© Taco Catalog No. 100-9.0 Effective Date: July 1, 2010
Supersedes Date: July 1, 2007
TACO Zone Control Product Information
Switching Relays
Product No. Description
SR501 1 Zone Switching Relay
SR501-845RP 1 Zone Switching Relay Replacement PC Board for
Honeywell R845, RA89A, RA832 or Comparable Relay
SR502 2 Zone Switching Relay with Priority
SR503 3 Zone Switching Relay with Priority
SR504 4 Zone Switching Relay with Priority
SR506 6 Zone Switching Relay with Priority
Fan Controls
Product No. Description
HAFC101 Hydro Air Fan Control
HAFC201 Hydro Air Fan Control with Optional Time Delays
Do it once.
Do it right.
2
SR501 Switching Relay Wiring
THERMOSTAT THERMOSTAT
T T 24 VAC
SIGNAL
JUMPER
TO: ZC
TO: TT ON BOILER TO: ZR TO: TT ON BOILER
H
TO: 120 VAC POWER
N
TO: 120 VAC POWER
CIRCULATOR CIRCULATOR CIRCULATOR
3
(cont.)
L1 L2
THERMOSTATS
(HOT) (NEUTRAL)
CIRCUIT THERMOSTAT
BREAKER
ZONE 4
PRIORITY
ON
SR 504 OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4
CUSTOMER
EMERGENCY FOUR ZONE SWITCHING RELAY L1 L2 T T
WITH OPTIONAL PRIORITY
SWITCH
HONEYWELL L8124
POWER
ZONE 1
OR EQUAL
ZONE 2
C1 ZC
THERMAL ZONE 3
FUSE ZONE 4
B2 C2 ZR B1
(FIROMATIC) 24 VAC 120V RELAY
POWER
X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT CIRCULATOR
ON BOILER
(IF ATTACHED)
SERVICE
FUSE 1 AMP
SWITCH
LINE VOLTAGE
OIL BURNER RELAY
LOW
WATER
CUTOFF
L1 L2
(HOT) (NEUTRAL) THERMOSTAT
CIRCUIT THERMOSTAT
BREAKER
24 VAC
POWER
SR 503
ZONE 1 ZONE 2 ZONE 3
CUSTOMER
EMERGENCY THREE ZONE SWITCHING RELAY L1 L2 T T
FUSE 1 AMP WITH OPTIONAL PRIORITY
SWITCH
HONEYWELL L8124
POWER
ZONE 1
OR EQUAL
ZONE 2
C1 ZC
THERMAL ZONE 3
FUSE B2 C2 ZR B1
(FIROMATIC)
LOW
WATER
CUTOFF
NOTE: The boiler operating control’s ZC terminal will see the load of the circulator(s).
4
SR502/503 Switching Relay Controlling Another SR502/503 Switching Relay
AQUASTAT
ON DHW A T T
HEATER
MASTER
24 VAC
POWER
PRIORITY ON
VIA JUMPER
PLACEMENT SR 503 ZONE1 ZONE2 ZONE3
X2
N P ZC H X1 ZR ZONE1 ZONE2 ZONE3
JUMPER
120 VOLT
N CIRCULATORS
120 VAC POWER
H DHW
HEATER
CIRCULATOR
T T T PRIORITY OFF
VIA JUMPER
SLAVE PLACEMENT
24 VAC
POWER
X2
N P ZC H X1 ZR ZONE1 ZONE2 ZONE3
JUMPER
BOILER
5
SR502/503 Switching Relay Controlling Another SR504/506 Switching Relay
AQUASTAT
ON DHW
HEATER A T T
MASTER
PRIORITY ON
24 VAC VIA JUMPER
POWER
PLACEMENT
X2
N P ZC H X1 ZR ZONE1 ZONE2 ZONE3
JUMPERS
120 VOLT
CIRCULATORS
THERMOSTATS
T
SLAVE PRIORITY
ZONE 6 OFF
PRIORITY
ON
SR 506 ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
OFF
FUSE 1 AMP
H
REMOVE 120 VAC INPUT
JUMPER N
BOILER
6
Two SR504/506 Switching Relays Connected Together
AQUASTAT ON
A DHW HEATER
T T T
ZONE 4
PRIORITY
ON PRIORITY
OFF ON
SR 504 ZONE 1 ZONE 2 ZONE 3 ZONE 4
FUSE 1 AMP
DHW
HEATER
CIRCULATOR
T T T
BOILER
ZONE 4
PRIORITY
ON PRIORITY
OFF ON
SR 504 ZONE 1 ZONE 2 ZONE 3 ZONE 4
FUSE 1 AMP
H
120 VAC INPUT
JUMPER
TO: "TT" ON BOILER N
OUTPUT
NOT
USED
7
Priority Zoning Circulator Controlling SR504/506 Switching Relay
MASTER
PRIORITY
ON
PRIORITY ZONING CIRCULATOR
PRIORITY
OFF ON
AQUASTAT ON
DHW HEATER
THERMOSTATS
T PRIORITY
SLAVE OFF
ZONE 6
PRIORITY
ON
SR 506 ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
OFF
FUSE 1 AMP
H
REMOVE 120 VAC INPUT
JUMPER N
BOILER
8
Priority Zoning Circulator Controlling 2 SR504/506 Switching Relays
MASTER
T T T T T T T T
SLAVE SLAVE
ZONE 4 PRIORITY ZONE 4 PRIORITY
PRIORITY OFF PRIORITY OFF
ON ON
SR 504 OFF SR 504 OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 1 ZONE 2 ZONE 3 ZONE 4
X X ZONE1 ZONE2 ZONE3 ZONE4 POWER X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT SWITCH 120 VOLT CIRCULATORS INPUT
24 VAC
POWER
24 VAC
POWER
FUSE 1 AMP FUSE 1 AMP
REMOVE REMOVE
JUMPER JUMPER
9
10
SR502/503 Switching Relay Controlling 2 SR504/506 Switching Relays
AQUASTAT ON
DHW HEATER
A T T
MASTER
PRIORITY
24 VAC
POWER ON
X2
N P ZC H X1 ZR ZONE1 ZONE2 ZONE3
JUMPER
T T T T T T T T
SLAVE SLAVE
ZONE 4 PRIORITY ZONE 4 PRIORITY
PRIORITY OFF PRIORITY OFF
ON ON
SR 504 OFF SR 504 OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 1 ZONE 2 ZONE 3 ZONE 4
X X ZONE1 ZONE2 ZONE3 ZONE4 POWER X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT SWITCH 120 VOLT CIRCULATORS INPUT
24 VAC
POWER
24 VAC
POWER
FUSE 1 AMP FUSE 1 AMP
REMOVE REMOVE
JUMPER JUMPER
24
R W VAC
SR501 T T COM
POWER
1 ZONE SWITCHING RELAY
T STAT
JUMPER
DHW
CIRCULATOR
T T T T T T T T
SLAVE PRIORITY OFF SLAVE PRIORITY OFF
ZONE 4 ZONE 4
PRIORITY PRIORITY
ON ON
SR 504 OFF SR 504 OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 1 ZONE 2 ZONE 3 ZONE 4
REMOVE REMOVE
JUMPER JUMPER
11
SR501-EXP Switching Relay Controlling Another SR504/506 Switching Relay
AQUASTAT ON
DHW HEATER
MODE
POWER
MASTER CONTROLS RESET
END ZONE
EXPANSION THERMOSTAT
SWITCH VALVE
NORMAL
SLAVE
X X 1 2 3 4 T/R T/W COM 1 2
FUSE
1 AMP
SR 501-EXP
MASTER
POWER
FUSE T STAT
5 AMP
N H ZC ZR H H
POWER 120VAC 120VAC CIRC PRIORITY
INPUT INPUT OUTPUT OUTPUT OUTPUT
DHW CIRCULATOR
JUMPER
T THERMOSTATS
SLAVE PRIORITY
ZONE 6 OFF
PRIORITY
ON
SR 506 ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
OFF
FUSE 1 AMP
H
REMOVE 120 VAC INPUT
JUMPER N
BOILER
12
SR501-EXP Switching Relay Controlling a ZVC404/406 Zone Valve Control
AQUASTAT ON
MASTER DHW HEATER
TO BOILER AQUASTAT RELAY A
TO: OPTIONAL ZONE VALVE
OR iSeries MIXING VALVE
MODE
POWER
CONTROLS RESET
END ZONE
EXPANSION THERMOSTAT
SWITCH VALVE
NORMAL
X X 1 2 3 4 T/R T/W COM 1 2
SLAVE
FUSE
1 AMP SR 501-EXP
MASTER
POWER
FUSE T STAT
5 AMP
N H ZC ZR H H
POWER 120VAC 120VAC CIRC PRIORITY
INPUT INPUT OUTPUT OUTPUT OUTPUT
THERMOSTAT THERMOSTAT THERMOSTAT
DHW
HEATER
CIRCULATOR
JUMPER
T T T
24 VAC
SLAVE
WHITE ZONE 6 PRIORITY
MODE
120 VAC N NORMAL RESET
120 VAC 24 VAC OFF
INPUT INPUT T STAT 1
FACTORY
H ON
INSTALLED
BLACK VALVE 1
TRANSFORMER
POWER IN
T T T T T T T T T T T T
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 T STAT 2
VALVE 2
T STAT 3
ZVC 406 VALVE 3
WHITE T STAT 4
120 VAC
SIX ZONE ZONE VALVE CONTROL VALVE 4
24 VAC
INPUT
FUSE (7 AMP MAX)
FACTORY
WITH OPTIONAL PRIORITY T STAT 5
INSTALLED
BLACK
TRANSFORMER
VALVE 5
T STAT 6
MAIN EXTRA N/O COM N/C
END END ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
SWITCH SWITCH ZONE 6 RELAY VALVE 6
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
POWER
JUMPER JUMPER
3&4 3&4
SEE NOTE
PRIORITY
ZONE
BOILER 1 MOTOR END
SYSTEM SWITCH
2
PUMP
3
BOILER TURNS ON WHEN ANY ZONE VALVE OPENS. Note: When a circulator is used on the
2 WIRE ZONE VALVE TACO 4 WIRE
(NO END SWITCH) 3 WIRE ZONE VALVE ZONE VALVE
priority zone instead of a zone valve,
SYSTEM PUMP TURNS ON WHEN ANY ZONE VALVE OPENS (POWER OPEN, SELF CLOSING) jumper 3 and 4 of the priority zone.
EXCEPT WHEN THE DHW HEATER (SR501-EXP) CALLS.
13
2 Expandable Switching Relays Connected Together
SWITCH SETTINGS
Master/Slave: Slave
Reset/Normal: Normal
Priority Zone: Off THERMOSTATS
T
SLAVE
SLAVE PLUG-IN CARDS ZONE 4
PRIORITY
MASTER 1 2 3 4 ON
POWER EXPANSION OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4
CONTROL
INTERFACE
SR504-EXP
RESET NORMAL FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
POWER
ZONE 1
ZONE 2
ZONE 3
ZONE 4
24 VAC 120V RELAY
POWER
SR 504-EXP
X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT
FUSE 1 AMP
SWITCH SETTINGS
Master/Slave: Master
Reset/Normal: Normal
Priority Zone: On
THERMOSTATS AQUASTAT
ON DHW
T A HEATER
MASTER
SLAVE PLUG-IN CARDS ZONE 6
PRIORITY
POWER MASTER ON
CONTROL 1 2 3 4 OFF
INTERFACE EXPANSION ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
SR 506-EXP
RESET NORMAL SIX ZONE SWITCHING RELAY
POWER
WITH OPTIONAL PRIORITY ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
24 VAC ZONE 6
120V RELAY
POWER
X X ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6 POWER
END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT
FUSE 1 AMP
H
JUMPER
N
TO: "TT" ON BOILER 120 VAC INPUT
BOILER DHW
CIRCULATOR
14
2 Indirect Water Heaters with Priority Connected to Standard Switching Relays
AQUASTATS ON
DHW HEATERS
A A
PRIORITY
MASTER 24 VAC
POWER OFF
X2
N P ZC H X1 ZR ZONE1 ZONE2 ZONE3
JUMPERS
T T T T T T
SLAVE SLAVE
ZONE 4 PRIORITY ZONE 4 PRIORITY
PRIORITY ON PRIORITY ON
ON ON
SR 504 OFF SR 504 OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 1 ZONE 2 ZONE 3 ZONE 4
JUMPER JUMPER
ZONE
ZONE
NOT
NOT
USED
USED
15
16
2 Indirect Water Heaters with Priority Connected to EXP Switching Relays
AQUASTATS ON
A A DHW HEATERS
24 VAC
PRIORITY
POWER OFF
X2
N P ZC H X1 ZR ZONE1 ZONE2 ZONE3
JUMPERS
DHW
CIRCULATORS
SWITCH SETTINGS
Master/Slave: Slave
SWITCH SETTINGS Reset/Normal: Normal
Master/Slave: Master Priority Zone: Off
Reset/Normal: Normal
Priority Zone: On T T
MASTER SLAVE
SLAVE PLUG-IN CARDS ZONE 4 SLAVE PLUG-IN CARDS ZONE 4
PRIORITY PRIORITY
MASTER 1 2 3 4 ON MASTER ON
POWER EXPANSION OFF POWER 1 2 3 4 OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 1 ZONE 2 ZONE 3 ZONE 4
CONTROL CONTROL EXPANSION
INTERFACE INTERFACE
SR504-EXP SR504-EXP
RESET NORMAL FOUR ZONE SWITCHING RELAY RESET NORMAL FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY WITH OPTIONAL PRIORITY
POWER POWER
ZONE 1 ZONE 1
ZONE 2 ZONE 2
ZONE 3 ZONE 3
ZONE 4 ZONE 4
24 VAC 120V RELAY 24 VAC 120V RELAY
POWER
SR 504-EXP POWER
SR 504-EXP
X X ZONE1 ZONE2 ZONE3 ZONE4 POWER X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT SWITCH 120 VOLT CIRCULATORS INPUT
JUMPER JUMPER
OUTDOOR
SENSOR
SWITCH SETTINGS
Master/Slave: Master
Reset/Normal: Reset
PC700 THERMOSTAT
END ZONE
EXPANSION THERMOSTAT
SWITCH VALVE
NORMAL
SLAVE
X X 1 2 3 4 T/R T/W COM 1 2
FUSE
1 AMP
SR 501-EXP
MASTER
POWER
FUSE T STAT
5 AMP
N H ZC ZR H H
POWER 120VAC 120VAC CIRC PRIORITY
INPUT INPUT OUTPUT OUTPUT OUTPUT
BOILER
JUMPER
H SYSTEM
120 VAC INPUT CIRCULATOR
N
17
SR501-EXP and PC700 Boiler Reset Control Connected to an Existing Switching Relay
OUTDOOR
SENSOR AQUASTAT ON
A DHW HEATER
Note: If Zone Control comes on without a call for heat,
reverse Reset Override input (1 & 2) wires on SR501-EXP.
TO: "TT" ON BOILER
PC700
EXISTING THERMOSTATS T
POWER
BOIL OUT ZONE CONTROLS ZONE
SEN SEN CONTROL CONTROL
END RESET MODE
EXPANSION THERMOSTAT
SWITCH OVERRIDE RESET ZONE 4
X X 1 2 3 4 T/R T/W COM 1 2 SR 504 PRIORITY
ON
K1-A ZONE1 ZONE2 ZONE3 ZONE4
BOILER SENSOR MASTER OFF
FUSE
1 AMP SR 501-EXP NORMAL
FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY POWER
ZONE 1
SLAVE ZONE 2
K1 K2 POWER
ZONE 3
T STAT ZONE 4
FUSE
5 AMP 120V RELAY
24 VAC
POWER
K1-B K2-A K2-A X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT
N H ZC ZR H H
POWER 120VAC 120VAC CIRC PRIORITY
INPUT INPUT OUTPUT OUTPUT OUTPUT FUSE 1 AMP
JUMPER
MASTER
JUMPER
PRIMARY
SYSTEM
CIRCULATOR DHW
BOILER (Optional) HEATER
CIRCULATOR 120 VAC
INPUT
H
N
T THERMOSTATS
PC700 MASTER
EXISTING
POWER
BOIL OUT ZONE CONTROLS ZONE
SEN SEN CONTROL CONTROL SLAVE
END RESET MODE
EXPANSION THERMOSTAT
SWITCH OVERRIDE RESET ZONE 4
X X 1 2 3 4 T/R T/W COM 1 2 SR 504 PRIORITY
ON
ZONE1 ZONE2 ZONE3 ZONE4
BOILER SENSOR K1-A
MASTER OFF
FUSE
1 AMP SR 501-EXP NORMAL
FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY POWER
ZONE 1
SLAVE ZONE 2
K1 K2 POWER
ZONE 3
T STAT ZONE 4
FUSE
5 AMP 120V RELAY
24 VAC
POWER
JUMPER
REMOVE
DHW JUMPER
HEATER
BOILER CIRCULATOR 120 VAC
INPUT
H
N
18
SR501-EXP and PC700 Boiler Reset Control Connected to an Existing Zone Valve Control
OUTDOOR
SENSOR AQUASTAT ON
Note: If Zone Control comes on without a call for heat, A DHW HEATER
reverse Reset Override input (1 & 2) wires on SR501-EXP.
TO: "TT" ON BOILER
THERMOSTATS
EXISTING T T T
TRANSFORMER
PC700 WHITE
INSTALLED
FACTORY
120 VAC
INPUT
24
VAC
ZONE
POWER
BOIL OUT ZONE CONTROLS BLACK CONTROL 24 VAC
SEN SEN CONTROL
MODE ZONE 4
END RESET MODE PRIORITY
SWITCH
EXPANSION THERMOSTAT
OVERRIDE
NORMAL RESET
RESET OFF
(3 AMP MAX)
ZVC 404 VALVE 2
FUSE
FOUR ZONE ZONE VALVE CONTROL T STAT 3
SLAVE
K1 K2 POWER VALVE 3
WITH OPTIONAL PRIORITY
T STAT T STAT 4
FUSE VALVE 4
5 AMP
POWER
MAIN
END
EXTRA
END
N/O COM N/C ZONE 1 ZONE 2 ZONE 3 ZONE 4
SWITCH SWITCH ZONE 4 RELAY
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
K1-B K2-A K2-A
N H ZC ZR H H
POWER 120VAC 120VAC CIRC PRIORITY
JUMPER JUMPER
INPUT INPUT OUTPUT OUTPUT OUTPUT 3&4
3&4
SEE NOTE
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
3
H 120 VAC
N INPUT
EXISTING T T T
TRANSFORMER
120 VAC
INPUT
24
VAC
ZONE
POWER
BOIL OUT ZONE CONTROLS BLACK CONTROL 24 VAC SLAVE
SEN SEN CONTROL
MODE ZONE 4
END RESET MODE PRIORITY
SWITCH
EXPANSION THERMOSTAT
OVERRIDE
NORMAL RESET
RESET OFF
X X 1 2 3 4 T/R T/W COM 1 2 POWER IN T T T T T T T T ON
K1-A ZONE 1 ZONE 2 ZONE 3 ZONE 4 T STAT 1
BOILER SENSOR MASTER
VALVE 1
FUSE
1 AMP SR 501-EXP NORMAL
T STAT 2
(3 AMP MAX)
N H ZC ZR H H
POWER 120VAC 120VAC CIRC PRIORITY
JUMPER JUMPER
INPUT INPUT OUTPUT OUTPUT OUTPUT 3&4
3&4 SEE NOTE
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
3
H 120 VAC
N INPUT
19
SR501-EXP and PC700 Boiler Reset Control Connected to an Existing
Tankless Coil Boiler – Zoning with Circulators
OUTDOOR
SENSOR T THERMOSTATS
EXISTING
POWER
CONTROLS ZONE
CONTROL
END RESET MODE
EXPANSION THERMOSTAT
SWITCH OVERRIDE RESET ZONE 4
PC700 X X 1 2 3 4 T/R T/W COM 1 2 SR 504 PRIORITY
ON
K1-A ZONE1 ZONE2 ZONE3 ZONE4
MASTER OFF
BOIL OUT ZONE
FUSE
1 AMP SR 501-EXP NORMAL
FOUR ZONE SWITCHING RELAY
SEN SEN CONTROL POWER
WITH OPTIONAL PRIORITY
ZONE 1
SLAVE ZONE 2
K1 K2 POWER
ZONE 3
BOILER SENSOR T STAT ZONE 4
FUSE
5 AMP 120V RELAY
24 VAC
POWER
K1-B K2-A K2-A X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT
N H ZC ZR H H
POWER 120VAC 120VAC CIRC PRIORITY
INPUT INPUT OUTPUT OUTPUT OUTPUT FUSE 1 AMP
JUMPER
PRIMARY REMOVE
SYSTEM JUMPER
CIRCULATOR
(Optional)
TO: "ZR" ON BOILER CONTROL
120 VAC
TO: "ZC" ON BOILER CONTROL INPUT
H
BOILER
N
Boiler and Zone Control(s) need to be on same power supply (same circuit breaker).
THERMOSTATS
TRANSFORMER
WHITE
INSTALLED
FACTORY
N H ZC ZR H H
POWER 120VAC 120VAC CIRC PRIORITY JUMPER JUMPER
INPUT INPUT OUTPUT OUTPUT OUTPUT 3&4
3&4
SEE NOTE
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
3
Boiler and Zone Control(s) need to be on same power supply (same circuit breaker).
20
PC700 Boiler Reset Control Connected to EXP Switching Relay
OUTDOOR
SENSOR
SWITCH SETTINGS
THERMOSTATS
Master/Slave: Master
Reset/Normal: Reset
Priority Zone: On or Off
T
PC700
SLAVE 1234 PLUG-IN CARDS ZONE 4
BOIL OUT ZONE PRIORITY
SEN SEN CONTROL ON
MASTER
POWER OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4
CONTROL
INTERFACE
BOILER SENSOR SR 504-EXP
RESET NORMAL FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
POWER
ZONE 1
ZONE 2
ZONE 3
ZONE 4
24 VAC 120V RELAY
POWER
X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT
FUSE 1 AMP
H
JUMPER 120 VAC INPUT
N
TO: "TT" ON BOILER
BOILER
21
22
PC702 2–Stage Boiler Reset Control Connected to EXP Switching Relay
OUTDOOR
SENSOR
DHW
DEMAND
SWITCH SETTINGS
Master/Slave: Master
PC702 THERMOSTATS
Reset/Normal: Normal
Priority Zone: On or Off
STAGE STAGE BOIL OUT ZONE
T
1 2 SEN SEN CONTROL
FUSE 1 AMP
H
JUMPER 120 VAC INPUT
N
BOILER
#2
SYSTEM
WIRING NEEDED ONLY IF CIRCULATOR
PRIORITY ZONE IS DHW (OPTIONAL)
PC705 Variable Speed Pump Injection Control Connected to EXP Switching Relay
SWITCH SETTINGS
THERMOSTATS
OUTDOOR
SENSOR GREEN/GROUND Master/Slave: Master
Reset/Normal: Reset
Priority Zone: On or Off T
(SEE NOTE B)
RED
SYSTEM
CIRCULATOR SLAVE 1234 PLUG-IN CARDS ZONE 4
AND/OR BOILER PRIORITY
BLUE
MASTER ON
PC705-2 OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4
INJECTION
BOIL SUP OUT ZONE BLACK CIRCULATOR
SEN SEN SEN CONTROL SR 504-EXP
RESET NORMAL FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
SUPPLY SENSOR POWER
ZONE 1
BOILER SENSOR
ZONE 2
ZONE 3
ZONE 4
24 VAC 120V RELAY
POWER
X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT
FUSE 1 AMP
JUMPER
TO: "TT" ON BOILER
SYSTEM
BOILER CIRCULATOR
AND/OR BOILER
(SEE NOTE A)
N
120 VAC INPUT
H
NOTE A: WHEN SYSTEM CIRCULATOR IS CONNECTED TO ZR TERMINAL ON SWITCHING RELAY, THE MODE SWITCH MUST BE SET TO NORMAL.
THE PC705-2 WILL NOT RESET THE BOILER WHEN IN THE NORMAL MODE.
NOTE B: WHEN SYSTEM CIRCULATOR IS CONNECTED TO RED WIRE ON PC705-2, THE CIRCULATOR WILL OPERATE ONLY WHEN THERMOSTAT CALLS FOR HEAT
AND THE OUTDOOR TEMPERATURE IS BELOW THE WARM WEATHER SHUT DOWN (WWSD) TEMPERATURE. THE WWSD CAN BE ADJUSTED OR TURNED
OFF SO THAT THE CIRCULATOR IS NOT AFFECTED BY OUTDOOR TEMPERATURE.
23
PC700 Boiler Reset Control Connected to 2 EXP Switching Relays
OUTDOOR
SENSOR
SWITCH SETTINGS
Master/Slave: Master THERMOSTATS
Reset/Normal: Reset
Priority Zone: On or Off T
MASTER
PC700 SLAVE PLUG-IN CARDS ZONE 4
PRIORITY
BOIL OUT ZONE MASTER 1 2 3 4 ON
SEN SEN CONTROL
POWER EXPANSION OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4
CONTROL
INTERFACE
SR 504-EXP
BOILER SENSOR
RESET NORMAL FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
POWER
ZONE 1
ZONE 2
ZONE 3
ZONE 4
24 VAC 120V RELAY
POWER
X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT
FUSE 1 AMP
SWITCH SETTINGS
THERMOSTATS
Master/Slave: Slave
Reset/Normal: Normal T
Priority Zone: No Priority SLAVE
SLAVE PLUG-IN CARDS ZONE 4
PRIORITY
MASTER 1 2 3 4 ON
POWER EXPANSION OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4
CONTROL
INTERFACE
SR 504-EXP
RESET NORMAL FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
POWER
ZONE 1
ZONE 2
ZONE 3
ZONE 4
24 VAC 120V RELAY
POWER
X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT
FUSE 1 AMP
JUMPER
H
N
120 VAC INPUT
SYSTEM
CIRCULATOR
(OPTIONAL)
24
PC702 2–Stage Boiler Reset Control Connected to 2 EXP Switching Relays
OUTDOOR
SENSOR SWITCH SETTINGS
Master/Slave: Master
THERMOSTATS
Reset/Normal: Normal
DHW
Priority Zone: On or Off
DEMAND
T
MASTER
PC702
SLAVE PLUG-IN CARDS ZONE 4
PRIORITY
STAGE STAGE BOIL OUT ZONE
MASTER 1 2 3 4 ON
1 2 SEN SEN CONTROL
POWER EXPANSION OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4
CONTROL
INTERFACE
BOILER SENSOR SR 504-EXP
RESET NORMAL FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
POWER
ZONE 1
ZONE 2
ZONE 3
ZONE 4
24 VAC 120V RELAY
POWER
BOILER X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
#1 END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT
FUSE 1 AMP
BOILER
#2
SWITCH SETTINGS
Master/Slave: Slave
THERMOSTATS
Reset/Normal: Normal
Priority Zone: No Priority
T
SLAVE
SLAVE PLUG-IN CARDS ZONE 4
PRIORITY
MASTER 1 2 3 4 ON
POWER EXPANSION OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4
CONTROL
INTERFACE
SR 504-EXP
RESET NORMAL FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
POWER
ZONE 1
ZONE 2
ZONE 3
ZONE 4
24 VAC 120V RELAY
POWER
X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT
FUSE 1 AMP
H
JUMPER
N
120 VAC INPUT
SYSTEM
CIRCULATOR
(OPTIONAL)
25
PC705 Variable Speed Pump Injection Control Connected to 2 EXP Switching Relays
SWITCH SETTINGS
Master/Slave: Master
Reset/Normal: Reset THERMOSTATS
Priority Zone: On or Off
T
OUTDOOR
SENSOR GREEN/GROUND MASTER
(SEE NOTE B SLAVE PLUG-IN CARDS ZONE 4
ON PAGE 23) PRIORITY
MASTER 1 2 3 4 ON
RED EXPANSION OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4
SYSTEM
CIRCULATOR
BLUE SR 504-EXP
PC705-2
RESET NORMAL FOUR ZONE SWITCHING RELAY
INJECTION WITH OPTIONAL PRIORITY
BOIL SUP OUT ZONE BLACK CIRCULATOR POWER
SEN SEN SEN CONTROL
ZONE 1
ZONE 2
ZONE 3
SUPPLY SENSOR
ZONE 4
24 VAC 120V RELAY
BOILER SENSOR
POWER
X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT
FUSE 1 AMP
JUMPER
TO: "TT" ON BOILER 120 VAC
INPUT
BOILER
SWITCH SETTINGS
Master/Slave: Slave THERMOSTATS
Reset/Normal: Normal
Priority Zone: No Priority T
SLAVE
SLAVE PLUG-IN CARDS ZONE 4
PRIORITY
MASTER 1 2 3 4 ON
POWER EXPANSION OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4
CONTROL
INTERFACE
SR 504-EXP
RESET NORMAL FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
POWER
ZONE 1
ZONE 2
ZONE 3
ZONE 4
24 VAC 120V RELAY
POWER
X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT
FUSE 1 AMP
H
JUMPER
N
120 VAC INPUT
SYSTEM
CIRCULATOR
(OPTIONAL)
(SEE NOTE A ON PAGE 23)
26
PC700 and PC705 Controls Connected to 2 EXP Switching Relays
OUTDOOR
SENSOR
SWITCH SETTINGS
FUSE 1 AMP
BOILER
SWITCH SETTINGS
Master/Slave: Slave
Reset/Normal: Normal
Priority Zone: No Priority
THERMOSTATS
OUTDOOR
SENSOR GREEN/GROUND
(SEE NOTE B
T
ON PAGE 23) SLAVE
SLAVE PLUG-IN CARDS ZONE 4
RED
PRIORITY
SYSTEM
MASTER 1 2 3 4 ON
CIRCULATOR OFF
BLUE EXPANSION ZONE 1 ZONE 2 ZONE 3 ZONE 4
PC705-2
INJECTION
SR 504-EXP
BOIL SUP OUT ZONE BLACK CIRCULATOR FOUR ZONE SWITCHING RELAY
SEN SEN SEN CONTROL RESET NORMAL
WITH OPTIONAL PRIORITY
POWER
ZONE 1
SUPPLY SENSOR
ZONE 2
ZONE 3
BOILER SENSOR
ZONE 4
24 VAC 120V RELAY
POWER
X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT
FUSE 1 AMP
JUMPER
SYSTEM CIRCULATOR
(OPTIONAL LOCATION)
(SEE NOTE A ON PAGE 23)
H
N
120 VAC INPUT
27
PC702 and PC705 Controls Connected to 2 EXP Switching Relays
SWITCH SETTINGS
OUTDOOR
SENSOR
Master/Slave: Master
Reset/Normal: Normal THERMOSTATS
Priority Zone: On or Off
T
DHW
DEMAND MASTER
SLAVE PLUG-IN CARDS ZONE 4
PRIORITY
PC702 1 2 3 4 ON
MASTER
POWER EXPANSION OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4
STAGE STAGE BOIL OUT ZONE CONTROL
1 2 SEN SEN CONTROL INTERFACE
SR 504-EXP
RESET NORMAL FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
BOILER SENSOR
POWER
ZONE 1
ZONE 2
ZONE 3
ZONE 4
24 VAC 120V RELAY
POWER
X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT
BOILER
#1
FUSE 1 AMP
BOILER
#2
SWITCH SETTINGS
Master/Slave: Slave
Reset/Normal: Normal
THERMOSTATS
Priority Zone: No Priority
OUTDOOR
SENSOR
GREEN/GROUND
T
(SEE NOTE B
ON PAGE 23) SLAVE
SLAVE PLUG-IN CARDS ZONE 4
RED PRIORITY
SYSTEM MASTER 1 2 3 4 ON
BLUE
CIRCULATOR
EXPANSION OFF
ZONE 1 ZONE 2 ZONE 3 ZONE 4
PC705-2
INJECTION
SR 504-EXP
BOIL SUP OUT ZONE BLACK CIRCULATOR RESET NORMAL FOUR ZONE SWITCHING RELAY
SEN SEN SEN CONTROL
WITH OPTIONAL PRIORITY
POWER
ZONE 1
SUPPLY SENSOR ZONE 2
ZONE 3
BOILER SENSOR
ZONE 4
24 VAC 120V RELAY
POWER
X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT
FUSE 1 AMP
JUMPER
SYSTEM CIRCULATOR
(OPTIONAL LOCATION)
(SEE NOTE A ON PAGE 23)
H
N
120 VAC INPUT
28
ZVC403/405 with System Pump
T T T
WHITE
24 VAC
N 120 VAC 24 VAC
INPUT
FACTORY
H
INSTALLED
BLACK
TRANSFORMER
T STAT 1
POWER IN
T T T T T T T T T T
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 VALVE 1
WHITE
T STAT 2
120 VAC 24 VAC
INPUT VALVE 2
FACTORY
INSTALLED
BLACK ZVC 405 T STAT 3
TRANSFORMER
VALVE 3
FIVE ZONE ZONE VALVE CONTROL T STAT 4
JUMPER
3&4
TO BOILER AQUASTAT RELAY
1 MOTOR END
SWITCH
2
BOILER 3
29
30
ZVC404/406 with System Pump
AQUASTAT ON
T T T A DHW HEATER
WHITE
24 VAC
N 120 VAC 24 VAC
INPUT
FACTORY
H
INSTALLED
BLACK
TRANSFORMER
MODE ZONE 6 PRIORITY
NORMAL RESET
OFF
T STAT 1
ON
VALVE 1
POWER IN
T T T T T T T T T T T T
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 T STAT 2
WHITE
VALVE 2
120 VAC 24 VAC
INPUT T STAT 3
FACTORY
INSTALLED
BLACK ZVC 406 VALVE 3
TRANSFORMER
T STAT 4
SIX ZONE ZONE VALVE CONTROL VALVE 4
JUMPER JUMPER
3&4 3&4
SEE NOTE
TO BOILER AQUASTAT RELAY
PRIORITY
ZONE
DRY 1 MOTOR END
CONTACTS SWITCH
2
BOILER 3
AQUASTAT ON
T T T A DHW HEATER
WHITE
24 VAC
N 120 VAC 24 VAC
INPUT
FACTORY
H
INSTALLED
BLACK
TRANSFORMER
ZONE 6 PRIORITY
MODE
NORMAL RESET
OFF
T STAT 1
ON
VALVE 1
POWER IN
T T T T T T T T T T T T
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 T STAT 2
WHITE
VALVE 2
120 VAC 24 VAC
INPUT T STAT 3
FACTORY
INSTALLED
BLACK ZVC 406 VALVE 3
TRANSFORMER
T STAT 4
SIX ZONE ZONE VALVE CONTROL VALVE 4
JUMPER JUMPER
3&4 3&4
SEE NOTE
TO BOILER AQUASTAT RELAY
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
BOILER 3
31
32
ZVC404/406 with System and DHW Pumps
AQUASTAT ON
T T T A DHW HEATER
WHITE
24 VAC
N 120 VAC 24 VAC
INPUT
FACTORY
H
INSTALLED
BLACK
TRANSFORMER
ZONE 6 PRIORITY
MODE
NORMAL RESET
OFF
T STAT 1
ON
VALVE 1
POWER IN
T T T T T T T T T T T T
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 T STAT 2
WHITE
VALVE 2
120 VAC 24 VAC
INPUT T STAT 3
FACTORY
INSTALLED
BLACK ZVC 406 VALVE 3
TRANSFORMER
T STAT 4
SIX ZONE ZONE VALVE CONTROL VALVE 4
JUMPER JUMPER
3&4 3&4
SEE NOTE
TO BOILER AQUASTAT RELAY
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
BOILER SYSTEM 3
PUMP
DHW 2 WIRE ZONE VALVE TACO 4 WIRE ZONE VALVE
PUMP (NO END SWITCH) 3 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
AQUASTAT ON
T T T A DHW HEATER
WHITE
24 VAC
N 120 VAC 24 VAC
INPUT
FACTORY
H
INSTALLED
BLACK
TRANSFORMER
ZONE 6 PRIORITY
MODE
NORMAL RESET
OFF
T STAT 1
ON
VALVE 1
POWER IN
T T T T T T T T T T T T
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 T STAT 2
WHITE
VALVE 2
120 VAC 24 VAC
INPUT T STAT 3
FACTORY
INSTALLED
BLACK ZVC 406 VALVE 3
TRANSFORMER
T STAT 4
SIX ZONE ZONE VALVE CONTROL VALVE 4
SECONDARY
PUMP
Note: When a circulator is used on the
SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS. priority zone instead of a zone valve,
DHW PUMP TURNS ON ONLY WHEN PRIORITY ZONE CALLS. jumper 3 and 4 of the priority zone.
SECONDARY PUMP COMES ON WHEN ANY ZONE CALLS EXCEPT PRIORITY ZONE.
33
2 ZVC404/406 Connected Together with Priority
T T T
24 VAC
OFF
FACTORY
N
120 VAC 24 ON
INPUT VAC
H BLACK
POWER IN T T T T T T T T
ZONE 1 ZONE 2 ZONE 3 ZONE 4 T STAT 1
VALVE 1
TO BOILER
AQUASTAT RELAY
JUMPER JUMPER
3&4
3&4 SEE NOTE
PRIORITY
ZONE
DRY 1 MOTOR END
SWITCH
CONTACTS 2
3
AQUASTAT ON
DHW HEATER
THERMOSTAT THERMOSTAT THERMOSTAT A
T T T
24 VAC
ZONE 4 PRIORITY
PRIORITY
MODE ON
TRANSFORMER
NORMAL RESET
WHITE
INSTALLED
OFF
FACTORY
120 VAC 24 ON
INPUT VAC
BLACK
POWER IN T T T T T T T T
ZONE 1 ZONE 2 ZONE 3 ZONE 4 T STAT 1
VALVE 1
FUSE (3 AMP MAX)
T STAT 2
ZVC 404 VALVE 2
T STAT 3
FOUR ZONE ZONE VALVE CONTROL
VALVE 3
WITH OPTIONAL PRIORITY
T STAT 4
VALVE 4
POWER
MAIN
END
EXTRA
END
N/O COM N/C ZONE 1 ZONE 2 ZONE 3 ZONE 4
ZONE 4 RELAY 1 2 3 4
SWITCH SWITCH 1 2 3 4 1 2 3 4 1 2 3 4
JUMPER JUMPER
3&4 3&4
SEE NOTE
TO BOILER AQUASTAT RELAY PRIORITY
ZONE
BOILER DRY 1 MOTOR END
SWITCH
CONTACTS 2
3
34
2 EXP Zone Valve Controls Connected Together with System Pump
SWITCH SETTINGS
Master/Slave: Master
Reset/Normal: Normal
Priority Zone: On AQUASTAT ON
A DHW HEATER
T T T
24 VAC
MASTER
TRANSFORMER
PLUG-IN ZONE 6
WHITE
INSTALLED
CARDS PRIORITY
FACTORY
120 VAC ON
POWER IN
24 VAC SLAVE T STAT 1
INPUT 1 2 3 4 T T T T T T T T T T T T
POWER OFF
BLACK EXPANSION ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 VALVE 1
CONTROLS
MASTER T STAT 2
MODE
RESET NORMAL
ZVC 406-EXP VALVE 2
SIX ZONE ZONE VALVE CONTROL
TACO, INC ZVC406-EXP
T STAT 3
WHITE T STAT 5
INSTALLED
FACTORY
JUMPER
JUMPER 3&4
3&4 SEE NOTE
PRIORITY
TO BOILER AQUASTAT RELAY ZONE
1 MOTOR END
SWITCH
2
BOILER
3
N 120 VAC
H INPUT
SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
SWITCH SETTINGS
Master/Slave: Slave
Reset/Normal: Normal
Priority Zone: Off
T T T
SLAVE
TRANSFORMER
PLUG-IN ZONE 6
WHITE
INSTALLED
CARDS PRIORITY
FACTORY
120 VAC ON
POWER IN
T STAT 3
FUSE 7 AMP MAX
WHITE T STAT 5
INSTALLED
FACTORY
JUMPER
DRY JUMPER 3&4
CONTACTS 3&4 SEE NOTE
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
3
35
2 EXP Zone Valve Controls Connected Together with DHW Pump
SWITCH SETTINGS
Master/Slave: Master
Reset/Normal: Normal
Priority Zone: On AQUASTAT ON
A DHW HEATER
T T T
24 VAC
MASTER
TRANSFORMER
PLUG-IN ZONE 6
WHITE
INSTALLED
CARDS PRIORITY
FACTORY
120 VAC ON
POWER IN
T STAT 3
WHITE T STAT 5
INSTALLED
FACTORY
TO BOILER JUMPER
JUMPER 3&4
AQUASTAT RELAY 3&4 SEE NOTE
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
BOILER
3
N 120 VAC
H INPUT
BOILER TURNS ON WHEN ANY ZONE VALVE OPENS.
DHW PUMP TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
SWITCH SETTINGS
Master/Slave: Slave
Reset/Normal: Normal
Priority Zone: Off
T T T
SLAVE
TRANSFORMER
PLUG-IN ZONE 6
WHITE
INSTALLED
CARDS PRIORITY
FACTORY
120 VAC ON
POWER IN
T STAT 3
FUSE 7 AMP MAX
WHITE T STAT 5
INSTALLED
FACTORY
JUMPER
DRY JUMPER 3&4
CONTACTS 3&4 SEE NOTE
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
3
36
2 EXP Zone Valve Controls Connected Together with System and DHW Pumps
SWITCH SETTINGS
Master/Slave: Master
Reset/Normal: Normal
Priority Zone: On AQUASTAT ON
A DHW HEATER
T T T
24 VAC
MASTER
TRANSFORMER
PLUG-IN ZONE 6
WHITE
INSTALLED
CARDS PRIORITY
FACTORY
120 VAC ON
POWER IN
24 VAC SLAVE T STAT 1
INPUT 1 2 3 4 T T T T T T T T T T T T
POWER OFF
BLACK EXPANSION ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 VALVE 1
CONTROLS
MASTER T STAT 2
MODE
RESET NORMAL
ZVC 406-EXP VALVE 2
SIX ZONE ZONE VALVE CONTROL
TACO, INC ZVC406-EXP
T STAT 3
WHITE T STAT 5
INSTALLED
FACTORY
TO BOILER JUMPER
JUMPER 3&4
AQUASTAT RELAY 3&4 SEE NOTE
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
BOILER DHW SYSTEM 3
PUMP PUMP
2 WIRE ZONE VALVE TACO 4 WIRE ZONE VALVE
(NO END SWITCH) 3 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
N 120 VAC
H INPUT
SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
DHW PUMP TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
SWITCH SETTINGS
Master/Slave: Slave
Reset/Normal: Normal
Priority Zone: Off
T T T
SLAVE
TRANSFORMER
PLUG-IN ZONE 6
WHITE
INSTALLED
CARDS PRIORITY
FACTORY
120 VAC ON
POWER IN
T STAT 3
FUSE 7 AMP MAX
WHITE T STAT 5
INSTALLED
FACTORY
JUMPER
DRY JUMPER 3&4
CONTACTS 3&4 SEE NOTE
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
3
37
2 EXP Zone Valve Controls Connected Together with System, DHW and Secondary Pumps
SWITCH SETTINGS
Master/Slave: Master
Reset/Normal: Normal
Priority Zone: On AQUASTAT ON
A DHW HEATER
T T T
24 VAC
MASTER
TRANSFORMER
PLUG-IN ZONE 6
WHITE
INSTALLED
CARDS PRIORITY
FACTORY
120 VAC ON
POWER IN
T STAT 3
WHITE T STAT 5
INSTALLED
FACTORY
TO BOILER JUMPER
JUMPER 3&4
AQUASTAT RELAY 3&4 SEE NOTE
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
BOILER
DHW SYSTEM 3
PUMP PUMP
SECONDARY
PUMP 2 WIRE ZONE VALVE TACO 4 WIRE ZONE VALVE
(NO END SWITCH) 3 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
N 120 VAC
H INPUT
SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
DHW PUMP TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
SECONDARY PUMP TURNS ON WHEN ANY ZONE CALLS, EXCEPT PRIORITY ZONE.
SWITCH SETTINGS
Master/Slave: Slave
Reset/Normal: Normal
Priority Zone: Off
T T T
SLAVE
TRANSFORMER
PLUG-IN ZONE 6
WHITE
INSTALLED
CARDS PRIORITY
FACTORY
120 VAC ON
POWER IN
T STAT 3
FUSE 7 AMP MAX
WHITE T STAT 5
INSTALLED
FACTORY
JUMPER
DRY JUMPER 3&4
CONTACTS 3&4 SEE NOTE
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
3
38
PC700 Boiler Reset Control Connected To EXP Zone Valve Control
OUTDOOR
SENSOR
SWITCH SETTINGS
Master/Slave: Master
Reset/Normal: Reset
Priority Zone: On or Off
Note: When a circulator is used on the
priority zone instead of a zone valve,
jumper 3 and 4 of the priority zone.
PC700
THERMOSTAT THERMOSTAT THERMOSTAT
BOIL OUT ZONE INDIRECT
SEN SEN CONTROL WATER HEATER
AQUASTAT
OR THERMOSTAT
BOILER SENSOR T T T
24 VAC
PLUG-IN ZONE 6
WHITE CARDS PRIORITY
120 VAC ON
24 VAC SLAVE T STAT 1
INPUT 1 2 3 4 T T T T T T T T T T T T OFF
FACTORY
POWER
INSTALLED
BLACK EXPANSION ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 VALVE 1
CONTROLS
TRANSFORMER
POWER IN
MASTER T STAT 2
MODE
ZVC 406-EXP VALVE 2
RESET NORMAL
SIX ZONE ZONE VALVE CONTROL T STAT 3
WITH OPTIONAL PRIORITY VALVE 3
T STAT 4
VALVE 4
WHITE T STAT 5
FACTORY
INSTALLED
BLACK END END ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
SWITCH SWITCH
TRANSFORMER
N/O COM N/C VALVE 6
B A 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
PUMP ZONE 6 RELAY BOILER
JUMPER
DRY JUMPER 3&4
TO BOILER CONTACTS 3&4 SEE NOTE
AQUASTAT RELAY PRIORITY
ZONE
1 MOTOR END
SWITCH
2
3
BOILER SYSTEM
CIRCULATOR 2 WIRE ZONE VALVE TACO 4 WIRE ZONE VALVE
(NO END SWITCH) 3 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
H
N
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
39
40
PC702 2–Stage Boiler Reset Control Connected To EXP Zone Valve Control
OUTDOOR
SENSOR
SWITCH SETTINGS
Master/Slave: Master
DHW Reset/Normal: Normal
DEMAND
Priority Zone: On or Off
Note: When a circulator is used on the
priority zone instead of a zone valve,
PC702 jumper 3 and 4 of the priority zone.
THERMOSTAT THERMOSTAT THERMOSTAT
INDIRECT
STAGE STAGE BOIL OUT ZONE WATER HEATER
1 2 SEN SEN CONTROL
AQUASTAT
OR THERMOSTAT
WIRING NEEDED ONLY IF T T T
PRIORITY ZONE IS DHW
BOILER SENSOR 24 VAC
PLUG-IN ZONE 6
WHITE CARDS PRIORITY
120 VAC ON
INPUT 24 VAC SLAVE T STAT 1
1 2 3 4 T T T T T T T T T T T T OFF
FACTORY
POWER
INSTALLED
BLACK EXPANSION ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 VALVE 1
CONTROLS
TRANSFORMER
POWER IN
MASTER T STAT 2
MODE
ZVC 406-EXP VALVE 2
RESET NORMAL
SIX ZONE ZONE VALVE CONTROL T STAT 3
WITH OPTIONAL PRIORITY VALVE 3
T STAT 4
WHITE
VALVE 4
24 VAC
120 VAC
INPUT T STAT 5
FACTORY
INSTALLED
BLACK VALVE 5
TRANSFORMER
T STAT 6
BOILER END END ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
SWITCH N/O COM N/C SWITCH VALVE 6
B A 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
#1 PUMP ZONE 6 RELAY BOILER
JUMPER
JUMPER 3&4
3&4 SEE NOTE
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
3
OUTDOOR
SENSOR GREEN/GROUND
FACTORY
POWER
INSTALLED
BLACK EXPANSION ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 VALVE 1
CONTROLS
TRANSFORMER
POWER IN
MASTER T STAT 2
MODE
ZVC 406-EXP VALVE 2
RESET NORMAL
SIX ZONE ZONE VALVE CONTROL T STAT 3
WITH OPTIONAL PRIORITY VALVE 3
T STAT 4
VALVE 4
WHITE T STAT 5
FACTORY
INSTALLED
BLACK END END ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
SWITCH SWITCH VALVE 6
TRANSFORMER
B
N/O COM N/C A
PUMP ZONE 6 RELAY BOILER
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
JUMPER
DRY JUMPER 3&4
TO BOILER CONTACTS 3&4 SEE NOTE
AQUASTAT RELAY PRIORITY
ZONE
1 MOTOR END
SWITCH
2
3
BOILER
SYSTEM CIRCULATOR 2 WIRE ZONE VALVE TACO 4 WIRE ZONE VALVE
(OPTIONAL LOCATION) (NO END SWITCH) 3 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
H
N
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
41
PC700 Boiler Reset Control Connected To 2 EXP Zone Valve Controls
OUTDOOR
SENSOR
Note: When a circulator is used on the
SWITCH SETTINGS priority zone instead of a zone valve,
jumper 3 and 4 of the priority zone.
Master/Slave: Master
Reset/Normal: Reset
Priority Zone: On or Off
INDIRECT WATER HEATER
PC700 AQUASTAT OR THERMOSTAT
BOILER SENSOR
T T T
MASTER 24 VAC
TRANSFORMER
PLUG-IN ZONE 6
WHITE
INSTALLED
CARDS PRIORITY
FACTORY
120 VAC ON
POWER IN
24 VAC SLAVE T STAT 1
INPUT 1 2 3 4 T T T T T T T T T T T T
POWER OFF
BLACK EXPANSION ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 VALVE 1
CONTROLS
MASTER T STAT 2
MODE
RESET NORMAL
ZVC 406-EXP VALVE 2
SIX ZONE ZONE VALVE CONTROL
TACO, INC ZVC406-EXP
T STAT 3
WHITE T STAT 5
INSTALLED
FACTORY
JUMPER
TO BOILER JUMPER 3&4
AQUASTAT RELAY 3&4 SEE NOTE
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
BOILER 3
H
N
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
SWITCH SETTINGS
Master/Slave: Slave
Reset/Normal: Normal
Priority Zone: Off
T T T
SLAVE 24 VAC
TRANSFORMER
PLUG-IN ZONE 6
INSTALLED
FACTORY
CARDS PRIORITY
WHITE
ON
POWER IN
T STAT 3
FUSE 7 AMP MAX
WHITE T STAT 5
INSTALLED
FACTORY
JUMPER
DRY JUMPER 3&4
CONTACTS 3&4 SEE NOTE
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
3
42
PC702 2–Stage Boiler Reset Control Connected To 2 EXP Zone Valve Controls
OUTDOOR
SENSOR
Note: When a circulator is used on the
SWITCH SETTINGS priority zone instead of a zone valve,
Master/Slave: Master jumper 3 and 4 of the priority zone.
DHW
Reset/Normal: Normal
DEMAND
Priority Zone: On or Off
BOILER SENSOR
T T T
MASTER 24 VAC
TRANSFORMER
PLUG-IN ZONE 6
WHITE
INSTALLED
CARDS PRIORITY
FACTORY
T STAT 3
VALVE 4
TRANSFORMER
WHITE T STAT 5
INSTALLED
FACTORY
JUMPER
BOILER JUMPER 3&4
3&4 SEE NOTE
#1 PRIORITY
ZONE
1 MOTOR END
SWITCH
2
3
SYSTEM DHW
2 WIRE ZONE VALVE TACO 4 WIRE ZONE VALVE
CIRCULATOR CIRCULATOR
(NO END SWITCH) 3 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
H
N
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
BOILER
#2
SWITCH SETTINGS
Master/Slave: Slave
Reset/Normal: Normal
Priority Zone: Off
T T T
SLAVE 24 VAC
TRANSFORMER
PLUG-IN ZONE 6
WHITE
INSTALLED
CARDS PRIORITY
FACTORY
120 VAC ON
POWER IN
T STAT 3
FUSE 7 AMP MAX
VALVE 4
TRANSFORMER
WHITE T STAT 5
INSTALLED
FACTORY
JUMPER
DRY JUMPER 3&4
CONTACTS 3&4 SEE NOTE
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
3
43
PC705 Variable Speed Pump Injection Control Connected To 2 EXP Zone Valve Controls
OUTDOOR
SENSOR GREEN/GROUND SWITCH SETTINGS
Master/Slave: Master Note: When a circulator is used on the
(SEE NOTE B ON PAGE 23)
RED Reset/Normal: Reset priority zone instead of a zone valve,
SYSTEM Priority Zone: On or Off jumper 3 and 4 of the priority zone.
CIRCULATOR
BLUE
PC705-2 INJECTION
CIRCULATOR
BLACK INDIRECT WATER HEATER
AQUASTAT OR THERMOSTAT
BOIL SUP OUT ZONE
SEN SEN SEN CONTROL
SUPPLY SENSOR T T T
24 VAC
BOILER SENSOR MASTER
TRANSFORMER
PLUG-IN ZONE 6
WHITE
INSTALLED
FACTORY
CARDS PRIORITY
120 VAC ON
POWER IN
T STAT 3
WHITE T STAT 5
INSTALLED
FACTORY
VALVE 5
24 VAC
T STAT 6
BLACK END
SWITCH
END
SWITCH
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 VALVE 6
N/O COM N/C
B
PUMP ZONE 6 RELAY
A
BOILER
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
POWER ON
JUMPER
DRY JUMPER 3&4
CONTACTS 3&4 SEE NOTE
TO BOILER
PRIORITY
AQUASTAT RELAY
ZONE
1 MOTOR END
SWITCH
2
3
BOILER
2 WIRE ZONE VALVE TACO 4 WIRE ZONE VALVE
SYSTEM CIRCULATOR (NO END SWITCH) 3 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
(OPTIONAL LOCATION)
H
N
SWITCH SETTINGS
Master/Slave: Slave
Reset/Normal: Normal
Priority Zone: Off
T T T
SLAVE 24 VAC
TRANSFORMER
PLUG-IN ZONE 6
WHITE
INSTALLED
FACTORY
CARDS PRIORITY
120 VAC ON
POWER IN
T STAT 3
FUSE 7 AMP MAX
WHITE T STAT 5
INSTALLED
FACTORY
VALVE 5
24 VAC
T STAT 6
BLACK END END ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 VALVE 6
SWITCH N/O COM N/C SWITCH
B
PUMP ZONE 6 RELAY
A
BOILER
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
POWER ON
JUMPER
DRY JUMPER 3&4
CONTACTS 3&4 SEE NOTE
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
3
44
PC700 and PC705 Connected To 2 EXP Zone Valve Controls
OUTDOOR
SENSOR
Note: When a circulator is used on the
SWITCH SETTINGS priority zone instead of a zone valve,
jumper 3 and 4 of the priority zone.
Master/Slave: Master
Reset/Normal: Reset
Priority Zone: On or Off
INDIRECT WATER HEATER
PC700 AQUASTAT OR THERMOSTAT
BOILER SENSOR
T T T
TRANSFORMER MASTER 24 VAC
PLUG-IN ZONE 6
WHITE
INSTALLED
CARDS PRIORITY
FACTORY
120 VAC ON
POWER IN
24 VAC SLAVE T STAT 1
INPUT 1 2 3 4 T T T T T T T T T T T T OFF
POWER VALVE 1
BLACK CONTROLS EXPANSION ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
MASTER T STAT 2
MODE
RESET NORMAL
ZVC 406-EXP VALVE 2
SIX ZONE ZONE VALVE CONTROL
TACO, INC ZVC406-EXP
T STAT 3
WHITE T STAT 5
INSTALLED
FACTORY
JUMPER
TO BOILER JUMPER 3&4
AQUASTAT RELAY 3&4 SEE NOTE
PRIORITY
ZONE
1 MOTOR END
SWITCH
2
BOILER 3
H
N
OUTDOOR SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
SENSOR GREEN/GROUND
DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
(SEE NOTE B ON PAGE 23)
SYSTEM
RED CIRCULATOR
BLUE
PC705-2 INJECTION
CIRCULATOR
SUPPLY SENSOR
BOILER SENSOR
T T T
SLAVE 24 VAC
TRANSFORMER
PLUG-IN ZONE 6
INSTALLED
CARDS PRIORITY
FACTORY
WHITE
ON
POWER IN
T STAT 3
FUSE 7 AMP MAX
WHITE T STAT 5
INSTALLED
FACTORY
JUMPER
SWITCH SETTINGS DRY JUMPER 3&4
CONTACTS 3&4 SEE NOTE
Master/Slave: Slave PRIORITY
ZONE
Reset/Normal: Normal 1 MOTOR END
SWITCH
45
PC702 and PC705 Connected To 2 EXP Zone Valve Controls
OUTDOOR
SENSOR
SWITCH SETTINGS
Master/Slave: Master
Reset/Normal: Normal Note: When a circulator is used on the
priority zone instead of a zone valve,
DHW
Priority Zone: On or Off jumper 3 and 4 of the priority zone.
DEMAND
BOILER SENSOR T T T
MASTER 24 VAC
TRANSFORMER
PLUG-IN ZONE 6
WHITE
INSTALLED
CARDS PRIORITY
FACTORY
T STAT 3
VALVE 4
TRANSFORMER
WHITE T STAT 5
INSTALLED
FACTORY
JUMPER
JUMPER 3&4
BOILER 3&4 SEE NOTE
#2 PRIORITY
ZONE
1 MOTOR END
SWITCH
2
3
H
N
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
OUTDOOR
SENSOR GREEN/GROUND DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
BLUE
PC705-2 INJECTION
CIRCULATOR
BLACK
SUPPLY SENSOR
BOILER SENSOR
T T T
SLAVE 24 VAC
TRANSFORMER
PLUG-IN ZONE 6
WHITE
INSTALLED
CARDS PRIORITY
FACTORY
120 VAC ON
POWER IN
T STAT 3
FUSE 7 AMP MAX
WHITE T STAT 5
INSTALLED
FACTORY
SWITCH SETTINGS
JUMPER
DRY JUMPER
Master/Slave: Slave CONTACTS 3&4
3&4
SEE NOTE
Reset/Normal: Normal PRIORITY
ZONE
Priority Zone: Off 1 MOTOR END
SWITCH
2
3
46
HAFC101 with 1 Speed Air Handler
THERMOSTAT
T
Optional Power Wire To: Aquastat on
to Thermostat Return Line of
that Requires 24VAC Hydro Coil
C R W Y G T T
THERMOSTAT AQUASTAT
HAFC101 Power On
HYDRO AIR FAN CONTROL Call for Heat
Fan, Cooling
Fan, Heating
X X C R Y G G LOW HIGH
Jumper
“T T” on Boiler
or Switching Relay Outdoor
Fan Condenser
Relay
Unit
M
Line
47
HAFC101 with 2 Speed Air Handler
THERMOSTAT
T
Optional Power Wire To: Aquastat on
to Thermostat Return Line of
that Requires 24VAC Hydro Coil
C R W Y G T T
THERMOSTAT AQUASTAT
HAFC101 Power On
HYDRO AIR FAN CONTROL Call for Heat
Fan, Cooling
Fan, Heating
X X C R Y G G LOW HIGH
“T T” on Boiler
or Switching Relay
Fan Relays
Outdoor
Condenser
High
Low
Unit
M
Line
48
HAFC201 with 1 Speed Air Handler
C R W Y G T T T T
WATER COIL FREEZE PR
THERMOSTAT AQUASTATS
Power On
HAFC201
HYDRO AIR FAN CONTROL Call for Heat
Fan, Cooling
Fan, Heating
OFF
DRY CONTACTS
5 AMP 1/6 HP RATED
NOTE: For 4 minute
PUMP BOILER AIR HANDLER
ON
Jumper
Hot
Neutral
(or to “T T” on
24 VAC
switching relay)
Outdoor
Circulator Fan Condenser
Relay
Unit
Relay
49
HAFC201 with 2 Speed Air Handler
C R W Y G T T T T
WATER COIL FREEZE PR
THERMOSTAT AQUASTATS
Power On
HAFC201
HYDRO AIR FAN CONTROL Call for Heat
Fan, Cooling
Fan, Heating
OFF
DRY CONTACTS
5 AMP 1/6 HP RATED
NOTE: For 4 minute
PUMP BOILER AIR HANDLER
ON
Hot
Neutral
(or to “T T” on
24 VAC
switching relay)
Fan Relays
Outdoor
Condenser
High
Circulator
Low
Unit
“T T” on Boiler
or Switching
Relay M
Line
50
Multiple HAFC’s and Switching Relay
C R W Y G T T C R W Y G T T C R W Y G T T
THERMOSTAT AQUASTAT THERMOSTAT AQUASTAT THERMOSTAT AQUASTAT
24 VAC
24 VAC
24 VAC
Low
Low
Low
CONDENSER
High
High
High
CONDENSER CONDENSER
Fan Relays
Fan Relays
Fan Relays
M M M
Line
Line
Line
ZONE 4
PRIORITY
ON
ZONE 1 ZONE 2 ZONE 3 ZONE 4 OFF
SR 504
FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
POWER
ZONE 1 DHW
ZONE 2 HEATER
ZONE 3 AQUASTAT
ZONE 4
24 VAC 120V RELAY
POWER
X X ZONE1 ZONE2 ZONE3 ZONE4 POWER
END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT
FUSE 1 AMP
H
JUMPER 120 VAC INPUT
TO: "TT" ON BOILER N
BOILER
51
3 Wire Thermostat Connected to TACO Switching Relay
3 WIRE
THERMOSTAT
COM T
T T T
W R
ZONE 4
PRIORITY
ON
OFF
SR 504 ZONE 1 ZONE 2 ZONE 3 ZONE 4
FUSE 1 AMP
H
120 VAC INPUT
JUMPER
N
BOILER
T T T
TRANSFORMER
WHITE C
INSTALLED
FACTORY
W R
120 VAC
RED
24 VAC
WH
INPUT
BLACK
COMMON
POWER IN
T STAT 1
T T T T T T T T T T
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 VALVE 1
TRANSFORMER
WHITE
INSTALLED
FACTORY
T STAT 2
120 VAC 24 VAC
INPUT VALVE 2
BLACK ZVC 405 T STAT 3
VALVE 3
FIVE ZONE ZONE VALVE CONTROL T STAT 4
VALVE 4
T STAT 5
VALVE 5
END ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5
SWITCH
POWER
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
BLACK
BLACK
T JUMPER
RED
RED
T 3&4
TO T&T ON BOILER
OR PUMP RELAY
1 MOTOR END
SWITCH
2
3
52
White-Rogers 1361 Hydronic Zone Valve with TACO Zone Valve Control
TERMINAL ASSIGNMENT
ZONE VALVE CONTROL
NOTE: WHEN USING ZVC 404 OR ZVC 406, 1 1
CONNECT WIRE #2 OF ZONE VALVE
TO PRIORITY ZONE RIGHT TT SCREW THERMOSTAT THERMOSTAT THERMOSTAT 2 TT (Rt)
3 3
4 2
T T T
WHITE
RIGHT TT
120 VAC 24 VAC SCREW
INPUT (SEE NOTE)
FACTORY
INSTALLED
BLACK
TRANSFORMER
T STAT 1
POWER IN
T T T T T T T T T T
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 VALVE 1
WHITE
T STAT 2
120 VAC 24 VAC
INPUT VALVE 2
FACTORY
INSTALLED
BLACK ZVC 405 T STAT 3
TRANSFORMER
VALVE 3
FIVE ZONE ZONE VALVE CONTROL T STAT 4
VALVE 4
T STAT 5
VALVE 5
END ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5
SWITCH POWER
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
T
T
BLACK
BLACK
RED
RED
TO T&T ON BOILER
OR PUMP RELAY
1 MOTOR END
2 1 4 3 SWITCH
2
3
53
54
Honeywell VC 40 & 80 (spdt) Hydronic Zone Valve with TACO Zone Valve Control
TERMINAL ASSIGNMENT
ZONE VALVE CONTROL
NOTE: WHEN USING ZVC 404 OR ZVC 406,
CONNECT WIRE #3 OF ZONE VALVE
ORANGE 1 3
TO PRIORITY ZONE RIGHT TT SCREW THERMOSTAT THERMOSTAT THERMOSTAT BLUE 2 1
BROWN 3 TT (Rt)
GRAY 4 4
T T T BLACK 6 2
WHITE
RIGHT TT
120 VAC 24 VAC SCREW
INPUT (SEE NOTE)
FACTORY
INSTALLED
BLACK
TRANSFORMER
T STAT 1
POWER IN
T T T T T T T T T T
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 VALVE 1
WHITE
T STAT 2
120 VAC 24 VAC
INPUT VALVE 2
FACTORY
INSTALLED
BLACK ZVC 405 T STAT 3
TRANSFORMER
VALVE 3
FIVE ZONE ZONE VALVE CONTROL T STAT 4
VALVE 4
T STAT 5
VALVE 5
END ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5
SWITCH
POWER
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
T
T
BLACK
BLACK
RED
RED
TO T&T ON BOILER
OR PUMP RELAY
1 MOTOR END
3 2 6 4 1 SWITCH
2
3
T THERMOSTAT
24 VAC
TRANSFORMER
1
2
24 VAC
POWER
X2
N P ZC H X1 ZR ZONE1 ZONE2 ZONE3
JUMPERS
120 VOLT
CIRCULATORS
TO: 120 VAC POWER (NEUTRAL)
55
56
Zone Valve Control with 1 Low Temperature Zone Using Priority Zoning Circulator
AQUASTAT ON
T T T A DHW HEATER
WHITE
24 VAC
N 120 VAC 24 VAC
INPUT
FACTORY
H
INSTALLED
BLACK
TRANSFORMER
MODE ZONE 6 PRIORITY
NORMAL RESET
OFF
T STAT 1
ON
VALVE 1
POWER IN
T T T T T T T T T T T T
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 T STAT 2
WHITE
VALVE 2
120 VAC 24 VAC
INPUT T STAT 3
FACTORY
INSTALLED
BLACK ZVC 406 VALVE 3
TRANSFORMER
T STAT 4
SIX ZONE ZONE VALVE CONTROL VALVE 4
JUMPER JUMPER
3&4 3&4
SEE NOTE
TO BOILER AQUASTAT RELAY
PRIORITY
ZONE
DRY MOTOR END 1 MOTOR END
CONTACTS SWITCH SWITCH
2
BOILER Note: When a circulator is
3
used on the priority zone
SYSTEM instead of a zone valve,
4 WIRE TACO 4 WIRE
PUMP ZONE VALVE 3 WIRE ZONE VALVE jumper 3 and 4 of the
(POWER OPEN, ZONE VALVE (POWER OPEN, priority zone.
SELF CLOSING) SELF CLOSING)
Boiler Operation
Off-Enable On-Control
Front of R
Power: 120 V + 10% Meets Class B:
Canadian ICES
C US 50/60 Hz, 750 VA
Control 158033 Var. Speed: 120 V
(ac) 1 A
FCC Part 15
Boiler
(ac) 5 A, 1/6 hp
Use copper
conductors only
Fuse
Sys
Com Sup Sys Com Boil Out Com Heat Pump
Boiler Ret Dem Y R B
MENU ITEM Man
H
Var N
RADIANT MIXING BLOCK
Supply
Sensor Injection
Boiler Circulator
To
Sensor Zone
Control
End
Outdoor Switch
or Radiant
Sensor Thermostat Circulator
Boiler Operation
RMB
Boiler
Off-Enable On-Control
Back of Control Thermostat
T (Dry Contact)
Pump
Boiler
Sensor
Supply
Sensor
Transformer
Power H
Installed
Factory
Input
Outdoor
N
Sensor
POWER IN
T T T T T T
ZONE 1 ZONE 2 ZONE 3
Boiler Operation
RMB Off-Enable On-Control ZVC 403
Boiler
FUSE
(5 AMP MAX)
Back of Control THREE ZONE ZONE VALVE CONTROL
E ND
SWITCH
N/O COM N/C ZONE 1 ZONE 2 ZONE 3
Pump
1 2 3 4 1 2 3 4 1 2 3 4
End Switch
End Switch
Motor
Motor
N M M
Boiler
Sensor
Supply
Sensor
Radiant Mixing Block Connected to 2 EXP Switching Relays with DHW Pump
T Thermostats
Thermostats T
T A DHW Power Cord
Aquastat
T Outdoor SLAVE PLUG-IN CARDS
ZONE 3
1 2 3 4 PRIORITY
Sensor MASTER
EXPANSION ZONE1 ZONE2 ZONE3 ON
SLAVE POWER CONTROL OFF
PLUG-IN CARDS ZONE 3
PRIORITY
INTERFACE THREE ZONE SWITCHING RELAY
MASTER 1 2 3 4 ON RESET NORMAL WITH OPTIONAL PRIORITY
EXPANSION ZONE1 ZONE2 ZONE3 OFF Boiler Operation SR503-EXP
POWER CONTROL
RMB Off-Enable On-Control
Boiler
INTERFACE
THREE ZONE SWITCHING RELAY
RESET NORMAL WITH OPTIONAL PRIORITY
SR503-EXP Back of Control
Pump X
END
X
ZC ZR ZONE1 ZONE2 ZONE3 POWER
24 VAC SWITCH 120 VOLT CIRCULATORS INPUT
ComSup Sys Com Boil Out ComHeat POWER
Ret Dem H FUSE 1 AMP
X X ZONE1 ZONE2 ZONE3 POWER
END
SWITCH
ZC ZR 120 VOLT CIRCULATORS INPUT
24 VAC N
POWER
FUSE 1 AMP
H Power
N Input
DHW
Circ.
Boiler Supply
Sensor Sensor
Control R
Power: 120 V + 10%
50/60 Hz, 750 VA
Meets Class B:
Canadian ICES
C US FCC Part 15
158033 Var. Speed: 120 V
(ac) 1 A
Pmp Relay: 120 V
Boiler
(ac) 5 A, 1/6 hp
Use copper
conductors only
Fuse
Manual
Sys
MENU ITEM
Operation
Com Sup Sys Com Boil Out Com Heat Pump
Ret Dem Y R B
Switch
Heat Source Man
X – PUMP BLOCK
H
Outdoor Power
Sensor Cord
Boiler Operation
XPB Off-Enable On-Control
Boiler
Back of Control
Thermostat
Pump (Relay or Mechanical Type)
Pressure
Relief
HEAT Exp
Tank
SOURCE Supply
Input from Output to Sensor
Heat Source System
XPB
Boiler
NORMAL RESET
Off-Enable On-Control OFF
POWER IN T T T T T T T T ON
ZONE 1 ZONE 2 ZONE 3 ZONE 4
Back of Control
FUSE ZVC 404
Pump (3 AMP MAX) FOUR ZONE ZONE VALVE CONTROL
WITH OPTIONAL PRIORITY
ComSup Sys Com Boil Out Com Heat MAIN EXTRA
N/O COM N/C
Ret Dem END END ZONE 1 ZONE 2 ZONE 3 ZONE 4
H SWITCH SWITCH ZONE 4 RELAY
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
Pressure
Relief
T
T
T
24 VAC
POWER Power T
SR 502 ZONE1 ZONE2 Cord
TWO ZONE SWITCHING RELAY Outdoor
24 VAC
FUSE 1 AMP Sensor POWER
Off-Enable On-Control
Boiler
XPB
Back of Control N P ZC H X1
X2
ZR ZONE1 ZONE2
Power H
Input N
Pump
ComSup Sys Com Boil Out Com Heat
Ret Dem
H Power H
N Input N
Pressure
Relief
Exp
Return Tank Supply
Sensor Input from Output to Sensor
Heat Source System
Domestic Cold
Hot Supply
Supply
X-PUMP
BLOCK
Air Relief
Separator Valve
C
MIX
H
Return
ASSE 1017
Tempering Exp.
Valve Tank
RADIANT
SYSTEM
(Secondary Side
Supply
of the System)
Check
Valve
Hot
Cold
WATER
HEATER WARNING! A pressure relief valve and expansion tank must be installed on the secondary
side in addition to any pressure relief valve and expansion tank which is installed on primary
side of system. Use dedicated supply and return piping to the X-Pump Block from the water
heater so as not to add heated water into the house’s cold water piping.
SYSTEM
RETURN Air
SENSOR Relief
Separator
(Tb) Exp. Valve
Tank X-PUMP
BLOCK Return
Note 1 Note 2
{
{
Note 2
Exp.
{ Tank
Note 3
{
Note 1
} (ΔTs)
Note 3
{
SYSTEM
SUPPLY
SENSOR
(Ts)
Supply SNOW MELT
SYSTEM
HEAT SOURCE VARIABLE SPEED
FIXED SPEED
HEAT RETURN SENSOR CIRCULATOR
CIRCULATOR
(OPTIONAL)
SOURCE (4 PIN PLUG) (3 PIN PLUG)
Tb = Boiler Supply Temperature Note 1: There must be no more than 4 pipe diameters between the tees in the boiler and
system loops in order to prevent ghost flow when the variable speed injection
Ts = System Supply Temperature pump is off and either the boiler pump or system pump is on.
Note 2: There must be at least 6 pipe diameters of straight pipe on either side of the tees in
ΔTs = System Temperature Drop order to prevent the momentum of water in the boiler and system loops from pushing
(typically 20°F for convectors flow through the injection loop.
and 10°F for radiant floor heating) Note 3: There should be a minimum 1 foot drop to create a thermal trap in order to prevent
convective heat transfer through the injection loop.
61
iSeries Mixing Valve
Boiler
System Return
Supply Back of Sensor Back of
Sensor Control System Control
Supply
Boiler Sensor
Return
Sensor
(optional)
C R C R
POWER POWER
BOILER GREEN 24 VAC BOILER GREEN 24 VAC
SUPPLY POWER INPUT SUPPLY POWER INPUT
SENSOR SENSOR
ERROR ERROR
SETBACK RED OUTDOOR RED
Outdoor
Sensor
Setback
Input 24 V (ac) or End 24 V (ac) or End
Transformer Switch Transformer Switch
iValve-S iValve-R
Outdoor Thermostat
T
Sensor
H Power
N Input
iSeries-R
A B
Supply
Sensor
Boiler
Sensor
DHW Aquastat
A T
Power
24 VAC
Input POWER
Transformer
24 Volt
X2
N P ZC H X1 ZR Z ONE1 Z ONE2 Z ONE3
BOILER POWER SENSOR 24 VAC
SUPPLY GREEN COMMON POWER INPUT
OUTDOOR
C R
SENSOR
ERROR
RED
DHW
Circ.
iSeries-R
B
B
C
C
Supply A
A
Sensor Boiler
Sensor
Power H
Installed
SENSOR 24 VAC
Factory
BOILER POWER
POWER IN
(5 AMP MAX)
THREE ZONE ZONE VALVE CONTROL
24 Volt
SENSOR
ERROR E ND
N/O COM N/C ZONE 1 ZONE 2 ZONE 3
SWITCH
RED 1 2 3 4 1 2 3 4 1 2 3 4
End Switch
Motor
Motor
Switch
End
M M
Supply iSeries-R
Sensor
Boiler
Sensor
TACO LTR0243T-1
MALE
CONNECTOR
GROUND
CONNECTION
24 VAC
CLASS 2
TRANSFORMER
LIMIT
CONTROLS
HOT
120
VAC
24 VAC
GAS
VALVE
COMMON
64
Wiring Boilers with a United Technologies Integrated Control Module and a Taco LTR0243U-1
INTEGRATED BOILER
CONTROL
MALE
CONNECTOR
FEMALE
CONNECTOR
FACTORY WIRING
BOILER MODULE
WIRING HARNESS
Wiring Boilers with a United Technologies Ucontrol or other Integrated Control Modules
which accept a 4-pin harness and a Taco LTR0243L-1
INTEGRATED
CONTROL
MODULE
WIRING HARNESS
Wiring Instructions
1. Plug the 4-pin connector on the wiring harness (#1 as
shown) into the integrated control module.
2. Plug the 4-pin connector on the wiring harness (#2 as
shown) into the LTR.
65
Wiring Taco LN and LTA-2 Series Low Water Cutoffs
Using Burner Circuit Power Source
*Factory Installed
66
Wiring Taco LT Series (1st generation, -1) Low Water Cutoffs
Using Burner Circuit Power Source
*
*Factory Installed
67
Wiring Taco LF Series Low Water Cutoffs Using Burner Circuit Power Source
NOTE: For 24 VAC models, LFx024xx, 24 VAC to be supplied by an EXTERNAL Class 2 power source to terminals H and N.
For 120 VAC models, LFx120xx, 120 VAC is supplied by an external circuit to terminals H and N.
Wiring Taco LF Series Low Water Cutoffs Using Power Source Other Than Burner Circuit
NOTE: For 24 VAC models, LFx024xx, 24 VAC to be supplied by an EXTERNAL Class 2 power source to terminals H and N.
For 120 VAC models, LFx120xx, 120 VAC is supplied by an external circuit to terminals H and N.
68
Taco Low Water Cutoff Replacement Guide
HOT
HOT
BURNER 120 VAC
FACTORY BURNER
CIRCUIT INSTALLED CIRCUIT 120 VAC
JUMPER CIRCUIT CIRCUIT
NEUTRAL
NEUTRAL
2 1 P1 P2 A N H C W B
HOT HOT
NEUTRAL NEUTRAL
NC NO COM H N GND P 1 2 3 4 5
2 1 P1 P2 A N H C W B
NEUTRAL NEUTRAL
24 VAC 24 VAC
TRANSFORMER TRANSFORMER
70
Taco LF Series 24 Volt LWCO Competitive Wiring Cross Reference
TACO LFx024x
NC NO COM H N GND P
HOT
BURNER 24 VAC
FACTORY
CIRCUIT INSTALLED CIRCUIT
JUMPER
NEUTRAL
2 1 P1 P2 A N H C W B
HOT HOT
NEUTRAL NEUTRAL
TACO LFx024x
NC NO COM H N GND P
HOT
BURNER
CIRCUIT 120 VAC
24 VAC CIRCUIT
TRANSFORMER
NEUTRAL
2 1 P1 P2 A N H C W B
HOT HOT
BURNER BURNER
120 VAC CIRCUIT 120 VAC CIRCUIT
CIRCUIT CIRCUIT
24 VAC 24 VAC
TRANSFORMER TRANSFORMER
NEUTRAL NEUTRAL
71
Taco LTA-2 Series 120 Volt LWCO Competitive Wiring Cross Reference
N H COM NC NO 1 2 3 4 5
HOT HOT
N H COM NC NO 1 2 3 4 5
HOT HOT
BURNER BURNER
CIRCUIT CIRCUIT
120 VAC 120 VAC
CIRCUIT CIRCUIT
NEUTRAL NEUTRAL
24 VAC 24 VAC
TRANSFORMER TRANSFORMER
72
Taco LTR and LTA-2 Series 24 Volt LWCO Competitive Wiring Cross Reference
HOT HOT
24 VAC BURNER
24 VAC BURNER 24 VAC BURNER JUMPER
CIRCUIT
CIRCUIT CIRCUIT CIRCUIT CIRCUIT CIRCUIT
N H COM NC NO 2 1 P1 P2 A
HOT HOT
120 VAC 120 VAC
CIRCUIT CIRCUIT
BURNER BURNER
CIRCUIT CIRCUIT
NEUTRAL NEUTRAL
24 VAC 24 VAC
TRANSFORMER TRANSFORMER
73
Wiring Taco LF Series Low Water Cutoffs
to Taco Electric Water Feeder with the Same Voltages
NC NO COM H N GND P
HOT
BURN ER
C IR C U IT FACTORY 120 V AC / 24 V A C
INSTALLED C I R C U IT
JUMPER
NEUTRAL
LW N H
T a co L F x1 2 0 x T a c o L F x 02 4 x
* HO T * HO T
B UR NE R B UR NE R
CI RC UI T 12 0 V A C CI RC UI T 24 V AC
C IR C U IT C IR C U IT
NE U TR AL NE U TR AL
HO T HO T
24 V AC 12 0 V A C
H N LW C IR C U IT H N LW C IR C U IT
NE U TR AL NE U TR AL
T a co E W F 0 2 4 T a co E W F 1 2 0
* N O T E : R e m o v e f a c to r y i n s t a ll e d
ju m p e r b etw e e n H a n d C O M t e r m in a ls
74
Wiring Taco 24VAC Electric Water Feeder to Taco LF Series 24VAC Low Water Cutoff
or 24VAC McDonnell & Miller or Hydrolevel Low Water Cutoffs
M c D o n n e l l & M il l e r
P S -8 0 2 /8 5 2 -2 4
B W C H N
H yd ro le v e l
P2 A P1 1 2
400, 50 0, 600, & 700
HOT
** Ma y be fa ctory installed on
B UR N E R
C IR C U IT INSTALLED 24 V A C som e L W C O s
JUMPER ** C IR C U IT
Wiring Taco 120VAC Electric Water Feeder to Taco LF Series 120VAC Low Water Cutoff
or 120VAC McDonnell & Miller or Hydrolevel Low Water Cutoffs
M c D o n n e ll & M ill e r
P S -8 0 1 /8 5 1 -1 2 0 w /R e d & 5 4 3 1 2
A m b e r L E D s , S e rie s 7 5 0
M c D o n n e ll & M ill e r
P S -8 0 1 /8 5 1 -1 2 0 B W C H N
w /R e d & G r e e n L E D s
H yd ro le v e l
P2 A P1 1 2
450, 55 0, 650, & 750
B UR N E R
C IR C U IT INSTALLED N O T E : W iring s hown only for control
JUMPER **
120 V A C
C IR C U IT an d burner circuits of the sam e
volta ge. S om e term ina l designations
NEUTRAL are n ot in their actual order on the
LW C O s.
LW N H
Taco EW F 120
75
Wiring TACO LTA-2 or LF Series 24VAC Low Water Cutoff to
McDonnell & Miller Series WF2 Uni-Match Electric Water Feeder
SWITCH POSITION #2
UNI-MATCH 1 2 3
0R M&M
WATER FEEDER 2
MODEL WF2-U-24 W N H 3
24VAC N
SUPPLY Note on switch position:
H
50/60 Hz
BURNER Switch setting 1 (M&M), the feed cycle repeats
indefinitely. Position 2 and 3 gives one feed cycle.
SWITCH POSITION #2
UNI-MATCH 1 2 3
0R M&M
WATER FEEDER 2
MODEL WF2-U-120 W N H 3
120VAC N
SUPPLY Note on switch position:
50/60 Hz H
Switch setting 1 (M&M), the feed cycle repeats
BURNER indefinitely. Position 2 and 3 gives one feed cycle.
24VAC N
SUPPLY
50/60 Hz H BURNER
120VAC N
SUPPLY
50/60 Hz H BURNER
77
Wiring TACO LTA-2 or LF Series 24VAC Low Water Cutoff to
Hydrolevel VXT-24 Programmable Water Feeder (Model with Display)
24VAC N
SUPPLY
50/60 Hz H BURNER
120VAC N
SUPPLY
50/60 Hz H BURNER
78
Taco LTR, LN, LT-1, LTA-2 & LF Series Low Water Cutoff and Taco Electric Water Feeder Wiring Cross Reference
Taco LTR Series Red Wire White Wire Yellow Wire Yellow Wire — — —
PS-801/851 (Older Models
McDonnell & Miller 1 2 3 5 4 P or J2 Chassis GND
w/Red & Amber LEDs)
PS-801/851 (New Models
McDonnell & Miller H N C B W J2 Chassis GND
w/Red & Green LEDs)
PS-802/852 (Older Models
McDonnell & Miller H N C B W J7 Chassis GND
w/Red & Amber LEDs)
PS-802/852 (Older Models
McDonnell & Miller H N C B W J3 Chassis GND
w/Red & Green LEDs)
McDonnell & Miller Series 750 1 2 3 5 4 P Chassis GND
H N C B
McDonnell & Miller RB-122 — — —
(Black Wire) (White Wire) (Yellow Wire) (Yellow Wire)
McDonnell & Miller RB-120 1 2 3 4 5 — —
McDonnell & Miller RB-24 Red Wire White Wire Yellow Wire Yellow Wire — — —
Hydrolevel 24 1 2 P1 P2 A — —
Hydrolevel 170 H GN P1 P2 A — —
Hydrolevel 1100 Red Wire White Wire Yellow Wire Yellow Wire — — —
H N CUT-OFF CUT-OFF
Hydrolevel 1150 — — —
(Black Wire) (White Wire) (Yellow Wire) (Yellow Wire)
400, 500, 600, 700, 450,
Hydrolevel 1 2 P1 P2 A H3 Chassis GND
550, 650, 750
RW700 Series 2 Red Wires,
Hydrolevel L1 L2 — B A Green Wire
(Except RW700A1098) White Wire
2 Red Wires,
Hydrolevel RW700A1098 T1 T2 — B A Green Wire
White Wire
79
Aquastat Wiring
L1 L2
(HOT) (NEUTRAL)
120 VAC
INPUT
TACO
L1 L2 T T ZONE
CONTROL
END SWITCH
C1 ZC
B2 C2 ZR B1
CIRCULATOR
ON BOILER HONEYWELL L8124A & C OR EQUAL
(IF ATTACHED) LINE VOLTAGE
OIL BURNER RELAY
OR GAS VALVE
MILLI-VOLTAGE
GAS VALVE
TACO
B1 B2 T T ZONE
CONTROL
END SWITCH
C
CIRCULATOR
ON BOILER
L1 L2 C2
(IF ATTACHED)
L1 L2
(HOT) 120 VAC (NEUTRAL) HONEYWELL L8124B OR EQUAL
INPUT
TACO
TV T Z ZONE
CONTROL
END SWITCH
CIRCULATOR
ON BOILER
(IF ATTACHED)
C1 C2
B1 B2 L1 L2
120 VAC
L1 INPUT
L2
LOW VOLTAGE (HOT) (NEUTRAL) HONEYWELL L8124E OR EQUAL
GAS VALVE
80
Aquastat Wiring
TACO
TV T Z ZONE
CONTROL
END SWITCH
LINE
VOLTAGE
OIL BURNER
ZC ZR B1 RELAY OR
GAS VALVE
L1 L2 B2 C1
C2
120 VAC
INPUT CIRCULATOR
ON BOILER
HONEYWELL L8124G & L OR EQUAL
L1 L2
(HOT) (NEUTRAL) (IF ATTACHED)
L1 L2
(HOT) (NEUTRAL)
120 VAC
INPUT
TACO
L1 L2 T T ZONE
CONTROL
END SWITCH
C1 ZC
B2 C2 ZR B1
CIRCULATOR
ON BOILER HONEYWELL L8124M OR EQUAL
(IF ATTACHED) LINE VOLTAGE
OIL BURNER RELAY
OR GAS VALVE
L1 L2
(HOT) (NEUTRAL)
120 VAC
INPUT
TACO
L1 L2 T T ZONE
CONTROL
END SWITCH
C1 C2 B1 B2
81
Aquastat Wiring
TACO
TV W T ZONE
CONTROL
END SWITCH
Z CIRCULATOR
ON BOILER
(IF ATTACHED)
C1 C2
B1 B2 L1 L2
120 VAC
L1 INPUT
L2
LOW VOLTAGE (HOT) (NEUTRAL) HONEYWELL L8148E OR EQUAL
GAS VALVE
TACO
TV W T ZONE
CONTROL
END SWITCH
TP Z CIRCULATOR
ON BOILER
(IF ATTACHED)
C1 C2
MILLI-
VOLTAGE
GAS B1 B2 B3 L1 L2
VALVE
120 VAC
L1 INPUT
L2
LOW VOLTAGE (HOT) (NEUTRAL) HONEYWELL L8148J OR EQUAL
OR
GAS VALVE
L1 L2
(HOT) (NEUTRAL)
120 VAC
INPUT
CIRCULATOR
ZC ON BOILER
(IF ATTACHED)
ZR
T T F F
CAD CELL
HONEYWELL L8182D OR EQUAL
82
Aquastat Wiring
L1 120 VAC L2
(HOT) INPUT (NEUTRAL)
TACO
SWITCHING
L1 L2 T T RELAY
END SWITCH
X X ZC ZR N H
T
THERMOSTAT
(IF INDEPENDENT ZONE)
C1 ZC
B2 C2 ZR B1
CIRCULATOR
ON BOILER LINE VOLTAGE HONEYWELL L8124A & C OR EQUAL
(IF ATTACHED) OIL BURNER RELAY
OR GAS VALVE
THERMOSTAT
T (IF INDEPENDENT ZONE) TACO
SWITCHING
RELAY
END SWITCH
TV T Z X X ZC ZR N H
ZC ZR B1
LINE
L1 L2 B2 C1 VOLTAGE
C2
OIL BURNER
RELAY OR
120 VAC GAS VALVE
INPUT CIRCULATOR
ON BOILER
L1 L2
(IF ATTACHED)
(HOT) (NEUTRAL)
L1 120 VAC L2
(HOT) INPUT (NEUTRAL)
TACO
L1 L2 T T SWITCHING
RELAY
END SWITCH
T X X ZC ZR N H
THERMOSTAT
(IF INDEPENDENT ZONE)
C1 ZC
B2 C2 ZR B1
CIRCULATOR
ON BOILER LINE VOLTAGE
(IF ATTACHED) OIL BURNER RELAY
HONEYWELL L8124M OR EQUAL
OR GAS VALVE
83
Aquastat Wiring
L1 L2
(HOT) 120 VAC (NEUTRAL)
INPUT
L1 L2 T T
TACO
SWITCHING
R RELAY
T END SWITCH
B2 X X ZC ZR N H
3
W THERMOSTAT
(IF INDEPENDENT ZONE)
B
B
R
L6006
LOW
LIMIT C1 C2 B1 B2
CONTROLER
L1 L2
(HOT) 120 VAC (NEUTRAL)
INPUT
B1 OIL BURNER
L1 L2 AND TACO
B2 IGNITION SWITCHING
C2 RELAY
END SWITCH
C1 X X ZC ZR N H
CIRCULATOR
ON BOILER
ZC (IF ATTACHED)
ZR
T T F F
THERMOSTAT
CAD CELL
T (IF INDEPENDENT HONEYWELL L8182D OR EQUAL
ZONE)
84
Wiring for Boilers with Honeywell Aquastat Model L8124E or Equivalent
FACTORY WIRING
(unplug from B1 terminal) TACO LTR0243T-1
TV T Z
CIRCULATOR
HONEYWELL ON BOILER
L8124E (IF ATTACHED)
MALE
CONNECTOR
C1 C2
B1 B2
L1 L2
G
L1 L2
FEMALE (HOT) (NEUTRAL)
CONNECTOR 120 VAC
INPUT
TV W T
Z
CIRCULATOR
ON BOILER MALE
HONEYWELL (IF ATTACHED)
L8148E CONNECTOR
C1 C2
B1 B2
L1 L2
G
L1 L2
(HOT) (NEUTRAL)
FEMALE 120 VAC
CONNECTOR INPUT
85
Aquastat Wiring to 24VAC Low Water Cutoff
TO
THERMOSTAT TACO LNA024 or LTA024-2
N H COM NC NO
TV W T HONEYWELL
L8148E
Z
B CIRCULATOR
ON BOILER
(IF ATTACHED)
R
C1 C2
B1 B2 L1 L2 G
SPILL
SWITCH L1 L2
(HOT) (NEUTRAL)
120 VAC
INPUT
LOW VOLTAGE
GAS VALVE
TV W T HONEYWELL
L8148E
Z
CIRCULATOR
ON BOILER
(IF ATTACHED)
B
R
C1 C2
B1 B2 L1 L2 G
SPILL
SWITCH
L1 L2
(HOT) (NEUTRAL)
LOW VOLTAGE
GAS VALVE 120 VAC
INPUT
86
Instruction Sheet
SR501 Switching Relay
Typical Alternative
Features: Wiring
THERMOSTAT
Wiring
THERMOSTAT
TO: ZC
TO: TT ON BOILER TO: ZR
Power Input:
Connect 120 volt ac power to terminals N and H. TO: 120 VAC POWER TO: 120 VAC POWER
CIRCULATOR CIRCULATOR
Jumper Placement: Note: When using Alternative Wiring diagram, the boiler operating con-
The jumper is factory installed between terminals H trol’s ZC terminal will see the load of the circulator(s).
and 3 to switch power on terminals 4 n/o and 4 n/c. Warning: When using Alternative Wiring diagram, wiring instructions
must be followed so power originates from the boiler aquastat. Failure to
External Diagnostics: follow these wiring instructions may result in a secondary source of power
The External lights show full functionality of the being connected to the boiler that may activate it under certain circum-
switching relay. The green light should always be on, stances, causing injury or death.
indicating that power is connected. When the ther-
mostat calls for heat, both the appropriate circulator Terminal Description:
and red indicating light is energized. T&T Thermostat Connection
COM Common side of transformer, to power some setback thermostats
The Taco Connection: N Neutral wire of power input
Combine the reliability of the Taco Zone Valves, H Hot wire of power input
3 Common terminal for 4 n/o and 4 n/c
Priority Zoning Circulators, Thermostats, and the “00”
4 n/o Normally open terminal
family of circulators with the advanced features of the
4 n/c Normally closed terminal
Taco Zone Controls to achieve total system integra-
6 n/c Normally closed terminal
tion. No matter the application, Taco now provides
6 n/o Normally open terminal
the products to maximize system performance while
5 Common terminal for 6 n/o and 6 n/c
simplifying both installation and service.
TACO SR501 REPLACEMNENT CROSS-REFERENCE
87
Instruction Sheet
SR501-845RP Universal Replacement Relay
Typical THERMOSTAT Alternative THERMOSTAT
Wiring Wiring
Features:
Universal Replaceability
OR COMPARABLE RELAY
OR COMPARABLE RELAY
Indicator Lights
REPLACES HONEYWELL
REPLACES HONEYWELL
Operation: L2 L1 3 4 5 6 L2 L1 3 4 5 6
Connect a thermostat to the “T T” terminals on
the switching relay. When the thermostat calls for
TO: TT ON BOILER
heat, the relay is energized and power is given to TO: ZC
the circulator. CIRCULATOR
TO: ZR
CIRCULATOR
JUMPER
Power Input: TO: 120 VAC POWER TO: 120 VAC POWER
24 VAC 24 VAC
POWER POWER
X2 X2
N P ZC H X1 ZR ZONE1 ZONE2 ZONE3 N P ZC H X1 ZR ZONE1 ZONE2 ZONE3
JUMPERS JUMPERS
TO: 120 VAC POWER (NEUTRAL) TO: 120 VAC POWER (NEUTRAL)
TO: 120 VAC POWER (HOT) TO: 120 VAC POWER (HOT)
120 VOLT
120 VOLT CIRCULATORS
TO: "TT" ON AQUASTAT CONTROL TO: "ZC" ON AQUASTAT CONTROL
CIRCULATORS
Note: When using Alternative Wiring diagram, the boiler operating control’s ZC terminal will see the load of the circulator(s).
Warning: When using Alternative Wiring diagram, wiring instructions must be followed so power originates from the boiler aquastat. Failure to
follow these wiring instructions may result in a secondary source of power being connected to the boiler that may activate it under certain cir-
cumstances, causing injury or death.
Operation: When the thermostat calls for heat, the appropriate circu- Operation: When any thermostat calls for heat, the boiler and appro-
lator is energized and the isolated end switch (X1 and X2) will start the priate circulator are energized when the boiler temperature is above the
boiler. set low limit.
Jumper Placement: The jumper should be placed between terminals Jumper Placement: A jumper should be placed between terminals ZC
ZC and H. Connect the isolated end switch, X1 and X2 to the boiler and X1. Connect terminal ZC to ZC terminal on the aquastat control.
aquastat control. For zone 1 priority, remove jumper between Connect terminal ZR to ZR terminal on the aquastat control. Confirm
terminals P and ZC. polarity is consistent between boiler aquastat and switching relay. For
zone 1 priority, remove jumper between terminals
P and ZC.
Power Input: Connect 120 volt ac power input to terminals N and H. Power Input: Connect 120 volt ac power input to terminals N and H.
Neutral wire to terminal N. Hot wire to terminal H. Neutral wire to terminal N. Hot wire to terminal H.
ZONE 6 ZONE 6
PRIORITY PRIORITY
ON ON
SR 506 ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
OFF SR 506 ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
OFF
Warning: When using Alternative Wiring diagram, wiring instructions must be followed so power originates from the boiler aquastat. Failure to
follow these wiring instructions may result in a secondary source of power being connected to the boiler that may activate it under certain cir-
cumstances, causing injury or death.
Operation: When any thermostat calls for heat, the appropriate circu- Operation: When any thermostat calls for heat, the boiler and appro-
lator is energized and the isolated end switch (X and X) will start the priate circulator are energized when the boiler temperature is above the
boiler. set low limit.
Priority Operation: When zone 6 is switched to the priority setting Priority Operation: When zone 6 is switched to the priority setting
and is actuated, all other zones will stop operation until zone 6 is sat- and is actuated, all other zones will stop operation until zone 6 is sat-
isfied. When zone 6 is not switched to priority, all zones will operate isfied. When zone 6 is not switched to priority, all zones will operate
independently. independently.
Jumper Placement: The jumper should be placed between terminals Jumper Placement: MOVE the jumper between terminals ZC and ZR
ZC and ZR. Connect the isolated end switch to the aquastat control on to end switch X and ZC. Connect terminal ZC to ZC terminal on the
the boiler. aquastat control. Connect the other end switch X to ZR terminal on the
aquastat control. Confirm polarity is consistent between boiler aquas-
tat and switching relay.
Power Input: Connect 120 volt ac power input to terminals N and H. Power Input: Connect 120 volt ac power input to terminals N and H.
Neutral wire to terminal N. Hot wire to terminal H. Neutral wire to terminal N. Hot wire to terminal H.
POWER POWER
CONTROLS CONTROLS
MODE MODE
END RESET END RESET
EXPANSION THERMOSTAT RESET EXPANSION THERMOSTAT RESET
SWITCH OVERRIDE SWITCH OVERRIDE
SLAVE K1 K2 SLAVE K1 K2
POWER POWER
T STAT T STAT
FUSE FUSE
5 AMP 5 AMP
N H ZC ZR H H N H ZC ZR H H
POWER 120VAC 120VAC CIRC PRIORITY POWER 120VAC 120VAC CIRC PRIORITY
INPUT INPUT OUTPUT OUTPUT OUTPUT INPUT INPUT OUTPUT OUTPUT OUTPUT
SR 501-EXP SR 501-EXP
Warning: When using Alternative Wiring diagram, wiring instructions must be followed so power originates from the boiler aquastat. Failure to
follow these wiring instructions may result in a secondary source of power being connected to the boiler that may activate it under certain cir-
cumstances, causing injury or death.
Operation: When the thermostat calls for heat, the appropriate circulator is ener- Operation: When the thermostat calls for heat, the appropriate circulator is ener-
gized and the isolated end switch (X and X) will start the boiler. Priority Output gized when the boiler’s aquastat is above the set low limit. The ZR (120VAC) out-
has power all the time, except when the thermostat is calling. put will signal the boiler to start. Priority Output has power all the time, except
when the thermostat is calling.
Mode Operation: When the mode switch is set to NORMAL, the end switch Mode Operation: When the mode switch is set to NORMAL, the end switch
relay will be energized if any zone is in operation. When the switch is set to relay will be energized if any zone is in operation. When the switch is set to
RESET, the end switch relay will only be energized through the operation of a RESET, the end switch relay will only be energized through the operation of a
plug-in reset control or closure of Priority Input. plug-in reset control or closure of Priority Input.
Jumper Placement: The jumper should be placed between terminals ZC and H. Jumper Placement: REMOVE the jumper between terminals ZC and H. Connect
Connect the isolated end switch to the aquastat control on the boiler. terminal ZC to ZC terminal on the aquastat control. Connect terminal ZR to ZR
terminal on the aquastat control. Confirm polarity is consistent between boiler
aquastat and switching relay.
Power Input: Connect 120 volt ac power input to terminals N and H. Neutral Power Input: Connect 120 volt ac power input to terminals N and H. Neutral
wire to terminal N. Hot wire to terminal H. wire to terminal N. Hot wire to terminal H.
Expansion Connections: Set the expansion switch to MASTER on the switching Expansion Connections: Set the expansion switch to MASTER on the switching
relay that has the designated priority zone or is utilizing the PowerPort options. relay that has the designated priority zone or is utilizing the PowerPort options.
Set all other daisy chained controls to SLAVE. Connect thermostat wire (18-22 Set all other daisy chained controls to SLAVE. Connect thermostat wire (18-22
gauge) between terminals 1, 2, 3, 4 on the master control to the corresponding gauge) between terminals 1, 2, 3, 4 on the master control to the corresponding
1, 2, 3, 4 on the SLAVE control(s). Controls may be daisy chained up to 20 zones 1, 2, 3, 4 on the SLAVE control(s). Controls may be daisy chained up to 20 zones
using any combination of -EXP controls. using any combination of -EXP controls.
Features: External Indicator Lights Expandable to 20 Zones External Diagnostics: Externally visible lights show full functionality of the
Ideal for Retrofitting Contractor Friendly PC Board switching relay. The green light should always be on, indicating that power is
Priority Output Layout connected. When the thermostat calls for heat, both the appropriate circulator
Simplified Wiring Universal Thermostat and red indicating light are energized.
Add-On Power Controls Compatibility Specifications:
Sealed Relays UL Approved PRODUCT NUMBER POWER TRANSFORMER MAXIMUM DIMENSIONS OF ENCLOSURE
NUMBER OF ZONES CONTROLS VOLTAGE COMBINED LOAD WIDTH HEIGHT DEPTH
Compact Design 24 volt Power Input or Output
Fuse Protected Terminal SR501-EXP 1 1 120 VAC Input 5.0 amps 4 1/4" 5 1/4" 2 3/4"
100% Factory Tested Extended 3 Year Warranty All Switching Relays are relay type DPDT, have a thermostat current of .18, and have a
Isolated End Switch Made in the USA single phase motor rating per zone of 1/3 hp (5.0A) @ 120 VAC.
Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only with a minimum temperature rating of 60/75°C. Failure to follow this instruction can
result in personal injury or death and/or property damage. 12-18 gauge wire recommended for 120 VAC connections, 14-22 gauge wire for thermostat connections, and 14-22 gauge wire for 24 VAC source
connections.
Application Application
EXPANSION EXPANSION
CONNECTIONS CONNECTIONS
1234 PLUG-IN CARDS ZONE 6 1234
SLAVE SLAVE PLUG-IN CARDS ZONE 6
PRIORITY PRIORITY
POWER MASTER ON POWER ON
CONTROL MASTER
OFF CONTROL OFF
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6 ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
INTERFACE INTERFACE
RESET NORMAL
SIX ZONE SWITCHING RELAY SIX ZONE SWITCHING RELAY
RESET NORMAL
WITH OPTIONAL PRIORITY POWER WITH OPTIONAL PRIORITY POWER
ZONE 1 ZONE 1
ZONE 2 ZONE 2
ZONE 3 ZONE 3
ZONE 4 ZONE 4
ZONE 5 ZONE 5
24 VAC ZONE 6 24 VAC ZONE 6
120V RELAY 120V RELAY
POWER SR 506-EXP POWER SR 506-EXP
X X ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6 POWER X X ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6 POWER
END ZC ZR END ZC ZR
SWITCH 120 VOLT CIRCULATORS INPUT SWITCH 120 VOLT CIRCULATORS INPUT
Warning: When using Alternative Wiring diagram, wiring instructions must be followed so power originates from the boiler aquastat. Failure to
follow these wiring instructions may result in a secondary source of power being connected to the boiler that may activate it under certain cir-
cumstances, causing injury or death.
Operation: When any thermostat calls for heat, the appropriate circulator is Operation: When any thermostat calls for heat, the boiler and appropriate cir-
energized and the isolated end switch (X and X) will start the boiler. culator are energized when the boiler temperature is above the set low limit.
Priority Operation: When zone 6 is switched to the priority setting and is actu- Priority Operation: When zone 6 is switched to the priority setting and is actu-
ated, all other zones will stop operation until zone 6 is satisfied. When zone 6 is ated, all other zones will stop operation until zone 6 is satisfied. When zone 6 is
not switched to priority, all zones will operate independently. not switched to priority, all zones will operate independently.
Mode Operation: When the mode switch is set to NORMAL, the end switch Mode Operation: When the mode switch is set to NORMAL, the end switch
relay will be energized if any zone is in operation. When the switch is set to relay will be energized if any zone is in operation. When the switch is set to
RESET, the end switch relay will only be energized if priority zone is in operation, RESET, the end switch relay will only be energized if priority zone is in operation,
or through the operation of a plug-in reset control. or through the operation of a plug-in reset control.
Jumper Placement: The jumper should be placed between terminals ZC and ZR. Jumper Placement: MOVE the jumper between terminals ZC and ZR to end
Connect the isolated end switch to the aquastat control on the boiler. switch X and ZC. Connect terminal ZC to ZC terminal on the aquastat control.
Connect the other end switch X to ZR terminal on the aquastat control. Confirm
polarity is consistent between boiler aquastat and switching relay.
Power Input: Connect 120 volt ac power input to terminals N and H. Neutral Power Input: Connect 120 volt ac power input to terminals N and H. Neutral
wire to terminal N. Hot wire to terminal H. wire to terminal N. Hot wire to terminal H.
Expansion Connections: Set the expansion switch to MASTER on the switching Expansion Connections: Set the expansion switch to MASTER on the switching
relay that has the designated priority zone or is utilizing the PowerPort options. relay that has the designated priority zone or is utilizing the PowerPort options.
Set all other daisy chained controls to SLAVE. Connect thermostat wire (18-22 Set all other daisy chained controls to SLAVE. Connect thermostat wire (18-22
gauge) between terminals 1, 2, 3, 4 on the master control to the corresponding gauge) between terminals 1, 2, 3, 4 on the master control to the corresponding
1, 2, 3, 4 on the SLAVE control(s). Controls may be daisy chained up to 20 zones 1, 2, 3, 4 on the SLAVE control(s). Controls may be daisy chained up to 20 zones
using any combination of -EXP controls. using any combination of -EXP controls.
Features: External Indicator Isolated End Switch External Diagnostics: Externally visible lights show full functionality of the
Lights Expandable to 20 Zones switching relay. The green light should always be on, indicating that power is
Plug-In PowerPort Cards Contractor Friendly PC Board connected. When the thermostat calls for heat, both the appropriate circulator
Switchable Priority Layout and red indicating light is energized.
Simplified Wiring Universal Thermostat
Specifications:
Add-On Power Controls Compatibility PRODUCT NUMBER POWER TRANSFORMER MAXIMUM DIMENSIONS OF ENCLOSURE
Fully Enclosed Snap-Out UL Approved NUMBER OF ZONES PORTS VOLTAGE COMBINED LOAD WIDTH HEIGHT DEPTH
Relays 24 volt Power Input or Output SR503-EXP 3 with Priority 3 120 VAC Input 20 amps 10 1/4" 6 3/4" 2 3/4"
Compact Design Terminal SR504-EXP 4 with Priority 3 120 VAC Input 20 amps 10 1/4" 6 3/4" 2 3/4"
Fuse Protected Extended 3 Year Warranty SR506-EXP 6 with Priority 3 120 VAC Input 20 amps 11 3/4" 7 1/2" 3"
100% Factory Tested Made in the USA All Switching Relays are relay type DPST, have a thermostat current of .18, and have a single phase
motor rating per zone of 1/3 hp (7.2A) @ 120 VAC.
Warning: Wiring connections must be made in accordance with all applicable electrical codes and these instructions. Use copper wire only. Failure to follow this instruction can result in personal injury or
death and/or property damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire
for 24 VAC source with 5 in.lbs. max torque.
TRANSFORMER
WHITE INSTALLED
FACTORY
24 VAC
120 VAC 24 VAC
INPUT
BLACK
POWER IN
T STAT 1
T T T T T T T T T T
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 VALVE 1
TRANSFORMER
WHITE
INSTALLED
FACTORY
T STAT 2
120 VAC
HOT
T
BOILER 120 VAC
T
NEUTRAL
WHITE TRANSFORMER
INSTALLED
FACTORY
24 VAC
120 VAC 24 VAC
INPUT
BLACK
ZONE 6 PRIORITY
MODE
NORMAL RESET
OFF
POWER IN
T STAT 1
ON
VALVE 1
T T T T T T T T T T T T
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 T STAT 2
TRANSFORMER
WHITE
INSTALLED
FACTORY
VALVE 2
120 VAC
T
T JUMPER JUMPER
3&4 3&4
MAIN EXTRA
N/O COM N/C
TO CIRCULATOR SEE NOTE
END END OR BOILER
SWITCH SWITCH
AQUASTAT RELAY
PRIORITY
ZONE
DRY 1 MOTOR END
CONTACTS SWITCH
2
3
T SYSTEM CIRCULATOR
BOILER 2 WIRE ZONE VALVE TACO 4 WIRE ZONE VALVE
T (NO END SWITCH) 3 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
DHW CIRCULATOR (See Note)
NEUTRAL
120 VAC
HOT
setting and is actuated, all other zones will stop operation until Features: External Indicator Lights
zone 6 is satisfied. When zone 6 is not switched to priority, all Switchable Priority
zones will operate independently. Note: When a circulator is Simplified Wiring
used on the priority zone instead of a zone valve, jumper 3 and Works with 2, 3, or 4-Wire Zone Valves
4 of the priority zone. Compact Design
Fuse Protected
Mode Operation: When the mode switch is set to NORMAL, 100% Factory Tested
the end switch relay will be energized if any zone is in opera- Isolated End Switch
tion. When the switch is set to RESET, the end switch relay Extra Set of Dry Contacts
will only be energized if priority zone is in operation. Contractor Friendly PC Board Layout
Universal Thermostat Compatibility
The Taco Connection: Combine the reliability of the Taco UL Approved
Zone Valves, Priority Zoning Circulators, Thermostats, and the Sturdy Screw Connections
“00” family of circulators with the advanced features of the Extended 3 Year Warranty
Taco Zone Controls to achieve total system integration. No Made in the USA
matter the application, Taco now provides the products to Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper
wire only. Failure to follow this instruction can result in personal injury or death and/or property damage.
maximize system performance while simplifying both instal- 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for
lation and service. thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24 VAC source with 5 in.lbs.
max torque.
94
Instruction Sheet
ZVC404-EXP & ZVC406-EXP Zone Valve Control
WHITE
INSTALLED
FACTORY
24 VAC
120 VAC 24 VAC
INPUT
BLACK POWER PLUG-IN ZONE 6
CONTROLS CARDS PRIORITY
ON
POWER IN
SLAVE T STAT 1
1 2 3 4 T T T T T T T T T T T T OFF
EXPANSION ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 VALVE 1
MASTER T STAT 2
MODE
TRANSFORMER
RESET NORMAL
SIX ZONE ZONE VALVE CONTOL
TACO, INC ZVC406-EXP
T STAT 3
T T
BOILER
DHW 120 VAC
CIRCULATOR
(See Note)
NEUTRAL HOT
Operation/External Diagnostics: When any thermostat calls for The Taco Connection: Combine the reliability of the Taco Zone Valves,
heat, the appropriate zone valve is energized and the yellow light goes Priority Zoning Circulators, Thermostats, and the “00” family of circula-
on. When the zone valve is fully open, the red light goes on and ener- tors with the advanced features of the Taco Zone Controls to achieve
gizes the end switch relays. The green light should always be on, indi- total system integration. No matter the application, Taco now provides
cating that power is connected. the products to maximize system performance while simplifying both
Priority Operation: When zone 6 is switched to the priority setting installation and service.
and is actuated, all other zones will stop operation until zone 6 is sat-
Specifications:
isfied. When zone 6 is not switched to priority, all zones will operate PRODUCT NUMBER TRANSFORMER MAX OUTPUT DIMENSIONS OF ENCLOSURE
independently. Note: When a circulator is used on the priority zone NUMBER OF ZONES VOLTAGE AT 24 VAC WIDTH HEIGHT DEPTH
instead of a zone valve, jumper 3 and 4 of the priority zone. ZVC404-EXP 4 with Priority 120 VAC Input 80 VA 113⁄4" 71⁄2" 3"
Mode Operation: When the mode switch is set to NORMAL, both end ZVC406-EXP 6 with Priority 120 VAC Input 80 VA 113⁄4" 71⁄2" 3"
switch relays will be energized if any zone is in operation. When the All Zone Valve Controls are relay type DPDT and have a single phase motor rating per zone
of 1⁄6 hp (5A) @ 120 VAC.
mode switch is set to RESET, the end switch relay “A” will only be ener-
gized when the priority zone is in operation. The end switch relay “B” Features:
will be energized when any zone is in operation External Indicator Lights Isolated End Switch
Power Input: Connect 120 volt ac power input to leads on trans- Plug-In PowerPort Cards Expandable to 20 Zones
former. Neutral to white wire. Hot to black wire. Switchable Priority Extra Set of Dry Contacts
Expansion Connections: Set the expansion switch to MASTER on the Simplified Wiring Contractor Friendly PC
zone valve control that has the designated priority zone or is utilizing Add-On Power Controls Board Layout
the PowerPort options. Set all other daisy chained controls to SLAVE. Works with 2, 3, or 4-Wire Universal Thermostat
Connect thermostat wire (18-22 gauge) between terminals 1, 2, 3, 4 on Zone Valves Compatibility
the master control to the corresponding 1, 2, 3, 4 on the SLAVE control(s). UL Approved Sturdy Screw Connections
Controls may be daisy chained up to 20 zones using any combination Fuse Protected Extended 3 Year Warranty
100% Factory Tested Made in the USA
of Switching Relay -EXP or Zone Valve -EXP controls.
Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only. Failure to follow this instruction can result in personal injury or death and/or property
damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24 VAC source with
5 in.lbs. max torque.
95
Instruction Sheet
Hydro Air Fan Controls
THERMOSTAT To: Optional THERMOSTAT
Aquastat on
Return Line of
Hydro Coil
Operation HAFC101 and 201: Optional Power Wire Optional Power Wire To: Aquastat on
To: Optional Aquastat
to Thermostat to Thermostat Return Line of
The Hydro Air Fan Control is an interface that Requires 24VAC
or Thermostat to sense
low ambient
that Requires 24VAC Hydro Coil
end switch relay and allows the fan to operate HAFC201 Power On
Power On
Call for Heat HAFC101
at low speed when the water is above the HYDRO AIR FAN CONTROL
Fan, Cooling HYDRO AIR FAN CONTROL Call for Heat
Fan, Cooling
optional aquastat setting. When the thermo- Fan, Heating
OFF
Fan, Heating
DRY CONTACTS
stat calls for cooling, the Fan Control energizes 5 AMP 1/6 HP RATED
PUMP BOILER AIR HANDLER BOILER AIR HANDLER
ON
30 SEC @ 2 WK - PUMP
XX X X C R Y G G X X C R Y G G
Additional HAFC201 Operations: Jumper
24 VAC
24 VAC
switching relay) To: “T T” on Boiler
or Switching Relay
24 hours minimizes the chance of bacteria
Fan Relays
Outdoor Outdoor
Fan Condenser Condenser
High
Circulator
Low
Relay
Unit Unit
build-up in an open loop system. Thirty sec-
Dry Contacts
onds every two weeks minimizes seasonal To: “T T” on
Boiler or
start-up problems generally associated with Switching M
Line
M
Relay
Line
harsh water conditions. Optional aquastat or
thermostat can be connected to Freeze 1 Speed Air Handler* 2 Speed Air Handler*
Protection TT terminals to reduce the chance
of pipes freezing by energizing the pump dry * Both HAFC101 and 201 capable of 1 and 2 speed applications
contacts (boiler contacts not activated.)
Terminal Description:
Switch Settings (HAFC201): Thermostat:
1 1 minute on fan delay, in heating mode C Optional: Common side of transformer W White - Heating signal
2 3 minute on fan delay, in heating mode to power some styles of thermostats Y Yellow - Condenser signal
1&2 4 minute on fan delay, in heating mode R Red - Hot side of transformer used to G Green - Fan signal
switch all functions
3 Pump dry contact activated for 2 min-
Water Coil Aquastat:
utes every 24 hours (boiler contacts not
TT Connect to aquastat at air handler to control operation of the fan when
activated) in the heating mode. Install a jumper if the aquastat is not used
4 Pump dry contacts activated for 30 sec- Freeze Protection Aquastat:
onds every two weeks (boiler contacts TT Connect to aquastat or thermostat to sense low ambient temperature.
not activated) Reduces the chance of pipes freezing by energizing the pump dry contacts.
External Diagnostics: Pump Dry Contacts:
XX May switch pump directly by bringing in external line voltage or connect
The external lights show full functionality of
to “T T” on a switching relay.
the Hydro Air Fan Control. The green light
Boiler Dry Contacts:
should always be on, indicating that power is
XX Connect to the boiler or “T T” terminals on a switching relay.
connected. Red lights indicate fan operation
for heating and cooling modes. Air Handler:
C Common side of transformer to power the Fan Control
Warning: R Red - Hot side of transformer used to switch all functions
Wiring connections must be made in accordance with Y Yellow - Condenser signal
all applicable electrical codes. Use copper wire only.
Failure to follow this instruction can result in personal One Speed Motor:
injury or death and/or property damage. 10-18 gauge Glow Connect the fan to the relay. Keep the jumper installed between Ghigh and Glow.
wire recommended for 120 VAC connections with
9 in.lbs. max torque, 12-22 gauge wire for thermostat Two Speed Motor:
connections with 9 in.lbs. max torque, and 12-22 gauge Ghigh Remove jumper and connect Ghigh to the high speed fan relay and
wire for 24 VAC source with 5 in.lbs. max torque. connect Glow to the low speed fan relay.
96
Instruction Sheet 102-094
PC600 Post Purge Timer Plug-In PowerPort Card
SUPERSEDES: August 1, 1997 EFFECTIVE: May 1, 2000
Plant ID No. 9300-867
Operation:
Once the priority zone is satisfied, the PC600 maintains power to the circulator, but does not fire the boiler. The circulator purges excess heat into the priority zone,
minimizing standby loss during warm weather months and optimizing boiler operation when used with a boiler reset control. Power can be maintained to the circu-
lator from a minimum of 10 seconds to a maximum of 420 seconds. The power LED light is energized when the priority zone or the post purge card is in operation.
Installation:
The PC600 can be installed in any one of the PowerPort terminals located on the Taco Expandable (-EXP) Control(s). Remove the shunt/jumper between pins 9
& 10 on the PowerPort terminal before installing the PC600. Align the connector on the base of the post purge card with the PowerPort terminal on the Expandable
Control and push until the two mate.
XX Terminals (Optional):
The XX terminals on the post purge card can be wired to TT on the boiler to fire only when the priority zone is calling for heat. If using a boiler with an internal
reset control, wire the XX terminals in parallel with the TT connections of the internal reset control.
Switching Relay: Transformer and relay in one box, which allows a low voltage thermostat to control a line voltage load (circulator),
with an isolated end switch that can energize the boiler.
Zone Valve Control: Transformer and relay in one box, which allows a low voltage thermostat to control a low voltage zone valve, with
an isolated end switch that can energize the boiler and/or circulators.
Dry Contacts: Set of relay contacts that make and beak, where no voltage is present. Usually can switch 24 or 120 VAC.
Isolated End Set Switch: Set of dry contacts that make when a zone calls for heat. Usually connected to a boiler’s aquastat TT.
Mode Switch: Switch set to NORMAL – When any zone calls for heat, the end switch will make and fire the boiler.
Switch set to RESET – When any zone calls for heat, a heat demand signal is given to external add-on reset control and it controls
boiler operation.Also when the priority zone calls for heat and is switched to priority, the end switch will override reset control and
fire boiler to high limit.
TT: Where thermostat or aquastat connects on a heating control.
XX: Denotes Isolated End Switch.
Low Voltage: 24 VAC for most HVAC systems.
Line Voltage: Normally 120 VAC relative to ground.
H or L1: Hot side of line voltage.
N or L2: Neutral side of line voltage.
ZR: 120 VAC (Hot) signal from switching relay to boiler’s operating aquastat to fire the burner to high limit when any zone calls for
heat. Also ideal for controlling primary circulator.
ZC: 120 VAC (Hot) signal from boiler’s operating aquastat to switching relay allowing circulator(s) to run when aquastat is above the
set low limit.
Cold Start: A boiler that fires only when there is a call for heat.
Tankless Coil: A method of heating domestic water utilizing a heat exchanger inside a boiler.The boiler also maintains heat year round
to deliver hot water on demand.
DHW Heater: A method of heating domestic water utilizing a heat exchanger and storage tank.
Transformer: A component for increasing or reducing AC voltage. Rated in VA (volts x amps).
OHMS Law: Example: A 24 volt, 40 VA transformer can produce how much current?
RELAY CONTACTS:
98
TACO Zone Controls Cross-Reference
SWITCHING RELAYS
1 Zone Switching Relay (DPDT) SR501 AR821 (1), AR822 SR100 RA89A (2), RA845A (1), RA832A (1) 889-189 (2), 829-845 (1)
1 Zone Switching Relay Replacement PC Board (DTSP) SR501-845RP
2 Zone Switching Relay with Priority SR502 AR-861-2 (3) SR201
3 Zone Switching Relay with Priority SR503 AR-861-3 (3) SR301 R8888A1007
4 Zone Switching Relay with Priority SR504 AR-842 SR601 R8888B1005
6 Zone Switching Relay with Priority SR506 AR-866 SR601 (4)
SWITCHING RELAYS
WITH POWERPORT OPTIONS
3 Zone Switching Relay with Priority and 3 Power Ports SR503-EXP ARM-861-DP (5,6), ARM-3P
4 Zone Switching Relay with Priority and 3 Power Ports SR504-EXP ARM-842-DP (5,6), ARM-4P
6 Zone Switching Relay with Priority and 3 Power Ports SR506-EXP ARM-866-DP (5,6), ARM-6P
99
100
TACO Zone Controls Cross-Reference (Continued)
FAN CONTROLS
1 Zone Hydro Air Fan Control (1 or 2 Speed) HAFC101 ARH-1, ARH-2, ARH-3 WA300
1 Zone Hydro Air Fan Control with Time Delays (1 or 2 Speed) HAFC201
REPLACEMENT PARTS
NOTES:
1. Does not have both normally open and normally closed contacts.
2. Has only one set of normally open contacts (SPST).
3. Does not have optional priority.
4. Can be expanded to five and six zones with the addition of EXP10 relays.
5. Argo ARM units are expandable to 10 zones using special controls (ARM-1, ARM-4) with a phone jack.
TACO switching relays can be expanded up to 20 zones using any combination of -EXP models with no special connections.
6. Includes only one data port for adding data port modules.
7. All TACO zone valve controls include an extra set of dry contacts (N/O, Common, N/C).
8. VL500 is only 5 zones, 4 normal and 1 priority.
CONTROLS MADE EASY.® Printed in USA