Project: ETAP Page: 1

Location: 16.1.1C Date: 02-22-2018

Contract: SN: TATASTEEL6

Engineer: Revision: Base


Study Case: SC
Filename: TCC SLD 120118 Config.: Normal

Electrical Transient Analyzer Program

Short-Circuit Analysis

IEC 60909 Standard

3-Phase, LG, LL, & LLG Fault Currents

Swing V-Control Load Total

Number of Buses: 2 0 19 21

XFMR2 XFMR3 Reactor Line/Cable Impedance Tie PD Total

Number of Branches: 3 0 0 15 0 1 19

Synchronous Power Synchronous Induction Lumped


Generator Grid Motor Machines Load Total

Number of Machines: 0 2 0 9 1 12

System Frequency: 50.00

Unit System: Metric

Project Filename: TCC SLD 120118

Output Filename: C:\Users\500327\Desktop\SK (1)\Untitled.SI2S


Project: ETAP Page: 2

Location: 16.1.1C Date: 02-22-2018

Contract: SN: TATASTEEL6

Engineer: Revision: Base


Study Case: SC
Filename: TCC SLD 120118 Config.: Normal

Adjustments

Apply Individual
Tolerance Adjustments /Global Percent

Transformer Impedance: Yes Individual

Reactor Impedance: Yes Individual

Overload Heater Resistance: No

Transmission Line Length: No

Cable Length: No

Apply Individual
Temperature Correction Adjustments /Global Degree C

Transmission Line Resistance: Yes Individual

Cable Resistance: Yes Individual


Project: ETAP Page: 3

Location: 16.1.1C Date: 02-22-2018

Contract: SN: TATASTEEL6

Engineer: Revision: Base


Study Case: SC
Filename: TCC SLD 120118 Config.: Normal

Bus Input Data

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

Bus1 Load 6.600 6.600 1 100.00 0.00


Bus2 SWNG 6.600 6.600 1 100.00 0.00
Bus3 Load 6.900 6.600 1 100.00 0.00
Bus4 Load 6.900 6.600 1 100.00 0.00
Bus5 Load 6.900 6.600 1 100.00 0.00
Bus7 Load 6.600 6.600 1 100.00 0.00
Bus8 Load 6.600 6.600 1 100.00 0.00
Bus9 Load 6.600 6.600 1 100.00 0.00
Bus10 Load 6.900 6.600 1 100.00 0.00
Bus11 Load 6.900 6.600 1 100.00 0.00
Bus12 Load 6.900 6.600 1 100.00 0.00
Bus13 Load 6.900 6.600 1 100.00 0.00
Bus14 Load 6.600 6.600 1 100.00 0.00
Bus19 SWNG 11.000 11.000 2 100.00 0.00
Bus21 Load 0.433 0.433 1 100.00 -30.00
Bus22 Load 6.600 6.600 1 100.00 0.00
Bus24 Load 6.600 6.600 1 100.00 0.00
Bus27 Load 6.900 6.600 1 100.00 0.00
Bus28 Load 0.433 0.433 1 100.00 -30.00
Bus29 Load 0.433 0.433 1 100.00 -30.00
Bus31 Load 6.600 6.600 1 100.00 0.00

21 Buses Total

All voltages reported by ETAP are in % of bus Nominal kV.


Base kV values of buses are calculated and used internally by ETAP.
Project: ETAP Page: 4

Location: 16.1.1C Date: 02-22-2018

Contract: SN: TATASTEEL6

Engineer: Revision: Base


Study Case: SC
Filename: TCC SLD 120118 Config.: Normal

Line/Cable Input Data

ohms or siemens per 1000 m per Conductor (Cable) or per Phase (Line)

Line/Cable Length

ID Library Size Adj. (m) % Tol. #/Phase T (°C) R1 X1 Y1 R0 X0 Y0

Cable1 6.6NALN3 120 500.0 0.0 1 75 0.3096746 0.0914 0.0001194 0.3096746 0.0914 0.0001194

Cable2 6.6NALN3 120 500.0 0.0 1 75 0.3096746 0.0914 0.0001194 0.3096746 0.0914 0.0001194

Cable3 6.6NALN3 120 500.0 0.0 1 75 0.3096746 0.0914 0.0001194 0.3096746 0.0914 0.0001194

Cable4 6.6NALN3 120 500.0 0.0 1 75 0.3096746 0.0914 0.0001194 0.3096746 0.0914 0.0001194

Cable5 6.6NALN3 120 500.0 0.0 1 75 0.3096746 0.0914 0.0001194 0.3096746 0.0914 0.0001194

Cable6 6.6NALN3 120 500.0 0.0 1 75 0.3096746 0.0914 0.0001194 0.3096746 0.0914 0.0001194

Cable7 6.6NALN3 120 500.0 0.0 1 75 0.3096746 0.0914 0.0001194 0.3096746 0.0914 0.0001194

Cable8 6.6NALN3 120 500.0 0.0 1 75 0.3096746 0.0914 0.0001194 0.3096746 0.0914 0.0001194

Cable9 6.6NALN3 120 500.0 0.0 1 75 0.3096746 0.0914 0.0001194 0.3096746 0.0914 0.0001194

Cable10 6.6NALN3 120 500.0 0.0 1 75 0.3096746 0.0914 0.0001194 0.3096746 0.0914 0.0001194

Cable11 6.6NALN3 120 500.0 0.0 1 75 0.3096746 0.0914 0.0001194 0.3096746 0.0914 0.0001194

Cable12 6.6NALN3 120 500.0 0.0 1 75 0.3096746 0.0914 0.0001194 0.3096746 0.0914 0.0001194

Cable22 6.6NALN3 120 500.0 0.0 1 75 0.3096746 0.0914 0.0001194 0.3096746 0.0914 0.0001194

Cable23 6.6NALN3 120 500.0 0.0 1 75 0.3096746 0.0914 0.0001194 0.3096746 0.0914 0.0001194

Cable26 6.6NALN3 120 500.0 0.0 1 75 0.3096746 0.0914 0.0001194 0.3096746 0.0914 0.0001194

Line / Cable resistances are listed at the specified temperatures.


Project: ETAP Page: 5

Location: 16.1.1C Date: 02-22-2018

Contract: SN: TATASTEEL6

Engineer: Revision: Base


Study Case: SC
Filename: TCC SLD 120118 Config.: Normal

2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted Phase Shift

ID MVA Prim. kV Sec. kV %Z X/R + 5% - 5% % Tol. Prim. Sec. %Z Type Angle

1.6 MVA RMGP TRAFO FDR#1 1.600 6.600 0.433 6.25 6.00 0 0 0 0 0 6.25 Dyn 30.00

HWT TRAFO1 2.500 6.600 0.433 6.25 6.00 0 0 0 0 0 6.25 Dyn 30.00

hwt trafo 2 2.500 6.600 0.433 6.25 6.00 0 0 0 0 0 6.25 Dyn 30.00

2-Winding Transformer Grounding Input Data

Grounding
Transformer Rating Conn. Primary Secondary

ID MVA Prim. kV Sec. kV Type Type kV Amp ohm Type kV Amp ohm

1.6 MVA RMGP TRAFO FDR#1 1.600 6.600 0.433 D/Y Solid

HWT TRAFO1 2.500 6.600 0.433 D/Y Solid

hwt trafo 2 2.500 6.600 0.433 D/Y Solid


Project: ETAP Page: 6

Location: 16.1.1C Date: 02-22-2018

Contract: SN: TATASTEEL6

Engineer: Revision: Base


Study Case: SC
Filename: TCC SLD 120118 Config.: Normal

Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb

ID Type From Bus To Bus R X Z Y

1.6 MVA RMGP TRAFO FDR#1 2W XFMR Bus24 Bus21 61.77 370.64 375.75

HWT TRAFO1 2W XFMR Bus7 Bus29 39.53 237.21 240.48

hwt trafo 2 2W XFMR Bus14 Bus28 39.53 237.21 240.48

Cable1 Cable Bus1 Bus3 35.55 10.49 37.06 0.0026005

Cable2 Cable Bus1 Bus4 35.55 10.49 37.06 0.0026005

Cable3 Cable Bus1 Bus5 35.55 10.49 37.06 0.0026005

Cable4 Cable Bus1 Bus22 35.55 10.49 37.06 0.0026005

Cable5 Cable Bus1 Bus7 35.55 10.49 37.06 0.0026005

Cable6 Cable Bus1 Bus8 35.55 10.49 37.06 0.0026005

Cable7 Cable Bus2 Bus9 35.55 10.49 37.06 0.0026005

Cable8 Cable Bus2 Bus10 35.55 10.49 37.06 0.0026005

Cable9 Cable Bus2 Bus11 35.55 10.49 37.06 0.0026005

Cable10 Cable Bus2 Bus12 35.55 10.49 37.06 0.0026005

Cable11 Cable Bus2 Bus13 35.55 10.49 37.06 0.0026005

Cable12 Cable Bus2 Bus14 35.55 10.49 37.06 0.0026005

Cable22 Cable Bus1 Bus24 35.55 10.49 37.06 0.0026005

Cable23 Cable Bus1 Bus27 35.55 10.49 37.06 0.0026005

Cable26 Cable Bus2 Bus31 35.55 10.49 37.06 0.0026005

B/C Tie Breakr Bus2 Bus1


Project: ETAP Page: 7

Location: 16.1.1C Date: 02-22-2018

Contract: SN: TATASTEEL6

Engineer: Revision: Base


Study Case: SC
Filename: TCC SLD 120118 Config.: Normal

Power Grid Input Data

% Impedance
Rating 100 MVA Base
Grounding
Power Grid ID Connected Bus ID MVASC kV R X" R/X" Type

U2 Bus2 457.261 6.600 1.55813 21.81375 0.07 Wye - Solid

U3 Bus19 457.261 11.000 1.55813 21.81375 0.07 Wye - Solid

Total Connected Power Grids ( = 2 ): 914.523 MVA


Project: ETAP Page: 8

Location: 16.1.1C Date: 02-22-2018

Contract: SN: TATASTEEL6

Engineer: Revision: Base


Study Case: SC
Filename: TCC SLD 120118 Config.: Normal

Induction Machine Input Data

Pos. Seq. Imp.


Induction Machine Connected Bus Rating (Motor Base) Grounding mFact.

ID Type Qty ID HP/kW kVA kV Amp PF %R % X" R/X" Conn. Type Amp MW/PP

TCC#2 Motor 1 Bus3 250.00 292.42 6.600 25.58 91.92 3.25 15.04 0.22 Wye Open 0.13
TCC#3 Motor 1 Bus4 630.00 730.09 6.600 63.87 92.30 2.51 15.18 0.17 Wye Open 0.32
TCC#4 Motor 1 Bus5 200.00 234.44 6.600 20.51 91.83 3.45 14.99 0.23 Wye Open 0.10
TCC#7 Motor 1 Bus10 710.00 821.82 6.600 71.89 92.35 2.43 15.19 0.16 Wye Open 0.36
CO-17A Motor 1 Bus11 450.00 523.23 6.600 45.77 92.16 2.76 15.14 0.18 Wye Open 0.23
SPARE Motor 1 Bus12 710.00 821.82 6.600 71.89 92.35 2.43 15.19 0.16 Wye Open 0.36
TCC#5 Motor 1 Bus13 500.00 580.81 6.600 50.81 92.20 2.68 15.15 0.18 Wye Open 0.25
TCC#1 Motor 1 Bus22 315.00 367.61 6.600 32.16 92.01 3.04 15.08 0.20 Wye Open 0.16
SPARE MOTOR FEEDER Motor 1 Bus27 500.00 580.81 6.600 50.81 92.20 2.68 15.15 0.18 Wye Open 0.25

Total Connected Induction Machines ( = 9 ): 4953.0 kVA


Project: ETAP Page: 9

Location: 16.1.1C Date: 02-22-2018

Contract: SN: TATASTEEL6

Engineer: Revision: Base


Study Case: SC
Filename: TCC SLD 120118 Config.: Normal

Lumped Load Input Data

Motor Loads
Lumped Load % Impedance
Rating % Load Loading (Machine Base) Grounding mFact.
Lumped Load ID kVA kV Amp % PF MTR STAT kW kvar R X" R/X" Conn. Type Amp MW/PP

Lump1 1300.0 0.433 1733.38 85.00 80 20 884.00 547.85 6.46 15.37 0.42 Delta 0.88

Total Connected Lumped Loads ( = 1 ): 1300.0 kVA


Project: ETAP Page: 10

Location: 16.1.1C Date: 02-22-2018

Contract: SN: TATASTEEL6

Engineer: Revision: Base


Study Case: SC
Filename: TCC SLD 120118 Config.: Normal

SHORT- CIRCUIT REPORT

Fault at bus: Bus13


Nominal kV = 6.900
Voltage c Factor = 1.10 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus13 Total 0.00 20.553 0.00 101.10 100.31 20.266 20.266 3.65E+001 3.27E+001 3.73E+001 3.45E+001

Bus2 Bus13 78.02 20.256 77.37 105.88 104.43 20.088 20.266 3.74E+001 3.27E+001 3.73E+001 3.45E+001

TCC#5 Bus13 104.55 0.380 104.55 104.55 104.55 0.228 0.000 4.61E+002 2.61E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 20.553 20.266 17.752 20.490
Peak Current (kA), Method C : 30.859 30.427 26.653 30.764
Breaking Current (kA, rms, symm) : 20.266 17.752 20.490
Steady State Current (kA, rms) : 19.815 20.266 17.752 20.490

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta-Y transformer.
Project: ETAP Page: 11

Location: 16.1.1C Date: 02-22-2018

Contract: SN: TATASTEEL6

Engineer: Revision: Base


Study Case: SC
Filename: TCC SLD 120118 Config.: Normal

Short-Circuit Summary Report

3-Phase, LG, LL, LLG Fault Currents

Bus 3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground


ID kV I"k ip Ik I"k ip Ib Ik I"k ip Ib Ik I"k ip Ib Ik

Bus13 6.900 20.553 30.859 19.815 20.266 30.427 20.266 20.266 17.752 26.653 17.752 17.752 20.490 30.764 20.490 20.490

All fault currents are in rms kA. Current ip is calculated using Method C.

* LLG fault current is the larger of the two faulted line currents.
Project: ETAP Page: 12

Location: 16.1.1C Date: 02-22-2018

Contract: SN: TATASTEEL6

Engineer: Revision: Base


Study Case: SC
Filename: TCC SLD 120118 Config.: Normal

Sequence Impedance Summary Report

Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)

ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance

Bus13 6.900 0.15880 0.14227 0.21321 0.15927 0.14346 0.21435 0.16230 0.15022 0.22115 0.00000 0.00000 0.00000