4.13 Ɂɚɯɪɚɧɜɚɧɟ ɡɚ ɜɴɧɲɟɧ ɦɨɧɬɚɠ ECM1500 Outdoor Cabinet Power


Supply System ɧɚ Emerson

Ɉɡɧɚɱɟɧɢɟɬɨ ɧɚ ɦɨɞɟɥɚ ɧɚ ɡɚɯɪɚɧɜɚɧɟɬɨ Emerson ɢɦɚ ɫɥɟɞɧɢɹ ɫɦɢɫɴɥ:

EC M 1500 F 1 - 48 300
Internal power capacity: 300A, 150A, 120A
Internal power voltage:48Vdc
Version No.
Thermal control method: F (forced ventilation), H (heat exchanger), A (air-condition)
Maximum heat productivity in cabinet:1500W
Application: mobile network integrated cabinet
Emerson outdoor cabinet

ɋɢɫɬɟɦɚɬɚ ɟ ɞɨɫɬɴɩɧɚ ɜ ɬɪɢ ɜɟɪɫɢɢ, ɢɡɩɴɥɧɟɧɢ ɫ ɬɪɢ ɜɢɞɚ ɬɟɪɦɨ-ɤɨɧɬɪɨɥɧɢ


ɦɨɞɭɥɢ ( ɩɪɢɧɭɞɢɬɟɥɧɚ ɜɟɧɬɢɥɚɰɢɹ, ɬɨɩɥɨ ɨɛɦɟɧɧɨ ɬɹɥɨ ɢɥɢ ɤɥɢɦɚɬɢɤ).

¤ 2012 VIVACOM ɫɬɪ.43 ɨɬ 74 ALCATEL • LUCENT


Ʉɨɧɮɢɞɟɧɰɢɚɥɧɨ
Ⱦɨɤɭɦɟɧɬ ʋ PRG-VDM-001 Ɋɟɜ.2 / V002542

4.13.1 Ɇɨɧɬɚɠɧɢ ɢɡɢɫɤɜɚɧɢɹ ɧɚ ɮɢɪɦɚɬɚ ɩɪɨɢɡɜɨɞɢɬɟɥ.

ɋɥɟɞɜɚɣɬɟ ɫɥɟɞɧɢɬɟ ɢɡɢɫɤɜɚɧɢɹ, ɜ ɫɥɭɱɚɣ, ɱɟ ȼɢɜɚɤɨɦ ɧɟ ɟ ɩɪɟɞɨɫɬɚɜɢɥɚ


ɞɪɭɝɢ.

Front Top Left Right Back


Clearances 750mm 700mm 100mm 100mm 100mm
657

480
650
88.5

700

900
650± 0.5
130
480± 0.5
1100

Expansion bolt

Front door

¤ 2012 VIVACOM ɫɬɪ.44 ɨɬ 74 ALCATEL • LUCENT


Ʉɨɧɮɢɞɟɧɰɢɚɥɧɨ
Ⱦɨɤɭɦɟɧɬ ʋ PRG-VDM-001 Ɋɟɜ.2 / V002542

4.13.2 Ɋɚɡɦɟɪɢ ɢ ɬɟɝɥɚ


Parameter
Parameter Description
category
-10°C ~ +45°C (forced ventilation model), -40°C ~ +45°C (heat exchanger
Operating temperature
model), -40°C ~ +50°C (air-condition model)
Storage temperature -40°C ~ +70°C
Environmental
Relative humidity 5%RH ~ 100%RH
Altitude ” 2,000m (derating is required above 2,000m)
Others No conductive dust or erosive gases. No possibility of explosion
Conducted emission
Class A EN55022
Radiated emission
Immunity to EFT Level 3 EN61000-4-4
EMC Immunity to ESD Level 3 EN61000-4-2
Immunity to Surges Level 4 EN61000-4-5
Immunity to radiation Level 3 EN61000-4-3
Immunity to conduction Level 3 EN61000-4-6
Safety regulation Compliant with IEC60950-1, IEC60950-22
At temperature of 15°C ~ 35°C and relative humidity not bigger than 90%RH,
apply a test voltage of 500Vdc. The insulation resistances between AC circuit
Insulation resistance
and earth, DC circuit and earth, and AC and DC circuits are all not less than
10Mȍ
(Remove the SPD, monitoring module and rectifiers from the system before the
test.)
Others AC circuit to earth: 50Hz, 2,500Vac
DC circuit to earth: 50Hz, 1,000Vac
Insulation strength
Assistant circuit (not directly connected to the host circuit): 50Hz, 500Vac
AC to DC circuits: 50Hz, 3,000Vac
For all the three tests above, there should be no breakdown or flashover within
1min, with leakage current not bigger than 10mA
MTBF 100,000hr
ROHS Compliant with R5 requirement
Cabinet 700 (W) × 700 (D) ×1800 (H)
Dimensions (mm) Internal space of
534 (W) × 558 (D) × 330 (H)
battery compartment
Forced ventilation
” 125 (excluding subrack and battery string)
Mechanical model cabinet
Heat exchanger
Weight (kg) ” 180 (excluding subrack and battery string)
model cabinet
Air-condition model
” 175 (excluding subrack and battery string)
cabinet

¤ 2012 VIVACOM ɫɬɪ.45 ɨɬ 74 ALCATEL • LUCENT