protection shall be via material selection (e.g., stainless steel,
aluminum) or plating. Paint shall not be used for corrosion or oxidization
prevention.
Exception:
9 Labeling/Listing/Certification
9.2.2 FM procedures
Page 11 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
9.3 Labeling, listing or certification of all equipment shall be by at least one of the
following:
10 Rating
Page 12 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
(NA Supplement)
(IEC Supplement)
11 Structure
11.1.2 Steel which has been hot-dip galvanized after completion of the
welding and drilling associated with the fabrication of switchrack
structure. It is acceptable to field drill the holes necessary to attach the
FBAs providing the bare metal is touched-up with a zinc-rich paint.
11.2 The switchrack structure shall not be painted or coated after galvanizing.
11.3 Equipment shall be fastened to the rack with stainless steel or hot-dip
galvanized hardware.
11.5.1 Shall extend a minimum of 1 meter horizontally from the surface of the
Page 13 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
11.5.2 With the top of the switchrack structure as the horizontal plane, the
gable canopy(ies) shall be sloped a minimum of 15 degrees.
Exception to Section 11.5:
11.6 Lifting attachments/connectors shall be provided for lifting the entire switchrack,
with canopy attached, without permanent distortion to any part of the structure.
12 Enclosures
12.1 General
12.1.1 As indicated within Section 9, all enclosures shall bear labels from a
third party testing laboratory (i.e., UL, CSA, BASEEFA, KEMA, etc.)
indicating that they are designed, constructed and tested to the
applicable standards referenced within this specification.
Exception:
Page 14 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
12.1.6 All switchrack devices shall meet the requirements of the following:
a) Under the test conditions indicated below it shall not be possible
for a flexible rod, having a diameter of 13 mm and a rounded tip
(radius of 0.5 times rod diameter), to contact live parts or be
inserted into any openings.
Page 15 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
Exception:
b) The term “live part(s)” shall mean parts at a voltage greater than
24V.
c) The “test conditions” shall be each of the following:
i) With the main circuit disconnector compartment door/cover
open, the switching device in the open position and the line
side of the main circuit disconnector energized.
ii) With any of the FBA doors/covers in the open position, the
associated switching device in the open position and the
line side of the switching device energized.
12.1.8 Stainless steel breathers and drains shall be provided for enclosures
installed outdoors, including bus enclosures. Aluminum alloy vent
caps are acceptable.
Page 16 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
13 Wireways/Raceways
13.1 General
13.1.1 As indicated within section 19, conduit or cable armor shall not be
depended upon for equipment grounding.
13.1.2 The Supplier shall make provisions for the termination of the field
cable(s)/raceway(s) into the appropriate enclosure(s). The details shall
be provided on the Reference Drawings.
13.2 Conduit
Page 17 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
ii) The internal surfaces of PVC sleeves and other mating PVC
surfaces shall be coated with a PVC patching compound.
13.2.3 When cables entering enclosures are required to be sealed by the NEC,
they shall be sealed by means of: barrier type cable glands, utilizing
sealing compound, (EEx d) or MI cable. These are called explosionproof
glands by some manufacturers, flameproof by others. See SAES-P-100
for third party approval requirements. Flameproof (EEx d) non-barrier
type cable glands, without sealing compound, are not acceptable.
14 Conductors/Cables
14.1 General
14.2 Material
Page 18 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
Page 19 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
14.2.4 For armored cable, a cable terminator (gland) shall be used with the
following characteristics:
a) Shall ground the metallic sheath or armor. Terminators relying
on inward protruding flat springs (tines) for grounding the
metallic sheath or armor are prohibited.
b) Shall be designed to permit disconnection without the need to
rotate the cable or the device on which the gland is terminated
(e.g., sealing glands shall have built-in union).
c) Shall be threaded in accordance with paragraph 7.6.
14.3 Terminations
b) Compression ferrules.
14.3.2 The size and number of main circuit supply conductors shall be as
indicated within Data Schedule 1.
14.3.3 Connectors shall only be used with the type and size of conductors
approved by the connector manufacturer.
Page 20 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
14.3.5 Shorting type terminal blocks shall be provided for current transformer
circuits.
14.3.6 Low voltage circuit terminal blocks used to terminate the field cables
to the switchrack shall have the following characteristics:
a) Be factory labeled to indicate that they comply with the standards
listed at the end of this section.
b) Operational voltage rating shall be a minimum of 600 V.
c) Continuous current rating shall be a minimum of 10 A.
d) Be either panel or rail mounted.
e) Be open style with screw terminals.
f) Be rated for 75°C.
g) Within enclosures dedicated to wire/cable terminations, spare
capacity shall be provided to allow the Buyer to add 10%
additional terminations. This shall be provided as spare terminal
blocks, spare rail/panel space or a combination of both.
Exception:
Page 21 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
14.3.10 Within the enclosure dedicated to distribute the incoming power to the
individual FBAs, there shall be capability to add a minimum of two (2)
additional outgoing circuits without, in the case of cast metal
enclosures, drilling or tapping the equipment.
(NA Supplement)
14.3.NA1 Terminal blocks used to terminate the field cables shall also meet
the requirements of NEMA ICS 4.
(IEC Supplement)
14.3.IEC1 Terminal blocks used to terminate the field cables shall also meet
the requirements of IEC 60947-7-1.
15.1 General
15.1.1 All switches and circuit breakers connected to the main circuit shall
have the following characteristics:
a) Be manually operable only with the external compartment door
in the closed, secured position. Note that this is conditional upon
the mechanical interlocking described within Section 18.
b) The center of the grip of the operating handle shall be a
maximum of 200 mm from the base of the switchrack or the
working surface.
c) The operating handle shall be directly mechanically connected to
the switch/circuit breaker irrespective of the position of any
compartment doors/covers.
d) The operating handle shall be padlockable in the OPEN
(switched off) position.
e) It shall not be necessary to remove the padlock(s) from the
operating handle to open or close the associated compartment
doors/covers.
Commentary Notes 15.1.1c), d) and e):
Page 22 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
15.1.2 When the switch/circuit breaker is in the OPEN position, the only
voltage present inside the switching assembly shall be at the incoming
terminals of the switch/circuit breaker.
Exception:
15.1.3 Rated Making and Breaking Capacity shall not be less than the
Operational Rating of the switching device.
15.1.5 When a main circuit disconnector has been specified in Data Schedule
1, it shall function to isolate the switchrack from the main incoming
circuit. This device shall have the following additional characteristics:
a) For the purposes of meeting the short circuit interrupting rating,
shall not be, or considered to be, a short circuit protective device.
b) The switchrack shall not have more than one Main Disconnector.
Exception:
15.2 Switches
Page 23 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
(NA Supplement)
(IEC Supplement)
Page 24 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
15.3.3 Circuit breakers within switching assemblies shall have a short circuit
rating not less than that of the complete switchrack.
Exceptions:
Page 25 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
15.3.4 Circuit breakers rated as part of a series rated protection system are
not acceptable (refer to paragraph 15.1.5).
(NA Supplement)
(IEC Supplement)
Page 26 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
15.4 Contactors
15.4.3 The contactor drop-out voltage shall not be greater than 75%, or less
than 10% of the rated voltage of the contactor coil which is holding the
main contacts closed.
15.4.4 The contactor coil shall withstand 110% of rated voltage continuously,
without damage to operating coils, and close successfully at 85% of
rated voltage.
(NA Supplement)
15.4.NA1 Shall be Class A Controllers and shall also meet the general
requirements of NEMA ICS-2, Part 1 and UL 508.
Page 27 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
(IEC Supplement)
15.4.IEC1 Shall also be designed and rated in accordance with IEC 60947-4-1.
15.4.IEC7 Contactors for motor service shall be selected based upon the
following:
a) On the assumption that all motors operate under 90% AC-3
duty and 10% AC-4 duty.
b) Under the above conditions, the endurance of the main contacts
shall be a minimum of 50,000 make/break operations.
15.5 Panelboards
Page 28 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
a) Dry-type.
b) Windings and all main circuit conductors shall be copper.
Exception:
16.1 General
16.1.1 Control, metering and protection devices, with manual features which
are operable with the compartment doors closed, (e.g., selector
switches, pushbuttons, protective relays, etc.) shall be mounted a
maximum of 2000 mm from the base of the switchrack.
Page 29 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
16.1.5 Series rated protection systems are not acceptable. Note that
paragraph 15.3.3 accepts the use of non-rated magnetic only breakers
under certain conditions.
16.1.6 All devices shall have screw type terminals suitable to accept the
connectors indicated within Section 14.
(NA Supplement)
16.1.NA1 Pilot devices shall meet the requirements of NEMA ICS 5, Part 5
and shall have the following characteristics:
a) Pilot devices shall be heavy-duty and oil tight.
b) Pilot devices shall have the same, or better,
environmental/corrosion resistance rating as the enclosure in
which they are mounted.
c) Contact ratings shall be a minimum of A600/P600.
(IEC Supplement)
Page 30 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
16.2 Fuses
16.2.1 Fuses shall not be used in the main circuit except to provide the
current limiting function as part of a circuit breaker (refer to Section 16
for restrictions).
(NA Supplement)
(IEC Supplement)
Page 31 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
Phase Overcurrent.
16.3.3 Devices which provide the overload function shall have the following
characteristics:
a) An overload on any of the three phase conductors shall open the
main circuit to the motor.
b) Trip characteristics shall be automatically ambient compensated.
c) Class 20 trip class. If specified for specialized applications
(e.g., submersible motors, hermetic motors, etc.) or where
specifically recommended by the motor manufacturer, Class 10
or 30 trip class is acceptable.
d) Be manually resettable with the switching assembly
compartment door closed.
e) Trip setting be either:
i) Adjustable over a minimum range of 90% to 110%.
The overload device shall be selected so the required setting
shall be at the midpoint of the operating range (i.e., 100%
±10%).
ii) Have interchangeable heating elements.
f) For manually controlled motors 0.75 kW (1.0 HP) or less, it is
acceptable that the overload function be provided by a thermal-
magnetic circuit breaker.
g) Be trip free.
Page 32 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
(NA Supplement)
(IEC Supplement)
Page 33 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
16.4.3 All phase current transformers within each switching assembly shall
be identical in all characteristics.
16.4.4 The rated burden of all instrument, control and voltage transformers
shall be a minimum of 125% of the load burden.
(NA Supplement)
16.7 Meters
Page 34 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
16.7.2 Main incoming amperage and voltage metering shall be provided for
each switchrack assembly. This metering shall have the following
additional requirements:
a) Shall display a continuous voltage indication of at least one
phase. If a main circuit disconnector is used, voltage shall be
measured on the load side of the Disconnector.
b) Shall display a continuous amperage indication of at least one
phase.
c) Voltmeter or ammeter switches shall not be used.
(NA Supplement)
16.8.NA1 All relays which interface with the field cabling shall meet the
Page 35 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
(IEC Supplement)
17 Utilities
17.1 Receptacles
If the switchrack includes a 230 VAC distribution system, a 230 VAC utility
receptacle shall be provided with the following characteristics:
a) SASO 2203 type.
b) Mounted within an approved enclosure and equipped with self-closing
covers.
c) Weatherproof when the covers are closed.
d) Fed from a minimum of 16 A rated Ground Fault Circuit Breaker with
5 mA or 30 mA sensitivity. (i.e., receptacles with integral ground fault
protection are not acceptable).
17.2 Lighting
Task lighting fixture(s) shall be provided which have the following characteristics:
a) High Pressure Sodium type.
b) Fixture operates at a maximum voltage of 277 V.
Page 36 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
18 Grounding (Earthing)
18.1 The switchrack structure shall be designed to accommodate two, two hole
compression connectors, one at each end of the switchrack structure.
Unless mentioned otherwise within Data Schedule 1, these lugs shall be
provided by the supplier and shall be designed to accommodate a 70 mm²
(2/0 AWG) copper grounding conductor.
18.2 Conduit, cable armor, wireway, raceways or cable trays shall not be depended
upon for equipment grounding. A separate grounding conductor shall be
installed within each conduit or cable.
19 Interlocks
19.2 The switch-disconnector or circuit breaker operating handle from being closed
unless the compartment door/cover is in the closed, secured position. This
interlock shall be defeatable with two separate operations.
Exception:
Page 37 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
21 Testing
(NA Supplement)
21.1.NA2 The above Dielectric Voltage Withstand Test “Production Test” results
shall be submitted prior to the delivery of the equipment:
Page 38 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
(IEC supplement)
21.1.IEC1 “Routine Tests” (i.e., tests shall be performed on each switchrack at the
manufacturer's or FBA manufacturer premises) shall meet the following
requirements:
a) Routine testing of the FBAs shall be as required within the standards
to which they are manufactured.
b) The entire main circuit of the switchrack shall be submitted to a
Dielectric Test per the requirements of IEC 60439-1.
21.1.IEC2 The above Dielectric Test “Routine Test” results shall be submitted to the
Buyer prior to the delivery of the equipment.
22 Shipping
Unless specified otherwise, the switchrack shall arrive at its installation location
completely assembled.
Commentary Note:
Revision Summary
29 November 2011 Revised the “Next Planned Update.” Reaffirmed the contents of the document, and reissued
with minor revision to eliminate conflict with other standard requirement.
5 March 2015 Minor revision to synchronize the document to use area classifications as per SAES-P-100
and voltage change to 230 V.
Page 39 of 40
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-512
Issue Date: 5 March 2015
Next Planned Update: 29 November 2016 Outdoor Switchrack - Low Voltage
Data Schedule 1
For 16-SAMSS-512: Switchrack - Outdoor
(Information to be Supplied to Supplier)
Line #
Notes to Buyer: (1) Refer to SAES-P-100 for definition of “Severe Corrosive Environment.”
Page 40 of 40