Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
A Project
MASTER OF SCIENCE
in
by
FALL
2016
© 2016
ii
TESTING PROCEDURES FOR RELAYING FUNCTIONS
A Project
by
Approved by:
____________________________
Date
____________________________
Date
iii
Student: Aaron Snelson Wernecke
I certify that this student has met the requirements for format contained in the University
format manual, and that this project is suitable for shelving in the Library and credit is to
iv
Abstract
of
by
Relaying elements from different manufacturers use different concepts and algorithms to
produce the same results. A significant variety of commonly used relaying elements, that
are used for protection of power system elements, exist in Electro Mechanical (EM),
performing commonly used protective functions offered by EM, SS, and modern MP
routines for commonly used relaying elements, using modern test equipment and
equipment and associated software capable of producing current and voltage signals of
various magnitudes and frequencies necessary for testing relaying elements will be used
v
Various IEEE papers written by professionals in the field of relaying applications where
utilized. Also the functionality of the Omicron Test Universe software was used to
demonstrate the capabilities of various test set equipment available to perform the
The approach presented in the following analysis for testing relay functions can be
utilized as a guideline for development of automated test routines for various types of MP
based relaying elements offered by the industry independent of their make, model, or
manufacturer. Non typical relaying element and concepts that may exist in relays made
for special functions are excluded in the scope of this project report.
_______________________
Date
vi
ACKNOWLEDGEMENTS
I would like to thank all of the professors throughout my education that helped me to
Svetlana Podkolzina and Dorothy Hawkes helped me through the confusing maze of
Calculus and Differential Equations. In Physics Mr. Johnston and Melanie Lutz where
two of the best teachers you could ask for as far as explaining all the complicated
Russ Tatro, Turan Gonen, Mohammad Vaziri and Mahyar Zarghami all helped teach the
Without their assistance I would not have become the engineer that I am today. I owe
vii
TABLE OF CONTENTS
Page
Chapter
1. INTRODUCTION ….……………………………………………………………. 1
References ................................................................................................................... 32
viii
LIST OF TABLES
Tables Page
ix
LIST OF FIGURES
Figures Page
x
1
Chapter 1
INTRODUCTION
Collaboration between academia and industry has resulted in a new state of the art relay
testing laboratory that has been created at California State, Sacramento (CSUS). This
classes related to power system protection as well as a research and training center for
graduate students and members of industry. The laboratory utilizes programmable test
equipment that is capable of producing current and voltage signals necessary for testing
different types of EM and MP based relays that are commonly used by the industry. Lab
equipment is capable of testing a large variety of relaying functions, also known as relay
Protective relays have long been used as integral elements for protection of various
power system components such as: lines, transformers, motors, generators, reactors,
capacitors, and others. The main function of a relay is to detect abnormal operating
conditions in the system or the component that it is monitoring and initiate a trip (or
alarm) signal to its associated breaker (or annunciator) to de-energize the component (or
Earlier generations of relays were EM types. While these relays are extremely reliable
and are still in use today, they have limited functionality as they are typically designed to
2
perform a single task. Also these relays are designed to only monitor one of the phases of
a multiphase system. Thus, for a 3-phase system three separate relays would have to be
The next generation of relays were electronic types, also known as Solid State (SS)
relays. In these relays the mechanical functions were replaced with electronic circuitry,
eliminating the problems of wear and tear. SS relays were still limited in their
functionality as they were usually designed for one or maybe two functions as well as
typically only being able to monitor a single phase, limiting the usefulness of their
design.
The modern generations of relays were Micro-Processor (MP) types also known as
numerical or digital relays. This class of relay is capable of performing multiple and new
include: multiple relaying elements for all 3 phases, “Oscillography and event recording,
functions. [1]
computerized test equipment known as the Omicron® CMC-356 test sets for relay
testing. The test set is capable of producing currents and voltages at varying magnitudes,
3
phase
angles, and frequencies. This gives the student or researcher the ability to produce any
signals that are necessary to test various types of EM, SS, or MP based relaying functions
This is important since the industry is still in a transitional mode in utilization of various
types of modern relays in their facilities. While MP relays are becoming more dominant,
EM and solid state relays can still be frequently encountered due to situations where “For
retrofit, it is easiest to replace existing relays with identical types. None of the existing
equipment has to be adapted and the personnel can still deal with the known equipment.”
[2]
The following sections of this project report will discuss developing a standardized
approach for testing various commonly used relay elements that exist in EM, SS and MP
relays. These relay elements are the fundamental units that are employed in practically all
relay protection schemes. These include current elements, voltage elements, frequency
Chapter 2 will cover relay tolerances and testing equipment. Chapter 3 will cover current
elements [3]. Voltage and frequency elements are discussed in Chapter 4 [4, 5].
Impedance and differential elements are handled in Chapter 5 [6]. The conclusion is
presented in Chapter 6.
4
Table 1 refers to the commonly used relay elements examined in this project report. The
table shows whether the elements are capable of forward/reverse directionality as well as
Chapter 2
The main objectives for testing relays are: to ensure that they are functioning correctly
for the input signals and to determine if the results of the procedure fall within acceptable
tolerances. The tolerances are the limits in the variations of input signals that the tested
element must operate on to be within the specifications given by the manufacturer of the
relay.
In testing relaying elements, tolerances usually fall within two classes. The first class of
tolerances are for the pickup values, and the second class of tolerances relate to the
timing of the relay elements. For testing pickup values, the tolerances can usually be
given in current, voltage, frequency, ohms, and power (real/reactive), although other
variables may be encountered. When testing the timing of relay elements the tolerance
can be expressed in terms of seconds or cycles since both are measurements of time. But
when using cycles the timing in terms of seconds depends on the frequency of the system
being tested.
Watt/Var elements), may be specified in terms of Ohms, Watts, and Vars, as well as in
terms of current and voltage. This is because the element is operating either based on the
6
ratio of current and voltage (such as in distance elements) or based on their product (such
as in Watt/Var elements). Note that the tolerance is the important factor, since it refers to
the variable that operates the relay which may be any of the variables of current, voltage,
Some relay elements may also have a setting that is given in per-unit (p.u.) values. If such
cases, it will be necessary to determine how the p.u. value is being calculated. Thus the
necessary current or voltage values can be injected into the relay based on the conversion
from secondary values to p.u. values. This also means the tolerance of such an element
will be given in percentage of the p.u. value that the element is set to.
For timing of elements, seconds and cycles can typically be converted from one to the
other based on the frequency of the system (60 Hz or 50 Hz). An exception arises when
testing frequency elements. Frequency elements are set to trip for abnormal conditions
seconds and cycles must be based on the element’s frequency set point in order to
tolerance independent of the value being tested), and a percentage (which is a plus/minus
value depending on the setting of the element). Also note that the tolerances in timing of
7
elements can be a combination of seconds and cycles (where the offset is in terms of
additional calculations to determine what the proper deviances from the nominal value
Modern day testing equipment typically involves utilizing a test set, as well as testing
software that is run on a computer that interfaces with the test set. When testing MP
relays, the computer running the test set can also interface with the relay being tested to
The software that runs the test set can be programmed with multiple functions for
enhanced testing. In this report, the discussions will focus on utilization of the Omicron
CMC-356 test set and the Omicron Test Universe software package. The software
package is equipped with several modules that are useful for testing. These modules
include Ramping (R) and State Sequencer (STSQ) modules which are used for testing
pickup values and timing respectively. It also includes more specialized modules used for
testing time overcurrent, distance and differential elements among others. Test sets and
their associated software packages are also available from other manufacturers while the
A “Ramping” (R) module is used to ramp current, voltage, or frequency from a value
below the pickup setting of the relay element to a value above its setting. This determines
the actual (tested) magnitude of the input variable initiating the trip of the relay element.
The “overcurrent” module is specifically designed for testing the pickup and timing of
elements. The “State Sequencer” (STSQ) is a module that utilizes different “states” of
operation to determine timing. Thus a pre-fault state is created where the system would
be operating under normal steady state conditions. Then after a specified amount of time
the STSQ switches to a fault condition where the conditions of the test step into an
abnormal condition which would cause the relay to trip. Once the step into abnormal
conditions begins the test set starts a timer. This state continues until a “trip” signal
initiated by the relay is received by the test set to end the state. Using the STSQ module,
the test set is able to evaluate the time difference between the start of the abnormal
condition, and when the relay element initiates its “trip” command. .
For most testing purposes, such as overcurrent, over/under voltage or frequency, the R
function and the STSQ module are sufficient. For testing elements such as impedance or
power where ratio or multiplication of voltage and current is required, the test set has
been designed with the capability of holding either voltage or current at a constant value
to avoid measurement errors as one of the variables approaches zero. It should also be
noted that
9
the differential module of the test set is capable of comparing “Operate” and “Restraint”
quantities and evaluating the slope of the differential element’s characteristic curve.
10
Chapter 3
In the following section overcurrent elements will be discussed. This will include
instantaneous as well as inverse time elements, whether they are non-directional versus
directional in nature and if they operate on negative and zero sequence values. Over as
well as Under current elements in protective schemes can be present depending on the
desired application. The scope of this section is to only cover Overcurrent applications as
Overcurrent elements are the most commonly used form of protective function used by
elements. They can also be single (or three) phase, directional or non-directional.
current relative to a polarizing voltage or current. The element can assert based on
positive, negative, or zero sequence current values. Relay type (single/three phase),
actuating overcurrent relay. In this case only the pickup value of the relay needs to be
11
known. In order to test the pickup value, a “ramping” function that linearly increases the
current from a value well below the pickup value to one well above is utilized.
During testing, the test set will ramp the current up until a trip is initiated by the relay.
The exact value of the current for which the trip occurred is recorded as the pickup value
figure, ramp begins with an offset that holds for a specific length of time at the initial
value that the ramp is set at. The test set will then increment the amplitude of the
actuating signal (in this case current) in pre-determined steps. Once an increment in
amplitude is performed, a delay is implemented where the test set will hold the amplitude
at the specified level to see if a trip signal is received from the relay.
14.5
14.0 Expected Pickup Zone
13.5
13.0
Pickup at 14 Amps
12.5
Increment Delay
12.0
C 11.5
U
R
R 11.0
EN Offset
T
A
2.25
M
P 0.25 0.5 0.75 1.0 1.25 1.5 1.75 2.0
LI
T TIME (s)
U
D
E
Figure 1. Representation of a Ramping Function
12
If a trip signal is not received, then the test set will increment the amplitude to the next
level in the ramp and repeat the process. This is performed until a trip signal is received
from the relay at which point the final level of the amplitude of the signal will be
recorded as the pickup value and compared to the tolerance of the relay for acceptability.
When choosing the increment and delay variables shown in Figure 1, careful
consideration should be made to ensure that the step size in the ramp is smaller than the
tolerance of the element. If it is larger, then there is a possibility that the test set will skip
past the pickup value of the element and not sense the pickup until it has already ramped
to a level outside of the tolerance zone. Time delay should be selected so that it is long
enough for the element to have adequate time to initiate the trip signal and close (or open)
must also be applied along with the actuating current. The phase angles between the
actuating current and the polarizing signal (voltage or current) are compared to a per-set
angle known as the Maximum Torque Angle (MTA). The line perpendicular to the MTA,
known as the “zero torque line”, defines the boundary where the relay determines if the
commonly used connection type for directional phase overcurrent relays is the 90 degree
connection in which the polarizing voltage as compared to the actuating current at its
unity power factor positon at 90 degrees. (VBC vs. IA for A phase real)” [3]. This design
is to ensure existence of adequate polarizing voltage for the directional phase overcurrent
relay (to be able to respond as a back up to the ground relay) during a single phase to
ground fault. A directional ground overcurrent relay with a different concept will also
For testing a time-overcurrent element, the “overcurrent” module of the Omicron® test
set software known as “Test Universe” will be used. The overcurrent module can be
programmed for the time delays associated with various types of current vs time inverse
The inverse time curves are based on equations such as the one suggested by Equation
(1).
B D E
t = TD �A + M−C + (M−C)2 + (M−C)3 � (1)
Where M is the pickup value, TD is the time dial and A, B, C, D, and E are constants.
With proper curve, pickup value, and time dial as input, several points along the curve
can be tested. The module can also test based on negative or zero sequence currents as
needed. The easiest way to test for negative sequence element would be to inject ACB
currents on a relay designed to measure ABC values as positive sequence. For zero
sequence elements, all three phases can be set to the same angle to create zero sequence
15
current. Note that the pickup values for negative and/or zero sequence values may need to
be divided by 3 if the relay element uses 3I2 (or 3I0) as the pickup.
16
Chapter 4
characteristic like their current element counterparts. Normally, only instantaneous and
definite time elements are utilized. “Protective devices should operate as fast as possible
or fast time operations will have less undesirable effects as compared to inverse operating
time characteristics for voltage elements.” [4] Similar to current elements, voltage
elements can be based on positive, negative or zero sequence input values. They can also
Three phase voltage elements can take positive, negative or zero sequence quantities as
their pickup values. There are also elements that only take voltage magnitude of all three
phases independently regardless of their phase angles. In this case a voltage dip/rise in
any of the 3 phases below/above the pickup value and the tolerance of the element will
cause a trip.
For testing positive, negative and zero sequence voltage elements, the angles between the
three phases can be varied to create the proper sequence when compared to the pickup
17
value to initiate tripping. For example, to create negative sequence voltage the phase
angles between any two phases may be swapped. For zero sequence the phase angles of
The frequency of the voltage input signal is varied to determine pickup and timing values
function, where in this case the frequency, rather than magnitude, of voltage is varied.
For the timing of a frequency element the test can be a bit more complicated. Some MP
relays determine the timing of a frequency element in terms of seconds, while others
resolve the time delay in terms of cycles. If the timing is in terms of cycles then the
period of the test frequency needs to be taken into account to determine the correct time
delay in seconds. According to Stringer, “There are two separate timing operations
occurring simultaneously--that of the relay and the one for the test set.” [5] “The test set
may provide a 58-Hz signal to the relay while it is timing at 60 Hz. Thus, the timing
results must be converted to the appropriate timing base for accurate analysis of the
results.” [5]
Hz with a time delay of 60 cycles. A STSQ module is used that starts with a voltage at
the
18
60 cycles
62 Hz
= 0.9677 seconds (2)
That is, the time delay is slightly less than 1 second, which is the time delay when the
system was operating at 60 Hz before the abnormal condition occurred. The opposite is
60 cycles
58 Hz
= 1.0345 seconds (3)
The difference between the time delay when the system is operating at 60 Hz and 62 Hz
(or 58 Hz) may seem minimal, because the time delay itself is relatively short in duration
at 60 cycles. If the time delay becomes larger, then the calculation error described above
becomes more significant. For example, if the over-frequency element in the above
example had a delay of 3600 cycles instead of 60 cycles, then the time delay in seconds
would become:
3600 cycles
62 Hz
= 58.0645 seconds (4)
Noting that the time delay would be 60 seconds when the operating frequency is 60 Hz.
This shows that the discrepancy between the measured time delay (based on a 60 Hz
system) increases as the time delay (measured in cycles) increases as the “testing
frequency” deviates from 60 Hz. This can lead to erroneous time delay measurements
when testing the timing delays of frequency elements. Similar errors can be encountered
19
when the testing frequency becomes lower than the nominal frequency of 60 Hz and long
time delays are employed. The solution is to convert the delay which is specified in
number of cycles into a delay in terms of seconds based on the testing frequency. With
the time delay converted into seconds, an accurate measurement of the delay of the
A solution is to convert the delay in terms of cycles into the one in terms of seconds
based on the test frequency as it deviates from the pickup value of the element. That way
Another complexity encountered when testing frequency elements is the delay between
detection of a faulted condition and the actual closure of output contact. This can depend
on the actual time when the test set initiates the frequency change to the relay. “The
zero crossing, or at the point on the waveform when the test is initiated” [4]. Also “The
timer is normally stopped upon the sensed operation of an external contact. Each test set
utilizes an input contact from the relay to stop its timer. The test set may require as much
Chapter 5
Impedance relay elements require both voltage and current inputs to measure impedance.
The impedance being measured by the relay is plotted on an impedance plane as shown
by Figure 3.
Forward Direction
(Zone 1 & 2) Zone 2
Line Angle
Zone 1 Reach
Zone 1
R (REAL Z)
Zone 3 Reach Zone 3
Reverse Direction
(Zone 3)
The points near the origin refer to small values of impedance, while points lying away
from the origin indicate larger values. Depending on the phase angle of the current as
21
compared to that of the voltage which is normally taken as the reference, the measured
impedance by the relay could be in the forward or reverse direction as shown by Figure 3.
There are two options for testing an impedance element. One is to hold the current
constant while varying the voltage. This is useful when measuring impedance values that
are close to the origin. As the voltage becomes increasingly small, the value of
Voltage V
Impedance = Current , or Z = I
(5)
The other option is to hold the voltage constant while varying the current which is better
Note that there are settable time delays for different impedance zones of protection, with
Zone 1 being instantaneous while Zones 2 & 3 have finite settable time delays. Also note
that for EM relays the speed of the relay depends on the location of the fault relative to
“For faults at the relay location, with operating currents greater than 50 Amperes the
relay will operate in 0.5 cycles on a 60 Hz basis.” [6] For faults between 85-90% of the
relay reach setting and at an operating current of 10 amperes the relay will operate in 2-3
cycles on a 60 Hz basis.” [6] “Below 10 amperes or between 90% and 100% of the relay
reach setting, the relay operating time is indeterminate.” [6] SS and MP based relays are
immune to these effects since their operations are independent of mechanical devices.
22
characteristic. Two variables, the “operate current” and “restraint current”, are plotted on
a graph and the operating zone falls above the characteristic line as shown in Figure 4.
The slope that defines the operation of the element is typically given as a percentage.
Thus for a slope of 25%, the equation of the characteristic line is given by Equation (3).
With the “trip” region above the characteristic line shown by Figure 4, the element will
operate for all values above its pickup and when Ioperate is greater than 25% of Irestraint .
The pickup value defines the minimum value Ioperate must attain for operation. To better
understand how the differential element functions, let’s assume that the Ioperate and
where I1 and I2 are defined as shown by Figure 5. For testing the pickup value of a
differential element, only one current input to the relay is necessary. For example if I��⃗1 (or
I���⃗2 ) is set to zero, then the ratio of the operate current to the restraint current will always
equal 1 (or 100%) which always places the element in the operating region. To test the
slope, using the facts given by Equation (7) & Equation (8) about operate and restraint
currents, we can start at a point where the two currents are 180° out of phase with each
other. Then we proceed with ramping the phase angles between the two currents from
being 180° out of phase with each other to being in phase with each other. Eventually a
point will be reached where the operate current rises above the characteristic line and into
Restraint Coil
Dashed
Arrows:
Normal i1 i2
Condition or i1 i2
Out of Zone
Fault Operating Coil
Bold Arrows:
In Zone Fault
Protected
Device
I1 I2
Note that Ioperate must always be above the pickup value. To explain the process assume
the pickup value is 0.3 pu, the slope is 25%, with the following restraint conditions.
Firstly, the slope can’t exceed 1 (or 100%). Secondly, the equation for the restraint
current is the same as presented in Equation (5). Finally, the magnitudes of I1 and I2
remain equal.
For values above pickup of .3 pu, such as Ioperate = 0.5 pu, Equation (3) shows that for the
25% slope, Irestraint = 2 pu. The next step is to divide the restraint current in half (1 pu) and
apply that as the magnitude of both I1 and I2 since they are equal in this example. By
ramping the phase angles between I1 and I2 as explained above the pickup is found to be:
25
|1∠0°+1∠151.045°| pu
|1∠0°|+|1∠151.045°| pu
= .25 pu (9)
The phase angle of 151.045° was found using simple geometric equations since the
With some relays like the SEL-311L, the slope characteristic described above is not
utilized. Instead, what is known as an “alpha plane” characteristic is used. When utilizing
a SEL-311L relay for differential protection, it should be realized that the relay is
specifically designed for line differential protection. The relays are only equipped with
the capability to monitor 3 current inputs from 3 Current Transformers (CTs) in a 3 Phase
minimum of 6 CTs are necessary (2 CTs per phase). To determine the differential current
for each phase it is necessary to compare 2 independent current signals from 2 separate
It is necessary to have two SEL-311L relays, each placed at one end a two-terminal
power transmission line to monitor and compare the line current in each phase at both
ends. For proper measurement of the differential current entering at one end leaving
from the other end of the line, it is necessary that the two SEL-311L relays are able to
schemes is a fiber-optic channel. It is also necessary for the test sets feeding the current
signals to the relays at each end to be synchronized with one another when performing
26
the test. This is necessary since both the magnitudes as well as the phase angles of the
current signals at each end must be compared with the same signals at the other end to
properly determine the differential value. If the test sets are not synchronized when the
test begins, there is the possibility of an unintentional phase difference between the
current signals generated by the test sets at each end. “The Line Differential protection
element (87L) requires time-aligned current signal from the local and remote terminals. If
the line has more than 2 terminals, then naturally, the scheme will need to be injected at
all the different terminals simultaneously in order to test it. This means that not only the
current signals must be applied at multiple terminals but, the injected current signals must
be applied with controlled phase and timing with respect to one another.” [7] If the
current signals being injected by the different test sets into the multiple relays are not
synchronized with each other, then it is possible that a false differential current will be
generated due to the phase angle differences between the test sets.
Note that latency in the communications channels can also create a false reading in the
estimated maximum possible error that could be produced into the calculations. A
“buffer” zone can be created between operate and restraint characteristic of the
differential element. This will ensure that the differential element will not trip for false
The SEL-311L utilizes what is known as an “alpha plane” to determine operate and
restraint regions of the differential element. The alpha plane consists of real and
imaginary axes, where the vectors presented on the plane are a ratio of the remote (IR ) to
local (IL ) current signals. A representation of the alpha plane is presented in figure 6.
Im
1
External
Faults and
Load Current
Restraint Operate
-1 Region Region 1
Re
-1
It should be noted that the “local” current signal in this case is the current signal to be
measured by the local SEL-311L relay that is connected directly to the CTs and
measuring current through its current inputs. The “remote” current is the current being
measured by the SEL-311L remote relay that is connected to the local relay through a
communications channel.
Considering that in a 2 terminal transmission line, the current flowing into the local
terminal of this line is 180° out of phase with the same magnitude as the current flowing
28
out of the remote terminal (assuming no intermediate shunt loading), then the ratio 𝐼𝐼���⃗ ��⃗
𝑅𝑅 /𝐼𝐼𝐿𝐿
will have a value of 1 at 180° on the alpha plane. This is the point on the plane when the
line is carrying normal load or external fault currents. This also locates the point on the
If the currents being measured locally and remotely are equal in magnitude and phase,
then it would mean that the currents are both flowing into the protected line and an
internal fault has occurred in the zone of protection. This would place ���⃗
𝐼𝐼𝑅𝑅 /𝐼𝐼��⃗𝐿𝐿 at a value of
1 at 0° on the alpha plane which makes it a point in the operate region of the differential
element. However, there are certain factors that may make an internal fault not lie
• CT saturation
The source voltage and the source impedance angles can add up to a 20° phase shift.
Channel asymmetry can add an additional 21.6° shift, as well as CT saturation which can
add another 40°. Thus the operate zone should encompass a region of +/- 81.6° around
the 0° axis to ensure that all of these effects have been considered. This renders the rest
Another fact that needs to be taken into account is the CT ratio that the local and remote
relays are connected to. In an ideal situation the CT ratios would be equal, but this is not
29
always the case. Therefore during normal operations the local and remote relays may be
measuring different magnitudes of current on the secondary of the CTs that they are
connected to, even though the primary side values are the same. This is taken into
account in the relay settings, which contain information about the local as well as the
remote CT settings. However this must also be taken into account when test currents are
injected into the two relays during testing. For example the local relay may have a setting
for its CT ratio that is twice that of the remote CT ratio. Thus when injecting current into
the relays using two separate test sets, the current being injected into the local relay
should be half of the current being injected into the remote relay. This will correctly
emulate the situation where the magnitudes of the primary currents are considered equal
by the local and remote relays as they communicate with each other.
All factors discussed above need to be considered when testing the differential elements.
Determination of the restraint region versus the operate region is the first step. Then the
differences in CT ratios between the relays at each terminal must be accounted for. The
final step is determining the currents necessary to be injected by each of the test sets into
Chapter 6
CONCLUDING REMARKS
Various types of relay elements require different approaches for testing. Some elements
only require magnitude and frequency of one variable such as voltage or current for
operation and testing. Voltage, frequency and non-directional current elements are
examples of such elements. Other elements may require inputs from two variables of
voltage and/or current. Directional overcurrent relays require taking a polarizing variable
which maybe current or voltage. Impedance elements take both voltage and current
inputs, and some differential elements need to compare two current inputs.
Caution must be exercised for proper determination and testing of time delay functions in
some frequency relays. This is due to different methods of time delay calculations
In this project report, standardized approaches for testing commonly used EM, SS, and
MP based relaying elements, using modern test equipment was presented, analyzed, and
test routines for various types of MP based relaying elements offered by the industry
independent of their make, model, or manufacturer. While this project report only covers
the commonly used relay elements in protection schemes, it was also intended to serve as
31
an introduction to many of the potential problems that may be encountered during the
References
relays," Pulp and Paper Industry Technical Conference, 2004. Conference Record of
maintenance testing," in IEEE Industry Applications Magazine, vol. 11, no. 5, pp. 50-
Principals and Applications, 3rd ed. Boca Raton, USA: CRC Press, 2007, ch. 3,
Relaying," in IEEE Transactions on Power Apparatus and Systems, vol. PAS-98, no.