WL Liquid Scale

Remover
Virginia WL Liquid Scale Remover is
ideal for removing scales from water-
cooled condensers, chillers, hydronic
boilers or any other non-potable
water system when economy and ease
of use is of maximum importance. Of
all water quality problems, scale is
the most prevalent. Scale is primarily
composed of calcium and magnesium
carbonate, but may also form as
calcium sulfate, silica complexes and
ferric oxide. These materials enter the
system in a dissolved state and due to
certain chemical and physical forces,
they become insoluble and fall out of
solution. Scale in a system can coat
the inside of the tubing, restricting
water flow and acting as an insulator,
reducing the transfer of heat as well
as increasing water demand from
systems.

Made from a hydrochloric acid


base, Virginia Liquid Scale Remover
for standard descaling contains
anti-foaming agents in its formula. Characteristics: Uses:
However, in some instances, Any non-potable cooling or heating
• Inhibited hydrochloric acid base.
additional quantities may be required water application which requires
to control excessive foaming. Our • Contains antifoaming agents. descaling through the use of an
catalog number AF1 AntiFoam is • Includes pH test papers. effective and economical solution
available for this purpose. Virginia that is easy to use.
Liquid Scale Remover contains an • Available in two different
inhibitor to minimize potential metal concentrations.
damage and comes complete with • Easy to use.
pH test papers to test the solution • Economical.
acid strength.
WL Liquid Scale Remover
Dilution Ratios: Gallons of Gallons of
The following table, developed Thickness
Type of Regular Liquid Concentrated Liquid
from field experience, will provide of Scale
Scale (WL) per 10 Tons (WL C) per 10 Tons
Deposit
a rough estimate of the actual of System Capacity of System Capacity
requirement for complete scale Less than
removal. The chemical requirements Light Scale 2.5 2
1/16"
in this table are approximations
only – they are not intended for use Average Scale 1/16" to 1/8" 5 4
as final materials costs when making
Heavy Scale 1/8" to 1/4" 10 7
up bids on specific jobs. Actual
requirements may vary due to scale Very Heavy
1/4" and over 15 10
Scale
composition and thickness.

Suggested Instructions for Use: the sump and resume normal


Copper Pipe Steel Pipe
1. Turn off the circulating pump. operation.
Nominal U.S. gal. Nominal U.S. gal.
2. Drain and flush all sludge and Size per foot Size per foot Cautionary Notes:
dirt out of the sump since these 3/8 .008 3/8 .010 • For professional use only.
consume and waste cleaner. 1/2 .012 1/2 .016
• Never leave the cleaning solution
3. Close, bleed and refill the sump 5/8 .018 3/4 .028 in the equipment for more than 10
with fresh water. 3/4 .025 1 .046 hours; scale may be redeposited
4. Estimate the total number of 1 .043 1-1/2 .102 and will be more resistant to
gallons of water in the system 1-1/2 .093 2 .170
further chemical cleaning.
and add initial dosage of 2 .1607 • Exceeding concentration can result
chemical at a ratio of one gallon in damage to sheet metal.
of Virginia Liquid Scale Remover 5. Operate the system in the normal • Do not use on stainless steel.
to 15 gallons of water (One manner. Check the cleaning
gallon of Concentrated Liquid solution with the Exact Control Refer to MSD sheet for further
Scale Remover to 20 gallons Test Strips® every 15 to 20 minutes information. MSD sheets are
of water). To determine the (See instructions accompanying the available at your local wholesaler.
systems capacity in gallons, the test strips). Package Sizes Available:
best source for system capacity
6. A
 lowering of head pressure to Standard formulation available in
is the manufacturer of the
normal levels will indicate when the 1 and 5 gallon containers.
equipment. Another method is to
unit is clean. Inspect the tubes when
fill the system up completely and
possible.
measure the capacity as you drain NON-WARRANTY – All data, statements and
it. If these options aren’t possible, 7. When cleaning is complete, drain recommendations contained herein are based
upon the best information available and are
you can calculate your system the spent solution. Disposal believed to be reliable. However, no warranty,
capacity based on the following must be in accordance with all either expressed or implied, is made concern-
formulas: applicable Federal, State and ing the application of this product since the
customer’s use cannot be controlled. State-
Local regulations. Notes: Acid
Rectangular Objects (Tanks and ments concerning the use of this product
should be neutralized with soda should not be construed as suggestions,
Sumps):
ash or other means before disposal. recommendations or inducements that it be
(Length) x (Width) x (Height)(in feet) used in violation of patent rights or in violation
x 7.5 gal/cu.ft. = gallons Do not drain to lawns or plants of any applicable laws or regulations. Product
that might be damaged. improvement is a continuous process at
Cylindrical Objects (Vessels): Virginia, therefore, product specifications may
(3.14) x (Radius2) x (Height)(in feet) 8. Rinse out the system with at least change without notice. Please contact your
x 7.5 gal/cu.ft. = gallons two fillings of fresh water. Refill representative or distributor to verify details.

© 2012 Parker Hannifin Corporation Form P-378_112012