Sei sulla pagina 1di 24

SECTION 11: page 1

by Honeywell
Section 11:
Emergency Lighting
Design Guide &
Central Battery Systems

Contents
Emergency Lighting
Design Guide

Emergency Lighting

Central Battery Systems


SECTION 11: page 3

by Honeywell
Section 11.1:
Emergency Lighting
Design Guide

Contents
Product Descriptions

Design Stage 1:
Initial Considerations

Design Stage 2:
Compulsory lighting
locations- Points of
Emphasis

Design Stage 3:
Exit Signage

Design Stage 4:
Escape Routes

Design Stage 5:
Anti Panic or Open
Areas

Design Stage 6:
High Risk Task Areas

Design Stage 7:
Which type – Self
contained or centrally
supplied luminaires?

Design Stage 8:
Maintenance and
Testing
SECTION 11: page 5

1 1 . 1 : e m e r genc y lighting design G u ide

by Honeywell
Product Descriptions
The list below has been taken from ICEL 1006 and provides a brief explanation of various terms used widely in
Emergency Escape Lighting System Design.

Application terminology Product description and definitions

Emergency escape lighting Standby lighting


That part of emergency lighting provided to enable safe exit in the That part of emergency lighting provided to enable normal activities
event of failure of the normal supply. to continue in the event of failure of the normal mains supply.
Emergency exit
Ballast
A way out which is intended to be used any time that the premises
are occupied. Controls the operation of a fluorescent lamp for a specified AC or
DC source (typically between 12 and 240 Volts). It can also include
Escape route lighting elements for starting the lamp, for power factor correction or radio
frequency interference suppression.
That part of emergency lighting provided to enable safe exit for
building occupants by providing appropriate visual conditions and
Ballast lumen factor (BLF)
direction finding on escape routes and in special areas/locations,
and to ensure that fire fighting and safety equipment can be readily The ratio of the light output of the lamp when the ballast under test
located and used. is operated at its design voltage, compared with the light output
of the same lamp operated with the appropriate reference ballast
Final exit supplied at its rated voltage and frequency.

The terminal point of an escape route, beyond which persons are no


Battery capacity
longer in danger from fire or any other hazard requiring evacuation
of the building. The discharge capability of a battery, being a product of average
current and time, expressed as ampere hours over a stated duration.
High risk task area lighting Note that a shorter total discharge period gives rise to a smaller
available capacity.
That part of emergency lighting provided to ensure the safety of
people involved in a potentially dangerous process or situation, and
Central battery system
to enable proper shut down procedures to be carried out for the
safety of other occupants of the premises. A system in which the batteries for a number of luminaires are
housed in one location, usually for all the emergency luminaires in
Open area (or anti-panic area) lighting one lighting sub circuit, sometimes for all emergency luminaires in a
complete building.
That part of emergency escape lighting provided to reduce the
likelihood of panic and to enable safe movement of occupants
Design voltage
towards escape routes by providing appropriate visual conditions and
direction finding. The voltage declared by the manufacturer to which all the ballast
characteristics are related.

‘F’ mark
Shows the luminaire can be mounted on combustible surfaces. It
does not show that the luminaire is fire retardant.

Fire retardant housing 850ºC Test


All emergency luminaires housings on escape routes must pass the
850ºC glow wire test as specified in EN 60 598-2-22.

Flux
The illumination produced by one lumen over 1 square metre.

Illuminance
The luminous flux density at a surface, i.e the luminous flux incidence
per unit area. The unit of illuminance is lux (Lumens/m2).
SECTION 11: page 6

1 1 . 1 : e m e r genc y lighting design G u ide

by Honeywell
Product Descriptions
Product description and definitions continued…

K factor Room index


This is the ratio of light output of the lamp in the worst condition i.e. The relationship between the height, length and width of a room
normally at the end of a full battery discharge, and the light output used for illuminance calculations.
measured at normal voltage.
Self contained (single point) luminaires
Lumen A luminaire or sign providing maintained or non-maintained
A standard measure of light output. emergency lighting in which all the elements such as the battery, the
lamp and the control unit are contained within the housing or within
Lux one metre of the housing.
A measure of lighting density, expressed in lumens per area.
Service factor
Maintained mode This is the ratio that compares the level of illuminance provided
A luminaire containing one or more lamps all of which operate by a system after a number of years in service, with the output
from the normal supply or from the emergency supply at all provided by the same system when new. Sometimes known as
material times. Maintenance factor.

Mounting height Slave luminaires


The vertical distance between the luminaire and the working An emergency luminaire without its own batteries designed to work
plane. Note that the floor is taken to be the working plane for with a Central Battery System.
emergency lighting.
Uniformity ratio
Non-maintained mode This is the ratio of minimum illuminance, and the average illuminance
A luminaire containing one or more lamps, which operate from the measured at floor level.
emergency supply only upon failure of the normal mains supply.
Utilisation factor at zero reflectance (UFO)
Rated duration This establishes the proportion of a lamp’s light output that falls
The length of time a luminaire is designed to operate after the mains directly on the floor, for various room indexes and types of diffuser.
has failed. (Typically 1 or 3 hours from a fully charged battery).

Rated load
The maximum load that may be connected to the system and will be
supplied for the rated duration.

Re-charge period
The time necessary for the batteries to regain sufficient capacity to
achieve their rated duration.
SECTION 11: page 7

1 1 . 1 : e m e r genc y lighting design G u ide

by Honeywell
Design Stage 1
Design Stage 1: Initial Considerations – current statutory requirements and
product standards
The design specification, selection and installation of emergency lighting is covered by an extensive range of legislation which are under continual
review, being amended, in response to Directives and Standards issued by the relevant statutory bodies of the European Union. The first stage
of system design is to gather all information for the project through reference to local authorities for current legislative Standards and Directives,
and must pay due regard to users/customers preferences.

primary uk legislation

DESCRIPTION
The Fire Precautions in the workplace Act of 1997 – Further guidance is available in the HSE book FIRE SAFETY – an Employers Guide

Health and Safety at work etc. Act 1974

The Workplace (Health, Safety and Welfare) Regulations 1992

Building Regulations Act 2000 – Document B

The Cinematograph Act 1952

Health & Safety (Safety Signs and Signals) Regulations Act 1996
Other legislation dealing with premises licensed or registered for public assembly or residential purposes, e.g. Licensing Act, Local Government Miscellaneous
Provisions) Act, Theatres Act, Residential Homes Act etc, the guides for which all contain a requirement for emergency lighting

Standards and codes of practice

code / standard DESCRIPTION


1999 Code of practice for the emergency lighting of premises other than cinemas and certain other specified premises used for
BS 5266: Pt 1
entertainment
CP1007 1955 Maintained lighting for cinemas

BS EN 60598-2-22 1999 Specification for luminaires for emergency lighting

BS 5499: Pt 1 1990 Specification of safety sign, inc.fire safety signs

BS 5499: Pt 2 1990 Specification for self-luminous fire safety signs

BS 5499: Pt 3 1990 Specification for internally-illuminated fire safety signs

ISO3864-1 Graphical symbols – safety colours and safety signs

harmonised european standards

code / standard DESCRIPTION

HD 384 Electrical installation of buildings

EN 60598-2-22 Specification for luminaires for emergency lighting

EN 1838 (BS 5266:Pt7) Lighting applications – emergency lighting

EN 50171 Central power supply systems

draft european standards

code / standard DESCRIPTION

prEN 50172 Emergency escape lighting systems


doc. CEN/TC 169WG7
Measurement and presentation of photometric data for lamps and luminaires
N61D/E/F

european directives and recommendations

directive DESCRIPTION

89/654 EEC Workplace Directive

92/58 EEC Safety Signs Directive

89/106 EEC Construction Products Directive

86/666 EEC Fire Safety in Hotels Recommendation – Requirements for Europe


SECTION 11: page 8

1 1 . 1 : e m e r genc y lighting D E S I G N G u ide

by Honeywell
Design Stage 2
Design Stage 2: Compulsory lighting locations – Points of Emphasis
The positioning and selection of emergency lighting equipment is subject to the nature of the area to be protected, and should be identified
during risk assessment. This should cover specific hazards and highlight safety equipment and signs. This section provides outline guidance on
each of the defined areas that require protection.
Areas initially requiring cover for designing a scheme are (these are mandatory):

A Each flight of stairs B Change in direction along the C Exit doors


escape route

D Safety signs E Each final exit point (internally F Fire alarm call points
and externally)

G Each intersection H Change of floor level I Fire fighting equipment / first


aid points

Additional emergency lighting should be provided at the following:


A Lift cars
B Toilet facilities and other tiled areas which exceed 8m2 floor area and toilet facilities for the disabled
C Escalators
D Motor generator, control or plant rooms
E Covered car parks along pedestrian routes
F External escape routes
SECTION 11: page 9

1 0 . 1 : e m e r genc y lighting design G u ide

by Honeywell
Design Stage 3
Design Stage 3: Exit signage
These are required at all exits, emergency exits and along escape routes. A directional sign is required when sight of an emergency exit sign is not
possible or doubt may exist. BS 5266 and EN 1838 state that all the emergency escape route signs and luminaires, which should be of the same
design format, should be placed in all areas.

The Format

EXIT
1975 1990 1999
To be replaced by Deemed to comply with HSE Signs
24 December 1998 Signs Directive for existing Directive Format
installations

Sign Height (H)

100 x H

200 x H

Maximum Viewing Distance


Calculated using the following formulas:
200 x H for internally illuminated signs
100 x H for externally illuminated signs
SECTION 11: page 10

1 1 . 1 : e m e r genc y lighting design G u ide

by Honeywell
Typical Scheme

C Exit doors D Safety signs E Each final exit point F Fire alarm call points
(internally and externally)

al Call Point >8m >8m OFFICE NO.1 OFFICE NO.2

der
MALE FEMALE
WC WC
e Route

gency Luminaire

gency Exit Sign STAFF ROOM

BOILER ROOM G Each intersection

OFFICE NO.3

DANGEROUS DANGEROUS
WORKSHOP
MACHINERY MACHINERY

RECEPTION INSPECTION PIT

HAZARDOUS
AREA

H Change of floor level

Key:

Manual Call Point >8m >

Sounder
MALE FE
WC
Escape Route

Emergency Luminaire

Emergency Exit Sign


B Change in direction along A Each flight of stairs I Fire fighting equipment /
the escape route first aid points

BOILER RO
SECTION 11: page 11

1 1 . 1 : e m e r genc y lighting design G u ide

by Honeywell
Design Stage 4
Design Stage 4: Escape routes
After all mandatory Luminaires and Exit signs have been positioned, it may be necessary to provide additional luminaires so that a minimum light
level is reached along the escape route. The luminaires on an escape route of up to 2m wide should be positioned centrally. The illuminance is
specified along the centre line with 50% of that illuminance over the 1 metre wide central band. Wider routes are treated as Open Areas or as
multiple routes.

1 lux minimum
on centre line
of escape route

1 lux to wall

Transverse
spacing to wall

Transverse spacing
between luminaires

1 lux minimum between luminaires


(0.5 lux being provided by each luminaire)

In terms of illumination, EN 1838 calls for a minimum of 1.0 Lux anywhere along the centre line of the escape route. The UK has a National
Exception which accepts 0.2 Lux along the centre line as long as the escape route is permanently unobstructed with points of emphasis to 1 Lux.
Spacing table provide assistance in these calculations.
BS 5266 recommends using a larger number of low power luminaires rather than a few high power units. In this way it ensures no part of the
escape route is lit by just one luminaire.
Reference to the Photometric Data will provide you with the information needed to determine the number of additional fittings that are required,
with the existing luminaires provided to illuminate points of emphasis.
SECTION 11: page 12

1 1 . 1 : e m e r genc y lighting design G u ide

by Honeywell
Design Stage 4

Maximum permitted spacing (in metres) to achieve 0.2 lux


Permanently unobstructed route only
e.g. UL8

Height (m) TrTr AxAx TrWall AxWall

2 12.2 7.5 5.8 3.1

2.5 14.8 8.0 6.2 3.3

3 17.2 9.0 7.1 3.6

4 19.3 9.9 8.2 3.5

6 23.7 10.1 6.9 2.9

8 20.9 8.9 - -

10 11.1 5.7 - -

Maximum permitted spacing (in metres) to achieve 0.2 lux


Open (Antipanic) core areas
e.g. UL8

Height (m) TrTr AxAx TrWall AxWall

2 11.3 5.9 4.6 2.2

2.5 12.1 6.2 5.2 2.2

3 13.6 6.4 5.3 2.2

4 15.1 6.2 4.0 1.7

6 10.7 4.5 - -

8 - - - -

10 - - - -

Maximum permitted spacing (in metres) to achieve 0.2 lux


Points of emphasis & normal risks
e.g. UL8

Height (m) TrTr AxWall TrWall AxWall

2 9.3 4.4 3.7 1.5

2.5 10.4 4.5 3.3 1.4

3 10.6 4.4 2.7 1.1

4 8.1 3.5 - -

6 - - - -

8 - - - -

10 - - - -
SECTION 11: page 13

1 1 . 1 : e m e r genc y lighting design G u ide

by Honeywell
Design Stage 5
Design Stage 5: Anti panic or open areas
Areas that are not escape routes or high risk, but still within the general requirements of current legislation, are known as open areas.
The European Standard EN 1838 calls for a minimum of 0.5 Lux measured at floor level anywhere within the area excluding shadowing effects
of room contents. The core area also excludes a 0.5m perimeter.
Spacing Data for Anti Panic or Open Areas
The number of luminaires required can be calculated using the following equation:
Calculation Example
Room measures 12 metres wide by 15 metres in length.
8 watt self-contained luminaires, with an ELDL of 130 lumens are to be mounted at 3 metres from the floor. The Service factor is 0.8, the K Factor
is 0.65 and UFO is 0.47.

Core area
Number of Luminaires required = 1 x 12 x 15 (excludes 0.5m border)

0.47 x 0.8 x 130 x 0.65

= 180 = 5.7 (rounded up to 6) luminaires


31.7

The example is calculated by using the following equation:


N = E x room width x room length Transverse
spacing
UFO x SF x ELDL x K Axial spacing to wall
between luminaires
Transverse spacing
N number of luminaires Axial spacing between luminaires
to wall
E is the average illuminance required (i.e. 1 lux)
UFO is the Utilisation Factor for an appropriate room index at zero reflectance

The UFO can be obtained by first calculating the Room Index (RI) by using the following equation:
RI = Length of room (L) x width of room (W)
Mounting height of luminaire x (L + W

Once the RI has been calculated, refer to the UFO table within the Photometric Data
SF is the Service Factor, which takes account of cable voltage drop, lamp replacement period, component ageing and dust accumulation.
For most purposes, a Service factor of 0.8 is valid for self contained and mains luminaires, and 0.75 for DC central battery luminaires.
ELDL is the Design Lumen Output of the luminaire at its nominal operating voltage.
K is a factor which relates to the reduction in light output at the end of discharge, or 5 seconds after mains failure, whichever is the
lowest.

K factors vary with circuit types as follows:

model self contained units dc central systems ac central systems

type NM/s m

Luminaires fluorescent 0.65 0.55 0.70 1.00

Luminaires tungsten 0.55 0.55 0.55 1.00

Conversion units 0.70 0.70 0.75 N/A


SECTION 11: page 14

1 1 . 1 : e m e r genc y lighting design G u ide

by Honeywell
Design Stage 6

Design Stage 6: High risk task areas


The European Standard EN 1838 requires that higher levels of emergency lighting are provided in areas that are considered to present danger to
a building’s occupants, in the event of a mains lighting failure, to be adequately illuminated.
Adequate illumination is defined as at least 10% of the normal lighting, with a minimum level of 15 lux and continues for as long as the hazard
exists. The average horizontal illuminance on the reference plane (not necessarily the floor) should be as high as the risk demands.

SUMMARY OF ILLUMINANCE REQUIREMENTS

en 1838 BS 5266: Pt 1: 1988 (Superseded)

0.2 Lux minimum


Escape routes 1 Lux minimum
Routes with obstruction or used by elderly people require higher levels of lighting

Open areas 0.5 Lux minimum in core area 1 Lux average over total area

Additional areas 0.5 Lux minimum Not specified

High risk task areas 10% of normal illuminance Not specified


SECTION 11: page 15

1 1 . 1 : e m e r genc y lighting design G u ide

by Honeywell
Design Stage 7
Design Stage 7: Which type – self-contained or centrally supplied luminaires?
Essentially there are two basic systems to select from.

Self-contained luminaires
The first is a system that utilises luminaires with their own battery, charger and changeover circuits. They also include conversion kits that can be
used to enhance mains fluorescent luminaires, enabling them to provide illumination in the event of a normal supply failure.

Benefits Drawbacks
l Easy and quick to install l Batteries have a limited working
l Minimal wiring costs life, and are susceptible to high
ambient temperatures
l Reliable
l Relatively expensive for larger
l Ideal for smaller installations
installations
l Safe: if one luminaire fails, the
rest will still operate
l Site expansion easily catered for
l Widely available off-the-shelf

Centrally-Supplied Systems
The second type of system is one that is linked to a remote back-up power supply, which provides energy in the event of a normal supply failure.
Of these, there are two basic types.

DC Battery Systems
These comprise of a battery, charging circuit and control circuit to provide DC power when needed.

Benefits Drawbacks
l Low running cost l Requires separate fire resistant
l Extended system life distribution wiring
l Easy to test and maintain
l Relatively low luminaire cost
l Luminaires able to operate at
high ambient temperatures

AC Battery systems
These are central battery systems fitted with an inverter, to provide AC power in the event of a normal supply failure. Control circuitry is also
incorporated to ensure a stabilised power output.

Benefits Drawbacks
l Low running cost l Requires separate fire resistant
l Extended system life distribution wiring
l Easy to test and maintain
l Relatively low luminaire cost
l Luminaires able to operate at
high ambient temperatures
l Able to utilise existing mains
luminaires
l Potential for producing higher
light output
SECTION 11: page 16

1 1 . 1 : e m e r genc y lighting design G u ide

by Honeywell
Design Stage 8
Design Stage 8: Maintenance and testing
The tasks of regular maintenance and testing are vital to make sure that a systems integrity and capacity to fulfil its task are maintained at all
times. Essential servicing should be well defined to ensure that the scheme remains fully operational. Consumable items such as lamps & batteries
should be available for immediate use.
BS 5266 recommends a test procedure, elements of which will become mandatory once new draft European directives become law.
All periodical testing as defined in BS 5266 should wherever possible be undertaken at times of minimum risk. All tests, results and corrective
actions should be recorded in the site log book.
SECTION 11: page 17

by Honeywell
Section 11.2:
Emergency Lighting

Contents
8W Luminaire Classic

High Light Output 8W


Luminaire

Rectangular 8W Exit
Sign

2 x 18W Twinlight
(Surtwin)

Photometric Data
SECTION 11: page 19

1 1 . 2 : e m e r genc y lighting

by Honeywell
8W Luminaire Classic
l Suitable for a wide range
of interior and exterior
applications
l Cost effective with an optically
efficient and durable lens
design
l Maintained /non-maintained
versions
l Weatherproof (fit seal
supplied if an IP65 rating is
required)
l Snap-fit construction with
hinged gear tray
l Simple to install with screw
terminal block and a BESA
box mounting facility
8W Luminaire Classic
l Stylish, slim profile design
with a range of optional
Technical Specification pictograms
Ca8/Nm/3f Ca8/m/3f
Mode Non-maintained Maintained
Emergency Duration 3 hours
Emergency Lamp O/P 105 lumens
Maintained Lamp O/P N/A 380 lumens
Construction Styron housing, polycarbonate diffusor and mild steel geartray
Dimensions H x L x D 345 x 95 x 75
Weight 1000g 1200g
Cable Entry Drill guides on sides and one end BESA in rear of fitting
Supply Voltage 230/240V 50/60Hz
Power Consumption Standby
4.0VA 4.2VA
Mode
Power Consumption Mains
N/A 19.0VA
Mode
Recharge Period 24 hours
Battery 2 x 1.2V, 4000 mAh, Ni-Cd, high temp, rechargeable batteries pack
Light Source 8 watt T5 cool white fluorescent tube
Monitor Green LED monitoring mains supply and battery connection
Operating Temperature 0ºC to +30ºC
IP Rating IP65 when seal fitted
Warranty 1 Year
Certification CE – Ref. BS 4533 / EN 60598-2-22

Mode LIST NUMBER DESCRIPTION


Self contained CA8/M/3F 8 watt maintained Order Codes
Self contained CA8/NM/3F 8 watt non-maintained
8W Luminaire, IP65,
CLASSIC Pictograms Non-maintained CA8/NM/3F
PICTogram LIST NUMBER DESCRIPTION 8W Luminaire, IP65,
Maintained CA8/M/3F
BULK/DOWN Pictogram arrow down
Semi-recessing Bezel for
8W Luminaire, White RK1/CA
BULK/UP Pictogram arrow up Pictogram, arrow down BULK/DOWN
Pictogram, arrow up BULK/UP
BULK/RIGHT Pictogram arrow right Pictogram, arrow right BULK/RIGHT
Pictogram, srrow left BULK/LEFT

BULK/LEFT Pictogram arrow left


SECTION 11: page 20

1 1 . 2 : e m e r genc y lighting

by Honeywell
High Light Output 8W Luminaire
l A flexible high light output
luminaire
l A separate mounting bracket
and battery compartment
makes the Unilux easy to
install and maintain
l Elegant and functional design

LumHigh8 Luminaire

Technical Specification
UL8/m/3f UL8/Nm/3f
Mode Maintained Non-maintained
Emergency Duration 3 hours
Emergency Lamp O/P 137 lumens
Maintained Lamp O/P 150 lumens
Construction ABS / Polycarbonate, self extinguishing
Weight 1160g
Cable Entry 16mm/20mm cut-out on side of base. Also BESA entry from rear
Supply Voltage 230V ac, 50/60Hz
Power Consumption 18VA 16VA
Recharge Period Max 24 hours
Battery 3.6V 4.5Ah
IP Rating IP20
Certification CE, NEMKO

Mode LIST NUMBER DESCRIPTION


Self contained UL8/M/3F 8 watt maintained
Self contained UL8/NM/3F 8 watt non-maintained

Unilux Pictograms
PICTogram LIST NUMBER DESCRIPTION

LUM/DOWN Pictogram arrow down

LUM/UP Pictogram arrow up

Order Codes
LUM/RIGHT Pictogram arrow right
High Light Output 8W Luminaire,
IP20, Non-maintained UL8/NM/3F
LUM/LEFT Pictogram arrow left
High Light Output 8WLuminaire,
IP20, Maintained UL8/M/3F
Pictogram, arrow down LUM/DOWN
Pictogram, arrow up LUM/UP
Pictogram, arrow right LUM/RIGHT
Pictogram, arrow left LUM/LEFT
SECTION 11: page 21

1 1 . 2 : e m e r genc y lighting

by Honeywell
Rectangular 8W Exit Sign
l Cost effective lighting solution
for interior applications
l Suitable for mounting on
emergency escape routes as
defined by BS 5266
l Maintained/non-maintained
versions
l Single-sided low profile unit
with pictogram accessible
from bottom entry
l Integral threshold down-
lighter
l Robust construction for
simple surface-mounted
installation
l Range of self-adhesive
Rectangular Exit Sign
pictogram options

Technical Specification
XLS8/M/3F XLS8/NM/3F
Mode Maintained Non-maintained
Emergency Duration 3 hours
Emergency Lamp O/P 70 lumens
Maintained Lamp O/P 230 lumens N/A
Construction Rectangular mild steel housing
Dimensions H x L x D 385 x 205 x 65
Weight 2200g 2000g
Cable Entry 20mm knockouts in left, top and rear
Supply Voltage 230/240V ac 50/60Hz
Power Consumption Standby
4.2VA 4.0VA
Mode
Power Consumption Mains
19.0VA N/A
Mode
Recharge Period 24 hours
Battery 2 x 1.2V, 4000 mAh, Ni-Cd, high temp, rechargeable batteries pack
Light Source 8 watt T5 cool white fluorescent tube
Monitor Green LED monitoring mains supply and battery connection
Operating Temperature 0ºC to +30ºC
IP Rating N/A
Warranty 1 Year
Certification CE – EN 60598-2-22
Order Codes
Mode LIST NUMBER DESCRIPTION
Rectangular 8W Exit Sign,
Self contained XLS8/M/3F 8 watt maintained
IP20, Non-maintained XLS8/NM/3F
Self contained XLS8/NM/3F 8 watt non-maintained
Rectangular 8W Exit Sign,
XLS8 Pictograms
IP20, Maintained XLS8/M/3F
PICTogram LIST NUMBER DESCRIPTION
Pictogram for Rectangular Exit Sign,
EXIT/DOWN Pictogram arrow down arrow down EXIT/DOWN
Pictogram for Rectangular Exit Sign,
arrow up EXIT/UP
EXIT/UP Pictogram arrow up
Pictogram for Rectangular Exit Sign,
arrow right EXIT/RIGHT
EXIT/RIGHT Pictogram arrow right
Pictogram for Rectangular Exit Sign,
arrow left EXIT/LEFT

EXIT/LEFT Pictogram arrow left


SECTION 11: page 22

1 1 . 2 : e m e r genc y lighting

by Honeywell
2 x 18W Twinlight (Surtwin)
l Suitable for interior
applications
l Cost-effective solution
for large open areas with
undefined escape routes
l Non-maintained
l Ideal for illuminating
areas which could become
dangerous if mains
power fails
l Stylish design features
adjustable lamps with
polycarbonate lenses
l Snap-fit construction
l Simple to install
l Maintenance-free batteries 18W Twinlight
l A high intensity LED on
the unit front indicates Technical specification
healthy supply Mode Non-maintained
l Independent lamp tests give Emergency Duration 3 hours
indications of both left and Emergency Lamp O/P 2 x 280 lumens
right lamp integrity Construction Rectangular mild steel housing with PC lamp head
Dimensions H x L x D 340 x 315 x 115
Weight 7000g
Cable Entry 20mm knockouts in left, right, top and rear
Supply Voltage 230/240V 50/60Hz
Power Consumption 28.0VA
Recharge Period 24 hours
Battery 2 x sealed lead acid 12V 7.2Ah
Light Source G4 12V 20 watt 3200K Halogen lamp
Monitor 3 Green LED monitoring batteries and lamp connection
Operating Temperature 0ºC to +30ºC
IP Rating N/A
Warranty 1 Year
Certification CE – EN 60598-2-22

Mode LIST NUMBER DESCRIPTION


Self contained SURTWIN/NM 8 watt non-maintained

Order Codes
Twinlight, 2 x 18W, SURTWIN/NM
3-hour, IP20, Non-maintained
SECTION 11: page 23

1 1 . 2 : e m e r genc y lighting

by Honeywell
Photometric Data

Maximum permitted spacing to achieve 0.2 Lux (in metres)


Height (m) Axial to wall Axial to Axial
2.5 3.5 9.0
4 3.3 9.8
Axial
6 2.5 9.3
CA8/NM/3F 8 - 7.8
10 - -
Bulkhead
Height (m) Transverse to wall Transverse to Transverse
Non Maintained 2.5 5.3 13.7
4 5.7 15.7
Transverse
6 4.3 15.9
8 - 13.9
10 - -
Height (m) Axial to wall Axial to Axial
2.5 3.2 9.0
4 3.1 9.2
Axial
6 1.8 8.7
CA8/M/3F 8 - 6.5
10 - -
Bulkhead
Height (m) Transverse to wall Transverse to Transverse
Maintained 2.5 5.1 13.0
4 5.3 14.4
Transverse
6 3.3 14.8
8 - 10.8
10 - -
Height (m) Twinspot to wall Twinspot to Twinspot
4 10.4 25.2
SURTWIN Twinspot 6 10.6 26.6
8 11.6 28.6
10 13.8 25.8

Maximum permitted spacing to achieve 0.2 Lux (in metres)


Height (m) Axial to wall Axial to Axial
2.5 1.3 4.3
4 - 2.9
Axial
6 - -
CA8/NM/3F 8 - -
10 - -
Bulkhead
Height (m) Transverse to wall Transverse to Transverse
Non Maintained 2.5 2.2 7.4
4 - 4.8
Transverse
6 - -
8 - -
10 - -
Height (m) Axial to wall Axial to Axial
2.5 1.1 3.9
4 - 1.4
Axial
6 - -
CA8/M/3F 8 - -
10 - -
Bulkhead
Height (m) Transverse to wall Transverse to Transverse
Maintained 2.5 1.7 6.8
4 - 3.2
Transverse
6 - -
8 - -
10 - -
Height (m) Twinspot to wall Twinspot to Twinspot
4 5.2 13.3
SURTWIN Twinspot 6 5.0 12.4
8 4.4 11.2
10 3.2 8.1
SECTION 11: page 24

1 1 . 2 : e m e r genc y lighting

by Honeywell
Photometric Data
Illuminance perpendicular to beam (lux)
10m 20m
SURTWIN/NM 0 degrees 90 degrees 0 degrees 90 degrees
0 degrees 2.89 2.89 0.72 0.72
10 degrees 6.31 1.87 1.58 0.47
(data for single lamp) 12V 20 degrees 1.25 0.35 0.31 0.09
18W filament lamp 30 degrees 0.24 0.25 0.06 0.06
Lamp Output (1m):264 40 degrees 0.18 0.23 0.05 0.06
50 degrees 0.16 0.23 0.04 0.06
60 degrees 0.11 0.12 0.03 0.03

LUMINAIRE UTILISATION FACTOR DATA (self-contained luminaires at zero reflectance)


Room Index (RI)
0.75 1.00 1.25 1.50 2.00 2.50 3.00 4.00 5.00
CA8 - 0.25 0.28 0.31 0.37 0.40 0.43 0.47 0.50
UL8 - 0.29 0.33 0.37 0.44 0.48 0.52 0.56 0.59
Note: All photometric data has been compiled in accordance with BS 5225: Part 3 (Method of Photometric measurement of
battery-operated emergency lighting luminaires).

Escape route spacing using self contained luminaires


All figures are verified by the British
Min. - 1.0 LUX Min. - 0.2 LUX
Standards Institute and registered
Specified Points of Emphasis & Normal Risks Permanently Unobstructed Routes Only
by ICEL.
Ceiling Transverse to Transverse to
Transverse to Transverse to Axial to Axial Axial to Wall Transverse to Transverse to Axial to Axial Axial to Wall
Mounting Transverse Transverse
Wall (m) Axial (m) (m) (m) Wall (m) Axial (m) (m) (m)
Height (m) (m) (m)
2.5 1.3 4.7 4.4 4.0 1.2 4.5 12.4 10.0 7.6 3.0
Optilite / Stormlite
4 - 2.8 2.6 2.3 - 3.7 12.7 10.8 8.8 3.2
Non-Maintained
6 - - - - - 2.5 10.0 9.4 8.9 2.2
2.5 1.1 4.0 3.9 3.7 0.9 4.1 11.6 9.4 7.2 2.9
Optilite / Stormlite
4 - 1.5 1.1 0.8 - 3.2 11.6 10.0 8.3 2.9
Maintained
6 - - - - - 1.8 8.7 8.4 8.0 1.4

Note: Spacing data includes a maintenance factor of 0.8 and a maintained lamp derating factor of 0.85 as defined by BSI and ICEL.

Potrebbero piacerti anche