Sei sulla pagina 1di 4

OPERATING MANUAL

UNIVERSAL TEMPERATURE CONTROLLER


UTC-1131,2131 & 4131
UTC 1131

 UTC 2131


ºC

R
 PV
UTC 4131

R

TUNE
SET

UTC 1131 UTC 2131 UTC 4131


96 X 96 mm 72 X 72 mm 48 X 48 mm

Technical Specification
1) Display : 3 dig. 7 seg, 0.56”,red LED display.
2) Input : J, K, PT-100 (selectable)
3) Temperature Range : J: 0 to 600°C / K: 0 to 999°C / PT-100: -99 to 400ºC
4) Control Action : TP/ON-OFF (selectable)
5) Output : 1 relay, 1 C/O contact, 230V AC, 5A/ S.S.R,12V DC,30mA
6) Power Supply : 100 to 250V AC, 50 / 60 Hz smps

Note:
1) Press + key for 3 sec to go to Factory Setting mode.
2) Press SET key to go to next parameter.
3) Press or to enter value or to select option.
4) Every time the instrument is turned ON, following pattern will be
displayed

POWER ON

  All digit segment will be turned ON for 3 sec

 Previous or default sensor input will be display for 2 sec

 Process Value

Page - 1 www.multispanindia.com
 PROCESS VALUE
SET POINT SETTING
 SET POINT


Press SET key for 6 sec to enter
Password parmeter
BASIC CONFIGURATION  Password Message

TO ENTER BASIC 


CONFIGURATION
SETTING, ENTER “73”

 Password Message


SET


SET

 Input

 K  J/K/PT100

 OFF-SET



 Set Point Low Limit



 Set Point High Limit



 Control Action

 TP  ON-OFF

 Relay Mode


Press SET key

 

Press SET + key to Save & Exit

Page - 2 www.multispanindia.com
CONTROL PARAMETER

TO ENTER CONTROL
PARAMETER  Password Message
SETTING, ENTER “37” SET

 to enter Control Parameter setting,enter “37”


SET
IF TP SELECTED IF ON-OFF SELECTED

  ON-OFF

Proportional Band  

  If Heat is selected


If Cool is then press +SET

Selected key to Save & Exit.


Cycle Timer 
 Delay time




Manual Reset 


Press SET + key
to Save & Exit


Press SET + key


to Save & Exit

Sr. Parameter Range for J, K, PT100


1 PB 1 TO 15
2 CT 4 Sec to 30 Sec
3 MR -10 to +10°C
4 DELAY TIME 1 sec to 999 sec
5 Hysteresis 1°C to 50°C
6 Off-set correction -20°C to +20°C

Page - 3 www.multispanindia.com
Note :
1) Press SET key to go to next parameter.
2) Press or key to enter value or to
select option.

FACTORY SETTING
Process Value FACTORY SETTING
Press + key for 3 sec SR. PARAMETER VALUES
Factory Setting 1 PB 5
2 CT 8 SEC
3 MR 0°C
4 OFFSET 0°C
SET
 : press + key to apply factory set values as shown in table. HYSTERESIS
 : press + key to escape from factory setting.
5 3°C
SET
6 DELAY TIME 6 sec

1) Connection Diagram with Relay Output.:


8 L 1
SUPPLY
T/C 100-250V AC
20 19 18 17 16 15 14 13 12 11 (SMPS)
9 N 2
10 L 1
T/C SUPPLY
10 T/C 100 To 250V AC
3
NO 9 N 2
SUPPLY 11 RELAY C 4 8 3
100-250V AC NC
RELAY NC
(SMPS) NC C NO
12 5 7 RELAY C 4
L N
13 6 6 5
1 2 3 4 5 6 7 8 9 10 NO
14 7

UTC 1131 UTC 2131 UTC 4131

2) Connection Diagram with SSR Output.:


8 L 1
SUPPLY
T/C 100-250V AC
(SMPS)
20 19 18 17 16 15 14 13 12 11 9 N 2
- O/P -
S.S.R T/C 10 3 10 L 1
SUPPLY
T/C 100 To 250V AC
9 N 2
11 4
SUPPLY
100-250V AC 8 3
12 5
(SMPS)
7 4
L N 13 6 S.S.R
O/P
1 2 3 4 5 6 7 8 9 10 S.S.R 6 5
14 7

UTC 1131 UTC 2131 UTC 4131

Product improvement and upgrade is a constant procedure. So for more updated operating information and support, please