Sei sulla pagina 1di 22




G E O E S T R U C T U R A Ingeniería Civil Ltda.
E s t r u c t u r a l G e o t é c n i c a H i d r á u l i c a

MEMORIA DE CÁLCULO

VIVIENDA SECTOR PUERTAS NEGRAS

UBICACIÓN:

COMUNA DE TALCA

ELABORADO POR:

CARLOS CRISTIAN GONZALEZ PARRA


INGENIERO CIVIL UTFSM

MAGISTER EN INGENIERIA ESTRUCTURAL Y GEOTECNICA PUC

TALCA, Febrero de 2017

1 sur # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
2 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

ÍNDICE PÁGINA

1. I N T R O D U C C I Ó N Y A N T E C E D E N T E S .......................................................................... 3
2. C A R A C T E R Í S T I C A S D E L O S E L E M E N T O S E S T R U C T U R A L E S .......................... 4
2.1. MATERIALES .......................................................................................................................... 4
2.2. NORMAS Y REFERENCIAS.......................................................................................................... 4
3. E S T A D O S D E C A R G A ........................................................................................................ 5
4. C A R G A S D E D I S E Ñ O ......................................................................................................... 7
5. G E N E R A C I Ó N D E L M O D E L O E S T R U C T U R A L ......................................................... 9
6. D I S E Ñ O E S T R U C T U R A L E N H O R M I G Ó N ............................................................... 10
7. A N E X O S ................................................................................................................................ 11
7.1. ANEXO N° 1 ANÁLISIS EN STAAD PRO DE VIGAS Y CADENAS........................................................................ 12
7.2. ANEXO N° 2 ANÁLISIS EN STAAD PRO DE COLUMNAS O PILARES ................................................................ 15
7.3. ANEXO N° 3 ANÁLISIS EN STAAD PRO DE LOSA MACIZA............................................................................... 18
7.4. ANEXO N° 4 RESULTADOS DEL PERIODO Y MASAS SÍSMICAS PARTICIPATIVAS ................................. 20

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
3 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

1. INTRODUCCIÓN Y ANTECEDENTES

La presente memoria de cálculo corresponde al diseño estructural de una Vivienda


Unifamiliar, ubicado en Sector Puertas Negras, VII Región del Maule.

El objetivo de la presente memoria es establecer las normas y estándares utilizados, las


premisas, criterios y los resultados del diseño para el desarrollo de la estructura y
cimientos de la vivienda en hormigón armado y metalcon.

La Edificación tiene una fundación corrida. La losa de entrepiso será una losa maciza de
hormigón armado, la estructura de la cubierta y las divisiones interiores se ejecutaran en
metalcon según se muestra en planos.

Se verificarán los elementos más solicitados y las deformaciones exigidas por la norma de
diseño. El modelo estructural se hace considerando las dimensiones de los elementos,
según lo indicado en los planos.

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
4 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

2. CARACTERÍSTICAS DE LOS ELEMENTOS ESTRUCTURALES

2.1. Materiales
Albañilería hecha a máquina
Hormigones:
Emplantillado H-5,
Cimientos H-15
Cadenas, pilares y sobrecimientos H-25
Acero A44-28 H
Metalcon Cintac N° 2.8 ASTM A 653 SQ Gr. 40.

2.2. Normas y Referencias

Para realizar la evaluación estructural y verificación de todos los elementos involucrados,


esto es vigas, columnas, muros, cimientos y techumbre, se consideró la siguiente
normativa y códigos de diseño:
 Ordenanza General de Urbanismo y Construcciones (Decreto 854 de 1949 y sus
modificaciones posteriores).
 Código ACI 318-05 “Requisitos del Reglamento para Concreto Estructural y
Comentario” American Concrete Institute.
 Norma NCh 433 of 96. Diseño sísmico de edificios.
 Norma NCh 1537 of 86 Diseño estructural de edificios, cargas permanentes y
sobrecargas de uso.
 NCh 1928 Of 89 Norma Chilena de albañilería confinada.
 Nch 3171 of 2010 Disposiciones Generales y Combinaciones de Carga.

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
5 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

3. ESTADOS DE CARGA

Para el análisis de la estructura hay que considerar diferentes cargas que influyen al se han
considerado los siguientes estados de carga:

a. CARGA MUERTA (D)


Corresponde al peso propio de la estructura más los elementos que en forma permanente
se encontraran apoyados en ella.

b. CARGA VIVA (L)


Corresponden a las cargas producidas por el uso y ocupación del edificio o estructura.
Estas incluyen el peso de las cargas móviles, incluyendo personas, herramientas.

c. CARGA VIVA DE TECHO (Lr)


Corresponde a la carga variable para techos inaccesibles salvo con fines de mantenimiento,
la cual es 100 kgf/m², de acuerdo con la Norma.

d. CARGA DE SISMO (E)


La carga de sismo se aplica de acuerdo a lo indicado por la Norma Chilena NCh 433, para
la séptima región.

e. COMBINACIONES DE CARGA
Para el análisis de la estructura se han considerado las siguientes combinaciones de carga
según el método de diseño por tensiones admisibles SEGÚN Nch 3171 of 2010:
Combinación Nº1 PP
Combinación Nº2 PP + SC
Combinación Nº3 PP + SISMO
Combinación Nº4 PP + VIENTO

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
6 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

Combinaciones según ACI 318:


NÚMERO
CARGAS PRIMARIAS
EN STAADPRO
1 CARGA PERMANENTE(PP)
2 CARGA VIVA DE TECHO (L)
3 CARGA VIVA DE TECHO (Lr)
4 SISMO EN X (EX)
5 SISMO EN Y (EY)
6 SISMO EN Z (EZ)
COMB. No.
COMBINACIONES MAYORADAS
EN STAADPRO
100 1.4 PP
101 1.2 PP + 1.6 L 0.5 Lr
102 1.2 PP + 0.5 L + 1.6 Lr
103 1.2 PP + EX
104 1.2 PP + EY
105 1.2 PP + EZ
106 0.9 (PP) + EX
107 0.9 (PP) + EY
108 0.9 (PP) + EZ
COMB. No.
COMBINACIONES DE SERVICIO
EN STAADPRO
300 PP
301 PP + L + Lr
302 PP + 0.75 L + 0.75 Lr
303 PP + 0.7 EX
304 PP + 0.7 EY
305 PP + 0.7 EZ
306 PP + 0.525 EX
307 PP + 0.525 EY
308 PP + 0.525 EZ
309 0.6(PP) + 0.7 EX
310 0.6(PP) + 0.7 EY
311 0.6(PP) + 0.7 EZ

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
7 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

f. DEFORMACIONES ADMISIBLES

Se consideran las siguientes deformaciones admisibles:

Deformaciones verticales: Elementos principales L/360

Elementos secundarios L/240

Deformaciones horizontales: enrejados L/360

0.002 h (Sísmicas)

g. TENSIONES ADMISIBLES DE SUELO

De acuerdo a los criterios de diseño SERVIU, se toman los siguientes valores como
tensiones admisibles.

Tensión admisible estática: σe= 0,75 kg/cm2


Tensión admisible dinámica: σs= 1,00 kg/cm2

4. CARGAS DE DISEÑO

a. Peso Propio

Albañilería q alb= 1.800 kg/m3


Hormigón q Ho=2.500 kg/m3
Techo Metalcon:
Cubierta : 10 Kgf/m²
Costaneras : 10 Kgf/m²
Estructura : 30 Kgf/m²
Aislación : 5 Kgf/m²
Suplido de Cielo : 5 Kgf/m²
Cielo : 10 Kgf/m²
PP (techo) : 70 Kgf/m²

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
8 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

b. Carga Viva

Carga viva en entrepiso de vivienda = 250 kg/m 2


Carga viva en escalera = 300 kg/m2

c. Carga Viva de Techo

Carga viva de techo = 100 kg/m2

d. Nieve (N)

Dada la ubicación en Pencahue, no se considera nieve.

e. Sismo (E)

La carga lateral producida por sismo se determina según Norma NCh 433 Of. 2009 como:
Qo = C I P
Donde:
C=coeficiente sísmico
I =coeficiente de importancia relativa del edificio
P =peso total del edificio, medido desde el nivel basal

Datos:
Ubicación: Talca, VII Región
Zona Sísmica 3: Ao = 0.40 g
Suelo Tipo E S = 1,30
Estructura de Albañilería R =4

Con los datos anteriores y según la 6.4 de la Nch433 se determina el valor máximo del
coeficiente sísmico:
C max = 0.55 S Ao /g
C max = 0.28

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
9 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

5. GENERACIÓN DEL MODELO ESTRUCTURAL

El análisis y diseño de la estructura de la edificación se plantea mediante un modelo


matemático, capaz de predecir el comportamiento que tendrá la estructura cuando se vea
sometida a las solicitaciones generadas por los estímulos aplicados. Se consideran los
estímulos que se producirán en condiciones normales y eventuales durante la vida útil de
la estructura.
A continuación se muestra la idealización de la estructura:

Figura 1. Idealización (Lado Oriente) de Vivienda Puertas Negras

Figura 2. Idealización (Lado Poniente) de Vivienda Puertas Negras

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
10 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

Figura 3. Dimensiones de Planta de Vivienda

6. DISEÑO ESTRUCTURAL EN HORMIGÓN

Losa Maciza

Se analizó la losa maciza, en una franja de un (1,00) metro de ancho, armada en dos
dirección. Considerando ambos extremos continuos el espesor mínimo es L/40, siendo L =
480 cm, dando como resultado una altura de losa de (480 /40= 12) 12 cm.

Los resultados del análisis de la losa maciza, se pueden observar en el Anexo 3

Vigas

Para el diseño de las vigas, primeramente, se obtuvo su altura preliminar asociada a su luz
libre, y se asignaron las propiedades y dimensiones a los elementos, para posteriormente
verificar que las mismas son suficientes para soportar las fuerzas y momentos máximos
probables con un arreglo de fierros adecuado.

Para el armado a flexión de los pórticos se utilizó la herramienta TRACK 2 en Staad Pro, la
cual provee las áreas de fierros necesarias en los distintos tramos de las vigas.

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
11 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

El armado por corte de los pórticos se calculó de acuerdo a al capítulo 21.5.4 de la norma
ACI 318, en el Anexo 5 se muestra el diseño de la viga más desfavorable.

Los resultados del análisis de vigas, se pueden observar en el Anexo 1

Columnas
Las columnas fueron diseñadas a flexocompresión y corte haciendo uso de software
STAAD.Pro V8i para obtener el área de fierros necesaria para la máxima fuerza axial y
máximos momentos generados, se verificó que la cuantía de fierros no excediera el 4%.

Los resultados del análisis de columnas, se pueden observar en el Anexo 2

Cimientos

Criterios de Diseño
Los Cimientos corridos deberán ser capaces de soportar adecuadamente todas las cargas
aplicadas durante la construcción y operación de las estructuras, sin sufrir daños, fallas, ni
asentamientos excesivos que provoquen pérdidas de los servicios, ni disminución de su
vida útil.
Los Cimientos corridos de la estructura fueron diseñadas para ejercer una presión sobre el
suelo aproximadamente igual para que los asentamientos sean similares y uniformes.
Los Cimientos serán de hormigón armado, vaciadas en sitio, y los mismos fueron
dimensionadas limitando las presiones sobre el suelo, de modo que los asentamientos
permisibles y los valores de capacidad soporte no sean excedidos.

7. ANEXOS

Carlos González Parra


Ingeniero Civil

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
12 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

7.1. Anexo N° 1 Análisis en Staad Pro de Vigas y Cadenas

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
13 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

ACI 318-11 BEAM NO. 58 DESIGN RESULTS


=============================================

LEN - 5000. MM FY - 412. FC - 25. MPA, SIZE - 200. X 400. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
___________________________________________________________________

1 44. 2 - 12MM 0. 5000. YES YES


|----------------------------------------------------------------|
| CRITICAL POS MOMENT= 10.07 KN-MET AT 0.MM, LOAD 131|
| REQD STEEL= 102.MM2, RHO=0.0014, RHOMX=0.0191 RHOMN=0.0033 |
| MAX/MIN/ACTUAL BAR SPACING= 288./ 37./ 113. MMS |
| REQD. DEVELOPMENT LENGTH = 361. MMS |
|----------------------------------------------------------------|

Cracked Moment of Inertia Iz at above location = 18078.8 cm^4

2 356. 2 - 12MM 0. 2552. YES NO


|----------------------------------------------------------------|
| CRITICAL NEG MOMENT= 15.14 KN-MET AT 0.MM, LOAD 103|
| REQD STEEL= 155.MM2, RHO=0.0022, RHOMX=0.0191 RHOMN=0.0033 |
| MAX/MIN/ACTUAL BAR SPACING= 288./ 37./ 113. MMS |
| REQD. DEVELOPMENT LENGTH = 361. MMS |
|----------------------------------------------------------------|

Cracked Moment of Inertia Iz at above location = 18078.8 cm^4

3 356. 2 - 12MM 2656. 5000. NO YES


|----------------------------------------------------------------|
| CRITICAL NEG MOMENT= 17.24 KN-MET AT 5000.MM, LOAD 107|
| REQD STEEL= 177.MM2, RHO=0.0025, RHOMX=0.0191 RHOMN=0.0033 |
| MAX/MIN/ACTUAL BAR SPACING= 288./ 37./ 113. MMS |
| REQD. DEVELOPMENT LENGTH = 361. MMS |
|----------------------------------------------------------------|

Cracked Moment of Inertia Iz at above location = 18078.8 cm^4

REQUIRED REINF. STEEL SUMMARY :

-------------------------------
SECTION REINF STEEL(+VE/-VE) MOMENTS(+VE/-VE) LOAD(+VE/-VE)

( MM ) (SQ. MM ) (KNS-MET )
0. 79./ 119. 10./ 15. 131/ 103
417. 75./ 89. 10./ 11. 131/ 103
833. 69./ 63. 9./ 8. 107/ 127
1250. 63./ 41. 8./ 5. 107/ 127
1667. 53./ 22. 7./ 3. 107/ 127
2083. 40./ 5. 5./ 1. 107/ 127
2500. 24./ 0. 3./ 0. 107/ 0
2917. 25./ 0. 3./ 0. 107/ 0
3333. 34./ 18. 4./ 2. 107/ 127
3750. 39./ 41. 5./ 5. 131/ 103
4167. 45./ 70. 6./ 9. 131/ 103
4583. 48./ 101. 6./ 13. 131/ 103
5000. 48./ 136. 6./ 17. 127/ 107

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
14 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

B E A M N O. 58 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 4.88 KNS Vc= 58.56 KNS Vs= 0.00 KNS
Tu= 0.04 KN-MET Tc= 1.6 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 6.47 KNS Vc= 58.56 KNS Vs= 0.00 KNS
Tu= 0.04 KN-MET Tc= 1.6 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___ 61J____________________ 5000X 200X 400_____________________ 68J____


| |
||===================================== ===================================||
| 2No12 H 356. 0.TO 2552 2No12 H 356.2656.TO 5000 |
| |
| 2No12 H 44. 0.TO 5000 |
||=========================================================================||
| |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| oo | | oo | | oo | | oo | | oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 | | 2#12 | | 2#12 | | 2#12 | | 2#12 |
| | | | | | | | | | | | | |
| 2#12 | | 2#12 | | 2#12 | | 2#12 | | 2#12 | | 2#12 | | 2#12 |
| oo | | oo | | oo | | oo | | oo | | oo | | oo |
| | | | | | | | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
15 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

7.2. Anexo N° 2 Análisis en Staad Pro de Columnas o Pilares

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
16 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

ACI 318-11 COLUMN NO. 21 DESIGN RESULTS


===============================================

FY - 413.7 FC - 27.6 MPA, SQRE SIZE - 200.0 X 200.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 400.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 12 MM 1.131 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 192.00 MM

ACI 318-11 COLUMN NO. 45 DESIGN RESULTS


===============================================

FY - 413.7 FC - 27.6 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


AREA OF STEEL REQUIRED = 1360.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

8 - 16 MM 2.011 127 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 148.88 MM

ACI 318-11 COLUMN NO. 35 DESIGN RESULTS


===============================================

FY - 413.7 FC - 27.6 MPA, RECT SIZE - 200.0 X 450.0 MMS, TIED


AREA OF STEEL REQUIRED = 1530.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

8 - 16 MM 2.011 107 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 157.91 MM

ACI 318-11 COLUMN NO. 38 DESIGN RESULTS


===============================================

FY - 413.7 FC - 27.6 MPA, RECT SIZE - 200.0 X 500.0 MMS, TIED


AREA OF STEEL REQUIRED = 1497.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

8 - 16 MM 2.011 131 STA 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
17 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

ACI 318-11 COLUMN NO. 4236 DESIGN RESULTS


===============================================

FY - 413.7 FC - 27.6 MPA, RECT SIZE - 200.0 X 600.0 MMS, TIED


AREA OF STEEL REQUIRED = 1578.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

8 - 16 MM 2.011 139 STA 0.900


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

ACI 318-11 COLUMN NO. 43 DESIGN RESULTS


===============================================

FY - 413.7 FC - 27.6 MPA, RECT SIZE - 200.0 X 700.0 MMS, TIED


AREA OF STEEL REQUIRED = 1488.2 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

10 - 16 MM 2.011 115 STA 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

ACI 318-11 COLUMN NO. 12 DESIGN RESULTS


===============================================

FY - 413.7 FC - 27.6 MPA, RECT SIZE - 200.0 X 800.0 MMS, TIED


AREA OF STEEL REQUIRED = 2008.6 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

10 - 16 MM 2.011 111 STA 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
18 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

7.3. Anexo N° 3 Análisis en Staad Pro de Losa Maciza

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
19 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

ACI 318-11 ELEMENT DESIGN SUMMARY


=====================================

ELEMENT LONG. REINF MOM-X /LOAD TRANS. REINF MOM-Y /LOAD


(SQ.MM/MM) (KN-MM/MM) (SQ.MM/MM) (KN-MM/MM)

FY: 411.876 MPA FC: 24.516 MPA COVER (TOP): 25.000 MM


COVER (BOTTOM): 25.000 MM TH: 120.000 MM
1477 TOP : Longitudinal direction - Only minimum steel required.
1477 BOTT: Longitudinal direction - Only minimum steel required.
1477 TOP : Transverse direction - Only minimum steel required.
1477 BOTT: Transverse direction - Only minimum steel required.
1477 TOP : 0.240 4.16 / 135 0.240 0.53 / 111
BOTT: 0.240 4.80 / 115 0.240 0.50 / 139

FY: 411.876 MPA FC: 24.516 MPA COVER (TOP): 25.000 MM


COVER (BOTTOM): 25.000 MM TH: 120.000 MM
1478 TOP : Longitudinal direction - Only minimum steel required.
1478 BOTT: Longitudinal direction - Only minimum steel required.
1478 TOP : Transverse direction - Only minimum steel required.
1478 BOTT: Transverse direction - Only minimum steel required.
1478 TOP : 0.240 1.05 / 127 0.240 0.13 / 135
BOTT: 0.240 2.02 / 107 0.240 0.16 / 115

FY: 411.876 MPA FC: 24.516 MPA COVER (TOP): 25.000 MM


COVER (BOTTOM): 25.000 MM TH: 120.000 MM
1479 TOP : Longitudinal direction - Only minimum steel required.
1479 BOTT: Longitudinal direction - Only minimum steel required.
1479 TOP : Transverse direction - Only minimum steel required.
1479 BOTT: Transverse direction - Only minimum steel required.
1479 TOP : 0.240 1.93 / 135 0.240 0.40 / 111
BOTT: 0.240 2.26 / 115 0.240 0.36 / 139

FY: 411.876 MPA FC: 24.516 MPA COVER (TOP): 25.000 MM


COVER (BOTTOM): 25.000 MM TH: 120.000 MM
1480 TOP : Longitudinal direction - Only minimum steel required.
1480 BOTT: Longitudinal direction - Only minimum steel required.
1480 TOP : Transverse direction - Only minimum steel required.
1480 BOTT: Transverse direction - Only minimum steel required.
1480 TOP : 0.240 6.33 / 111 0.240 1.09 / 111
BOTT: 0.240 5.04 / 139 0.240 0.84 / 139

FY: 411.876 MPA FC: 24.516 MPA COVER (TOP): 25.000 MM


COVER (BOTTOM): 25.000 MM TH: 120.000 MM
1481 TOP : Longitudinal direction - Only minimum steel required.
1481 BOTT: Longitudinal direction - Only minimum steel required.
1481 TOP : Transverse direction - Only minimum steel required.
1481 BOTT: Transverse direction - Only minimum steel required.
1481 TOP : 0.240 5.91 / 111 0.240 1.70 / 111
BOTT: 0.240 5.27 / 139 0.240 1.58 / 139

FY: 411.876 MPA FC: 24.516 MPA COVER (TOP): 25.000 MM


COVER (BOTTOM): 25.000 MM TH: 120.000 MM
1482 TOP : Longitudinal direction - Only minimum steel required.
1482 BOTT: Longitudinal direction - Only minimum steel required.
1482 TOP : Transverse direction - Only minimum steel required.
1482 BOTT: Transverse direction - Only minimum steel required.
1482 TOP : 0.240 3.92 / 135 0.240 0.34 / 103
BOTT: 0.240 4.58 / 115 0.240 0.28 / 131

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
20 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

7.4. Anexo N° 4 Resultados del Periodo y Masas Sísmicas Participativas

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
21 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

EIGEN METHOD : SUBSPACE


-------------------------
NUMBER OF MODES REQUESTED = 25
NUMBER OF EXISTING MASSES IN THE MODEL = 1752
NUMBER OF MODES THAT WILL BE USED = 25

STAAD SPACE -- PAGE NO. 27

CALCULATED FREQUENCIES FOR LOAD CASE 4

MODE FREQUENCY(CYCLES/SEC) PERIOD(SEC) ACCURACY

1 3.105 0.32205 2.987E-16


2 4.161 0.24034 3.327E-16
3 4.970 0.20120 3.497E-16
4 5.924 0.16881 9.848E-16
5 6.453 0.15497 0.000E+00
6 6.723 0.14875 2.167E-15
7 6.904 0.14484 2.054E-15
8 6.987 0.14312 1.180E-16
9 7.029 0.14227 2.098E-15
10 7.329 0.13645 1.072E-15
11 7.872 0.12704 2.156E-14
12 8.389 0.11920 2.471E-14
13 9.071 0.11025 1.131E-12
14 9.183 0.10890 1.943E-12
15 9.286 0.10769 2.174E-12
16 9.292 0.10762 1.019E-11
17 9.651 0.10362 2.020E-13
18 10.217 0.09788 1.462E-12
19 10.372 0.09641 6.122E-11
20 10.471 0.09550 1.365E-10
21 10.695 0.09350 1.737E-09
22 11.256 0.08884 3.767E-09
23 11.793 0.08479 2.169E-07
24 11.974 0.08351 1.777E-07
25 12.269 0.08151 6.646E-08
26 13.056 0.07660 6.063E-07
27 13.279 0.07531 1.028E-06
28 14.104 0.07090 1.539E-06
29 14.287 0.06999 1.485E-06

1 norte # 690 Ed. Plaza Talca Of. 906 Fono 71-228722 Info@geoestructura.cl
22 de 22
G E O E S T R U C T U R A
I ngeniería Civil Ltda. Rev. A, Febrero de 2017

MASS PARTICIPATION FACTORS IN PERCENT


-------------------------------------- ------------------

MODE X Y Z SUMM-X SUMM-Y SUMM-Z

1 0.02 0.31 0.00 0.024 0.314 0.001


2 1.84 0.90 0.00 1.869 11.214 0.005
3 46.10 0.05 0.33 47.970 23.161 0.339
4 0.17 0.00 0.25 48.138 38.261 0.593
5 9.07 0.00 41.76 57.208 38.261 42.355
6 0.16 0.00 0.32 57.369 38.261 42.679
7 1.13 0.00 4.77 58.494 41.264 47.449
8 0.00 0.00 9.30 58.495 41.264 56.747
9 0.68 0.76 1.28 59.177 52.028 58.024
10 16.95 0.06 16.30 76.127 62.087 74.321
11 0.11 0.00 0.02 76.234 62.087 74.342
12 12.27 0.01 1.81 88.503 64.095 76.147
13 2.57 0.39 0.79 91.069 68.483 76.941
14 0.39 1.26 0.19 91.455 73.746 77.133
15 0.02 0.03 0.01 91.471 75.772 77.146
16 1.95 0.00 0.01 93.426 79.776 77.152
17 0.68 0.01 2.31 94.106 81.787 79.463
18 0.58 0.00 6.53 94.685 83.789 85.993
19 0.09 0.40 1.49 94.775 84.188 87.484
20 0.13 0.00 1.88 94.905 87.191 89.361
21 1.19 0.01 0.55 96.095 87.200 89.915
22 0.53 0.01 0.16 96.627 89.210 90.076
23 0.44 0.00 1.21 97.065 90.211 91.283
24 0.15 0.00 1.67 97.212 91.212 92.956
25 0.06 0.03 0.04 97.269 94.237 92.997