A. LONGITUDINAL STEEL:
Subscribe
1. The cross-sectional area of longitudinal steel in a column shall not be less than 0.8 and not more
than 6% of the gross-sectional area of the column.
In places where bars from a column below have to be lapped with those in the column to be
RECENT POSTS
designed, the maximum percentage of steel should not exceed 4%.
How To Calculate Quantity Of Soil/Sand For
2. The diameter of longitudinal bars should not be less than 12 mm and should not be more than Filling Plot
50 mm. Procedure To Get Sanction Of Building
Permit From The Local Authority
3. Round columns and columns having helical binders should have at least bars.
What Is Guniting – Advantages And
Ads by Google Disadvantages Of Guniting
Concrete Column Foundation Steel and Concrete Construction Difference Between Pier And Abutment
How To Store Cement At Site – Storage Of
A Construction Slab Foundation
Cement
4. The minimum cover of concrete to the outside of longitudinal bars shall be 4 cm or the diameter
of the bar whichever is greater. In case where the maximum dimension of a column does not CATEGORIES
exceed 20 cm and the diameter of the longitudinal bars does not exceed 12 mm, the cover of 2.5
CIVIL ENGINEERING
cm may be used.
http://www.dailycivil.com/basic-rules-for-design-of-column/ 2/7
5/8/2018 Basic Rules For Design Of Column
5. Where it is necessary to splice the longitudinal bars, the bars shall overlap for a distance of not CONCRETE
less than 24 times the diameter of the smallest bar. CONSTRUCTION
6. The spacing of bars measured along the periphery of the column shall not exceed 300 mm. HIGHWAY
RAILWAY
B. TRANSVERSE REINFORCEMENT:
SHARES STRUCTURAL
j Transverse steel may be provided either in the form of lateral ties or helical bars (spiral). SURVEYING
s
4Kminimum diameter of the ties or helical reinforcement shall not less than 1/4th the
1. The
diameter of the largest longitudinal bars and in no case less than 5 mm.
FOLLOW US ON TWITTER
h 4K
2. The maximum diameter of the ties or helical steel should preferably be not more than 12 mm Tweets by @civil_daily
b
and 25 mm respectively.
Civil Daily
1 f
Download PDF (Free) Download Here free.propdfconverter.com @civil_daily
25m³/hr-180m³/hr Concrete Batching Plant, Reasonable Price, Email Top 10 Branches In Civil Engineering
q
2 Concrete Mixing Plant Us Now jinsheng-constructionmachinery.com dailycivil.com/civil-engineer…
3. The pitch of the ties should not be more than the least of the following
Civil Engineering Branch…
Top 10 Civil Engineering Br…
a) Least lateral dimension of the column.
dailycivil.com
b) 16 times the diameter of the smallest longitudinal bar nearest to the compression face of the
member. Mar 29, 2018
4. Pitch of the helical reinforcement should not be more than least of the following:
http://www.dailycivil.com/basic-rules-for-design-of-column/ 3/7
5/8/2018 Basic Rules For Design Of Column
Ad Atlas Quantum
b) 75mm.
4K
5. The least spacing of the lateral ties may be 150 mm and for spirals, the minimum pitch shall be
25 mm or
4Kthree times the diameter of the helical bars whichever is greater.
j 4K s h b f q o 4K
SHARES
RELATED POSTS
http://www.dailycivil.com/basic-rules-for-design-of-column/ 4/7
5/8/2018 Basic Rules For Design Of Column
ABOUT
4KTHE AUTHOR
Admin
3 COMMENTS
http://www.dailycivil.com/basic-rules-for-design-of-column/ 5/7
5/8/2018 Basic Rules For Design Of Column
to cast column for 1st floor…what should I do. Can you plzz help me how to provide lap length
for column…
ADD A4KCOMMENT
Your email address will not be published. Required fields are marked *
Comment:*
Name:*
Email Address:*
http://www.dailycivil.com/basic-rules-for-design-of-column/ 6/7
5/8/2018 Basic Rules For Design Of Column
Website:
ADD COMMENT
4K
4
4K
HOW TO CALCULATE PROCEDURE TO GET WHAT IS GUNITING – DIFFERENCE BETWEEN HOW TO STORE WHY COVER BLOCKS
QUANTITY OF SANCTION OF ADVANTAGES AND PIER AND ABUTMENT CEMENT AT SITE – ARE USED IN
SOIL/SAND FOR BUILDING PERMIT DISADVANTAGES OF STORAGE OF CEMENT REINFORCEMENT
FILLING PLOT FROM THE LOCAL GUNITING
AUTHORITY
http://www.dailycivil.com/basic-rules-for-design-of-column/ 7/7