Most experienced HVAC engineers, when questioned about what supply air temperature they typically use for comfort air ► July (1)
conditioning applications, will answer 55°F almost without exception.  As consistent as this answer will be repeated, one would think ► April (1)
that there must be some basic law of physics that makes it so universal.  In fact, the answer is not simple at all.  It is based on a
▼ February (2)
series of principles that span several interrelated topics from physics and chemistry to the basic temperature regulation systems of
the human body.  This discussion will provide a very brief overview of the parameters that conspire to make that 55°F supply air When I'm Sixty-Four
answer appropriate for comfort air conditioning. Why is the Supply Air
Temperature 55°F?
The first element of the answer has to do with what constitutes human comfort (after all, we do call it comfort air conditioning). 
► January (3)
But before we can address human comfort, we need to talk about the sea of atmospheric air that we all live in.  Atmospheric air is
composed of a mixture of several gases, principally oxygen and nitrogen, but also containing a very small amount of water vapor. 
Water vapor is always present in atmospheric air, and though its relative weight in the atmosphere averages less than 1% in FOLLOW BY EMAIL
temperate climates, it is nevertheless one of the most important factors in human comfort.  Its impact on human activities is in fact
altogether disproportionate to its relative weight. Email address... Submit

The human body, at the most fundamental level, is a heat machine with a complex set of mechanisms to control core body
temperature.  The food we take in is used in chemical processes to provide the energy for our body to function.  In turn, this heat
must be rejected to our environment (usually atmospheric air) to maintain what we refer to as “comfort” – not enough heat
rejected, we feel warm; too much heat rejected, we feel cold.  The heat rejection that takes place from our bodies occurs by three
principal means:

· Convection – heat transfer based on the temperature of the air around us.  The higher the air temperature, the less heat
transfer that occurs tending to make us feel hot; the colder the air temperature, the more heat transfer that occurs making
us feel cold.
· Radiation – heat transfer based on the difference in temperature between our skin temperature and the temperature of
surfaces around us; we lose heat sitting next to a cold window surface in the winter even though the air temperature
around us may be warm.
· Evaporation – heat transfer based on the relative humidity or the amount of water vapor in the air.  Water leaving the
surface of the human body (sweat) evaporates and cools the body.  The higher the relative humidity of the air, the lower
the evaporation that takes place making us feel warmer; the lower the relative humidity, the more the evaporation that
takes place making us feel colder.

In the years before about 1950 when our buildings were typically heated only, making people comfortable relied principally on
convection and radiation – maintaining the air temperature was the only parameter that was needed for control in the winter.  If
there were large windows, we installed warm radiators below them to (1) warm the air and (2) offset the radiation heat loss from
the window.  Since the air in the winter was very dry (low relative humidity), evaporation heat transfer occurred at a relatively
constant rate as needed and convection based on air temperature could be controlled to make us comfortable.  In the summertime,
everyone inside buildings knew they were going to be uncomfortable since the air temperature was generally high (reduced
convection heat transfer), the building surfaces were warm (less or no radiation heat transfer), and the air relative humidity was
generally high (reduced evaporation heat transfer).

When air conditioning became common after the early 1950’s, the picture changed dramatically.  Suddenly the relative humidity
became an equally important parameter in comfort.  In humid climates like St. Louis, summer outdoor relative humidity is high and
the evaporation component of body cooling is appreciably reduced.  Exhaustive tests were performed in controlled settings to
determine what combination of space temperature and relative humidity in indoor environments made people comfortable.  The
result was that 75°F, 50% relative humidity became the target that seemed to please the maximum number of test subjects.  Thus
75°F, 50% relative humidity became the indoor air standard for summer air conditioning.  To maintain the indoor air temperature at
75°F in the summer, colder air needed to be introduced into rooms to provide cooling.  But the physics of the cooling process could
be satisfied by introducing supply air into the room at any temperature below 75°F, as long as the quantity of such air could be
controlled (much more 70°F air would be required than 50°F air for the same amount of room cooling).  But the evaporative side of
the heat transfer equation turned out to be a bit more complicated.

In the summertime, the relative humidity in air conditioned spaces increases principally due to the evaporation of water vapor from
the skin surfaces of the people in the spaces.  The process of controlling indoor humidity occurs in the same basic process as that of
temperature control described above – drier air (below the 75°F, 50% relative humidity) is introduced into the spaces to limit the
relative humidity rise to 50%.  Again, the physics of the drying process could be satisfied by introducing supply air into the room at
any dryness below 75°F, 50% relative humidity, as long as the quantity of such air could be controlled (much more 75°F, 49% relative
humidity air would be required than 75°F, 30% relative humidity air for the same amount of room air drying).  Though our technology
provides many options to heat, cool, and add water vapor to air, only one simple option is available to remove water vapor from air. 
And that option is only available because of a unique property of the air/water vapor atmosphere we live in – as air is cooled, it can
physically hold less water vapor.

If we pass air over a cooling coil that is at a colder temperature than the air entering it, cooling of the air occurs.  If the air is humid
as on a rainy spring morning, the air is cooled but because the cooler air can hold less moisture, water vapor begins to condense out
of the airstream and onto the coil as liquid water.  If the coil is very efficient, the air leaving the coil is at nearly 100% relative
humidity (a condition referred to as saturation).  The air leaving the coil now becomes both cooler and drier.  It turns out that if you
pass 75°F, 50% relative humidity air across the coil, at a coil temperature of a little below 56°F, water begins to condense on the
coil and air cooling and drying begins to take place.  At a coil leaving air temperature of about 55°F, the drying effect of this air
leaving the coil is sufficient to reduce the water vapor increase from the building occupants for typical people densities in our
modern buildings.  And because of the property of air/water vapor described above, the 55°F air is at nearly 100% relative humidity

http://8760engineeringblog.blogspot.in/2013/02/why-is-supply-air-temperature-55f.html 1/3
11/1/2017 8760 Engineering Blog: Why is the Supply Air Temperature 55°F?
and a single specification of 55°F supply air temperature satisfies both the cooling and the drying of the air necessary for comfort air
conditioning.  Thus, all of these parameters together make the simple answer- deliver supply air at 55°F.

As year-round air conditioning systems were then developed over the ensuing years, most of these systems were based on delivering
55°F supply air to satisfy the air cooling and drying required during summertime conditions.

8760 Engineering would like to thank Jerry Williams for this blog post, and stay tuned for several more insightful entries from our
very own senior engineer!

To end this blog post we present and energy conservation measure that almost always exist and is never found unless an engineer
employs data logging.  This is the case of the broken heating valve, which will heat the air up in excess of 100°F before it is cooled
back down to 55°F.

ECM:  Replace Cracked / Failed Heating Valve


kWh Saved per CFM: 86

Article Author:  Jerry Williams


jwilliams@8760engineering.com
Blog Post:  Ryan Corrigan 
rcorrigan@8760engineering.com

Posted by 8760 Engineering at 2:45 PM

11 comments:

way2 college April 1, 2013 at 1:52 AM


I'm happy to find numerous useful info here in the post. I would really like to come back again right here for likewise good articles or blog
posts. Thanks for sharing...
Top MBA Colleges in Kolkata
MBA Colleges in Kolkata

Reply

Arab Academy September 10, 2016 at 3:36 AM

I appreciate your efforts and i always like to learn more and more ... thanks a lot for nice efforts
fire courses
safety courses
Reply

Mohamed Elnaseh September 16, 2016 at 4:38 AM

Thank you very much for your good efforts


ad your ads here
nasih network

Reply

priya sharma April 21, 2017 at 2:00 AM


A pioneer Institute owned by industry professionals to impart vibrant, innovative and global education in the field of Hospitality to bridge
the gap of 40 lakh job vacancies in the Hospitality sector. The Institute is contributing to the creation of knowledge and offer quality
program to equip students with skills to face the global market concerted effort by dedicated faculties, providing best learning
environment in fulfilling the ambition to become a Leading Institute in India.
cha jaipur
management college in jaipur
management of hospitality administration jaipur
cha management jaipur
Best hotel college in jaipur
Best management college in jaipur
Reply

priya sharma April 21, 2017 at 2:11 AM

A pioneer Institute owned by industry professionals to impart vibrant, innovative and global education in the field of Hospitality to bridge
the gap of 40 lakh job vacancies in the Hospitality sector. The Institute is contributing to the creation of knowledge and offer quality
program to equip students with skills to face the global market concerted effort by dedicated faculties, providing best learning
environment in fulfilling the ambition to become a Leading Institute in India.

Best hotel management goo.gl/xOlrNL college.

cha jaipur
management college in jaipur
management of hospitality administration jaipur
cha management jaipur
Best hotel college in jaipur
Best management college in jaipur

Reply

priya sharma April 21, 2017 at 2:14 AM

http://8760engineeringblog.blogspot.in/2013/02/why-is-supply-air-temperature-55f.html 2/3

Potrebbero piacerti anche