UPS System
Technical Specifications
380 V, 400 V, 415 V
03/2017
www.schneider-electric.com
Legal Information
The Schneider Electric brand and any registered trademarks of Schneider Electric
Industries SAS referred to in this guide are the sole property of Schneider Electric
SA and its subsidiaries. They may not be used for any purpose without the owner's
permission, given in writing. This guide and its content are protected, within the
meaning of the French intellectual property code (Code de la propriété
intellectuelle français, referred to hereafter as "the Code"), under the laws of
copyright covering texts, drawings and models, as well as by trademark law. You
agree not to reproduce, other than for your own personal, noncommercial use as
defined in the Code, all or part of this guide on any medium whatsoever without
Schneider Electric's permission, given in writing. You also agree not to establish
any hypertext links to this guide or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the guide or its
content, except for a non-exclusive license to consult it on an "as is" basis, at your
own risk. All other rights are reserved.
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
As standards, specifications, and designs change from time to time, please ask for
confirmation of the information given in this publication.
UPS System
Table of Contents
Important Safety Instructions — SAVE THESE
INSTRUCTIONS .........................................................................................5
Electromagnetic Compatibility .....................................................................6
Safety Precautions .....................................................................................6
Technical Data .............................................................................................8
System Overview .......................................................................................8
Model List ................................................................................................10
Overview of Configurations .......................................................................10
Overview of UPSs with 1000 kW I/O Cabinet – Single Utility/Mains
System .............................................................................................. 11
Overview of UPSs with 1000 kW I/O Cabinet – Dual Utility/Mains
System .............................................................................................. 11
Overview of UPSs with 1500 kW I/O Cabinet – Single Utility/
Mains.................................................................................................12
Overview of UPSs with 1500 kW I/O Cabinet – Dual Utility/Mains ...........12
Input Power Factor ...................................................................................13
Input Voltage Window ...............................................................................13
Efficiency .................................................................................................15
Derating Due to Load Power Factor ...........................................................16
Batteries ..................................................................................................16
End of Discharge Voltage ....................................................................16
Battery Voltage Range ........................................................................17
Compliance..............................................................................................17
Communication and Management .............................................................18
Overview of Input Contacts and Output Relays......................................18
EPO Connections ...............................................................................19
Facility Planning ........................................................................................20
Specifications for UPSs with 1000 kW I/O Cabinet ......................................20
Input Specifications.............................................................................20
Bypass Specifications .........................................................................20
Output Specifications ..........................................................................21
Battery Specifications..........................................................................21
Recommended Upstream Protection and Cable Sizes ...........................22
UPS Weights and Dimensions .............................................................24
Clearance ..........................................................................................24
Specifications for UPSs with 1500 kW I/O Cabinet ......................................25
Input Specifications.............................................................................25
Bypass Specifications .........................................................................25
Output Specifications ..........................................................................26
Battery Specifications..........................................................................27
Recommended Upstream Protection and Cable Sizes ...........................27
UPS Weights and Dimensions .............................................................29
Clearance ..........................................................................................29
Guidance for Organizing Battery Cables.....................................................29
Torque Specifications................................................................................30
Environment.............................................................................................30
Heat Dissipation .................................................................................30
990–5850B-001 3
UPS System
Drawings ....................................................................................................32
Galaxy VX 1000 kW Single Mains ..............................................................33
Galaxy VX 1500 kW Single Mains ..............................................................34
Options .......................................................................................................35
Hardware Options.....................................................................................35
Configuration Options ...............................................................................35
Limited Factory Warranty .........................................................................36
4 990–5850B-001
Important Safety Instructions — SAVE THESE
INSTRUCTIONS UPS System
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
990–5850B-001 5
Important Safety Instructions — SAVE THESE
UPS System INSTRUCTIONS
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
Electromagnetic Compatibility
NOTICE
RISK OF ELECTROMAGNETIC DISTURBANCE
This is a product Category C3 according to IEC 62040-2. This is a product for
commercial and industrial applications in the second environment - installation
restrictions or additional measures may be needed to prevent disturbances. The
second environment includes all commercial, light industry, and industrial
locations other than residential, commercial, and light industrial premises directly
connected without intermediate transformer to a public low-voltage mains
supply. The installation and cabling must follow the electromagnetic compatibility
rules, e.g.:
• the segregation of cables,
• the use of shielded or special cables when relevant,
• the use of grounded metallic cable tray and supports.
Failure to follow these instructions can result in equipment damage.
Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The product must be installed according to the specifications and
requirements as defined by Schneider Electric. It concerns in particular the
external and internal protections (upstream circuit breakers, battery circuit
breakers, cabling, etc.) and environmental requirements. No responsibility is
assumed by Schneider Electric if these requirements are not respected.
• After the UPS system has been electrically wired, do not start up the system.
Start-up must only be performed by Schneider Electric.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS System must be installed according to local and national regulations.
Install the UPS according to:
• IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
4–42 - protection against thermal effect, and 60364–4–43 - protection against
overcurrent), or
• NEC NFPA 70
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.
6 990–5850B-001
Important Safety Instructions — SAVE THESE
INSTRUCTIONS UPS System
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Install the UPS system in a temperature controlled area free of conductive
contaminants and humidity.
• Install the UPS system on a non-inflammable, level, and solid surface (e.g.
concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS is not designed for and must therefore not be installed in the following
unusual operating environments:
• Damaging fumes
• Explosive mixtures of dust or gases, corrosive gases, or conductive or radiant
heat from other sources
• Moisture, abrasive dust, steam or in an excessively damp environment
• Fungus, insects, vermin
• Salt-laden air or contaminated cooling refrigerant
• Pollution degree higher than 2 according to IEC 60664-1
• Exposure to abnormal vibrations, shocks, and tilting
• Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.
NOTICE
RISK OF OVERHEATING
Respect the clearance requirements around the UPS system and do not cover
the product’s ventilation openings when the UPS system is in operation.
Failure to follow these instructions can result in equipment damage.
NOTICE
RISK OF EQUIPMENT DAMAGE
Do not connect the UPS output to regenerative load systems including
photovoltaic systems and speed drives.
Failure to follow these instructions can result in equipment damage.
990–5850B-001 7
UPS System Technical Data
Technical Data
System Overview
Each Galaxy VX UPS consists of the following components:
• An I/O cabinet for wield wiring containing the static switch, a backfeed
protection switch, and the user interface.
• A number of 250 kW power cabinets containing the power electronics.
8 990–5850B-001
Technical Data UPS System
990–5850B-001 9
UPS System Technical Data
Model List
UPSs with 1000 kW I/O Cabinet
• GVX500K500HS: Galaxy VX 500 kW 400 V, start-up 5x8
• GVX750K500HS: Galaxy VX 500 kW N+1 400 V N+1 redundant UPS, start-up
5x8
• GVX625K625HS: Galaxy VX 625 kW 400 V, start-up 5x8
• GVX1000K625HS: Galaxy VX 625 kW 400 V N+1 redundant UPS, start-up 5x8
• GVX500K750HS: Galaxy VX 500 kW 400 V scalable to 750 kW, start-up 5x8
• GVX750K750HS: Galaxy VX 750 kW 400 V, start-up 5x8
• GVX1000K750HS: Galaxy VX 750 kW 400 V N+1 redundant UPS, start-up 5x8
• GVX500K1000HS: Galaxy VX 500 kW 400 V scalable to 1000 kW, start-up 5x8
• GVX625K1000HS: Galaxy VX 625 kW 400 V scalable to 1000 kW, start-up 5x8
• GVX750K1000HS: Galaxy VX 750 kW 400 V scalable to 1000 kW, start-up 5x8
• GVX1000K1000HS: Galaxy VX 1000 kW 400 V, start-up 5x8
• GVX1250K1000HS: Galaxy VX 1000 kW 400 V N+1 redundant UPS, start-up
5x8
Overview of Configurations
Breakers in the System
BB Battery breaker
10 990–5850B-001
Technical Data UPS System
990–5850B-001 11
UPS System Technical Data
12 990–5850B-001
Technical Data UPS System
50% 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99
75% 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99
100% 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
50% 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99
75% 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99
100% 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
990–5850B-001 13
UPS System Technical Data
14 990–5850B-001
Technical Data UPS System
Efficiency
NOTE: Efficiencies are preliminary until validated efficiency data is available.
Load 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
25% 95.2 95.3 95.4 98.3 98.3 98.3 97.6 97.6 97.6 94.9 94.9 94.9
50% 95.9 96.0 96.1 98.8 98.8 98.8 98.6 98.6 98.6 95.6 95.6 95.6
75% 95.7 95.8 95.9 99.0 99.0 99.0 98.8 98.8 98.8 95.7 95.7 95.7
100% 94.9 95.0 95.1 99.0 99.0 99.0 98.8 98.8 98.8 95.5 95.5 95.5
Load 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
25% 95.7 95.8 95.9 98.5 98.5 98.5 97.6 97.6 97.6 95.2 95.2 95.2
50% 96.1 96.2 96.3 98.9 98.9 98.9 98.6 98.6 98.6 95.6 95.6 95.6
75% 95.5 95.6 95.7 99.0 99.0 99.0 98.8 98.8 98.8 95.6 95.6 95.6
100% 94.6 94.7 94.8 99.0 99.0 99.0 98.8 98.8 98.8 95.3 95.3 95.3
Load 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
25% 95.4 95.5 95.6 98.2 98.2 98.2 97.3 97.3 97.3 94.9 94.9 94.9
50% 95.9 96.0 96.1 98.8 98.8 98.8 98.4 98.4 98.4 95.4 95.4 95.4
75% 95.7 95.8 95.9 98.9 98.9 98.9 98.8 98.8 98.8 95.6 95.6 95.6
100% 95.0 95.1 95.2 98.9 98.9 98.9 98.8 98.8 98.8 95.3 95.3 95.3
Load 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
25% 95.1 95.2 95.3 97.9 97.9 97.9 97.0 97.0 97.0 94.6 94.6 94.6
50% 95.7 95.8 95.9 98.6 98.6 98.6 98.2 98.2 98.2 95.2 95.2 95.2
75% 95.7 95.8 95.9 98.9 98.9 98.9 98.8 98.8 98.8 95.6 95.6 95.6
100% 95.0 95.1 95.2 98.9 98.9 98.9 98.8 98.8 98.8 95.3 95.3 95.3
990–5850B-001 15
UPS System Technical Data
Load 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
25% 94.8 94.9 95.0 97.6 97.6 97.6 96.7 96.7 96.7 94.3 94.3 94.3
50% 95.5 95.6 95.7 98.4 98.4 98.4 98.0 98.0 98.0 95.0 95.0 95.0
75% 95.7 95.8 95.9 98.9 98.9 98.9 98.8 98.8 98.8 95.6 95.6 95.6
100% 95.0 95.1 95.2 98.9 98.9 98.9 98.8 98.8 98.8 95.3 95.3 95.3
Batteries
End of Discharge Voltage
The voltage is 1.6 to 1.75 per cell depending on discharge ratio.
16 990–5850B-001
Technical Data UPS System
Compliance
Safety IEC 62040-1: 2008-06, 1st edition Uninterruptible Power Systems (UPS) - Part 1: General and safety requirements
for UPS
EN 62040-1: 2013-01, 1st edition amendment 1
EMC/EMI/RFI IEC 62040-2: 2005-10, 2nd edition Uninterruptible Power Systems (UPS) - Part 2: Electromagnetic compatibility
(EMC) requirements
Performance IEC 62040-3: 2011-03, 2nd edition Uninterruptible Power Systems (UPS) - Part 3: Method of specifying the
performance and test requirements
Environmental IEC 62040-4: 2013-04, 1st edition Uninterruptible Power Systems (UPS) - Part 4: Environmental aspects –
Requirements and reporting
Transportation ISTA 2B
990–5850B-001 17
UPS System Technical Data
Do not connect any circuit to the input contacts unless it can be confirmed that the
circuit is Class 2/SELV.
All circuits connected must have the same 0 V reference.
Common signalling to the input contacts must be galvanically isolated to avoid
cross currents between parallel UPSs. An external supply must be connected to
640–3640 terminal J5530 and the switch SW5500 must be in closed position
(PWR IN 24V DC SELV).
Output Relays
18 990–5850B-001
Technical Data UPS System
EPO Connections
990–5850B-001 19
UPS System Facility Planning
Facility Planning
Specifications for UPSs with 1000 kW I/O Cabinet
Input Specifications
Voltage (V) 380 400 415 380 400 415 380 400 415 380 400 415
Minimum input 340 340 353 340 340 353 340 340 353 340 340 353
voltage (V)
Maximum input 456 480 498 456 480 498 456 480 498 456 480 498
voltage (V)
Frequency range 40 – 70
(Hz)
Nominal input 800 760 731 1001 950 914 1201 1139 1097 1601 1519 1463
current (A)
Maximum input 886 851 819 1107 1063 1024 1328 1276 1229 1771 1702 1638
current (A)2
Bypass Specifications
Voltage (V) 380 400 415 380 400 415 380 400 415 380 400 415
Minimum bypass 342 360 374 342 360 374 342 360 374 342 360 374
voltage (V)
Maximum bypass 418 440 457 418 440 457 418 440 457 418 440 457
voltage (V)
Frequency (Hz) 50 or 60
Nominal bypass 763 729 703 959 911 878 1151 1093 1054 1535 1458 1405
current (A)
20 990–5850B-001
Facility Planning UPS System
Voltage (V) 380 400 415 380 400 415 380 400 415 380 400 415
Output Specifications
Voltage (V) 380 400 415 380 400 415 380 400 415 380 400 415
Nominal output 760 722 696 950 902 870 1140 1083 1043 1519 1443 1391
current (A)
Battery Specifications
NOTE: Refer to battery manufacturer’s manual for information on installation and
maintenance.
Maximum charging 60,000 at 100% load 75,000 at 100% load 90,000 at 100% load 120,000 at 100% load
power (W) 175,000 at <80% load 218,750 at <80% load 262,500 at <80% load 350,000 at <80% load
990–5850B-001 21
UPS System Facility Planning
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
A readily accessible “LSIG” type breaker is required upstream for earth fault
protection. Trip settings for earth fault protection:
• Ig: Equal to input breaker rating.
• Tg: 1 second
Failure to follow these instructions will result in death or serious injury.
Cable sizes in this manual are based on table B.52.12 and B.52.13 of IEC 60364–
5–52 with the following assertions:
• 90 °C conductors
• An ambient temperature of 30 °C
• Use of copper or aluminium conductors
• Installation method F
If the ambient temperature is greater than 30 °C, larger conductors are to be
selected in accordance with the correction factors of the IEC.
22 990–5850B-001
Facility Planning UPS System
990–5850B-001 23
UPS System Facility Planning
Part Number Parts Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
GVX500K500HS In total 1880 (4145) 1970 (77.6) 2700 (106) 900 (35.4)
GVX500K750HS – Power cabinets 2x540 (2x1190) 2X600 (2x23.6)
GVX500K1000HS – I/O cabinet 800 (1764) 1500 (59.1)
GVX750K500HS In total 2420 (5335) 1970 (77.6) 3300 (130.0) 900 (35.4)
GVX625K625HS – Power cabinets 3x540 (3x1190) 3X600 (3x23.6)
GVX750K750HS – I/O cabinet 800 (1764) 1500 (59.1)
GVX625K1000HS
GVX750K1000HS
GVX1000K625HS In total 2960 (6526) 1970 (77.6) 3900 (153.5) 900 (35.4)
GVX1000K750HS – Power cabinets 4x540 (4x1190) 4X600 (4x23.6)
GVX1000K1000HS – I/O cabinet 800 (1764) 1500 (59.1)
GVX1250K1000HS In total 3500 (7716) 1970 (77.6) 4500 (177.2) 900 (35.4)
– Power cabinets 5x540 (5x1190) 5x600 (5x23.6)
– I/O cabinet 800 (1764) 1500 (59.1)
Clearance
NOTE: Clearance dimensions are published for airflow and service access only.
Consult with the local safety codes and standards for additional requirements in
your local area.
NOTE: The UPS system can be placed up against a wall and there is no
requirement for rear or side access.
24 990–5850B-001
Facility Planning UPS System
Voltage (V) 380 400 415 380 400 415 380 400 415
Minimum input voltage (V) 340 340 353 340 340 353 340 340 353
Maximum input voltage (V)14 456 480 498 456 480 498 456 480 498
Nominal input current (A) 1601 1519 1463 2001 1899 1828 2401 2279 2194
Maximum input current (A)15 1771 1702 1638 2214 2127 2048 2657 2552 2457
Bypass Specifications
Voltage (V) 380 400 415 380 400 415 380 400 415
Minimum bypass voltage (V) 342 360 374 342 360 374 342 360 374
Maximum bypass voltage (V) 418 440 457 418 440 457 418 440 457
Frequency (Hz) 50 or 60
Nominal bypass current (A) 1535 1458 1405 1918 1822 1757 2302 2187 2108
990–5850B-001 25
UPS System Facility Planning
Output Specifications
Voltage (V) 380 400 415 380 400 415 380 400 415
Nominal output current (A) 1519 1443 1391 1899 1804 1739 2279 2165 2087
26 990–5850B-001
Facility Planning UPS System
Battery Specifications
NOTE: Refer to the battery manufacturer’s manual for information on installation
and maintenance.
Maximum charging power (W) 120,000 at 100% load 150,000 at 100% load 180,000 at 100% load
350,000 at <80% load 437,500 at <80% load 525,000 at < 80% load
Battery current at full load and nominal battery 2183 2728 3274
voltage (A)
Battery current at full load and minimum battery 2728 3410 4092
voltage (A)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
A readily accessible “LSIG” type breaker is required upstream for earth fault
protection. Trip settings for earth fault protection:
• Ig: Equal to input breaker rating.
• Tg: 1 second
Failure to follow these instructions will result in death or serious injury.
Cable sizes in this manual are based on table B.52.12 and B.52.13 of IEC 60364–
5–52 with the following assertions:
• 90 °C conductors
• An ambient temperature of 30 °C
• Use of copper or aluminium conductors
• Installation method F
If the ambient temperature is greater than 30 °C, larger conductors are to be
selected in accordance with the correction factors of the IEC.
990–5850B-001 27
UPS System Facility Planning
28 990–5850B-001
Facility Planning UPS System
Part Number Parts Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
GVX1000K1250HS In total 3036 (6693) 1970 (77.6) 4400 (173.2) 900 (35.4)
GVX1000K1500HS – Power cabinets 4x540 (4x1190) 4x600 (4x23.6)
– I/O cabinet 876 (1931) 2000 (78.7)
GVX1250K1250HS In total 3576 (7884) 1970 (77.6) 5000 (196.9) 900 (35.4)
GVX1250K1500HS – Power cabinets 5x540 (5x1190) 5x600 (5x23.6)
– I/O cabinet 876 (1931) 2000 (78.7)
GVX1500K1250HS In total 4116 (9074) 1970 (77.6) 5600 (220.5) 900 (35.4)
GVX1500K1500HS – Power cabinets 6x540 (6x1190) 6x600 (6x23.6)
– I/O cabinet 876 (1931) 2000 (78.7)
GVX1750K1500HS In total 4656 (10265) 1970 (77.6) 6200 (244.1) 900 (35.4)
– Power cabinets 7x540 (7x1190) 7x600 (7x23.6)
– I/O cabinet 876 (1931) 2000 (78.7)
Clearance
NOTE: Clearance dimensions are published for airflow and service access only.
Consult with the local safety codes and standards for additional requirements in
your local area.
NOTE: The UPS system can be placed up against a wall with no requirement for
rear or side access.
Front View
990–5850B-001 29
UPS System Facility Planning
Cable Length
Torque Specifications
Bolt size Torque
M6 5 Nm (3.69 lb-ft)
Environment
Operating Storage
Altitude derating according to ANSI C57.96– 1000 m (3300 ft): 1.000 0 – 15000 m (0 – 50000 ft)
199923 1500 m (5000 ft): 0.975
2000 m (6600 ft): 0.950
2500 m (8300 ft): 0.925
3000 m (10000 ft): 0.900
Heat Dissipation
Heat Dissipation for 500 kW UPS
22. For temperatures between 40 °C and 50 °C, the load power rating must be derated with 2.5% per °C of rated output power. Above 40 °C
the minimum input voltage is 340 V, and from 380 V to 340 V, the charge power must be linearly derated from 12% to 1%.
23. Maximum operation altitude is 3000 m (10000 ft).
30 990–5850B-001
Facility Planning UPS System
Load 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
25% 26677 26090 25504 9176 9176 9176 12998 12998 12998 28479 28479 28479
50% 45008 43851 42696 12918 12918 12918 15139 15139 15139 49074 49074 49074
75% 71975 70230 68489 16645 16645 16645 20081 20081 20081 72737 72737 72737
100% 114405 112040 109680 21192 21192 21192 26338 26338 26338 101631 101631 101631
Load 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
25% 29038 28339 27642 9551 9551 9551 15597 15597 15597 32461 32461 32461
50% 52290 50905 49523 14257 14257 14257 18167 18167 18167 59281 59281 59281
75% 89879 87778 85681 19171 19171 19171 24098 24098 24098 87347 87347 87347
100% 145637 142782 139932 25718 25718 25718 31605 31605 31605 127135 127135 127135
Load 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
25% 41089 40153 39218 15635 15635 15635 23490 23490 23490 46116 46116 46116
50% 72864 71011 69162 20721 20721 20721 27740 27740 27740 82785 82785 82785
75% 114464 111674 108890 28462 28462 28462 32130 32130 32130 116463 116463 116463
100% 178105 174332 170566 37949 37949 37949 42141 42141 42141 169513 169513 169513
Load 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
25% 54883 53705 52530 22872 22872 22872 32750 32750 32750 61210 61210 61210
50% 95722 93396 91075 30279 30279 30279 39089 39089 39089 108180 108180 108180
75% 143080 139593 136112 35578 35578 35578 40163 40163 40163 145579 145579 145579
100% 222631 217914 213207 47437 47437 47437 52676 52676 52676 211891 211891 211891
Load 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
25% 70112 68690 67271 31463 31463 31463 43391 43391 43391 77757 77757 77757
50% 120461 117658 114861 41610 41610 41610 52224 52224 52224 135478 135478 135478
75% 171697 167511 163335 42693 42693 42693 48195 48195 48195 174694 174694 174694
100% 267158 261497 255849 56924 56924 56924 63211 63211 63211 254270 254270 254270
990–5850B-001 31
UPS System Drawings
Drawings
NOTE: A comprehensive set of drawings is available on the engineering website at
engineer.apc.com.
NOTE: These drawings are for reference ONLY – subject to change without notice.
32 990–5850B-001
Drawings UPS System
990–5850B-001 33
UPS System Drawings
34 990–5850B-001
Options UPS System
Options
Hardware Options
• Standard top cable entry battery cabinets or custom front terminal battery
cabinets
• Optional remote 10–inch LCD
• Optional Modbus RS-485 card
Configuration Options
• Single or dual feed
• Default top or bottom cable entry
• N+1 redundancy
• Parallel up to three UPS units for redundancy (N+1 configuration) and two UPS
units for capacity
• ECO mode
• ECOnversion mode
• StruxureWare Data Center Expert compatible
• Generator compatible
• Internal synchronization to alternate source (single system)
• Seismic rated brackets included
• Touchscreen LCD
990–5850B-001 35
UPS System Limited Factory Warranty
Terms of Warranty
Schneider Electric warrants that the product shall be free from defects in materials
and workmanship for a period of one year from the date of product start-up when
start-up is performed by Schneider Electric-authorized service personnel and
occurs within six months of the Schneider Electric shipment date. This warranty
covers repairing or replacing any defective parts including on-site labor and travel.
In the event that the product fails to meet the foregoing warranty criteria, the
warranty covers repairing or replacing defective parts at the sole discretion of
Schneider Electric for a period of one year from the shipment date. For Schneider
Electric cooling solutions, this warranty does not cover circuit breaker resetting,
loss of refrigerant, consumables, or preventive maintenance items. Repair or
replacement of a defective product or part thereof does not extend the original
warranty period. Any parts furnished under this warranty may be new or factory-
remanufactured.
Non-transferable Warranty
This warranty is extended to the first person, firm, association or corporation
(herein referred to by “You” or “Your”) for whom the Schneider Electric product
specified herein has been purchased. This warranty is not transferable or
assignable without the prior written permission of Schneider Electric.
Assignment of Warranties
Schneider Electric will assign you any warranties which are made by
manufacturers and suppliers of components of the Schneider Electric product and
which are assignable. Any such warranties are assigned “AS IS” and Schneider
Electric makes no representation as to the effectiveness or extent of such
warranties, assumes no responsibility for any matters which may be warranted by
such manufacturers or suppliers and extends no coverage under this Warranty to
such components.
Drawings, Descriptions
Schneider Electric warrants for the warranty period and on the terms of the
warranty set forth herein that the Schneider Electric product will substantially
conform to the descriptions contained in the Schneider Electric Official Published
Specifications or any of the drawings certified and agreed to by contract with
Schneider Electric if applicable thereto (“Specifications”). It is understood that the
Specifications are not warranties of performance and not warranties of fitness for a
particular purpose.
Exclusions
Schneider Electric shall not be liable under the warranty if its testing and
examination disclose that the alleged defect in the product does not exist or was
36 990–5850B-001
Limited Factory Warranty UPS System
caused by end user or any third person misuse, negligence, improper installation
or testing. Further, Schneider Electric shall not be liable under the warranty for
unauthorized attempts to repair or modify wrong or inadequate electrical voltage or
connection, inappropriate on-site operation conditions, corrosive atmosphere,
repair, installation, start-up by non-Schneider Electric designated personnel, a
change in location or operating use, exposure to the elements, Acts of God, fire,
theft, or installation contrary to Schneider Electric recommendations or
specifications or in any event if the Schneider Electric serial number has been
altered, defaced, or removed, or any other cause beyond the range of the intended
use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF
LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED
UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. SCHNEIDER
ELECTRIC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY,
SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER
ELECTRIC EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED,
OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF,
SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER ADVICE OR
SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING
WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER
WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE
CONSTITUTE SCHNEIDER ELECTRIC SOLE LIABILITY AND PURCHASER’S
EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES.
SCHNEIDER ELECTRIC WARRANTIES RUN ONLY TO PURCHASER AND ARE
NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS,
AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT,
SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE
USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH
DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT,
NEGLIGENCE OR STRICT LIABILITY OR WHETHER SCHNEIDER ELECTRIC
HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH
DAMAGES, SPECIFICALLY, SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY
COSTS, SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT,
LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA,
COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NO SALESMAN, EMPLOYEE OR AGENT OF SCHNEIDER ELECTRIC IS
AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY.
WARRANTY TERMS MAY BE MODIFIED, IF AT ALL, ONLY IN WRITING SIGNED
BY AN SCHNEIDER ELECTRIC OFFICER AND LEGAL DEPARTMENT.
Warranty Claims
Customers with warranty claims issues may access the SCHNEIDER ELECTRIC
worldwide customer support network through the SCHNEIDER ELECTRIC web
site: http://www.schneider-electric.com. Select your country from the country
selection pull-down menu. Open the Support tab at the top of the web page to
obtain contact information for customer support in your region.
990–5850B-001 37