Sei sulla pagina 1di 10

Designing

Spiral-Plate
Heat Exchangers
Spiral-p,late ex~hangers offer compactness, a variety of f,low arrangements,
efficient heat transfer, and low maintenance costs. lihese
and other features are described, along with a shortcut design method.

P. E. MINTON, Union Carbide Corp. water. Electrodes may also be wound into the assem.
bly to ano.dlcally protect surfaces ag~inst: corrosion.
Spirall heat exchangers have a number of advan- Spiral-plate exchangers are normally designed' for,
tages over conventional shell-and-tube exchangers: the full pressure of each passage. Because the turns
centrifugal forces increase heat transfer; the compact of the spirall are of relatively large diameter, each
configuration results in a shorter undisturbed flow turn must. contain its design pressure,, and plate thick-
lengtH; relatively easy cleaning; and resistance to foul- ness is somewhat restricted-for these three reasons,
ing: These curved-flow units (spiral plate and spiral the maximum design pressure is 150 psi.,. although
tube") are particularly useful1 for handing viscous foX' smaller diameters the pressure. may sometimes be
or .solids-containing fluids .. higher. J.:.imitations of materials of construction gov•
ern design temperature.
Spiral-Plate-Exchanger Fabrication
Flow Arrangements and Applications
A spiral-plate excHanger is fabt'icated from two
relatively long strips of plate, which, are spaced apart The spiral assembly can' be fitted with covers to
and wound around an open1 split center' to form a provide three flow patterns: (:1) both fluids in spiral
pair of concentric spiral 1passages. Spacing is main- flows; (2)' one fluid in spiral flow andi the other in
tained uniformly along the length of the spiral by · axial flow across the spiral; ( 3), one fluid: in spiral
spacer· studs welded to the. plates. flow and the other' in a combination of axial and
For most services, both, fluid-flow channels are spiral i flow.
closed by alternate channels welded at both sides of For spiral flow in both channels,. the spiral assem.
the spiral plate (Fig. 1) .. In some applications, one bly includes flat covers at both sides (Fig. 1). In
of the channels is left completely open (Fig. 4) ,. this arrangement, the fluids usually flow· countercur-
the other closed at both sides of the plate.. These rently., with the cold fluid entering at the periphery
two types of construction' prevent the fluids from, and Bowing toward' the core; and the hot fluid enter-
mixing. ing at the core andi flowing toward the periphery.
Spiral-plate exchangers are fabricated from any 11his type of exchanger can be mounted with the
material that can' be cold worked and welded, such' axis either vertical or horizontal. It finds wide
as: carbon steelj stainless steels, Hastelloy :m and: C, application' in liquid-to-liquid service,. and for gases
nickel and nickel alloys, aluminum alloys, titanium, or condensing vapors if the volumes are not too large
and copper alloys.. Baked phenolic-resin coatings,, for. the maximum flow area of 72 sq. in.
among others, protecti against corrosion from· cooling For spiral flow in one channel, and axial flow in
• Although the spiral-plate and spiral-tutJe exchangers or• aimHar,
the other, the spiral assembly contains conical covers,
their applications. and methods of· fobricaticm ore. quit• different; Thi~ diShed heads, or· extensions with, flat covers (Fig. 2).
article i• devoted wholly. to the spital-plate exchanger; an article in
tiM Ml:ly 18 i1we of Chemical fnginH,;ng wilt take up the 1-piral+tul:Je h1 this design, the passage for axial flow is open. on,
exchanger. ·
both sides, and the spiral flow channel is welded on·
For infonnation on aheU-and-tvbe exchangen, se. Ref. 8, 9,
The desion method presented is used: bf, Union Carbide Corp, for the both sides.
thermal and hydraulic det,ign of· IP!irat-p ate exchangers, and, is lOme· This type of exchanger is suitable for' services in·
wllot,dilfe,...nt from that used by the fabricator.

Reprinted from CHEMICAL ENGINEERING, May 4,. 1970• Copyright ©• 1970' by McGtaw·Hill I no. 330· West 42nd St •• New York, N.Y·. 10036

2030368834
SPI,RAL·PLATE · EXCHANGERS

SPIRAL FLOW in both channels is widely use~ig. 1 FlOW is spiral in one channel, axial in other,.-Fig. 2

which there is a large difference in the volt.unes The spiral-plate exchanger offers many advantages
of the two liquids. This includes liquid-liquid service, over the shell-and-tube exchanger·:
heating or rooling gases, condensing vapors, or as (1)' Single-flow passage makes it ideal for· cooling
reboilers. It may be fabricated with one or more or heating sludges or slurries. Slurries can. be proc·
passes on the axial-flow side. And it can be mounted essed in the spiral at velocities as low as 2 ft./sec.
with the axis of the spiral either vertical or hori- For some sizes and: design pressures, eliminating the
zontal (usually vertically' for condensing or boiling)'· spacer studs enables the exchanger to handle liquids
For combiMtion flow, a conical cover dist:ibutes having a high content. of fioers.
the fluid into its passage (Fig. 3). Part of the spiral (2) Distribution is good because of the single-Bow
is closed at• the top, and the entering fluid flows channel.
only through the center part of, the assembly; A flat• {3) The spiraHplate exchanger. generally fouls at
cover at the bottom• forces the fluid to Bow spirally much lower rates tlian the shell-and-tube exchanger
before leaving the exchanger. because of the single-How passage and curved-How.
This type is most· often used for condensing vapors path. If it fouls, it can be effectively cleaned chemi-
(mounted vertically)'· Vapors &rst flow axially until I cally because of the single-How path and reduced
their volume is reduced sufficiently for finali condens- bypassing. Because the spiral can also be fabricated:
ing and subcooling in spiral flow. with identical! passages, it is used for services in•
A modification of this type: the column-mounted which the switching of fluids allows one fluid to
condenser (Fig. 4). A bottom extension is flanged remove the scale deposited by the other.. Also, be-
to· mate with the column. flange. Vapor flows upward cause the maximum' plate width is 6 ft.,. it is easily
through a large central tube and: then axially across cleaned with. High-pressure water or steam.
the spiral, where it is condensed. Subcooling may (4). This exchanger is well suited for heating or
be by falling~film. cooling or by controlling a level cooling viscous fluids because its LID' ratio is lower·
of condensate in the channel. In the latter case, the than. that; of tubular exchangers. Consequently, lam•
vent• stream leaves in spiraf flow. This type is also inar-flow heat .transfer is much higher for spiral plates.
designed to allow condensate to dropointo an accumu- When' heating or cooling a viscous fluid, the spiral
lator without appreciable subcooling. should be oriented with the axis horizontal. With
COMBINAnON FLOW is used to condense vapors-Fig. 3

the uis verticaL the viscous fluid stratifies and this


reduces heat transfer as much as 50%.
(5)' With both fluids fl.owing spirally, flow can
be countercurrent (although not truly so, because,
MODifiiED combination flow serves on colum~g. 4
throughout the unit, each channel is adjoined by an
ascending and a· descending turn of the other chan-
nel! and because heat-transfer areas are not equal
for each side of the channel, the diameters. being of the spiral assembly. However, repairs on the inner
different). A correction factor may be applied;l how~ parts of the plates are complicated. ·
ever, it is so small' it can generally be ignored. (2) The spiral•plate exchanger is sometimes pre-
Countercurrent flow and' long passages make pos- cluded from serviee in which thennal eyclmg is
sible clbse temperature approaches and precise tem- frequent. When used in cycling services, its mechani-.
perature control. cal. design sometimes must• be altered to provide. for
{6) The spiral-plate exchanger avoids problems much higher stresses. Full-faced gaskets of com-
associated with differential thennal expansion in non- pressed asl:lestos are not generally acceptable for
cyclic service. cycling services because the growth' of the spiral!
(7) In axial flow, a large_flow area affords a low plates. cuts the gasket~ which results in' excessive
pressure. drop, which becomes especially important bypassing and; in some cases,. erosion of the cover.
when condensing under vacuum. Metal-to-metal seals are generally necessary.
(8) This exchanger is compact: 2;000 sq. ft. of ( 3) This exchanger · usually should not be used
heat-transfer· surface in a 58-in.-dia. unit' with a 72- when a hard deposit forms during operation, be- ·
in.-wide plate.. cause the spacer studs prevent such' deposits hom
being easily· removed by drilling. When1 as £or some
Umitations Besides Pressure pressures,. sucli studs can be omitted, this. !.imitatiOn
is not present'
In addition to the pressure limitation· noted earlier, ( 4) For spiral-axial' flow, the temperature difference
the spiral-plate exchanger also has the followimg must be corrected. The conventionali correction for
disadvantages: cross flow applies. Fluids are not mixed\ flows are
{1 Repairing it in the field is difficult. A leak
1
) generally single pass. Axial B.ow may be multipass.
cannot be plugged as in a shell~and-tube exchanger
(however, the possibility of; leakage in a spiral is less SHORT,tUT RATING METHOD
because it is fabricated from' plate generally much
thicker than tube walls). Should a spiral need I repair- The shortcut rating method for spiral-plate ex-
ing, removing the covers exposes most of the welding changers depends on the same technique as that

CHEMICAL ENGINEERING/MAY 4, 1970 2030368836


SPIRAL-PLATE EXCHANGERS • • •

Empirical Heat-Transfer and Pressure-Drop Rel'ationshi'.p


Eq.
No. Mechanism or Restriction EmpiricaliEquation-Heat Transfer

Spiral Flow
(l) No phase change (liquid~'• N •• > N 11u h = (11 + 3:54.D,!Du) 0~023cG (NM.)-• ·~Pr)-' 11

{2) No phase change (gas),N11. > N 11... h = (11 + 3.54 D,/D 11 } 0.0144 cG• • (D,) -•.:

(3) No phase change (!liquid), NR., < N ~<•··


Spiral or Axial Flow
(4) Condensing vapor, vertical, Na. < 2,100 k = 0.925 k [gcpL'IJ<ll]l' 1"

(5,) Condensate subcooling, vertical, N., < 2,100 h = 1.225 k/B [cB!kL.~~]' 1 '

Axia1 Fiow
1

~6) No phase change (lliquid}, N 11 , > 10,000 1

n> No phase change (gas). N Re > 10,000 h = 0.0144 c G"·". (D.) -•':

(8) Condensing vapor, horizontaH N R• < 2,100


(9) Nucleate boiling, vertical

Plate
(10) Plate, sensible heat transfer It= 12 k,./p

(11) Flate, latent heat transfer h = 12 k.,/p

Fouling
(12) Fouling, sensible heat transfer h =assumed

(13) Fouling, latent heat transfer h =assumed

Eq.
No. Mechanism or Restriction E!Tlpirical Equation>-~ressure Drop

~ [d~r Ld,1
Spiral Flow
(14) No phase change, N ~<• >N 11..- aP = 0:0011 1~-!;;5) (~r· + 1.5 + ~]
(15~, No phase change, 100 < N 11 , < Nt..c t>.P = 0·001 sL [-W Jl [. 1.035 Z!'· (~)".·" (.#-)'"
d~H (d~ 0.125) z~
-t; W
,- , 16-
+ 1.;> L- -++

(Hi) No phase change, N11. < 100 t>.P = 3,38~~~,): "(i;J" (~)
(17) Condensing t>.P = 0;000 5 -;
L [ W ]• [
d,H (d,
1.3 z•;• /,H)\''
+ 0.125) \w ' + 1'.5 +
1'L6]
AxiaJIFiow
(18) No phase change, N 11 , > 10,000 t>.P = 4 x 10-'
s d~'
(w)u
L
0.0115 z•' !!.. + 1 + 0.03 H
d,
(19) Condensing t>.P =
2
: d~?~-. (~)' • [ Oi0115,zo' ~ + 1 + 0.03 H J
Notes:
1. NR..- = 20,000(D,/D/1) 0 "
2 .. G = W.pd(Ap,,)
3. Surface-condition factor (~') for copper and steel= LO; for stainless steel= 1.7; for pol.ished surfaces= 2.5.

MA'20~EERING
for Rating Spiral-Plate Heat Exchangers-Table I
:o-:"umerical Physical Work MecHanical
Factor Property Factor Factor Design Factor

:..T,
·'II
~
= 20.6 X ,.....
z•·•"M•·••• X
W... (T;,-TL)
flT 11
X
d,
LH•·•
(See Note 11
)

:,, = 19.6 X
W ... (T"-T,,)
X
d, (See Note 1)
. ,. flT11 LH•·•
-1 ..

.! 77,
X
M'''(z,)•·" X W 2' 3 (T 11 -TL} X
d, (See Note 1)
=32.6 s"'' (,z.p.u flT 11 LH"i7•
·II

= 3.8 X
M''"Z'', X
W'',A
X
1
cs• ll.T• £-I•H
M''"Zl'11 W• 11 (T .. -Td 1
~ 1.18 X 8 .,. X X H•t•L•t•
ll.T~r

= 167 X
z•·•4•M•·"' X
W0·'(TH-TL) X
d,
J
8 ..... ll.T. HL•·•
W•·•(TH-TL) d,
~

•• 11
= 158 X
ll.T11
X
H£0·"
.·r
·;..!_ = 16.1 z•l•M•ts
- -- X
W'' A3
X
1
X L•t3H•r•
C8 2 ll.T.
..,.'" M•··•z•·•a•·'" Pt·o.r w···A d,"·'I'
-~
... r ..
= 0.619 X cs•·••• P"···
X
ll.T11
X
L•·•H•·•
(See Notes 2 and 3)

500
c X
W~TH-Td X
p
X
.l. k, ATM 1Ii
:.T,. = 278 1 WA _.1?._
x· X X
LH
J.T II k.. ll.T11

J.T, = 6,000 X
c X
W(Tit-Td X
1
J.T,. h. flT11 LH
~~: = 3,333 1 WA 1
X X X
h ll.T11 LH

(See Note 1)

(See Note 1:)

CHEMICAL ENGINEERING/MAY 4,.1970


2030368838
1
SPIRAL·Pl.ATE.. EXCHANGERS •

for sheU.and~tube heat exchangers (which were dis- is lrnown, a pseudomolecular weight may be used:
cussed oy Lord, Minton and Slusser&).
M -= 0.636 (c/k)l~
Primarily; the method combines into one relation-
ship• the classical' empirical equations for fihn, heat- In what follows, each of tHe equations in Table I'
transfer coefficients with• heat'-ballmce equations and i~ review~d, and the conditions in· which each equa-
with correlations tHat describe tHe geometry of the tion apphes, as well as its limitations, are given 1
heat exc~ger. The resulting .overall; equation• is Jn, several' cases, numerical factors are inserted or
recast into three separate groups. that contain• factors appr?xim~tions made, so as to adapt the empirlcal
relating to the physical properties of the fluid, the relationshtps to the. design of spiral-plate exchangers.
performance or duty of the exchanger, and the Such modifications have been• made to increase the
mechanical design or arrangement of the heat-transfer· accuracy, to simplify, or to Broaden the use of the
~ethod. Rather than by any simplifying approxima-
surface. These groups are then multiplied tbgether'
with• a numerical factor to obtain a product that is tions,. the accuracy of the method is limited by. that
equal: to' the fraction of the total driving force-or with which fouling factors, fluid properties and fab-
rication tolerances can be predicted.
log mean temperature difference (b.Tll or LMTD)-
that is dissipated across each element of resistance
in the. heat-How path1 Eq:uations tor: Heat; Transfer-Spiral Flow
When the sum of the products for the individual
resistance equa15 1, the trial design may be assumed
. Eq; (1):.-No Phase Change (Liquid), NR.. > Na •.--
1~ for. liquids with Reynolds numbers greater than
to be satisfactory for heat: transfer. The physical
the critical Reynolds number. Because the term
significance is that the sum of the temperature drops.
(1 + 3.54 D,IDH) is not constant for any given
across each· resistance is equal to the total available
heat, exchanger, a weighted average of 1.11 has oeen
t!.Tll· The pressure. drops for both' fluid~flow paths
used for• this method. If a design is selected with
must be checked: to ensure that: both are within
a different value, the numerical factor can be. adjusted
acceptable limits .. Usually, several trials are necessary
to reflect the new value.
to get a satisfactbry balance between heat transfer
Eq. (2):..-No Phase Change ~Gas), N 11 , > NR.rc-is
and pressure drop.
for gases with Reynolds numbers greater than the
Table I summarizes the equations used with the
critical ReynoiCis number;. Because tlie Prandtl number
method for heat transfer and: pressure drop •. The
of common• gases is appromately eq)Ja) to 0178: and
columns on the left list the conditions to which each
the viscosity enters only as l-'o.2, the relationship of
equation applies, and the second columns. gives the
physical' properties for gases is essentially a constant.
standard forms of the correlations for .6hn coefficients
This constant, when combined with the numerical
that are found in texts. The remaining columns in
coefficient in Eq. (I) to eliminate the physical prop.
Table I: tabulate the numericaL physical property,
erty factors for gases, results ih Eq. ( 2). As in Eq. (l ).,
work and mechanical design factors-all of which
the term (•1 + 3.54 D,/D'H) has been taken• ·as l.L
together. form tlie recast dimensional equation. 1'he
Eq. (3)-No Phase Change (,Liquid), N 11 , < N 11 , . -
product of these factors gives. the fraction of total
is for liquids in laminar Bow, at moderate ~T and
temperature drop' or driving force ( tJ. T1/b.T11 ) across
with' large kinematic viscosity (p.Lfp). The accuracy
the. resistance.
of the correlation, decreases as the operating conditions
As stated, the sum of t!.Thl t!.T11 (the hot-fluid
or the geometry of, the heat-transfer surface are
factor), tJ.T./tJ.TM (the cold-fluid factor)', b.T,/b.TJI.
changed tQ increase the effect of natural convection.
(the fouling factor), and AT..,/ti.T11 (the plate factor)
For a spiral plate:n
determines the adequacy of: heat transfer. Any com-
binations of b.T1/ b.T11 may be used, as long as the (D/L)1 11 = [12 112 D,j(DHd,)"•J"' = 2"' (d,/dn)•"
orientation specified: by the equation matches that The value of ( d,/d;, )1'6 varies from 0.4 to 0;6. A value
of the exchanger's flowpath .. of o,s for (d.ldH) 1' 8 has been used for this method.
The units in tHe pressure-drop eq1.1ations are con-
sistent with those used for heat transfer. Pressure drop Heat Tramsfer Equations-Spirator Axial Flow
is calculated directly in psi.
Eq. (4}-Cond.ensing Vapor,. Vertical, NR.. < 2,100
Approximations and Assumptions -is for film condensation of vapors on a vertical
plate with a terminal Reynolds number (41J'/~) of·
For many organic liquids, thermal conductivity less than' 2,l00. Condensate loading (or) for veftical
data are either· not available or difficult to obtain. plates is II' = W/2L. For Reynolds numbers above
JSecause molecular weights ('M) are known, the 2,100,. or fbr high Ptandtl numbers, the equation
Weber equation, which, follows,. yields thermal con- should be • adjusted by means of the Dukler plot,
ductivities. whose accuracies are quite satisfactory as discussed by Lord, Minton, andi Slusser.s To use
for most design purposes: · · Eq. ( 4)' most conveniently, the constant in it should
be multiplied by the ratio of the value obtained by
k - 0.86 (q#'/M"') the Nusselt equation to the Dukler plot.
u; on the other hand, the thermal conductivity 1'he preceding only applies to the condensation
of condensable vapors. Noncondensable gases in, the Eq. (8)-CondenMg Vapor,. HorU:ontal, Na. <
vapor decrease the &1m coefficient, the reduction 2,100-is for &1m condensation on spiral plates ar-
depending on the relative sizes a£ the gas-cooling ranged for horizontal axial flow witli a terminal
load and the total cooling and condensing duty. Reynolds number a£ less than 2,100. For a spiral
(A method for analyzing condensing in the presence plate, eondensate loading (r) depends on the length
of noncondensable g~~Ses is discussed by Lord, Minton of the plate and spacing between adjacent plates.
and Slusser.~} For any given' plate length and channel spacing, the
Eq .. (5)-Condensate Subcooling, Vertical,. Na. < heat-transfer area for each' 360-deg. winding of the
2,100-is fbr laminar films flowing in layer form down spiral fucreases with the diameter of, the spiral. The
vertical plates. ThiS equation is used when, the. con- number of revolutions affects the eondensate load-
densate from' a vertical condenser is tb be cooled ing in two ways: ( 1) the heat-transfer area changes,.
below the bubble point. In, such cases, it is con- resulting in' more condensate being formed in the
venient to treat the condenser-subcooler as two outer spirals; and (2) the effective length over which
separate heat exchangers-the first operating only as the condensate is formed is.determiiled by the number
a condenser, (no subcooling), and the second as a of revolutions and the plate width. 'Ilhe. equations
liquid cooler only. Fig. 5 shows the assumptions that presented depend: on a value for the effective number
must be made to determine the height of each section, of spirals of: L/7. Therefore,. the eondensate load-
so as to calculate intermediate temperatures that will ing is given by:.
permit in, fum the calculation of the LMTID. · r - W (1,000) 7 (12)/4HL- 21,000 W/HL
Eq. ( 4) is used in combination with appropriate This equation can be corrected if a design is. obtained
expressions for other resistances to heat transfer, tb with a significantly dilferent condensate loading.
calirulate the height of the subcooling section. In tlle It does not include allowances for turbulence due
case of the subcooling section only (See Fig. 5), the to vapor-liquid sHearing or splashing of, the con-
arithmetic mean temperature · difference,, [ ( T hm - densate. At high condensate loadings, the liquid
T..,.) + CThL - T.L)]/2, of the two fluids should condensate on the bottom of the spiral channels may
be used instead of the log mean temperature dif- blanket part of the exchanger,'s effective heat-transfer
ference .. surface.
Eq. (9)-Nucleate Boiling, Vertical-is for nucleate
Equations for Heat Transfer-Axial Flow boiling on vertical plates. In a rigorous analysis of
a thermosyphon reboiler, the calculation of heat
Eq. (6)-No Phase Change (Liquid)l NR., > 10;000 transfer is combined with the hydrodynamics of the
-is for liquids. with Reynoltls numbers greater than system to determine the circulating rate through the
Hl,OOO;. reboiler. How.ever, for most design purposes, tliis
Eq. (7)-No Phase Change (Gas),. NR., > 10,000- calculation is not necessary. For atmospheric pres-
is for. gases with Reynolds numbero greater than sure and higher, the assumption, of nucleate boiling
10,000 .. Again, because the physical property factor over the full height of the plate gives. satisfactory
for common, gases is essentially a constant, thiS con- results. The assumption of nucleate boiling over the
stant is combined with the numerical' factor in entire height of the plate in. vacuum service produces
Eq. (:6) to get Eq, (7). overly optimistic results. (The mechanism of thermo-

Condensing
zone

stiBCOOUNG·ZONE calculations
depend on arittlmetic·mean tem·
perature difference of, the tWo
fluids instead of log·mean tem·
perature differenoes-Fig. 5

CHEMICAL ENGINEERING/MAY 4, 1970


2030368840
SPIRAL·Pl.ATE EXCHANGERS • • •

syphon reboilers has been already discussed by Lord,


Minton and Slt1sser.s. ')
Nomenclature
A surface condition factor, I, appears. in the empiri·
cal correlations for boiling coefficients. This. is a A Heat-transfer area, sq. ft.
B Filln thickness (:0J00187, z r/ g, r) 111,.ft.
measure of, the number of nucleation sites for, bubble c Core dia., in.
formation on the heated surface. The equations for c Specific liea.t, l3tu./ (lb.) ("F.)
t!.Tt/tl.TII contaim,I' (the reciprocal of I), which Has D. Equivalent dia., ft.
values of 1.0 for copper and steel, 1.7 for stainless D. Helix or spi.ral dia., R
steel or chrome.nickel alloys, and 2.5 for polished D. Exchanger outside dia.,in ..
d, Channel spacing, in.
surfaces. I Fanning friction factor, dimensionless
G Mass veloeity,lb./(hr.H!Iq. ft~)
Equations for Heat Transfer-Plate g. Gravitational I constant, ft,./. (hr.)• (4.18 x
1:0")
H Channel plate wi.dtli, in.
Eq. ~10) and (llrHeat Transfer Through the h Film coefficient of heat t:ransfer.,. Btu./
Plate-are for calculating the plate factor. The inte- (hr.) (sq. ft.) (•F.)
grated form of the Fourier equation is QlfJ =
(k..,A k Thermal conductiVity, Btu./{hr.) (sq •. ft.)
tl.'Pw)/X, with X the plate thickness. Expressed in (•F;fft.)
the form of a heat-transfer coefficient; hw =
12k..,/p. L
M
Plate length, ft.
Molecular weight, dimensionless
Eq. (10) is used whenever sensible heat transfer p Pressure, psia.
i.'i involved for either fluid. Eq. (H) is usedi when p Plate thickness; in.
there is latent heat transfer for each fluidl t:J' Pressure drop,.psi.
Q Heat transferred, Btu.
s Specific gravity (referred to water at
Equations for Heat Transfer-Fouling 20 C.)
Logarithmic mean temperature difference
Eq. (12) and (13)-Fouling-is for conduction of, ·· (LM'IlD), •c.
heati through scale or solids deposits.. Fouling co• u Overalll heat-transfer coefficient, Btu./.
(hr.) (sq. ft.) eF.)·
efficients are selected by the designer,. based upon w Flowrate, (lb./hr.) /1,000
his experience. Fouling coefficients of 1,000 to 500 r Condensate loading, lb./. (hr.) (ft.)
(fouling factors ofi 0.001 to 0.002) normally require z Viscosity, op.
6 Time, hr.
exchangers 10 to' 30% larger than for clean service;
The selection of, a fouling factor is arbitrary be- ' A Heat of vaporization, Btu./lb.
I
Viscosity, lb./.(hr.) (ft.)
cause there is usually insufficient data for accurately I ~£ Liquidldensity, ll:L/cu1ft.
assessing the degree of fouling that should be assumed P• Vapor density, lb.f.cu.ft.
for a (itiven design. Generally, fouling for a spiral- I:, I:' Surface condition factor, dimensionli!ss
plate exchanger' is considerably less than for shell- IT Surface tension, dynes/em.
and-tube exchangers. Because fouling varies with Subscripts
material. velocities and temperature, the extent to 11 Built fluid properties
which this influences design depends on operating c Cold stream
conditions and, to a great degree, the design· itself. I Film fluid properties
Eq. (12) iS used for sensible heat transfer for . H High temperature
either fluid, and Eq .. ( 13) when latent heat is trans- h Hot stream
L .IJ.ow temperature
ferred' on both sides ofi the. plate; m Median temperature (1see Fig. 5)
s Scale or fouling material
Equations for; Pressure Dro~Spiral Flow w Wall, plate material
Dimensionless Groups
Eq .. (U)-No PhDse Change Nth > N a ..-iS based
on equations proposed by Sander.4 • 12 'Ilerm A in
Sander's equation €an be closely approximated by.
N...
N ••
Nr.r
Reynolds number
Critical Reynolds number
Prandtl number
the value of 28/(d. + 0.125). Term B in Sander's
equation accounts for the spacer studs. The factor
1.5 assumes 18 studs/sq. ft. and a stud dia. of 5/16 in.
Eq. (15)-No Phase Change 100 < Na, < Na,.-
again is based upon the equation proposed by Sander. little effect· on the pressure drop,. and any such effect
For, this flow regime, the. term A can be closely is included' in the Sander equation.
approximated' by the 'lalue of 103.5/(d, + 0.125). Eq; (17rCondensing-is for calculating the pres-
As in Eq .. (14h the factor of 1.5 accounts for the sure drop for· condensing vapors and is identical to
spacer studs. that for no phase change, except for a facto11 of
Eq. (16)-No Phase Ch4nge N 2 , < JOO:..aJso is 0.5 used with the condensing equation. For total
based on the Sander eq1.1ations. For this flow regime,, condensers, the weight rate of flow used in the
term A can be closely approximated by the value of calculation should be the inlet flowrate. Because the
2,170 d 1I.'f5. For this flow regime, the studs have average Bow for partial condensers is greater than

MAY 4,.1970/CHEMICAL ENGINEERING

2030368841
far total condensers,. the multip]ymg factor should Hot side Na. • (10,(!)()() X 6.225/(24 X 3.35) • 714
be 0.7 instead of 0.5. Because the estimation of the CoiC:I aide Na, • (lOiOOO X 5.925)/(24 X 8) • 309
pressure drop for condensing vapors is not clear-cut,
Because the ftuids willi be in· lamimar flow, spiral
the equation should be used only to approximate
flow is selected for the heat exchanger design. From
the. pressure drop, so as to prevent the design of Table I, the appropriate expressions for rating are:
exchangers with, excessive. pressure losses.
Eq. (3)' for both fluids, Eq. (10). for the plate,
Eq, (12) for fouling and Eq. (15) far pressure drop.
Equations for Pressure Drop--Axiali Flow

Eq .. (:18}-No Phase Change N., > 10,000-is an Heat-Transfer Calculations


expression• of the Fanning equation for noncompressi~
Now; substitute values:
ble fluids,.in which the friction factOr f. in, the Fanning
Hot side, Eq. (3):
equation = 0.046/N.,u. The equation has been
revised to• account for pressure lbsses in the inlet
and outlet nozzles, and the irnlet and outlet heads.
~T.!..
aTJI -
200 4
· '~].
32.6[ 0:843'.. , X
The equation also, includes the correction for the 6
spacer studs in the flow. eliannels. [ ·~5~ 80 J[ 241~·~~2.5]
Eq. (19}-Conden.ring-again is identical to, that • 32.6 X3.775 X 4.967 X 0.001387, • 0.848
for no phase change, except for a factor of 0.5. Again.
Colli side, Eq. (3):
for partial condensers,. a value of 0.7 should be used
instead of 0.5. For condensing pressure drop, only aT. _ ·[ 200.4 .•
1 111
][
111
5.925 X9C:U ]'X
approximate results. should: be expected, which them- t:.TM 32.6 0.843'... . 54.5
selves should be used only to prevent designs that
would result in excessive pressure losses. 0.375
[ 24111 X 32.5,
J
For overhead condensers, the pressure drop in
= 32.6 X 3.775 X 5.431 X 0.001387 • 0.927
the center tube must be added to the pressure drop
calculated from Eq. (19). Foulin.g, Eq. ( 12):

t:.T, _ 6 OOO f. 0J66 J [ 5.925 X 90.4 J [ . I J


SAMPLE CALCUlATIONS t.TJI - , L
1,000 54.5 32.5 X 24
• 6,000 X 0;00066 X 9.828 X 0.001282 • 0.050
This example applies the rating method to the
Flate,. Eq. (10):
design of a liquid~Jiquid spiral-plate heat exchanger
under the following conditions: E'· .., 500 [~'66-J f 5.925 X 9CMJ [ O.I25 ]
t:.'/111 10 •L54.5 32.5 X 24
ConditiODs Hot Side Coldi Side = 500 X 01066 X 9.828 X 0.0001603 • 0.052
Flowrate, lb./hr................. 6,225 5,,925
Inlet temperature, •c.. . . . . . . . . . . 200 60
Outlet temperature, •c.. . . . . . . . ... I20 I 50.4
V:iscoeity, cp. . . . . . . . . . . . . . . . . . .. .. 3. 35' . 8
Specific heat, Btu./lb.;oF.... ... . ... 0.71 0.66
Molecular, weight................. 200.4 200.4
Specific ~Vfovity............... ... 0 . 843 liL843 Some Spi,r,ai-Piate Exchanger; Standar;ds-Table Ill
Allowable yressure drop, psi.. . . . . . I I'
Material o construction ........... stainless steel (k - Ul) Plate Outside 018., Core
(Z,/z.)u•: . . . . . . .. . . . . . . . . . . . . . . I I Widths,, lin. Maximum, .lin. Dia.,ln•.
4 32 8
6 32 8
Preliminary Calculations 12 32 8
Heat transferred =
61225 X (200-120) X 1.8 X 12
18
58 l2
0,11: =
636,400 Btu./hr.
18 58
32
12
8

t.T11 (or LMTD) • (~ - 49.4)/ln(60/4U) • 54.5 C. 24 32 8


For a flrst trial, the approximate surface can be 24 58 12
calculated' using an assumed overall heat-transfer 30 58 12
coefficient, U, of 50 :Btu./(hr.) (sq.. ft.) (°F.): 36 58 12
48 58 12
A - 636,400/(50 X I.8 X 54.5) = I30 sq. ft. 6C' 58 12
Because this is a small exchanger, a plate width 72 58 12
of 24 in. is assumed. Therefore, L =
i30/ (2 X 2). = ahannel spacings, in.: 3/16 (12 in. maximum width.),
32~5 ft. A channel spacing of % in. for both. fluids 114 (48 ;n. maximum width), 5/16, %. %. %. 3f4
is also assumed. The Reynolds number for spiral flow and: l.
can be calculated from the expressiont Plate thiCknesses: stainless steel) 14-3 U.S. gage; car·
bon steel, ~. 3/16, 114 and 5/16 in.
N •• "' IO,OOO (JV/HZ)
Therefore:

CHEMICAL ENGINEERING/MAY 4, 1970


2o3oasss42
SPIRAL·PLATE EXCHANGERS

Sum of Products (SOP): The diameter of the outside spiral can now be
SOP = 0.848 + 0.927 + 0.050 + 0.052 = 1.877 calculated with Table II and the following equation:
Because S0P is greater than 1, the assumed: heat Ds = [15.36 X L (d,. -t+ d;, + 2p) + Q2jtl•
Ds = 115,36 (4L8) [0,25 + 0:25 + 2 (0.125)) + 81f112
_xchanger is inadequate. The smface • area must Ds-= 23.4 in.
be enlarged by increasing the plate width or the For a spiral-plate exchanger, the best design• is
plate .length. Because, in all the equations 1 L applles often• that• in. which• the outside diameter approximately
directly, the follbwing new length is adopted: equals the plate width.
1.877 X 32.5 - 61i ft. Design summary:
Plate width.. . . . . .. . .. .. .. . 24 in.
Plate length.............. . . . 41.8 ft
Pr,essur;e-Drop Cal.culations Channel spacing............ 1/4 in .. (both sides)
Spiral diameter.. .. . . . .. . . . . 23.4 in ..
Hot side, Eq. (15): Heat-transfer area... . . . . . . 167 sq. ft.
Hot-side pressure drop ..... 0.607 psi.
Cold~side pressure drop ..... 0. 861 psi.
4 p .. [ 0.001 X.61 ] [-6·~] X U... ... . . . . . . ... . . . . . . ... . . . 38.8 Btu./(hr.)(sq.ft.)("F.)•
0;843 0.375 X 24

[
1.035 X 3.35112 X 1 X 24112
(0.375+ 0.125) 6.2251 12 + 1.5 + 6f
16 J •
t:.P ·- 0.07236 X 0.6917 X 9.202 =- 0J461i psi. Acknowledgements
Cold side, Eq .. (,15):
The author thanks American Heat Reclaiming Corp.
t:.P .. [1).(101 X 61 J[--5.9~] X
for. providing figures and for permission to use certain
0.843 0.375 X 24 design.standards. He is also grateful to the Union Car-
bide Corp .. for permission to publish this article.
f 1.035 X8 X 1 X 24
11
:
112
16] ,
ti (0.375 + €1.125) 5.925112 + LS+ 61
References
t:.P = 0.07236 X 0.6583 X 13.55 = 0.645 psi.
H Baird, M. H. I.. MoCrae, W .. Rumford. F .. and Sle--.
Because the pressure drop is less than the allowal:lle; C. G. M.. Some Consldera.tlon" on Heat Tm.naofer In
SpLI"al Plate Heat Exchangers, Chem. Eng. Science., 7,
the spacing can• be decreased. For the second trial, 1 and 2, 1957, p. 112.
2. BLasius, H.. Dae .\hnlichkeit.sgesets bel Rlebunpvor-
¥4 in. spacing for botH channels is adoptedl gangzen in Flussigkeiten, Fonol&uug81&e/t. Ul, 1913.
3. Colbu~n,.A. P .. A Method of CoJ:TelaUng Forced•ConW~e­
Because the Heat-transfer· equation for every factor tlon Heat TTansfer Da.ta and e. Comparison With Fluid
except the plate varies directly witH d,, a new SOP· F'rlot.lon, A.ICI&F: TMM., !9, 1'933, p. 1174.
4: HargiS, A. M ... Beok.mann, A. T. and Lola.oonoa., JL J.,.
can be calculated~ Applica.tion6 of Spiral' Plate Heat: Ex<lhangers, Chem.
Eng. Proyr .. July 1967; p .. 62.
t:.Tl/llTM "" 0.848 (0.25/0.375) = 0.565 5. "HeliHow Confers and Heaters," Bull. SBG; Gl"&h&m
Mfg. Co•. Grea.t .:\leek, N.Y.
tJ.T;/tJ.7'M = 0.927 (0;25/0.375) = 0.618 6. Ito, H .. F'rlotion• F'act<>n~ for Turbulent Flow ln. Curved
t:.T,/ATII = 0.052 (0;25/0.375) = 0.035 Pipes. Tran8. AS&fE., 81, 2;, 1959,. p .. 123.
tJ.T,./tJ.TM = 0.050 7. La.mb,. B. R., The Rosenbl.ad Spiral Heat !Exch&nger,
Trana. Inst. Cllem. Engr3. {IIJ.Ondon), June 196Z, p. A101.
SOP - 0;565 + 0.618 + 0.050 + 0.052 == 1.285 8; Lord, R. C., Min-ton. P. E. <and Slusser, R. P., Dettlgn
Pa.l'ameters for Condensers and Reboilers, CJ1em. Eng.,
L = 1.285 X 32.5 = 41.8 ft. Mar.. 2'3, 1970, p. 127.
A = 41.8 X 2 X 2 = 167 sq. ft. 9 .. Loro, R. C:, Min·ton, P. E. and Slusser, R. P .. Dealgn
o! Heat Exchangers, Ghem. Eng., Jan, 26, 19-'70, p. H.
10. Noble, M .. A ... Kamlanl, J. S. <and McKetta, JL J., H-.t
The new pressure drop becomes: 'l'ransfer in Spiral Colla .. Petr. Eng., Apr. 1952, p. 723.
Hot side: 11. PerTy, J! H .• Ed .. "OHemlcal Englneera· Handbook."' 4th
ed., McGraw-Hill, New York. 1963, 10, p. 24:
12. Sander·, J.. ( unpublf.shed). A. B. RoaenbladAI. Pa.tenter,
llP- [' 0.001 X41.8
0.843
J[-·6·~~~-]
0.25 X 24
X 13.
Stockholm .. Sweden. 1955.
"Spiral Heat Exchangers," Bull. S.A. 1UO I-ff HRSII,
Amerloan Hea.t Reclaiming Corp., New York.
14. Tangn, N. N. and Ja:raraman, R., Hea.t Transfer on e.
Spiral Pla.te. Hea.t Exchanger,, Tran~. In1t. Chem. Engr11.
1.035 X 3.35112 X 1 X 24 112 16 ] (London), 40, 3, 1962, p, 161.
[ --M75 X 6.225112 ·-- + ·1.5 + 411:8- 15. "Thermal Handbook," AI~·La.va1/De!J.aval Group,
Sweden, 1969.
16. White, C. M., Streamline Flow Through Curved Pipes,
tJ.P - 0;04958 X 1.037 X 11.80 = 0.607 psi. Proceedhtga Roval Soc. (Londonh Serlea A. 1Z3, 1929,
p. 645.
Colo· side:

tJ.P _ [· o.oo~_4h8~]( 5.925_.] x Meet the Author


0.843 ' 0.25 X 24
Paul E. Mlnfon is a project
engine~r in t~e ~ngineering
D.035 X 8 112 X 1' X 24 112
1

16 .] department at Union Carbide


[ --o37sx 5.92511··- -- + 1. 5 + ·us Corp.'s Technical Center (P 0;
Box 8361, So. Charleston.
W. Va. 25303), where he is a
AP = 0.04958 X 0.9875•X 17.59 = 0.8611 part· of the heat·transfO!r tech·
nology group. A graduate In
chem•cal engineering with a
The pressure drops are less than the maximum B.S. degree from the Missouri
allowable. The plate spacing cannot be less than School of Mines and Metal·
lurgy, he is a member of
¥4 in. for a 24!.in. plate width; decreasing the width AIChE.
would result: in a higher than allowable pressure drop.
Therefore, the design is accept:able.

MAY 4, 1970/«HEMICAL ENGINEERING

2030368843.

Potrebbero piacerti anche