Modbus Register Mapping

Control

PS0500
PS0600
PC500/PC550
PCC 1301
PowerCommand 1.1
PowerCommand 1.2
PowerCommand 2.2
PowerCommand 2.3
PowerCommand 3.3
DMC 1000
DMC 1500
MCM 3320
AUX101/102

English
Original Instructions 8-2017 A029X159 (Issue 19)
Table of Contents
1. IMPORTANT SAFETY INSTRUCTIONS ....................................................................................... 1
1.1 Warning, Caution, and Note Styles Used in This Manual ..................................................... 1
1.2 Fuel and Fumes Are Flammable ............................................................................................ 1
1.2.1 Gaseous Fuels ............................................................................................................. 2
1.2.2 Exhaust Gases Are Deadly.......................................................................................... 2
1.3 Moving Parts Can Cause Severe Personal Injury or Death ................................................... 2
1.4 Do Not Operate in Flammable and Explosive Environments ................................................. 2
1.5 Electrical Shock Can Cause Severe Personal Injury Or Death.............................................. 3
1.5.1 Medium Voltage Equipment (601 V to 15 kV - U.S. and Canada) .............................. 3
1.6 General Safety Precautions.................................................................................................... 3
1.7 Decommissioning and Disassembly ....................................................................................... 6

2. INTRODUCTION............................................................................................................................ 7
2.1 Controllers............................................................................................................................... 7
2.2 Bitmapping .............................................................................................................................. 7

3. PCC 1301/POWERCOMMAND 1.X/PS0500 MODBUS REGISTER MAP.................................... 9

4. PS0600 MODBUS REGISTER MAP ........................................................................................... 49


4.1 General Instructions.............................................................................................................. 49
4.1.1 Modbus RTU Supported Functions............................................................................ 49
4.1.2 Modbus RTU Serial Port Configuration Options ........................................................ 50
4.2 PS0600 Modbus Register Map............................................................................................. 54

5. POWERCOMMAND 2.X/3.X MODBUS REGISTER MAP........................................................... 77


5.1 Modbus Communications ..................................................................................................... 77
5.2 Parametrics (Analog Values) ................................................................................................ 77

6. POWERCOMMAND 2.X/3.X MODBUS FAULT STATUS BITMAPS ........................................ 419

7. NFPA 110 AND EXTENDED ANNUNCIATION BITMAP .......................................................... 457

8. NFPA 110 BITMAP (PS0600) .................................................................................................... 461

9. DMC 1000 MODBUS PARAMETRIC DATA .............................................................................. 463

10. DMC 1000 MODBUS ENUMERATED DATA........................................................................... 497

11. DMC 1000 MODBUS BITMAP DATA....................................................................................... 519

12. DMC 1500 COMMUNICATION SERVER 1 ............................................................................. 523


12.1 Modbus Address: 2 (Slave) .............................................................................................. 523
12.2 Generator Set Bus Data ................................................................................................... 526
12.3 Utility Bus Data ................................................................................................................. 528
12.4 ATS 1-5 DATA .................................................................................................................. 529

A029X159 (Issue 19) i Copyright © 2017 Cummins Inc.


Table of Contents 8-2017

12.5 Word Data......................................................................................................................... 531


12.6 ATS 6-10 DATA ................................................................................................................ 532

13. DMC 1500 COMMUNICATION SERVER 2 ............................................................................. 535


13.1 Modbus Address: 1 (Slave) .............................................................................................. 535
13.2 Generator Raw Data Gen 1-5........................................................................................... 539
13.3 Word Data......................................................................................................................... 541
13.4 Generator Raw Data Gen 6-8........................................................................................... 543

14. MCM3320 MODBUS REGISTER MAP .................................................................................... 547


14.1 Modbus Communications ................................................................................................. 547
14.2 Reference Documents ...................................................................................................... 547
14.3 Serial Port Configuration................................................................................................... 547
14.4 Device Addresses ............................................................................................................. 547
14.5 Power-Up Time ................................................................................................................. 547
14.6 Response Time................................................................................................................. 547
14.7 Data Formatting ................................................................................................................ 547
14.8 Modbus Activity LED......................................................................................................... 548
14.9 Supported Functions......................................................................................................... 548
14.10 Holding Register Function............................................................................................... 548
14.11 Preset Single/Preset Multiple Registers Function........................................................... 548
14.12 Diagnostic Counters........................................................................................................ 548
14.13 Register Maps................................................................................................................. 549
14.14 Application Layer ............................................................................................................ 549
14.15 Read Hold Registers....................................................................................................... 549
14.16 Set Single Register ......................................................................................................... 549
14.17 Modbus Loopback........................................................................................................... 550
14.18 Set Multiple Registers ..................................................................................................... 550
14.19 Modbus Register Table................................................................................................... 550

15. MCM3320 MODBUS FAULT STATUS BITMAPS.................................................................... 649

16. MCM3320 MODBUS ADDRESS 42506, 42507....................................................................... 651

17. PC500/550 MODBUS TCP REGISTER MAP .......................................................................... 653

18. AUX101/102 MODBUS REGISTER MAP ................................................................................ 663

Copyright © 2017 Cummins Inc. ii A029X159 (Issue 19)


1 Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed
during installation and maintenance of the generator set and batteries.
Before operating the generator set, read the Operator's Manual and become familiar with it and the
equipment. Safe and efficient operation can be achieved only if the equipment is properly operated
and maintained. Many accidents are caused by failure to follow fundamental rules and precautions.

1.1 Warning, Caution, and Note Styles Used in This


Manual
The following safety styles and symbols found throughout this manual indicate potentially hazardous
conditions to the operator, service personnel, or equipment.

DANGER
Indicates a hazardous situation that, if not avoided, will result in death or serious injury.

WARNING
Indicates a hazardous situation that, if not avoided, could result in death or serious injury.

CAUTION
Indicates a hazardous situation that, if not avoided, could result in minor or moderate injury.

NOTICE
Indicates information considered important, but not hazard-related (e.g., messages relating to
property damage).

1.2 Fuel and Fumes Are Flammable


Fire, explosion, and personal injury or death can result from improper practices.
• DO NOT fill fuel tanks while the engine is running unless the tanks are outside the engine
compartment. Fuel contact with hot engine or exhaust is a potential fire hazard.
• DO NOT permit any flame, cigarette, pilot light, spark, arcing equipment, or other ignition source
near the generator set or fuel tank.
• Fuel lines must be adequately secured and free of leaks. Fuel connection at the engine should be
made with an approved flexible line. Do not use copper piping on flexible lines as copper will
become brittle if continuously vibrated or repeatedly bent. Do not use zinc coated fuel lines with
diesel fuel.
• Make sure all fuel supplies have a positive shutoff valve.
• Make sure the battery area has been well-ventilated prior to servicing near it. Lead-acid batteries
emit a highly explosive hydrogen gas that can be ignited by arcing, sparking, smoking, etc.

A029X159 (Issue 19) 1 Copyright © 2017 Cummins Inc.


1. Important Safety Instructions 8-2017

1.2.1 Gaseous Fuels


Natural gas is lighter than air, and will tend to gather under covered areas.

1.2.2 Exhaust Gases Are Deadly


• Provide an adequate exhaust system to properly expel discharged gases away from enclosed or
sheltered areas, and areas where individuals are likely to congregate. Visually and audibly inspect
the exhaust system daily for leaks per the maintenance schedule. Make sure that exhaust manifolds
are secured and not warped. Do not use exhaust gases to heat a compartment.
• The exhaust vent should be high enough to help clear gases, avoid accumulation of snow, and in
accordance with all local mechanical codes.
• Make sure the unit is well ventilated.
• Engine exhaust and some of its constituents are known to the state of California to cause cancer,
birth defects, and other reproductive harm.

1.3 Moving Parts Can Cause Severe Personal Injury or


Death
• Keep hands, clothing, and jewelry away from moving parts.
• Before starting work on the generator set, disconnect the battery charger from its AC source, then
disconnect the starting batteries using an insulated wrench, negative (–) cable first. In lean-burn
natural gas (LBNG) generator sets, also make sure the starter's air supply line is disconnected or
completely vented until the generator set is ready to start. This will prevent accidental starting.
• Make sure that fasteners on the generator set are secure. Tighten supports and clamps; keep
guards in position over fans, drive belts, etc.
• Do not wear loose clothing or jewelry in the vicinity of moving parts or while working on electrical
equipment. Loose clothing and jewelry can become caught in moving parts.
• If any adjustments must be made while the unit is running, use extreme caution around hot
manifolds, moving parts, etc.

1.4 Do Not Operate in Flammable and Explosive


Environments
Flammable vapor can cause an engine to over speed and become difficult to stop, resulting in possible
fire, explosion, severe personal injury, and death. Do not operate a generator set where a flammable
vapor environment can be created, unless the generator set is equipped with an automatic safety device
to block the air intake and stop the engine. The owners and operators of the generator set are solely
responsible for operating the generator set safely. Contact your authorized Cummins distributor for more
information.

Copyright © 2017 Cummins Inc. 2 A029X159 (Issue 19)


8-2017 1. Important Safety Instructions

1.5 Electrical Shock Can Cause Severe Personal Injury


Or Death
• Remove electric power before removing protective shields or touching electrical equipment. Use
rubber insulated mats placed on dry wood platforms over floors that are metal or concrete when
around electrical equipment. Do not wear damp clothing (particularly wet shoes) or allow skin
surface to be damp when handling electrical equipment. Do not wear jewelry. Jewelry can short out
electrical contacts and cause shock or burning.
• Use extreme caution when working on electrical components. High voltages can cause injury or
death. DO NOT tamper with interlocks.
• Follow all applicable state and local electrical codes. Have all electrical installations performed by a
qualified licensed electrician. Tag and lock open switches to avoid accidental closure.
• DO NOT CONNECT GENERATOR SET DIRECTLY TO ANY BUILDING ELECTRICAL SYSTEM.
Hazardous voltages can flow from the generator set into the utility line. This creates a potential for
electrocution or property damage. Connect only through an approved isolation switch or an
approved paralleling device.

1.5.1 Medium Voltage Equipment (601 V to 15 kV - U.S. and


Canada)
• Medium voltage acts differently than low voltage. Special equipment and training is required to work
on or around medium voltage equipment. Operation and maintenance must be done only by persons
trained and experienced to work on such devices. Improper use or procedures will result in severe
personal injury or death.
• Do not work on energized equipment. Unauthorized personnel must not be permitted near energized
equipment. Due to the nature of medium voltage electrical equipment, induced voltage remains even
after the equipment is disconnected from the power source. Plan the time for maintenance with
authorized personnel so that the equipment can be de-energized and safely grounded.

1.6 General Safety Precautions


WARNING
Hot Pressurized Liquid
Contact with hot liquid can cause severe burns.
Do not open the pressure cap while the engine is running. Let the engine cool down before
removing the cap. Turn the cap slowly and do not open it fully until the pressure has been
relieved.

WARNING
Moving Parts
Moving parts can cause severe personal injury.
Use extreme caution around moving parts. All guards must be properly fastened to prevent
unintended contact.

A029X159 (Issue 19) 3 Copyright © 2017 Cummins Inc.


1. Important Safety Instructions 8-2017

WARNING
Toxic Hazard
Used engine oils have been identified by some state and federal agencies to cause cancer or
reproductive toxicity.
Do not ingest, breathe the fumes, or contact used oil when checking or changing engine oil.
Wear protective gloves and face guard.

WARNING
Electrical Generating Equipment
Incorrect operation can cause severe personal injury or death.
Do not operate equipment when fatigued, or after consuming any alcohol or drug.

WARNING
Toxic Gases
Substances in exhaust gases have been identified by some state and federal agencies to cause
cancer or reproductive toxicity.
Do not breathe in or come into contact with exhaust gases.

WARNING
Combustible Liquid
Ignition of combustible liquids is a fire or explosion hazard which can cause severe burns or
death.
Do not store fuel, cleaners, oil, etc., near the generator set.

WARNING
High Noise Level
Generator sets in operation emit noise, which can cause hearing damage.
Wear appropriate ear protection at all times.

WARNING
Hot Surfaces
Contact with hot surfaces can cause severe burns.
The unit is to be installed so that the risk of hot surface contact by people is minimized. Wear
appropriate PPE when working on hot equipment and avoid contact with hot surfaces.

WARNING
Electrical Generating Equipment
Incorrect operation and maintenance can result in severe personal injury or death
Make sure that only suitably trained and experienced service personnel perform electrical and/or
mechanical service.

Copyright © 2017 Cummins Inc. 4 A029X159 (Issue 19)


8-2017 1. Important Safety Instructions

WARNING
Toxic Hazard
Ethylene glycol, used as an engine coolant, is toxic to humans and animals.
Wear appropriate PPE. Clean up coolant spills and dispose of used coolant in accordance with
local environmental regulations.

WARNING
Combustible Liquid
Ignition of combustible liquids is a fire or explosion hazard which can cause severe burns or
death.
Do not use combustible liquids like ether.

WARNING
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal injury or death.
Isolate all auxiliary supplies and use an insulated wrench to disconnect the starting battery
cables (negative [–] first).

WARNING
Fire Hazard
Materials drawn into the generator set are a fire hazard. Fire can cause severe burns or death.
Keep the generator set and the surrounding area clean and free from obstructions.

WARNING
Fire Hazard
Materials drawn into the generator set are a fire hazard. Fire can cause severe burns or death.
Make sure the generator set is mounted in a manner to prevent combustible materials from
accumulating under the unit.

WARNING
Fire Hazard
Accumulated grease and oil are a fire hazard. Fire can cause severe burns or death.
Keep the generator set and the surrounding area clean and free from obstructions. Repair oil
leaks promptly.

NOTICE
Keep multi-type ABC fire extinguishers close by. Class A fires involve ordinary combustible
materials such as wood and cloth. Class B fires involve combustible and flammable liquid fuels
and gaseous fuels. Class C fires involve live electrical equipment. (Refer to NFPA No. 10 in the
applicable region.)

NOTICE
Before performing maintenance and service procedures on enclosed generator sets, make sure
the service access doors are secured open.

A029X159 (Issue 19) 5 Copyright © 2017 Cummins Inc.


1. Important Safety Instructions 8-2017

NOTICE
Stepping on the generator set can cause parts to bend or break, leading to electrical shorts, or to
fuel, coolant, or exhaust leaks. Do not step on the generator set when entering or leaving the
generator set room.

1.7 Decommissioning and Disassembly


NOTICE
Decommissioning and disassembly of the generator set at the end of its working life must
comply with local guidelines and legislation for disposal/recycling of components and
contaminated fluids. This procedure must only be carried out by suitably trained and
experienced service personnel. For more information contact your authorized distributor.

Copyright © 2017 Cummins Inc. 6 A029X159 (Issue 19)


2 Introduction
2.1 Controllers
NOTICE
• Cummins controllers that have Modbus RS485 Communication built-in have a dedicated
Modbus holding register for "Save Trims". The number of write cycles on any flash memory
device are finite.
• Only save trims once all configuration changes are complete; saving them on a schedule
can reduce the lifetime of the physical control. Do not save trims unless a change has
occurred.

NOTICE
There is a fixed number of write cycles available in the life of the control. Once these are used
up, the control must be replaced.

This note is targeted to, but not limited to, the following Modbus registers per Cummins device. If the
device is not listed in the table, please reference the dedicated Modbus register for "Save Trims".

Device Holding Register Access Specifications Description


Address
PC 1.x 40004 Read and Write 0: No action Save configuration
PS0500 1: Save unconditional parameters or
PCC 1301 adjustments to non-
volatile memory.
PCC 1302
Perform Save Trims
PS0600 408039 Read and Write 0: IsFalse after all configurations
1: IsTrue have been updated.
Do not save trims
PC 2.x 43910 Read and Write 0: Do nothing unless a change has
PC 3.x 1: Save Trims occurred.
PCC 2300
PCC 3300
DMC 1000 /DMC 42004 Read and Write 0: Do nothing
1: Save Trims
Default: Do Nothing
AUX 101 43052 Read and Write 0: Do Nothing
1: Save Trims

2.2 Bitmapping
Bitmapped registers are based in a 0-bit system. For a 16-bit register, 0 is the low-order bit and 15 is the
high-order bit.

A029X159 (Issue 19) 7 Copyright © 2017 Cummins Inc.


2. Introduction 8-2017

This page is intentionally blank.

Copyright © 2017 Cummins Inc. 8 A029X159 (Issue 19)


3 PCC 1301/PowerCommand 1.x/PS0500
Modbus Register Map
The controller contains data that can be read by a master device communicating via Modbus RTU
protocol on a two-wire RS485 multi-drop bus. The Cummins control is a slave unit.
For more information about the Modbus protocol, refer to Modbus Application Protocol V1.1b3 and
Modbus Serial Line Implementation Guide V1.02, which are both available at www.modbus.org.

TABLE 1. RS485 PINS

PCC 1301 PS0500/PowerCommand 1.x


A (+) TB2-3 TB15-3
B (-) TB2-4 TB15-4
Common TB2-1 TB15-1

NOTICE
Earlier versions of this software may not support all of the Modbus registers in the table below. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
For the PS0500 control, Modbus functionality is ONLY available from software version 6.02 and
later.

NOTICE
If an address or bit is not listed in the table below, it has not been implemented.

NOTICE
The master device can read 1-16 contiguous registers, write 1-16 contiguous registers, or read
diagnostic counters.

A029X159 (Issue 19) 9 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

TABLE 2. PCC 1301/POWERCOMMAND 1.X/PS0500 MODBUS REGISTER MAP

Addr. Parameter Access Specifications Description Control


40004 Save Trims Read and 0: No action Save configuration PC1.x,
Write 1: Save Unconditional parameters or adjustments to PS0500,
non-volatile memory; perform PCC1301
Save Trims after all
configurations have been
updated; do not save trims
unless a change has
occurred
40009 Controller Read Only Multiplier: 1 Device type of controller PC1.x,
Type Size(Bits): 8 PS0500,
Sign: U PCC1301
Lower Limit: 0
Upper Limit: 255
40010 Operation Read Only 0: Off Current position of the PC1.x,
Mode Switch 1: Auto generator set switch panel PS0500,
Position 2: Manual Off-Run-Auto switch as seen PCC1301
by the generator set control
40011 Genset State Read Only 0: Ready This parameter reflects the PC1.x,
1: Precrank current state of the generator PS0500,
2: Ramp set. PCC1301
3: Running
40012 Active Fault Read Only Multiplier: 1 This register contains the PC1.x,
Offset: 0 fault code number of the PS0500,
Size(Bits) 16 currently active fault. See the PCC1301
service manual for a list of
Sign: U
supported fault codes.
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
40013 Active Fault Read Only 0: Normal This register contains the PC1.x,
Type 1: Warning fault type of the currently PS0500,
4: Shutdown active fault. PCC1301
40016 NFPA 110 Read Only Multiplier: 1 16 bit number to represent PC1.x,
fault register Offset: 0 the status of the NFPA110 PS0500,
Size(Bits): 16 logical; see Table 8 on page PCC1301
457
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA

Copyright © 2017 Cummins Inc. 10 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


40017 Extended Read Only Multiplier: 1 16 bit number to represent PC1.x,
Annunciation Offset: 0 the status of the NFPA110 PS0500,
fault register Size(Bits): 16 logical; see Table 8 on page PCC1301
457
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
40018 Alternator L1- Read Only Multiplier: 1 Generator set L1-N voltage PC1.x,
N Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40019 Alternator L2- Read Only Multiplier: 1 Generator set L2-N voltage PC1.x,
N Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40020 Alternator L3- Read Only Multiplier: 1 Generator set L3-N voltage PC1.x,
N Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40022 Alternator L1- Read Only Multiplier: 1 Generator set L1-L2 voltage PC1.x,
L2 Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 19) 11 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40023 Alternator L2- Read Only Multiplier: 1 Generator set L2-L2 voltage PC1.x,
L3 Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40024 Alternator L3- Read Only Multiplier: 1 Generator set L3-L1 voltage PC1.x,
L1 Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40025 Alt Voltage Read Only Multiplier: 1 Generator set line to line PC1.x,
Offset: 0 average voltage PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40026 Alternator L1 Read Only Multiplier: 0.1 Monitors the generator set L1 PC1.x,
Current Offset: 0 current value PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: amps
Lower Limit: 0
Upper Limit: 65535
Default: NA
40027 Alternator L2 Read Only Multiplier: 0.1 Monitors the generator set L2 PC1.x,
Current Offset: 0 current value PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: amps
Lower Limit: 0
Upper Limit: 65535
Default: NA

Copyright © 2017 Cummins Inc. 12 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


40028 Alternator L3 Read Only Multiplier: 0.1 Monitors the generator set L3 PC1.x,
Current Offset: 0 current value PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: amps
Lower Limit: 0
Upper Limit: 65535
Default: NA
40029 Genset Read Only Multiplier: 0.1 Generator set average PC1.x,
Average Offset: 0 current PS0500,
Current Size(Bits): 16 PCC1301
Sign: U
Units: amps
Lower Limit: 0
Upper Limit: 65535
Default: NA
40040 Alternator Read Only Multiplier: 1 Alternator output volt- PC1.x,
Output Volt- Offset: 0 amperes (Phase A) PS0500,
Amperes Size(Bits): 16 PCC1301
(Phase A)
Sign: U
Units: kVa
Lower Limit: 0
Upper Limit: 65535
Default: NA
40041 Alternator Read Only Multiplier: 1 Alternator output volt- PC1.x,
Output Volt- Offset: 0 amperes (Phase B) PS0500,
Amperes Size(Bits): 16 PCC1301
(Phase B)
Sign: U
Units: kVa
Lower Limit: 0
Upper Limit: 65535
Default: NA
40042 Alternator Read Only Multiplier: 1 Alternator output volt- PC1.x,
Output Volt- Offset: 0 amperes (Phase C) PS0500,
Amperes Size(Bits): 16 PCC1301
(Phase C)
Sign: U
Units: kVa
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 19) 13 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40043 Alternator Read Only Multiplier: 1 Alternator output volt- PC1.x,
Output Volt- Offset: 0 amperes (total) PS0500,
Amperes Size(Bits): 16 PCC1301
(Total)
Sign: U
Units: kVa
Lower Limit: 0
Upper Limit: 65535
Default: NA
40044 Average Alt Read Only Multiplier: 0.1 Average alternator line PC1.x,
Line Offset: 0 frequency PS0500,
Frequency Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 65535
Default: NA
40058 Rated Read Only Multiplier: 0.1 Monitors the generator set PC1.x,
Alternator L1 Offset: 0 standby L1 current PS0500,
Current (%) Size(Bits): 16 percentage output PCC1301
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 65535
Default: NA
40059 Rated Read Only Multiplier: 0.1 Monitors the generator set PC1.x,
Alternator L2 Offset: 0 standby L2 current PS0500,
Current (%) Size(Bits): 16 percentage output PCC1301
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 65535
Default: NA
40060 Rated Read Only Multiplier: 0.1 Monitors the generator set PC1.x,
Alternator L3 Offset: 0 standby L3 current PS0500,
Current (%) Size(Bits): 16 percentage output PCC1301
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 65535
Default: NA

Copyright © 2017 Cummins Inc. 14 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


40061 Battery Read Only Multiplier: 0.1 Value of battery voltage PC1.x,
Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
40062 Oil Pressure Read Only Multiplier: 1 Monitor point for oil pressure PC1.x,
Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: kPa
Lower Limit: 0
Upper Limit: 65535
Default: NA
40064 Coolant Read Only Multiplier: 0.1 Monitor point for coolant PC1.x,
Temperature Offset: 0 temperature PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: degc
Lower Limit: 0
Upper Limit: 65535
Default: NA
40068 Engine Read Only Multiplier: 1 Monitor point for average PC1.x,
Speed Offset: 0 engine speed PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Rpm
Lower Limit: 0
Upper Limit: 65535
Default: NA
40069 Total Runs Read Only Multiplier: 1 Parameter reflects total PC1.x,
Offset: 0 number of starts PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

A029X159 (Issue 19) 15 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40070 Engine Run Read Only Multiplier: 1 Total engine run time PC1.x,
Time (High Offset: 0 PS0500,
Byte) Size(Bits): 16 PCC1301
Sign: U
Units: Sec
Lower Limit: 0
Upper Limit: 65535
Default: NA
40071 Engine Run Read Only Multiplier: 1 Total engine run time PC1.x,
Time (Low Offset: 0 PS0500,
Byte) Size(Bits): 16 PCC1301
Sign: U
Units: Sec
Lower Limit: 0
Upper Limit: 65535
Default: NA
40210 AUX101 Read Only Multiplier: 0.01 AUX101 speed bias PCC1301
Speed Bias Offset: 0
Size(Bits): 16
Sign: S
Units: RPM
Lower Limit: -100
Upper Limit: 100
Default: NA
40211 AUX101 Read Only Multiplier: 0.01 AUX101 Voltage bias PCC1301
Voltage Bias Offset: 0
Size(Bits): 16
Sign: S
Units: Volt
Lower Limit: -100
Upper Limit: 100
Default: NA
40229 Barometric Read Only Multiplier : 0.1 Monitor point for the PC 1.x
Absolute Offset: 0 barometric absolute pressure
Pressure Size (Bits) : 16
Sign: U
Units: PSI
Lower Limit: 0
Upper Limit: 19
Default: NA

Copyright © 2017 Cummins Inc. 16 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


40242 LTA Read Only Multiplier : 1 The processed value of the PC 1.x
Temperature Offset: 0 LTA temperature sensor for
Size (Bits) : 16 the system IO module
Sign: S
Units: degF
Lower Limit: NA
Upper Limit: NA
Default: NA
40254 Fuel Pressure Read Only 0. Invalid Indicates if the fuel pressure PC 1.x
Valid 1. Valid is valid/invalid from the
AUX101 or ECM datalink
40278 Configurable Read Only 0. Inactive Measured state of hardware PC 1.x
Input #4 1. Active input
Status
40300 Genset start Read and 0: Stop Remote start via Modbus PC1.x,
stop control Write 1: Start PS0500,
via Modbus PCC1301
40301 Fault reset Read and 0: Inactive Fault reset PC1.x,
via Modbus Write 1: Active PCC1301,
(No logical) PS0500
40302 Genset E- Read and 0: E-stop Inactive Status of E-stop switch PC1.x,
stop switch Write 1: E-stop Active PCC1301,
via Modbus PS0500
(no logical)
40535 Customer Read Only 0. Inactive Output of Customer Output 1 PC 1.x
Output 1 1. Active Event command
Event
40536 Customer Read Only 0. Inactive Output of Customer Output 2 PC 1.x
Output 2 1. Active Event command
Event
40583 Dead Battery Read Only Multiplier : 1 Tracks the number of crank PC 1.x
Prevention Offset: 0 attempts in order to limit the
Counter Size (Bits) : 8 attempts when the battery is
so low that the control resets
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
40587 Exercise Read Only 0. Inactive Displays the status of the PC 1.x
Scheduler 1. Active Exercise Scheduler
Status

A029X159 (Issue 19) 17 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43000 Alternator Read and Multiplier: 1 This register represents PC1.x,
Nominal Write Offset: 0 alternator nominal voltage. PS0500,
Voltage Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 190
Upper Limit: 600
Default: 208
43001 Alternator Read and 0: 60 Hz Set to 50 Hz or 60 Hz PC1.x,
Frequency Write 1: 50 Hz PS0500,
Switch PCC1301
43002 Single/3 Read and 0: Single Phase Generator output connection PC1.x
Phase Write 1: Three Phase type
Connection
43003 Connection Read and 0: Delta Alternator connection type PC1.x,
Type Write 1: Wye PS0500,
PCC1301
43004 Glow Plug Read and 0: Disable Glow plug driver feature PC1.x,
Enable Write 1: Enable enable PS0500,
PCC1301
43005 Charging Read and 0: Disable Used to disable the controller PC1.x,
Alternator Write 1: Enable related charging alt functions PS0500,
Functions PCC1301
Disable
43006 Start Time Read and Multiplier: 1 Remote start time delay PC1.x,
Delay Write Offset: 0 setting PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Sec
Lower Limit: 0
Upper Limit: 300
Default: 0
43007 Stop Time Read and Multiplier: 1 Remote stop time delay PC1.x,
Delay Write Offset: 0 setting PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Sec
Lower Limit: 0
Upper Limit: 600
Default: 0

Copyright © 2017 Cummins Inc. 18 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43008 Cycle Crank Read and Multiplier: 1 Maximum number of start PC1.x,
Attempts Write Offset: 0 attempts for cycle crank PS0500,
Size(Bits): 16 mode PCC1301
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 7
Default: 3
43009 Cycle Crank Read and Multiplier: 1 Maximum starter engage time PC1.x,
Engage Time Write Offset: 0 for cycle crank mode PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: sec
Lower Limit: 3
Upper Limit: 30
Default: 15
43010 Cycle Crank Read and Multiplier: 1 Engine starting cycle crank PC1.x,
Reset Time Write Offset: 0 attempts setting PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: sec
Lower Limit: 0
Upper Limit: 60
Default: 30
43011 Fault bypass Read and 0: Disable Operator panel enable for PC1.x,
(battle short) Write 1: Enable Battle Short PCC1301
feature
enable

A029X159 (Issue 19) 19 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43012 Battle Short Read and 0: None, Switch Input for Battle Short PC1.x
Switch Input Write 1: Configurable Input #1, 0= None
2: Configurable Input #2, 1=Customer Input 1
3: Configurable Input #3, 2=Customer Input 2
4: Configurable Input #4, 3 =Customer Input 3
5: Operator Panel 4 =Customer Input 4
5=Operator Panel
PCC1301 Modbus mapping
for parameters having
different limits as compared
to PC1.x and PS0500; see
Table 3 on page 42

Note: For PC1.x SW versions


less than 2.73, the "Battle
Short Switch Input" range is 0
to 3. For PC1.x SW versions
2.73 and greater, the "Battle
Short Switch Input" range is 0
to 5.
43013 AVR Enable Read and 0: Disable Automatic voltage regulation PC1.x,
Write 1: Enable enable PCC1301
43014 V/Hz Knee Read and Multiplier: 0.1 Automatic voltage regulator PC1.x,
Frequency Write Offset: 0 volts per hertz roll off knee PCC1301
Size(Bits): 16 setting
Sign: S
Units: Hz
Lower Limit: 0
Upper Limit: 1000
Default: 500
43015 V/Hz Rolloff Read and Multiplier: 0.1 Automatic voltage regulator PC1.x,
Slope Write Offset: 0 volts per hertz roll off slope PCC1301
Size(Bits): 16 setting
Sign: U
Units: %v/Hz
Lower Limit: 0
Upper Limit: 50
Default: 22
43016 AVR Gain Read and Multiplier: 1 Automatic voltage regulator PC1.x,
Adjust Write Offset: 0 gain setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 5
Upper Limit: 1000
Default: 100

Copyright © 2017 Cummins Inc. 20 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43017 AVR K2 Gain Read and Multiplier: 1 Automatic voltage regulator PC1.x,
Adjust Write Offset: 0 K2 gain setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 5
Upper Limit: 1000
Default: 100
43018 AVR D Gain Read and Multiplier: 1 Automatic voltage regulator PC1.x,
Adjust Write Offset: 0 K2 gain setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 95
Upper Limit: 105
Default: 100
43019 Electronic Read and 0: Disable Electronic governor enable PC1.x,
Governor Write 1: Enable feature PCC1301
Enable
43020 Initial Crank Read and Multiplier: 0.1 Electronic governing initial PC1.x,
Fueling Write Offset: 0 duty cycle setting PCC1301
Command Size(Bits): 16
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 500
Default: 250
43021 Initial Crank Read and Multiplier: 0.1 Time spent at Initial Crank PC1.x,
Fueling Write Offset: 0 Fueling command PCC1301
Period Size(Bits): 8
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 100
Default: 20
43022 Crank Fueling Read and Multiplier: 0.1 Electronic governing start PC1.x,
Ramp Rate Write Offset: 0 ramp duty cycle setting PCC1301
Size(Bits): 16
Sign: U
Units: %/sec
Lower Limit: 50
Upper Limit: 1000
Default: 250

A029X159 (Issue 19) 21 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43023 Maximum Read and Multiplier: 0.1 Electronic governing PC1.x,
Crank Fueling Write Offset: 0 maximum duty cycle setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 500
Upper Limit: 1000
Default: 1000
43024 Governor Read and Multiplier: 1 Electronic governing gain PC1.x,
Gain Adjust Write Offset: 0 setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 5
Upper Limit: 1000
Default: 100
43025 Gov K2 Gain Read and Multiplier: 1 Electronic governor K2 gain PC1.x,
Adjust Write Offset: 0 setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 5
Upper Limit: 1000
Default: 100
43026 Gov D Gain Read and Multiplier: 1 Electronic governor damping PC1.x,
Adjust Write Offset: 0 adjustment PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 95
Upper Limit: 105
Default: 100
43027 Crank Exit Read and Multiplier: 0.1 Electronic governing crank PC1.x,
Fueling Write Offset: 0 exit fuel duty cycle setting PCC1301
Command Size(Bits): 16
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 1000
Default: 250

Copyright © 2017 Cummins Inc. 22 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43028 Dither Factor Read and Multiplier: 1 Electronic governing dither PC1.x,
Write Offset: 0 factor setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 30
Default: 25
43029 Governor Read and Multiplier: 1 Electronic governing start PC1.x,
Ramp Time Write Offset: 0 ramp time setting PCC1301
Size(Bits): 16
Sign: U
Units: sec
Lower Limit: 0
Upper Limit: 15000
Default: 25
43030 Governor Read and Multiplier: 1 Engine speed at which PC1.x,
Enable Write Offset: 0 governor is enabled PS0500,
Speed Size(Bits): 16 PCC1301
Sign: U
Units: RPM
Lower Limit: 0
Upper Limit: 1400
Default: 1100
43031 Minimum Read and Multiplier: 1 Setting for electronic PC1.x,
Governor Write Offset: 0 governor minimum duty cycle PCC1301
Duty Cycle Size(Bits): 8
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 100
Default: 20
43032 Maximum Read and Multiplier: 1 Setting for electronic PC1.x,
Governor Write Offset: 0 governor maximum duty cycle PCC1301
Duty Cycle Size(Bits): 8
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 100
Default: 95

A029X159 (Issue 19) 23 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43033 Model Read and Multiplier: 1 Byte 1 for model number PC1.x,
number Write Offset: 0 PS0500,
character #1 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43034 Model Read and Multiplier: 1 Byte 2 for model number PC1.x,
number Write Offset: 0 PS0500,
character #2 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43035 Model Read and Multiplier: 1 Byte 3 for model number PC1.x,
number Write Offset: 0 PS0500,
character #3 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43036 Model Read and Multiplier: 1 Byte 4 for model number PC1.x,
number Write Offset: 0 PS0500,
character #4 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43037 Model Read and Multiplier: 1 Byte 5 for model number PC1.x,
number Write Offset: 0 PS0500,
character #5 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

Copyright © 2017 Cummins Inc. 24 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43038 Model Read and Multiplier: 1 Byte 6 for model number PC1.x,
number Write Offset: 0 PS0500,
character #6 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43039 Model Read and Multiplier: 1 Byte 7 for model number PC1.x,
number Write Offset: 0 PS0500,
character #7 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43040 Model Read and Multiplier: 1 Byte 8 for model number PC1.x,
number Write Offset: 0 PS0500,
character #8 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43041 Model Read and Multiplier: 1 Byte 9 for model number PC1.x,
number Write Offset: 0 PS0500,
character #9 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43042 Model Read and Multiplier: 1 Byte 10 for model number PC1.x,
number Write Offset: 0 PS0500,
character #10 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

A029X159 (Issue 19) 25 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43043 Model Read and Multiplier: 1 Byte 11 for model number PC1.x,
number Write Offset: 0 PS0500,
character #11 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43044 Model Read and Multiplier: 1 Byte 12 for model number PC1.x,
number Write Offset: 0 PS0500,
character #12 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43045 Model Read and Multiplier: 1 Byte 13 for model number PC1.x,
number Write Offset: 0 PS0500,
character #13 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43046 Model Read and Multiplier: 1 Byte 14 for model number PC1.x,
number Write Offset: 0 PS0500,
character #14 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43047 Model Read and Multiplier: 1 Byte 15 for model number PC1.x,
number Write Offset: 0 PS0500,
character #15 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

Copyright © 2017 Cummins Inc. 26 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43048 Model Read and Multiplier: 1 Byte 16 for model number PC1.x,
number Write Offset: 0 PS0500,
character #16 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43049 Serial number Read and Multiplier: 1 Byte 1 for serial number PC1.x,
character #1 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43050 Serial number Read and Multiplier: 1 Byte 2 for serial number PC1.x,
character #2 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43051 Serial number Read and Multiplier: 1 Byte 3 for serial number PC1.x,
character #3 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43052 Serial number Read and Multiplier: 1 Byte 4 for serial number PC1.x,
character #4 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

A029X159 (Issue 19) 27 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43053 Serial number Read and Multiplier: 1 Byte 5 for serial number PC1.x,
character #5 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43054 Serial number Read and Multiplier: 1 Byte 6 for serial number PC1.x,
character #6 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43055 Serial number Read and Multiplier: 1 Byte 7 for serial number PC1.x,
character #7 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43056 Serial number Read and Multiplier: 1 Byte 8 for serial number PC1.x,
character #8 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43057 Serial number Read and Multiplier: 1 Byte 9 for serial number PC1.x,
character #9 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

Copyright © 2017 Cummins Inc. 28 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43058 Serial number Read and Multiplier: 1 Byte 10 for serial number PC1.x,
character #10 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43059 Serial number Read and Multiplier: 1 Byte 11 for serial number PC1.x,
character #11 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43060 Serial number Read and Multiplier: 1 Byte 12 for serial number PC1.x,
character #12 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43061 Serial number Read and Multiplier: 1 Byte 13 for serial number PC1.x,
character #13 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43062 Serial number Read and Multiplier: 1 Byte 14 for serial number PC1.x,
character #14 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

A029X159 (Issue 19) 29 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43063 Serial number Read and Multiplier: 1 Byte 15 for serial number PC1.x,
character #15 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43064 Serial number Read and Multiplier: 1 Byte 16 for serial number PC1.x,
character #16 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43065 Configurable Read and 0: None Configurable Input #1 Fault PC1.x,
Input #1 Fault Write 1: Warning Level Response PS0500,
Level 2: Shutdown PCC1301
Response
43066 Configurable Read and 0: None Configurable Input #2 Fault PC1.x,
Input #2 Fault Write 1: Warning Level Response PS0500,
Level 2: Shutdown PCC1301
Response
43067 Configurable Read and Multiplier: 1 Configurable Customer PC1.x,
Customer Write Offset: 0 Output 1; the default setting PS0500,
Output 1 Size(Bits): 16 for FC 1540 which is a PCC1301
COMMON WARNING fault
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 1540
43068 Configurable Read and Multiplier: 1 Configurable Customer PC1.x,
Customer Write Offset: 0 Output 2; the default setting PS0500,
Output 2 Size(Bits): 16 for FC 1541 which is a PCC1301
COMMON SHUTDOWN fault
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 1541

Copyright © 2017 Cummins Inc. 30 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43069 Voltage Read and Multiplier: 0.0001 Make actual voltage match PC1.x
Regulator Write Offset: 0 nominals 60 Hz when the set
Calibration Size(Bits): 16 point = 100%
60Hz PCC1301 Modbus mapping
Sign: U
for parameters have different
Units: %
limits as compared to PC1.x;
Lower Limit: 9000 see Table 3 on page 42.
Upper Limit: 11000
Default: 10000
43070 Voltage Read and Multiplier: 0.0001 Make actual voltage match PC1.x
Regulator Write Offset: 0 nominals 50 Hz when the set
Calibration Size(Bits): 16 point = 100%
50Hz PCC1301 Modbus mapping
Sign: U
for parameters have different
Units: %
limits as compared to PC1.x;
Lower Limit: 9000 see Table 3 on page 42.
Upper Limit: 11000
Default: 10000
43071 Frequency Read and Multiplier: 0.1 PC1.x,
Adjust Trim Write Offset: 0 PCC1301
Size(Bits): 16
Sign: S
Units: Hz
Lower Limit: -600
Upper Limit: 600
Default: 0
43072 Alternator L1- Read and Multiplier: 0.0001 60 Hz line 1 to neutral PC1.x,
N 60Hz Write Offset: 0 metering voltage calibration PS0500
Voltage Size(Bits): 16 PCC1301 Modbus mapping
Display for parameters have different
Sign: U
Adjust limits as compared to PC1.x
Units: %
and PS0500; see Table 3 on
Lower Limit: 9000* page 42.
Upper Limit: 11000*
Default: 10000 *Note: For the PS0500
control, SW versions lower
than 6.03, the range is 6000
to 14000. For the PS0500
control, SW versions higher
than 6.03, the range is 9000
to 11000.

A029X159 (Issue 19) 31 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43073 Alternator L2- Read and Multiplier: 0.0001 60 Hz line 2 to neutral PC1.x,
N 60Hz Write Offset: 0 metering voltage calibration PS0500
Voltage Size(Bits): 16 *Note: For the PS0500
Display control, SW versions lower
Sign: U
Adjust than 6.03, the range is 6000
Units: %
to 14000. For the PS0500
Lower Limit: 9000* control, SW versions higher
Upper Limit: 11000* than 6.03, the range is 9000
Default: 10000 to 11000.

43074 Alternator L3- Read and Multiplier: 0.0001 60 Hz line 3 to neutral PC1.x,
N 60Hz Write Offset: 0 metering voltage calibration PS0500
Voltage Size(Bits): 16 *Note: For the PS0500
Display control, SW versions lower
Sign: U
Adjust than 6.03, the range is 6000
Units: %
to 14000. For the PS0500
Lower Limit: 9000* control, SW versions higher
Upper Limit: 11000* than 6.03, the range is 9000
Default: 10000 to 11000.

43075 Alternator L1- Read and Multiplier: 0.0001 50 Hz line 1 to neutral PC1.x,
N 50Hz Write Offset: 0 metering voltage calibration PS0500
Voltage Size(Bits): 16 *Note: For the PS0500
Display control, SW versions lower
Sign: U
Adjust than 6.03, the range is 6000
Units: %
to 14000. For the PS0500
Lower Limit: 9000* control, SW versions higher
Upper Limit: 11000* than 6.03, the range is 9000
Default: 10000 to 11000.

43076 Alternator L2- Read and Multiplier: 0.0001 50 Hz line 2 to neutral PC1.x,
N 50Hz Write Offset: 0 metering voltage calibration PS0500
Voltage Size(Bits): 16 *Note: For the PS0500
Display control, SW versions lower
Sign: U
Adjust than 6.03, the range is 6000
Units: %
to 14000. For the PS0500
Lower Limit: 9000* control, SW versions higher
Upper Limit: 11000* than 6.03, the range is 9000
Default: 10000 to 11000.

43077 Alternator L3- Read and Multiplier: 0.0001 50 Hz line 3 to neutral PC1.x,
N 50Hz Write Offset: 0 metering voltage calibration PS0500
Voltage Size(Bits): 16 *Note: For the PS0500
Display control, SW versions lower
Sign: U
Adjust than 6.03, the range is 6000
Units: %
to 14000. For the PS0500
Lower Limit: 9000* control, SW versions higher
Upper Limit: 11000* than 6.03, the range is 9000
Default: 10000 to 11000.

Copyright © 2017 Cummins Inc. 32 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43078 Alternator L1 Read and Multiplier: 0.001 60 Hz line 1 metering current PC1.x,
60Hz Current Write Offset: 0 calibration PS0500,
Adjust Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000
43079 Alternator L2 Read and Multiplier: 0.001 60 Hz line 2 metering current PC1.x,
60Hz Current Write Offset: 0 calibration PS0500,
Adjust Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000
43080 Alternator L3 Read and Multiplier: 0.0001 Adjust to make the displayed PC1.x
60Hz Current Write Offset: 0 current match actual values in
Adjust Size(Bits): 16 50 Hz applications
Sign: U
Units: NA
Lower Limit: .8
Upper Limit: 1.2
Default: 1
43081 Alternator L1 Read and Multiplier: 0.001 50 Hz line 1 metering current PC1.x,
50Hz Current Write Offset: 0 calibration PS0500,
Adjust Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000
43082 Alternator L2 Read and Multiplier: 0.001 50 Hz line 2 metering current PC1.x,
50Hz Current Write Offset: 0 calibration PS0500,
Adjust Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000

A029X159 (Issue 19) 33 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43083 Alternator L3 Read and Multiplier: 0.001 50 Hz line 3 metering current PC1.x,
50Hz Current Write Offset: 0 calibration PS0500,
Adjust Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000
43084 Annunciator Read and 0: None Sets the generator set PC1.x,
#1 Switch Write 1: Warning response to an active PCC1301
Fault 2: Shutdown Annunciator #1 switch input
Response
43085 Annunciator Read and 0: None Sets the generator set PC1.x,
#2 Switch Write 1: Warning response to an active PCC1301
Fault 2: Shutdown Annunciator #2 switch input
Response
43086 Annunciator Read and 0: None Sets the generator set PC1.x,
#3 Switch Write 1: Warning response to an active PCC1301
Fault 2: Shutdown Annunciator #3 switch input
Response
43087 Annunciator Read and Multiplier: 1 Annunciator configurable PC1.x,
Output 1 Write Offset: 0 output #1 event code number PCC1301
Event Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43088 Annunciator Read and Multiplier: 1 Annunciator configurable PC1.x,
Output 2 Write Offset: 0 output #2 event code number PCC1301
Event Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43089 Annunciator Read and Multiplier: 1 Annunciator configurable PC1.x,
Output 3 Write Offset: 0 output #3 event code number PCC1301
Event Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

Copyright © 2017 Cummins Inc. 34 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43090 Annunciator Read and Multiplier: 1 Annunciator configurable PC1.x,
Output 4 Write Offset: 0 output #4 event code number PCC1301
Event Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43344 Clock Date Read Write Multiplier : 1 Use to set or read the current PC 1.x
Offset: 0 date
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 31
Default: NA
43345 Clock Hours Read Write Multiplier : 1 Use to set or read the current PC 1.x
Offset: 0 hour
Size (Bits) : 8
Sign: U
Units: hours
Lower Limit: 1
Upper Limit: 12
Default: 0
43346 Clock Read Write Multiplier : 1 Use to set or read the current PC 1.x
Minutes Offset: 0 minute
Size (Bits) : 8
Sign: U
Units: minutes
Lower Limit: 0
Upper Limit: 59
Default: 0
43347 Clock Mode Read Write 0. NORMAL_MODE Allows the user to go into Set PC 1.x
1. SET_MODE Mode for Clock setup and in
2. SAVE_CLOCK_MODE Clock Save Mode

43348 Clock Month Read Write Multiplier : 1 Use to set or read the current PC 1.x
Offset: 0 month
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: NA

A029X159 (Issue 19) 35 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43349 Clock Read Only Multiplier : 1 Use to set or read the current PC 1.x
Seconds Offset: 0 second
Size (Bits) : 8
Sign: U
Units: seconds
Lower Limit: NA
Upper Limit: NA
Default: 0
43350 Clock Year Read Write Multiplier : 1 Use to set or read the current PC 1.x
Offset: 0 year
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 99
Default: NA
43351 Daylight Read Write Multiplier : 1 Use to set the hour of the day PC 1.x
Savings End Offset: 0 when Daylight Savings Time
Hour Size (Bits) : 8 ends
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 2
43352 Daylight Read Write Multiplier : 1 Use to set the month when PC 1.x
Savings End Offset: 0 Daylight Savings Time ends
Month Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: 10
43353 Daylight Read Write 0. Default Use to set the end week PC 1.x
Savings End 1.FIRST_OCCURRENCE occurrence in a Daylight
Week Occ 2. SECOND_OCCURRENCE Savings Time end month
Month
3. THIRD_OCCURRENCE
4. FOURTH_OCCURRENCE
5. FIFTH_OCCURRENCE

Copyright © 2017 Cummins Inc. 36 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43354 Daylight Read Write 0. Sunday Use to set the day of the PC 1.x
Savings Start 1. Monday week when Daylight Savings
Day 2. Tuesday Time starts
3. Wednesday
4. Thursday
5. Friday
6. Saturday
43355 Daylight Read Write Multiplier : 1 Use to set the hour of the day PC 1.x
Savings Start Offset: 0 when Daylight Savings Time
Hour Size (Bits) : 8 starts
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 2
43356 Daylight Read Write Multiplier : 1 Use to set the month when PC 1.x
Savings Start Offset: 0 Daylight Savings Time starts
Month Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: 4
43357 Daylight Read Write 0. Default Use to set the week PC 1.x
Savings Start 1.FIRST_OCCURRENCE occurrence in a Daylight
Week Occ 2. SECOND_OCCURRENCE Savings Time start month
Month
3. THIRD_OCCURRENCE
4. FOURTH_OCCURRENCE
5. FIFTH_OCCURRENCE
43358 Daylight Read Write Multiplier : 1 Use to set the amount of PC 1.x
Savings Time Offset: 0 Daylight Savings Time
Adjustment Size (Bits) : 8 adjustment applied
Sign: U
Units: minutes
Lower Limit: 0
Upper Limit: 120
Default: 60
43359 Daylight Read Write 0. Disabled Use to enable the Daylight PC 1.x
Savings Time 1. Enabled Savings Time feature
Enable
43376 Scheduler Read Write 0. PCCNet Devices User to set Duration in PC 1.x
Prog Duration 1. Group for PCCNet device Minutes for Exercise
(Mins) interface parameters Scheduler

A029X159 (Issue 19) 37 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43377 Scheduler Read Write 0. Disabled Trim - user to edit for running PC 1.x
Prog x 1. Enabled the Scheduler Exercise
Enable Program
43378 Scheduler Read Write 0. Weekly User to select the Exercise PC 1.x
Prog Repeat 1. Bi-Monthly Scheduler Interval
Interval 2. Monthly
3. Quarterly
4. Semi-Annual
43380 Scheduler Read Write 0. Sunday User can set the Start Day of PC 1.x
Prog Start 1. Monday the week, month for Exercise
Day 2. Tuesday Scheduler
3. Wednesday
4. Thursday
5. Friday
6. Saturday
43381 Scheduler Read Write Multiplier : 1 User to set Start Hour for PC 1.x
Prog Start Offset: 0 Exercise Scheduler
Hour Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: 2
43382 Scheduler Read Write Multiplier : 1 User to set Start Minute for PC 1.x
Prog Start Offset: 0 Exercise Scheduler
Minute Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 1
43383 Daylight Read Write 0. Sunday Use to set the day of the PC 1.x
Savings End 1. Monday week when Daylight Savings
Day 2. Tuesday Time ends
3. Wednesday
4. Thursday
5. Friday
6. Saturday

Copyright © 2017 Cummins Inc. 38 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43719 AUX101 Read Only Multiplier: 1 AUX101 input as Alternator PCC1301
Alternator Offset: 0 Temp
Temp Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43722 AUX101 Read Only Multiplier: 1 AUX101 input as Ambient PCC1301
Ambient Offset: 0 Temp
Temp Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43723 AUX101 input Read Only Multiplier: 1 AUX101 input 1 voltage PCC1301
1 Voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43724 AUX101 input Read Only Multiplier: 1 AUX101 input 2 voltage PCC1301
2 Voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43725 AUX101 input Read Only Multiplier: 1 AUX101 input 3 voltage PCC1301
3 Voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

A029X159 (Issue 19) 39 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43726 AUX101 input Read Only Multiplier: 1 AUX101 input 4 voltage PCC1301
4 Voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43727 AUX101 input Read Only Multiplier: 1 AUX101 input 5 voltage PCC1301
5 Voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43728 AUX101 input Read Only Multiplier: 1 AUX101 input 6 voltage PCC1301
6 Voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43729 AUX101 input Read Only Multiplier: 1 AUX101 input 67voltage PCC1301
67 Voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43730 AUX101 input Read Only Multiplier: 1 AUX101 input 8 voltage PCC1301
8 Voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

Copyright © 2017 Cummins Inc. 40 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43741 AUX101 Read Only Multiplier: 1 AUX101 input as Exhaust PCC1301
Exhaust Offset: 0 Temp
Temp Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43745 AUX101 Fuel Read Only Multiplier: 1 AUX101 input as Fuel Level PCC1301
Level Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43750 AUX101 Read Only Multiplier: 1 AUX101 input as Intake PCC1301
Intake Offset: 0 Manifold Temp
Manifold Size(Bits): 16
Temp
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43757 AUX101 Oil Read Only Multiplier: 1 AUX101 input as Oil Temp PCC1301
Temp Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43793 Configurable Read Only 0. Inactive Measured state of hardware PC 1.x
Input #1 1. Active input
Status
43794 Configurable Read Only 0. Inactive Measured state of hardware PC 1.x
Input #2 1. Active input
Status
43795 Configurable Read Only 0. Inactive Measured state of hardware PC 1.x
Input #3 1. Active input
Status

A029X159 (Issue 19) 41 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43822 Re-Transfer Read Write Multiplier : 1 This is the delay after the PC 1.x
Delay Offset: 0 utility has returned and before
Size (Bits) : 8 the transfer switch is moved
back to the utility side
Sign: U
position.
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 1
43825 Transfer Read Write Multiplier : 1 This is the delay after the PC 1.x
Delay Offset: 0 generator set is started
Size (Bits) : 16 before the transfer switch is
moved to the generator set
Sign: U
side position.
Units: seconds
Lower Limit: 60
Upper Limit: 600
Default: 300
43905 Network Read and 0: Normal Used to command a fixed 0.5 PC1.x
Speed Adjust Write 1: Active Hz increase in the speed
Command setpoint.

TABLE 3. PCC1301 MODBUS MAPPING FOR PARAMETERS HAVING DIFFERENT LIMITS AS COMPARED TO
PC1.X AND PS05000

Addr. Parameter Access Specifications Description Control


43012 Battle Short Read and 0: None, Switch input for Battle Short PCC1301
Switch Input Write 1: Configurable Input #1, ONLY
2: Configurable Input #2,
3: Configurable Input #3
43069 Voltage Read and Multiplier: 0.0001 Make actual voltage match PCC1301
Regulator Write Offset: 0 nominals 60 Hz when the set ONLY
Calibration Size(Bits): 16 point = 100%
60Hz
Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43070 Voltage Read and Multiplier: 0.0001 Make actual voltage match PCC1301
Regulator Write Offset: 0 nominals 50 Hz when the set ONLY
Calibration Size(Bits): 16 point = 100%
50Hz
Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000

Copyright © 2017 Cummins Inc. 42 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43072 Alternator L1- Read and Multiplier: 0.0001 60 Hz line 1 to neutral PCC1301
N 60Hz Write Offset: 0 metering voltage calibration ONLY
Voltage Size(Bits): 16
Display
Sign: U
Adjust
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43073 Alternator L2- Read and Multiplier: 0.0001 60 Hz line 2 to neutral PCC1301
N 60Hz Write Offset: 0 metering voltage calibration ONLY
Voltage Size(Bits): 16
Display
Sign: U
Adjust
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43074 Alternator L3- Read and Multiplier: 0.0001 60 Hz line 3 to neutral PCC1301
N 60Hz Write Offset: 0 metering voltage calibration ONLY
Voltage Size(Bits): 16
Display
Sign: U
Adjust
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43075 Alternator L1- Read and Multiplier: 0.0001 50 Hz line 1 to neutral PCC1301
N 50Hz Write Offset: 0 metering voltage calibration ONLY
Voltage Size(Bits): 16
Display
Sign: U
Adjust
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43076 Alternator L2- Read and Multiplier: 0.0001 50 Hz line 2 to neutral PCC1301
N 50Hz Write Offset: 0 metering voltage calibration ONLY
Voltage Size(Bits): 16
Display
Sign: U
Adjust
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000

A029X159 (Issue 19) 43 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43077 Alternator L3- Read and Multiplier: 0.0001 50 Hz line 3 to neutral PCC1301
N 50Hz Write Offset: 0 metering voltage calibration ONLY
Voltage Size(Bits): 16
Display
Sign: U
Adjust
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
47031 Auto Mains Read Write 0. At Utility Trim to enable/disable ATS PC 1.x
Failure 1. At Genset functionality
Enable 2. Unknown Position
3. Not Available
47032 Transition to Read Write Multiplier : 1 This is the delay after the PC 1.x
Genset Delay Offset: 0 transfer switch is commanded
Size (Bits) : 8 to move to generator side
awaiting for the feedback.
Sign: U
Units: seconds
Lower Limit: 1
Upper Limit: 10
Default: 3
47033 Re-Transition Read Write Multiplier : 1 This is the delay after the PC 1.x
to Utility Offset: 0 transfer switch is commanded
Delay Size (Bits) : 8 to move to utility side awaiting
for the feedback.
Sign: U
Units: seconds
Lower Limit: 1
Upper Limit: 10
Default: 3
47034 Utility Fail To Read Write Multiplier : 1 This is the delay after the PC 1.x
Close Delay Offset: 0 transfer switch is moved to
Size (Bits) : 8 utility side, awaiting for the fault
to become active or inactive.
Sign: U
Units: seconds
Lower Limit: 1
Upper Limit: 10
Default: 3
47035 Genset Fail Read Write Multiplier : 1 This is the delay after the PC 1.x
To Close Offset: 0 transfer switch is moved to
Delay Size (Bits) : 8 generator set side, awaiting for
the fault to become active or
Sign: U
inactive.
Units: seconds
Lower Limit: 1
Upper Limit: 10
Default: 5

Copyright © 2017 Cummins Inc. 44 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


47036 Transfer Read Write Multiplier : 1 This is the delay after the PC 1.x
Switch Signal Offset: 0 transfer switch is moved to any
Unknown Size (Bits) : 8 of the sides, awaiting for the
Warning fault to become active or
Sign: U
Delay inactive.
Units: seconds
Lower Limit: 5
Upper Limit: 10
Default: 5
47037 Transfer Read Only 0. At Utility This is the status of the PC 1.x
Switch 1. At Genset transfer switch depending upon
Feedback 2. Unknown Position the feedback received.
Status
3. Not Available
47038 Transfer Read Only 0. Not Available This is the status of the PC 1.x
Retransfer 1. OFF transfer and retransfer
Status 2. Transfer Start process.
3. Retransfer Start
4. Transfer Progress
5. Retransfer Progress
6. Transfer Complete
7. Retransfer Complete
8. Transfer Failed
9. Retransfer Failed
47039 Transfer Read Only 0. At Utility This is the status of the PC 1.x
Switch 1. At Genset transfer switch depending upon
2. Unknown Position the fault.
3. Not Available
47040 Clock Cycle Read Write 0. AM Used to set AM_PM Cycle or PC 1.x
1. PM read the same

47041 Scheduler Read Write 0. AM User can set the AM/PM period PC 1.x
Prog Start 1. PM for the Scheduler
Period
47042 Transfer Read Write 0. Disable Trim to enable transfer switch PC 1.x
Switch 1. Enable feedback logic
Feedback
Enable
47043 Fuel System Read Write 0. Diesel Type of fuel and ignition PC 1.x
1. Gas system used by the generator
set
47044 Gas Fuel Read Write 0. Natural Gas Trim to set the type of gaseous PC 1.x
Type 1. Propane fuel
2. Dual
47045 Low Fuel Read Only 0.Inactive Displays inactive/active status PC 1.x
Pressure 1.Active of the switch
Switch

A029X159 (Issue 19) 45 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


47046 Low Fuel Read Write 0. Active Closed State selection of the low fuel PC 1.x
Pressure 1. Active Open pressure switch
Switch Active
State
Selection
47047 LTA Read Only Multiplier : 1 The processed value of the PC 1.x
Temperature Offset: 0 LTA Temperature sensor for
Size (Bits) : 16 the System IO Module
Sign: S
Units: DegF
Lower Limit: NA
Upper Limit: NA
Default: NA
47048 Intake Read Write 0. Disabled Trim to enable the detection of PC 1.x
Manifold Over 1. Enabled Intake Manifold Backfire
Pressure condition
(IMOP)
Enable
47049 Intake Read Write 0. SPN 105 Source for Intake Manifold PC 1.x
Manifold 1. SPN 52 Temperature; SPN 105 Default
Temperature Source and SPN 52 when the
Source IMOP is enabled
47050 Intake Read Write Multiplier : 0.1 Threshold to decide the Intake PC 1.x
Manifold Offset: 0 Manifold Backfire condition; the
Temp Rate of Size (Bits) : 8 value entered is for degF/secs;
Change degF/2secs is obtained by a
Sign: U
Threshold scalar of 2 in the PCC software
Units: DegF/sec
Lower Limit: 2
Upper Limit: 10
Default: 5
47051 Annunciator Read Only 0. Driver Off State of output as seen by the PC 1.x
Output 1 1.Driver On Annunciator
Status
47052 Annunciator Read Only 0. Driver Off State of output as seen by the PC 1.x
Output 1 1.Driver On Annunciator
Status
47053 Annunciator Read Only 0. Driver Off State of output as seen by the PC 1.x
Output 3 1.Driver On Annunciator
Status
47054 Annunciator Read Only 0. Driver Off State of output as seen by the PC 1.x
Output 4 1.Driver On Annunciator
Status

Copyright © 2017 Cummins Inc. 46 A029X159 (Issue 19)


8-2017 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


47055 KTA Fuel Read Only Multiplier : 0.1 The D.F.P for the KTA engine's PC 1.x
Differential Offset: 0 high side sensor
Pressure Size (Bits) : 16
High Side
Sign: S
Units: PSI
Lower Limit: NA
Upper Limit: NA
Default: NA
47056 KTA Fuel Read Only Multiplier : 0.1 The D.F.P for the KTA engine's PC 1.x
Differential Offset: 0 low side sensor
Pressure Low Size (Bits) : 16
Side
Sign: S
Units: PSI
Lower Limit: NA
Upper Limit: NA
Default: NA
47057 Air Shutoff Read Only Multiplier : 0.01 The Air Shutoff Valve Voltage PC 1.x
Valve Offset: 0 configured for SID sender input
Voltage Size (Bits) : 16 7 or 8 (enabled only for oil and
gas features)
Sign: S
Units: Vdc
Lower Limit: NA
Upper Limit: NA
Default: NA
47058 Percent Dirty Read Only Multiplier : 0.1 The calculated level at which PC 1.x
Fuel Filter Offset: 0 the fuel filter is clogged
Size (Bits) : 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
47059 QSK Read Only Multiplier : 0.1 The fuel pressure measure on PC 1.x
Differential Offset: 0 the QSK engine's low side of
Pressure Low Size (Bits) : 16 the fuel filter
Side
Sign: S
Units: PSI
Lower Limit: NA
Upper Limit: NA
Default: NA

A029X159 (Issue 19) 47 Copyright © 2017 Cummins Inc.


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


47060 Main Relay Read Only Multiplier : 1 System IO Main Relay Status PC 1.x
Status Offset: 0
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
47061 Expansion Read Only Multiplier : 1 System IO Expansion Relay PC 1.x
Relay Status Offset: 0 Status
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA

Copyright © 2017 Cummins Inc. 48 A029X159 (Issue 19)


4 PS0600 Modbus Register Map
4.1 General Instructions
4.1.1 Modbus RTU Supported Functions
The control supports the Modbus function codes described below. The control shall respond to any
function code other than those listed by sending an exception response of Illegal Function (01).
Read Holding Registers (Function Code 03)
The control provides the ability to read 1 to 125 consecutive holding registers.
The control shall respond to any read request to address not defined in the control by returning 0xFFFF
data for that address.
The control will return an Illegal Address exception code 02 if any of the following conditions occur:
• The first register in the holding register read request is not defined on the control.
• The first register in the holding register read request does not allow for the full representation of a
numeric value. This would occur if the first register in the read request is not mapped to the most
significant 2 bytes of a binary value parameter.
• The last register in the holding register read request does not allow for the full representation of a
numeric value. This would occur if the last register in the read request is not mapped to the least
significant 2 bytes of a binary value parameter.
Read requests for string type parameters where not every register associated with the string is in the
request shall return only the requested portion of the string.
Read Input Registers (Function Code 04)
The control provides the ability to read 1 to 125 consecutive input registers.
The control shall respond to any read request to address not defined in the control by returning 0xFFFF
data for that address.
The control will return an Illegal Address exception code 02 if any of the following conditions occur:
• The first register in the input register read request is not defined on the control.
• The first register in the input register read request does not allow for the full representation of a
numeric value. This would occur if the first register in the read request is not mapped to the most
significant 2 bytes of a parameter.
• The last register in the input register read request does not allow for the full representation of a
numeric value. This would occur if the last register in the read request is not mapped to the least
significant 2 bytes of a parameter.
The Input Registers support by each port on the control are listed in the Read Input Registers Table
below.
Write Single Holding Register (Function Code 06)
The control will return an Illegal Address exception code 02 if any of the following conditions occur:
• The register in the holding register write request is not defined on the control.
• The register in the holding register write request does not allow for the full writing of a numeric value.
This would occur if the register is part of a numeric parameter that requires more than one address
to represent.

A029X159 (Issue 19) 49 Copyright © 2017 Cummins Inc.


4. PS0600 Modbus Register Map 8-2017

• If writing to a string values, the register in the holding register write request is not the first register of
that string.
Write requests for string type parameters where not every register associated with the string is in the
request shall write only the requested portion of the string, null terminating the remainder of the string.
Write requests to this control may return an Illegal Data Value exception code 03. This means that the
requested write failed to occur.
Write Multiple Holding Registers (Function Code 16)
The control provides the ability to write to 1 to 123 consecutive holding registers.
The control will return an Illegal Address exception code 02 if any of the following conditions occur:
• The first register in the holding register write request is not defined on the control.
• The first register in the holding register write request does not allow for the full writing of a numeric
value. This would occur if the first register in the write request is not mapped to the most significant
2 bytes of a parameter.
• The last register in the holding register write request does not allow for the full writing of a numeric
value. This would occur if the last register in the write request is not mapped to the least significant 2
bytes of a parameter.
• If string values are in the write request, the first register for any string is not within the requested
register range.
Write requests for string type parameters where not every register associated with the string is in the
request shall write only the requested portion of the string, null terminating the remainder of the string.
Write requests to this control may return an Illegal Data Value exception code 03. This means that some
or all of the requested writes failed to occur. It is the responsibility of the requestor to read the data again
to determine which parameters were not written to their requested new values and to respond as
necessary.

4.1.2 Modbus RTU Serial Port Configuration Options


The following configuration options shall be available for each port the control that supports the Modbus
RTU protocol. See the controller Modbus register map for individual register assignments for these
parameters on any given port.

Copyright © 2017 Cummins Inc. 50 A029X159 (Issue 19)


8-2017 4. PS0600 Modbus Register Map

TABLE 4. CONFIGURATION OPTIONS

Parameter Name Description Specification


Modbus Node Address Sets this ports node address. Multiplier: 1
Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 247
Modbus Baud Rate Sets this ports baud rate. 0: 2400
1: 4800
2: 9600
3: 19200
4: 28800
5: 38400
6: 57600
7: 115200
Modbus Parity and Stop Bit Selection Sets this ports parity and stop bit 0: No Parity (1 Stop)
communications settings. 1: No Parity (2 Stop)
2: Even Parity (1 Stop)
3: Odd Parity (1 Stop)
Modbus Failure Time Delay Sets the time delay for the detection Multiplier: 1
of the lack of Modbus packets on the Offset: 0
communications bus. Size (bits): 8
Sign: U
Unit: seconds
Lower Limit: 1
Upper Limit: 60

NOTICE
Changes to the Modbus Baud Rate and the Modbus Parity and Stop Bit Selection parameters will
be immediately reflected on the serial port being configured. Any Modbus commands in progress
on that port in the old communications settings will fail until the Modbus master also updates its
communications settings to match those of the slave.

Modbus RTU Extended Status information


The control represents abnormal states in the data by using the five most positive values of the data to
convey that these abnormal states exist. The states will only be applicable to numeric parameters with the
following data types:
• UINT8, INT8, UINT16, INT16, UINT32, INT32, UINT64, INT64 (signed and unsigned 8-bit through
64-bit parameters)
Note that enumerated parameters and parameters with a floating point data type will not follow these
abnormal state representation methods.
The following abnormal states are supported:

A029X159 (Issue 19) 51 Copyright © 2017 Cummins Inc.


4. PS0600 Modbus Register Map 8-2017

Supported Abnormal States

Value Examples
Examples of
Abnormal State Value Description Unsigned 2-Byte Signed 2-Byte Failures
Integer Value Integer Value
This data shall An on controller
Hardware/ represented as 4 less hardware/component
than the highest 65531 32763 failure that provides
Component Failure positive value for that data like voltage,
parameter. current and power
Data that comes from
This data shall be
a network that has
represented as 3 less
failed such as sensor
Network Failed Data than the highest 65532 32764
data coming from I/O
positive value for that
modules on a PCCnet
parameter.
or CAN network
Data that has been
determined to be out
This data shall be of range LOW or out
represented as 2 less of range (when there
Out of Range Low than the highest 65533 32765 is no distinction
positive value for that between out of range
parameter. high and out of range
low) due to an open
sensor
Data that has been
determined to be out
This data shall be of range HIGH or out
represented as 1 less of range (when there
Out of Range
than the highest 65534 32766 is no distinction
High/Out of Range
positive value for that between out of range
parameter. high and out of range
low) due to an open
sensor
Parameters which are
not available due to
This data shall be
the sensor not being
Unsupported (Not represented as the
65535 32767 installed or not
Available) Data highest positive value
enabled in the
for that parameter.
controller’s
configuration

Working with 8-Bit Data Types


When reading a register that contains information in an 8 bit data type, the data will be put the least
significant byte of the register. If the data type is unsigned, the upper byte will be populated with zeros. If
the data type is signed, the upper byte will be sign extended with the sign bit value of the data byte.
When writing a register that contains information that is expected to be in an 8 bit data type, the control
will expect the data to be in the least significant byte of the register and ignore the upper byte.

Copyright © 2017 Cummins Inc. 52 A029X159 (Issue 19)


8-2017 4. PS0600 Modbus Register Map

Representation of Multi-Register Parameters


• For numeric parameters requiring more than one Register to represent the data, the Register
Address listed in the Controllers Modbus Register Map represents the most significant 2 bytes of the
data. The additional bytes of the data will always be provided in Register Address + 1, Register
Address + 2, and Register Address +3 as appropriate.
• For string parameters, the first two characters in the string will be mapped to the Register Address
listed in the Controllers Modbus Register Map. Additional characters will be provided in the following
registers. For example, for the string "String1" at address 400031, the characters will be mapped the
following registers:
400031: "St" 400032: "ri" 400033: "ng" 400034: "1_"
Modbus RTU Slave Protocol Support for Read Input Registers
Each port instance of Modbus RTU Slave Protocol shall support interface to the following read input
registers through function code 04. These are the only input registers supported by this control.
The following table applies for each instance of the Modbus RTU protocol on any control and will return
the data from the port being read only.

TABLE 5. READ INPUT REGISTERS TABLE

Register Data Size Scaling


Name Description
Address Type (Registers) Factor
This parameter contains the
quantity of messages that
this port has detected on
30001 Bus Message Count the communications system uint32 2 1
since its last restart, clear
counters operation, or
power-up.
This parameter stores
quantity of CRC errors
encountered by this port
30003 Bus CRC Error Count uint32 2 1
since its last restart, clear
counters operation, or
power-up.
This parameter contains the
quantity of exception
responses returned by this
30005 Bus Exception Error Count uint32 2 1
port since its last restart,
clear counters operation, or
power-up.
This parameter contains the
quantity of messages
addressed to this port for
30007 Server No Response Count which it has returned no uint32 2 1
response since its last
restart, clear counters
operation, or power-up,

A029X159 (Issue 19) 53 Copyright © 2017 Cummins Inc.


4. PS0600 Modbus Register Map 8-2017

Register Data Size Scaling


Name Description
Address Type (Registers) Factor
The parameter contains the
quantity of messages
addressed to this port that it
30009 Server Message Count uint32 2 1
has processed since its last
restart, clear counters
operation, or power-up.
This parameter holds the
Modbus Time Stamp at year of the time stamp
30011 uint8 1 1
Counter Reset - Year record when counters were
cleared last time.
This parameter holds the
Modbus Time Stamp at month of the time stamp
30012 uint8 1 1
Counter Reset - Month record when counters were
cleared last time.
This parameter holds the
day of the month of the time
Modbus Time Stamp at
30013 stamp record when uint8 1 1
Counter Reset - Date
counters were cleared last
time.
This parameter holds the
Modbus Time Stamp at hour of the time stamp
30014 uint8 1 1
Counter Reset – Hour record when counters were
cleared last time.
This parameter holds the
Modbus Time Stamp at minute of the time stamp
30015 uint8 1 1
Counter Reset - Minute record when counters were
cleared last time.
This parameter holds the
Modbus Time Stamp at seconds of the time stamp
30016 uint8 1 1
Counter Reset - Seconds record when counters were
cleared last time.
This parameter maintains
Modbus Time Since Last the time in seconds since
30017 uint32 2 1
Counter Reset the last reset of Modbus
diagnostic counters.

4.2 PS0600 Modbus Register Map


The controller contains data that can be read by a master device communicating via Modbus RTU
protocol on a two-wire RS485 multi-drop bus. The Cummins control is a slave unit.
For more information about the Modbus protocol, refer to Modbus Application Protocol V1.1b3 and
Modbus Serial Line Implementation Guide V1.02, which are both available at www.modbus.org.
See also the NFPA 110 Bitmap (PS0600) section.
PS0600 RS485 Pins
• A (+): TB15-3

Copyright © 2017 Cummins Inc. 54 A029X159 (Issue 19)


8-2017 4. PS0600 Modbus Register Map

• B (-): TB15-4
• Common: TB15-1

TABLE 6. ACCESS LEVELS

Level Description
Read Only This defines the specific parameter as a read-only type.
Guest This defines the specific parameter as read or write type.
Technician An authorized service person must set the Modbus communication port access level parameter to
"Technician" through the service tool to enable writing.

NOTICE
If an address or bit is not listed in the table below, it has not been implemented.

NOTICE
The master device can read 1-16 contiguous registers, write 1-16 contiguous registers, or read
diagnostic counters.

NOTICE
To connect with the Modbus tool, set the TB15 Protocol selection parameter to “Modbus” via a
service tool or LCD, which will immediately disconnect the PC tool. To reconnect the PC tool, set
the TB15 protocol selection to “Mon through Display configuration”, or enter "0" in the specific
TB15 protocol selection Modbus resistor address.

NOTICE
Earlier versions of this software may not support all of the Modbus registers in the following
table. If a particular register is not available in your installation, it is possible that the Modbus
connection is working but the controller software does not support that particular register.

TABLE 7. PS0600 MODBUS REGISTER MAP

Addr Parameter Access Specifications Description Control


400009 Application Read Only Multiplier: 1 The common device type PS0600
Device Type Size (Bits): 16 identifier parameter for all
Data Type: uint16 PGBASE applications
Unit: NA
Lower Limit: 0
Upper Limit: 65535
400010 Control Read Only 0: Off Current position of the PS0600
Switch 1: Auto generator set switch panel
Position 2: Manual Off-Run-Auto switch as seen
by the generator set control

A029X159 (Issue 19) 55 Copyright © 2017 Cummins Inc.


4. PS0600 Modbus Register Map 8-2017

Addr Parameter Access Specifications Description Control


400011 Genset State Read Only 0: Off Provides the state in which PS0600
1: Stop the generator set is currently
2: Preheat present
3: Precrank
4: Crank
5: Starter Disconnect
6: PreRamp
7: Ramp
8: Running
9: Fault Shutdown
10: Prerun Setup
11: Runtime Setup
12: Factory Test
13: Waiting For Powerdown
400012 Current Fault Read Only Multiplier: 1 Fault number of active fault; PS0600
Size (Bits): 16 clears when all faults are
Data Type: uint16 Inactive
Unit: NA
Lower Limit: 0
Upper Limit: 65535
400013 Current Fault Read Only 0: None Displays fault severity of PS0600
Severity 1: Warning recently occurred fault
2: Shutdown
400016 NFPA 110 Read Only Multiplier: 1 32-bit number to represent PS0600
Fault Register Size (Bits): 32 the status of the NFPA 110
Data Type: uint32 fault register; refer to the
NFPA 110 Bitmap (PS0600)
Unit: NA
section
Lower Limit: 0
Upper Limit: 4294967295
400018 Genset L1-N Read Only Multiplier: 1 RMS Voltage between Line 1 PS0600
RMS Voltage Size (Bits): 16 and Neutral
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400019 Genset L2-N Read Only Multiplier: 1 RMS Voltage between Line 2 PS0600
RMS Voltage Size (Bits): 16 and Neutral
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000

Copyright © 2017 Cummins Inc. 56 A029X159 (Issue 19)


8-2017 4. PS0600 Modbus Register Map

Addr Parameter Access Specifications Description Control


400020 Genset L3-N Read Only Multiplier: 1 RMS Voltage between Line 3 PS0600
RMS Voltage Size (Bits): 16 and Neutral
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400022 Genset L1-L2 Read Only Multiplier: 1 RMS Voltage between Line 1 PS0600
RMS Voltage Size (Bits): 16 and Line 2
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400023 Genset L2-L3 Read Only Multiplier: 1 RMS Voltage between Line 2 PS0600
RMS Voltage Size (Bits): 16 and Line 3
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400024 Genset L3-L1 Read Only Multiplier: 1 RMS Voltage between Line 3 PS0600
RMS Voltage Size (Bits): 16 and Line 1
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400026 Genset L1 Read Only Multiplier: 1 RMS Current through Line 1 PS0600
RMS Current Size (Bits): 16
Data Type: uint16
Unit: Amps
Lower Limit: 0
Upper Limit: 10000
400027 Genset L2 Read Only Multiplier: 1 RMS Current through Line 2 PS0600
RMS Current Size (Bits): 16
Data Type: uint16
Unit: Amps
Lower Limit: 0
Upper Limit: 10000
400028 Genset L3 Read Only Multiplier: 1 RMS Current through Line 3 PS0600
RMS Current Size (Bits): 16
Data Type: uint16
Unit: Amps
Lower Limit: 0
Upper Limit: 10000

A029X159 (Issue 19) 57 Copyright © 2017 Cummins Inc.


4. PS0600 Modbus Register Map 8-2017

Addr Parameter Access Specifications Description Control


400031 Genset L1 Read Only Multiplier: 1 kW value at Line 1 PS0600
kW Size (Bits): 16
Data Type: int16
Unit: kW
Lower Limit: -10000
Upper Limit: 10000
400032 Genset L2 Read Only Multiplier: 1 kW value at Line 2 PS0600
kW Size (Bits): 16
Data Type: int16
Unit: kW
Lower Limit: -10000
Upper Limit: 10000
400033 Genset L3 Read Only Multiplier: 1 kW value at Line 3 PS0600
kW Size (Bits): 16
Data Type: int16
Unit: kW
Lower Limit: -10000
Upper Limit: 10000
400034 Genset Total Read Only Multiplier: 1 Sum of kW values of all PS0600
kW Size (Bits): 16 phases
Data Type: int16
Unit: kW
Lower Limit: -10000
Upper Limit: 10000
400035 Genset L1 Read Only Multiplier: 1 kVAR value at Line 1 PS0600
kVAr Size (Bits): 16
Data Type: int16
Unit: kVAr
Lower Limit: -10000
Upper Limit: 10000
400036 Genset L2 Read Only Multiplier: 1 kVAR value at Line 2 PS0600
kVAr Size (Bits): 16
Data Type: int16
Unit: kVAr
Lower Limit: -10000
Upper Limit: 10000
400037 Genset L3 Read Only Multiplier: 1 kVAR value at Line 3 PS0600
kVAr Size (Bits): 16
Data Type: int16
Unit: kVAr
Lower Limit: -10000
Upper Limit: 10000

Copyright © 2017 Cummins Inc. 58 A029X159 (Issue 19)


8-2017 4. PS0600 Modbus Register Map

Addr Parameter Access Specifications Description Control


400038 Genset Total Read Only Multiplier: 1 Total kVAR Value PS0600
kVAr Size (Bits): 16
Data Type: int16
Unit: kVAr
Lower Limit: -10000
Upper Limit: 10000
400040 Genset L1 Read Only Multiplier: 1 kVA value at Line 1 PS0600
kVA Size (Bits): 16
Data Type: uint16
Unit: kVA
Lower Limit: 0
Upper Limit: 10000
400041 Genset L2 Read Only Multiplier: 1 kVA value at Line 2 PS0600
kVA Size (Bits): 16
Data Type: uint16
Unit: kVA
Lower Limit: 0
Upper Limit: 10000
400042 Genset L3 Read Only Multiplier: 1 kVA value at Line 3 PS0600
kVA Size (Bits): 16
Data Type: uint16
Unit: kVA
Lower Limit: 0
Upper Limit: 10000
400043 Genset Total Read Only Multiplier: 1 Sum of kVA values of all PS0600
kVA Size (Bits): 16 phases
Data Type: uint16
Unit: kVA
Lower Limit: 0
Upper Limit: 10000
400044 Genset Read Only Multiplier: 0.01 Measured Frequency for PS0600
Frequency Size (Bits): 16 Meter1
Data Type: uint16
Unit: Hz
Lower Limit: 0
Upper Limit: 100
400058 Genset L1 Read Only Multiplier: 0.1 % RMS Current value at Line PS0600
RMS Current Size (Bits): 16 1
% Data Type: uint16
Unit: %
Lower Limit: 0
Upper Limit: 1000

A029X159 (Issue 19) 59 Copyright © 2017 Cummins Inc.


4. PS0600 Modbus Register Map 8-2017

Addr Parameter Access Specifications Description Control


400059 Genset L2 Read Only Multiplier: 0.1 % RMS Current value at Line PS0600
RMS Current Size (Bits): 16 2
% Data Type: uint16
Unit: %
Lower Limit: 0
Upper Limit: 1000
400060 Genset L3 Read Only Multiplier: 0.1 % RMS Current value at Line PS0600
RMS Current Size (Bits): 16 3
% Data Type: uint16
Unit: %
Lower Limit: 0
Upper Limit: 1000
400061 Battery Read Only Multiplier: 0.001 Measured battery voltage PS0600
Voltage Size (Bits): 16 value.
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 41
400062 Oil Pressure Read Only Multiplier: 0.1 Metered Engine Oil Pressure PS0600
Size (Bits): 16
Data Type: uint16
Unit: psi
Lower Limit: 0
Upper Limit: 900
400064 Coolant Read Only Multiplier: 0.1 Metered Engine Coolant PS0600
Temperature Size (Bits): 16 Temperature value in DegF
Data Type: int16
Unit: degF
Lower Limit: -40
Upper Limit: 410
400068 Average Read Only Multiplier: 0.125 Average Engine Speed used PS0600
Engine Size (Bits): 16 for controls and governing.
Speed Data Type: uint16
Unit: rpm
Lower Limit: 0
Upper Limit: 8191.875
400069 Start Guest Multiplier: 1 Number of times generator PS0600
Attempts Size (Bits): 16 set start request has been
Data Type: uint16 provided over the life of unit.
Unit: NA
Lower Limit: 0
Upper Limit: 65535

Copyright © 2017 Cummins Inc. 60 A029X159 (Issue 19)


8-2017 4. PS0600 Modbus Register Map

Addr Parameter Access Specifications Description Control


400070 Engine Guest Multiplier: 0.05 Engine Running time in PS0600
Running Time Size (Bits): 32 hours; pper limit is 13.6 years
Data Type: uint32
Unit: Hours
Lower Limit: 0
Upper Limit: 119304.65
400118 Utility L1-N Read Only Multiplier: 1 RMS Voltage between Line 1 PS0600
RMS Voltage Size (Bits): 16 and Neutral
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400119 Utility L2-N Read Only Multiplier: 1 RMS Voltage between Line 2 PS0600
RMS Voltage Size (Bits): 16 and Neutral
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400120 Utility L3-N Read Only Multiplier: 1 RMS Voltage between Line 3 PS0600
RMS Voltage Size (Bits): 16 and Neutral
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400122 Utility L1-L2 Read Only Multiplier: 1 RMS Voltage between Line 1 PS0600
RMS Voltage Size (Bits): 16 and Line 2
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400123 Utility L2-L3 Read Only Multiplier: 1 RMS Voltage between Line 2 PS0600
RMS Voltage Size (Bits): 16 and Line 3
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400124 Utility L3-L1 Read Only Multiplier: 1 RMS Voltage between Line 3 PS0600
RMS Voltage Size (Bits): 16 and Line 1
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000

A029X159 (Issue 19) 61 Copyright © 2017 Cummins Inc.


4. PS0600 Modbus Register Map 8-2017

Addr Parameter Access Specifications Description Control


400144 Utility Read Only Multiplier: 0.001 Measured Frequency for PS0600
Frequency Size (Bits): 32 Meter 2
Data Type: uint32
Unit: Hz
Lower Limit: 0
Upper Limit: 100
400207 Charging Read Only Multiplier: 0.001 Measured Charging PS0600
Alternator Size (Bits): 16 Alternator voltage value
Voltage Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 41
400300 Modbus Guest 0: Inactive Modbus Remote Start PS0600
Remote Start 1: Active
400301 Modbus Fault Guest 0: Inactive Fault reset via Modbus PS0600
Reset 1: Active
400302 Network Guest 0: Inactive Displays network shutdown PS0600
Shutdown 1: Active Modbus command as
Modbus received from Modbus
Command master; set to simulate the
associated diagnostic
400535 Diagnostic Guest Multiplier: 1 Sets the diagnostic code to PS0600
Output #1 Size (Bits): 16 activate Customer Output #1
Fault Code Data Type: uint16 actuator
Unit: NA
Lower Limit: 0
Upper Limit: 65535
400536 Diagnostic Guest Multiplier: 1 Sets the diagnostic code to PS0600
Output #2 Size (Bits): 16 activate Customer Output #2
Fault Code Data Type: uint16 actuator
Unit: NA
Lower Limit: 0
Upper Limit: 65535
400540 Diagnostic Read Only 0: IsFalse The digital output command PS0600
Output #3 1: IsTrue to the Customer Output
Output Status
400541 Diagnostic Read Only 0: IsFalse The digital output command PS0600
Output #4 1: IsTrue to the Customer Output
Output Status
400543 Fuel Shutoff Read Only 0: IsFalse The digital output command PS0600
Output Status 1: IsTrue to the Fuel Shutoff actuator

400552 Diagnostic Read Only 0: IsFalse The digital output command PS0600
Output #6 1: IsTrue to the Customer Output
Output Status

Copyright © 2017 Cummins Inc. 62 A029X159 (Issue 19)


8-2017 4. PS0600 Modbus Register Map

Addr Parameter Access Specifications Description Control


400553 Diagnostic Read Only 0: IsFalse The digital output command PS0600
Output #5 1: IsTrue to the Customer Output
Output Status
400557 Starter Read Only 0: IsFalse The digital output command PS0600
Output Status 1: IsTrue to the Starter actuator

400709 Application Read Only Multiplier: 1 The common device type PS0600
Device Type Size (Bits): 16 identifier parameter for all
Data Type: uint16 PGBASE applications
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401000 Metering Technician 0: Three Phase Wye Used to select the phase PS0600
Phase Config 1: Three Phase Delta configuration and Delta/Wye
2: Single Phase configuration for AC power
distribution
3: Split Phase
401001 Customer Guest 0: None The fault response for PS0600
Input #3 Fault 1: Warning Customer Input 3
Response 2: Shutdown
401002 Active Read Only Multiplier: 1 First entry of Active shutdown PS0600
Shutdown Size (Bits): 16 fault code present in Active
Fault Code Data Type: uint16 Shutdown Fault table
Row 1
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401003 Active Read Only Multiplier: 1 Second entry of Active PS0600
Shutdown Size (Bits): 16 shutdown fault code present
Fault Code Data Type: uint16 in Active Shutdown Fault
Row 2 table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401004 Active Read Only Multiplier: 1 Third entry of Active PS0600
Shutdown Size (Bits): 16 shutdown fault code present
Fault Code Data Type: uint16 in Active Shutdown Fault
Row 3 table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401005 Active Read Only Multiplier: 1 Fourth entry of Active PS0600
Shutdown Size (Bits): 16 shutdown fault code present
Fault Code Data Type: uint16 in Active Shutdown Fault
Row 4 table
Unit: NA
Lower Limit: 0
Upper Limit: 65535

A029X159 (Issue 19) 63 Copyright © 2017 Cummins Inc.


4. PS0600 Modbus Register Map 8-2017

Addr Parameter Access Specifications Description Control


401006 Active Read Only Multiplier: 1 Fifth entry of Active shutdown PS0600
Shutdown Size (Bits): 16 fault code present in Active
Fault Code Data Type: uint16 Shutdown Fault table
Row 5
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401007 Active Read Only Multiplier: 1 Sixth entry of Active PS0600
Shutdown Size (Bits): 16 shutdown fault code present
Fault Code Data Type: uint16 in Active Shutdown Fault
Row 6 table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401008 Active Read Only Multiplier: 1 Seventh entry of Active PS0600
Shutdown Size (Bits): 16 shutdown fault code present
Fault Code Data Type: uint16 in Active Shutdown Fault
Row 7 table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401009 Active Read Only Multiplier: 1 Eighth entry of Active PS0600
Shutdown Size (Bits): 16 shutdown fault code present
Fault Code Data Type: uint16 in Active Shutdown Fault
Row 8 table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401010 Active Read Only Multiplier: 1 Ninth entry of Active PS0600
Shutdown Size (Bits): 16 shutdown fault code present
Fault Code Data Type: uint16 in Active Shutdown Fault
Row 9 table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401011 Active Read Only Multiplier: 1 Tenth entry of Active PS0600
Shutdown Size (Bits): 16 shutdown fault code present
Fault Code Data Type: uint16 in Active Shutdown Fault
Row 10 table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401012 Active Read Only Multiplier: 1 First entry of Active warning PS0600
Warning Fault Size (Bits): 16 fault code present in Active
Code Row 1 Data Type: uint16 warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535

Copyright © 2017 Cummins Inc. 64 A029X159 (Issue 19)


8-2017 4. PS0600 Modbus Register Map

Addr Parameter Access Specifications Description Control


401013 Active Read Only Multiplier: 1 Second entry of Active PS0600
Warning Fault Size (Bits): 16 warning fault code present in
Code Row 2 Data Type: uint16 Active warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401014 Active Read Only Multiplier: 1 Third entry of Active warning PS0600
Warning Fault Size (Bits): 16 fault code present in Active
Code Row 3 Data Type: uint16 warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401015 Active Read Only Multiplier: 1 Fourth entry of Active warning PS0600
Warning Fault Size (Bits): 16 fault code present in Active
Code Row 4 Data Type: uint16 warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401016 Active Read Only Multiplier: 1 Fifth entry of Active warning PS0600
Warning Fault Size (Bits): 16 fault code present in Active
Code Row 5 Data Type: uint16 warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401017 Active Read Only Multiplier: 1 Sixth entry of Active warning PS0600
Warning Fault Size (Bits): 16 fault code present in Active
Code Row 6 Data Type: uint16 warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401018 Active Read Only Multiplier: 1 Seventh entry of Active PS0600
Warning Fault Size (Bits): 16 warning fault code present in
Code Row 7 Data Type: uint16 Active warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401019 Active Read Only Multiplier: 1 Eighth entry of Active warning PS0600
Warning Fault Size (Bits): 16 fault code present in Active
Code Row 8 Data Type: uint16 warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535

A029X159 (Issue 19) 65 Copyright © 2017 Cummins Inc.


4. PS0600 Modbus Register Map 8-2017

Addr Parameter Access Specifications Description Control


401020 Active Read Only Multiplier: 1 Ninth entry of Active warning PS0600
Warning Fault Size (Bits): 16 fault code present in Active
Code Row 9 Data Type: uint16 warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401021 Active Read Only Multiplier: 1 Tenth entry of Active warning PS0600
Warning Fault Size (Bits): 16 fault code present in Active
Code Row 10 Data Type: uint16 warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401022 Auto Mains Guest 0: Disable Used to enable or disable the PS0600
Failure 1: Enable Auto Mains Failure Feature
Enable
401023 Load Transfer Guest 0: GTEC Provides the type of Load PS0600
Switch Type 1: Contact Pair Transfer Switch

401024 AMF State Read Only 0: AMF Not Available Provides the state in which PS0600
1: Transfer Retransfer Off the Auto Mains Failure is
2: Utility Pickup currently present
3: Utility Dropout
4: Genset Starting
5: Transfer Start
6: Utility CB Opened
7: Genset CB Closed
8: Transfer Complete
9: Retransfer Start
10: Genset CB Opened
11: Utility CB Closed
12: Retransfer Complete
13: Transfer Fail
14: Retransfer Fail
401025 Transfer Read Only 0: Not Available Provides value of Transfer PS0600
Switch 1: At Utility switch feedback status
Feedback 2: At Genset
Status
3: Unknown Open
4: Unknown Closed
402355 Time Delay Guest Multiplier: 0.1 Provides the value of Time PS0600
Engine Start Size (Bits): 16 Delay Engine Start (TDES)
Data Type: uint16
Unit: sec
Lower Limit: 0
Upper Limit: 3600

Copyright © 2017 Cummins Inc. 66 A029X159 (Issue 19)


8-2017 4. PS0600 Modbus Register Map

Addr Parameter Access Specifications Description Control


402356 Time Delay Guest Multiplier: 0.1 Provides the value of Time PS0600
Engine Size (Bits): 16 Delay Engine Cooldown
Cooldown Data Type: uint16 (TDEC)
Unit: sec
Lower Limit: 0
Upper Limit: 3600
403000 Genset Technician Multiplier: 1 Nominal voltage for the PS0600
Nominal Size (Bits): 16 source
Voltage Data Type: uint16
Unit: V
Lower Limit: 1
Upper Limit: 45000
403001 System Operator 0: 50 Hz AC frequency of the power PS0600
Nominal 1: 60 Hz system
Frequency
403005 Charging Guest 0: Disable Used to disable the controller PS0600
Alternator 1: Enable related charging alternator
Enable functions
403006 Start Time Technician Multiplier: 1 Time delay before engine PS0600
Delay Size (Bits): 16 cranks after remote start
Data Type: uint16 status becomes active
Unit: sec
Lower Limit: 0
Upper Limit: 300
403007 Stop Time Technician Multiplier: 1 Time delay after which the PS0600
Delay Size (Bits): 16 engine initiation of
Data Type: uint16 cooldown/stop sequence.
Unit: sec
Lower Limit: 0
Upper Limit: 600
403008 Crank Guest Multiplier: 1 The trim provides number of PS0600
Attempts Size (Bits): 16 crank attempts for each
Data Type: uint16 genset start request
Unit: NA
Lower Limit: 1
Upper Limit: 7
403009 Cycle Crank Guest Multiplier: 1 Sets the time to engage the PS0600
Engage Time Size (Bits): 16 starter during a single crank
Data Type: uint16 attempt for cycle crank mode
Unit: sec
Lower Limit: 2
Upper Limit: 20

A029X159 (Issue 19) 67 Copyright © 2017 Cummins Inc.


4. PS0600 Modbus Register Map 8-2017

Addr Parameter Access Specifications Description Control


403010 Cycle Crank Guest Multiplier: 1 Sets the starter rest time PS0600
Rest Time Size (Bits): 16 between start attempts for
Data Type: uint16 cycle crank mode
Unit: sec
Lower Limit: 7
Upper Limit: 40
403011 Battleshort Guest 0: Disable Used to enable or disable the PS0600
Enable 1: Enable Battle short Feature.

403012 TB16-10 Guest 0: Not Connected Used to set the value of PS0600
Sensor 1: Diagnostic Input #1 TB16-10 Sensor Selection
Selection 2: Battle Short
403033 Genset Model Guest Multiplier: 1 Number indentifying the PS0600
Number Size (Bits): 168 model of this generator set
Data Type: string20
Unit: NA
Lower Limit: 0
Upper Limit: 9999999999
403049 Genset Serial Guest Multiplier: 1 Serial number for identifying PS0600
Number Size (Bits): 168 this generator set
Data Type: string20
Unit: NA
Lower Limit: 0
Upper Limit: 9999999999
403065 Customer Guest 0: None The fault response for PS0600
Input #1 Fault 1: Warning Customer Input 1
Response 2: Shutdown
403066 Customer Guest 0: None The fault response for PS0600
Input #2 Fault 1: Warning Customer Input 2
Response 2: Shutdown
403067 Diagnostic Read Only 0: IsFalse The digital output command PS0600
Output #1 1: IsTrue to the Customer Output
Output Status
403068 Diagnostic Read Only 0: IsFalse The digital output command PS0600
Output #2 1: IsTrue to the Customer Output
Output Status
403309 Over Guest 0: Disable Enables overfrequency PS0600
Frequency 1: Enable diagnostic
Shutdown
Enable

Copyright © 2017 Cummins Inc. 68 A029X159 (Issue 19)


8-2017 4. PS0600 Modbus Register Map

Addr Parameter Access Specifications Description Control


403344 Clock Day Technician Multiplier: 1 Provides the value of Clock PS0600
Size (Bits): 8 Day
Data Type: uint8
Unit: NA
Lower Limit: 1
Upper Limit: 31
403345 Clock Hour Technician Multiplier: 1 Provides the value of Clock PS0600
Size (Bits): 8 Hour
Data Type: uint8
Unit: NA
Lower Limit: 0
Upper Limit: 23
403346 Clock Minute Technician Multiplier: 1 Provides the value of Clock PS0600
Size (Bits): 8 Minute
Data Type: uint8
Unit: NA
Lower Limit: 0
Upper Limit: 59
403347 Clock Mode Technician 0: Normal Set the value of Clock Mode PS0600
1: Set Clock
2: Save Clock
403348 Clock Month Technician Multiplier: 1 Provides the value of Clock PS0600
Size (Bits): 8 Month
Data Type: uint8
Unit: NA
Lower Limit: 1
Upper Limit: 12
403349 Clock Second Technician Multiplier: 1 Provides the value of Clock PS0600
Size (Bits): 8 Second
Data Type: uint8
Unit: NA
Lower Limit: 0
Upper Limit: 59
403350 Clock Year Technician Multiplier: 1 Provides the value of Clock PS0600
Size (Bits): 8 Year
Data Type: uint8
Unit: NA
Lower Limit: 0
Upper Limit: 99

A029X159 (Issue 19) 69 Copyright © 2017 Cummins Inc.


4. PS0600 Modbus Register Map 8-2017

Addr Parameter Access Specifications Description Control


403351 Daylight Technician Multiplier: 1 Provides the value of Daylight PS0600
Saving End Size (Bits): 8 Saving End Hour
Hour Data Type: uint8
Unit: NA
Lower Limit: 0
Upper Limit: 23
403352 Daylight Technician Multiplier: 1 Provides the value of Daylight PS0600
Saving End Size (Bits): 8 Saving End Month
Month Data Type: uint8
Unit: NA
Lower Limit: 1
Upper Limit: 12
403353 Daylight Technician 0: Invalid Provides the value of Daylight PS0600
Saving End 1: First Occurrence Saving End Week
Week 2: Second Occurrence
3: Third Occurrence
4: Fourth Occurrence
5: Last Occurrence
403354 Daylight Technician 0: Sunday Provides the value of Daylight PS0600
Saving Start 1: Monday Saving Start Day
Day 2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
403355 Daylight Technician Multiplier: 1 Provides the value of Daylight PS0600
Saving Start Size (Bits): 8 Saving Start Hour
Hour Data Type: uint8
Unit: NA
Lower Limit: 0
Upper Limit: 23
403356 Daylight Technician Multiplier: 1 Provides the value of Daylight PS0600
Saving Start Size (Bits): 8 Saving Start Month
Month Data Type: uint8
Unit: NA
Lower Limit: 1
Upper Limit: 12
403357 Daylight Technician 0: Invalid Provides the value of Daylight PS0600
Saving Start 1: First Occurrence Saving Start Week
Week 2: Second Occurrence
3: Third Occurrence
4: Fourth Occurrence
5: Last Occurrence

Copyright © 2017 Cummins Inc. 70 A029X159 (Issue 19)


8-2017 4. PS0600 Modbus Register Map

Addr Parameter Access Specifications Description Control


403358 Daylight Technician Multiplier: 1 Value of Daylight Saving PS0600
Saving Time Size (Bits): 8 Time Adjustment
Adjustment Data Type: uint8
Unit: min
Lower Limit: 0
Upper Limit: 120
403359 Daylight Technician 0: Disable Used to Enable or Disable the PS0600
Saving Time 1: Enable value of Daylight Saving Time
Enable
403376 Scheduler Guest Multiplier: 1 Used to adjust the length in PS0600
Program Size (Bits): 8 minutes for the selected
Duration Data Type: uint8 program.
Minute
Unit: min
Lower Limit: 1
Upper Limit: 60
403377 Scheduler Guest 0: Disable Used to enable or disable the PS0600
Program 1: Enable selected program
Enable
403378 Scheduler Guest 0: Weekly Used to adjust the repeat PS0600
Program 1: Bi-Monthly interval for the selected
Repeat 2: Monthly program
Interval
3: Quarterly
4: Semi-Annualy
403380 Scheduler Guest 0: Sunday Used to adjust the start day PS0600
Program Start 1: Monday of the week for the selected
Day 2: Tuesday program
3: Wednesday
4: Thursday
5: Friday
6: Saturday
403381 Scheduler Guest Multiplier: 1 Used to adjust the start hour PS0600
Program Start Size (Bits): 8 for the selected program
Hour Data Type: uint8
Unit: Hours
Lower Limit: 0
Upper Limit: 23
403382 Scheduler Guest Multiplier: 1 Used to adjust the start PS0600
Program Start Size (Bits): 8 minute for the selected
Minute Data Type: uint8 program
Unit: min
Lower Limit: 0
Upper Limit: 59

A029X159 (Issue 19) 71 Copyright © 2017 Cummins Inc.


4. PS0600 Modbus Register Map 8-2017

Addr Parameter Access Specifications Description Control


403383 Daylight Technician 0: Sunday Provides the value of Daylight PS0600
Saving End 1: Monday Saving End Day
Day 2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
403511 Low Battery Read Only Multiplier: 0.1 Holds low battery voltage PS0600
Voltage Size (Bits): 16 fault threshold value based
Threshold Data Type: uint16 upon 12V/24V
Unit: V
Lower Limit: 0
Upper Limit: 99
403550 Weak Battery Read Only Multiplier: 0.1 Holds weak battery voltage PS0600
Voltage Size (Bits): 16 fault threshold value based
Threshold Data Type: uint16 upon 12V/24V
Unit: V
Lower Limit: 0
Upper Limit: 99
403551 Weak Battery Guest Multiplier: 1 The time delay until a weak PS0600
Voltage Set Size (Bits): 8 battery condition is reported
Time Data Type: uint8 as a fault
Unit: sec
Lower Limit: 1
Upper Limit: 5
403562 Customer Read Only 0: IsFalse The digital status of Customer PS0600
Input #3 1: IsTrue Input

403599 Customer Read Only 0: IsFalse The digital status of Customer PS0600
Input #2 1: IsTrue Input

403647 Low Coolant Guest Multiplier: 1 Sets time to set the low PS0600
Temperature Size (Bits): 8 coolant temperature fault
Warning Set Data Type: uint8
Time
Unit: min
Lower Limit: 0
Upper Limit: 30
403648 Low Coolant Guest Multiplier: 1 Sets threshold for the low PS0600
Temperature Size (Bits): 16 coolant temperature fault
Warning Data Type: uint16 warning
Threshold
Unit: degF
Lower Limit: -20
Upper Limit: 130

Copyright © 2017 Cummins Inc. 72 A029X159 (Issue 19)


8-2017 4. PS0600 Modbus Register Map

Addr Parameter Access Specifications Description Control


403651 High Battery Guest Multiplier: 0.1 Sets 12V high battery voltage PS0600
Voltage Size (Bits): 16 fault threshold
Threshold Data Type: uint16
12V
Unit: V
Lower Limit: 14
Upper Limit: 17
403652 Low Battery Guest Multiplier: 0.1 Sets 12V low battery voltage PS0600
Voltage Size (Bits): 16 fault threshold for generator
Running Data Type: uint16 set operation while in rated
Threshold mode
Unit: V
12V
Lower Limit: 12
Upper Limit: 16
403653 Low Battery Guest Multiplier: 0.1 Sets 12V low battery voltage PS0600
Voltage Size (Bits): 8 fault threshold for generator
Stopped Data Type: uint8 set operation in all modes
Threshold except rated
Unit: V
12V
Lower Limit: 10
Upper Limit: 13
403654 Weak Battery Guest Multiplier: 0.1 Sets 12V weak battery PS0600
Voltage Size (Bits): 16 voltage fault threshold
Threshold Data Type: uint16
12V
Unit: V
Lower Limit: 6
Upper Limit: 10
403655 High Battery Guest Multiplier: 0.1 Sets 24V high battery voltage PS0600
Voltage Size (Bits): 16 fault threshold
Threshold Data Type: uint16
24V
Unit: V
Lower Limit: 28
Upper Limit: 34
403656 Low Battery Guest Multiplier: 0.1 Sets 24V low battery voltage PS0600
Voltage Size (Bits): 16 fault threshold for generator
Running Data Type: uint16 set operation while in rated
Threshold mode
Unit: V
24V
Lower Limit: 24
Upper Limit: 28
403657 Low Battery Guest Multiplier: 0.1 Sets 24V low battery voltage PS0600
Voltage Size (Bits): 16 fault threshold for generator
Stopped Data Type: uint16 set operation in all modes
Threshold except rated
Unit: V
24V
Lower Limit: 22
Upper Limit: 26

A029X159 (Issue 19) 73 Copyright © 2017 Cummins Inc.


4. PS0600 Modbus Register Map 8-2017

Addr Parameter Access Specifications Description Control


403658 Weak Battery Guest Multiplier: 0.1 Sets 24V weak battery PS0600
Voltage Size (Bits): 16 voltage fault threshold
Threshold Data Type: uint16
24V
Unit: V
Lower Limit: 10
Upper Limit: 16
403662 Charging Guest Multiplier: 1 Sets the time delay for the PS0600
Alternator Set Size (Bits): 16 charging alt failure fault
Time Data Type: uint16
Unit: sec
Lower Limit: 2
Upper Limit: 300
403676 High Battery Read Only Multiplier: 0.1 Holds high battery voltage PS0600
Voltage Size (Bits): 16 fault threshold value based
Threshold Data Type: uint16 upon 12V/24V
Unit: V
Lower Limit: 0
Upper Limit: 99
403688 Low Battery Guest Multiplier: 1 The time delay until a low PS0600
Voltage Set Size (Bits): 8 battery voltage condition is
Time Data Type: uint8 reported as a fault
Unit: sec
Lower Limit: 2
Upper Limit: 60
403693 Nominal Guest 0: Twelve Volt Selects the nominal battery PS0600
Battery 1: TwentyFour Volt operating voltage
Voltage
403778 Exercise Read Only 0: Inactive Indicates state of an exercise PS0600
Scheduler 1: Active scheduler
State 2: Abort
403793 Customer Read Only 0: IsFalse The digital status of Customer PS0600
Input #1 1: IsTrue Input

403821 Time Delay Operator Multiplier: 0.1 Provides the value of Time PS0600
Programmed Size (Bits): 16 Delay Programmed Transition
Transition Data Type: uint16 (TDPT)
Unit: sec
Lower Limit: 0
Upper Limit: 600

Copyright © 2017 Cummins Inc. 74 A029X159 (Issue 19)


8-2017 4. PS0600 Modbus Register Map

Addr Parameter Access Specifications Description Control


403822 Time Delay Guest Multiplier: 0.1 Provides the Value of Time PS0600
Emergency to Size (Bits): 16 Delay Emergency to Normal
Normal Data Type: uint16 (TDEN)
Unit: sec
Lower Limit: 0
Upper Limit: 1800
403825 Time Delay Guest Multiplier: 1 Provides the value of Time PS0600
Normal to Size (Bits): 16 Delay Normal to Emergency
Emergency Data Type: uint16 (TDNE)
Unit: sec
Lower Limit: 0
Upper Limit: 300
403952 Speed/Frequ Guest Multiplier: 0.1 Sets delay time for generating PS0600
ency Conflict Size (Bits): 16 the Speed/Frequency
Shutdown Set Data Type: uint16 mismatch fault
Time
Unit: sec
Lower Limit: 0.5
Upper Limit: 10
403953 Speed/Frequ Guest Multiplier: 0.1 Sets the threshold for PS0600
ency Conflict Size (Bits): 16 generating the
Shutdown Data Type: uint16 Speed/Frequency mismatch
Threshold fault
Unit: Hz
Lower Limit: 0.5
Upper Limit: 20
408025 TB15 Modbus Technician Multiplier: 1 This trim allows for the PS0600
Inactivity Size (Bits): 8 configuring of the Modbus
Interval Data Type: uint8 failure time delay for this port.
Unit: sec
Lower Limit: 1
Upper Limit: 60
408028 TB15 Modbus Technician Multiplier: 1 This ports node address is PS0600
Node Size (Bits): 8 configurable from 1 to 247.
Address Data Type: uint8
Unit: NA
Lower Limit: 1
Upper Limit: 247
408029 TB15 Modbus Administrator 0: Guest Used to select the Access PS0600
Access Level 1: Operator Level of this port
2: Technician
408031 TB15 UART Technician 0: MON Used to select the active PS0600
Protocol 1: Modbus protocol on this port
Selection

A029X159 (Issue 19) 75 Copyright © 2017 Cummins Inc.


4. PS0600 Modbus Register Map 8-2017

Addr Parameter Access Specifications Description Control


408033 TB15 Modbus Technician 0: None (1 Stop) This trim allows configuring of PS0600
Parity Stop 1: None (2 Stop) the parity and stop bits for
Bit Selection 2: Even (1 Stop) this port.
3: Odd (1 Stop)
408035 TB15 Modbus Read Only 0: Not Available Updates TB15 ports Modbus PS0600
Activity 1: Inactive communication activity
Status 2: Bus Active
3: Local Active
408038 TB15 Modbus Technician 0: 2400 Sets the TB15 ports' baud PS0600
Baud Rate 1: 4800 rate
Selection 2: 9600
3: 19200
4: 28800
5: 38400
6: 57600
7: 115200
408039 Save Trims Operator 0: IsFalse Setting this parameter to PS0600
1: IsTrue IsTrue will trigger a save of all
non-volatile trims on the
entire device.
408041 TB15 Modbus Technician 0: Inactive Setting this to active clears all PS0600
Clear 1: Active the Modbus status counters
Counters for TB15 port.

Copyright © 2017 Cummins Inc. 76 A029X159 (Issue 19)


5 PowerCommand 2.x/3.x Modbus
Register Map
5.1 Modbus Communications
Use the following equation to calculate the value of 32-bit parameters.
• A = high register value
• B = low register value
parameter = (A * 65536 * multiplier) + (B * multiplier)
alternate formula: parameter = ((A*65536)+B)* multiplier
For example: Engine Running Time is a 32-bit parameter in registers 40070 and 40071.
• Register 40070 has 322 (high register value = A).
• Register 40071 has 15637 (low register value = B).
Engine Running Time = (322 * 65536 * 0.1) + (15637 * 0.1)
The engine run-time is 2111823 seconds, or 586.6 hours.
To write a 32-bit value to 2 Modbus registers, calculate the value for each register as follows:
• A (High register value) = INT ((Parameter / Multiplier) / 65536))
• B (Low register value) = INT ((Parameter / Multiplier) % (65536))
• % = Modulus (the remainder of integer division)
For example: To write Load Demand Genset Run Hours = 80000.5
• Register 40769 (high register value A) should be written to INT ((80000.5/0.1)/65536) = 12
• Register 40770 (low register value B) should be written to INT ((80000.5/.01)%65536) = 13573
To write 32-bit values to 2 modbus addresses always write the high register value followed by the low
register value. Both registers must be written to change the 32-bit value in the control.

5.2 Parametrics (Analog Values)


Unsupported (Not Available) Data=> "Not Available" data shall be represented as highest positive value
for that parameter. For example for a two byte, unsigned integer that would be 65535. For a signed
integer that would be 32767.
• Parameters which are not available due to the sensor not being installed, or not enabled in the
controllers configuration will classified like this.
Network Failed Data=> "Network Failure" data shall be represented as three less than the highest
positive value for that parameter. For example for a two byte, unsigned integer that would be 65532. For a
signed integer that would be 32764.
• Data that comes from a network that has failed, such as sensors on the PCCnet I/O Module or
sensor data coming in via the CAN datalink will be classified like this.

A029X159 (Issue 19) 77 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Hardware/Component Failure=> "Hardware/Component Failure" data shall be represented as four less


than the highest positive value for that parameter. For example for a two byte, unsigned integer that would
be 65531. For a signed integer that would be 32763.
• A hardware/component failure that provides the data, such as the voltage, current and power data
that comes from an external metering chip will be classified like this.
Out of Range High/Out of Range=> "Out of Range High/Out of Range" data shall be represented as one
less than the highest positive value for that parameter. For example for a two byte, unsigned integer that
would be 65534. For a signed integer that would be 32766.
• Data that has been determined to be out of range high or out of range (when there is no distinction
between out of range high and out of range low) due to an open sensor for example, will be
classified like this.
Out of Range Low=> "Out of Range Low" data shall be represented as two less than the highest positive
value for that parameter. For example for a two byte, unsigned integer that would be 65533. For a signed
integer that would be 32765.
• Data that has been determined to be out of range low due to a shorted sensor for example, will be
classified like this.
Data within Normal Operating Range (Valid)=> Anything other than above.

NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

NOTICE
The Master device can read 1-40 contiguous registers, write 1-40 contiguous registers, or read
diagnostic counters.

NOTICE
The lowest Modbus register value is considered as the High Register Value and the highest
Modbus register value is considered as the Low Register Value.

Copyright © 2017 Cummins Inc. 78 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40010 Control Read Only 0: Off Current position of the PC 2.x,
Switch 1: Auto generator set switch panel PC 3.x
Position 2: Manual Off-Run-Auto switch as seen
by the generator set control.
SEE ALSO ADDRESS
40580.
NOTE: Both address 40580
and 40010 show the same
information however the
specification for each is
different.
40011 Genset Run Read Only 0: Stop Current genset operating PC 2.x,
Sequence 1: Time Delay to Start mode. Modbus mapping shall PC3.x
State 2: Warmup at Idle be in both addresses 43500
and 40011
3: Rated Freq and Voltage
4: Cooldown / Stop Delay
5: Cooldown at Idle
6: Rated to Idle Transition
Delay
40012 Most Recent Read Only Multiplier: 1 This Modbus Register PC 2.x,
Fault or Offset: 0 displays most recent Fault or PC 3.x
Warning Size (bits): 16 Warning. It is not mapped
with any logical.
Sign: U
Unit:
Lower Limit:
Upper Limit: 65530
40013 Modbus Read Only 0: None This register returns the Fault PC 2.x,
register 1: Warning Type of the Fault Code. This PC 3.x
40013 2: Shutdown is not associated with any
logical.
40014 Genset % Read Only Multiplier: 0.01 Monitors the total generator PC 2.x,
Standby Total Offset: 0 set standby KW percentage PC 3.x
kW Size (bits): 16 output.
Sign: S
Unit: %
Lower Limit:
Upper Limit:
40016 NFPA 110 Read Only Multiplier: 1.0 16-bit number to represent PC 2.x,
Logical Offset: 0 the status of the NFPA 110 PC 3.x
Status Size (bits): 16 logical. See NFPA 110
bitmap.
Sign: U
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 79 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40017 Extended Read Only Multiplier: 1.0 16-bit number to represent PC 2.x,
NFPA 110 Offset: 0 the status of the NFPA 110 PC 3.x
Logical Size (bits): 16 logical. See NFPA 110
Status bitmap.
Sign: U
Unit:
Lower Limit:
Upper Limit:
40018 Genset L1N Read Only Multiplier: 1 Generator set L1N voltage PC 2.x,
Voltage Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40019 Genset L2N Read Only Multiplier: 1 Generator set L2N voltage PC 2.x,
Voltage Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40020 Genset L3N Read Only Multiplier: 1 Generator set L3N voltage PC 2.x,
Voltage Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40021 Genset LN Read Only Multiplier : 1 Genset Line to Neutral PC 2.x,
Average Offset: 0 average voltage PC 3.x
Voltage Size (Bits) : 16
Sign: U
Units: Vac
Upper Limit: NA
Default: 0
40022 Genset L1L2 Read Only Multiplier: 1 Generator set L1L2 voltage PC 2.x,
Voltage Lower Limit: NA PC 3.x
Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 80 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40023 Genset L2L3 Read Only Multiplier: 1 Generator set L2L3 voltage PC 2.x,
Voltage Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40024 Genset L3L1 Read Only Multiplier: 1 Generator set L3L1 voltage PC 2.x,
Voltage Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40025 Genset LL Read Only Multiplier: 1 Generator set Line to Line PC 2.x,
Average Offset: 0 average voltage PC 3.x
Voltage Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40026 Genset L1 Read Only Multiplier: 1 Monitors the generator set L1 PC 2.x,
Current Offset: 0 current value. PC 3.x
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40027 Genset L2 Read Only Multiplier: 1 Generator set L2 current PC 2.x,
Current Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40028 Genset L3 Read Only Multiplier: 1 Generator set L3 current PC 2.x,
Current Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 81 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40029 Genset Read Only Multiplier: 1 Generator set average PC 2.x,
Average Offset: 0 current PC 3.x
Current Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40030 Genset Read Only Multiplier: 1 Generator set neutral current PC 3.x
Neutral Offset: 0
Current Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40031 Genset L1 Read Only Multiplier: 1 Generator set L1 kW PC 2.x,
kW Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:
40032 Genset L2 Read Only Multiplier: 1 Generator set L2 kW PC 2.x,
kW Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kW
Lower Limit: -32768
Upper Limit: 32762
40033 Genset L3 Read Only Multiplier: 1 Generator set L3 kW PC 2.x,
kW Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kW
Lower Limit: -32768
Upper Limit: 32762
40034 Genset Total Read Only Multiplier: 1 Generator set total kW PC 2.x,
kW Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 82 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40035 Genset L1 Read Only Multiplier: 1 Generator set L1 kVAR PC 2.x,
kVAR Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:
40036 Genset L2 Read Only Multiplier: 1 Generator set L2 kVAR PC 2.x,
kVAR Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit: -32768
Upper Limit: 32762
40037 Genset L3 Read Only Multiplier: 1 Generator set L3 kVAR PC 2.x,
kVAR Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit
40038 Genset Total Read Only Multiplier: 1 Generator set total kVAR PC 2.x,
kVAR Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit
40039 Genset Total Read Only Multiplier: 0.01 Generator set total power PC 2.x,
Power Factor Offset: 0 factor (L1+L2+L3) PC 3.x
Size (bits): 8
Sign: S
Unit: PF
Lower Limit:
Upper Limit
40040 Genset L1 Read Only Multiplier: 1 Generator set L1 kVA PC 2.x,
kVA Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit

A029X159 (Issue 19) 83 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40041 Genset L2 Read Only Multiplier: 1 Generator set L2 kVA PC 2.x,
kVA Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit
40042 Genset L3 Read Only Multiplier: 1 Generator set L3 kVA PC 2.x,
kVA Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit kVA
Lower Limit:
Upper Limit
40043 Genset Total Read Only Multiplier: 1 Generator set total kVA PC 2.x,
kVA Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit
40044 Genset Read Only Multiplier : 0.01 Genset Frequency OP. PC 2.X,
Frequency Offset: 0 Modbus has different PC 3.X
OP Size (bits): 16 multiplier than PCCnet. For
Modbus use only,
Sign: U
Multiplier/Units = 0.1 Hz
Unit: Hz
Lower Limit: NA
Upper Limit: NA
40046 Genset Total Read Only Multiplier: 1 Generator set total negative PC 2.x,
Negative kWh Offset: 0 kWh accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:
40047 Genset Total Read Only Multiplier: 1 Generator set total negative PC 2.x,
Negative kWh Offset: 0 kWh accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 84 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40048 Genset Total Read Only Multiplier: 1 Generator set total positive PC 2.x,
Positive kWh Offset: 0 kWh accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit: 0
Upper Limit: 4294967290
40049 Genset Total Read Only Multiplier: 1 Generator set total positive PC 2.x,
Positive kWh Offset: 0 kWh accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit: 0
Upper Limit: 4294967290
40050 Genset Total Read Only Multiplier: 1 Generator set total net kWh PC 2.x,
Net kWh Offset: 0 accumulation PC 3.x
Size (bits): 32
Sign: S
Unit: kWh
Lower Limit: -2147483648
Upper Limit: 2147483643
40051 Genset Total Read Only Multiplier: 1 Generator set total net kWh PC 2.x,
Net kWh Offset: 0 accumulation PC 3.x
Size (bits): 32
Sign: S
Unit: kWh
Lower Limit: -2147483648
Upper Limit: 2147483643
40052 Genset Total Read Only Multiplier: 1 Generator set total negative PC 2.x,
Negative Offset: 0 kVARh accumulation PC 3.x
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:
40053 Genset Total Read Only Multiplier: 1 Generator set total negative PC 2.x,
Negative Offset: 0 kVARh accumulation PC 3.x
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 85 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40054 Genset Total Read Only Multiplier: 1 Generator set total positive PC 2.x,
Positive Offset: 0 kVARh accumulation PC 3.x
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit: 0
Upper Limit: 4294967290
40055 Genset Total Read Only Multiplier: 1 Generator set total positive PC 2.x,
Positive Offset: 0 kVARh accumulation PC 3.x
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit: 0
Upper Limit: 4294967290
40056 Genset Total Read Only Multiplier: 1 Generator set total net PC 2.x,
Net kVARh Offset: 0 kVARh accumulation PC 3.x
Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit: -2147483648
Upper Limit: 2147483643
40057 Generator set Read Only Multiplier: 1 Generator set total net PC 2.x,
Total Net Offset: 0 kVARh accumulation PC 3.x
kVARh Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit: -2147483648
Upper Limit: 2147483643
40058 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Standby L1 Offset: 0 standby L1 current PC 3.x
Current Size (bits): 16 percentage output.
Sign: U
Unit: %
Lower Limit:
Upper Limit:
40059 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Standby L2 Offset: 0 standby L2 current PC 3.x
Current Size (bits): 16 percentage output.
Sign: U
Unit: %
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 86 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40060 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Standby L3 Offset: 0 standby L3 current PC 3.x
Current Size (bits): 16 percentage output.
Sign: U
Unit: %
Lower Limit:
Upper Limit:
40061 Battery Read Only Multiplier: 0.1 Battery voltage value. PC 2.x,
Voltage Offset: 0 Modbus and PCCNet has PC 3.x
Size (bits): 16 different multiplier value. For
Modbus use only,
Sign: U
multiplier/units = 0.1 volts
Unit: Vdc
Lower Limit:
Upper Limit:
40062 Oil Pressure Read Only Multiplier: 1 Monitor point for the Oil PC 2.x,
Offset: 0 Pressure. Modbus and PC 3.x
Size (bits): 16 PCCNet have different
multiplier value. For Modbus
Sign: U
use only, Multiplier/Units =
Unit: kPa 1kPa
Lower Limit:
Upper Limit:
40063 Oil Read Only Multiplier: 0.1 Monitor point for the Oil PC 2.x,
Temperature Offset: 0 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit:
Upper Limit:
40064 Coolant Read Only Multiplier: 0.1 Monitor point for the Coolant PC 2.x,
Temperature Offset: 0 Temperature. Modbus PC 3.x
Size (bits): 16 mapping shall be to both
46126 and 40064 addresses.
Sign: S
For Modbus use only,
Unit: degC Multiplier/Units = 0.1C
Lower Limit:
Upper Limit:
40065 Intake Read Only Multiplier: 0.1 To monitor Intake Manifold PC 2.x,
Manifold Offset: 0 Temperature. This parameter PC 3.x
Temperature Size (bits): 16 represents ”Intake Manifold
Temperature 1”.
Sign: S
Unit: degF
Lower Limit: -40
Upper Limit: 410

A029X159 (Issue 19) 87 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40065 Intake Read Only Multiplier: 0.1 To monitor Intake Manifold PC 2.x,
Manifold Offset: 0 Temperature. This parameter PC 3.x
Temperature Size (bits): 16 represents ”Intake Manifold
Temperature 1”.
Sign: S
Unit: degF
Lower Limit: -40
Upper Limit: 410

40066 Fuel Read Only Multiplier: 0.1 Monitor point for the Fuel PC 2.x,
Temperature Offset: 0 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -40
Upper Limit: 410
40067 Fuel Rate Read Only Multiplier: 0.05 Monitor point for the Fuel PC 2.x,
Offset: 0 Rate PC 3.x
Size (bits): 16
Sign: S
Unit: gal/hr
Lower Limit:
Upper Limit:
40068 Average Read Only Multiplier: 1 Monitor point for the Average PC 2.x,
Engine Offset: 0 Engine Speed. Modbus and PC 3.x
Speed Size (bits): 16 PCCNet have different
multiplier value. For Modbus
Sign: U
use only, Multiplier/Units = 1
Unit: RPM RPM
Lower Limit:
Upper Limit:
40069 Total Start Read Only Multiplier : 1 Total number of start PC 2.X,
Attempts OP Offset: 0 attempts PC3.X
Size (bits): 16
Sign: U
Unit: NAr
Lower Limit: 0
Upper Limit: 65535
40070 Engine Read Only Multiplier: 0.1 Total engine run time. PC 2.x,
Running Time Offset: 0 Modbus has different PC 3.x
Size (bits): 32 multiplier than PCCNet. For
Modbus use only,
Sign: U
multiplier/units = 0.1 Sec
Unit: seconds
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 88 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40071 Engine Read Only Multiplier: 0.1 Total engine run time. PC 2.x,
Running Time Offset: 0 Modbus has different PC 3.x
Size (bits): 32 multiplier than PCCnet. For
Modbus use only,
Sign: U
multiplier/units = 0.1 Sec
Unit: seconds
Lower Limit:
Upper Limit:
40072 Total Fuel Read Only Multiplier: 0.1 Total fuel consumption since PC 2.x,
Consumption Offset: 0 start of engine. PC 3.x
Size (bits): 32
Sign: U
Unit: gallons
Lower Limit:
Upper Limit:
40073 Total Fuel Read Only Multiplier: 0.1 Total fuel consumption since PC 2.x,
Consumption Offset: 0 start of engine. PC 3.x
Size (bits): 32
Sign: U
Unit: gallons
Lower Limit:
Upper Limit:
40074 Total Number Read Only Multiplier: 1 Total number of generator set PC 2.x,
of Runs Offset: 0 runs. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967295

40075 Total Number Read Only Multiplier: 1 Total number of generator set PC 2.x,
of Runs Offset: 0 runs. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967295

A029X159 (Issue 19) 89 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40076 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076-
40092 for 17 char of this
string.
40077 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076-
40092 for 17 char of this
string.
40078 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076 -
40092 for 17 char of this
string.
40079 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076-
40092 for 17 char of this
string.

Copyright © 2017 Cummins Inc. 90 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40080 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076-
40092 for 17 char of this
string.
40081 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076-
40092 for 17 char of this
string.
40082 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076-
40092 for 17 char of this
string.
40083 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076-
40092 for 17 char of this
string.

A029X159 (Issue 19) 91 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40084 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076-
40092 for 17 char of this
string.
40085 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076-
40092 for 17 char of this
string.
40086 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076-
40092 for 17 char of this
string.
40087 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076-
40092 for 17 char of this
string.

Copyright © 2017 Cummins Inc. 92 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40088 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076-
40092 for 17 char of this
string.
40089 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076-
40092 for 17 char of this
string.
40090 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076-
40092 for 17 char of this
string.
40091 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076-
40092 for 17 char of this
string.

A029X159 (Issue 19) 93 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40092 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Size (bits): 144 Run Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40076-
40092 for 17 char of this
string.
40096 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.
40097 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.
40098 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.
40099 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.

Copyright © 2017 Cummins Inc. 94 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40100 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.
40101 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.
40102 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.
40103 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.
40104 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.

A029X159 (Issue 19) 95 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40105 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.
40106 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.
40107 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.
40108 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.
40109 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.

Copyright © 2017 Cummins Inc. 96 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40110 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.
40111 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.
40112 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Size (bits): 144 Start Attempts were reset.
This parameter is
Sign: C
READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
Upper Limit: implementation or the Real
time stamp will use 40096-
0112 for 17 char of this string.
40118 Utility L1N Read Only Multiplier: 1 Utility L1N voltage PC 3.x
Voltage Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

40119 Utility L2N Read Only Multiplier: 1 Utility L2N voltage PC 3.x
Voltage Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 97 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40120 Utility L3N Read Only Multiplier: 1 Utility L3N voltage PC 3.x
Voltage Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40121 Utility LN Read Only Multiplier : 1 Utility Line to Neutral average PC3.X
Average Offset: 0 voltage
Voltage Size (bits): 16
Sign: U
Unit: Vac
Lower Limit: NA
Upper Limit: NA
40122 Utility L1L2 Read Only Multiplier: 1 Utility L1L2 voltage PC 3.x
Voltage Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40123 Utility L2L3 Read Only Multiplier: 1 Utility L2L3 voltage PC 3.x
Voltage Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40124 Utility L3L1 Read Only Multiplier: 1 Utility L3L1 voltage PC 3.x
Voltage Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40125 Utility LL Read Only Multiplier: 1 Utility Line to Line average PC 3.x
Average Offset: 0 voltage
Voltage Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 98 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40126 Utility L1 Read Only Multiplier: 1 Utility L1 current PC 3.x
Current Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:

40127 Utility L2 Read Only Multiplier: 1 Utility L2 current PC 3.x


Current Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40128 Utility L3 Read Only Multiplier: 1 Utility L3 current PC 3.x
Current Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
Offset: 0
40129 Utility Read Only Multiplier : 1 Utility average current PC 3.x
Average Offset: 0
Current Size (bits): 16
Sign: U
Unit: Amps
Lower Limit: NA
Upper Limit: NA
Default: NA
40131 Utility L1 kW Read Only Multiplier: 1 Utility L1 kW PC 3.x
Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 99 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40132 Utility L2 kW Read Only Multiplier: 1 Utility L2 kW PC 3.x
Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:
40133 Utility L3 kW Read Only Multiplier: 1 Utility L3 kW PC 3.x
Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:
40134 Utility Total Read Only Multiplier: 1 Utility total kW PC 3.x
kW Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:
40135 Utility L1 Read Only Multiplier: 1 Utility L1 kVAR PC 3.x
kVAR Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:

40136 Utility L2 Read Only Multiplier: 1 Utility L2 kVAR PC 3.x


kVAR Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:
40137 Utility L3 Read Only Multiplier: 1 Utility L3 kVAR PC 3.x
kVAR Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 100 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40138 Utility Total Read Only Multiplier: 1 Utility total kVAR PC 3.x
kVAR Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:
40139 Utility Total Read Only Multiplier: 0.01 Utility total power factor PC 3.x
Power Factor Offset: 0
Size (bits): 8
Sign: S
Unit: PF
Lower Limit:
Upper Limit:
40140 Utility L1 kVA Read Only Multiplier: 1 Utility L1 kVA PC 3.x
Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
40141 Utility L2 kVA Read Only Multiplier: 1 Utility L2 kVA PC 3.x
Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
40142 Utility L3 kVA Read Only Multiplier: 1 Utility L3 kVA PC 3.x
Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
40143 Utility Total Read Only Multiplier: 1 Utility total kVA PC 3.x
kVA Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 101 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40144 Utility Read Only Multiplier: 0.001 Utility line frequency PC 3.x
Frequency Offset: 0
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
40145 Utility Read Only Multiplier: 0.001 Utility line frequency PC 3.x
Frequency Offset: 0
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
40146 Utility Total Read Only Multiplier: 1 Utility total negative kWh PC 3.x
Negative kWh Offset: 0 accumulation
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:

40147 Utility Total Read Only Multiplier: 1 Utility total negative kWh PC 3.x
Negative kWh Offset: 0 accumulation
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:
40148 Utility Total Read Only Multiplier: 1 Utility total positive kWh PC 3.x
Positive kWh Offset: 0 accumulation
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:
40149 Utility Total Read Only Multiplier: 1 Utility total positive kWh PC 3.x
Positive kWh Offset: 0 accumulation
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 102 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40150 Utility Total Read Only Multiplier: 1 Utility total net kWh PC 3.x
Net kWh Offset: 0 accumulation
Size (bits): 32
Sign: S
Unit: kWh
Lower Limit:
Upper Limit:
40151 Utility Total Read Only Multiplier: 1 Utility total net kWh PC 3.x
Net kWh Offset: 0 accumulation
Size (bits): 32
Sign: S
Unit: kWh
Lower Limit:
Upper Limit:
40152 Utility Total Read Only Multiplier: 1 Utility total negative kVARh PC 3.x
Negative Offset: 0 accumulation
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:
40153 Utility Total Read Only Multiplier: 1 Utility total negative kVARh PC 3.x
Negative Offset: 0 accumulation
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:
40154 Utility Total Read Only Multiplier: 1 Utility total positive kVARh PC 3.x
Positive Offset: 0 accumulation
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:
40155 Utility Total Read Only Multiplier: 1 Utility total positive kVARh PC 3.x
Positive Offset: 0 accumulation
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 103 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40156 Utility Total Read Only Multiplier: 1 Utility total net kVARh PC 3.x
Net kVARh Offset: 0 accumulation
Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit:
Upper Limit:
40157 Utility Total Read Only Multiplier: 1 Utility total net kVARh PC 3.x
Net kVARh Offset: 0 accumulation
Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit:
Upper Limit:
40158 Genset Bus Read Only Multiplier: 1 Generator set Bus L1N PC 3.x
L1N Voltage Offset: 0 voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

40159 Genset Bus Read Only Multiplier: 1 Generator set Bus L2N PC 3.x
L2N Voltage Offset: 0 voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40160 Genset Bus Read Only Multiplier: 1 Generator set Bus L3N PC 3.x
L3N Voltage Offset: 0 voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40161 Genset Bus Read Only Multiplier : 1 Genset Bus Line to Neutral PC 3.x
LN Average Offset: 0 average voltage
Voltage Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 104 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40162 Genset Bus Read Only Multiplier: 1 Generator set Bus L1L2 PC 3.x
L1L2 Voltage Offset: 0 voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40163 Genset Bus Read Only Multiplier: 1 Generator set Bus L2L3 PC 3.x
L2L3 Voltage Offset: 0 voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40164 Genset Bus Read Only Multiplier: 1 Generator set Bus L3L1 PC 3.x
L3L1 Voltage Offset: 0 voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40165 Genset Bus Read Only Multiplier: 1 Generator set Bus Line to PC 3.x
LL Average Offset: 0 Line average voltage
Voltage Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40166 Genset Bus Read Only Multiplier: 1 Generator set Bus L1 current PC 3.x
L1 Current Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit: 0
Upper Limit: 65530
40167 Genset Bus Read Only Multiplier: 1 Generator set Bus L2 current PC 3.x
L2 Current Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 105 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40168 Genset Bus Read Only Multiplier: 1 Generator set Bus L3 current PC 3.x
L3 Current Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40169 Genset Bus Read Only Multiplier : 1 Genset Bus Average current PC3.X
Average Offset: 0
Current Size (bits): 16
Sign: U
Unit: Amps
Lower Limit: NA
Upper Limit: NA
40171 Genset Bus Read Only Multiplier: 1 Generator set Bus L1 kW PC 3.x
L1 kW Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit: -32768
Upper Limit: 32762
40172 Genset Bus Read Only Multiplier: 1 Generator set Bus L2 kW PC 3.x
L2 kW Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit: -32768
Upper Limit: 32762
40173 Genset Bus Read Only Multiplier: 1 Generator set Bus L3 kW PC 3.x
L3 kW Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:
40174 Genset Bus Read Only Multiplier: 1 Generator set Bus total kW PC 3.x
Total kW Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 106 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40175 Genset Bus Read Only Multiplier: 1 Generator set bus L1 kVar PC 3.x
L1 kVAR Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit: -32678
Upper Limit: 32672
40176 Genset Bus Read Only Multiplier: 1 Generator set bus L2 kVAR PC 3.x
L2 kVAR Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit: -32678
Upper Limit: 32672
40177 Genset Bus Read Only Multiplier: 1 Generator set bus L3 kVAR PC 3.x
L3 kVAR Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:
40178 Genset Bus Read Only Multiplier: 1 Generator set bus total kVAR PC 3.x
Total kVAR Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:
40179 Genset Bus Read Only Multiplier: 0.01 Generator set Bus Total PC 3.x
Total Power Offset: 0 power factor
Factor Size (bits): 8
Sign: S
Unit: PF
Lower Limit:
Upper Limit:
40180 Genset Bus Read Only Multiplier: 1 Generator set Bus L1 kVA PC 3.x
L1 kVA Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 107 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40181 Genset Bus Read Only Multiplier: 1 Generator set Bus L2 kVA PC 3.x
L2 kVA Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
40182 Genset Bus Read Only Multiplier: 1 Generator set Bus L3 kVA PC 3.x
L3 kVA Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
40183 Genset Bus Read Only Multiplier: 1 Generator set bus total kVA PC 3.x
Total kVA Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:

Addr. Parameter Access Specifications Description Control


40184 Genset Bus Read Only Multiplier: 0.001 Generator set bus line PC 3.x
Frequency Offset: 0 frequency
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
40185 Genset Bus Read Only Multiplier: 0.001 Generator set bus line PC 3.x
Frequency Offset: 0 frequency
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
40186 Genset Bus Read Only Multiplier: 1 Generator set bus total PC 3.x
Total Offset: 0 negative kWh accumulation
Negative kWh Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 108 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40187 Genset Bus Read Only Multiplier: 1 Generator set bus total PC 3.x
Total Offset: 0 negative kWh accumulation
Negative kWh Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:
40188 Genset Bus Read Only Multiplier: 1 Generator set bus total PC 3.x
Total Positive Offset: 0 positive kWh accumulation
kWh Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:
40189 Genset Bus Read Only Multiplier: 1 Generator set bus total PC 3.x
Total Positive Offset: 0 positive kWh accumulation
kWh Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:
40190 Genset Bus Read Only Multiplier: 1 Generator set bus total net PC 3.x
Total Net Offset: 0 kWh accumulation
kWh Size (bits): 32
Sign: S
Unit: kWh
Lower Limit:
Upper Limit:
40191 Genset Bus Read Only Multiplier: 1 Generator set bus total net PC 3.x
Total Net Offset: 0 kWh accumulation
kWh Size (bits): 32
Sign: S
Unit: kWh
Lower Limit:
Upper Limit:
40192 Genset Bus Read Only Multiplier: 1 Generator set bus total PC 3.x
Total Offset: 0 negative kVARh accumulation
Negative Size (bits): 32
kVARh
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 109 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40193 Genset Bus Read Only Multiplier: 1 Generator set bus total PC 3.x
Total Offset: 0 negative kVARh accumulation
Negative Size (bits): 32
kVARh
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:
40194 Genset Bus Read Only Multiplier: 1 Generator set bus total PC 3.x
Total Positive Offset: 0 positive kVARh accumulation
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:
40195 Genset Bus Read Only Multiplier: 1 Generator set bus total PC 3.x
Total Positive Offset: 0 positive kVARh accumulation
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:
40196 Genset Bus Read Only Multiplier: 1 Generator set Bus total net PC 3.x
Total Net Offset: 0 kVARh accumulation
kVARh Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit:
Upper Limit:
40197 Genset Bus Read Only Multiplier: 1 Generator set Bus total net PC 3.x
Total Net Offset: 0 kVARh accumulation
kVARh Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit:
Upper Limit:
40198 Ground Read Only Multiplier: 0.1 Ground current PC 3.x
Current Offset: 0
Size (bits): 16
Sign: U
Unit: amp
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 110 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40199 Genset Read Only Multiplier: 0.01 Generator set Negative PC 3.x
Negative Offset: 0 Sequence Current as Percent
Sequence Size (bits): 16 of Standby Current Rating
Current %
Sign: U
Unit: %
Lower Limit:
Upper Limit:
40201 Coolant Read Only 0: PGBU Either PGBU(Onan) or PC 2.x,
Temperature 1: EBU EBU(Cummins) sensor. PC 3.x
Sensor Type
40207 Battery Read Only Multiplier: 0.001 The Battery Charger PC 2.x,
Charger Offset: 0 Alternator Flash Voltage after PC 3.x
Alternator Size (bits): 16 all scaling and validity
Flash Voltage checks.
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 35
40208 Battery 1 Read Only Multiplier : 0.01 Battery 1 Voltage measured PC 3.x
Voltage Offset: 0 through AUX101. Applicable
(Aux101) Size (bits): 16 when multiple batteries are
used.
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 3850
Default: NA
40209 Battery 2 Read Only Multiplier : 0.01 Battery 2 Voltage measured PC 3.x
Voltage Offset: 0 through AUX101. Applicable
(Aux101) Size (bits): 16 when multiple batteries are
used.
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 3850
Default: NA
40210 External Read Only Multiplier: 0.01 Monitor point for the external PC 2.x,
Speed Bias Offset: 0 speed bias input. PC 3.x
Input Size (bits): 16
Sign: S
Unit: %
Lower Limit: -100
Upper Limit: 100

A029X159 (Issue 19) 111 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40211 External Read Only Multiplier: 0.01 Monitor point for the external PC 2.x,
Voltage Bias Offset: 0 voltage bias input. PC 3.x
Input Size (bits): 16
Sign: S
Unit: %
Lower Limit: -100
Upper Limit: 100
40212 Battery 3 Read Only Multiplier : 0.01 Battery 3 Voltage measured PC 3.x
Voltage Offset: 0 through AUX101. Applicable
(Aux101) Size (bits): 16 when multiple batteries are
used.
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 3850
Default: NA
40213 Battery 4 Read Only Multiplier : 0.01 Battery 4 Voltage measured PC 3.x
Voltage Offset: 0 through AUX101. Applicable
(Aux101) Size (bits): 16 when multiple batteries are
used.
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 3850
Default: NA
40214 kVAR Load Read Only Multiplier : 0.01 EU scaled value for the kVAR PC 3.x
Setpoint Offset: 0 load setpoint
Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
40217 kVAR Load Read Only Multiplier : 0.01 EU Scaled value for the PC 3.x
Share Level Offset: 0 kVAR load share level analog
Size (bits): 16 input
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA

Copyright © 2017 Cummins Inc. 112 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40219 kW load Read Only Multiplier : 0.01 EU scaled value for the kW PC 3.x
setpoint Offset: 0 load setpoint
Size (bits): 16
Sign: S
Unit: %
Lower Limit:
Upper Limit: 125.01
Default: NA
40222 kW Load Read Only Multiplier : 0.01 EU Scaled value for the kW PC 3.x
Share Level Offset: 0 load share level analog input
Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
40224 kVAR Load Read Only Multiplier : 0.1 uA signal being injected into PC 3.x
Share Output Offset: 0 a 10K ohm resistor network
Predictor Size (bits): 16
Sign: S
Unit: uA
Lower Limit: NA
Upper Limit: NA
Default: NA
40225 KW Load Read Only Multiplier : 0.1 uA signal being injected into PC 3.x
Share Output Offset: 0 a 10K ohm resistor network
Predictor Size (bits): 16
Sign: S
Unit: uA
Lower Limit: NA
Upper Limit: NA
Default: NA
40226 Speed Bias Read Only Multiplier: 0.01 Configurable analog output PC 3.x
Output / Offset: 0 voltage output value
Configurable Size (bits): 16 (predicted)
Analog output
Sign: S
#1 Output
Predictor Unit: Vdc
Lower Limit: NA
Upper Limit: NA

A029X159 (Issue 19) 113 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40227 Voltage Bias Read Only Multiplier: 0.01 Configurable analog output PC 3.x
Output / Offset: 0 voltage output value
Configurable Size (bits): 16 (predicted)
Analog output
Sign: S
#2 Output
Predictor Unit: Vdc
Lower Limit:
Upper Limit:
40228 Amber Read Only 0: Inactive Engine Control System PC 2.x,
Warning 1: Active indicates a warning condition. PC 3.x
Lamp Status
40229 Barometric Read Only Multiplier: 0.1 Monitor point for the PC 2.x,
Absolute Offset: 0 Barometric Absolute PC 3.x
Pressure Size (bits): 16 Pressure. Displayed as
”Ambient Pressure” in the
Sign: U
HMI.
Unit: psi
Lower Limit:
Upper Limit:
40230 Boost Read Only Multiplier: 0.1 Monitor point for the Boost PC 2.x,
Pressure Offset: 0 Absolute Pressure PC 3.x
Size (bits): 16
Sign: U
Unit: psi
Lower Limit:
Upper Limit:
40231 CAN Datalink Read Only 0: Inactive Indicates the status of the PC 2.x,
Status 1: Active CAN datalink PC 3.x
2: Failed
40232 Crankcase Read Only Multiplier: 0.1 Monitor point for the PC 2.x,
Pressure Offset: 0 Crankcase Pressure. PC 3.x
Size (bits): 16
Sign: S
Unit: psi
Lower Limit: -35.67
Upper Limit: 38
40235 ECM Derate Read Only 0: No Derate Request Request made by the ECS for PC 2.x,
Request 1: Derate Request a reduction in load PC 3.x
2: Error
3: Don’t Care
40236 Engine Read Only 0: ECM Monitor point for the output of PC 2.x,
Application 1: Hydro-Mechanical the Engine application type. PC 3.x
Type Either ECM (CAN) or Hydro-
Mechanical.

Copyright © 2017 Cummins Inc. 114 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40237 Engine State Read Only 0: Stop ECS engine state indication PC 2.x,
1: Ventilation PC 3.x
2: Start
3: Run
4: Normal Shutdown
5: Emergency Shutdown
6: Error
7: Don’t Care
8: Rapid Start
9: Reserved
10: Reserved
11: Reserved
12: Reserved
13: Reserved
14: Reserved
15: Don’t Care / Take No
Action
40238 PGI Major Read Only Multiplier :1 Displays Power Generation PC 3.x
Version Offset: 0 Interface Major Version to
Size (bits): 8 which Engine Software is
complying
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 225
Default: NA
40239 PGI Minor Read Only Multiplier :1 Displays Power Generation PC 3.x
Version Offset: 0 Interface Minor Version to
Size (bits): 8 which Engine Software is
complying
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 225
Default: NA
40240 PGI Read Only Multiplier :1 Displays Power Generation PC 3.x
Informational Offset: 0 Interface Informational
Version Size (bits): 8 Version to which Engine
Software is complying
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 225
Default: NA

A029X159 (Issue 19) 115 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40242 Aftercooler Read Only Multiplier: 0.1 Monitor point for the PC 2.x,
Temperature Offset: 0 Aftercooler Temperature. PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -40
Upper Limit: 410
Default: NA
40243 Internal ECM Read Only Multiplier : 0.1 Internal temperature of the PC 3.x
Module 1 Offset: 0 engine electronic control
Temperature Size (bits): 16 module 1
Sign: S
Unit: degF
Lower Limit: NA
Upper Limit: NA
Default: NA
40244 Internal ECM Read Only Multiplier : 0.1 Internal temperature of the PC 3.x
Module 2 Offset: 0 engine electronic control
Temperature Size (bits): 16 module 2
Sign: S
Unit: degF
Lower Limit: NA
Upper Limit: NA
Default: NA
40245 Internal ECM Read Only Multiplier : 0.1 Internal temperature of the PC 3.x
Module 3 Offset: 0 engine electronic control
Temperature Size (bits): 16 module 3
Sign: S
Unit: degF
Lower Limit: NA
Upper Limit: NA
Default: NA
40246 Internal ECM Read Only Multiplier : 0.1 Internal temperature of the PC 3.x
Module 4 Offset: 0 engine electronic control
Temperature Size (bits): 16 module 4
Sign: S
Unit: degF
Lower Limit: NA
Upper Limit: NA
Default: NA

Copyright © 2017 Cummins Inc. 116 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40247 ECM Module Read Only Multiplier : 0.1 Engine Control Module 1 PC 3.x
1 Battery Offset: 0 Battery Voltage.
Voltage Size (bits): 16
Sign: U
Units: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
40248 ECM Module Read Only Multiplier : 0.1 Engine Control Module 2 PC 3.x
2 Battery Offset: 0 Battery Voltage.
Voltage Size (bits): 16
Sign: U
Units: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
40249 ECM Module Read Only Multiplier : 0.1 Engine Control Module 3 PC 3.x
3 Battery Offset: 0 Battery Voltage.
Voltage Size (bits): 16
Sign: U
Units: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
40250 ECM Module Read Only Multiplier : 0.1 Engine Control Module 4 PC 3.x
4 Battery Offset: 0 Battery Voltage.
Voltage Size (bits): 16
Sign: U
Units: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
40254 Fuel Supply Read Only Multiplier: 0.1 Monitor point for the Fuel PC 2.x,
Pressure Offset: 0 Supply Pressure. Displayed PC 3.x
Size (bits): 16 as ”Fuel Supply Pressure” in
the HMI.
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 145

A029X159 (Issue 19) 117 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40257 Intake Read Only Multiplier : 0.1 Monitor point for the Intake PC 2.x,
Manifold 4 Offset: 0 Manifold 4 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Units: degF
Lower Limit: -40
Upper Limit: 410
Default: NA
40258 Fuel Outlet Read Only Multiplier: 0.1 Monitor point for the Fuel PC 2.x,
Pressure Offset: 0 Outlet Pressure. Displayed as PC 3.x
Size (bits): 32 ”Fuel Rail Pressure” in the
HMI.
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 36404
40259 Fuel Outlet Read Only Multiplier: 0.1 Monitor point for the Fuel PC 2.x,
Pressure Offset: 0 Outlet Pressure. Displayed as PC 3.x
Size (bits): 32 ”Fuel Rail Pressure” in the
HMI.
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 36404
40260 Intake Read Only Multiplier: 0.1 Monitor point for the Intake PC 2.x,
Manifold 2 Offset: 0 Manifold 2 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -40
Upper Limit: 410
40261 Intake Read Only Multiplier: 0.1 Monitor point for the Intake PC 2.x,
Manifold 3 Offset: 0 Manifold 3 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -40
Upper Limit: 410
40264 Percent Read Only Multiplier: 1 Monitor point for the percent PC 2.x,
Engine Offset: 0 engine torque output and the PC 3.x
Torque/Duty Size (bits): 16 governor percent duty cycle
Cycle output when used with the
Sign: S
HM ECM
Unit: %
Lower Limit: -40
Upper Limit: 410

Copyright © 2017 Cummins Inc. 118 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40276 Post-Filter Oil Read Only Multiplier: 0.1 Monitor point for the Post- PC 2.x,
Pressure Offset: 0 Filter Oil Pressure PC 3.x
Size (bits): 16
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 145
40277 Pre-Filter Oil Read Only Multiplier: 0.1 Monitor point for the Pre-Filter PC 2.x,
Pressure Offset: 0 Oil Pressure PC 3.x
Size (bits): 16
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 145
40278 Configurable Read Only 0: Inactive Configurable Input #14 input PC 2.x,
Input #14 1: Active software state status. Gives PC 3.x
Switch software Inactive/Active state
40279 Turbocharger Read Only Multiplier: 1 Monitor point for the PC 2.x,
1 Speed Offset: 0 Turbocharger 1 Speed PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit: 0
Upper Limit: 257000
40280 Turbocharger Read Only Multiplier: 1 Monitor point for the PC 2.x,
1 Speed Offset: 0 Turbocharger 1 Speed PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit: 0
Upper Limit: 257000
40281 Turbocharger Read Only Multiplier: 0.1 Monitor point for the PC 2.x,
2 Boost Offset: 0 Turbocharger 2 Boost PC 3.x
Pressure Size (bits): 32 Pressure
Sign: U
Unit: psi
Lower Limit:
Upper Limit:
40282 Water in Fuel Read Only 0: No Water in Fuel Indication PC 2.x,
Indicator 1: Yes PC 3.x

A029X159 (Issue 19) 119 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40282 Water in Fuel Read Only 0: Off The controller mode PC 2.x,
Indicator 1: Ready PC 3.x
2: Setup
3: Starting
4: Idle
5: Rated
6: Stop Normal
7: Stop Emergency
8: Factory Test
9: Wait to Power Down
40285 Power Down Read Only Multiplier: 1 Timer to count down the time PC 2.x,
Mode Timer Offset: 0 before the control goes to PC 3.x
Size (bits): 16 sleep
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 600
40286 Setup Mode Read Only Multiplier : 1 Time spent in Setup Mode. PC 2.x
Timer Offset: 0 PC3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: NA
Upper Limit: NA
Default: NA
40287 Tool Wake-up Read only 0: Inactive The control output to the PC 2.x
Command 1: Active common wake-up line to PC 3.x
wake up other devices
40289 Active Read only 0: None Indicates the currently active PC 2.x
Schedule 1: Program 1 scheduler program or PC 3.x
2: Program 2 exception.
3: Program 3
4: Program 4
5: Program 5
6: Program 6
7: Program 7
8: Program 8
9: Program 9
10: Program 10
11: Program 11
12: Program 12
13: Exception 1
14: Exception 2

Copyright © 2017 Cummins Inc. 120 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40290 Controller On Read Only Multiplier : 1 Controller ON time in PC 2.x
Time Offset: 0 seconds. Upper limit is 136 PC 3.x
Size (bits): 32 years.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 4294967295
Default: NA
40291 Controller On Read Only Multiplier : 1 Controller ON time in PC 2.x
Time Offset: 0 seconds. Upper limit is 136 PC 3.x
Size (bits): 32 years.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 4294967295
Default: NA
40298 Runs Since Read Only Multiplier: 1 Number of runs since the last PC 2.x,
Reset Offset: 0 reset. Upper limit is 2^32 -1. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290
40299 Runs Since Read Only Multiplier: 1 Number of runs since the last PC 2.x,
Reset Offset: 0 reset. Upper limit is 2^32 -1. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290
40300 Remote Start Read/Write 0: Inactive Modbus Remote Start PC 2.x,
Switch(Modb 1: Active PC 3.x
us)
40301 Fault Reset Read/Write 0: Inactive Modbus fault reset. PC 2.x,
(Modbus) 1: Active PC 3.x
40320 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 121 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40321 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40322 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40323 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40324 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40325 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40326 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 122 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40327 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40328 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40329 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40330 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40331 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40332 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 123 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40333 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40334 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40335 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40336 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

40337 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x


No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40338 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 124 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40339 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40340 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40341 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40342 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40343 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40344 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 125 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40345 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40346 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40347 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40348 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40349 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40350 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 126 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40351 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40352 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40353 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40354 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 operator panel when this fault
becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40355 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40356 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 127 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40357 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40358 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40359 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40360 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40361 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40362 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 128 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40363 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40364 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40365 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40366 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40367 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40368 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 129 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40369 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40370 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40371 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40372 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40373 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40374 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 130 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40375 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40376 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40377 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40378 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40379 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Size (bits): 168 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40422 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 2.x
Bitmap 23 Offset: 0 interface. PC 3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA

A029X159 (Issue 19) 131 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40423 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 2.x
Bitmap 24 Offset: 0 interface. PC 3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40424 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 2.x
Bitmap 25 Offset: 0 interface. PC3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40425 Event Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 2.x
Bitmap 2 Offset: 0 interface. PC 3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40426 Event Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 2.x
Bitmap 3 Offset: 0 interface. PC 3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40427 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 2.x
Bitmap 26 Offset: 0 interface. PC 3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

Copyright © 2017 Cummins Inc. 132 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40428 Fault Status Read Only Multiplier : 1 16 bit event bitmap for PC 3.x
Bitmap 32 Offset: 0 Modbus interface and Tier4F
Size (bits): 16 16 bit Diesel Fault Bitmap for
Modbus interface
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40430 Event Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 2.x
Bitmap 1 Offset: 0 interface. PC 3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40431 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 1 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40432 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 2 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40433 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 3 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 19) 133 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40434 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 4 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40435 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 5 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40436 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 6 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40437 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 7 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40438 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 8 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

Copyright © 2017 Cummins Inc. 134 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40439 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 9 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40440 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
10 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40441 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
11 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40442 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
12 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40443 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
13 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 19) 135 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40444 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
14 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40445 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
15 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40446 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
16 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40447 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
17 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40448 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
18 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

Copyright © 2017 Cummins Inc. 136 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40449 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
19 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40450 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
20 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40451 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
21 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40452 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
22 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40453 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
23 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 19) 137 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40454 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
24 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40455 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
25 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40456 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
26 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40457 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
27 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40458 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
28 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

Copyright © 2017 Cummins Inc. 138 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40459 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
29 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40460 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
30 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40461 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
31 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40462 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
32 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40463 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
33 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 19) 139 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40464 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
34 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40465 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
35 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40466 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
36 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40467 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
37 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40468 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
38 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

Copyright © 2017 Cummins Inc. 140 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40469 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
39 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40470 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
40 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40471 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
41 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40472 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
42 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40473 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
43 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 19) 141 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40474 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
44 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40475 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
45 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40476 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
46 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40477 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
47 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40478 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
48 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

Copyright © 2017 Cummins Inc. 142 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40479 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
49 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40480 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
50 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40481 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
51 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40482 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
52 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40483 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
53 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 19) 143 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40484 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
54 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40485 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
55 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40486 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
56 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40487 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
57 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40488 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
58 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

Copyright © 2017 Cummins Inc. 144 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40489 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
59 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40490 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
60 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40491 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
61 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40492 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
62 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40493 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
63 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 19) 145 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40494 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
64 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40495 AT Fault Read Only Multiplier : 1 16 bit AT Fault Bitmap for PC 3.x
Status Bitmap Offset: 0 Modbus interface
1 Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40496 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 3.x
Bitmap 27 Offset: 0 interface
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40497 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 3.x
Bitmap 28 Offset: 0 interface
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40498 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 3.x
Bitmap 29 Offset: 0 interface
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA

Copyright © 2017 Cummins Inc. 146 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40499 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 3.x
Bitmap 30 Offset: 0 interface
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40500 Low Fuel Read Only 0: Inactive Low Fuel input software state PC 2.x,
Switch 1: Active status. Gives software PC 3.x
Inactive/Active state
40501 Low Read Only 0: Inactive This is the status of the PC 2.x,
Fuel/Configur 1: Active Configurable Input #6. PC 3.x
able Input #6
Switch
40503 Differential Read Only 0: Inactive Differential fault trip monitor PC 3.x
Fault Trip 1: Active point
2: Reserved
3: Not Available
40504 Master First Read Only 0: Inactive This is the status of the PC 3.x
Start Input A 1: Active Master First Start A input

40505 Fire Trip Read Only 0: Inactive Fire trip monitor point. PC 3.x
1: Active
40506 Master First Read Only 0: Inactive Master First Start Input B PC 3.x
Start Input B 1: Active input software state status.
Switch Gives software Inactive/Active
state.
40507 Masterless Read Only 0: Inactive Masterless Load Demand PC 3.x
Load 1: Active Enable Switch function output
Demand status. Gives software
Enable Inactive/Active state
Switch
40508 Predictive Read Only 0: Inactive Predictive Load Enable PC 3.x
Load Enable 1: Active Switch function output status.
Switch Gives software Inactive/Active
state
40509 PTC Mode Read Only 0: Inactive PTC Mode Switch function PC 3.x
Switch 1: Active output status. Gives software
Inactive/Active state
40510 Extended Read Only 0: Inactive This is the status of the PC 3.x
Parallel/Confi 1: Active Configurable Input #32.
gurable Input
#32 Switch

A029X159 (Issue 19) 147 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40511 Ramp Read Only 0: Load Ramp Load/Unload input PC 3.x
Load/Unload 1: Unload software state status
Switch
40512 Remote E- Read Only 0: Inactive Remote E–stop input PC 2.x,
stop Switch 1: Active software state status. Gives PC 3.x
software Inactive/Active state
40513 Remote Start Read Only 0: Inactive Remote Start input software PC 2.x,
Switch 1: Active state status. Gives software PC 3.x
Inactive/Active state
40514 Retransfer Read Only 0: Inactive Retransfer Inhibit input PC 3.x
Inhibit Switch 1: Active software state status. Gives
software Inactive/Active state
40515 Retransfer Read Only 0: Inactive This is the status of the PC 3.x
Inhibit/Config 1: Active Configurable Input #21.
urable Input
#21 Switch
40516 Rupture Read Only 0: Inactive Rupture Basin input software PC 2.x,
Basin Switch 1: Active state status. Gives software PC 3.x
Inactive/Active state
40517 Rupture Read Only 0: Inactive This is the status of the PC 2.x,
Basin/Configu 1: Active Configurable Input #12. PC 3.x
rable Input
#12 Switch
40518 Speed Droop Read Only 0: Inactive Monitors the Speed Droop PC 2.x,
Enable 1: Active Enable Switch function; PC 3.x
Switch Inactive or Active state
40519 Start Type Read Only 0: Inactive Start Type input software PC 2.x,
Switch 1: Active state status. Gives software PC 3.x
Inactive/Active state
40520 Sync Enable Read Only 0: Inactive Sync Enable input software PC 3.x
Switch 1: Active state status. Gives software
Inactive/Active state
40521 Sync Read Only 0: Inactive This is the status of the PC 3.x
Enable/Confi 1: Active Configurable Input #30.
gurable Input
#30 Switch
40522 Tool Wakeup Read Only 0: Inactive Tool Wake-up input software PC 2.x,
Switch 1: Active state status. Gives software PC 3.x
Inactive/Active state
40523 Transfer Read Only 0: Inactive Transfer Inhibit input software PC 3.x
Inhibit Switch 1: Active state status. Gives software
Inactive/Active state
40524 Transfer Read Only 0: Inactive This is the status of the PC 3.x
Inhibit/Config 1: Active Configurable Input #20.
urable Input
#20 Switch

Copyright © 2017 Cummins Inc. 148 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40525 Utility CB Read Only 0: Inactive This is the status of the PC 3.x
Inhibit/Config 1: Active Configurable Input #25.
urable Input
#25 Switch
40526 Utility CB Pos Read Only 0: Inactive This is the status of the PC 3.x
B/Configurabl 1: Active Configurable Input #23.
e Input #23
Switch
40527 Utility CB Read Only 0: Inactive This is the status of the PC 3.x
Tripped/Confi 1: Active Configurable Input #24.
gurable Input
#24 Switch
40528 Utility Single Read Only 0: Inactive This is the status of the PC 3.x
Mode 1: Active Configurable Input #29.
Verify/Config
urable Input
#29 Switch
40529 Utility CB Read Only 0: Inactive Utility CB Inhibit input PC 3.x
Inhibit Switch 1: Active software state status. Gives
software Inactive/Active state
40530 Utility CB Pos Read Only 0: Inactive Utility CB Pos A input PC 3.x
A Switch 1: Active software state status. Gives
software Inactive/Active state
40531 Utility CB Pos Read Only 0: Inactive Utility CB Pos B input PC 3.x
B Switch 1: Active software state status. Gives
software Inactive/Active state
40532 Utility CB Read Only 0: Inactive Utility CB Tripped input PC 3.x
Tripped 1: Active software state status. Gives
Switch software Inactive/Active state
40533 Utility Single Read Only 0: Inactive Utility Single Mode Verify PC 3.x
Mode Verify 1: Active input software state status.
Switch Gives software Inactive/Active
state
40534 Voltage Read Only 0: Inactive Voltage Droop Enable Switch PC 2.x,
Droop Enable 1: Active function output status. Gives PC 3.x
Switch software Inactive/Active state.
40535 Configurable Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Output #1 1: Active is Inactive or Active PC 3.x
Status
40536 Configurable Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Output #2 1: Active is Inactive or Active PC 3.x
Status
40537 Configurable Read Only 0: Inactive Indicates if the output’s status PC 3.x
Output #20 1: Active is Inactive or Active
Status

A029X159 (Issue 19) 149 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40538 Configurable Read Only 0: Inactive Indicates if the output’s status PC 3.x
Output #21 1: Active is Inactive or Active
Status
40539 Configurable Read Only 0: Inactive Indicates if the output’s status PC 3.x
Output #22 1: Active is Inactive or Active
Status
40540 Configurable Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Output #3 1: Active is Inactive or Active PC 3.x
Status
40541 Configurable Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Output #4 1: Active is Inactive or Active PC 3.x
Status
40542 Delayed Off / Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Configurable 1: Active is Inactive or Active PC 3.x
Output #10
Status
40543 Fuel Shutoff Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Status 1: Active is Inactive or Active PC 3.x
40545 Genset CB Read Only 0: Inactive Indicates if the output’s status PC 3.x
Open Status 1: Active is Inactive or Active

40546 Hold Power Read Only 0: Inactive Indicates if the output’s status PC 2.x,
On Driver 1: Active is Inactive or Active PC 3.x
Status
40547 Keyswitch Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Status 1: Active is Inactive or Active PC 3.x
40548 KW/kVAR Read Only 0: Inactive Indicates if the output’s status PC 3.x
Load Share 1: Active is Inactive or Active
Relay Status
40549 Load Dump / Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Configurable 1: Active is Inactive or Active PC 3.x
Output #11
Status
40550 Local Status / Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Configurable 1: Active is Inactive or Active PC 3.x
Output #7
Status
40551 Master First Read Only 0: Inactive Indicates if the output’s status PC 3.x
Start Output 1: Active is Inactive or Active
Status
40552 Oil Priming Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Pump / 1: Active is Inactive or Active PC 3.x
Configurable
Output #6
Status

Copyright © 2017 Cummins Inc. 150 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40553 Ready To Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Load 1: Active is Inactive or Active PC 3.x
/Configurable
Output #5
Status
40554 Run Relay #1 Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Status 1: Active is Inactive or Active PC 3.x
40555 Run Relay #2 Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Status 1: Active is Inactive or Active PC 3.x
40556 Speed/Voltag Read Only 0: Inactive Indicates if the output’s status PC 3.x
e Bias Relay 1: Active is Inactive or Active
Status
40557 Starter Status Read Only 0: Inactive Indicates if the output’s status PC 2.x,
1: Active is Inactive or Active PC 3.x
40558 Tool Wake-up Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Driver Status 1: Active is Inactive or Active PC 3.x
40559 Utility CB Read Only 0: Inactive Indicates if the output’s status PC 3.x
Close Status 1: Active is Inactive or Active

40560 Utility CB Read Only 0: Inactive Indicates if the output’s status PC 3.x
Open Status 1: Active is Inactive or Active

40561 Common Read Only 0: Inactive The status of the Common PC 2.x,
Alarm Fault 1: Active Alarm Fault PC 3.x
Status
40562 Common Read Only 0: Inactive The status of the common PC 2.x,
Shutdown 1: Active shutdown command PC 3.x
Command
40563 Common Read Only 0: Inactive The status of the Common PC 2.x,
Shutdown 1: Active Shutdown Event PC 3.x
Event Status
40564 Common Read Only 0: Inactive The status of the common PC 3.x
Shutdown 1: Active shutdown w/Cooldown
w/Cooldown command
Command
40565 Common Read Only 0: Inactive The status of the Common PC 2.x,
Warning 1: Active Warning Event PC 3.x
Event Status
40566 Delayed Read Only 0: Inactive Monitor point for the Delayed PC 2.x,
Shutdown 1: Active shutdown flag. PC 3.x
Flag

A029X159 (Issue 19) 151 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40567 Delayed Read Only Multiplier : 0.1 Monitor point for the Delayed PC 2.x,
Shutdown Offset: 0 shutdown timer. PC 3.x
Timer Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: 0
Upper Limit: 3
Default: NA
40568 Derate Read Only Multiplier : 1 The requested % derate from PC 2.x
Request Offset: 0 the derate request logic. PC 3.x
Size (bits): 8
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 100
Default: NA
40569 Fault Read Only 0: Inactive The status of the Fault PC 2.x,
Detection 1: Active Detection Reset logic. PC 3.x
Reset
40570 Fault Reset Read Only 0: Inactive One shot due to fault reset PC 2.x,
Command 1: Active switch being active. PC 3.x
40571 Remote Read Only 0: Inactive Becomes active when a PC 2.x,
Shutdown 1: Active remote fault reset signal has PC 3.x
Fault Reset been initiated.
Signal
40572 Shutdown Read Only 0: Inactive The status of the Shutdown PC 2.x,
Fault Reset 1: Active Fault reset logic. PC 3.x
40573 Battle Short Read Only 0: Inactive Monitor point indicating the PC 2.x,
Flag 1: Active enabled/disabled status of the PC 3.x
battle short function
40574 Auto Read Only 0: Not Auto The output of the Auto PC 2.x,
Command 1: Auto Command OR logic PC 3.x
40575 Auto Read Only Multiplier : 1 Bitmask to show the inputs to PC 2.x,
Command Offset: 0 the Command output which PC 3.x
Inputs Size (bits): 8 are currently on
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
40576 AVR Read Only 0: Voltage The operational mode of the PC 2.x,
Regulation 1: Current AVR as a voltage or a current PC 3.x
Mode regulator

Copyright © 2017 Cummins Inc. 152 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40577 Base Read Only Multiplier: 0.001 Provides a point to monitor PC 2.x,
Frequency Offset: 0 the base frequency PC 3.x
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
40578 Base Read Only Multiplier: 0.001 Provides a point to monitor PC 2.x,
Frequency Offset: 0 the base frequency PC 3.x
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
40579 Battery Read Only Multiplier : 0.1 Time spent while the charger PC 2.x,
Charging Offset: 0 is sensed as failed PC 3.x
Fault Size (bits): 16
Integrator
Sign: U
Unit: Hz
Lower Limit: 0
Upper Limit: 300
Default: NA
40580 Control Read Only 0: Off Current position of the PC 2.x,
Switch 1: Manual generator set switch panel PC 3.x
Position 2: Auto Off-Run-Auto switch as seen
by the generator set control.
SEE ALSO ADDRESS
40010.
NOTE: Both address 40580
and 40010 show the same
information however the
specification for each is
different.
40581 Controlled Read /Write 0: Inactive Indicates status of the PC 3.x
Shutdown 1: Pending controlled shutdown logic
Status 2: Shutdown
40582 Crank Read Only 0: False Monitor Point indicates if PC 2.x,
Allowed 1: True Cranking is Allowed by the PC 3.x
Prelube State Machin

A029X159 (Issue 19) 153 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40583 Dead Battery Read Only Multiplier : 1 Tracks the number of crank PC 2.x,
Prevention Offset: 0 attempts in order to limit the PC 3.x
Counter Size (bits): 8 attempts when the battery is
so low that the control resets
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 250
Default: NA
40584 Delayed Off Read Only 0: Inactive The status of the delayed run PC 2.x,
Command 1: Active command off logic. PC 3.x
2: Reserved
3: Not Available
40586 Excitation Read Only 0: Disabled Shows the enable status of PC 2.x,
State 1: Enabled the excitation enabled = PC 3.x
regulator on.
40587 Exercise Read Only 0: Inactive The output of the Exercise PC 2.x,
Command 1: Active Command OR logic PC 3.x
2: Reserved
3: Not Available
40588 Exercise Read Only Multiplier : 1 Bitmask to show the inputs to PC 2.x,
Command Offset: 0 the Command output which PC 3.x
Inputs Size (bits): 8 are currently on
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 250
Default: NA
40589 Exercise Read Only Multiplier: 0.1 Time remaining until exercise PC 2.x,
Time Offset: 0 stop sequence begins PC 3.x
Remaining Size (bits): 16
Sign: U
Unit: hours
Lower Limit: 0
Upper Limit: 25
40590 Extended Read Only 0: Stop The output of the Extended PC 2.x,
Parallel 1: Start Parallel Switch Command OR PC 3.x
Switch logic
Command

Copyright © 2017 Cummins Inc. 154 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40591 Extended Read Only Multiplier : 1 Bitmask to show the inputs to PC 3.x
Parallel Offset: 0 the Command output which
Switch Size (bits): 8 are currently on
Command
Sign: U
Inputs
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
40592 Battle Short Read Only 0: Inactive Indicates status of battle short PC 2.x,
Command 1: Active inputs PC 3.x
40593 Shutdown Read Only 0: Inactive Indicates whether or not the PC 2.x,
Fault 1: Active genset will ignore non-critical PC 3.x
Override shutdown faults
40595 Final Read Only Multiplier: 0.001 The frequency scaled version PC 2.x,
Frequency Offset: 0 of the final speed reference PC 3.x
Reference Size (bits): 32
Sign: U
Unit: Hz
Lower Limit: 0
Upper Limit: 100
40596 Final Read Only Multiplier: 0.001 The frequency scaled version PC 2.x,
Frequency Offset: 0 of the final speed reference PC 3.x
Reference Size (bits): 32
Sign: U
Unit: Hz
Lower Limit: 0
Upper Limit: 100
40598 Fuel Shutoff Read Only 0: Inactive The result of the FSO driver PC 2.x,
Command 1: Active output command logic PC 3.x
2: Reserved
3: Not Available
40599 Genset Run Read Only 0: Emergency Stop Genset run / stop states PC 2.x,
Command 1: Stop PC 3.x
2: Load Demand Stop
3: Run
40600 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 155 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40601 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40602 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40603 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40604 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40605 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,


Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40606 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 156 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40607 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40608 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40609 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40610 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40611 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40612 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 157 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40613 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x, PC
Input #1 Fault Offset: 0 character string for use by the 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40614 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40615 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40620 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40621 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40622 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 158 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40623 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40624 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40625 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40626 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40627 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40628 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 159 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40629 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40630 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40631 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40632 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40633 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x, PC
Input #2 Fault Offset: 0 character string for use by the 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40634 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x, PC
Input #2 Fault Offset: 0 character string for use by the 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 160 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40635 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40640 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40641 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x, PC
Input #13 Offset: 0 character string for use by the 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40642 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x, PC
Input #13 Offset: 0 character string for use by the 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40643 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40644 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 161 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40645 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40646 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40647 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40648 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40649 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40650 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 162 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40651 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40652 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40653 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40654 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40655 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40660 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 163 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40661 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40662 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40663 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40664 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40665 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40666 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 164 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40667 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40668 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40669 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40670 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40671 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40672 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x, PC
Input #14 Offset: 0 character string for use by the 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 165 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40673 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40674 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40675 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Size (bits): 136 Operator panel when this
fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40709 Device Type Read Only Multiplier: 1 This Modbus register is PC 3.x
(Modlon) Offset: 0 created for Modlon register
Size (bits): 8 mapping. This parameter is
not associated with any
Sign: U
logical.
Unit:
Lower Limit:
Upper Limit:
40710 Control Read Only 0: Off This Modbus register is PC 3.x
Switch 1: Manual created for Modlon register
Position 2: Auto mapping.
(Modlon)
40711 Genset Run Read Only 0: Stop This Modbus register is PC 3.x
Sequence 1: Time Delay to Start created for Modlon register
State 2: Warmup at Idle mapping.
(Modlon)
3: Rated Freq and Voltage
4: Cooldown / Stop Delay
5: Cooldown at Idle
6: Rated to Idle Transition
Delay

Copyright © 2017 Cummins Inc. 166 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40712 Most Recent Read Only Multiplier: 1 This Modbus register is PC 3.x
Fault or Offset: 0 created for Modlon register
Warning Size (bits): 16 mapping. This Modbus
(Modlon) register is not associated with
Sign: U
any logical Address
Unit: Fault Code
Lower Limit:
Upper Limit:
40713 Fault Type Read Only 0: None This Modbus register is PC 3.x
(Modlon) 1: Warning created for Modlon register
2: Derate mapping. This Modbus
register is not associated with
3: Shutdown with cooldown
any logical address.
4: Shutdown
40714 Genset % Read Only Multiplier: 0.5 This Modbus register is PC 3.x
Standby Total Offset: 0 created for Modlon register
kW (Modlon) Size (bits): 16 mapping. Monitors the total
generator set standby KW
Sign: U
percentage output. Modbus
Unit: % has different multiplier than
Lower Limit: PCCnet. For Modlon use
Upper Limit: only, use multiplier 0.5 %

40715 Genset Total Read Only Multiplier: 1 This Modbus register is PC 3.x
kW (Modlon Offset: 0 created for Modlon register
GenStatus) Size (bits): 16 mapping. Generator set total
kW.
Sign: U
Unit: kW
Lower Limit:
Upper Limit:

Addr. Parameter Access Specifications Description Control


40716 NFPA 110 Read Only Multiplier: 1 This Modbus register is PC 3.x
Logical Offset: 0 created for Modlon register
Status Size (bits): 32 mapping. 32–bit number to
(Modlon) represent the status of the
Sign: U
NFPA 110 logical. See
Unit: NFPA110 bitmap. (See Table
Lower Limit: 3 on page 42).
Upper Limit:
40717 NFPA 110 Read Only Multiplier: 1 This Modbus register is PC 3.x
Logical Offset: 0 created for Modlon register
Status Size (bits): 32 mapping. 32-bit number to
(Modlon) represent the status of the
Sign: U
NFPA 110 logical. (See Table
Unit: 3 on page 42).
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 167 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40718 Genset Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Frequency Offset: 0 created for Modlon register
OP (Modlon) Size (bits): 16 mapping. Generator set
Frequency OP. Modbus has
Sign: U
different multiplier than
Unit: Hz PCCNet. For Modlon use
Lower Limit: only, Multiplier/Units = 0.1 Hz
Upper Limit:
40719 Genset Total Read Only Multiplier: 0.00005 This Modbus register is PC 3.x
Power Factor Offset: 0 created for Modlon register
(Modlon) Size (bits): 16 mapping. Generator set total
power factor (L1+L2+L3).
Sign: S
Modbus and PCCNet has
Unit: PF different multiplier value. For
Lower Limit: Modlon, use 0.00005 PF.
Upper Limit:
40720 Genset Total Read Only Multiplier: 1 This Modbus register is PC 3.x
kVA (Modlon) Offset: 0 created for Modlon register
Size (bits): 16 mapping. Generator set total
kVA
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
40721 Genset Total Read Only Multiplier: 1 This Modbus register is PC 3.x
kW (Modlon Offset: 0 created for Modlon register
GenACData) Size (bits): 16 mapping. Generator set total
kW in Gen AC Data.
Sign: S
Unit: kW
Lower Limit:
Upper Limit:
40722 Genset Total Read Only Multiplier: 1 This Modbus register is PC 3.x
kVAR Offset: 0 created for Modlon register
(Modlon) Size (bits): 16 mapping. Generator set total
kVAR
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:
40723 Genset L1L2 Read Only Multiplier: 1 This Modbus register is PC 3.x
Voltage Offset: 0 created for Modlon register
(Modlon) Size (bits): 16 mapping. Generator set L1L2
voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 168 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40724 Genset L2L3 Read Only Multiplier: 1 This Modbus register is PC 3.x
Voltage Offset: 0 created for Modlon register
(Modlon) Size (bits): 16 mapping. Generator set L2L3
voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40725 Genset L3L1 Read Only Multiplier: 1 This Modbus register is PC 3.x
Voltage Offset: 0 created for Modlon register
(Modlon) Size (bits): 16 mapping. Generator set L3L1
voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40726 Genset L1N Read Only Multiplier: 1 This Modbus register is PC 3.x
Voltage Offset: 0 created for Modlon register
(Modlon) Size (bits): 16 mapping. Generator set L1N
voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40727 Genset L2N Read Only Multiplier: 1 This Modbus register is PC 3.x
Voltage Offset: 0 created for Modlon register
(Modlon) Size (bits): 16 mapping. Generator set L2N
voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40728 Genset L3N Read Only Multiplier: 1 This Modbus register is PC 3.x
Voltage Offset: 0 created for Modlon register
(Modlon) Size (bits): 16 mapping. Generator set L3N
voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40729 Genset L1 Read Only Multiplier: 1 Monitors the generator set L1 PC 3.x
Current Offset: 0 current value.
(Modlon) Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 169 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40730 Genset L2 Read Only Multiplier: 1 Generator set L2 current PC 3.x
Current Offset: 0
(Modlon) Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40731 Genset L3 Read Only Multiplier: 1 This Modbus register is PC 3.x
Current Offset: 0 created for Modlon register
(Modlon) Size (bits): 16 mapping. Generator set L3
current
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40732 Genset % Read Only Multiplier: 0.5 This Modbus register is PC 3.x
Standby L1 Offset: 0 created for Modlon register
Current Size (bits): 16 mapping. Monitors the
(Modlon) generator set standby L1
Sign: U
current percentage output.
Unit: % Modbus and PCCNet have
Lower Limit: different multiplier value. For
Upper Limit: Modlon use 0.5 %

40733 Genset % Read Only Multiplier: 0.5 This Modbus register is PC 3.x
Standby L2 Offset: 0 created for Modlon register
Current Size (bits): 16 mapping. Monitors the
(Modlon) generator set standby L2
Sign: U
current percentage output.
Unit: % Modbus and PCCNet has
Lower Limit: different multiplier value. For
Upper Limit: Modlon, use 0.5 %

40734 Genset % Read Only Multiplier: 0.5 This Modbus register is PC 3.x
Standby L3 Offset: 0 created for Modlon register
Current Size (bits): 16 mapping. Monitors the
(Modlon) generator set standby L3
Sign: U
current percentage output.
Unit: % Modbus and PCCNet has
Lower Limit: different multiplier value. For
Upper Limit: Modlon use 0.5 %

40735 Battery Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Voltage Offset: 0 created for Modlon register
(Modlon) Size (bits): 16 mapping. Battery voltage
value. Modbus and PCCNet
Sign: S
has different multiplier value.
Unit: Vdc For Modlon use 0.1volts
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 170 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40736 Oil Pressure Read Only Multiplier: 0.1 This Modbus register is PC 3.x
(Modlon) Offset: 0 created for Modlon register
Size (bits): 16 mapping. Monitor point for the
Oil Pressure. Modbus and
Sign: U
PCCNet have different
Unit: kPa multiplier value. For Modlon,
Lower Limit: use 0.1 KPA
Upper Limit:
40737 Oil Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Temperature Offset: 0 created for Modlon register
(Modlon) Size (bits): 16 mapping. Monitor point for the
Oil Temperature. Modbus and
Sign: S
PCCNet has different
Unit: degK multiplier value. For Modlon
Lower Limit: use 0.1 deg Kelvin
Upper Limit:
40738 Coolant Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Temperature Offset: 0 created for Modlon register
(Modlon) Size (bits): 16 mapping. Monitor point for the
Coolant Temperature.
Sign: S
Modbus and PCCNet has
Unit: degK different multiplier value. For
Lower Limit: Modlon, use 0.1deg Kelvin.
Upper Limit:
40739 Intake Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Manifold Offset: 0 created for Modlon register
Temperature Size (bits): 16 mapping. To monitor Intake
(Modlon) Manifold Temperature.
Sign: S
Modbus and PCCNet has
Unit: degK different multiplier value. For
Lower Limit: -40 Modlon, use 0.1 deg Kelvin
Upper Limit: 410
40740 Fuel Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Temperature Offset: 0 created for Modlon register
(Modlon) Size (bits): 16 mapping. Monitor point for the
Fuel Temperature. Modbus
Sign: S
and PCCNet has different
Unit: degK multiplier value. For Modlon,
Lower Limit: -40 use 0.1 deg Kelvin.
Upper Limit: 410
40741 Fuel Rate Read Only Multiplier: 0.01 This Modbus register is PC 3.x
(Modlon) Offset: 0 created for Modlon register
Size (bits): 16 mapping. Monitor point for the
Fuel Rate. Modbus and
Sign: U
PCCNet has different
Unit: gal/hr multiplier value. For Modlon,
Lower Limit: use 0.01 gph
Upper Limit:

A029X159 (Issue 19) 171 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40742 Average Read Only Multiplier: 1 This Modbus register is PC 3.x
Engine Offset: 0 created for Modlon register
Speed Size (bits): 16 mapping. Monitor point for the
(Modlon) Average Engine Speed.
Sign: U
Modbus and PCCNet have
Unit: RPM different multiplier value. For
Lower Limit: Modlon, use 1 RPM.
Upper Limit:
40743 Total Number Read Only Multiplier: 1 This Modbus register is PC 3.x
of Runs Offset: 0 created for Modlon register
(Modlon) Size (bits): 32 mapping. Total number of
generator set runs.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967295
40744 Engine Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Running Time Offset: 0 created for Modlon register
(Modlon) Size (bits): 16 mapping. Total engine run
time. Modbus has different
Sign: U
multiplier than PCCNet. For
Unit: seconds Modbus, use 0.1 sec
Lower Limit:
Upper Limit:
40745 Engine Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Running Time Offset: 0 created for Modlon register
(Modlon) Size (bits): 16 mapping. Total engine run
time. Modbus has different
Sign: U
multiplier than PCCNet. For
Unit: seconds Modbus, use 0.1 sec
Lower Limit:
Upper Limit:
40746 Genset Total Read Only Multiplier: 1 This Modbus register is PC 3.x
Net kWh Offset: 0 created for Modlon register
(Modlon) Size (bits): 32 mapping. Generator set total
net kWh accumulation
Sign: S
Unit: kWh
Lower Limit: -2147483648
Upper Limit: 2147483643
40747 Genset Total Read Only Multiplier: 1 This Modbus register is PC 3.x
Net kWh Offset: 0 created for Modlon register
(Modlon) Size (bits): 32 mapping. Generator set total
net kWh accumulation
Sign: S
Unit: kWh
Lower Limit: -2147483648
Upper Limit: 2147483643

Copyright © 2017 Cummins Inc. 172 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40748 Total Fuel Read Only Multiplier: 0.01 This Modbus register is PC 3.x
Consumption Offset: 0 created for Modlon register
(Modlon) Size (bits): 32 mapping. Total fuel
consumption since start of
Sign: U
engine. Modbus and PCCNet
Unit: gallons has different multiplier value.
Lower Limit: For Modlon, use 0.01 Gallons
Upper Limit:
40749 Total Fuel Read Only Multiplier: 0.01 This Modbus register is PC 3.x
Consumption Offset: 0 created for Modlon register
(Modlon) Size (bits): 32 mapping. Total fuel
consumption since start of
Sign: U
engine. Modbus and PCCNet
Unit: gallons has different multiplier value.
Lower Limit: For Modlon, use 0.01 Gallons
Upper Limit:
40750 Utility/Genset Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Bus Offset: 0 created for Modlon register
Frequency Size (bits): 16 mapping. Utility line
(Modlon) frequency or Generator set
Sign: U
Bus Frequency depending on
Unit: Hz Paralleling Application.
Lower Limit: Modbus and PCCNet has
Upper Limit: different multiplier value. For
Modlon, use 0.1 Hz.
40751 Utility/Genset Read Only Multiplier: 1 This Modbus register is PC 3.x
Bus L1L2 Offset: 0 created for Modlon register
Voltage Size (bits): 16 mapping. Utility L1L2 Voltage
(Modlon) or Generator set Bus L1L2
Sign: U
voltage depending on
Unit: Vac paralleling application.
Lower Limit:
Upper Limit:
40752 Utility/Genset Read Only Multiplier: 1 This Modbus register is PC 3.x
Bus L2L3 Offset: 0 created for Modlon register
Voltage Size (bits): 16 mapping. Utility L2L3 voltage
(Modlon)
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40753 Utility/Genset Read Only Multiplier: 1 This Modbus register is PC 3.x
Bus L3L1 Offset: 0 created for Modlon register
Voltage Size (bits): 16 mapping. Utility L3L1 voltage
(Modlon) or Generator set Bus L3L1
Sign: U
voltage depending on
Unit: Vac paralleling application.
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 173 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40754 Utility/Genset Read Only Multiplier: 1 This Modbus register is PC 3.x
Bus L1N Offset: 0 created for Modlon register
Voltage Size (bits): 16 mapping. Utility L1N voltage
(Modlon) or Generator set Bus L1N
Sign: U
voltage depending on
Unit: Vac paralleling application.
Lower Limit:
Upper Limit:
40755 Utility/Genset Read Only Multiplier: 1 This Modbus register is PC 3.x
Bus L2N Offset: 0 created for Modlon register
Voltage Size (bits): 16 mapping. Utility L2N voltage
(Modlon) or Generator set Bus L2N
Sign: U
voltage depending on
Unit: Vac paralleling application.
Lower Limit:
Upper Limit:
40756 Utility/Genset Read Only Multiplier: 1 This Modbus register is PC 3.x
Bus L3N Offset: 0 created for Modlon register
Voltage Size (bits): 16 mapping. Utility L3N voltage
(Modlon) or Generator set Bus L3N
Sign: U
voltage depending on
Unit: Vac paralleling application.
Lower Limit:
Upper Limit:
40757 Customer Read Only Multiplier: 1 This Modbus register is PC 3.x
Faults Offset: 0 created for Modlon register
(Modlon) Size (bits): 16 mapping. 16 bit fault bitmap
for Modbus interface.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
40760 ES State Read Only 0: Standby This Modbus register is PC 3.x
(Modlon) 1: Dead Bus created for Modlon register
2: Synchronize mapping. Internal paralleling
status variable
3: Load Share
4: Load Goven
40761 Load Read Only 0: Inactive This Modbus register is PC 3.x
Demand Stop 1: Active created for Modlon register
Command mapping. Modbus input for
(Modlon) load demand stop command.
40764 Genset CB Read Only 0: Open This Modbus register is PC 3.x
Position 1: Closed created for Modlon register
Status 2: Not Available mapping. indicates generator
(Modlon) set breaker position
40765 Utility CB Read Only 0: Open This Modbus register is PC 3.x
Position 1: Closed created for Modlon register
Status 2: Not Available mapping. indicates utility
(Modlon) breaker position

Copyright © 2017 Cummins Inc. 174 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40766 Remote Start Read/Write 0: Inactive This Modbus register is PC 3.x
Switch(Modlo 1: Active created for Modlon register
n) mapping. Modbus Remote
Start
40767 Fault Reset Read/Write 0: Inactive This Modbus register is PC 3.x
(Modlon) 1: Active created for Modlon register
mapping. Modbus fault reset.
40768 System Read Only 0: Inactive Indicates communication PC 3.x
Network 1: Active status of the local genset on
Datalink 2: Failed System Network (used for
Status load demand). Available on
PCC3300MLD controls only.
40769 Load Read/Write Multiplier: 1 Run hour accumulator used PC 3.x
Demand Offset: 0 for load demand run hour
Genset Run Size: 32 equalization. This is writable.
Hours (Upper Available on PCC3300MLD
Sign: U
Register controls only.
Units: Hours
value)
Lower Limit: 0
Upper Limit: 999999.9
Default: 0
40770 Load Read/Write Multiplier: 1 Run hour accumulator used PC 3.x
Demand Offset: 0 for load demand run hour
Genset Run Size: 32 equalization. This is writable.
Hours (Lower Available on PCC3300MLD
Sign: U
Register controls only.
Units: Hours
value)
Lower Limit: 0
Upper Limit: 999999.9
Default: 0
40771 Load Read Only 0: Inactive Indicates the status of the PC 3.x
Demand 1: Active spare capacity request input.
Spare When ACTIVE additional
Capacity spare capacity (set by Load
Request Demand Spare Capacity
Status Request Value) is requested.
Available on PCC3300MLD
controls only.
40772 System Read Only 0: On Indicates the status of the on- PC 3.x
Network 1: Off board CAN termination
Termination resistor switch (S1). Available
Resistor on PCC3300MLD controls
Switch Status only.

A029X159 (Issue 19) 175 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40773 Genset ID Read/Write 0: Gen1 9: Gen10 Genset identifier. All load PC 3.x
1: Gen2 10: Gen11 demand gensets must have a
2: Gen3 11: Gen12 unique Genset ID. Available
on PCC3300MLD controls
3: Gen4 12: Gen13
only. Setup Mode must be
4: Gen5 13: Gen14 enabled to modify the value.
5: Gen6 14: Gen15 See Modbus Address 43343.
6: Gen7 15: Gen16
7: Gen8
8: Gen9
40774 Load Read/Write Multiplier: 1 Sets the kW value of PC 3.x
Demand Offset: 0 additional capacity to be
Spare Size(Bits): 32 requested from the system
Capacity when the Load Demand
Sign: U
Request Spare Capacity Request
Value (Upper Units: kW Status is YES. Available on
Register Lower Limit: 0 PCC3300MLD controls only.
value) Upper Limit: 80000 Setup Mode must be enabled
Default: 0 to modify the value. See
Modbus Address 43343.
40775 Load Read/Write Multiplier: 1 Sets the kW value of PC 3.x
Demand Offset: 0 additional capacity to be
Spare Size(Bits): 32 requested from the system
Capacity when the Load Demand
Sign: U
Request Spare Capacity Request
Value (Lower Units: kW Status is YES. Available on
Register Lower Limit: 0 PCC3300MLD controls only.
value) Upper Limit: 80000 Setup Mode must be enabled
Default: 0 to modify the value. See
Modbus Address 43343.
40776 Load Read/Write 0: Disable Disables or Enables load PC 3.x
Demand 1: Enable demand on this genset only.
Genset When set to disable the
Enable genset is not included in the
load demand system and can
be removed without triggering
a com error. Available on
PCC3300MLD controls only.
Setup Mode must be enabled
to modify the value. See
Modbus Address 43343.
40777 System Read Only 0: Out of Sync Indicates whether the system PC 3.x
Settings 1: In Sync settings on the local genset
Status are in sync with ones from
other genset in the network.
Available on PCC3300MLD
controls only.

Copyright © 2017 Cummins Inc. 176 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40800 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40801 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40802 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40803 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40804 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40805 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 177 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40806 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40807 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40808 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40809 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40810 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40811 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 178 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40812 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40813 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40814 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40815 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40816 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40817 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 179 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40818 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40819 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40820 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40821 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40822 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40823 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 180 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40824 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Input 7 Fault Offset: 0 field to allow for the entry of 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40825 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Input 7 Fault Offset: 0 field to allow for the entry of 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40826 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Input 7 Fault Offset: 0 field to allow for the entry of 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40827 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Input 7 Fault Offset: 0 field to allow for the entry of 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40828 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40829 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 181 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40830 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40831 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Input 7 Fault Offset: 0 field to allow for the entry of 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40832 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40833 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40834 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40835 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 182 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40836 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40837 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40838 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40839 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40840 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40841 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 183 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40842 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40843 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text string to enter the PC 3.x
configurable fault text for this
fault.
40844 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40845 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40846 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40847 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 184 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40848 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40849 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40850 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40851 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Fault 9 Text Offset: 0 string to enter the 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40852 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40853 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 185 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40854 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40855 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40856 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40857 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40858 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40859 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 186 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40860 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40861 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40862 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40863 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Fault 10 Text Offset: 0 string to enter the 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40864 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC


Fault 10 Text Offset: 0 string to enter the 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40865 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC


Fault 10 Text Offset: 0 string to enter the 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 187 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40866 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Fault 10 Text Offset: 0 string to enter the 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40867 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Fault 10 Text Offset: 0 string to enter the 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40868 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40869 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40870 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40871 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 188 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40872 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40873 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40874 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40875 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40876 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 189 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40877 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40878 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40879 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40880 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40881 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 190 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40882 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40883 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40884 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40885 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40886 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40887 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 191 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40888 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40889 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40890 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40891 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40892 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40893 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 192 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40894 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40895 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40896 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40897 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40898 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40899 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 193 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40900 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40901 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40902 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40903 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40904 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40905 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 194 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40906 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40907 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40908 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40909 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40910 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40911 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 195 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40912 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40913 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40914 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Addr. Parameter Access Specifications Description Control


40915 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40916 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40917 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 196 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40918 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40919 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40920 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Fault 9 Text Offset: 0 string to enter the 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40921 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Fault 9 Text Offset: 0 string to enter the 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40922 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Fault 9 Text Offset: 0 string to enter the 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40923 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 197 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40924 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40925 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40926 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40927 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40928 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40929 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 198 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40930 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40931 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40932 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40933 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40934 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40935 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 199 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40936 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40937 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40938 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40939 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40940 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40941 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 200 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40942 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40943 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40944 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40945 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40946 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40947 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 201 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40948 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40949 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40950 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40951 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40952 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 202 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40953 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40954 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40955 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40956 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40957 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 203 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40958 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40959 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 10 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40960 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40961 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40962 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 204 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40963 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40964 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40965 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40966 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40967 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40968 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 205 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40969 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40970 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40971 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40972 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40973 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40974 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 206 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40975 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40976 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40977 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40978 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40979 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40980 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 207 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40981 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40982 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40983 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40984 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40985 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40986 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 208 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40987 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40988 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40989 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40990 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40991 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 209 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


40992 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40993 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40994 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40995 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40996 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 210 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40997 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40998 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40999 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

41000 Load Read/Write 0: Disable Disables or Enables load PC 3.x


Demand 1: Enable demand operation of all
System connected gensets. Available
Enable on PCC3300MLD controls
only.
41001 Load Read/Write 0: Run Hours Equalization Sets the sequencing priority PC 3.x
Demand (Run Hr Eql) for load demand. Available on
Type 1: Fixed Sequence (Fixed PCC3300MLD controls only.
Seq)

41002 Load Read/Write 0: kW Sets whether the load PC 3.x


Demand 1: %kW demand start/stop control is
Threshold based on a relative (%) or
Method absolute (kW) threshold.
Available on PCC3300MLD
controls only.

A029X159 (Issue 19) 211 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


41003 Load Read/Write Multiplier: 1 When the ratio of load to PC 3.x
Demand Start Offset: 0 capacity is greater than this
Threshold Size(Bits): 8 value the next genset will
(%kW) start. Must be greater than
Sign: U
Load Demand Stop
Units: % Threshold by at least 5%.
Lower Limit: 25 Available on PCC3300MLD
Upper Limit: 100 controls only.
Default: 80

41004 Load Read/Write Multiplier: 1 When surplus capacity is less PC 3.x


Demand Start Offset: 0 than this value the next
Threshold Size(Bits): 16 genset will start. Must be less
(kW) than Load Demand Stop
Sign: U
Threshold (kW). Available on
Units: kW PCC3300MLD controls only.
Lower Limit: 5
Upper Limit: 5000
Default: 500

41005 Load Read/Write Multiplier: 1 When the ratio of load to PC 3.x


Demand Stop Offset: 0 capacity is less than this
Threshold Size(Bits): 8 value the next genset will
(%kW) stop. Must be less than Load
Sign: U
Demand Start Threshold by
Units: % at least 5%. Available on
Lower Limit: 20 PCC3300MLD controls only.
Upper Limit: 95
Default: 60

41006 Load Read/Write Multiplier: 1 When surplus capacity is PC 3.x


Demand Stop Offset: 0 greater than this value the
Threshold Size(Bits): 16 next genset will stop. Must be
(kW) greater than Load Demand
Sign: U
Start Threshold (kW).
Units: kW Available on PCC3300MLD
Lower Limit: 5 controls only.
Upper Limit: 5000
Default: 1000
41007 Load Read/Write Multiplier: 1 When the difference between PC 3.x
Demand Run Offset: 0 Load Demand Genset Run
Hours Size(Bits): 16 Hours between any running
Differential genset and any stopped
Sign: U
genset reaches this value the
Units: Hours stopped genset will be
Lower Limit: 1 started. Available on
Upper Limit: 250 PCC3300MLD controls only.
Default: 50

Copyright © 2017 Cummins Inc. 212 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


41008 Load Read/Write Multiplier: 1 Sets the time delay that the PC 3.x
Demand Offset: 0 system waits for a genset to
Genset Fail Size(Bits): 16 come online before declaring
Delay it as failed. Available on
Sign: U
PCC3300MLD controls only.
Units: seconds
Lower Limit: 10
Upper Limit: 900
Default: 60

41009 Load Read/Write Multiplier: 1 Sets the time delay before PC 3.x
Demand Offset: 0 gensets are allowed to stop
Initial Delay Size(Bits): 16 after initial start or after
resuming halted load
Sign: U
demand. Available on
Units: seconds PCC3300MLD controls only.
Lower Limit: 60
Upper Limit: 1500
Default: 300

41010 Load Read/Write Multiplier: 1 Sets the time delay before PC 3.x
Demand Start Offset: 0 next genset is allowed to
Delay Size(Bits): 16 start. Available on
PCC3300MLD controls only.
Sign: U
Units: seconds
Lower Limit: 0
Upper Limit: 1500
Default: 10

41011 Load Read/Write Multiplier: 1 Sets the time delay before PC 3.x
Demand Stop Offset: 0 next genset is allowed to
Delay Size(Bits): 16 stop. Available on
PCC3300MLD controls only.
Sign: U
Units: seconds
Lower Limit: 60
Upper Limit: 1500
Default: 300

41012 Clear Lost Read/Write 0: No When set to YES all gensets PC 3.x
Gensets 1: Yes in state ”Lost” will change to
Local state ”Gen Does Not Exist” in
order to clear Lost Genset
Warning. Available on
PCC3300MLD controls only.

A029X159 (Issue 19) 213 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


41013 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x
Demand 1: Gen2 priority 1. Used when Load
Fixed Priority 2: Gen3 Demand Type is set to Fixed
1 Sequence. Available on
3: Gen4
PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41014 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 2. Used when Load
Fixed Priority 2: Gen3 Demand Type is set to Fixed
2 Sequence. Available on
3: Gen4
PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

Copyright © 2017 Cummins Inc. 214 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


41015 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x
Demand 1: Gen2 priority 3. Used when Load
Fixed Priority 2: Gen3 Demand Type is set to Fixed
3 Sequence. Available on
3: Gen4
PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41016 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 4. Used when Load
Fixed Priority 2: Gen3 Demand Type is set to Fixed
4 Sequence. Available on
3: Gen4
PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

A029X159 (Issue 19) 215 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


41017 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x
Demand 1: Gen2 priority 5. Used when Load
Fixed Priority 2: Gen3 Demand Type is set to Fixed
5 Sequence. Available on
3: Gen4
PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41018 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 6. Used when Load
Fixed Priority 2: Gen3 Demand Type is set to Fixed
6 Sequence. Available on
3: Gen4
PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

Copyright © 2017 Cummins Inc. 216 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


41019 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x
Demand 1: Gen2 priority 7. Used when Load
Fixed Priority 2: Gen3 Demand Type is set to Fixed
7 Sequence. Available on
3: Gen4
PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41020 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 8. Used when Load
Fixed Priority 2: Gen3 Demand Type is set to Fixed
8 Sequence. Available on
3: Gen4
PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

A029X159 (Issue 19) 217 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


41021 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x
Demand 1: Gen2 priority 9. Used when Load
Fixed Priority 2: Gen3 Demand Type is set to Fixed
9 Sequence. Available on
3: Gen4
PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41022 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 10. Used when Load
Fixed Priority 2: Gen3 Demand Type is set to Fixed
10 Sequence. Available on
3: Gen4
PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

Copyright © 2017 Cummins Inc. 218 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


41023 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x
Demand 1: Gen2 priority 11. Used when Load
Fixed Priority 2: Gen3 Demand Type is set to Fixed
11 Sequence. Available on
3: Gen4
PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41024 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 12. Used when Load
Fixed Priority 2: Gen3 Demand Type is set to Fixed
12 Sequence. Available on
3: Gen4
PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

A029X159 (Issue 19) 219 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


41025 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x
Demand 1: Gen2 priority 13. Used when Load
Fixed Priority 2: Gen3 Demand Type is set to Fixed
13 Sequence. Available on
3: Gen4
PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41026 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 14. Used when Load
Fixed Priority 2: Gen3 Demand Type is set to Fixed
14 Sequence. Available on
3: Gen4
PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

Copyright © 2017 Cummins Inc. 220 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


41027 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x
Demand 1: Gen2 priority 15. Used when Load
Fixed Priority 2: Gen3 Demand Type is set to Fixed
15 Sequence. Available on
3: Gen4
PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41028 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 16. Used when Load
Fixed Priority 2: Gen3 Demand Type is set to Fixed
16 Sequence. Available on
3: Gen4
PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41029 System Read/Write 0: Inactive When set to YES all the PC 3.x
Network 1: Active system network faults in the
Remote Fault system would be reset.
Reset Available on PCC3300MLD
controls only.

41030 Synchronize Read/Write 0: No When set to YES system PC 3.x


System 1: Yes settings from the genset will
Settings be broadcasted and
synchronized to all other
gensets in the network.
Available on PCC3300MLD
controls only.

A029X159 (Issue 19) 221 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


41031 Battery Read Only 0: Inactive Battery Charger 2 Failed PC 3.x
Charger 2 1: Active Switch function output status;
Failed Switch gives software Inactive/Active
state
41032 Battery Read Only 0: Inactive Battery Charger 3 Failed PC 3.x
Charger 3 1: Active Switch function output status;
Failed Switch gives software Inactive/Active
state
41033 Battery Read Only 0: Inactive Battery Charger 4 Failed PC 3.x
Charger 4 1: Active Switch function output status;
Failed Switch gives software Inactive/Active
state
41034 Intake Air Read Only 0: Inactive Intake Air Restriction PC 3.x
Restriction 1: Active Indicator 1 fault switch
Indicator 1 function output status; gives
fault switch software Inactive/Active state
41035 Intake Air Read Only 0: Inactive Intake Air Restriction PC 3.x
Restriction 1: Active Indicator 2 fault switch
Indicator 2 function output status; gives
fault switch software Inactive/Active state
41036 Intake Air Read Only 0: Inactive Intake Air Restriction PC 3.x
Restriction 1: Active Indicator 3 fault switch
Indicator 3 function output status; gives
fault switch software Inactive/Active state
41037 Intake Air Read Only 0: Inactive Intake Air Restriction PC 3.x
Restriction 1: Active Indicator 4 fault switch
Indicator 4 function output status; gives
fault switch software Inactive/Active state
41038 Starter Air Read Only 0: Inactive Starter Air Supply Pressure PC 3.x
Supply 1: Active Low Fault Switch function
Pressure Low output status; gives software
Fault Switch Inactive/Active
41039 Starter Air Read Only 0: Inactive Starter Air Tank Volume Low PC 3.x
Tank Volume 1: Active Fault Switch function output
Low Fault status; gives software
Switch Inactive/Active state
41300 AmpSentry Read Only 0: Inactive A protection mode that PC 3.x
Maintenance 1: Active causes the alternator to
Mode Status shutdown instantly when a
short circuit is detected. Used
to limit arc flash energy with
personnel working

Copyright © 2017 Cummins Inc. 222 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


41301 AMM PC Read Only 0: Inactive Detects whether any service PC 3.x
Tool Detected 1: Active tool is connected via TB15 or
J14 by validating if a
read/write command has
been exchanged via MON
using a five second
decremental timer. If the timer
expires, then it is determine
service tool is no longer
connected.
41302 AMM Disable Read Only Multiplier : 1 Countdown timer when PC 3.x
Walkaway Units: Seconds walkaway is complete.
Timer Value Offset: 0
Lower Limit: NA
Size (Bits) : 16
Upper Limit: NA
Sign: U
Default: NA

41400 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 3.x
Bitmap 31 Units: NA interface.
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41401 Fault Status Read Only Multiplier : 1 16 bit Diesel Fault Bitmap for PC 3.x
Bitmap 33 Units: NA Modbus interface
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41402 Fault Status Read Only Multiplier : 1 16 bit Diesel Fault Bitmap for PC 2.x,
Bitmap 34 Units: NA Modbus interface PC 3.x
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA

A029X159 (Issue 19) 223 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


41403 AT Fault Read Only Multiplier : 1 16 bit AT Fault Bitmap for PC 3.x
Status Bitmap Units: NA Modbus interface
2 Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41404 AT Fault Read Only Multiplier : 1 16 bit AT Fault Bitmap for PC 3.x
Status Bitmap Units: NA Modbus interface
3 Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41405 AT Fault Read Only Multiplier : 1 16 bit AT Fault Bitmap for PC 3.x
Status Bitmap Units: NA Modbus interface
4 Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA

41406 AT Fault Read Only Multiplier : 1 16 bit AT Fault Bitmap for PC 3.x
Status Bitmap Units: NA Modbus interface
5 Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41407 AT Fault Read Only Multiplier : 1 16 bit AT Fault Bitmap for PC 3.x
Status Bitmap Units: NA Modbus interface
6 Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA

Copyright © 2017 Cummins Inc. 224 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


41408 AT Fault Read Only Multiplier : 1 16 bit AT Fault Bitmap for PC 3.x
Status Bitmap Units: NA Modbus interface
7 Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41409 AT Fault Read Only Multiplier : 1 16 bit AT Fault Bitmap for PC 3.x
Status Bitmap Units: NA Modbus interface
8 Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41416 Fault Status Read Only Multiplier : 1 16 bit Diesel Fault Bitmap for PC 3.x
Bitmap 35 Units: NA Modbus interface
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41417 Fault Status Read Only Multiplier : 1 16 bit Diesel Fault Bitmap for PC 3.x
Bitmap 36 Units: NA Modbus interface
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41418 Fault Status Read Only Multiplier : 1 16 bit Diesel Fault Bitmap for PC 3.x
Bitmap 37 Units: NA Modbus interface
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
42000 Load Read Only 0: Off Indicates the status of Load PC 3.x
Demand 1: Halted Demand operation. Available
State 2: Initial Delay on PCC3300MLD controls
only.
3: Load Monitor

A029X159 (Issue 19) 225 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


42001 Load Read Only Multiplier: 1.0 Indicates the total load of PC 3.x
Demand Offset: 0 System Network connected
Genset Bus Size (bits): 32 gensets. Available on
Total kW PCC3300MLD controls only.
Sign: U
(Upper
Register Units: kW
value) Lower Limit: 0
Upper Limit: 80000
Default: 0
42002 Load Read Only Multiplier: 1.0 Indicates the total load of PC 3.x
Demand Offset: 0 System Network connected
Genset Bus Size (bits): 32 gensets. Available on
Total kW PCC3300MLD controls only.
Sign: U
(Lower
Register Units: kW
value) Lower Limit: 0
Upper Limit: 80000
Default: 0
42003 Load Read Only Multiplier: 1.0 Indicates the total load of PC 3.x
Demand Offset: 0 System Network connected
Surplus Size (bits): 32 gensets. Available on
Capacity PCC3300MLD controls only.
Sign: U
(Upper
Register Units: kW
value) Lower Limit: 0
Upper Limit: 80000
Default: 0
42004 Load Read Only Multiplier: 1.0 Indicates the total load of PC 3.x
Demand Offset: 0 System Network connected
Surplus Size (bits): 32 gensets. Available on
Capacity PCC3300MLD controls only.
Sign: U
(Lower
Register Units: kW
value) Lower Limit: 0
Upper Limit: 80000
Default: 0
42005 Load Read Only Multiplier: 1.0 Indicates the total amount of PC 3.x
Demand Offset: 0 online kW bus capacity for
Online Size (bits): 32 load demand. Only gensets
Capacity which are eligible for load
Sign: U
(Upper demand are counted.
Register Units: kW Available on PCC3300MLD
value) Lower Limit: 0 controls only.
Upper Limit: 80000
Default: 0

Copyright © 2017 Cummins Inc. 226 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


42006 Load Read Only Multiplier: 1.0 Indicates the total amount of PC 3.x
Demand Offset: 0 online kW bus capacity for
Online Size (bits): 32 load demand. Only gensets
Capacity which are eligible for load
Sign: U
(Lower demand count. Available on
Register Units: kW PCC3300MLD controls only.
value) Lower Limit: 0
Upper Limit: 80000
Default: 0

Addr. Parameter Access Specifications Description Control


42007 Load Read Only Multiplier: 1.0 Indicates the time remaining PC 3.x
Demand Offset: 0 before gensets are allowed to
Initial Delay Size (bits): 16 stop after initial start or after
Timer resuming halted load
Sign: U
demand. This timer is set by
Units: Seconds Load Demand Initial Delay.
Lower Limit: 0 Available on PCC3300MLD
Upper Limit: 1500 controls only.
Default: 0
42008 Load Read Only Multiplier: 1.0 Indicates the time remaining PC 3.x
Demand Start Offset: 0 before next genset is allowed
Delay Timer Size (bits): 16 to start. This timer is set by
Load Demand Start Delay.
Sign: U
Available on PCC3300MLD
Units: Seconds controls only.
Lower Limit: 0
Upper Limit: 1500
Default: 0
42009 Load Read Only Multiplier: 1.0 Indicates the time remaining PC 3.x
Demand Stop Offset: 0 before next genset is allowed
Delay Timer Size (bits): 16 to stop. This timer is set by
Load Demand Stop Delay.
Sign: U
Available on PCC3300MLD
Units: Seconds controls only.
Lower Limit: 0
Upper Limit: 1500
Default: 0
42010 Load Read Only 0: No Indicates when the current PC 3.x
Demand 1: Yes load and spare capacity
Spare requirements are satisfied.
Capacity Available on PCC3300MLD
Available controls only.

A029X159 (Issue 19) 227 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


42011 Load Read Only Multiplier: 1.0 Indicates the total kW value PC 3.x
Demand Offset: 0 of all currently active spare
Total Spare Size (bits): 32 capacity requests in the
Capacity system. Available on
Sign: U
PCC3300MLD controls only.
Requested Units: kW
(Upper Lower Limit: 0
Register
Upper Limit: 80000
value)
Default: 0

42012 Load Read Only Multiplier: 1.0 Indicates the total kW value PC 3.x
Demand Offset: 0 of all currently active spare
Total Spare Size (bits): 32 capacity requests in the
Capacity system. Available on
Sign: U
PCC3300MLD controls only.
Requested Units: kW
(Lower Lower Limit: 0
Register
Upper Limit: 80000
value)
Default: 0

42013 Load Read Only Multiplier: 1.0 The kW load at which the PC 3.x
Demand Next Offset: 0 next genset will be started.
Start Size (bits): 32 Available on PCC3300MLD
Threshold controls only.
Sign: U
(kW) (Upper
Register Units: kW
value) Lower Limit: 0
Upper Limit: 80000
Default: 0

42014 Load Read Only Multiplier: 1.0 The kW load at which the PC 3.x
Demand Next Offset: 0 next genset will be started.
Start Size (bits): 32 Available on PCC3300MLD
Threshold controls only.
Sign: U
(kW) (Lower
Register Units: kW
value) Lower Limit: 0
Upper Limit: 80000
Default: 0

Copyright © 2017 Cummins Inc. 228 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


42015 Load Read Only Multiplier: 1.0 The kW load at which the PC 3.x
Demand Next Offset: 0 next genset will be stopped.
Stop Size (bits): 32 Available on PCC3300MLD
Threshold controls only.
Sign: U
(Upper
Register Units: kW
value) Lower Limit: 0
Upper Limit: 80000
Default: 0

42016 Load Read Only Multiplier: 1.0 The kW load at which the PC 3.x
Demand Next Offset: 0 next genset will be stopped.
Stop Size (bits): 32 Available on PCC3300MLD
Threshold controls only.
Sign: U
(Lower
Register Units: kW
value) Lower Limit: 0
Upper Limit: 80000
Default: 0

42017 Load Read Only 0: Gen1 Indicates the next genset to PC 3.x
Demand Next 1: Gen2 start by ID. Available on
Gen to start 2: Gen3 PCC3300MLD controls only.
(kW)
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

A029X159 (Issue 19) 229 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


42018 Load Read Only 0: Gen1 Indicates the next genset to PC 3.x
Demand Next 1: Gen2 stop by ID. Available on
Gen to Stop 2: Gen3 PCC3300MLD controls only.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
42019 Load Read Only 0: Inactive Indicates the status of the PC 3.x
Demand 1: Active Load Demand Inhibit input.
Inhibit Local When ACTIVE all the gensets
will start. Available on
PCC3300MLD controls only.
43000 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L1 current PC 3.x
L1 Current Size (bits): 16 percentage output.
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43001 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L2 current PC 3.x
L2 Current Size (bits): 16 percentage output.
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43002 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L1 kVA PC 3.x
L1 kVA Size (bits): 16 percentage output.
Sign: U
Unit: %
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 230 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43003 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L3 current PC 3.x
L3 Current Size (bits): 16 percentage output.
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43004 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L2 kVA PC 3.x
L2 kVA Size (bits): 16 percentage output.
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43005 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L3 kVA PC 3.x
L3 kVA Size (bits): 16 percentage output.
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43006 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L1 KW PC 3.x
L1 kW Size (bits): 16 percentage output.
Sign: S
Unit: %
Lower Limit:
Upper Limit:
43007 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L2 KW PC 3.x
L2 kW Size (bits): 16 percentage output.
Sign: S
Unit: %
Lower Limit:
Upper Limit:
43008 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L3 KW PC 3.x
L3 kW Size (bits): 16 percentage output.
Sign: S
Unit: %
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 231 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43009 Genset % Read Only Multiplier: 0.1 Monitors the total generator PC 2.x,
Application Offset: 0 set application kVA PC 3.x
Total kVA Size (bits): 16 percentage output.
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43010 Genset % Read Only Multiplier: 0.1 Monitors the total generator PC 2.x,
Application Offset: 0 set application KW PC 3.x
Total kW Size (bits): 16 percentage output.
Sign: S
Unit: %
Lower Limit:
Upper Limit:
43011 Genset % Read Only Multiplier : 0.1 Monitors the genset standby PC 2.x,
Standby L1 Offset: 0 L1 kVA percentage output. PC 3.x
kVA Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
43012 Genset % Read Only Multiplier : 0.1 Monitors the genset standby PC 2.x,
Standby L3 Offset: 0 L3 kVA percentage output. PC 3.x
kVA Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
43013 Genset % Read Only Multiplier : 0.1 Monitors the genset standby PC 2.x,
Standby L2 Offset: 0 L2 kVA percentage output. PC 3.x
kVA Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43014 Genset % Read Only Multiplier : 0.1 Monitors the genset standby PC 2.x,
Standby L1 Offset: 0 L1 KW percentage output. PC 3.x
kW Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA

Copyright © 2017 Cummins Inc. 232 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43015 Genset % Read Only Multiplier : 0.1 Monitors the genset standby PC 2.x,
Standby L2 Offset: 0 L2 KW percentage output. PC 3.x
kW Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43016 Genset % Read Only Multiplier : 0.1 Monitors the genset standby PC 2.x,
Standby L3 Offset: 0 L3 KW percentage output. PC 3.x
kW Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43017 Genset % Read Only Multiplier: 0.1 Monitors the total generator PC 2.x,
Standby Total Offset: 0 set standby kVA percentage PC 3.x
kVA Size (bits): 16 output.
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43018 Genset Read Only Multiplier: 0.1 The generator set kVA rating. PC 2.x,
Application Offset: 0 PC 3.x
kVA rating Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
43019 Genset Read Only Multiplier: 0.1 The generator set KW rating. PC 2.x,
Application Offset: 0 PC 3.x
kW rating Size (bits): 16
Sign: U
Unit: kW
Lower Limit:
Upper Limit:
43020 Genset Read Only Multiplier: 1 The value of the generator PC 2.x,
Application Offset: 0 set application nominal PC 3.x
Nominal Size (bits): 16 current. Displayed as
Current ”Generator set Application
Sign: U
Rated Current” in HMI
Unit: Amps
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 233 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43021 Genset Read Only Multiplier: 0.01 Generator set average PC 2.x,
Average Offset: 0 voltage percentage. PC 3.x
Voltage% Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43030 Genset L1 Read Only Multiplier: 0.01 Generator set L1 power factor PC 2.x,
Power Factor Offset: 0 PC 3.x
Size (bits): 8
Sign: S
Unit: PF
Lower Limit:
Upper Limit:
43031 Genset L1L2 Read Only Multiplier: 0.01 Generator set L1L2 voltage PC 2.x,
Phase Offset: 0 phase angle PC 3.x
Difference Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit:
Upper Limit:
43032 Genset L1L2 Read Only Multiplier: 0.01 Generator set L1L2 voltage% PC 2.x,
Voltage% Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43033 Genset L1N Read Only Multiplier: 0.01 Generator set L1N voltage% PC 2.x,
Voltage% Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43044 Genset L2 Read Only Multiplier: 0.01 Generator set L2 power factor PC 2.x,
Power Factor Offset: 0 PC 3.x
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: -1.28
Upper Limit: 1.27

Copyright © 2017 Cummins Inc. 234 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43045 Genset L2L3 Read Only Multiplier: 0.01 Generator set L2L3 voltage PC 2.x,
Phase Offset: 0 phase angle PC 3.x
Difference Size (bits): 8
Sign: U
Unit: Degrees
Lower Limit: 0
Upper Limit: 655.3
43046 Genset L2L3 Read Only Multiplier: 0.01 Generator set L2L3 voltage% PC 2.x,
Voltage% Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43047 Genset L2N Read Only Multiplier: 0.01 Generator set L2N voltage% PC 2.x,
Voltage% Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit: 0
Upper Limit: 655.3
43058 Genset L3 Read Only Multiplier: 0.01 Generator set L3 power factor PC 2.x,
Power Factor Offset: 0 PC 3.x
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: -1.28
Upper Limit: 1.22
43059 Genset L3L1 Read Only Multiplier: 0.01 Generator set L3L1 voltage PC 2.x,
Phase Offset: 0 phase angle PC 3.x
Difference Size (bits): 8
Sign: U
Unit: Degrees
Lower Limit: 0
Upper Limit: 655.3
43060 Genset L3L1 Read Only Multiplier: 0.01 Generator set L3L1 voltage% PC 2.x,
Voltage% Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit: 0
Upper Limit: 655.3

A029X159 (Issue 19) 235 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43061 Genset L3N Read Only Multiplier: 0.01 Generator set L3N voltage% PC 2.x,
Voltage% Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43062 Genset Read Only Multiplier: 0.1 kVA rating for the generator PC 2.x,
Standby kVA Offset: 0 set in Standby configuration. PC 3.x
rating Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
43063 Genset Read Only Multiplier: 0.1 KW rating for the generator PC 2.x,
Standby kW Offset: 0 set in Standby configuration. PC 3.x
rating Size (bits): 16
Sign: U
Unit: kW
Lower Limit:
Upper Limit:
43064 Genset Read Only Multiplier: 1 The value of the generator PC 2.x,
Standby Offset: 0 set standby nominal current. PC 3.x
Nominal Size (bits): 16 Displayed as ”Generator set
Current Standby Rated Current” in
Sign: U
HMI
Unit: Amps
Lower Limit:
Upper Limit:
43065 Genset Total Read Only Multiplier: 1 Generator set total kVAh PC 2.x,
kVAh Offset: 0 accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:
43066 Genset Total Read Only Multiplier: 1 Generator set total kVAh PC 2.x,
kVAh Offset: 0 accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 236 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43067 Genset Total Read Only Multiplier: 0.01 Total kVAR’s per Standby PC 2.x,
kVARs per Offset: 0 kVA. PC 3.x
Standby kVA Size (bits): 16
Sign: S
Unit: %
Lower Limit:
Upper Limit:
43100 Genset Bus Read Only Multiplier : 0.01 Genset Bus average PC 3.x
Average Offset: 0 voltage%
Voltage% Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43111 Genset Bus Read Only Multiplier: 0.01 Generator set Bus L1 power PC 3.x
L1 Power Offset: 0 factor
Factor Size (bits): 8
Sign: S
Unit: PF
Lower Limit: -1.28
Upper Limit: 1.22
43112 Genset Bus Read Only Multiplier: 0.01 Generator set bus L1L2 PC 3.x
L1L2 Phase Offset: 0 voltage phase angle
Difference Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit:
Upper Limit:
43113 Genset Bus Read Only Multiplier : 0.01 Genset Bus L1L2 voltage% PC 3.x
L1L2 Offset: 0
Voltage% Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
43114 Genset Bus Read Only Multiplier : 0.01 Genset Bus L1N voltage% PC 3.x
L1N Offset: 0
Voltage% Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA

A029X159 (Issue 19) 237 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43125 Genset Bus Read Only Multiplier: 0.01 Generator set Bus L2 power PC 3.x
L2 Power Offset: 0 factor
Factor Size (bits): 8
Sign: S
Unit: PF
Lower Limit: NA
Upper Limit: NA
43126 Genset Bus Read Only Multiplier: 0.01 Generator set bus L2L3 PC 3.x
L2L3 Phase Offset: 0 voltage phase angle
Difference Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit: NA
Upper Limit: NA
43127 Genset Bus Read Only Multiplier : 0.01 Genset Bus L2L3 voltage% PC 3.x
L2L3 Offset: 0
Voltage% Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43128 Genset Bus Read Only Multiplier : 0.01 Genset Bus L2N voltage% PC 3.x
L2N Offset: 0
Voltage% Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43139 Genset Bus Read Only Multiplier: 0.01 Generator set Bus L3 power PC 3.x
L3 Power Offset: 0 factor
Factor Size (bits): 8
Sign: S
Unit: PF
Lower Limit: -1.28
Upper Limit: 1.22
43140 Genset Bus Read Only Multiplier: 0.01 Generator set bus L3L1 PC 3.x
L3L1 Phase Offset: 0 voltage phase angle
Difference Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 238 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43141 Genset Bus Read Only Multiplier : 0.01 Genset Bus L3L1 voltage% PC 3.x
L3L1 Offset: 0
Voltage% Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43142 Genset Bus Read Only Multiplier : 0.01 Genset Bus L3N voltage% PC 3.x
L3N Offset: 0
Voltage% Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43143 Genset Bus Read Only Multiplier: 1 Generator set bus total kVAh PC 3.x
Total kVAh Offset: 0 accumulation
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:
Default: NA
43144 Genset Bus Read Only Multiplier: 1 Generator set bus total kVAh PC 3.x
Total kVAh Offset: 0 accumulation
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:
43145 Sync Phase Read Only Multiplier : 0.01 Other meter to genset meter PC 3.x
Difference Offset: 0 L1 voltage phase angle
Size (bits): 16
Sign: S
Units: deg
Lower Limit: NA
Upper Limit: NA
Default: NA
43146 Paralleling Read/Write 0: None Determines what the function PC 3.x
Application 1: Utility of the Other Meter is.
2: Genset Bus

A029X159 (Issue 19) 239 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43147 System Total Read Only Multiplier : 1 Sum of genset bus and utility PC 3.x
kVA Offset: 0 bus kVA
Size (bits): 16
Sign: U
Units: kVA
Lower Limit: NA
Upper Limit: NA
Default: NA
43148 System Total Read Only Multiplier : 1 Sum of genset bus and utility PC 3.x
kVAR Offset: 0 bus kVAR
Size (bits): 16
Sign: S
Units: kVAR
Lower Limit: NA
Upper Limit: NA
Default: NA
43149 System Total Read Only Multiplier : 1 Sum of genset bus and utility PC 3.x
kW Offset: 0 bus kW
Size (bits): 16
Sign: U
Units: kW
Lower Limit: NA
Upper Limit: NA
Default: NA
43150 System Total Read Only Multiplier : 0.01 System total power factor PC 3.x
Power Factor Offset: 0 (totalized value of utility bus
Size (bits): 8 plus genset bus)
Sign: U
Units: PF
Lower Limit: NA
Upper Limit: NA
Default: NA
43151 Utility Read Only Multiplier : 0.01 Utility average voltage% PC 3.x
Average Offset: 0
Voltage% Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA

Copyright © 2017 Cummins Inc. 240 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43162 Utility L1 Read Only Multiplier: 0.01 Utility L1 power factor PC 3.x
Power Factor Offset: 0
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: NA
Upper Limit: NA
43163 Utility L1L2 Read Only Multiplier: 0.01 Utility L1L2 voltage phase PC 3.x
Phase Offset: 0 angle
Difference Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit: NA
Upper Limit: NA
43164 Utility L1L2 Read Only Multiplier : 0.01 Utility L1L2 voltage% PC 3.x
Voltage% Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43165 Utility L1N Read Only Multiplier : 0.01 Utility L1N voltage% PC 3.X
Voltage% Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43176 Utility L2 Read Only Multiplier: 0.01 Utility L2 power factor PC 3.x
Power Factor Offset: 0
Size (bits): 8
Sign: S
Unit: PF
Lower Limit:
Upper Limit:
43177 Utility L2L3 Read Only Multiplier: 0.01 Utility L2L3 voltage phase PC 3.x
Phase Offset: 0 angle
Difference Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 241 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43178 Utility L2L3 Read Only Multiplier : 0.01 Utility L2L3 voltage% PC 3.x
Voltage% Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
43179 Utility L2N Read Only Multiplier : 0.01 Utility L2N voltage% PC 3.x
Voltage% Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43190 Utility L3 Read Only Multiplier: 0.01 Utility L3 power factor PC 3.x
Power Factor Offset: 0
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: NA
Upper Limit: NA
43191 Utility L3L1 Read Only Multiplier: 0.01 Utility L3L1 voltage phase PC 3.x
Phase Offset: 0 angle
Difference Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit: NA
Upper Limit: NA
43192 Utility L3L1 Read Only Multiplier : 0.01 Utility L3L1 voltage% PC 3.x
Voltage% Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA

Copyright © 2017 Cummins Inc. 242 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43193 Utility L3N Read Only Multiplier : 0.01 Utility L3N voltage% PC 3.x
Voltage% Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43194 Utility Total Read Only Multiplier: 1 Utility total kVAh PC 3.x
kVAh Offset: 0 accumulation
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:
43195 Utility Total Read Only Multiplier: 1 Utility total kVAh PC 3.x
kVAh Offset: 0 accumulation
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:
43196 Exhaust Read Only Multiplier : 0.1 Monitor point for the Exhaust PC 3.x
Stack Offset: 0 Stack Temperature Right
Temperature Size (bits): 16 Bank received from ECM
Right Bank
Sign: S
Units: degF
Lower Limit: -459
Upper Limit: 3155
Default: NA
43197 Exhaust Read Only Multiplier : 0.1 Monitor point for the Exhaust PC 3.x
Stack Offset: 0 Stack Temperature Left Bank
Temperature Size (bits): 16 received from ECM
Left Bank
Sign: S
Units: degF
Lower Limit: -459
Upper Limit: 3155
Default: NA

A029X159 (Issue 19) 243 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43200 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43200-43219
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit: -459
Upper Limit: 3155
43201 Genset Model Read Only Multiplier: 1 Number indentifying the PC 2.x,
Number Offset: 0 model of this generator set. PC 3.x
Size (bits): 168 Modbus uses addresses
43200-43219 for the 20
Sign: C
characters of this string.
Unit:
Lower Limit:
Upper Limit:
43202 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43200-43219
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43203 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43200-43219
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43204 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43200-43219
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43205 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43200-43219
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 244 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43206 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43200-43219
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43207 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43200-43219
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43208 Genset Model Read Only Multiplier: 1 Number indentifying the PC 2.x,
Number Offset: 0 model of this generator set. PC 3.x
Size (bits): 168 Modbus uses addresses
43200-43219 for the 20
Sign: C
characters of this string.
Unit:
Lower Limit:
Upper Limit:
43209 Genset Model Read Only Multiplier: 1 Number indentifying the PC 2.x,
Number Offset: 0 model of this generator set. PC 3.x
Size (bits): 168 Modbus uses addresses
43200 - 43219 for the 20
Sign: C
characters of this string.
Unit:
Lower Limit:
Upper Limit:
43210 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43200-43219
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43211 Genset Model Read Only Multiplier: 1 Number indentifying the PC 2.x,
Number Offset: 0 model of this generator set. PC 3.x
Size (bits): 168 Modbus uses addresses
43200-43219 for the 20
Sign: C
characters of this string.
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 245 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43212 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43200-43219
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43213 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43200-43219
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43214 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43200-43219
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43215 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43200-43219
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43216 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43200-43219
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43217 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43200-43219
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 246 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43218 Genset Model Read Only Multiplier: 1 Number indentifying the PC 2.x,
Number Offset: 0 model of this generator set. PC 3.x
Size (bits): 168 Modbus uses addresses
43200-43219 for the 20
Sign: C
characters of this string.
Unit:
Lower Limit:
Upper Limit:
43219 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43200-43219
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43220 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43221 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43222 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string. Uses logical addresses
Unit: 2048 - 6063 to store the first
Lower Limit: 16 characters. The last 4 are
Upper Limit: stored in 691-694.

43223 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 247 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43224 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43225 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43226 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43227 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43228 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43229 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 248 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43230 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43231 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43232 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43233 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43234 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43235 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 249 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43236 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43237 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43238 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43239 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
Size (bits): 168 uses addresses 43220-43239
for the 20 characters of this
Sign: C
string.
Unit:
Lower Limit:
Upper Limit:
43240 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43241 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 250 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43242 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43243 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43244 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43245 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43246 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43247 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 251 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43248 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43249 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43250 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43251 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

43252 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,


Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43253 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 252 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43254 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43255 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43256 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43257 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43258 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43259 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number Size (bits): 168 model number. Modbus uses
addresses 43240-43259 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 253 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43260 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43261 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

43262 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,


Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43263 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43264 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43265 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 254 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43266 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

43267 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,


Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43268 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

Addr. Parameter Access Specifications Description Control


43269 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43270 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 255 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43271 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43272 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43273 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

43274 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,


Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43275 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43276 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 256 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43277 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x, PC
Serial Offset: 0 this generator sets alternator 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43278 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43279 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number Size (bits): 168 serial number. Modbus uses
addresses 43260-43279 for
Sign: C
the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43280 Coolant Level Read Only 0: Inactive Coolant Level input software PC 2.x,
Switch 1: Active state status. Gives software PC 3.x
Inactive/Active state
43281 Coolant Read Only 0: Inactive This is the status of the PC 2.x,
Level/Configu 1: Active Configurable Input #5. PC 3.x
rable Input #5
Switch
43283 Fault Reset Read Only 0: Inactive Fault Reset input software PC 2.x,
Switch 1: Active state status. Gives software PC 3.x
Inactive/Active state
43284 Fault Read Only 0: Inactive This is the status of the PC 2.x,
Reset/Config 1: Active Configurable Input #10. PC 3.x
urable Input
#10 Switch
43285 Genset CB Read Only 0: Inactive This is the status of the PC 3.x
Inhibit/Config 1: Active Configurable Input #28.
urable Input
#28 Switch
43286 Genset CB Read Only 0: Inactive This is the status of the PC 3.x
Pos 1: Active Configurable Input #26.
B/Configurabl
e Input #26
Switch

A029X159 (Issue 19) 257 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43287 Genset CB Read Only 0: Inactive This is the status of the PC 3.x
Tripped/Confi 1: Active Configurable Input #27.
gurable Input
#27 Switch
43288 Genset CB Read Only 0: Inactive Genset CB Inhibit input PC 3.x
Inhibit Switch 1: Active software state status. Gives
software Inactive/Active state
43289 Genset CB Read Only 0: Inactive Genset CB Pos A input PC 3.x
Pos A Switch 1: Active software state status. Gives
software Inactive/Active state
43290 Genset CB Read Only 0: Inactive Genset CB Pos B input PC 3.x
Pos B Switch 1: Active software state status. Gives
software Inactive/Active state
43291 Genset CB Read Only 0: Inactive Genset CB Tripped input PC 3.x
Tripped 1: Active software state status. Gives
Switch software Inactive/Active state
43292 Ground Fault Read Only 0: Inactive Ground Fault Switch function PC 2.x,
Switch 1: Active output status. Gives software PC 3.x
Inactive/Active state
43293 High Alt Read Only 0: Inactive High Alt Temperature Switch PC 2.x,
Temp Switch 1: Active function output status. Gives PC 3.x
software Inactive/Active state
43295 Load Read Only 0: Inactive This is the status of the PC 3.x
Demand 1: Active Configurable Input #31.
Stop/Configur
able Input
#31 Switch
43296 Local E-stop Read Only 0: Inactive Monitors the E–Stop switch. PC 2.x,
Switch 1: Active PC 3.x
43297 Low Coolant Read Only 0: Inactive Low Coolant #2 Switch PC 2.x,
#2 Switch 1: Active function output status. Gives PC 3.x
software Inactive/Active state
43298 Low Engine Read Only 0: Inactive Low Engine Temperature PC 2.x,
Temperature 1: Active Switch function output status. PC 3.x
Switch Gives software Inactive/Active
state
43299 Low Fuel In Read Only 0: Inactive Low Fuel In Day Tank Switch PC 2.x,
Day Tank 1: Active function output status. Gives PC 3.x
Switch software Inactive/Active state
43300 Genset Bus Read/Write 0: Delta Delta or Wye for Utility PC 3.x
Delta/Wye 1: Wye connection
Connection

Copyright © 2017 Cummins Inc. 258 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43301 Genset Bus Read Only Multiplier: 1 Generator set Bus nominal PC 3.x
Nominal Offset: 0 voltage
Voltage Size (bits): 16
Sign: U
Unit: Vac
Lower Limit: 110
Upper Limit: 45000
43302 Genset Read Only 0: Delta Delta or Wye for Generator PC 2.x,
Delta/Wye 1: Wye set connection PC 3.x
Connection
43303 Genset Read Only Multiplier: 1 Generator set nominal line- PC 2.x,
Nominal Offset: 0 line voltage PC 3.x
Voltage Size (bits): 16
Sign: U
Unit: Vac
Lower Limit: 110
Upper Limit: 45000
43304 Single/3 Read Only 0: Single Phase Setup mode interlocked. PC 2.x,
Phase 1: Three Phase Generator set’s single PC 3.x
Connection phase/3 phase metering
setup configuration.
43306 Utility Read/Write 0: Delta Delta or Wye for Utility PC 3.x
Delta/Wye 1: Wye connection
Connection
43307 Utility Read Only Multiplier: 1 Utility nominal voltage PC 3.x
Nominal Offset: 0
Voltage Size (bits): 16
Sign: U
Unit: Vac
Lower Limit: 110
Upper Limit: 45000
43309 Overfrequenc Read/Write 0: Disabled Enables over frequency PC 2.x,
y Enable 1: Enabled diagnostic witness test. PC 3.x
43310 Overload Read/Write Multiplier: 1 The time delay until an PC 2.x,
Warning Set Offset: 0 overload condition is reported PC 3.x
Time Size (bits): 8 as a fault
Sign: U
Unit: seconds
Lower Limit: 1
Upper Limit: 120

A029X159 (Issue 19) 259 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43311 Overload Read/Write Multiplier: 0.01 Sets the Overload Warning PC 2.x,
Warning Offset: 0 fault trip threshold as PC 3.x
Threshold Size (bits): 16 percentage of generator set
application kW rating.
Sign: U
Unit: %
Lower Limit: 80
Upper Limit: 140
43312 Overload Read / Write Multiplier : 1 The time delay until an PC 3.x
Shutdown Set Offset: 0 overload condition is reported
Time Size (bits): 16 as Shutdown fault
Sign: U
Units: Seconds
Lower Limit: 1
Upper Limit: 120
Default: 60
43313 Overload Read / Write Multiplier : 0.01 Sets the Overload Shutdown PC 3.x
Shutdown Offset: 0 fault trip threshold as
threshold Size (bits): 16 percentage of genset
application kW rating. To
Sign: U
disable the Overload
Units: % shutdown fault set the value
Lower Limit: 70 to 655.35 or Not Available.
Upper Limit: 655.35
Default: 655.35
43314 Prelube Read / Write 0: GCS Selects whether prelube PC 3.x
Function 1: ECS function is being controlled by
Owner GCS or ECS
43315 Non Read / Write 0: Allow Start Selects whether to allow or PC 3.x
Lubricated 1: Block Start block genset starting when
Non- not lubricated in case of Non-
Emergency Emergency start. Applicable
Start only when Prelube Function
Owner = ECS
43338 CAN Failure Read/Write Multiplier: 1 Sets the maximum number of PC 2.x,
Retries Offset: 0 CAN communication retries PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 10
43339 Auto Sleep Read/Write 0: Awake in Auto Trim that determines if the PC 2.x,
Enable 1: Sleep in Auto control will stay awake in PC 3.x
Auto mode or Fall asleep in
Auto mode.

Copyright © 2017 Cummins Inc. 260 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43340 Max Setup Read/Write Multiplier: 1 Max time allowed in Setup PC 2.x,
Mode Time Offset: 0 Mode. PC 3.x
Size (bits): 16
Sign: U
Unit: Seconds
Lower Limit: 30
Upper Limit: 3600
43341 Power Down Read/Write 0: Disable Trim to enable Sleep Mode PC 2.x,
Mode Enable 1: Enable PC 3.x
43342 Power Down Read/Write Multiplier: 1 Timer setting for the Power PC 2.x,
Mode Time Offset: 0 Down delay feature PC 3.x
Delay Size (bits): 16
Sign: U
Unit: Seconds
Lower Limit: 0
Upper Limit: 600
43343 Setup Mode Read/Write 0: Disable Volatile to allow entry into PC 2.x,
Enable 1: Enable Setup Mode PC 3.x
43344 Clock Date Read/Write Multiplier: 1 Use to set or read the current PC 2.x,
Offset: 0 date. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 31
43345 Clock Hour Read/Write Multiplier: 1 Use to set or read the current PC 2.x,
Offset: 0 hour. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 32
43346 Clock Minute Read/Write Multiplier: 1 Use to set or read the current PC 2.x,
Offset: 0 minute. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 59
43347 Clock Mode Read/Write 0: Normal Use to set the real time clock PC 2.x,
1: Set Clock and save settings. PC 3.x
2: Save Clock

A029X159 (Issue 19) 261 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43348 Clock Month Read/Write Multiplier: 1 Use to set or read the current PC 2.x,
Offset: 0 month. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 12
43349 Clock Second Read/Write Multiplier: 1 Use to set or read the current PC 2.x,
Offset: 0 second. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 59
43350 Clock Year Read/Write Multiplier: 1 Use to set or read the current PC 2.x,
Offset: 0 year. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 99
43351 Daylight Read/Write Multiplier: 1 Use to set the hour of the day PC 2.x,
Savings End Offset: 0 when daylight savings time PC 3.x
Hour Size (bits): 8 ends.
Sign: U
Unit:
Lower Limit: 2
Upper Limit: 19
43352 Daylight Read/Write Multiplier: 1 Use to set the month when PC 2.x,
Savings End Offset: 0 daylight savings time ends. PC 3.x
Month Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 12
43353 Daylight Read/Write 0: First Occurrence Use to set the week of the PC 2.x,
Savings End 1: Second Occurrence month when daylight savings PC 3.x
Week 2: Third Occurrence time ends.
Occurrence in
3: Fourth Occurrence
Month
4: Last Occurrence

Copyright © 2017 Cummins Inc. 262 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43354 Daylight Read/Write 0: Sunday Use to set the day of the PC 2.x,
Savings Start 1: Monday week when daylight savings PC 3.x
Day 2: Tuesday time starts.
3: Wednesday
4: Thursday
5: Friday
6: Saturday
43355 Daylight Read/Write Multiplier: 1 Use to set the hour of the day PC 2.x,
Savings Start Offset: 0 when daylight savings time PC 3.x
Hour Size (bits): 8 starts.
Sign: U
Unit:
Lower Limit: 2
Upper Limit: 19
43356 Daylight Read/Write Multiplier: 1 Use to set the month when PC 2.x,
Savings Start Offset: 0 daylight savings time starts. PC 3.x
Month Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 12
43357 Daylight Read/Write 0: First Occurrence Use to set the week of the PC 2.x,
Savings Start 1: Second Occurrence month when daylight savings PC 3.x
Week 2: Third Occurrence time starts.
Occurrence in
3: Fourth Occurrence
Month
4: Last Occurrence
43358 Daylight Read/Write Multiplier: 1 Use to set the amount of PC 2.x,
Savings Time Offset: 0 daylight savings time PC 3.x
Adjustment Size (bits): 8 adjustment applied.
Sign: U
Unit: Minutes
Lower Limit: 0
Upper Limit: 120
43359 Daylight Read/Write 0: Disabled Use to enable the daylight PC 2.x,
Savings Time 1: Enabled savings time feature. PC 3.x
Enable
43360 Exercise Read/Write 0: Disabled Enables the exercise PC 2.x,
Scheduler 1: Enabled scheduler. PC 3.x
Enable
43361 Reset Fuel Read/Write 0: Inactive The reset trip fuel PC 2.x,
Consumption 1: Active consumption command. PC 3.x
43362 Reset Runs Read/Write 0: Inactive The reset runs command. PC 2.x,
1: Active PC 3.x

A029X159 (Issue 19) 263 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43363 Reset Start Read/Write 0: Inactive The reset start attempts PC 2.x,
Attempts 1: Active command. PC 3.x
43364 Scheduler Read/Write Multiplier: 1 Used to select an exception PC 2.x,
Exception Offset: 0 to adjust. PC 3.x
Select Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 6
43365 Scheduler Read / Write Multiplier : 1 Used to adjust the date for PC 2.x,
Exception x Offset: 0 the selected exception. PC 3.x
Date Size (bits): 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 31
43366 Scheduler Read / Write Multiplier : 1 Used to adjust the length in PC 2.x,
Exception x Offset: 0 days for the selected PC 3.x
Duration Size (bits): 8 exception.
Days
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 44
43367 Scheduler Read / Write Multiplier : 1 Used to adjust the length in PC 2.x,
Exception x Offset: 0 hours for the selected PC 3.x
Duration Size (bits): 8 exception.
Hours
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23
43368 Scheduler Read / Write Multiplier : 1 Used to adjust the length in PC 2.x,
Exception x Offset: 0 minutes for the selected PC 3.x
Duration Size (bits): 8 exception.
Minutes
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 0
43369 Scheduler Read / Write 0 : Disable Used to enable or disable the PC 2.x,
Exception x 1 : Enable selected exception. PC 3.x
Enable

Copyright © 2017 Cummins Inc. 264 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43370 Scheduler Read / Write Multiplier : 1 Used to adjust the starting PC 2.x
Exception x Offset: 0 hour for the selected PC 3.x
Hour Size (bits): 8 exception.
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 0
43371 Scheduler Read / Write Multiplier : 1 Used to adjust the starting PC 2.x,
Exception x Offset: 0 minute for the selected PC 3.x
Minute Size (bits): 8 exception.
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 0
43372 Scheduler Read / Write Multiplier : 1 Used to adjust the starting PC 2.x,
Exception x Offset: 0 month for the selected PC 3.x
Month Size (bits): 8 exception.
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: 1
43373 Scheduler Read / Write 0: Once Only Used to adjust the repeat PC 2.x,
Exception x 1: Every Year interval for the selected PC 3.x
Repeat exception.
43374 Scheduler Read/Write Multiplier: 1 Used to select a program to PC 2.x,
Program Offset: 0 adjust. PC 3.x
Select Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 12
43375 Scheduler Read / Write Multiplier : 1 Used to adjust the length in PC 2.x,
Program x Offset: 0 hours for the selected PC 3.x
Duration Size (bits): 8 program.
Hours
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 0

A029X159 (Issue 19) 265 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43376 Scheduler Read / Write Multiplier : 1 Used to adjust the length in PC 2.x,
Program x Offset: 0 minutes for the selected PC 3.x
Duration Size (bits): 8 program.
Minutes
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 0
43377 Scheduler Read/Write 0: Disable Used to enable or disable the PC 2.x,
Program x 1: Enable selected program. PC 3.x
Enable
43378 Scheduler Read / Write 0: Once Used to adjust the repeat PC 2.x,
Program x 1: Every Week interval for the selected PC 3.x
Repeat 2: Every 2 Weeks program.
Interval
3: Every 3 Weeks
4: Every 4 Weeks
5: Every 5 Weeks
6: First Week of Month
7: Second Week of Month
8: Third Week of Month
9: Fourth Week of Month
10: Last Week of Month
43379 Scheduler Read/Write 0: No Load Used to adjust the run mode PC 3.x
Program x 1: With Load for the selected program.
Run Mode 2: Extended Parallel
43380 Scheduler Read / Write 0: Sunday Used to adjust the start day PC 2.x,
Program x 1: Monday of the week for the selected PC 3.x
Start Day 2: Tuesday program.
3: Wednesday
4: Thursday
5: Friday
6: Saturday
43381 Scheduler Read / Write Multiplier : 1 Used to adjust the start hour PC 2.x,
Program x Offset: 0 for the selected program. PC 3.x
Start Hour Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 0

Copyright © 2017 Cummins Inc. 266 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43382 Scheduler Read / Write Multiplier : 1 Used to adjust the start PC 2.x,
Program x Offset: 0 minute for the selected PC 3.x
Start Minute Size (bits): 8 program.
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 0
43383 Daylight Read/Write 0: Sunday Use to set the day of the PC 2.x,
Savings End 1: Monday week when daylight savings PC 3.x
Day 2: Tuesday time ends.
3: Wednesday
4: Thursday
5: Friday
6: Saturday
43501 Genset Run Read Only 0: Emergency Remote Start Source or type of current PC 2.x,
Type 1: Non Emergency Remote genset run (if running) or PC 3.x
Start previous genset run (if
2: Load Demand Start stopped).
3: Manual Run
4: Exercise
43502 Idle Rated Read Only 0: Idle The output command of the PC 2.x,
Command 1: Rated Idle/Rated Logic PC 3.x
43503 Idle Request Read Only 0: False Indicates a request to go to PC 2.x,
1: True manual idle. Manual idle PC 3.x
allowed if breaker is open or
not controlled
43506 Load Dump Read Only 0: Inactive Monitors the software PC 2.x,
Command 1: Active command to the load dump PC 3.x
2: Reserved driver output
3: Not Available
43507 Load Dump Read Only 0: Inactive Monitors the state of the load PC 2.x,
Overload 1: Active dump overload detection PC 3.x
Condition 2: Reserved algorithm
3: Not Available
43508 Load Dump Read Only 0: Inactive The state of the load dump PC 2.x,
Underfrequen 1: Active underfrequency detection PC 3.x
cy Condition 2: Reserved algorithm
3: Not Available

A029X159 (Issue 19) 267 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43509 Low Battery Read Only Multiplier: 0.1 The low battery voltage PC 2.x,
Voltage Offset: 0 threshold when the generator PC 3.x
Running Size (bits): 16 set is in rated mode
Threshold
Sign: U
Unit: Vdc
Lower Limit:
Upper Limit:
43510 Low Battery Read Only Multiplier: 0.1 The low battery voltage PC 2.x,
Voltage Offset: 0 threshold when the generator PC 3.x
Stopped Size (bits): 16 set is not in rated mode
Threshold
Sign: U
Unit: Vdc
Lower Limit:
Upper Limit:
43511 Low Battery Read Only Multiplier: 0.1 The selection of the running PC 2.x,
Voltage Offset: 0 or stopped threshold PC 3.x
Threshold Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit:
Upper Limit:
43512 Manual Read Only 0: Not Manual The output of the Manual PC 2.x,
Command 1: Manual Command OR logic PC 3.x
43513 Manual Read Only Multiplier : 1 Bitmask to show the inputs to PC 2.x,
Command Offset: 0 the Command output which PC 3.x
Inputs Size (bits): 8 are currently on
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
43515 Oil Priming Read Only 0: Inactive The Prelube Driver PC 2.x,
Pump 1: Active Command. PC 3.x
Command 2: Reserved
3: Not Available
43516 Prelube Mode Read Only 0: Crank After Prelube Set to a required mode based PC 2.x,
1: Crank With Prelube on the type of starting PC 3.x
2: Prelube Only requirement

43517 Prelube State Read Only 0: Complete The monitor point for the PC 2.x,
1: Armed prelube state. PC 3.x
2: Prelube Output ON
3: Prelube Output OFF
4: Enable Crank

Copyright © 2017 Cummins Inc. 268 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43518 PTC Genset Read Only 0: Off Current mode for the genset PC 3.x
Operating 1: Manual operation part of the PTC
Mode 2: Normal function
3: Normal Override
4: Test
5: Exercise
6: Utility Fail
7: Extended Parallel
43519 PTC Mode Read Only 0: Inactive The output of the PTC Mode PC 3.x
Switch 1: Active Switch Command OR logic
Command 2: Reserved
3: Not Available
43520 PTC Mode Read Only Multiplier : 1 Bitmask to show the inputs to PC 3.x
Switch Offset: 0 the Command output which
Command Size (bits): 8 are currently on.
Inputs
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
43521 PTC Status Read Only 0: Off/ Not Enabled Indicates what the current PC 3.x
1: Manual Mode state is of PTC control action
2: Normal Utility
3: Retransfer
4: Retransfer Override
5: Emergency Test
6: Normal Test
7: Exercise
8: Utility Failure
9: Extended Parallel
43522 PTC Transfer Read Only 0: Off Operation mode for the PC 3.x
Pair 1: Manual breaker pair portion of the
Operating 2: Normal PTC function
Mode
3: Normal Override
4: Test
5: Exercise
6: Utility Fail
7: Extended Parallel
43523 Ready to Read Only 0: Inactive The state that the Ready to PC 2.x,
Load 1: Active Load Driver output is being PC 3.x
Command 2: Reserved commanded to
3: Not Available
43524 Remote Start Read Only 0: Stop The output of the Remote PC 2.x,
Command 1: Start Start Command OR logic PC 3.x

A029X159 (Issue 19) 269 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43526 Remote Start Read Only 0: Off Status of remote start and PC 2.x,
State 1: Remote Start load demand stop inputs PC 3.x
2: Load Demand Stop
3: Load Demand Start
43527 RMS Read Only Multiplier : 0.01 The RMS voltage (or current) PC 2.x,
Regulation Offset: 0 error at the AVR PC 3.x
Error Size (bits): 16
Sign: S
Units: %
Lower Limit: -100
Upper Limit: 100
Default: NA
43528 Run Read Only 0: Off The signal that is PC 2.x,
Command 1: Run commanding a change to the PC 3.x
run mode
43529 Run Relay Read Only 0: Inactive The status of relay command PC 2.x,
Command 1: Active when genset is in frequency PC 3.x
and rated mode.
43530 Speed and Read Only 0: Inactive Monitor point for the PC 3.x
Voltage Bias 1: Active command which closes the
Relay on-board relay enabling the
Command voltage and speed bias
outputs.
43531 Speed Bias Read Only Multiplier : 0.01 Indicates amount of speed PC 3.x
Command Offset: 0 bias offset GCS is
Size (bits): 16 commanding to ECS
governor or external governor
Sign: S
Units: %
Lower Limit: 0
Upper Limit: NA
Default: NA
43533 Start Read Only Multiplier: 1 Time remaining until start is PC 2.x,
Countdown Offset: 0 initiated PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 300
Default: NA
43536 Start Type Read Only 0: Emergency The output of the Start Type PC 2.x,
Command 1: Non Emergency Command OR logic PC 3.x

Copyright © 2017 Cummins Inc. 270 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43537 Start Type Read Only Multiplier : 1 Bitmask to show the inputs to PC 2.x,
Command Offset: 0 the Command output which PC 3.x
Inputs Size (bits): 8 are currently on
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
43538 Starter Read Only 0: Inactive State of hardware output. PC 2.x,
Command 1: Active PC 3.x
2: Reserved
3: Not Available
43539 Stop Read Only Multiplier: 1 Time remaining until PC 2.x,
Countdown Offset: 0 generator set stops PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 5000
43540 Switch Panel Read Only 0: None Status of run and exercise PC 2.x,
Run Request 1: Manual commands from display panel PC 3.x
2: Exercise
43542 Target Read Only Multiplier : 0.01 The target voltage without PC 2.x,
Voltage Offset: 0 ramping and torque match PC 3.x
Size (bits): 16 voltage rolloff effects
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 150
Default: NA
43543 Time At No Read Only Multiplier: 1 Amount of time the generator PC 2.x,
Load Offset: 0 set has run at no load PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 600
Default: NA

A029X159 (Issue 19) 271 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43544 Time at Read Only Multiplier: 1 Amount of time spend in PC 2.x,
Rated Offset: 0 Rated Cooldown PC 3.x
Cooldown Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 5000
43546 Voltage Bias Read Only Multiplier : 0.01 Indicates amount of voltage PC 3.x
Command Offset: 0 bias offset GCS is
Size (bits): 16 commanding to an external
regulator
Sign: S
Units: %
Lower Limit: 0
Upper Limit: NA
Default: NA
43547 Voltage Read Only Multiplier: 0.01 The voltage setpoint PC 2.x,
Setpoint Offset: 0 command PC 3.x
Size (bits): 16
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 150
43550 Weak Battery Read Only Multiplier: 0.1 Monitor point for the weak PC 2.x,
Threshold Offset: 0 battery voltage threshold PC 3.x
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 6
Upper Limit: 16
43551 Weak Battery Read/Write Multiplier: 1 The time delay until a weak PC 2.x,
Voltage Set Offset: 0 battery condition is reported PC 3.x
Time Size (bits): 16 as a fault
Sign: U
Unit: seconds
Lower Limit: 1
Upper Limit: 5
43552 Paralleling Read Only Multiplier : 0.01 Voltage offset to voltage PC 2.x,
Voltage Ref Offset: 0 regulator for paralleling PC 3.x
Offset Size (bits): 16 function
Sign: S
Units: %
Lower Limit: NA
Upper Limit: NA

Copyright © 2017 Cummins Inc. 272 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43553 Synchronizer Read Only 0: Synchronizer Off Indicates whether PC 3.x
Status 1: Synchronizer On synchronizer is on or off

43554 Active Read Only Multiplier: 0.1 Countdown value of the PC 3.x
Transition Offset: 0 active transition timer
Timer Size (bits): 16
Sign: U
Unit: seconds
Lower Limit:
Upper Limit:
43555 Active Read Only 0: None Indicates the active transition PC 3.x
Transition 1: Programmed Transition type for PTC
Type 2: Transfer
3: Retransfer
4: Max Parallel
43556 Arbitration Read Only 0: Off Indicates current arbitration PC3.x
State 1: Arbitrate0 state
2: Winner
3: Arbitrate1
4: Sleep
43557 Arbitration Read Only Multiplier : 1 Arbitration loop countdown PC 3.x
Timer Offset: 0 timer
Size (bits): 16
Sign: U
Units: msec
Lower Limit: NA
Upper Limit: NA
Default: NA
43567 Genset Read Only 0: Unknown Indicates genset breaker PC 3.x
Current 1: Closed position based on current
Based
Breaker
Position
43558 ES State Read Only 0: Standby Internal paralleling status PC 3.x
1: Dead Bus variable
2: Synchronize
3: Load Share
4: Load Govern

43559 First Start Read Only 0: First Start Not Allowed Indicates status of the first PC 3.x
State 1: First Start Requested start system
2: First Start Permitted
43560 Genset CB Read Only 0: Inactive Generator set cb close PC 3.x
Close 1: Active command status
Command

A029X159 (Issue 19) 273 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43561 Genset CB Read Only 0: Inactive Status of gen fail to close PC 3.x
Fail To Close 1: Active lockout function
Lockout
43562 Genset CB Read Only 0: Open Indicates generator set PC 3.x
Position 1: Closed breaker position
Status 2: Not Available
43563 Genset Read Only 0: Not Available Indicates status of the PC 3.x
Availability 1: Available generator set source
Status 2: Unknown
43564 Bus Status Read Only 0: Unavailable Indicates status of the bus PC 3.x
1: Dead
2: Live
43565 Genset CB Read Only 0: Inactive Generator set cb inhibit PC 3.x
Inhibit 1: Active command
Command
43566 Genset CB Read Only 0: Inactive Generator set cb tripped PC 3.x
Tripped 1: Active command
Command
43568 Genset Read Only Multiplier: 0.1 Indicates the lower drop-out PC 3.x
Frequency Offset: 0 threshold in Hz for generator
Lower Drop- Size (bits): 16 set frequency sensor
Out
Sign: U
Threshold
Unit: Hz
Lower Limit:
Upper Limit:
43569 Genset Read Only Multiplier: 0.1 Indicates the lower pick-up PC 3.x
Frequency Offset: 0 threshold in Hz for generator
Lower Pick- Size (bits): 16 set frequency sensor
Up Threshold
Sign: U
Unit: Hz
Lower Limit:
Upper Limit
43570 Genset Read Only 0: Unknown Indicates generator set PC 3.x
Frequency 1: Picked Up frequency sensor status
Sensor 2: Dropped Out
Status
43571 Genset Read Only Multiplier: 0.1 Indicates the upper drop-out PC 3.x
Frequency Offset: 0 threshold in Hz for generator
Upper Drop- Size (bits): 16 set frequency sensor
Out
Sign: U
Threshold
Unit: Hz
Lower Limit:
Upper Limit

Copyright © 2017 Cummins Inc. 274 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43572 Genset Read Only Multiplier: 0.1 Indicates the upper pick-up PC 3.x
Frequency Offset: 0 threshold in Hz for generator
Upper Pick- Size (bits): 16 set frequency sensor
Up Threshold
Sign: U
Unit: Hz
Lower Limit:
Upper Limit
43573 Genset Loss Read Only 0: Unknown Indicates generator set loss PC 3.x
of Phase 1: Picked Up of phase sensor status
Sensor 2: Dropped Out
Status
43574 Genset Read Only Multiplier: 1 Indicates the drop-out PC 3.x
Overvoltage Offset: 0 threshold in volts for
Drop-Out Size (bits): 16 generator set over voltage
Threshold sensor
Sign: U
Unit: Vac
Lower Limit:
Upper Limit
43575 Genset Read Only Multiplier: 1 Indicates the pick-up PC 3.x
Overvoltage Offset: 0 threshold in volts for
Pick-Up Size (bits): 16 generator set over voltage
Threshold sensor
Sign: U
Unit: Vac
Lower Limit:
Upper Limit
43576 Genset Read Only 0: Unknown Indicates generator set over PC 3.x
Overvoltage 1: Picked Up voltage sensor status
Sensor 2: Dropped Out
Status
43577 Genset Read Only 0: Unknown Indicates generator set phase PC 3.x
Phase 1: Picked Up rotation sensor status
Rotation 2: Dropped Out
Sensor
Status
43578 Genset Read Only Multiplier: 1 Indicates the drop-out PC 3.x
Undervoltage Offset: 0 threshold in volts for
Drop-Out Size (bits): 16 generator set under voltage
Threshold sensor
Sign: U
Unit: Vac
Lower Limit:
Upper Limit

A029X159 (Issue 19) 275 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43579 Genset Read Only Multiplier: 1 Indicates the pick-up PC 3.x
Undervoltage Offset: 0 threshold in volts for
Pick-Up Size (bits): 16 generator set under voltage
Threshold sensor
Sign: U
Unit: Vac
Lower Limit:
Upper Limit
43580 Genset Read Only 0: Unknown Indicates generator set under PC 3.x
Undervoltage 1: Picked Up voltage sensor status
Sensor 2: Dropped Out
Status
43581 Master First Read Only 0: Inactive Status of the first start output PC 3.x
Start Output 1: Active command
Command
43582 Maximum Read Only Multiplier : 0.1 Countdown value of the PC 3.x
Parallel Timer Offset: 0 maximum parallel timer
Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: NA
Upper Limit: NA
Default: NA
43583 Maximum Read Only 0: Not Timing Indicates status of the PC 3.x
Parallel Timer 1: Timing maximum parallel timer
Status 2: Expired
43584 Paralleling Read Only 0: Isochronous Indicates which speed control PC 2.x,
Speed 1: Droop algorithm is in effect PC 3.x
Control Mode 2: Synchronize
3: Load Share
4: Load Govern
43585 Paralleling Read Only 0: Isochronous Indicates which voltage PC 2.x,
Voltage 1: Droop control algorithm is in effect PC 3.x
Control Mode 2: Synchronize
3: Load Share
4: Load Govern
43586 Programmed Read Only Multiplier : 0.1 Countdown value of the PC 3.x
Transition Offset: 0 programmed transition timer
Timer Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: NA
Upper Limit: NA
Default: NA

Copyright © 2017 Cummins Inc. 276 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43587 Programmed Read Only 0: Not Timing Indicates status of the PC 3.x
Transition 1: Timing programmed transition timer
Timer Status 2: Expired
43588 PTC Enable Read Only 0: Disable Indicates if PTC functions are PC 3.x
Status 1: Enable running

43589 PTC Read Only 0: Open Transition Indicates the transition type PC 3.x
Operating 1: Hard Closed Transition currently in effect
Transition 2: Soft Closed Transition
Type
43590 PTC State Read Only 0: PTC Not Enabled Indicates the connected state PC 3.x
1: No Source Connected of the Power Transfer Control
2: Utility Connected
3: Genset Connected
4: Paralleled
43591 Retransfer Read Only Multiplier: 0.1 Countdown value of the PC 3.x
Timer Offset: 0 retransfer timer
Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: NA
Upper Limit: NA
Default: NA
43592 Retransfer Read Only 0: Not Timing Indicates status of the PC 3.x
Timer Status 1: Timing retransfer timer
2: Expired
43593 Speed Droop Read Only 0: Inactive Command value of speed PC 2.x,
Enable 1: Active droop enable PC 3.x
Command
43594 Speed Droop Read Only 0: Droop Disabled Indicates whether or not PC 2.x,
Status 1: Droop Enabled speed droop is in effect PC 3.x
43595 Transfer Read Only Multiplier : 0.1 Countdown value of the PC3.x
Timer Offset: 0 transfer timer
Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: NA
Upper Limit: NA
Default: NA
43596 Transfer Read Only 0: Not Timing Indicates status of the PC 3.x
Timer Status 1: Timing transfer timer
2: Expired

A029X159 (Issue 19) 277 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43597 Utility CB Read Only 0: Inactive Utility cb close command PC 3.x
Close 1: Active status
Command
43598 Utility CB Read Only 0: Inactive Utility cb open command PC 3.x
Open 1: Active status
Command
43599 Utility CB Read Only 0: Open Indicates utility breaker PC 3.x
Position 1: Closed position
Status 2: Not Available
43600 Load Govern Read/Write 0: Genset kW Use to select how generator PC 3.x
kW Method 1: Genset kW w/Utility set kW output will be
Constraint controlled when paralleled to
2: Utility kW utility.

43608 Configurable Read/Write Multiplier: 1 The event code for this PC 2.x,
Output #1 Offset: 0 output. PC 3.x
Event Code Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43610 Configurable Read/Write Multiplier: 1 The event code for this PC 2.x,
Output #2 Offset: 0 output. PC 3.x
Event Code Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43613 Configurable Read/Write Multiplier: 1 The event code for this PC 3.x
Output #20 Offset: 0 output.
Event Code Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43616 Configurable Read/Write Multiplier: 1 The event code for this PC 3.x
Output #21 Offset: 0 output.
Event Code Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

Copyright © 2017 Cummins Inc. 278 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43619 Configurable Read/Write Multiplier: 1 The event code for this PC 3.x
Output #22 Offset: 0 output.
Event Code Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43622 Configurable Read/Write Multiplier: 1 The event code for this PC 2.x,
Output #3 Offset: 0 output. PC 3.x
Event Code Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43625 Configurable Read/Write Multiplier: 1 The event code for this PC 2.x,
Output #4 Offset: 0 output. PC 3.x
Event Code Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43641 Delayed Read/Write 0: Disabled Enables the Delayed PC 2.x,
Shutdown 1: Enabled Shutdown feature. PC 3.x
Enable
43642 Delayed Read/Write Multiplier: 0.1 Sets the shutdown fault PC 2.x,
Shutdown Offset: 0 delayed time delay for the PC 3.x
Time Delay Size (bits): 16 Delayed Shutdown feature.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 3
43643 Remote Fault Read/Write 0: Disable Trim to enable Remote Fault PC 2.x,
Reset 1: Enable Reset. Can only reset PC 3.x
Enabled Warning Faults
43644 Fail To Read/Write Multiplier: 1 Trim to set the time for a PC 2.x, PC
Shutdown Offset: 0 shutdown fault to be active 3.x
Delay Size (bits): 16 and the generator set not
shutting down before the Fail
Sign: U
to Shutdown fault occurs.
Unit: seconds
Lower Limit: 0
Upper Limit: 30
43645 LCL Read/Write 0: None Sets low coolant level fault PC 2.x,
Detection 1: Warning response to None, Warning, PC 3.x
Response 2: Shutdown or Shutdown.

A029X159 (Issue 19) 279 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43646 LCT Warning Read/Write Multiplier: 1 Sets time to clear the low PC 2.x,
Clear Time Offset: 0 coolant temperature fault. PC 3.x
Size (bits): 8
Sign: U
Unit: Minutes
Lower Limit: 0
Upper Limit: 30
43647 LCT Warning Read/Write Multiplier: 1 Sets time to set the low PC 2.x,
Set Time Offset: 0 coolant temperature fault. PC 3.x
Size (bits): 8
Sign: U
Unit: Minutes
Lower Limit: 0
Upper Limit: 30
43648 LCT Warning Read/Write Multiplier: 1 Sets threshold for the low PC 2.x,
Threshold Offset: 0 coolant temperature fault PC 3.x
Size (bits): 16 warning.
Sign: S
Unit: degF
Lower Limit: -20
Upper Limit: 100
43649 V/Hz Knee Read/Write Multiplier: 0.1 The voltage will roll off PC 2.x,
Frequency Offset: 0 (decrease) proportionally to PC 3.x
Size (bits): 16 the V/Hz setup, once the
frequency drops below the
Sign: U
set point in the V/Hz Knee
Unit: Hz Frequency. This allows the
Lower Limit: 0 generator set to recover
Upper Limit: 10 faster when the frequency
drops.
43650 V/Hz Rolloff Read/Write Multiplier: 0.1 The amount of voltage roll off PC 2.x,
Slope Offset: 0 when the frequency is below PC 3.x
Size (bits): 16 the knee frequency
Sign: U
Unit: % / Hz
Lower Limit: 0
Upper Limit: 10
43651 12 V High Read Only Multiplier: 0.1 Sets 12V high battery voltage PC 2.x,
Battery Offset: 0 fault threshold. PC 3.x
Voltage Size (bits): 16
Threshold
Sign: U
Unit: Vdc
Lower Limit: 14
Upper Limit: 17

Copyright © 2017 Cummins Inc. 280 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43652 12 V Low Read Only Multiplier: 0.1 Sets 12V low battery voltage PC 2.x,
Battery Offset: 0 fault threshold for generator PC 3.x
Voltage Size (bits): 16 set operation while in rated
Running mode
Sign: U
Threshold
Unit: Vdc
Lower Limit: 12
Upper Limit: 16
43653 12 V Low Read Only Multiplier: 0.1 Sets 12V low battery voltage PC 2.x,
Battery Offset: 0 fault threshold for generator PC 3.x
Voltage Size (bits): 16 set operation in all modes
Stopped except rated
Sign: U
Threshold
Unit: Vdc
Lower Limit: 11
Upper Limit: 13
43654 12 V Weak Read/Write Multiplier: 0.1 Sets 12V weak battery PC 2.x,
Battery Offset: 0 voltage fault threshold PC 3.x
Voltage Size (bits): 16
Threshold
Sign: U
Unit: Vdc
Lower Limit: 6
Upper Limit: 10
43655 24 V High Read Only Multiplier: 0.1 Sets 24V high battery voltage PC 2.x,
Battery Offset: 0 fault threshold PC 3.x
Voltage Size (bits): 16
Threshold
Sign: U
Unit: Vdc
Lower Limit: 28
Upper Limit: 34
43656 24 V Low Read Only Multiplier: 0.1 Sets 24V low battery voltage PC 2.x,
Battery Offset: 0 fault threshold for generator PC 3.x
Voltage Size (bits): 16 set operation while in rated
Running mode
Sign: U
Threshold
Unit: Vdc
Lower Limit: 24
Upper Limit: 28
43657 24 V Low Read Only Multiplier: 0.1 Sets 24V low battery voltage PC 2.x,
Battery Offset: 0 fault threshold for generator PC 3.x
Voltage Size (bits): 16 set operation in all modes
Stopped except rated
Sign: U
Threshold
Unit: Vdc
Lower Limit: 24
Upper Limit: 26

A029X159 (Issue 19) 281 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43658 24 V Weak Read/Write Multiplier: 0.1 Sets 24V weak battery PC 2.x,
Battery Offset: 0 voltage fault threshold PC 3.x
Voltage Size (bits): 16
Threshold
Sign: U
Unit: Vdc
Lower Limit: 12
Upper Limit: 16
43659 Adjustable Read/Write Multiplier: 0.01 Sets the RPM/Hz conversion PC 2.x,
Freq/Speed Offset: 0 factor when the Freq to PC 3.x
Gain Size (bits): 16 Speed Gain Select trim is set
to this trim
Sign: U
Unit: RPM/Hz
Lower Limit: 12
Upper Limit: 240
43660 Alternate Read Only 0: 50 Hz Sets the generator set PC 2.x,
Frequency 1: 60 Hz nominal frequency. PC 3.x
Switch
43661 AVR Gain Read/Write Multiplier: 0.01 A trim that allows the user to PC 2.x,
Adjust Trim Offset: 0 modify the overall gains of the PC 3.x
Size (bits): 16 AVR.
Sign: U
Unit:
Lower Limit: 0.05
Upper Limit: 10
43662 Charging Read/Write Multiplier: 0.1 Sets the time delay for the PC 2.x,
Alternator Offset: 0 charging alt failure fault PC 3.x
Fault Time Size (bits): 16
Delay
Sign: U
Unit: seconds
Lower Limit: 2
Upper Limit: 300
43663 Continuous Read/Write Multiplier: 1 Sets the maximum amount of PC 2.x,
Crank Offset: 0 time to engage the starter PC 3.x
Engage Time Size (bits): 16 when using the continuous
cranking method
Sign: U
Unit: seconds
Lower Limit: 40
Upper Limit: 100

Copyright © 2017 Cummins Inc. 282 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43664 Controlled Read/Write Multiplier: 1 Delay allowed for a shutdown PC 3.x
Shutdown Offset: 0 with cooldown fault prior to
Advance Size (bits): 16 shutting down the generator
Notice Delay set
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 300
43665 Crank Read/Write Multiplier: 1 Sets the maximum number of PC 2.x,
Attempts Offset: 0 times to engage the starter PC 3.x
Size (bits): 16 when attempting to start
engine using the cycle
Sign: U
cranking method
Unit: seconds
Lower Limit: 1
Upper Limit: 7
43666 Cycle / Cont Read Only 0: Cycle Selects whether to use PC 2.x,
Crank Select 1: Continuous continuous cranking or cycle PC 3.x
cranking when attempting to
start engine
43667 Cycle Crank Read/Write Multiplier: 1 Sets the maximum amount of PC 2.x,
Engage Time Offset: 0 time to engage the starter PC 3.x
Size (bits): 16 during a single crank attempt
when using the cycle
Sign: U
cranking method
Unit: seconds
Lower Limit: 2
Upper Limit: 20
43668 Cycle Crank Read/Write Multiplier: 1 Sets the amount of time to PC 2.x,
Rest Time Offset: 0 wait between crank attempts PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 7
Upper Limit: 40
43669 Delayed Off Read/Write Multiplier: 0.1 Time delay between when the PC 2.x,
FSO Relay Offset: 0 Delayed Off Command turns PC 3.x
Time Size (bits): 16 off and Run Command turns
off
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 120

A029X159 (Issue 19) 283 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43670 External AVR Read / Write Multiplier : 0.1 Sets the knee frequency for PC 2.x,
Knee Offset: 0 the fixed knee freq logic. PC 3.x
Frequency Size (bits): 16
Sign: U
Units: Hz
Lower Limit: 0
Upper Limit: 10
Default: NA
43671 External Bias Read/Write 0: Disabled Enables the external bias PC 3.x
Commands 1: Enabled (speed and voltage
Enable commands) to the hardware
outputs.
43672 Frequency Read/Write Multiplier: 0.01 A method of adding in a PC 2.x,
Adjust Offset: 0 frequency offset to the base PC 3.x
Size (bits): 16 frequency subject to high and
low limit calibrations
Sign: S
Units: Hz
Lower Limit: -6
Upper Limit: 6
43673 Genset Read/Write Multiplier: 0.1 Sets the total exercise time PC 2.x,
Exercise Offset: 0 not including warmup at idle PC 3.x
Time Size (bits): 16 or idle cooldown time
Sign: U
Unit: hours
Lower Limit: 0
Upper Limit: 25
43674 Governor Read Only Multiplier: 0.01 A trim that allows the user to PC 2.x,
Gain Adjust Offset: 0 modify the overall gain of the PC 3.x
Size (bits): 16 governor
Sign: U
Unit:
Lower Limit: 0.05
Upper Limit: 15
43675 High Battery Read Only Multiplier: 1 The time delay until a high PC 2.x,
Voltage Set Offset: 0 battery voltage condition is PC 3.x
Time Size (bits): 16 reported as a fault.
Sign: U
Unit: seconds
Lower Limit: 2
Upper Limit: 60

Copyright © 2017 Cummins Inc. 284 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43676 High Battery Read Only Multiplier: 0.1 The high battery voltage PC 2.x,
Voltage Offset: 0 threshold PC 3.x
Threshold Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit:
Upper Limit:
43677 Idle Read/Write Multiplier: 0.25 Sets time to run at idle before PC 2.x,
Cooldown Offset: 0 shutting down generator set PC 3.x
Time Size (bits): 16 on normal stops
Sign: U
Unit: minutes
Lower Limit: 0
Upper Limit: 60
43678 Idle Speed Read Only Multiplier: 1 Sets the speed at which the PC 2.x,
Offset: 0 engine will idle subject to high PC 3.x
Size (bits): 16 and low limit calibrations
Sign: U
Unit: RPM
Lower Limit: 700
Upper Limit: 1100
43679 Idle to Rated Read/Write Multiplier: 0.1 The time over which the PC 2.x,
Ramp Time Offset: 0 speed reference is to ramp PC 3.x
Size (bits): 16 from idle speed to rated
speed
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 30
43680 Idle Warmup Read/Write Multiplier: 1 Coolant temperature PC 2.x,
Coolant Offset: 0 threshold to end idle warmup PC 3.x
Temp Size (bits): 16 time
Sign: S
Unit: degF
Lower Limit: -40
Upper Limit: 300
43681 Idle Warmup Read/Write Multiplier: 1 Sets maximum idle warmup PC 2.x,
Time Offset: 0 time. Warmup time may be PC 3.x
Size (bits): 16 less if coolant temperature
exceeds threshold
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 3600

A029X159 (Issue 19) 285 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43682 Load Dump Read/Write 0: Overload Enables the load dump output PC 2.x,
Activation 1: Underfrequency as a function of the overload PC 3.x
Method 2: Overload or and underfrequency
Underfrequency conditions
3: Disabled
43683 Load Dump Read/Write Multiplier: 1 The time delay until the load PC 2.x,
Overload Set Offset: 0 dump overload condition is PC 3.x
Time Size (bits): 16 set active
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 120
43684 Load Dump Read/Write Multiplier: 1 The load dump overload PC 2.x,
Overload Offset: 0 threshold as a percentage of PC 3.x
Threshold Size (bits): 16 the generator set application
rating
Sign: U
Unit: %
Lower Limit: 80
Upper Limit: 140
43685 Load Dump Read/Write Multiplier: 1 The frequency amount which PC 2.x,
Underfrequen Offset: 0 the load dump PC 3.x
cy Offset Size (bits): 16 underfrequency threshold is
below the final frequency
Sign: S
reference
Unit: Hz
Lower Limit: 0
Upper Limit: 10
43686 Load Dump Read/Write Multiplier: 1 The time delay until the load PC 2.x,
Underfrequen Offset: 0 dump underfrequency PC 3.x
cy Set Time Size (bits): 16 condition is set active
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 20
43687 Load Dump Read Only Multiplier: 0.1 The frequency trip threshold PC 2.x,
Underfrequen Offset: 0 for the load dump PC 3.x
cy Threshold Size (bits): 16 underfrequency condition
Sign: U
Unit: Hz
Lower Limit: 0
Upper Limit: 90

Copyright © 2017 Cummins Inc. 286 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43688 Low Battery Read Only Multiplier: 1 The time delay until a low PC 2.x,
Voltage Set Offset: 0 battery voltage condition is PC 3.x
Time Size (bits): 16 reported as a fault
Sign: U
Unit: seconds
Lower Limit: 2
Upper Limit: 60
43689 Low Fuel in Read/Write Multiplier: 1 Low Fuel in Day Tank Fault PC 2.x,
Day Tank Offset: 0 time delay from switch input PC 3.x
Time Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 20
43690 Low Fuel Read/Write Multiplier: 1 A trim that sets the delay time PC 2.x,
Set/Clear Offset: 0 for generating the inactive PC 3.x
Time Size (bits): 16 and active faults
Sign: U
Unit: seconds
Lower Limit: 2
Upper Limit: 60
43691 Manual Read/Write 0: Normal Use to command idle speed PC 2.x,
Warmup 1: Bypass Warmup or to bypass idle warmup PC 3.x
Bypass during a manual run
43692 Max Idle Read/Write Multiplier: 0.1 Sets the fault time for the Too PC 2.x,
Time Offset: 0 Long in Idle fault PC 3.x
Size (bits): 16
Sign: U
Unit: minutes
Lower Limit: 0
Upper Limit: 20
43693 Nominal Read Only 0: 12V Selects the generator set’s PC 2.x,
Battery 1: 24V nominal battery operating PC 3.x
Voltage voltage
43694 Prelube Cycle Read/Write 0: Disabled Enables Or Disables the PC 2.x,
Enable 1: Enabled cyclic mode of prelube PC 3.x
operation
43695 Prelube Cycle Read/Write Multiplier: 0.1 Sets the period of the Prelube PC 2.x,
Time Offset: 0 Cycle Iteration PC 3.x
Size (bits): 16
Sign: U
Unit: hours
Lower Limit: 1
Upper Limit: 1000

A029X159 (Issue 19) 287 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43696 Prelube Read/Write 0: Disabled Selects whether the Prelube PC 2.x,
Function 1: Enabled function is enabled or PC 3.x
Enable disabled. This is Setup mode
interlocked
43697 Prelube Oil Read/Write Multiplier: 0.1 The oil pressure value which PC 2.x,
Pressure Offset: 0 when reached the prelube PC 3.x
Threshold Size (bits): 16 driver will turn off
Sign: U
Unit: psig
Lower Limit: 0
Upper Limit: 10
43698 Prelube Read/Write Multiplier: 0.1 Sets the maximum time for PC 2.x,
Timeout Offset: 0 which the Prelube Driver will PC 3.x
Period Size (bits): 16 Remain ON
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 30
43699 Rated to Idle Read/Write Multiplier: 0.1 The time over which the PC 2.x,
Ramp Time Offset: 0 speed reference is to ramp PC 3.x
Size (bits): 16 from rated speed to idle
speed
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 30
43700 Utility Read Only 0: Not Available Indicates status of the utility PC 3.x
Availability 1: Available source
Status 2: Unknown
43701 Utility CB Read Only 0: Inactive Utility cb inhibit command PC 3.x
Inhibit 1: Active
Command
43702 Utility CB Read Only 0: Inactive Utility cb tripped command PC 3.x
Tripped 1: Active
Command
43703 Utility Current Read Only 0: Unknown Indicates utility breaker PC 3.x
Based 1: Closed position based on current
Breaker
Position
43704 Utility Read Only Multiplier: 0.1 Indicates the lower drop-out PC 3.x
Frequency Offset: 0 threshold in Hz for utility
Lower Drop- Size (bits): 16 frequency sensor
Out
Sign: U
Threshold
Unit: Hz
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 288 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43705 Utility Read Only Multiplier: 0.1 Indicates the lower pick-up PC 3.x
Frequency Offset: 0 threshold in Hz for utility
Lower Pick- Size (bits): 16 frequency sensor
Up Threshold
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
43706 Utility Read Only 0: Unknown Indicates utility frequency PC 3.x
Frequency 1: Picked Up sensor status
Sensor 2: Dropped Out
Status
43707 Utility Read Only Multiplier: 0.1 Indicates the upper drop-out PC 3.x
Frequency Offset: 0 threshold in Hz for utility
Upper Drop- Size (bits): 16 frequency sensor
Out
Sign: U
Threshold
Unit: Hz
Lower Limit:
Upper Limit:
43708 Utility Read Only Multiplier: 0.1 Indicates the upper pick-up PC 3.x
Frequency Offset: 0 threshold in Hz for utility
Upper Pick- Size (bits): 16 frequency sensor
Up Threshold
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
43709 Utility Loss of Read Only 0: Unknown Indicates utility loss of phase PC 3.x
Phase 1: Picked Up sensor status
Sensor 2: Dropped Out
Status
43710 Utility Read Only Multiplier: 1 Indicates the drop-out PC 3.x
Overvoltage Offset: 0 threshold in volts for utility
Drop-Out Size (bits): 16 over voltage sensor
Threshold
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
43711 Utility Read Only Multiplier: 1 Indicates the pick-up PC 3.x
Overvoltage Offset: 0 threshold in volts for utility
Pick-Up Size (bits): 16 over voltage sensor
Threshold
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 289 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43712 Utility Read Only 0: Unknown Indicates utility over voltage PC 3.x
Overvoltage 1: Picked Up sensor status
Sensor 2: Dropped Out
Status
43713 Utility Phase Read Only 0: Unknown Indicates utility phase rotation PC 3.x
Rotation 1: Picked Up sensor status
Sensor 2: Dropped Out
Status
43714 Utility Read Only Multiplier: 1 Indicates the drop-out PC 3.x
Undervoltage Offset: 0 threshold in volts for utility
Drop-Out Size (bits): 16 under voltage sensor
Threshold
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
43715 Utility Read Only Multiplier: 1 Indicates the pick-up PC 3.x
Undervoltage Offset: 0 threshold in volts for utility
Pick-Up Size (bits): 16 under voltage sensor
Threshold
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
43716 Utility Read Only 0: Unknown Indicates utility under voltage PC 3.x
Undervoltage 1: Picked Up sensor status
Sensor 2: Dropped Out
Status
43717 Voltage Read Only 0: Inactive Command value of voltage PC 2.x,
Droop Enable 1: Active droop enable PC 3.x
Command

43719 Alternator Read Only Multiplier: 1 Monitor point for the PC 2.x,
Temperature Offset: 0 Alternator Temperature 1 PC 3.x
1 (Aux101) Size (bits): 16 input from the Aux 101 I/O
module.
Sign: S
Unit: degF
Lower Limit: -32767
Upper Limit: 32762
43720 Alternator Read Only Multiplier: 1 Monitor point for the PC 2.x,
Temperature Offset: 0 Alternator Temperature 2 PC 3.x
2 (Aux101) Size (bits): 16 input from the Aux 101 I/O
module.
Sign: S
Unit: degF
Lower Limit: -32767
Upper Limit: 32762

Copyright © 2017 Cummins Inc. 290 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43721 Alternator Read Only Multiplier: 1 Monitor point for the PC 2.x,
Temperature Offset: 0 Alternator Temperature 3 PC 3.x
3 (Aux101) Size (bits): 16 input from the Aux 101 I/O
module.
Sign: S
Unit: degF
Lower Limit: -32767
Upper Limit: 32762
43722 Ambient Read Only Multiplier: 1 Monitor point for the Ambient PC 2.x,
Temperature Offset: 0 Temperature input from the PC 3.x
(Aux101) Size (bits): 16 Aux 101 I/O module.
Sign: S
Unit: degF
Lower Limit: -32767
Upper Limit: 32762
43723 Aux101 0 Read Only Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
Analog Input Offset: 0 analog input 1 in volts PC 3.x
1 Voltage Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit: -500
Upper Limit: 500
43724 Aux101 0 Read Only Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
Analog Input Offset: 0 analog input 2 in volts PC 3.x
2 Voltage Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit: -500
Upper Limit: 500
43725 Aux101 0 Read Only Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
Analog Input Offset: 0 analog input 3 in volts PC 3.x
3 Voltage Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43726 Aux101 0 Read Only Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
Analog Input Offset: 0 analog input 4 in volts PC 3.x
4 Voltage Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 291 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43727 Aux101 0 Read Only Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
Analog Input Offset: 0 analog input 5 in volts PC 3.x
5 Voltage Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43728 Aux101 0 Read Only Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
Analog Input Offset: 0 analog input 6 in volts PC 3.x
6 Voltage Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43729 Aux101 0 Read Only Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
Analog Input Offset: 0 analog input 7 in volts PC 3.x
7 Voltage Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43730 Aux101 0 Read Only Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
Analog Input Offset: 0 analog input 8 in volts PC 3.x
8 Voltage Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43731 Aux101 1 Read Only Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
Analog Input Offset: 0 analog input 1 in volts PC 3.x
1 Voltage Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit: -500
Upper Limit: 500
43732 Aux101 1 Read Only Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
Analog Input Offset: 0 analog input 2 in volts PC 3.x
2 Voltage Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit: -500
Upper Limit: 500

Copyright © 2017 Cummins Inc. 292 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43733 Aux101 1 Read Only Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
Analog Input Offset: 0 analog input 3 in volts PC 3.x
3 Voltage Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43734 Aux101 1 Read Only Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
Analog Input Offset: 0 analog input 4 in volts PC 3.x
4 Voltage Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43735 Aux101 1 Read Only Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
Analog Input Offset: 0 analog input 5 in volts PC 3.x
5 Voltage Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43736 Aux101 1 Read Only Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
Analog Input Offset: 0 analog input 6 in volts PC 3.x
6 Voltage Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43737 Aux101 1 Read Only Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
Analog Input Offset: 0 analog input 7 in volts PC 3.x
7 Voltage Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43738 Aux101 1 Read Only Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
Analog Input Offset: 0 analog input 8 in volts PC 3.x
8 Voltage Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 293 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43739 Battery Read Only 0: Inactive Monitor point for the battery PC 2.x,
Charger AC 1: Active charger failure input from the PC 3.x
Failure PCCNet annunciator.
(HMI113)
43740 Drive End Read Only Multiplier: 1 Monitor point for the Drive PC 2.x,
Bearing Offset: 0 End Bearing Temperature PC 3.x
Temperature Size (bits): 16 input from the I/O module.
(Aux101)
Sign: S
Unit: degF
Lower Limit: -32767
Upper Limit: 32762
43741 Exhaust Read Only Multiplier: 1 Monitor point for the Exhaust PC 2.x,
Stack Offset: 0 Stack Temperature1 input PC 3.x
Temperature Size (bits): 16 from the I/O module.
1 (Aux101)
Sign: S
Unit: degF
Lower Limit: -32767
Upper Limit: 32762
43742 Exhaust Read Only Multiplier: 1 Monitor point for the Exhaust PC 2.x,
Stack Offset: 0 Stack Temperature2 input PC 3.x
Temperature Size (bits): 16 from the I/O module.
2 (Aux101)
Sign: S
Unit: degF
Lower Limit: -32767
Upper Limit: 32762
43745 Fuel Level % Read Only Multiplier: 0.1 Monitor point for the % fuel PC 2.x,
(PCCNet) Offset: 0 level input from the I/O PC 3.x
Size (bits): 16 module.
Sign: S
Unit: %
Lower Limit:
Upper Limit:
43746 Fuel Level Read Only Multiplier: 1 Monitor point for the fuel level PC 2.x,
(PCCNet) Offset: 0 (in gallons) input from the I/O PC 3.x
Size (bits): 16 module.
Sign: S
Unit:
Lower Limit:
Upper Limit:
43747 HMI113 Fault Read Only 0: Inactive Monitor point for input #1 PC 2.x,
1 Status 1: Active from the annunciator. PC 3.x
43748 HMI113 Fault Read Only 0: Inactive Monitor point for input #2 PC 2.x,
2 Status 1: Active from the annunciator. PC 3.x

Copyright © 2017 Cummins Inc. 294 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43749 HMI113 Fault Read Only 0: Inactive Monitor point for the input #3 PC 2.x,
3 Status 1: Active from the annunciator. PC 3.x
43750 Intake Read Only Multiplier: 1 Monitor point for the Intake PC 2.x,
Manifold Offset: 0 Manifold Temperature 1 input PC 3.x
Temperature Size (bits): 16 from the I/O module.
1 (Aux101)
Sign: S
Unit: degF
Lower Limit: -32768
Upper Limit: 32762
43751 Low Coolant Read Only 0: Inactive Monitor point for the Low PC 2.x,
Level 1: Active Coolant Level input from the PC 3.x
(HMI113) PCCNet annunciator.
43752 Low Fuel Read Only 0: Inactive Monitor point for the Low Fuel PC 2.x,
Level 1: Active Level input from the PCCNet PC 3.x
(HMI113) annunciator.
43755 Non-Drive Read Only Multiplier: 1 Monitor point for the Non- PC 2.x,
End Bearing Offset: 0 Drive End Bearing PC 3.x
Temperature Size (bits): 16 Temperature input from the
(Aux101) I/O module.
Sign: S
Unit: degF
Lower Limit: -32768
Upper Limit: 32762
43756 Number of Read Only Multiplier: 1 Used to monitor the amount PC 2.x,
Connected Offset: 0 of connected bargraph PC 3.x
Bargraph Size (bits): 16 modules.
Modules
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
43757 Oil Read Only Multiplier: 1 Monitor point for the Oil PC 2.x,
Temperature Offset: 0 Temperature input from the PC 3.x
(Aux101) Size (bits): 16 I/O Module.
Sign: S
Unit: degF
Lower Limit: -65534
Upper Limit: 65535
43758 Modbus Bus Read Only Multiplier: 1 Modbus bus message count PC 2.x,
Message Offset: 0 PC 3.x
Count Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit

A029X159 (Issue 19) 295 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43759 Modbus CRC Read Only Multiplier: 1 Modbus CRC errors count PC 2.x,
Errors Count Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
43760 Modbus Read Only Multiplier: 1 Modbus exception count PC 2.x,
Exception Offset: 0 PC 3.x
Count Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
43761 Modbus No Read Only Multiplier: 1 Modbus no response count PC 2.x,
Response Offset: 0 PC 3.x
Count Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
43762 Modbus Read Only Multiplier: 1 Modbus slave message count PC 2.x,
Slave Offset: 0 PC 3.x
Message Size (bits): 16
Count
Sign: U
Unit:
Lower Limit:
Upper Limit
43763 Frequency Read Only Multiplier: 0.001 frequency match error value PC 3.x
Match Error Offset: 0 used by frequency match PI
Size (bits): 16 loop
Sign: S
Unit: Hz
Lower Limit:
Upper Limit
43764 Frequency Read Only Multiplier : 0.001 Offset to the frequency match PC 3.x
Match Offset Offset: 0 error calculation
Size (bits): 16
Sign: S
Unit: Hz
Lower Limit:
Upper Limit
Default: NA

Copyright © 2017 Cummins Inc. 296 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43765 Load Dump Read Only 0: Inactive Indicates a load dump is PC 2.x,
Request 1: Active desired due to load PC 3.x
exceeding derate level.
43766 Load Govern Read Only 0: Not Applicable Indicates status of load PC 3.x
kVAR Ramp 1: Ramp Load govern kVAR ramping control
State 2: Track Target
3: Ramp Unload
4: Ramp Unload Complete
43767 Load Govern Read Only Multiplier: 0.01 Indicates the final target PC 3.x
kVAR Target Offset: 0 setpoint for generator set
Size (bits): 16 kVAR output when paralleled
to utility
Sign: S
Unit: %
Lower Limit:
Upper Limit
Default: NA
43768 Load Govern Read Only 0: Not Applicable Indicates status of load PC 3.x
kW Ramp 1: Ramp Load govern kW ramping control
State 2: Track Target
3: Ramp Unload
4: Ramp Unload Complete
43769 Load Govern Read Only Multiplier: 0.01 Indicates the final target PC 3.x
kW Target Offset: 0 setpoint for generator set kW
Size (bits): 16 output when paralleled to
utility
Sign: S
Unit: %
Lower Limit:
Upper Limit
Default: NA
43770 Permissive Read Only 0: Not Allowed Indicates when permissive PC 3.x
Close 1: Allowed sync check conditions have
Allowed been met

43772 Permissive Read Only Multiplier : 0.01 Phase error signal for the PC 3.x
Phase Match Offset: 0 permissive sync check
Error Size (bits): 16 algorithm
Sign: S
Units: deg
Lower Limit: NA
Upper Limit: NA
Default: NA

A029X159 (Issue 19) 297 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43773 Phase Match Read Only Multiplier: 0.01 Phase error signal for the PC 3.x
Error Offset: 0 synchronizer control algorithm
Size (bits): 16
Sign: S
Units: deg
Lower Limit:
Upper Limit:
43774 Ramp Read Only 0: Load Indicates overall status of PC 3.x
Load/Unload 1: Unload ramp load unload inputs
Command
43775 Utility Read Only 0: Not Available Indicates unloaded status of PC 3.x
Unloaded 1: Not Unloaded the utility source
Status 2: Unloaded
43776 Genset CB Read Only 0: Inactive Indicates if the output’s status PC 3.x
Close Status 1: Active is Inactive or Active

43777 Start Read Only 0: Inactive This is the status of the PC 2.x,
Type/Configu 1: Active Configurable Input #11. PC 3.x
rable Input
#11 Switch
43778 Scheduler Read Only 0: Off Indicates the current run PC 2.x,
Run 1: No Load command coming from the PC 3.x
Command 2: With Load scheduler.
3: Extended Parallel
43785 Start Read Only Multiplier: 1 Number of start attempts PC 2.x,
Attempts Offset: 0 since the last reset. PC 3.x
Since Reset Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290
43786 Start Read Only Multiplier: 1 Number of start attempts PC 2.x,
Attempts Offset: 0 since the last reset. PC 3.x
Since Reset Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290
43787 Total Start Read Only Multiplier: 1 Total number of start PC 2.x,
Attempts Offset: 0 attempts. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290

Copyright © 2017 Cummins Inc. 298 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43788 Total Start Read Only Multiplier: 1 Total number of start PC 2.x,
Attempts Offset: 0 attempts. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290
43789 Backup Start Read Only 0: Inactive This is the status of the PC 3.x
Disconnect/C 1: Active Configurable Input #33.
onfigurable
Input #33
Switch
43790 Backup Start Read Only 0: Inactive Status of the Backup Start PC 3.x
Disconnect 1: Active Disconnect Switch Input
Switch
43791 Battery Read Only 0: Inactive Battery Charger Failed Switch PC 2.x,
Charger 1: Active function output status; gives PC 3.x
Failed Switch software Inactive/Active state
43792 Battle Short Read Only 0: Inactive Battle Short Switch function PC 2.x,
Switch 1: Active output status (Active or PC 3.x
Inactive)
43793 Configurable Read Only 0: Inactive Configurable Input #1 input PC 2.x,
Input #1 1: Active software state status. Gives PC 3.x
Switch software Inactive/Active state
43794 Configurable Read Only 0: Inactive Configurable Input #2 input PC 2.x,
Input #2 1: Active software state status. Gives PC 3.x
Switch software Inactive/Active state
43795 Configurable Read Only 0: Inactive Configurable Input #13 input PC 2.x,
Input #13 1: Active software state status. Gives PC 3.x
Switch software Inactive/Active state
43796 Genset CB Read Only 0: Inactive Generator set cb open PC 3.x
Open 1: Active command status
Command
43797 Number of Read Only Multiplier : 1 Used to monitor the amount PC 2.x,
Connected Offset: 0 of connected Battery PC 3.x
Battery Size (bits): 8 Chargers
Chargers
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

A029X159 (Issue 19) 299 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43800 Rated Read/Write Multiplier: 1 Minimum time to spend at PC 2.x,
Cooldown Offset: 0 rated speed less than 10% PC 3.x
Time Size (bits): 16 load before normal shutdown
is allowed
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 600
43801 Rated to Idle Read/Write Multiplier: 0.1 Sets the delay time for PC 2.x,
Transition Offset: 0 transitioning from Rated to PC 3.x
Delay Size (bits): 16 Idle speed. 0 seconds =
feature is disabled.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 10
43802 Rupture Read/Write Multiplier: 0.1 Rupture Basin fault time PC 2.x,
Basin Time Offset: 0 delay PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 20
43803 Start Time Read/Write Multiplier: 1 Sets the time to wait from PC 2.x,
Delay Offset: 0 receiving a valid remote start PC 3.x
Size (bits): 16 signal until starting the
generator set
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 300
43804 Starting to Read/Write Multiplier: 0.1 The time over which the PC 2.x,
Rated Ramp Offset: 0 speed reference is to ramp PC 3.x
Time Size (bits): 16 from starting speed to rated
speed
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 300
43805 Time Delay to Read/Write Multiplier: 1 Sets time to run at rated PC 2.x,
Stop Offset: 0 speed before going to PC 3.x
Size (bits): 16 cooldown at idle. Does not
apply to manual runs
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 600

Copyright © 2017 Cummins Inc. 300 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43806 Voltage Read/Write Multiplier: 0.01 A trim that allows the user to PC 2.x,
Adjust Offset: 0 add/subtract an offset to the PC 3.x
Size (bits): 16 nominal voltage when
calculating the voltage
Sign: S
setpoint
Unit: %
Lower Limit: -5
Upper Limit: 5
43807 Voltage Read/Write Multiplier: 0.01 The time period over which PC 2.x,
Ramp Time Offset: 0 the voltage setpoint PC 3.x
Size (bits): 16 command should rise from
0% to the target voltage
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 5
43808 Commit to Read Only 0: Not Committed PTC - Indicates if system is PC 3.x
Transfer 1: Committed committed to transferring to
State generator set
43810 Battle Short Read/Write 0: Inactive Trim to enable Battle Short PC 2.x,
Switch 1: Committed via Modbus. PC 3.x
(Modbus)
43811 Exercise Read/Write 0: Inactive Modbus exercise switch PC 2.x,
Switch 1: Active PC 3.x
(Modbus)
43813 Extended Read/Write 0: Inactive Modbus extended parallel PC 2.x,
Parallel 1: Active switch PC 3.x
Switch
(Modbus)
43814 PTC Mode Read/Write 0: Inactive Modbus PTC Mode switch PC 3.x
Switch 1: Active
(Modbus)
43815 Start Type Read/Write 0: Emergency Modbus start type switch PC 2.x,
(Modbus) 1: Non Emergency PC 3.x
43816 Sync Disable Read / Write 0: Inactive Use to turn off synchronizer PC 3.x
1: Active for testing purposes

43817 Genset Read/Write 0: Inactive Identical operation to the PC 3.x


Circuit 1: Active configurable input of the
Breaker same name. Opens genset
Inhibit breaker if closed; inhibits
closure if genset breaker is
open
43818 Isolated Bus Read/Write 0: Constant Sets the speed control PC 2.x,
Speed 1: Droop method for isolated bus PC 3.x
Control paralleling. Parameter is also
Method known as Load Share Speed
Droop Control Method

A029X159 (Issue 19) 301 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43819 Isolated Bus Read/Write 0: Constant Sets the voltage control PC 2.x,
Voltage 1: Droop method for isolated bus PC 3.x
Control paralleling
Method
43820 Maximum Read/Write Multiplier: 0.1 Sets the maximum time that PC 3.x
Parallel Time Offset: 0 the generator set can remain
(TDMP) Size (bits): 16 paralleled to the utility during
closed transition transfers
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 1800
43821 Programmed Read/Write Multiplier: 0.1 Sets the time delay from PC 3.x
Transition Offset: 0 when one source opens until
Delay (TDPT) Size (bits): 16 the other closes during open
transition transfers
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 60
43822 Retransfer Read/Write Multiplier: 0.1 Sets the amount of time that PC 3.x
Delay (TDEN) Offset: 0 the utility source must be
Size (bits): 16 available before the control
will retransfer to that source.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 1800
43823 Synchronizer Read/Write 0: Phase Match Sets the speed control PC 3.x
Speed 1: Slip Frequency method for synchronizing.
Control 2: External
Method
43824 Synchronizer Read/Write 0: Voltage Match Sets the voltage control PC 3.x
Voltage 1: External method for synchronizing.
Control
Method
43825 Transfer Read/Write Multiplier: 0.1 Sets the amount of time that PC 3.x
Delay (TDNE) Offset: 0 the generator set source must
Size (bits): 16 be available before the
control will transfer to that
Sign: U
source.
Unit: seconds
Lower Limit: 0
Upper Limit: 120
43826 Transition Read/Write 0: Open Transition Sets the load transfer PC 3.x
Type 1: Hard Closed Transition transition type for use when
2: Soft Closed Transition Generator set Application
Type = Power Transfer
Control.

Copyright © 2017 Cummins Inc. 302 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43827 Retransfer Read/Write 0: Inactive Identical operation to the PC 3.x
Inhibit 1: Active configurable input of the
same name. Normally inhibits
retransfer to the utility; under
some conditions it is ignored;
not the same as utility circuit
breaker inhibit.
43828 Utility Circuit Read/Write 0: Inactive Identical operation to the PC 3.x
Breaker 1: Active configurable input of the
Inhibit same name. Opens utility
main if closed; inhibits closure
if utility main is open.

43829 Utility Parallel Read/Write 0: Load Govern Sets the speed control PC 3.x
Speed 1: Droop method for utility paralleling.
Control
Method
43830 Utility Parallel Read/Write 0: Load Govern Sets the voltage control PC 3.x
Voltage 1: Droop method for utility paralleling.
Control 2: Load Govern with Droop
Method Feed Forward
43831 Aux101 Read/Write 0: Critical Device Response Selects the generator set PC 2.x,
Device 0 1: Non-Critical Device reaction to a loss of a Device PC 3.x
PCCNet Response 0 I/O module as critical
Failure (Shutdown) or non-critical
Response (Warning).
Type
43832 Aux101 Read/Write 0: Critical Device Response Selects the generator set PC 2.x,
Device 1 1: Non-Critical Device reaction to a loss of a Device PC 3.x
PCCNet Response 1 I/O module as critical
Failure (Shutdown) or non-critical
Response (Warning).
Type
43834 HMI113 Read/Write 0: Critical Device Response Selects the generator set PC 2.x,
Annunciator 1: Non-Critical Device reaction to a loss of an PC 3.x
PCCNet Response annunciator as critical or non-
Failure critical. Selecting critical will
Response cause a shutdown when the
Type annunciator loses
communication.
43835 HMI1xx Read / Write 0: Critical Device Response Selects the genset reaction to PC 2.x,
PCCNet 1: Non-Critical Device a loss of an HMI1xx Operator PC 3.x
Failure Response Panel as critical or non-
Response critical. A critical response will
Type shutdown the genset when
PCCNet communication is
lost.

A029X159 (Issue 19) 303 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43836 HMI220 Read/Write 0: Critical Device Response Selects the generator set PC 2.x,
PCCNet 1: Non-Critical Device reaction to a loss of an PC 3.x
Failure Response HMI220 operator panel as
Response critical or non-critical. A
Type critical response will
shutdown the generator set
when PCCNet communication
is lost.
43837 HMI320 Read/Write 0: Critical Device Response Selects the generator set PC 2.x,
PCCNet 1: Non-Critical Device reaction to a loss of an PC 3.x
Failure Response HMI320 operator panel as
Response critical or non-critical. A
Type critical response will
shutdown the generator set
when PCCNet communication
is lost.
43838 HMI4xx Read / Write 0: Critical Device Response Selects the genset reaction to PC 2.x
PCCNet 1: Non-Critical Device a loss of an HMI4xx Operator PC 3.x
Failure Response Panel as critical or non-
Response critical. A critical response will
Type shutdown the genset when
PCCNet communication is
lost.
43839 PCCNet Read/Write Multiplier: 1 Selects the time allowed for PC 2.x,
Device Offset: 0 arbitration to occur before a PC 3.x
Failure Time Size (bits): 16 PCCNet failure fault is
Delay generated.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 250
43840 Test With Read/Write 0: Disabled Use to choose whether a test PC 3.x
Load Enable 1: Enabled is with load or without load.

43841 Transfer Read/Write 0: Inactive Identical operation to the PC 3.x


Inhibit 1: Active configurable input of the
same name. Normally inhibits
transfer to the genset; under
some conditions it is ignored;
not the same as genset circuit
breaker inhibit.
43842 Commit to Read/Write 0: Utility Disconnect PTC - sets point at which PC 3.x
Transfer 1: Genset Start system commits to transfer to
Method 2: No Commit generator set

Copyright © 2017 Cummins Inc. 304 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43843 Commit to Read/Write Multiplier: 1 PTC - sets time system will PC 3.x
Transfer Offset: 0 wait for generator set when
Timeout Size (bits): 16 committed to transfer
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 3200
43844 Commit to Read Only Multiplier: 0.05 PTC - remaining time system PC 3.x
Transfer Offset: 0 to wait for generator set when
Timer Size (bits): 16 committed to transfer
Sign: U
Unit: sec
Lower Limit:
Upper Limit:
43845 Modbus Read/Write Multiplier: 1 Time delay before the control PC 2.x,
Failure Time Offset: 0 activates the Modbus failure PC 3.x
Delay Size (bits): 16 fault after the Master is
sensed as no longer present.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 10
43846 Modbus Read/Write 0: Do Nothing When set to Reset PC 2.x,
Communicati 1: Reset Commands Commands will reset the PC 3.x
ons Lost Modbus control logicals to an
Response inactive state when Modbus
Method communications are lost
43847 Modbus Clear Read/Write 0: Do Nothing Resets all Modbus counters, PC 2.x,
Counters 1: Clear Counters including J14 if applicable. PC 3.x
43848 Controlled Read/Write Multiplier: 1 maximum ramp unload time PC 3.x
Shutdown Offset: 0 during a shutdown with
Max Ramp Size (bits): 16 cooldown
Unload Time
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 300
43849 Genset kVAR Read/Write Multiplier: 1 Sets the generator set load PC 3.x
Setpoint Offset: 0 govern kVAR base load
Size (bits): 16 internal operating setpoint in
units of kVAR. Requires that
Sign: S
Load Govern kVAR Setpoint
Unit: kVAR Source = Internal and Load
Lower Limit: 0 Govern kVAR Method =
Upper Limit: 20000 generator set kVAR.

A029X159 (Issue 19) 305 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43850 Genset kVAR Read/Write Multiplier: 0.01 Sets the generator set load PC 3.x
Setpoint Offset: 0 govern kVAR base load
Percent Size (bits): 16 internal operating setpoint
in % of standby kVA rating.
Sign: S
Requires that Load Govern
Unit: % kVAR Setpoint Source =
Lower Limit: 0 Internal and Load Govern
Upper Limit: 60 kVAR Method = generator set
kVAR.
43851 Genset kW Read/Write Multiplier: 1 Sets the generator set load PC 3.x
Setpoint Offset: 0 govern kW base load internal
Size (bits): 16 operating setpoint in units of
kW. Requires that Load
Sign: S
Govern kW Setpoint Source =
Unit: kW Internal and Load Govern kW
Lower Limit: 0 Method = Genset kW.
Upper Limit: 20000
43852 Genset kW Read/Write Multiplier: 0.01 Sets the generator set load PC 3.x
Setpoint Offset: 0 govern kW base load internal
Percent Size (bits): 16 operating setpoint in % of
standby rating. Requires that
Sign: S
Load Govern kW Setpoint
Unit: % Source = Internal and Load
Lower Limit: 0 Govern kW Method = Genset
Upper Limit: 100 kW.

43853 Genset Read/Write Multiplier: 0.01 Sets the load govern setpoint PC 3.x
Power Factor Offset: 0 for generator set power factor
Setpoint Size (bits): 8 control. Requires that Load
Govern kVAR Setpoint
Sign: S
Source = Internal and Load
Unit: PF Govern kVAR Method =
Lower Limit: 0.7 Genset Power Factor.
Upper Limit: 1
43854 Load Read/Write 0: Inactive Modbus input for activating PC 3.x
Demand Stop 1: Active load demand stop on the
(Modbus) generator set
43855 Load Govern Read/Write 0: Genset kVAR Use to select how generator PC 3.x
kVAR Method 1: Genset Power Factor set kVAR output will be
2: Utility kVAR controlled when paralleled to
utility.
3: Utility Power Factor
43856 Load Govern Read/Write Multiplier: 1 Sets load govern kVAR ramp PC 3.x
kVAR Ramp Offset: 0 load rate = Genset Standby
Load Time Size (bits): 16 kVA * 0.6/ this time.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 900

Copyright © 2017 Cummins Inc. 306 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43857 Load Govern Read/Write Multiplier: 1 Sets load govern kVAR ramp PC 3.x
kVAR Ramp Offset: 0 unload rate = Genset
Unload Time Size (bits): 16 Standby kVA * 0.6/ this time.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 900
43858 Utility Breaker Read/Write 0: After Transfer Delay PTC - point in time at which PC 3.x
Opening 1: Upon Utility Failure system opens utility breaker
Point
43859 Load Govern Read/Write Multiplier: 1 Sets load govern kW ramp PC 3.x
kW Ramp Offset: 0 load rate = Genset Standby
Load Time Size (bits): 16 kW rating/ this time.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 900
43860 Load Govern Read/Write Multiplier: 1 Sets load govern kW ramp PC 3.x
kW Ramp Offset: 0 unload rate = Genset
Unload Time Size (bits): 16 Standby kW rating/ this time.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 900
43861 Ramp Read/Write 0: Load Use to control ramp load and PC 3.x
Load/Unload 1: Unload unload via Modbus
(Modbus)
43862 Slip Read/Write Multiplier: 0.001 Sets the synchronizer slip PC 3.x
Frequency Offset: 0 frequency. Requires that
Size (bits): 16 Sync Speed Control Method
= Slip Frequency.
Sign: S
Unit: Hz
Lower Limit: -3
Upper Limit: 3
43863 Utility kVAR Read/Write Multiplier: 1 Sets the utility kVAR peak PC 3.x
Setpoint Offset: 0 shave internal operating
Size (bits): 16 setpoint in units of kVAR.
Requires that Load Govern
Sign: S
kVAR Setpoint Source =
Unit: kVAR Internal and Load Govern
Lower Limit: -20000 kVAR Method = Utility kVAR
Upper Limit: 20000

A029X159 (Issue 19) 307 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43864 Utility kVAR Read/Write Multiplier: 0.01 Sets the utility kVAR peak PC 3.x
Setpoint Offset: 0 shave internal operating
Percent Size (bits): 16 setpoint in % of generator set
standby kVA rating. Requires
Sign: S
that Load Govern kVAR
Unit: % Setpoint Source = Internal
Lower Limit: -320 and Load Govern kVAR
Upper Limit: 320 Method = Utility kVAR.

43865 Utility kW Read/Write Multiplier: 1 Sets the utility kW minimum PC 3.x


Constraint Offset: 0 load level for constrained
Size (bits): 16 base load mode of operation.
Requires that Load Govern
Sign: S
kW Setpoint Source =
Unit: kW Internal and Load Govern kW
Lower Limit: -20000 Method = Genset kW w/Utility
Upper Limit: 20000 Constraint.

43866 Utility kW Read/Write Multiplier: 0.01 Sets utility kW minimum load PC 3.x
Constraint Offset: 0 level for constrained base
Percent Size (bits): 16 load mode in % of generator
set standby rating. Requires
Sign: S
that Load Govern kW
Unit: % Setpoint Source = Internal
Lower Limit: -320 and Load Govern kW Method
Upper Limit: 320 = Genset kW w/Utility
Constraint.
43867 Utility kW Read/Write Multiplier: 1 Sets the utility kW peak PC 3.x
Setpoint Offset: 0 shave internal operating
Size (bits): 16 setpoint in units of kW.
Requires that Load Govern
Sign: S
kW Setpoint Source =
Unit: kW Internal and Load Govern kW
Lower Limit: -20000 Method = Utility kW.
Upper Limit: 20000
43868 Utility kW Read/Write Multiplier: 0.01 Sets the utility kW peak PC 3.x
Setpoint Offset: 0 shave internal operating
Percent Size (bits): 16 setpoint in % of generator set
standby rating. Requires that
Sign: S
Load Govern kW Setpoint
Unit: % Source = Internal and Load
Lower Limit: -320 Govern kW Method = Utility
Upper Limit: 320 kW.

43869 Utility Power Read/Write Multiplier: 0.01 Sets the internal setpoint for PC 3.x
Factor Offset: 0 utility power factor control
Setpoint Size (bits): 16 mode when paralleled to
utility. Requires that Load
Sign: S
Govern kVAR Setpoint
Unit: PF Source = Internal and Load
Lower Limit: 0.7 Govern kVAR Method =
Upper Limit: 1 Utility Power Factor.

Copyright © 2017 Cummins Inc. 308 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43870 Aux101 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 2 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43871 Aux101 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 4 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43872 Aux101 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 5 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43873 Aux101 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 6 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43874 Aux101 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 7 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43875 Aux101 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 1 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

A029X159 (Issue 19) 309 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43876 Aux101 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 2 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43877 Aux101 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 3 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43878 Aux101 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 4 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43879 Aux101 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 5 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43880 Aux101 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 6 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43881 Aux101 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 7 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

Copyright © 2017 Cummins Inc. 310 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43882 Aux101 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 8 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43883 Aux102 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 10 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43884 Aux102 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 11 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43885 Aux102 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 12 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43886 Aux102 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 13 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43887 Aux102 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 14 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

A029X159 (Issue 19) 311 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43888 Aux102 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 15 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43889 Aux102 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 16 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43890 Aux102 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 9 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43891 Aux102 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 10 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

Copyright © 2017 Cummins Inc. 312 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43892 Aux102 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 11 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43893 Aux102 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 12 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43894 Aux102 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 13 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43895 Aux102 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 14 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43896 Aux102 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 15 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

A029X159 (Issue 19) 313 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43897 Aux102 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 16 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43898 Aux102 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 9 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43900 HMI113 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 1 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43901 HMI113 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 2 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43902 HMI113 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 3 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

Copyright © 2017 Cummins Inc. 314 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43903 HMI113 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 4 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43905 Network Read/Write 0: Normal Used to command a fixed 0.5 PC 2.x,


Speed Adjust 1: Active Hz increase in the speed PC 3.x
Command setpoint
43906 Speed Droop Read/Write 0: Inactive Speed droop enable switch PC 2.x,
Enable 1: Active input status from Modbus PC 3.x
Switch
(Modbus)
43907 Voltage Read/Write 0: Inactive Voltage droop enable switch PC 2.x,
Droop Enable 1: Active input status from Modbus PC 3.x
Switch
(Modbus)
43908 Genset CB Read/Write 0: Inactive Genset cb tripped from PC 3.x
Tripped 1: Active Modbus
Switch
(Modbus)
43909 Utility CB Read/Write 0: Inactive Utility cb tripped switch input PC 3.x
Tripped 1: Active from Modbus
Switch
(Modbus)
43910 Save Trims Read/Write 0: Do Nothing Save configuration PC 2.x,
1: Save Trims parameters or adjustments to PC 3.x
non-volatile memory. Perform
Save Trims after all
configurations have been
updated. Do not save trims
unless a change has
occurred.
43911 Aux101 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 3 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

A029X159 (Issue 19) 315 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43912 Aux101 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 1 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43913 Aux101 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 8 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event Size (bits): 16 which will turn the output
relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43915 Extended Read/Write 0: Disabled Use to enable the extended PC 3.x


Parallel 1: Enabled paralleling mode of PTC
Enable
43916 V/Hz Knee Read Only Multiplier: 0.1 The voltage will roll off PC 2.x,
Frequency Offset: 0 (decrease) proportionally to PC 3.x
50Hz Size (bits): 16 the V/Hz setup, once the
frequency drops below the
Sign: U
set point in the V/Hz Knee
Unit: Hz Frequency. This allows the
Lower Limit: 0 generator set to recover
Upper Limit: 10 faster when the frequency
drops. This is for 50Hz
frequency.
43917 V/Hz Knee Read Only Multiplier: 0.1 The voltage will roll off PC 2.x,
Frequency Offset: 0 (decrease) proportionally to PC 3.x
60Hz Size (bits): 16 the V/Hz setup, once the
frequency drops below the
Sign: U
set point in the V/Hz Knee
Unit: Hz Frequency. This allows the
Lower Limit: 0 generator set to recover
Upper Limit: 10 faster when the frequency
drops. This is for 60Hz
frequency.
43918 V/Hz Rolloff Read Only Multiplier: 0.1 The amount of voltage roll off PC 2.x,
Slope 50Hz Offset: 0 when the frequency is below PC 3.x
Size (bits): 16 the knee frequency
Sign: U
Unit: % / Hz
Lower Limit: 0
Upper Limit: 10

Copyright © 2017 Cummins Inc. 316 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43919 V/Hz Rolloff Read Only Multiplier: 0.1 The amount of voltage roll off PC 2.x,
Slope 60Hz Offset: 0 when the frequency is below PC 3.x
Size (bits): 16 the knee frequency
Sign: U
Unit: % / Hz
Lower Limit: 0
Upper Limit: 10

43920 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit: % / Hz
Lower Limit: 0
Upper Limit: 10

43921 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43922 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43923 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 317 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43924 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43925 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43926 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43927 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43928 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 318 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43929 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43930 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43931 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43932 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43933 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 319 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43934 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43935 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43952 Speed/Frequ Read/Write Multiplier: 0.1 Sets the delay time for PC 2.x,
ency Delay Offset: 0 generating the PC 3.x
Size (bits): 136 Speed/Frequency mismatch
fault
Sign: U
Unit: seconds
Lower Limit: 0.5
Upper Limit: 10

43953 Speed/Frequ Read/Write Multiplier: 0.1 Sets the threshold for PC 2.x,
ency Offset: 0 generating the PC 3.x
Threshold Size (bits): 16 Speed/Frequency mismatch
fault
Sign: U
Unit: Hz
Lower Limit: 0.5
Upper Limit: 20
43954 Sync Enable Read / Write 0: Inactive Modbus input for enabling the PC 3.x
(Modbus) 1: Active synchronizer

43955 Genset Idle Read Only 0: Disabled Enables or Disable idling of PC 2.x,
Enable 1: Enabled generator set with external PC 3.x
governor.
43956 Permissive Read Only Multiplier : 0.001 Frequency match error value PC 3.x
Frequency Offset: 0 used by permissive sync
Match Error Size (bits): 32 check
Sign: U
Unit: Hz
Lower Limit: NA
Upper Limit: NA
Default: NA

Copyright © 2017 Cummins Inc. 320 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43957 Permissive Read Only Multiplier : 0.001 Frequency match error value PC 3.x
Frequency Offset: 0 used by permissive sync
Match Error Size (bits): 32 check
Sign: U
Unit: Hz
Lower Limit: NA
Upper Limit: NA
Default: NA
43958 Sync Enable Read Only 0: Inactive Indicates overall status of PC 3.x
Command 1: Active sync enable inputs

43959 Utility Read/Write Multiplier: 1 Sets threshold at which utility PC 3.x


Unloaded Offset: 0 source is considered as
Level Size (bits): 16 unloaded.
Sign: S
Unit: kW
Lower Limit: -32768
Upper Limit: 32762
43960 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43961 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43962 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 321 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43963 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43964 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43965 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43966 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43967 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43968 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 322 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43969 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43970 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43971 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43972 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43973 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43974 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 323 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43975 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43976 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43977 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43978 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43979 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43980 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 324 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43981 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43982 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43983 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43984 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43985 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43986 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 325 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43987 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43988 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43989 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43990 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43991 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43992 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 326 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43993 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43994 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43995 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43996 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43997 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43998 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 327 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


43999 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
45999 Unrecognized Read Only 0: All Pairs Recognized Indicates whether or not all PC 2.x,
SPN/FMI 1: Pair Not Recognized pairs in current DM1 are PC 3.x
Status recognized
46000 Genset Read Only 0: L1-L2-L3 Generator set phase rotation PC 2.x,
Phase 1: L1-L3-L2 PC 3.x
Rotation 2: Not Available
46001 Utility Phase Read Only 0: L1-L2-L3 Utility phase rotation PC 3.x
Rotation 1: L1-L3-L2
2: Not Available
46002 Genset Bus Read Only 0: L1-L2-L3 Generator set bus phase PC 3.x
Phase 1: L1-L3-L2 rotation
Rotation 2: Not Available
46003 Base Speed Read Only Multiplier: 0.0625 Provides a point to monitor PC 2.x,
Offset: 0 the base speed PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit:
Upper Limit:
46004 Base Speed Read Only Multiplier: 0.0625 Provides a point to monitor PC 2.x,
Offset: 0 the base speed PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit:
Upper Limit:
46005 Final Speed Read Only Multiplier: 0.0625 Provides a point to monitor PC 2.x,
Reference Offset: 0 the final speed reference PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 328 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46006 Final Speed Read Only Multiplier: 0.0625 Provides a point to monitor PC 2.x,
Reference Offset: 0 the final speed reference PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit:
Upper Limit:
46008 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
1 Offset: 0 Port 1 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -459
Upper Limit: 3155
46009 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
2 Offset: 0 Port 2 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -459
Upper Limit: 3155
46010 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
3 Offset: 0 Port 3 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46011 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
4 Offset: 0 Port 4 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46012 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
5 Offset: 0 Port 5 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155

A029X159 (Issue 19) 329 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46013 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
6 Offset: 0 Port 6 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46014 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
7 Offset: 0 Port 7 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46015 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
8 Offset: 0 Port 8 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46016 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
9 Offset: 0 Port 9 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46017 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
10 Offset: 0 Port 10 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46018 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
11 Offset: 0 Port 11 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155

Copyright © 2017 Cummins Inc. 330 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46019 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
12 Offset: 0 Port 12 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46020 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
13 Offset: 0 Port 13 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46021 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
14 Offset: 0 Port 14 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46022 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
15 Offset: 0 Port 15 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46023 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
16 Offset: 0 Port 16 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46024 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
17 Offset: 0 Port 17 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155

A029X159 (Issue 19) 331 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46025 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
18 Offset: 0 Port 18 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46026 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
19 Offset: 0 Port 19 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46027 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
20 Offset: 0 Port 20 Temperature PC 3.x
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46028 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 1 PC 3.x
Cylinder 1 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46029 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 2 PC 3.x
Cylinder 2 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46030 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 3 PC 3.x
Cylinder 3 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 332 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46031 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 4 PC 3.x
Cylinder 4 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46032 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 5 PC 3.x
Cylinder 5 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46033 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 6 PC 3.x
Cylinder 6 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46034 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 7 PC 3.x
Cylinder 7 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46035 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 8 PC 3.x
Cylinder 8 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46036 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 9 PC 3.x
Cylinder 9 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 333 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46037 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 10 PC 3.x
Cylinder 10 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46038 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 11 PC 3.x
Cylinder 11 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46039 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 12 PC 3.x
Cylinder 12 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46040 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 13 PC 3.x
Cylinder 13 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46041 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 14 PC 3.x
Cylinder 14 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46042 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 15 PC 3.x
Cylinder 15 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 334 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46043 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 16 PC 3.x
Cylinder 16 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46044 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 17 PC 3.x
Cylinder 17 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46045 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 18 PC 3.x
Cylinder 18 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46046 Knock Level Read Only Multiplier : 1 Knock Level for cylinder 19 PC3.x
Cylinder 19 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
46047 Knock Level Read Only Multiplier : 1 Knock Level for cylinder 20 PC3.x
Cylinder 20 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
46048 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 1 Offset: 0 cylinder 1
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

A029X159 (Issue 19) 335 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46049 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 2 Offset: 0 cylinder 2
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46050 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 3 Offset: 0 cylinder 3
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46051 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 4 Offset: 0 cylinder 4
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46052 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 5 Offset: 0 cylinder 5
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46053 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 6 Offset: 0 cylinder 6
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46054 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 7 Offset: 0 cylinder 7
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

Copyright © 2017 Cummins Inc. 336 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46055 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cylr 8 Offset: 0 cylinder 8
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46056 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cylinder 9 Offset: 0 cylinder 9
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46057 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cylinder 10 Offset: 0 cylinder 10
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46058 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 11 Offset: 0 cylinder 11
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46059 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 12 Offset: 0 cylinder 12
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46060 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 13 Offset: 0 cylinder 13
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

A029X159 (Issue 19) 337 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46061 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 14 Offset: 0 cylinder 14
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46062 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 15 Offset: 0 cylinder 15
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46063 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 16 Offset: 0 cylinder 16
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46064 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 17 Offset: 0 cylinder 17
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46065 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 18 Offset: 0 cylinder 18
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46066 Knock Count Read Only Multiplier : 1 Knock count value for PC3.x
Cyl 19 Offset: 0 cylinder 19
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA

Copyright © 2017 Cummins Inc. 338 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46067 Knock Count Read Only Multiplier : 1 Knock count value for PC3.x
Cyl 20 Offset: 0 cylinder 20
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
46068 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 1 Offset: 0 cylinder 1
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit: 0
Upper Limit: 65530
Default: NA
46069 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 2 Offset: 0 cylinder 2
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46070 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 3 Offset: 0 cylinder 3
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46071 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 4 Offset: 0 cylinder 4
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46072 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 5 Offset: 0 cylinder 5
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 339 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46073 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 6 Offset: 0 cylinder 6
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46074 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 7 Offset: 0 cylinder 7
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46075 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 8 Offset: 0 cylinder 8
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46076 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 9 Offset: 0 cylinder 9
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46077 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 10 Offset: 0 cylinder 10
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46078 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 11 Offset: 0 cylinder 11
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 340 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46079 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 12 Offset: 0 cylinder 12
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46080 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 13 Offset: 0 cylinder 13
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46081 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 14 Offset: 0 cylinder 14
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46082 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 15 Offset: 0 cylinder 15
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46083 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 16 Offset: 0 cylinder 16
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46084 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 17 Offset: 0 cylinder 17
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 341 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46085 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 18 Offset: 0 cylinder 18
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46086 Spark Timing Read Only Multiplier : 0.1 Spark timing degrees for PC 3.x
Cyl 19 Offset: 0 cylinder 19
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46087 Spark Timing Read Only Multiplier : 0.1 Spark timing degrees for PC 3.x
Cyl 20 Offset: 0 cylinder 20
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit: NA
Upper Limit: NA
Default: NA
46088 Internal Read Only Multiplier: 0.1 Temperature of the engine PC 3.x
SSM558 1 Offset: 0 electronic control unit
Temperature Size (bits): 16 SSM558 1
Sign: S
Unit: degF
Lower Limit:
Upper Limit:
46089 Internal Read Only Multiplier: 0.1 Temperature of the engine PC 3.x
SSM558 2 Offset: 0 electronic control unit
Temperature Size (bits): 16 SSM558 2
Sign: S
Unit: degF
Lower Limit:
Upper Limit

Copyright © 2017 Cummins Inc. 342 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46090 Internal Read Only Multiplier: 0.1 Temperature of the engine PC 3.x
MCM700 Offset: 0 electronic control unit
Temperature Size (bits): 16 MCM700
Sign: S
Unit: degF
Lower Limit:
Upper Limit
46091 Derate Read Only 0: NO Derate authorization request PC 3.x
Authorization 1: YES from customer.
2: Reserved
3: N/A
46092 Start System Read Only 0: Not Tripped Start system status monitor PC 3.x
Status 1: Tripped point.
2: Reserved
3: N/A
4: Network Failure
46093 Ventilator Fan Read Only 0: OFF Vent Fan status monitor PC 3.x
Status 1: ON point.
2: TRIPPED
3: N/A
46094 Louvres Read Only 0: Open Louvres Closed monitor point. PC 3.x
Status 1: Closed
2: Reserved
3: N/A
4: Network Failure
46095 Radiator Fan Read Only 0: OFF Radiator Fan status monitor PC 3.x
Status 1: ON point.
2: TRIPPED
3: N/A
46096 GIB Isolator Read Only 0: Close GIB Isolator Open monitor PC 3.x
Open 1: Open point.
(Aux101) 2: Reserved
3: N/A
46097 Alternator Read Only 0: OFF Alternator Heater status PC 3.x
Heater Status 1: ON monitor point.
2: TRIPPED
3: N/A
46099 Gearbox Oil Read Only 0: No Gearbox Oil Pressure monitor PC 3.x
Pressure 1: Yes point.
(Aux101) 2: Reserved
3: N/A
4: Network Failure

A029X159 (Issue 19) 343 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46100 Gearbox Oil Read Only 0: No Gearbox Oil Temperature PC 3.x
Temperature 1: Yes monitor point.
(Aux101) 2: Reserved
3: N/A
4: Network Failure
46101 Start Inhibit Read Only 0: Inactive Start Inhibit No1 monitor PC 3.x
No1 (Aux101) 1: Active point.
2: Reserved
3: N/A
46102 Start Inhibit Read Only 0: Inactive Start Inhibit No2 monitor PC 3.x
No2 (Aux101) 1: Active point.
2: Reserved
3: N/A
46103 Start Inhibit Read Only 0: Inactive Start Inhibit No3 monitor PC 3.x
No3 (Aux101) 1: Active point.
2: Reserved
3: N/A
46104 DC PSU Read Only 0: No Engine PSU Not Available PC 3.x
Unavailable 1: Yes monitor point.
(Aux101)
46105 Ventilator Fan Read Only 0: No Ventilator Fan Trip monitor PC 3.x
Trip (Aux101) 1: Yes point.

46106 Aux101-3 Read Only Multiplier: 0.01 Software version of the PC 3.x
Software Offset: 0 firmware for the Aux101-3
Version Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
46107 Aux101-4 Read Only Multiplier: 0.01 Software version of the PC 3.x
Software Offset: 0 firmware for the Aux101-4
Version Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
46108 Aux101-5 Read Only Multiplier: 0.01 Software version of the PC 3.x
Software Offset: 0 firmware for the Aux101-5
Version Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit

Copyright © 2017 Cummins Inc. 344 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46109 Engine Read Only 0: Engine Stopped Indicate current state or mode PC 2.x
Operating 1: Pre-Start of operation by the engine PC 3.x
State 2: Starting
3: Warm-Up
4: Running
5: Cool-Down
6: Engine Stopping
7: Post-Run
8: Out Of Range
9: Out Of Range
10: Out Of Range
11: Out Of Range
12: Out Of Range
13: Out Of Range
14: Out Of Range
15: N/A
46110 Fuel Pump Read Only 0: Inactive Fuel pump state PC 3.x
Control 1: Active
Status 2: Reserved
3: Not Available
46112 Fuel Shutoff Read Only 0: Closed Fuel shutoff valve status PC 3.x
Vent Valve 1: Open
status 2: Reserved
3: Not Available
46113 Downstream Read Only 0: Open The result of the FSO driver PC 3.x
Valve 1: Closed output command logic for fuel
Command 2: Reserved shutoff valve 1
Status
3: N/A
46114 Upstream Read Only 0: Open The result of the FSO driver PC 3.x
Valve 1: Closed output command logic for fuel
Command 2: Reserved shutoff valve 2.
Status
3: N/A
46115 VPS Status Read Only 0: OFF Control setting for fuel shutoff PC 3.x
1: ON valve proving system test
2: Reserved
3: N/A
46116 Gas Supply Read Only Multiplier : 0.1 Gage Pressure of gas supply PC 3.x
Pressure Offset: 0 to fuel metering device
Size (bits): 16
Sign: U
Units: psi
Lower Limit: NA
Upper Limit: NA
Default: NA

A029X159 (Issue 19) 345 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46117 Engine Oil Read Only 0: OFF Engine Oil pre heater PC 3.x
PreHeater 1: ON command status
Ctrl Status 2: Reserved
3: N/A
46118 Engine Power Read Only 0: OFF Control setting for cutting PC 3.x
Conservation 1: ON power to various devices
Ctrl Status 2: Reserved when the engine is not in use
3: Not Available
46119 Engine Read Only 0: OFF Engine coolant PreHeater PC 3.x
Coolant 1: ON states
PreHeater 2: Reserved
Ctrl Status
3: N/A
46120 Engine Read Only 0: OFF Engine coolant circulating PC 3.x
Coolant 1: ON pump status
Pump Ctrl 2: Reserved
Status
3: N/A
46121 Engine Read Only 0: Inactive Active when the engine PC 3.x
Controlled 1: Active control request a controlled
Shutdown 2: Reserved shutdown (shutdown with
Request cooldown)
3: Not Available
46122 Emergency Read Only 0: Inactive Active when the engine PC 3.x
Shutdown 1: Active control request an emergency
Request 2: Reserved shutdown (immediate
shutdown)
3: Not Available
46123 Engine Read Only Multiplier : 0.4 Derate request in percent PC 3.x
Derate Offset: 0 made by the engine control
Request Size (bits): 8
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
46124 Coolant Read Only Multiplier: 0.1 Monitor point for the Coolant PC 2.x,
Pressure Offset: 0 Pressure. PC 3.x
Size (bits): 8
Sign: U
Unit: psi
Lower Limit: NA
Upper Limit: NA

Copyright © 2017 Cummins Inc. 346 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46125 Coolant 2 Read Only Multiplier: 0.1 Monitor point for the Coolant PC 3.x
Pressure Offset: 0 2 Pressure.
Size (bits): 16
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 145
46127 Coolant 2 Read Only Multiplier: 0.1 Monitor point for the Coolant PC 3.x
Temperature Offset: 0 2 Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit:
Upper Limit:
46128 Compressor Read Only Multiplier: 0.1 Engine turbocharger PC 3.x
Bypass Offset: 0 compressor bypass actuator
Position Size (bits): 16 position
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46129 Engine Oil Read Only Multiplier : 0.1 ”Engine oil pressure at the PC 3.x
Filter Outlet Offset: 0 outlet of the filter
Pressure Size (bits): 16 Search ””17185”” (2 hits in 2
Sign: U files)”
Units: psi
Lower Limit: NA
Upper Limit: NA
Default: NA
46130 Oil Priming Read Only 0: OFF Status for the priming pump PC 3.x
Pump Control 1: ON (ON or OFF)
Status 2: Reserved
3: N/A
46131 Oil Priming Read Only 0: Low Status of the engine before PC 3.x
State 1: Optimum start (Pre-Lubed or Not)
2: Reserved
3: N/A
46132 Oil Pre- Read Only 0: Cold Status of the engine oil PC 3.x
Heated State 1: Heated before start (Pre-Heated or
2: Reserved Not)
3: N/A

A029X159 (Issue 19) 347 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46133 Coolant Pre- Read Only 0: Cold Status of the engine coolant PC 3.x
Heated State 1: Heated before start (Pre-Heated or
2: Reserved Not)
3: N/A
46134 Ventilation Read Only 0: Vented Engine Ventilation Status PC 3.x
Status 1: Not Vented (Vented or Not)
2: Ventilation Delay
3: Currently Venting
4: Reserved
5: Reserved
6: Not Able To Determine
7: Not Available
46135 Intake Read Only Multiplier: 0.1 Intake Manifold Pressure 1 PC 3.x
Manifold Offset: 0
Pressure 1 Size (bits): 16
Sign: U
Units: psi
Lower Limit: NA
Upper Limit: NA
46136 Compressor Read Only Multiplier: 0.1 Absolute Pressure at the PC 3.x
Outlet Offset: 0 outlet of the compressor.
Pressure Size (bits): 16
Sign: U
Unit: kPa
Lower Limit: NA
Upper Limit: NA
46137 Turbocharger Read Only Multiplier : 0.1 Monitor point for the PC 3.x
1 Boost Offset: 0 Turbocharger 1 Boost
Pressure Size (bits): 16 Pressure
Sign: U
Units: psi
Lower Limit: NA
Upper Limit: NA
Default: NA
46138 Genset Avg Read Only Multiplier : 0.1 Average Genset AC PC 3.x
AC Offset: 0 frequency
Frequency Size (bits): 16
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA

Copyright © 2017 Cummins Inc. 348 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46139 Fuel Valve 1 Read Only Multiplier: 0.1 Absolute Pressure of Gas on PC 3.x
Inlet Absolute Offset: 0 the inlet side of the first
Pressure Size (bits): 16 system control valve
Sign: U
Unit: psi
Lower Limit: NA
Upper Limit: NA
46140 Fuel Valve 1 Read Only Multiplier: 0.1 Absolute Pressure of Gas on PC 3.x
Outlet Offset: 0 the outlet side of the first
Absolute Size (bits): 16 system control valve
Pressure
Sign: U
Unit: psi
Lower Limit: NA
Upper Limit: NA
46141 Fuel Valve 1 Read Only Multiplier: 0.1 PC 3.x
Position Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
46142 Fuel Valve 2 Read Only Multiplier: 0.1 Absolute Pressure of Gas on PC 3.x
Inlet Absolute Offset: 0 the inlet side of the second
Pressure Size (bits): 16 system control valve
Sign: U
Unit: psi
Lower Limit: NA
Upper Limit: NA
46143 Fuel Valve 2 Read Only Multiplier: 0.1 Absolute Pressure of Gas on PC 3.x
Outlet Offset: 0 the outlet side of the second
Absolute Size (bits): 16 system control valve
Pressure
Sign: U
Unit: psi
Lower Limit: NA
Upper Limit: NA
46144 Fuel Valve 2 Read Only Multiplier: 0.1 PC 3.x
Position Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA

A029X159 (Issue 19) 349 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46145 Gas Mass Read Only Multiplier: 0.1 Gas Mass Flow value of the PC 3.x
Flow Offset: 0 engine.
Size (bits): 16
Sign: U
Unit: Pounds per hour
Lower Limit:
Upper Limit:
46146 Gas Mass Read Only Multiplier: 0.1 Gas Mass Flow value of the PC 3.x
Flow Offset: 0 engine.
Size (bits): 32
Sign: U
Unit: Pounds per hour
Lower Limit:
Upper Limit:
46147 Throttle 1 Read Only Multiplier: 0.1 Position of the throttle 1. PC 3.x
Position Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46148 Throttle 2 Read Only Multiplier: 0.1 Position of the throttle 2. PC 3.x
Position Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46149 Raw Value Read Only Multiplier : 1 Raw Value for the DE RTD PC 3.x
DE RTD Offset: 0 Bearing from the Aux101
Bearing Size (bits): 16
Sign: U
Units: Count
Lower Limit: NA
Upper Limit: NA
Default: NA
46150 Raw Value Read Only Multiplier : 1 Raw Value Alternator RTD L1 PC 3.x
Alternator Offset: 0 from Aux101 (10 bits raw
RTD L1 Size (bits): 16 data)
Sign: U
Units: Count
Lower Limit: NA
Upper Limit: NA
Default: NA

Copyright © 2017 Cummins Inc. 350 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46151 Raw Value Read Only Multiplier : 1 Raw Value Alternator RTD L2 PC 3.x
Alternator Offset: 0 from Aux101 (10 bits raw
RTD L2 Size (bits): 16 data)
Sign: U
Units: Count
Lower Limit: NA
Upper Limit: NA
Default: NA
46152 Raw Value Read Only Multiplier : 1 Raw Value Alternator RTD L3 PC 3.x
Alternator Offset: 0 from Aux101 (10 bits raw
RTD L3 Size (bits): 16 data)
Sign: U
Units: Count
Lower Limit: NA
Upper Limit: NA
Default: NA
46153 Raw Value Read Only Multiplier : 1 Raw Value NDE RTD Bearing PC 3.x
NDE RTD Offset: 0 from Aux101 (10 bits raw
Bearing Size (bits): 16 data)
Sign: U
Units: Count
Lower Limit: NA
Upper Limit: NA
Default: NA
46155 MCM700 Read Only Multiplier: 0.1 Engine Control Module PC 3.x
Battery Offset: 0 Battery Voltage.
Voltage Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
46157 CM700 Read Only Multiplier : 0.1 Engine Control Module PC 3.x
Sensor Offset: 0 CM700 Sensor Voltage A
Voltage A Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: NA
Upper Limit: NA
Default: NA

A029X159 (Issue 19) 351 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46158 CM700 Read Only Multiplier : 0.1 Engine Control Module PC 3.x
Sensor Offset: 0 CM700 Sensor Voltage B
Voltage B Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: NA
Upper Limit: NA
Default: NA
46159 CM700 Read Only Multiplier : 0.1 Engine Control Module PC 3.x
Sensor Offset: 0 CM700 Sensor Voltage C
Voltage C Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: NA
Upper Limit: NA
Default: NA
46160 SSM558 1 Read Only Multiplier : 0.1 SSM558 1 Engine Control PC 3.x
Battery Offset: 0 Module Battery Voltage.
Voltage Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: NA
Upper Limit: NA
Default: NA
46161 SSM558 1 Read Only Multiplier: 0.1 SSM558 1 Engine Control PC 3.x
Isolated Offset: 0 Module Isolated Battery
Battery Size (bits): 16 Voltage.
Voltage
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
46162 SSM558 2 Read Only Multiplier : 0.1 SSM558 2 Engine Control PC 3.x
Battery Offset: 0 Module Battery Voltage.
Voltage Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA

Copyright © 2017 Cummins Inc. 352 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46163 SSM558 2 Read Only Multiplier: 0.1 SSM558 2 Engine Control PC 3.x
Isolated Offset: 0 Module Isolated Battery
Battery Size (bits): 16 Voltage.
Voltage
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
46164 Intake Read Only Multiplier: 0.1 Intake Manifold Pressure 2 PC 3.x
Manifold Offset: 0
Pressure 2 Size (bits): 16
Sign: U
Unit: psi
Lower Limit:
Upper Limit:
46165 Intake Read only Multiplier : 0.1 Monitor point for the Intake PC 3.x
Manifold Offset: 0 Manifold Temperature 2
Temperature Size (bits): 16
2
Sign: S
Units: degF
Lower Limit: -40
Upper Limit: 410
Default: NA
46166 Exhaust Back Read Only Multiplier: 0.1 Monitor point for exhaust PC 3.x
Pressure Offset: 0 back pressure value
Size (bits): 16
Sign: U
Unit: psi
Lower Limit: -40
Upper Limit: 410
46168 Air Filter Read only Multiplier : 0.1 Monitor point for air filter PC 3.x
Differential Offset: 0 differential pressure value
Pressure Size (bits): 16
Sign: S
Unit: psi
Lower Limit: NA
Upper Limit: NA
Default: NA

A029X159 (Issue 19) 353 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46170 Gas Mass Read Only Multiplier: 0.1 Gas Mass Flow 2 value of the PC 3.x
Flow 2 Offset: 0 engine.
Size (bits): 16
Sign: U
Unit: Pounds per hour
Lower Limit:
Upper Limit:
46171 Gas Mass Read Only Multiplier: 0.1 Gas Mass Flow 2 value of the PC 3.x
Flow 2 Offset: 0 engine.
Size (bits): 32
Sign: U
Unit: Pounds per hour
Lower Limit:
Upper Limit:
46180 E-Stops Read Only 0: Inactive PC 3.x
disengaged 1: Active
46176 Gearbox Read / Write 0: No Enables gearbox protection PC 3.x
Present 1: Yes
46182 Radiator Fan Read Only 0: Inactive Radiator fan control PC 3.x
control 1: Active command

46183 Ventilator Fan Read/Write 0: Limited Vent fan control mode, limited PC 3.x
mode 1: Continuous or continuous

46184 Louvre Read Only 0: Inactive Louvre control PC 3.x


Control 1: Active
46191 Ventilator Fan Read Only 0: Inactive Ventilator fan control PC 3.x
control 1: Active command

46192 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 1
1 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
46193 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 2
2 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

Copyright © 2017 Cummins Inc. 354 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46194 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 3
3 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46195 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 4
4 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46196 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 5
5 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46197 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 6
6 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46198 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 7
7 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

A029X159 (Issue 19) 355 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46199 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 8
8 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46200 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 9
9 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46201 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 10
10 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46202 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 11
11 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46203 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 12
12 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

Copyright © 2017 Cummins Inc. 356 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46204 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 13
13 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46205 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 14
14 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46206 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 15
15 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46207 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 16
16 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46208 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 17
17 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

A029X159 (Issue 19) 357 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46209 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 18
18 Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46273 Alternator Read Only 0: No Alternator Heater monitor PC 3.x
Heater ON 1: Yes point.
(Aux101) 2: Reserved
3: N/A
4: Network Failure
46288 DE/NDE Read/Write 0: Drive End Gives reference point for PC 3.x
Cylinder 1: Non-Drive End engine cylinder numbering
Viewpoint 2: Reserved
Reference
3: N/A
46291 Radiator Fan Read Only 0: Not Tripped Radiator Fan Trip monitor PC 3.x
Trip (Aux 1: Tripped point.
101) 2: Reserved
3: N/A
46300 LBNG Genset Read/Write 0: Disable Switch to enable or disable PC 3.x
Enable 1: Enable the gas specific features and
parameters
46301 Aux101-3 Read/Write 0: Disable Enable the processing for PC 3.x
Enable 1: Enable Aux101-3 messages

46302 Aux101-4 Read/Write 0: Disable Enable the processing for PC 3.x


Enable 1: Enable Aux101-4 messages

46303 Aux101-5 Read/Write 0: Disable Enable the processing for PC 3.x


Enable 1: Enable Aux101-5 messages

46304 Aux101-6 Read/Write 0: Disable Enable the processing for PC 3.x


Enable 1: Enable Aux101-6 messages

46308 Aux101-3 Read Only Multiplier: 1 Input Port configuration bye PC 3.x
Input Port Offset: 0 for the Aux101-3
Config Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255

Copyright © 2017 Cummins Inc. 358 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46309 Aux101-4 Read Only Multiplier: 1 Input Port configuration bye PC 3.x
Input Port Offset: 0 for the Aux101-4
Config Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46310 Aux101-5 Read Only Multiplier: 1 Input Port configuration bye PC 3.x
Input Port Offset: 0 for the Aux101-5
Config Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46311 Aux101-3 DI Read Only Multiplier: 1 Digital Input Port PC 3.x
Active Offset: 0 configuration active High or
High/Low Size (bits): 16 active low for the Aux101-3
Selection
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46312 Aux101-4 DI Read Only Multiplier: 1 Digital Input Port PC 3.x
Active Offset: 0 configuration active High or
High/Low Size (bits): 16 active low for the Aux101-4
Selection
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46313 Aux101-5 DI Read Only Multiplier: 1 Digital Input Port PC 3.x
Active Offset: 0 configuration active High or
High/Low Size (bits): 16 active low for the Aux101-5
Selection
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46314 Aux101-3 DI Read Only Multiplier: 1 Discrete Input configuration PC 3.x
Config Mask Offset: 0 bit mask for the Aux101-3
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255

A029X159 (Issue 19) 359 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46315 Aux101-4 DI Read Only Multiplier: 1 Discrete Input configuration PC 3.x
Config Mask Offset: 0 bit mask for the Aux101-4
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46316 Aux101-5 DI Read Only Multiplier: 1 Discrete Input configuration PC 3.x
Config Mask Offset: 0 bit mask for the Aux101-5
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46323 Vehicle Read/Write 0: Disabled A trim that enables the PC 3.x
Electrical 1: Enabled Vehicle Electrical Power 2
Power 2 message
PGN65165
Enable
46326 Gaseous Fuel Read/Write 0: Disabled A trim that enables the PC 3.x
Pressure 1: Enabled Gaseous Fuel Pressure
PGN65163 message
Enable
46327 Fuel Read/Write 0: Disabled A trim that enables the Fuel PC 3.x
Information 3 1: Enabled Information 3 - Gaseous
- Gaseous message
PGN64930
Enable
46328 Fuel Read/Write 0: Disabled A trim that enables the Fuel PC 3.x
Information 2 1: Enabled Information 2 - Gaseous
- Gaseous message
PGN65153
Enable
46332 Inlet/Exhaust Read/Write 0: Disabled A trim that enables the PC 3.x
Conditions 1: Enabled Inlet/Exhaust Conditions
PGN65270 message
Enable
46333 Knock Count Read/Write 0: Disabled A trim that enables Knock PC 3.x
1 PGN65336 1: Enabled Count 1 message
Enable
46334 Knock Count Read/Write 0: Disabled A trim that enables Knock PC 3.x
2 PGN65337 1: Enabled Count 2 message
Enable
46335 Knock Count Read/Write 0: Disabled A trim that enables Knock PC 3.x
3 PGN65338 1: Enabled Count 3 message
Enable

Copyright © 2017 Cummins Inc. 360 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46336 Knock Count Read/Write 0: Disabled A trim that enables Knock PC 3.x
4 PGN65339 1: Enabled Count 4 message
Enable
46337 Knock Count Read/Write 0: Disabled A trim that enables Knock PC 3.x
5 PGN65340 1: Enabled Count 5 message
Enable
46338 Ignition Read/Write 0: Disabled A trim that enables the PC 3.x
Timing 1 1: Enabled Ignition Timing 1 message
PGN65154
Enable
46339 Ignition Read/Write 0: Disabled A trim that enables the PC 3.x
Timing 2 1: Enabled Ignition Timing 2 message
PGN65155
Enable
46340 Ignition Read/Write 0: Disabled A trim that enables the PC 3.x
Timing 3 1: Enabled Ignition Timing 3 message
PGN65156
Enable
46341 Ignition Read/Write 0: Disabled A trim that enables the PC 3.x
Timing 4 1: Enabled Ignition Timing 4 message
PGN65157
Enable
46342 Ignition Read/Write 0: Disabled A trim that enables the PC 3.x
Timing 5 1: Enabled Ignition Timing 5 message
PGN65158
Enable
46344 Start-Enable Read/Write 0: Disable Remote Modbus Start-Enable PC 3.x
(Modbus 1: Enabled input.
Input)
46348 Target Speed Read Only Multiplier : 0.0625 The speed reference function PC 2.x,
Offset: 0 desired speed before ramping PC 3.x
Size (bits): 16
Sign: 32
Units: rpm
Lower Limit: NA
Upper Limit: NA
Default: NA
46349 Target Speed Read Only Multiplier : 0.0625 The speed reference function PC 2.x,
Offset: 0 desired speed before ramping PC 3.x
Size (bits): 16
Sign: 32
Units: rpm
Lower Limit: NA
Upper Limit: NA
Default: NA

A029X159 (Issue 19) 361 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46364 Modbus Read Only 0: Disable Modbus Register Read Only PC 2.x,
Register 1: Enable Enable For TB15 Modbus PC 3.x
Read Only Communication Port.
Enable
46365 Modbus Read Only 0: Disable Modbus Register Read Only PC 3.x
Register 1: Enable Enable For J14 Modbus
Read Only Communication Port.
Enable (J14)
46366 Modbus Stop Read/Write 0:01 Sets the Modbus number of PC 3.x
Bits (J14) 1:02 stop bits for this node Limited
to 1 bit if parity = Odd or
Even
46367 Modbus Bus Read Only Multiplier: 1 The number of Modbus PC 3.x
Message Offset: 0 messages with no response,
Count (J14) Size (bits): 16 for J14 port only
Sign: U
Unit:
Lower Limit:
Upper Limit:
46368 Modbus CRC Read Only Multiplier: 1 The number of Modbus CRC PC 3.x
Error Count Offset: 0 errors, for J14 only.
(J14) Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit:
46369 Modbus Read Only Multiplier: 1 Modbus exception count, for PC 3.x
Exception Offset: 0 J14 only.
Count (J14) Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit:
46370 Modbus No Read Only Multiplier: 1 Modbus no response count, PC 3.x
Response Offset: 0 for J14 only.
Count (J14) Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 362 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46371 Modbus Read Only Multiplier: 1 The number of Modbus slave PC 3.x
Slave Offset: 0 messages, for J14 only.
Message Size (bits): 16
Count (J14)
Sign: U
Unit:
Lower Limit:
Upper Limit:
46372 Modbus Node Read/Write Multiplier: 1 Sets the Modbus address for PC 3.x
Address (J14) Offset: 0 this node, for J14 only.
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 247
46373 Modbus Baud Read/Write 1.6666667 Sets the baud rate for PC 3.x
Rate (J14) 3.375 Modbus communications, for
6.75 J14 only.

46374 Modbus Read/Write 0: Even Sets the Modbus parity for PC 3.x
Parity (J14) 1: Odd this node, for J14 only.
2: None
46376 Modbus Baud Read/Write 0: 2400 Baud Sets the Modbus baud rate. PC 2.x,
Rate 1: 4800 Baud PC 3.x
2: 9600 Baud
3: 19200 Baud
4: 38400 Baud
46377 Modbus Read/Write 0: Even Sets the Modbus parity for PC 2.x,
Parity 1: Odd this node PC 3.x
2: None
46378 Modbus Node Read/Write Multiplier: 1 Sets the Modbus address for PC 2.x,
Address Offset: 0 this node PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 247
46379 Modbus Stop Read/Write 0:01 Sets the Modbus number of PC 2.x,
Bits 1:02 stop bits for this node Limited PC 3.x
to 1 bit if parity = Odd or
Even

A029X159 (Issue 19) 363 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46380 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46381 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46382 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46383 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46384 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46385 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 364 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46386 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46387 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46388 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46389 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46390 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46391 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 365 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46392 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46393 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46394 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46395 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46396 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46397 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 366 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46398 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46399 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
Size (bits): 168 configurable fault text for this
fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46600 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46601 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46602 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46603 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 367 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46604 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46605 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46606 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46607 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46608 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46609 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 368 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46610 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46611 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46612 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46613 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46614 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46615 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 369 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46616 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46617 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46618 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46619 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46620 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46621 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 370 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46622 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46623 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46624 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46625 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Addr. Parameter Access Specifications Description Control


46626 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46627 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 371 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46628 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46629 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46630 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46631 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46632 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46633 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 372 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46634 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46635 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46636 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46637 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46638 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46639 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 373 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46640 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46641 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46642 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46643 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46644 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46645 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 374 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46646 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46647 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46648 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46649 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46650 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46651 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 375 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46652 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46653 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46654 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46655 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46656 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46657 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 376 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46658 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46659 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46660 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46661 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46662 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46663 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 377 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46664 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46665 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46666 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46667 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46668 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46669 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 378 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46670 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46671 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46672 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46673 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46674 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46675 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 379 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46676 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46677 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46678 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46679 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46800 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46801 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 380 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46802 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46803 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46804 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46805 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46806 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46807 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 381 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46808 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46809 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46810 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46811 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46812 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46813 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 382 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46814 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46815 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46816 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46817 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46818 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46819 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 383 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46820 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46821 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46822 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46823 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46824 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46825 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 384 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46826 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46827 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46828 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46829 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46830 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46831 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 385 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46832 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46833 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46834 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46835 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46836 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46837 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 386 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46838 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46839 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46840 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46841 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46842 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46843 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 387 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46844 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46845 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46846 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46847 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46848 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46849 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 388 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46850 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46851 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46852 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46853 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46854 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46855 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 389 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46856 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46857 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46858 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46859 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46860 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46861 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 390 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46862 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46863 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46864 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46865 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46866 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46867 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 391 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46868 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46869 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46870 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46871 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46872 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46873 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 392 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46874 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46875 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46876 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46877 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46878 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46879 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 393 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46880 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46881 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46882 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46883 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46884 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46885 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 394 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46886 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46887 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46888 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46889 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46890 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46891 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 395 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46892 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46893 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46894 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46895 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46896 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46897 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 396 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46898 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46899 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46900 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
Unit:
46901 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46902 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46903 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 397 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46904 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46905 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46906 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46907 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46908 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46909 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 398 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46910 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46911 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46912 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46913 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46914 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46915 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 399 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46916 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46917 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Addr. Parameter Access Specifications Description Control


46918 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46919 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46920 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 400 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46921 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46922 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46923 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46924 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46925 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46926 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 401 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46927 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46928 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46929 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46930 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46931 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 402 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46932 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46933 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46934 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46935 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46936 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 403 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46937 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46938 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46939 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46940 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46941 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46942 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 404 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46943 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46944 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46945 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46946 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46947 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46948 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 405 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46949 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46950 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46951 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46952 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46953 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46954 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 406 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46955 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46956 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46957 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46958 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46959 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46960 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 407 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46961 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46962 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46963 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46964 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46965 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46966 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 408 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46967 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46968 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46969 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46970 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46971 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46972 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 409 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46973 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46974 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46975 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46976 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46977 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46978 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 410 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46979 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46980 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46981 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46982 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46983 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46984 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 411 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46985 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46986 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46987 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46988 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46989 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46990 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

Copyright © 2017 Cummins Inc. 412 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46991 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46992 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46993 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46994 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46995 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46996 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 19) 413 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


46997 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46998 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46999 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text Size (bits): 168 the displayed configurable
fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
47002 GK1 (60Hz) Read Only Multiplier: 1 The governor 60Hz K1 gain PC 2.x,
Offset: 0 adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47003 GK2 (60Hz) Read Only Multiplier: 1 The governor 60Hz integral PC 2.x,
Offset: 0 gain adjust. PC 3.x
Size (bits): 168
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47004 GK3 (60Hz) Read Only Multiplier: 1 The governor 60Hz K3 gain PC 2.x,
Offset: 0 adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

Copyright © 2017 Cummins Inc. 414 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


47005 Governor Read Only Multiplier: 1.52587890625E- The governor 60Hz damping PC 2.x,
Damping 05 adjust. PC 3.x
Effect (60Hz) Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0.6
Upper Limit: 0.95
47006 GK1 (50Hz) Read Only Multiplier: 1 The governor 50Hz K1 gain PC 2.x,
Offset: 0 adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47007 GK2 (50Hz) Read Only Multiplier: 1 The governor 50Hz integral PC 2.x,
Offset: 0 gain adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47008 GK3 (50Hz) Read Only Multiplier: 1 The governor 50Hz K3 gain PC 2.x,
Offset: 0 adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47009 Governor Read Only Multiplier: The governor 50Hz damping PC 2.x,
Damping 1.52587890625E–05 adjust. PC 3.x
Effect (50Hz) Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0.6
Upper Limit: 0.95
47010 GK1(Idle) Read Only Multiplier: 1 This trim is used to adjust gk1 PC 2.x,
Offset: 0 in idle mode. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

A029X159 (Issue 19) 415 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


47011 GK2(Idle) Read Only Multiplier: 1 This trim is used to adjust gk2 PC 2.x,
Offset: 0 in idle mode. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47014 Gain Read Only 0: Disable Either enables or disables PC 2.x,
Windowing 1: Enable Gain Windowing feature. PC 3.x
Enable
47015 GK1 Read Only Multiplier: 1 The governor 50Hz K1 low PC 2.x,
Low(50Hz) Offset: 0 gain adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47016 GK1 Read Only Multiplier: 1 The governor 60Hz K1 low PC 2.x,
Low(60Hz) Offset: 0 gain adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47017 GK1 Read Only Multiplier: 1 The governor 50Hz K1 high PC 2.x,
High(50Hz) Offset: 0 gain adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47018 GK1 Read Only Multiplier: 1 The governor 60Hz K1 high PC 2.x,
High(60Hz) Offset: 0 gain adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

Copyright © 2017 Cummins Inc. 416 A029X159 (Issue 19)


8-2017 5. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


47019 Governor Read Only Multiplier: 1 The speed error higher limit. PC 2.x,
Speed Delta Offset: 0 PC 3.x
High Size (bits): 16
Sign: U
Unit:
Lower Limit: 50
Upper Limit: 1000
47020 Governor Read Only Multiplier: 1 The speed error lower limit. PC 2.x,
Speed Delta Offset: 0 PC 3.x
Low Size (bits): 16
Sign: U
Unit:
Lower Limit: 50
Upper Limit: 1000
47021 Intake Read Only 0: PGBU Either PGBU(Onan) or PC 2.x,
Manifold 1: EBU EBU(Cummins) sensor. PC 3.x
Temperature
Sensor Type
47022 Intake Read Only 0: Disable Intake Manifold Temperature PC 2.x,
Manifold 1: Enable Sensor available or not. PC 3.x
Temperature
Sensor
Enable
47023 Oil Read Only 0: PGBU Either PGBU(Onan) or PC 2.x,
Temperature 1: EBU EBU(Cummins) sensor. PC 3.x
Sensor Type
47024 Oil Read Only 0: Disable High Oil Temperature Sensor PC 2.x,
Temperature 1: Enable available or not. PC 3.x
Sensor
Enable
47025 AVR PWM Read Only Multiplier: 0.01 The AVR PWM software PC 2.x,
Command Offset: 0 command. Linear relationship PC 3.x
Size (bits): 16 between counts and % duty
cycle with 10000
Sign: U
counts=100% duty cycle.
Unit: %
Lower Limit:
Upper Limit:
47026 Coolant Read Only 0: Disable Coolant Temperature 2 PC 3.x
Temperature 1: Enable Enable
2 Enable

A029X159 (Issue 19) 417 Copyright © 2017 Cummins Inc.


5. PowerCommand 2.x/3.x Modbus Register Map 8-2017

Addr. Parameter Access Specifications Description Control


47027 Start Inhibit Read Only Multiplier : 0.05 Delay progress until a fault is PC 3.x
Delay Offset: 0 declared for start inhibit
Progress Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: NA
Upper Limit: NA
Default: NA
47028 Genset Read Only 0: Close Indicates the Genset Voltage PC 3.x
Voltage 1: Open sensing MCB status.
Sensing MCB 2: Reserved
status
3: N/A
4: Network Failure
47029 Customer Read Only 0: Open Indicates the status of the PC 3.x
Gas Valve 1: Closed Customer Gas Valve position.
Status 2: Reserved
3: N/A
4: Network Failure
47030 Crankcase Read Only Multiplier : 0.01 Monitor point for the PC 2.x
Pressure Offset: 0 Crankcase Pressure with PC 3.x
Extended Size (bits): 16 extended precision.
Sign: S
Units: psi
Lower Limit: -35.67
Upper Limit: 38
Default: NA

Copyright © 2017 Cummins Inc. 418 A029X159 (Issue 19)


6 PowerCommand 2.x/3.x Modbus Fault
Status Bitmaps
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

NOTICE
The Master device can read 1-40 contiguous registers, write 1-40 contiguous registers, or read
diagnostic counters.

Fault
Addr. Bit# Name Event Name Response Control
Code

Fault Status Engine Magnetic Crankshaft PC 2.x,


40400 0 115 Shutdown
Bitmap 1 Speed/Position PC 3.x

Fault Status Intake Manifold 1 Pressure: Vtg PC 2.x,


40400 1 122 Warning
Bitmap 1 Above Normal PC 3.x

Fault Status Intake Manifold 1 Pressure: Vtg PC 2.x,


40400 2 123 Warning
Bitmap 1 Below Normal PC 3.x

Fault Status Intake Manifold 1 Pressure: PC 2.x,


40400 3 124 Warning
Bitmap 1 Moderately Severe PC 3.x

Fault Status Engine Oil Rifle Pressure 1: Vtg PC 2.x,


40400 4 135 Warning
Bitmap 1 Above Normal PC 3.x

Fault Status Engine Oil Rifle Pressure 1: Vtg PC 2.x,


40400 5 141 Warning
Bitmap 1 Below Normal PC 3.x

Fault Status Engine Oil Rifle Pressure - PC 2.x,


40400 6 143 Warning
Bitmap 1 Moderately Severe PC 3.x

Fault Status Engine Coolant Temp 1: Vtg Above PC 2.x,


40400 7 144 Warning
Bitmap 1 Normal PC 3.x

Fault Status Engine Coolant Temp 1: Vtg Below PC 2.x,


40400 8 145 Warning
Bitmap 1 Normal PC 3.x

Fault Status Engine Coolant Temp: Moderately PC 2.x,


40400 9 146 Derate
Bitmap 1 Above Normal PC 3.x

Fault Status Engine Coolant Temp: Severely PC 2.x,


40400 10 151 Shutdown
Bitmap 1 Above Normal PC 3.x

A029X159 (Issue 19) 419 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code

Fault Status Intake Manifold 1 Temp: Vtg Above PC 2.x,


40400 11 153 Warning
Bitmap 1 Normal PC 3.x

Fault Status Intake Manifold 1 Temp: Vtg Below PC 2.x,


40400 12 154 Warning
Bitmap 1 Normal PC 3.x

Fault Status Intake Manifold 1 Temp: Severely PC 2.x,


40400 13 155 Shutdown
Bitmap 1 Above Normal PC 3.x

Fault Status PC 2.x,


40400 14 187 Sensor Supply 2: Vtg Below Normal Warning
Bitmap 1 PC 3.x

Fault Status Coolant Level Sensor 1: Vtg Above PC 2.x,


40400 15 195 Warning
Bitmap 1 Normal PC 3.x

Fault Status Coolant Level Sensor 1: Vtg Below PC 2.x,


40401 0 196 Warning
Bitmap 2 Normal PC 3.x

Fault Status Coolant Level: Below Normal - PC 2.x,


40401 1 197 Warning
Bitmap 2 Moderately Severe PC 3.x

Fault Status Engine Oil Temp Sensor 1: Vtg PC 2.x,


40401 2 212 Warning
Bitmap 2 Above Normal PC 3.x

Fault Status Engine Oil Temp Sensor 1: Vtg PC 2.x,


40401 3 213 Warning
Bitmap 2 below Normal PC 3.x

Fault Status Engine Oil Temp: Above Normal - PC 2.x,


40401 4 214 Shutdown
Bitmap 2 Most severe PC 3.x

Fault Status Barometric Pressure: Vtg Above PC 2.x,


40401 5 221 Warning
Bitmap 2 Normal PC 3.x

Fault Status Barometric Pressure Sensor: Vtg PC 2.x,


40401 6 222 Warning
Bitmap 2 Below Normal PC 3.x

Fault Status Engine Oil Burn Valve Solenoid: Vtg PC 2.x,


40401 7 223 Warning
Bitmap 2 Below Normal PC 3.x

Fault Status Engine Oil Burn Valve Solenoid: Vtg PC 2.x,


40401 8 224 Warning
Bitmap 2 Above Normal PC 3.x

Fault Status PC 2.x,


40401 9 227 Sensor Supply 2: Vtg Above Normal Warning
Bitmap 2 PC 3.x

Fault Status Coolant Pressure: Below Normal- PC 2.x,


40401 10 228 Shutdown
Bitmap 2 Most Severe PC 3.x

Fault Status Coolant Pressure Sensor: Vtg Above PC 2.x,


40401 11 231 Warning
Bitmap 2 Normal PC 3.x

Fault Status Coolant Pressure Sensor: Vtg Below PC 2.x,


40401 12 232 Warning
Bitmap 2 Normal PC 3.x

Fault Status Engine Crankshaft Speed/Posn: PC 2.x,


40401 13 234 Shutdown
Bitmap 2 Above Normal PC 3.x

Copyright © 2017 Cummins Inc. 420 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code

Fault Status Coolant Level: Below Normal-Most PC 2.x,


40401 14 235 Shutdown
Bitmap 2 Severe PC 3.x

Fault Status PC 2.x,


40401 15 238 Sensor Supply 3: Vtg Below Normal Warning
Bitmap 2 PC 3.x

Fault Status PC 2.x,


40402 0 239 Voltage Supply C High Error Warning
Bitmap 3 PC 3.x

Fault Status Radiator Fan Control Driver Low PC 2.x,


40402 1 245 Warning
Bitmap 3 Error PC 3.x

Fault Status Engine Fuel Temp: Above Normal- PC 2.x,


40402 2 261 Warning
Bitmap 3 Moderately Severe PC 3.x

Fault Status Engine Fuel Temp Sensor 1: Vtg PC 2.x,


40402 3 263 Warning
Bitmap 3 Above Normal PC 3.x

Fault Status Engine Fuel Temp Sensor 1: Vtg PC 2.x,


40402 4 265 Warning
Bitmap 3 Below Normal PC 3.x

Fault Status Engine Fuel Temp: Above Normal- PC 2.x,


40402 5 266 Shutdown
Bitmap 3 Most severe PC 3.x

Fault Status Fuel Pump Pressurizing Assembly 1: PC 2.x,


40402 6 271 Warning
Bitmap 3 Vtg Below Normal PC 3.x

Fault Status Fuel Pump Pressurizing Assembly 1: PC 2.x,


40402 7 272 Warning
Bitmap 3 Vtg Above Normal PC 3.x

Fault Status APC_Diesel_CYL_PRS_IMBAL_Erro PC 2.x,


40402 8 281 Warning
Bitmap 3 r PC 3.x

Fault Status SAE J1939 Muxing PGN Timeout: PC 2.x,


40402 9 285 Warning
Bitmap 3 Abnormal Update Rate PC 3.x

Fault Status SAE J1939 Muxing Config: Out of PC 2.x,


40402 10 286 Warning
Bitmap 3 Calibration PC 3.x

Fault Status PC 2.x,


40402 13 295 Ambient_Air_Press_KeyOn_Error Warning
Bitmap 3 PC 3.x

Fault Status RTC PWR Intr: Data Erratic PC 2.x,


40402 14 319 Warning
Bitmap 3 Intermittent or Wrong PC 3.x

Fault Status Injector Solenoid Driver Cylinder 1: PC 2.x,


40402 15 322 Warning
Bitmap 3 UnderCurrent PC 3.x

Fault Status Injector Solenoid Driver Cylinder 5: PC 2.x,


40403 0 323 Warning
Bitmap 4 UnderCurrent PC 3.x

Fault Status Injector Solenoid Driver Cylinder 3: PC 2.x,


40403 1 324 Warning
Bitmap 4 UnderCurrent PC 3.x

Fault Status Injector Solenoid Driver Cylinder 6: PC 2.x,


40403 2 325 Warning
Bitmap 4 UnderCurrent PC 3.x

A029X159 (Issue 19) 421 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code

Fault Status Injector Solenoid Driver Cylinder 2: PC 2.x,


40403 3 331 Warning
Bitmap 4 UnderCurrent PC 3.x

Fault Status Injector Solenoid Driver Cylinder 4: PC 2.x,


40403 4 332 Warning
Bitmap 4 UnderCurrent PC 3.x

Fault Status Electronic Calibration Code: Out of PC 2.x,


40403 6 342 Shutdown
Bitmap 4 Calibration PC 3.x

Fault Status Eng Ctrl: internal h/w failure-Bad PC 2.x,


40403 7 343 Warning
Bitmap 4 Device/Component PC 3.x

Fault Status Injector Power Supply: Bad PC 2.x,


40403 8 351 Warning
Bitmap 4 Device/Component PC 3.x

Fault Status PC 2.x,


40403 9 352 Sensor Supply 1: Vtg Below Normal Warning
Bitmap 4 PC 3.x

Fault Status PC 2.x,


40403 10 359 Fail To Start Fault Shutdown
Bitmap 4 PC 3.x

Fault Status PC 2.x,


40403 11 386 Sensor Supply 1: Vtg Above Normal Warning
Bitmap 4 PC 3.x

Fault Status Eng Oil Rifle Pressure: Below PC 2.x,


40403 12 415 Shutdown
Bitmap 4 Normal-Most Severe PC 3.x

Fault Status Water in Fuel Indicator: Above PC 2.x,


40403 13 418 Warning
Bitmap 4 Normal-Least Severe PC 3.x

Fault Status Eng Oil Temp: Above Normal- PC 2.x,


40403 14 421 Warning
Bitmap 4 Moderately Severe PC 3.x

Fault Status PC 2.x,


40403 15 422 Coolant_Level_Reading_Incorrect Warning
Bitmap 4 PC 3.x

Fault Status PC 2.x,


40404 0 425 OIL_Temperature_In_Range_Error Warning
Bitmap 5 PC 3.x

Fault Status J1939 Datalink: Data PC 2.x,


40404 1 426 NONE
Bitmap 5 Erratic/Intermittent/Wrong PC 3.x

Fault Status PC 2.x,


40404 2 427 CAN Datalink Degraded Warning
Bitmap 5 PC 3.x

Fault Status PC 2.x,


40404 3 435 OIL_Pressure_Switch_Error Warning
Bitmap 5 PC 3.x

Fault Status PC 2.x,


40404 4 441 Low Battery Voltage Warning
Bitmap 5 PC 3.x

Fault Status PC 2.x,


40404 5 442 High Battery Voltage Warning
Bitmap 5 PC 3.x

Fault Status Injector Metering Rail 1 Pressure: PC 2.x,


40404 6 449 Shutdown
Bitmap 5 Above Normal PC 3.x

Copyright © 2017 Cummins Inc. 422 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code

Fault Status Injector Metering Rail 1 Pressure: Vtg PC 2.x,


40404 7 451 Warning
Bitmap 5 Above Normal PC 3.x

Fault Status Injector Metering Rail 1 Pressure: Vtg PC 2.x,


40404 8 452 Warning
Bitmap 5 Below Normal PC 3.x

Fault Status Intake Manifold 1 Temp: Above PC 2.x,


40404 9 488 Derate
Bitmap 5 Normal-Moderate PC 3.x

Fault Status Fuel Delivery Pressure: Vtg Above PC 2.x,


40404 10 546 Warning
Bitmap 5 Normal PC 3.x

Fault Status Fuel Delivery Pressure: Vtg Below PC 2.x,


40404 11 547 Warning
Bitmap 5 Normal PC 3.x

Fault Status PC 2.x,


40404 12 553 APC_Diesel_High_PRS_Error Warning
Bitmap 5 PC 3.x

Fault Status PC 2.x,


40404 13 554 APC_DieselL_PRS_SIR_Error Warning
Bitmap 5 PC 3.x

Fault Status Injector Metering Rail 1 Pressure: PC 2.x,


40404 15 559 Warning
Bitmap 5 Below Normal PC 3.x

Fault Status Engine Shut Down Hot Condition PC 2.x,


40405 1 611 Warning
Bitmap 6 Exists PC 3.x

Fault Status PC 2.x,


40405 2 698 ECM Internal Temperature Low Error Warning
Bitmap 6 PC 3.x

Fault Status PC 2.x,


40405 3 689 Eng Crankshaft Speed/Pos Warning Warning
Bitmap 6 PC 3.x

Fault Status Eng Speed: Cam/Crankshaft PC 2.x,


40405 4 731 Warning
Bitmap 6 Misalignment PC 3.x

Fault Status At Least One ACK: Most Severe PC 2.x,


40405 5 2661 Shutdown
Bitmap 6 Fault PC 3.x

Fault Status PC 2.x,


40405 6 781 CAN Datalink Failed Shutdown
Bitmap 6 PC 3.x

Fault Status PC 2.x,


40405 7 1117 Power Lost With Ignition On Warning
Bitmap 6 PC 3.x

Fault Status PC 2.x,


40405 8 1122 Rated to Idle Transition NONE
Bitmap 6 PC 3.x

Fault Status PC 2.x,


40405 9 1124 Delayed Shutdown Fault Warning
Bitmap 6 PC 3.x

Fault Status PC 2.x,


40405 10 1131 Battle Short Mode Active Warning
Bitmap 6 PC 3.x
Fault Status
40405 11 1132 Controlled Shutdown In Process Warning PC 3.x
Bitmap 6

A029X159 (Issue 19) 423 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code

Fault Status PC 2.x,


40405 13 1243 Engine Derate Derate
Bitmap 6 PC 3.x

Fault Status Shutdown PC 2.x,


40405 14 1244 Engine Normal Shutdown
Bitmap 6 w/Cooldown PC 3.x

Fault Status PC 2.x,


40405 15 1245 Engine Shutdown Shutdown
Bitmap 6 PC 3.x

Fault Status PC 2.x,


40406 0 1246 Unrecognized Engine Fault Warning
Bitmap 7 PC 3.x

Fault Status PC 2.x,


40406 1 1247 Engine Shutdown – Unannounced Shutdown
Bitmap 7 PC 3.x

Fault Status PC 2.x,


40406 2 1248 Engine Warning Warning
Bitmap 7 PC 3.x

Fault Status Ctrl Module ID Input State Warning PC 2.x,


40406 3 1256 Warning
Bitmap 7 Error PC 3.x

Fault Status Ctrl Module ID I/P State shutdown PC 2.x,


40406 4 1257 Shutdown
Bitmap 7 Error PC 3.x
Fault Status
40406 5 1322 kW Load Setpoint OOR High Warning PC 3.x
Bitmap 7
Fault Status
40406 6 1323 kW Load Setpoint OOR Low Warning PC 3.x
Bitmap 7
Fault Status
40406 7 1324 kVAR Load Setpoint OOR High Warning PC 3.x
Bitmap 7
Fault Status
40406 8 1325 kVAR Load Setpoint OOR Low Warning PC 3.x
Bitmap 7

Fault Status PC 2.x,


40406 9 1336 Cooldown Completed Fault Shutdown
Bitmap 7 PC 3.x

Fault Status Eng Oil Level Remote Reservoir: PC 2.x,


40406 10 1357 Warning
Bitmap 7 Below Normal PC 3.x

Fault Status Eng Oil Level Remote Reservoir: PC 2.x,


40406 11 219 Warning
Bitmap 7 Least Severe Level PC 3.x

Fault Status PC 2.x,


40406 12 233 HT Coolant Pressure Moderate Low Warning
Bitmap 7 PC 3.x

Fault Status PC 2.x,


40406 13 254 FSO NON Low Control Error Shutdown
Bitmap 7 PC 3.x

Fault Status PC 2.x,


40406 14 686 Turbo 1 Speed Incorrect Warning
Bitmap 7 PC 3.x

Fault Status PC 2.x,


40406 15 697 ECM Internal Temperature High Error Warning
Bitmap 7 PC 3.x

Copyright © 2017 Cummins Inc. 424 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code

Fault Status PC 2.x,


40407 0 1376 Eng Camshaft Speed/Pos Warning Warning
Bitmap 8 PC 3.x
Fault Status
40407 1 3611 Custom Overcurrent Fault Warning PC 3.x
Bitmap 8
Fault Status
40407 2 3513 Negative Sequence Overcurrent Warning PC 3.x
Bitmap 8

Fault Status PC 2.x,


40407 3 1416 Fail to Shutdown Warning
Bitmap 8 PC 3.x

Fault Status PC 2.x,


40407 4 1417 Power Down Failure Warning
Bitmap 8 PC 3.x

Fault Status PC 2.x,


40407 5 1433 Local E-Stop Shutdown
Bitmap 8 PC 3.x

Fault Status PC 2.x,


40407 6 1434 Remote E-Stop Shutdown
Bitmap 8 PC 3.x

Fault Status PC 2.x,


40407 7 1435 Low Coolant Temperature Warning
Bitmap 8 PC 3.x

Fault Status PC 2.x,


40407 8 1438 Fail To Crank Fault Shutdown
Bitmap 8 PC 3.x

Fault Status PC 2.x,


40407 9 1439 Low Fuel in Day Tank Warning
Bitmap 8 PC 3.x

Fault Status PC 2.x,


40407 10 1441 Low Fuel Level Warning
Bitmap 8 PC 3.x

Fault Status PC 2.x,


40407 11 1442 Weak Battery Warning
Bitmap 8 PC 3.x

Fault Status PC 2.x,


40407 12 1443 Dead Battery Shutdown
Bitmap 8 PC 3.x

Fault Status PC 2.x,


40407 13 1444 Overload Warning
Bitmap 8 PC 3.x

Fault Status PC 2.x,


40407 14 1445 Short Circuit Shutdown
Bitmap 8 PC 3.x

Fault Status PC 2.x,


40407 15 1446 High AC Voltage Shutdown
Bitmap 8 PC 3.x

Fault Status PC 2.x,


40408 0 1447 Low AC Voltage Shutdown
Bitmap 9 PC 3.x

Fault Status PC 2.x,


40408 1 1448 Underfrequency Shutdown
Bitmap 9 PC 3.x

Fault Status PC 2.x,


40408 2 1449 Overfrequency Warning
Bitmap 9 PC 3.x

A029X159 (Issue 19) 425 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code

Fault Status PC 2.x,


40408 3 1459 Reverse kW Shutdown
Bitmap 9 PC 3.x

Fault Status PC 2.x,


40408 4 1461 Loss of Field Shutdown
Bitmap 9 PC 3.x

Fault Status PC 2.x,


40408 5 1463 Not In Auto NONE
Bitmap 9 PC 3.x

Fault Status PC 2.x,


40408 6 1464 Load Dump Warning
Bitmap 9 PC 3.x

Fault Status PC 2.x,


40408 7 1465 Ready To Load NONE
Bitmap 9 PC 3.x

Fault Status PC 2.x,


40408 8 1469 Speed/Frequency Mismatch Fault Shutdown
Bitmap 9 PC 3.x

Fault Status PC 2.x,


40408 9 1471 High Current Warning Warning
Bitmap 9 PC 3.x

Fault Status PC 2.x,


40408 10 1472 Overcurrent Shutdown Shutdown
Bitmap 9 PC 3.x

Fault Status PC 2.x,


40408 11 1483 Common Alarm None
Bitmap 9 PC 3.x

Fault Status Injector Solenoid Driver Cylinder 7: PC 2.x,


40408 12 1548 Warning
Bitmap 9 UnderCurrent PC 3.x

Fault Status Injector Solenoid Driver Cylinder 8: PC 2.x,


40408 13 1549 Warning
Bitmap 9 UnderCurrent PC 3.x

Fault Status Injector Solenoid Driver Cylinder 10: PC 2.x,


40408 14 1551 Warning
Bitmap 9 UnderCurrent PC 3.x

Fault Status Injector Solenoid Driver Cylinder 11: PC 2.x,


40408 15 1552 Warning
Bitmap 9 UnderCurrent PC 3.x

Fault Status Injector Solenoid Driver Cylinder 12: PC 2.x,


40409 0 1553 Warning
Bitmap 10 UnderCurrent PC 3.x

Fault Status Injector Solenoid Driver Cylinder 13: PC 2.x,


40409 1 1554 Warning
Bitmap 10 UnderCurrent PC 3.x

Fault Status Injector Solenoid Driver Cylinder 14: PC 2.x,


40409 2 1555 Warning
Bitmap 10 UnderCurrent PC 3.x

Fault Status Injector Solenoid Driver Cylinder 15: PC 2.x,


40409 3 1556 Warning
Bitmap 10 UnderCurrent PC 3.x

Fault Status Injector Solenoid Driver Cylinder 16: PC 2.x,


40409 4 1557 Warning
Bitmap 10 UnderCurrent PC 3.x

Fault Status Injector Solenoid Driver Cylinder 9: PC 2.x,


40409 7 1622 Warning
Bitmap 10 UnderCurrent PC 3.x

Copyright © 2017 Cummins Inc. 426 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code

Fault Status Real Time Clock Power Interrupt PC 2.x,


40409 8 1689 Warning
Bitmap 10 Fault PC 3.x

Fault Status Sensor_Supply_5_Voltage_High_Err PC 2.x,


40409 9 1695 Warning
Bitmap 10 or PC 3.x

Fault Status SENSOR_SUPPLY_5_VOLTAGE_L PC 2.x,


40409 10 1696 Warning
Bitmap 10 OW_ERROR PC 3.x

Fault Status Crankcase Pressure: Vtg Above PC 2.x,


40409 11 1843 Warning
Bitmap 10 Normal PC 3.x

Fault Status Crankcase Pressure: Vtg Below PC 2.x,


40409 12 1844 Warning
Bitmap 10 Normal PC 3.x

Fault Status Water in Fuel Indicator: Vtg Above PC 2.x,


40409 13 1845 Warning
Bitmap 10 Normal PC 3.x

Fault Status Water in Fuel Indicator: Vtg Below PC 2.x,


40409 14 1846 Warning
Bitmap 10 Normal PC 3.x

Fault Status Eng Coolant Temp - Shutdown Shutdown PC 2.x,


40409 15 1847
Bitmap 10 w/Cool w/Cooldown PC 3.x

Fault Status Water in Fuel Indicator: Above PC 2.x,


40410 0 1852 Warning
Bitmap 11 Normal-Moderate PC 3.x

Fault Status PC 2.x,


40410 1 1853 HMI113 Fault 1 NONE
Bitmap 11 PC 3.x

Fault Status PC 2.x,


40410 2 1854 HMI113 Fault 2 NONE
Bitmap 11 PC 3.x

Fault Status PC 2.x,


40410 3 1855 HMI113 Fault 3 NONE
Bitmap 11 PC 3.x

Fault Status PC 2.x,


40410 5 1891 Eng Oil Change Interval Warning
Bitmap 11 PC 3.x

Fault Status J39_EGR_Valve_Comm_Timeout_Er PC 2.x,


40410 6 1893 Warning
Bitmap 11 ror PC 3.x

Fault Status PC 2.x,


40410 7 1894 J39_VGT_Comm_Timeout_Error Warning
Bitmap 11 PC 3.x

Fault Status PC 2.x,


40410 8 1896 EGR_DL_Valve_Stuck_Error Warning
Bitmap 11 PC 3.x

Fault Status PC 2.x,


40410 9 1899 EGR_Delta_P_IR_Low_Error Warning
Bitmap 11 PC 3.x
Fault Status
40410 11 1912 Utility Loss Of Phase Warning PC 3.x
Bitmap 11
Fault Status
40410 12 1913 Genset Loss Of Phase Warning PC 3.x
Bitmap 11

A029X159 (Issue 19) 427 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status
40410 13 1914 Utility Phase Rotation Warning PC 3.x
Bitmap 11
Fault Status
40410 14 1915 Genset Phase Rotation Warning PC 3.x
Bitmap 11
Fault Status
40410 15 1916 Sync Check OK NONE PC 3.x
Bitmap 11

Fault Status PC 2.x,


40411 0 1917 High Fuel Level Warning
Bitmap 12 PC 3.x

Fault Status PC 2.x,


40411 1 1918 Very Low Fuel Level Shutdown
Bitmap 12 PC 3.x

Fault Status PC 2.x,


40411 2 1933 EGR_DL_Voltage_High_Error Warning
Bitmap 12 PC 3.x

Fault Status PC 2.x,


40411 3 1934 EGR_DL_Voltage_Low_Error Warning
Bitmap 12 PC 3.x

Fault Status PC 2.x,


40411 4 1935 EGR_DL_Command_Source_Error Warning
Bitmap 12 PC 3.x

Fault Status PC 2.x,


40411 5 1942 Beyond_THD_AZ_Error Warning
Bitmap 12 PC 3.x

Fault Status PC 2.x,


40411 6 1943 CBR_Density_Detrat_Error_ID NONE
Bitmap 12 PC 3.x

Fault Status PC 2.x,


40411 7 1944 HMI113 Output Configuration Fault Warning
Bitmap 12 PC 3.x

Fault Status PC 2.x,


40411 8 1961 EGR_DL_EDU_TMPTR_High_Error Warning
Bitmap 12 PC 3.x

Fault Status Crankcase_Pressure_Least_Sev_Hig PC 2.x,


40411 9 1974 Warning
Bitmap 12 h PC 3.x

Fault Status Eng Crankshaft Speed/Posn: Above PC 2.x,


40411 10 1992 Shutdown
Bitmap 12 Normal PC 3.x
Fault Status
40411 11 1999 Maximum Parallel Time Warning PC 3.x
Bitmap 12

Fault Status PC 2.x,


40411 12 2185 Sensor Supply 4: Vtg Above Normal Warning
Bitmap 12 PC 3.x

Fault Status PC 2.x,


40411 13 2186 Sensor Supply 4: Vtg Below Normal Warning
Bitmap 12 PC 3.x

Fault Status Fuel Pump Delivery Pressure: Below PC 2.x,


40411 14 2215 Warning
Bitmap 12 Normal PC 3.x

Fault Status PC 2.x,


40411 15 2249 APC_Diesel_Low2_Prs_Error Warning
Bitmap 12 PC 3.x

Copyright © 2017 Cummins Inc. 428 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code

Fault Status Fuel Pump Delivery Pressure: Above PC 2.x,


40412 0 2261 Warning
Bitmap 13 Normal PC 3.x

Fault Status PC 2.x,


40412 1 2262 Fuel Pump Delivery-Below Normal Warning
Bitmap 13 PC 3.x

Fault Status Electric Lift Pump for Eng Fuel: Vtg PC 2.x,
40412 2 2265 Warning
Bitmap 13 Above Normal PC 3.x

Fault Status Electric Lift Pump for Eng Fuel: Vtg PC 2.x,
40412 3 2266 Warning
Bitmap 13 Below Normal PC 3.x

Fault Status PC 2.x,


40412 4 2292 APC_Diesel_Flow_High_Error Warning
Bitmap 13 PC 3.x

Fault Status PC 2.x,


40412 5 2293 APC_Diesel_Flow_Low_Error Warning
Bitmap 13 PC 3.x

Fault Status Electronic Fuel Injection Control PC 2.x,


40412 6 2311 Warning
Bitmap 13 Valve PC 3.x
Fault Status
40412 7 2328 Utility Available NONE PC 3.x
Bitmap 13
Fault Status
40412 8 2331 Utility Undervoltage Warning PC 3.x
Bitmap 13
Fault Status
40412 9 2332 Utility Connected NONE PC 3.x
Bitmap 13
Fault Status
40412 10 2333 Genset Connected NONE PC 3.x
Bitmap 13

Fault Status Excitation/Loss of AC Voltage PC 2.x,


40412 11 2335 Shutdown
Bitmap 13 Sensing PC 3.x

Fault Status PC 2.x,


40412 13 2342 Too Long in Idle Warning
Bitmap 13 PC 3.x
Fault Status
40412 14 2358 Utility Overvoltage Warning PC 3.x
Bitmap 13

Fault Status PC 2.x,


40412 15 2377 Fan Control: Vtg Above Normal Warning
Bitmap 13 PC 3.x
Fault Status
40413 0 2396 Utility Breaker Fail To Close Warning PC 3.x
Bitmap 14
Fault Status
40413 1 2397 Utility Breaker Fail To Open Warning PC 3.x
Bitmap 14
Fault Status
40413 2 3226 Base Load NONE PC 3.x
Bitmap 14
Fault Status
40413 3 3227 Peak Shave NONE PC 3.x
Bitmap 14

Fault Status PC 2.x,


40413 4 2555 GHC_Low_Voltage_Error_1 Warning
Bitmap 14 PC 3.x

A029X159 (Issue 19) 429 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code

Fault Status PC 2.x,


40413 5 2556 GHC_High_Voltage_Error_1 Warning
Bitmap 14 PC 3.x

Fault Status PC 2.x,


40413 6 2678 Charging Alternator Failure Fault Warning
Bitmap 14 PC 3.x
Fault Status
40413 7 2965 Genset Available NONE PC 3.x
Bitmap 14

Fault Status PC 2.x,


40413 8 2971 Test/Exercise is Active Fault NONE
Bitmap 14 PC 3.x

Fault Status PC 2.x,


40413 9 2972 Field Overload Shutdown
Bitmap 14 PC 3.x

Fault Status PC 2.x,


40413 10 2973 Charge_Press_IR_Error Warning
Bitmap 14 PC 3.x

Fault Status PC 2.x,


40413 11 2943 Manual Switch Configuration Fault Warning
Bitmap 14 PC 3.x

Fault Status PC 2.x,


40413 12 2944 Auto Switch Configuration Fault Warning
Bitmap 14 PC 3.x

Fault Status PC 2.x,


40413 13 2914 Genset AC Meter Failed Shutdown
Bitmap 14 PC 3.x
Fault Status
40413 14 2915 Genset Bus AC Meter Failed Warning PC 3.x
Bitmap 14
Fault Status
40413 15 2916 Utility AC Meter Failed Warning PC 3.x
Bitmap 14

Fault Status PC 2.x,


40414 0 2814 Genset CT Ratio Too Small Shutdown
Bitmap 15 PC 3.x

Fault Status PC 2.x,


40414 1 2815 Genset CT Ratio Too Large Warning
Bitmap 15 PC 3.x

Fault Status PC 2.x,


40414 2 2816 Genset PT Ratio Too Small Shutdown
Bitmap 15 PC 3.x

Fault Status PC 2.x,


40414 3 2817 Genset PT Ratio Too Large Warning
Bitmap 15 PC 3.x
Fault Status
40414 4 2818 Genset Bus PT Ratio Too Small Shutdown PC 3.x
Bitmap 15
Fault Status
40414 5 2819 Genset Bus PT Ratio Too Large Warning PC 3.x
Bitmap 15
Fault Status
40414 6 2821 Utility PT Ratio Too Small Shutdown PC 3.x
Bitmap 15
Fault Status
40414 7 2822 Utility PT Ratio Too Large Warning PC 3.x
Bitmap 15

Copyright © 2017 Cummins Inc. 430 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code

Fault Status PC 2.x,


40414 8 2619 Aux101 0 Input 1 Fault Warning
Bitmap 15 PC 3.x

Fault Status PC 2.x,


40414 9 2621 Aux101 0 Input 2 Fault Warning
Bitmap 15 PC 3.x

Fault Status PC 2.x,


40414 10 2622 Aux101 0 Input 3 Fault Warning
Bitmap 15 PC 3.x

Fault Status PC 2.x,


40414 11 2623 Aux101 0 Input 4 Fault Warning
Bitmap 15 PC 3.x

Fault Status PC 2.x,


40414 12 2624 Aux101 0 Input 5 Fault Warning
Bitmap 15 PC 3.x

Fault Status PC 2.x,


40414 13 2625 Aux101 0 Input 6 Fault Warning
Bitmap 15 PC 3.x

Fault Status PC 2.x,


40414 14 2626 Aux101 0 Input 7 Fault Warning
Bitmap 15 PC 3.x

Fault Status PC 2.x,


40414 15 2627 Aux101 0 Input 8 Fault Warning
Bitmap 15 PC 3.x

Fault Status PC 2.x,


40415 0 2882 Aux101 1 Input 1 Fault Warning
Bitmap 16 PC 3.x

Fault Status PC 2.x,


40415 1 2883 Aux101 1 Input 2 Fault Warning
Bitmap 16 PC 3.x

Fault Status PC 2.x,


40415 2 2884 Aux101 1 Input 3 Fault Warning
Bitmap 16 PC 3.x

Fault
Addr. Bit# Name Event Name Response Control
Code
PCC3300,
Fault Status Engine Friction Below Baseline -
41419 9 7548 None PCC3300V
Bitmap 38 Least Severe
2
PC3300,
Fault Status Engine Friction Below Baseline -
41419 10 7549 Warning PCC3300V
Bitmap 38 Moderately Severe
2
PCC3300,
Fault Status Engine Friction Above Baseline -
41419 11 7551 None PCC3300V
Bitmap 38 Least Severe
2
PCC3300,
Fault Status Engine Friction Above Baseline -
41419 12 7552 Warning PCC3300V
Bitmap 38 Moderately Severe
2
PCC3300,
Fault Status Engine Friction Devn Above -
41419 13 7553 Warning PCC3300V
Bitmap 38 Baseline - Mod Severity
2

A029X159 (Issue 19) 431 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code
PCC3300,
Fault Status Engine Friction Devn Above Baseline
41419 14 7554 Shutdown PCC3300V
Bitmap 38 - Most Severe
2
PCC3300,
Fault Status
41419 15 7555 Alternator Feedback Power Shutdown PCC3300V
Bitmap 38
2

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas Shutdown
40440 7 1588 Heavy_Knock_Error_17_(A9) PC 3.x
Bitmap 10 w/Cooldown
Fault Status Gas Continuous_Light_Knock_Error_18_( Shutdown
40440 8 1593 PC 3.x
Bitmap 10 B9) w/Cooldown
Fault Status Gas Exhaust Gas Temp, Cyl 1 (A1)
40440 9 1618 Warning PC 3.x
Bitmap 10 OORH
Fault Status Gas Exhaust Gas Temp, Cyl 4 (B2)
40440 10 1619 Warning PC 3.x
Bitmap 10 OORH
Fault Status Gas
40440 11 1636 Intake Manif Press 2 OORH Warning PC 3.x
Bitmap 10
Fault Status Gas
40440 12 1637 Intake Manif Press 2 OORL Warning PC 3.x
Bitmap 10
Fault Status Gas Shutdown
40440 13 1737 CAN_Throttle_Internal_Failure_Error PC 3.x
Bitmap 10 w/Cooldown
Fault Status Gas
40440 14 1738 CAN_Throttle_Internal_Fault_Error Warning PC 3.x
Bitmap 10
Fault Status Gas Engine Throttle Control Condition
40440 15 1739 Warning PC 3.x
Bitmap 10 Exists
Fault Status Gas CAN_Throttle_High_Temp_Warning_
40441 0 1741 Warning PC 3.x
Bitmap 11 Error
Fault Status Gas
40441 1 1742 CAN_Throttle_Temp_Limiting_Error Warning PC 3.x
Bitmap 11
Fault Status Gas Shutdown
40441 2 1743 Throttle Ctrl 2 OOR High PC 3.x
Bitmap 11 w/Cooldown
Fault Status Gas Shutdown
40441 3 1744 Throttle Ctrl 2 OOR Low PC 3.x
Bitmap 11 w/Cooldown
Fault Status Gas Shutdown
40441 4 1745 Throttle Ctrl 2 Incorrect PC 3.x
Bitmap 11 w/Cooldown
Fault Status Gas Shutdown
40441 5 1746 Throttle Ctrl 2 Out of Adjustment PC 3.x
Bitmap 11 w/Cooldown
Fault Status Gas Shutdown
40441 6 1747 Throttle Ctrl 2 Bad Device PC 3.x
Bitmap 11 w/Cooldown

Copyright © 2017 Cummins Inc. 432 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas
40441 7 1748 Throttle Ctrl 2 Root Unknown Warning PC 3.x
Bitmap 11
Fault Status Gas
40441 8 1749 Throttle Ctrl 2 Condition Exists Warning PC 3.x
Bitmap 11
Fault Status Gas
40441 9 1751 Throttle Ctrl 2 Warning High Warning PC 3.x
Bitmap 11
Fault Status Gas
40441 10 1752 Throttle Ctrl 2 Moderate High Warning PC 3.x
Bitmap 11
Fault Status Gas
40441 11 1753 Fuel Shutoff 2 OOR High Warning PC 3.x
Bitmap 11
Fault Status Gas
40441 12 1754 Fuel Tmp 2 OOR High Warning PC 3.x
Bitmap 11
Fault Status Gas
40441 13 1755 Fuel Tmp 2 OOR Low Warning PC 3.x
Bitmap 11
Fault Status Gas
40441 14 1756 Gas Flow 2 OOR High Warning PC 3.x
Bitmap 11
Fault Status Gas
40441 15 1757 Gas Flow 2 OOR Low Warning PC 3.x
Bitmap 11
Fault Status Gas
40442 0 1758 Gas Flow 2 Incorrect Data Warning PC 3.x
Bitmap 12
Fault Status Gas Shutdown
40442 1 1759 FCV 2 Pos Feedback Incorrect PC 3.x
Bitmap 12 w/Cooldown
Fault Status Gas Shutdown
40442 2 1761 FCV_Actuator_Error_1761 PC 3.x
Bitmap 12 w/Cooldown
Fault Status Gas
40442 3 1984 Int Man 2 Tmp Moderate High Warning PC 3.x
Bitmap 12
Fault Status Gas
40442 4 1765 FCV 2 In Pr OOR High Warning PC 3.x
Bitmap 12
Fault Status Gas
40442 5 1766 FCV 2 In Pr OOR Low Warning PC 3.x
Bitmap 12
Fault Status Gas
40442 6 1767 FCV 2 Out Pr OOR High Warning PC 3.x
Bitmap 12
Fault Status Gas
40442 7 1768 FCV 2 Out Pr OOR Low Warning PC 3.x
Bitmap 12
Fault Status Gas
40442 8 1769 E_Shutd Indication OORH Warning PC 3.x
Bitmap 12
Fault Status Gas
40442 9 1771 E_Shutd Indication OORL Warning PC 3.x
Bitmap 12
Fault Status Gas
40442 10 1772 Eng Derate Request OORH Warning PC 3.x
Bitmap 12

A029X159 (Issue 19) 433 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas
40442 11 1773 Eng Derate Request OORL Warning PC 3.x
Bitmap 12
Fault Status Gas
40442 12 1774 Oil Priming Pump OORH Warning PC 3.x
Bitmap 12
Fault Status Gas
40442 13 1775 Oil Priming Pump OORL Warning PC 3.x
Bitmap 12
Fault Status Gas
40442 14 3362 Power Conservation Control OORH Warning PC 3.x
Bitmap 12
Fault Status Gas
40442 15 3363 Power Conservation Control OORL Warning PC 3.x
Bitmap 12
Fault Status Gas Engine_Heater_Control_Driver_High
40443 0 1778 Warning PC 3.x
Bitmap 13 _Error
Fault Status Gas Engine_Heater_Control_Driver_Low_
40443 1 1779 Warning PC 3.x
Bitmap 13 Error
Fault Status Gas
40443 2 1781 Shutd Request OOR High Warning PC 3.x
Bitmap 13
Fault Status Gas
40443 3 1782 Shutd Request OOR Low Warning PC 3.x
Bitmap 13
Fault Status Gas Coolant_Pump_Control_Driver_High_
40443 4 1783 Warning PC 3.x
Bitmap 13 Error
Fault Status Gas Coolant_Pump_Control_Driver_Low_
40443 5 1784 Warning PC 3.x
Bitmap 13 Error
Fault Status Gas Oil_Priming_Pump_Manual_Override
40443 6 1785 Warning PC 3.x
Bitmap 13 _Input_On
Fault Status Gas
40443 7 1786 Oil_Priming_Pump_Stuck_On_Error Warning PC 3.x
Bitmap 13
Fault Status Gas
40443 8 1787 Post_Lube_Oil_Priming_Error Warning PC 3.x
Bitmap 13
Fault Status Gas Maintenance_Lube_Oil_Priming_Erro
40443 9 1788 Warning PC 3.x
Bitmap 13 r
Fault Status Gas Shutdown
40443 10 1789 Pre_Start_Lube_Oil_Priming_Error PC 3.x
Bitmap 13 w/Cooldown
Fault Status Gas Shutdown
40443 11 1791 Failure_To_Meet_Load_Speed_Error PC 3.x
Bitmap 13 w/Cooldown
Fault Status Gas
40443 12 1792 Idle when CB Closed Warning PC 3.x
Bitmap 13
Fault Status Gas
40443 13 1793 Speed/Posit sensor out of Adj Warning PC 3.x
Bitmap 13
Fault Status Gas Shutdown
40443 14 1794 Fire Detected PC 3.x
Bitmap 13 w/Cooldown

Copyright © 2017 Cummins Inc. 434 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas Compressor_Bypass_Position_High_
40443 15 1795 Warning PC 3.x
Bitmap 13 Error
Fault Status Gas Compressor_Bypass_Position_Low_
40444 0 1796 Warning PC 3.x
Bitmap 14 Error
Fault Status Gas
40444 1 1797 Compressor Bypass ctrl OORH Warning PC 3.x
Bitmap 14
Fault Status Gas
40444 2 1798 Compressor Bypass ctrl OORL Warning PC 3.x
Bitmap 14
Fault Status Gas
40444 3 1799 CB_Position_Err_Status Warning PC 3.x
Bitmap 14
Fault Status Gas HIGH_SIDE_DRV2_High_Control_Er
40444 4 1811 Warning PC 3.x
Bitmap 14 ror (VPS)
Fault Status Gas HIGH_SIDE_DRV2_Low_Control_Err
40444 5 1812 Warning PC 3.x
Bitmap 14 or (VPS)
Fault Status Gas Valve_Proving_System_Test_Failed_
40444 6 1813 Warning PC 3.x
Bitmap 14 Warning_Error
Fault Status Gas Valve_Proving_System_Test_Failed_ Shutdown
40444 7 1814 PC 3.x
Bitmap 14 Shutdown_Error w/Cooldown
Fault Status Gas
40444 8 1815 RLY14_High_Control_Error Warning PC 3.x
Bitmap 14
Fault Status Gas
40444 9 1816 Oil Pre-Heater Ctrl OOR Low Warning PC 3.x
Bitmap 14
Fault Status Gas
40444 10 1817 Oil_Pre-Heater_Tripped_Error Warning PC 3.x
Bitmap 14
Fault Status Gas
40444 11 1818 Oil_Pre-Heater_Not_Warming_Error Warning PC 3.x
Bitmap 14
Fault Status Gas
40444 12 1819 Common AC Aux CB tripped Warning PC 3.x
Bitmap 14
Fault Status Gas Shutdown
40444 13 1821 Min_FSO_Speed_Error PC 3.x
Bitmap 14 w/Cooldown
Fault Status Gas LT Coolant Level Low Shutdown Shutdown
40444 14 1822 PC 3.x
Bitmap 14 Error w/Cooldown
Fault Status Gas
40444 15 1823 LT Coolant Level Low Warning Error Warning PC 3.x
Bitmap 14
Fault Status Gas Idle_Rated_Trans_Oil_Temp_Low_Er
40445 0 1824 Warning PC 3.x
Bitmap 15 ror
Fault Status Gas
40445 1 1825 Dirty_Oil_Level_Error Warning PC 3.x
Bitmap 15
Fault Status Gas Shutdown
40445 2 1826 ECM Software incompatible PC 3.x
Bitmap 15 w/Cooldown

A029X159 (Issue 19) 435 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas
40445 3 1827 Fuel_Inlet_Pressure_High_Error Warning PC 3.x
Bitmap 15
Fault Status Gas
40445 4 1828 Fuel_Inlet_Pressure_Low_Error Warning PC 3.x
Bitmap 15
Fault Status Gas Shutdown
40445 5 1829 Vent_Gas_Valve_Error PC 3.x
Bitmap 15 w/Cooldown
Fault Status Gas Shutdown
40445 6 1831 Upstream_FSO_Valve_Error PC 3.x
Bitmap 15 w/Cooldown
Fault Status Gas Shutdown
40445 7 1832 Downstream_FSO_Valve_Error PC 3.x
Bitmap 15 w/Cooldown
Fault Status Gas
40445 8 1833 Engine_Heater_Trip_Error Warning PC 3.x
Bitmap 15
Fault Status Gas
40445 9 1834 Coolant_Pump_Trip_Error Warning PC 3.x
Bitmap 15
Fault Status Gas
40445 10 1835 Oil_Priming_Pump_Tripped_Error Warning PC 3.x
Bitmap 15
Fault Status Gas Shutdown
40445 11 1836 LCP_(LT)_Low_Serious_Error PC 3.x
Bitmap 15 w/Cooldown
Fault Status Gas Permanent_FS_Cam_Sync_Lost_Err Shutdown
40445 12 1837 PC 3.x
Bitmap 15 or w/Cooldown
Fault Status Gas Partial_Engine_Overload_Shutdown_ Shutdown
40445 13 1838 PC 3.x
Bitmap 15 Error w/Cooldown
Fault Status Gas
40445 14 1839 Fuel_Supply_Pressure_High_Error Warning PC 3.x
Bitmap 15
Fault Status Gas
40445 15 1841 Fuel_Supply_Pressure_Low_Error Warning PC 3.x
Bitmap 15
Fault Status Gas
40446 0 1842 Radiator_Fan_Trip_Error Warning PC 3.x
Bitmap 16
Fault Status Gas
40446 1 1858 Exhaust Aft Inlet O2 OOR High Warning PC 3.x
Bitmap 16
Fault Status Gas
40446 2 1859 Exhaust Aft Inlet O2 OOR Low Warning PC 3.x
Bitmap 16
Fault Status Gas
40446 3 1861 Exhaust Aft Inlet O2 Incorrect Warning PC 3.x
Bitmap 16
Fault Status Gas
40446 4 1862 Exhaust Aft Out O2 OOR High Warning PC 3.x
Bitmap 16
Fault Status Gas
40446 5 1863 Exhaust Aft Outlet O2 OOR Low Warning PC 3.x
Bitmap 16
Fault Status Gas
40446 6 1864 Exhaust Aft Outlet O2 Incorrect Warning PC 3.x
Bitmap 16

Copyright © 2017 Cummins Inc. 436 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas
40446 7 1985 Int Man 3 Tmp Moderate High Warning PC 3.x
Bitmap 16
Fault Status Gas
40446 8 1986 Int Man 4 Tmp Moderate High Warning PC 3.x
Bitmap 16
Fault Status Gas Coolant_Inlet_Temperature_(LT)_Hig
40446 9 2111 Warning PC 3.x
Bitmap 16 h_Error
Fault Status Gas Coolant_Inlet_Temperature_(LT)_Lo
40446 10 2112 Warning PC 3.x
Bitmap 16 w_Error
Fault Status Gas
40446 11 2113 CIT_(LT)_High_Warning_Error Warning PC 3.x
Bitmap 16
Fault Status Gas Shutdown
40446 12 2114 CIT_(LT)_High_Serious_Error PC 3.x
Bitmap 16 w/Cooldown
Fault Status Gas
40446 13 2115 LT_Coolant_Pressure_High_Error Warning PC 3.x
Bitmap 16
Fault Status Gas
40446 14 2116 LT_Coolant_Pressure_Low_Error Warning PC 3.x
Bitmap 16
Fault Status Gas
40446 15 2117 LCP_(LT)_Low_Warning_Error Warning PC 3.x
Bitmap 16
Fault Status Gas Exhaust_Temp_1_(A1)_High_Warnin
40447 0 2121 Warning PC 3.x
Bitmap 17 g_Error
Fault Status Gas Exhaust_Temp_3_(A2)_High_Warnin
40447 1 2122 Warning PC 3.x
Bitmap 17 g_Error
Fault Status Gas Exhaust_Temp_5_(A3)_High_Warnin
40447 2 2123 Warning PC 3.x
Bitmap 17 g_Error
Fault Status Gas Exhaust_Temp_7_(A4)_High_Warnin
40447 3 2124 Warning PC 3.x
Bitmap 17 g_Error
Fault Status Gas Exhaust_Temp_9_(A5)_High_Warnin
40447 4 2125 Warning PC 3.x
Bitmap 17 g_Error
Fault Status Gas Exhaust_Temp_11_(A6)_High_Warni
40447 5 2126 Warning PC 3.x
Bitmap 17 ng_Error
Fault Status Gas Exhaust_Temp_13_(A7)_High_Warni
40447 6 2127 Warning PC 3.x
Bitmap 17 ng_Error
Fault Status Gas Exhaust_Temp_15_(A8)_High_Warni
40447 7 2128 Warning PC 3.x
Bitmap 17 ng_Error
Fault Status Gas Exhaust_Temp_17_(A9)_High_Warni
40447 8 2129 Warning PC 3.x
Bitmap 17 ng_Error
Fault Status Gas Exhaust_Temp_2_(B1)_High_Warnin
40447 9 2131 Warning PC 3.x
Bitmap 17 g_Error
Fault Status Gas Exhaust_Temp_4_(B2)_High_Warnin
40447 10 2132 Warning PC 3.x
Bitmap 17 g_Error

A029X159 (Issue 19) 437 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas Exhaust_Temp_6_(B3)_High_Warnin
40447 11 2133 Warning PC 3.x
Bitmap 17 g_Error
Fault Status Gas Exhaust_Temp_8_(B4)_High_Warnin
40447 12 2134 Warning PC 3.x
Bitmap 17 g_Error
Fault Status Gas Exhaust_Temp_10_(B5)_High_Warni
40447 13 2135 Warning PC 3.x
Bitmap 17 ng_Error
Fault Status Gas Exhaust_Temp_12_(B6)_High_Warni
40447 14 2136 Warning PC 3.x
Bitmap 17 ng_Error
Fault Status Gas Exhaust_Temp_14_(B7)_High_Warni
40447 15 2137 Warning PC 3.x
Bitmap 17 ng_Error
Fault Status Gas Exhaust_Temp_16_(B8)_High_Warni
40448 0 2138 Warning PC 3.x
Bitmap 18 ng_Error
Fault Status Gas Exhaust_Temp_18_(B9)_High_Warni
40448 1 2139 Warning PC 3.x
Bitmap 18 ng_Error
Fault Status Gas
40448 2 2141 Start_Air_Pressure_High_Error Warning PC 3.x
Bitmap 18
Fault Status Gas
40448 3 2142 Start_Air_Pressure_Low_Error Warning PC 3.x
Bitmap 18
Fault Status Gas
40448 4 2143 SAP_Overpressure_Error Warning PC 3.x
Bitmap 18
Fault Status Gas Exhaust Temp 16 (B8) High Serious Shutdown
40448 5 2144 PC 3.x
Bitmap 18 Error w/Cooldown
Fault Status Gas Exhaust Temp 18 (B9) High Serious Shutdown
40448 6 2145 PC 3.x
Bitmap 18 Error w/Cooldown
Fault Status Gas
40448 7 2146 EGT 17 (A9) OOR Low Warning PC 3.x
Bitmap 18
Fault Status Gas
40448 8 2147 EGT 18 (B9) OOR Low Warning PC 3.x
Bitmap 18
Fault Status Gas Oil_Filter_Outlet_Pressure_High_Err
40448 9 2154 Warning PC 3.x
Bitmap 18 or
Fault Status Gas Oil_Filter_Outlet_Pressure_Low_Erro
40448 10 2155 Warning PC 3.x
Bitmap 18 r
Fault Status Gas Shutdown
40448 11 2157 Int Man 2 Tmp Abnormal Rate PC 3.x
Bitmap 18 w/Cooldown
Fault Status Gas Shutdown
40448 12 2158 Int Man 3 Tmp Abnormal Rate PC 3.x
Bitmap 18 w/Cooldown
Fault Status Gas Shutdown
40448 13 2159 Int Man 4 Tmp Abnormal Rate PC 3.x
Bitmap 18 w/Cooldown
Fault Status Gas
40448 14 2188 Exhaust O2 OOR High Warning PC 3.x
Bitmap 18

Copyright © 2017 Cummins Inc. 438 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas
40448 15 2191 ST_Throttle_Press_Err_Status Warning PC 3.x
Bitmap 18
Fault Status Gas
40449 0 2192 Exhaust O2 OOR Low Warning PC 3.x
Bitmap 19
Fault Status Gas
40449 1 2217 RAM_Image_Word_Error Warning PC 3.x
Bitmap 19
Fault Status Gas
40449 2 2219 Exhaust O2 Moderate High Warning PC 3.x
Bitmap 19
Fault Status Gas
40449 3 2221 Exhaust O2 Moderate Low Warning PC 3.x
Bitmap 19
Fault Status Gas Shutdown
40449 4 2281 Knock 11 (A6) Moderate High PC 3.x
Bitmap 19 w/Cooldown
Fault Status Gas Shutdown
40449 5 2282 Knock 11 (A6) Critical High PC 3.x
Bitmap 19 w/Cooldown
Fault Status Gas
40449 6 2298 Fuel Shutoff 2 OOR Low Warning PC 3.x
Bitmap 19
Fault Status Gas
40449 7 2315 Red Lamp OOR High Warning PC 3.x
Bitmap 19
Fault Status Gas
40449 8 2316 Amber Lamp OOR High Warning PC 3.x
Bitmap 19
Fault Status Gas
40449 9 2317 Amber Lamp OOR Low Warning PC 3.x
Bitmap 19
Fault Status Gas
40449 10 2427 Fuel_Outlet_Pressure_High_Error Warning PC 3.x
Bitmap 19
Fault Status Gas
40449 11 2428 Fuel_Outlet_Pressure_Low_Error Warning PC 3.x
Bitmap 19
Fault Status Gas
40449 12 2453 Total Real Power Circuit OORH Warning PC 3.x
Bitmap 19
Fault Status Gas
40449 13 2454 Total Real Power Circuit OORL Warning PC 3.x
Bitmap 19
Fault Status Gas
40449 14 2455 Speed_Bias_Low_Error Warning PC 3.x
Bitmap 19
Fault Status Gas
40449 15 2456 Speed_Bias_High_Error Warning PC 3.x
Bitmap 19
Fault Status Gas Shutdown
40450 0 2457 Max_Total_Misfire_Error PC 3.x
Bitmap 20 w/Cooldown
Fault Status Gas
40450 1 2458 Cylinder_2_(B1)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
Fault Status Gas
40450 2 2459 Cylinder_4_(B2)_Total_Misfire_Error Warning PC 3.x
Bitmap 20

A029X159 (Issue 19) 439 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas
40450 3 2461 Cylinder_6_(B3)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
Fault Status Gas
40450 4 2462 Cylinder_8_(B4)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
Fault Status Gas Cylinder_10_(B5)_Total_Misfire_Erro
40450 5 2463 Warning PC 3.x
Bitmap 20 r
Fault Status Gas Cylinder_12_(B6)_Total_Misfire_Erro
40450 6 2464 Warning PC 3.x
Bitmap 20 r
Fault Status Gas Cylinder_14_(B7)_Total_Misfire_Erro
40450 7 2465 Warning PC 3.x
Bitmap 20 r
Fault Status Gas Cylinder_16_(B8)_Total_Misfire_Erro
40450 8 2466 Warning PC 3.x
Bitmap 20 r
Fault Status Gas Cylinder_18_(B9)_Total_Misfire_Erro
40450 9 2467 Warning PC 3.x
Bitmap 20 r
Fault Status Gas
40450 10 2469 Cylinder_1_(A1)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
Fault Status Gas
40450 11 2471 Cylinder_3_(A2)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
Fault Status Gas
40450 12 2472 Cylinder_5_(A3)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
Fault Status Gas
40450 13 2473 Cylinder_7_(A4)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
Fault Status Gas
40450 14 2475 Cylinder_9_(A5)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
Fault Status Gas Cylinder_11_(A6)_Total_Misfire_Erro
40450 15 2476 Warning PC 3.x
Bitmap 20 r
Fault Status Gas Cylinder_13_(A7)_Total_Misfire_Erro
40451 0 2477 Warning PC 3.x
Bitmap 21 r
Fault Status Gas Cylinder_15_(A8)_Total_Misfire_Erro
40451 1 2478 Warning PC 3.x
Bitmap 21 r
Fault Status Gas Cylinder_17_(A9)_Total_Misfire_Erro
40451 2 2479 Warning PC 3.x
Bitmap 21 r
Fault Status Gas Shutdown
40451 3 2482 Start_Before_Ready_Error PC 3.x
Bitmap 21 w/Cooldown
Fault Status Gas Shutdown
40451 4 2483 Continuous_Starter_Failure_Error PC 3.x
Bitmap 21 w/Cooldown
Fault Status Gas Exhaust Temperature 1 (A1) Shutdown
40451 5 2484 PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 3 (A2) Shutdown
40451 6 2485 PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown

Copyright © 2017 Cummins Inc. 440 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas Exhaust Temperature 5 (A3) Shutdown
40451 7 2486 PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 7 (A4) Shutdown
40451 8 2487 PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 9 (A5) Shutdown
40451 9 2488 PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 11 (A6) Shutdown
40451 10 2489 PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 13 (A7) Shutdown
40451 11 2491 PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 15 (A8) Shutdown
40451 12 2492 PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 17 (A9) Shutdown
40451 13 2493 PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 2 (B1) Shutdown
40451 14 2494 PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 4 (B2) Shutdown
40451 15 2495 PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 6 (B3) Shutdown
40452 0 2496 PC 3.x
Bitmap 22 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 8 (B4) Shutdown
40452 1 2497 PC 3.x
Bitmap 22 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 10 (B5) Shutdown
40452 2 2498 PC 3.x
Bitmap 22 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 12 (B6) Shutdown
40452 3 2499 PC 3.x
Bitmap 22 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 14 (B7) Shutdown
40452 4 2511 PC 3.x
Bitmap 22 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 16 (B8) Shutdown
40452 5 2512 PC 3.x
Bitmap 22 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 18 (B9) Shutdown
40452 6 2513 PC 3.x
Bitmap 22 Abnormal Rate w/Cooldown
Fault Status Gas Compressor_Outlet_Pressure_High_
40452 7 2517 Warning PC 3.x
Bitmap 22 Error
Fault Status Gas Compressor_Outlet_Pressure_Low_
40452 8 2518 Warning PC 3.x
Bitmap 22 Error
Fault Status Gas Shutdown
40452 9 2521 Bank_Id_Error PC 3.x
Bitmap 22 w/Cooldown
Fault Status Gas Continuous_Light_Knock_Error_1_(A Shutdown
40452 10 2522 PC 3.x
Bitmap 22 1) w/Cooldown

A029X159 (Issue 19) 441 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas Continuous_Light_Knock_Error_2_(B Shutdown
40452 11 2523 PC 3.x
Bitmap 22 1) w/Cooldown
Fault Status Gas Continuous_Light_Knock_Error_3_(A Shutdown
40452 12 2524 PC 3.x
Bitmap 22 2) w/Cooldown
Fault Status Gas Continuous_Light_Knock_Error_4_(B Shutdown
40452 13 2525 PC 3.x
Bitmap 22 2) w/Cooldown
Fault Status Gas Continuous_Light_Knock_Error_5_(A Shutdown
40452 14 2526 PC 3.x
Bitmap 22 3) w/Cooldown
Fault Status Gas Continuous_Light_Knock_Error_6_(B Shutdown
40452 15 2527 PC 3.x
Bitmap 22 3) w/Cooldown
Fault Status Gas Continuous_Light_Knock_Error_7_(A Shutdown
40453 0 2528 PC 3.x
Bitmap 23 4) w/Cooldown
Fault Status Gas Continuous_Light_Knock_Error_8_(B Shutdown
40453 1 2529 PC 3.x
Bitmap 23 4) w/Cooldown
Fault Status Gas Continuous_Light_Knock_Error_9_(A Shutdown
40453 2 2531 PC 3.x
Bitmap 23 5) w/Cooldown
Fault Status Gas Continuous_Light_Knock_Error_10_( Shutdown
40453 3 2532 PC 3.x
Bitmap 23 B5) w/Cooldown
Fault Status Gas Shutdown
40453 4 2544 ECM_Overtemp_Error PC 3.x
Bitmap 23 w/Cooldown
Fault Status Gas
40453 5 2567 DG_Air_Compressor_Trip_Error Warning PC 3.x
Bitmap 23
Fault Status Gas
40453 6 2643 Throttle Pos 2 Feedback OOR High Warning PC 3.x
Bitmap 23
Fault Status Gas
40453 7 2644 Throttle Pos 2 Feedback OOR Low Warning PC 3.x
Bitmap 23
Fault Status Gas
40453 9 2724 Gas Supply Pr Moderate High Warning PC 3.x
Bitmap 23
Fault Status Gas
40453 10 2725 Gas Supply Pr Moderate Low Warning PC 3.x
Bitmap 23
Fault Status Gas Shutdown
40453 11 2737 Exh Gas Tmp Critical High PC 3.x
Bitmap 23 w/Cooldown
Fault Status Gas Shutdown
40453 12 2766 Bank_A_CCD_Failed_Error PC 3.x
Bitmap 23 w/Cooldown
Fault Status Gas Shutdown
40453 13 2767 Bank_B_CCD_Failed_Error PC 3.x
Bitmap 23 w/Cooldown
Fault Status Gas Shutdown
40453 14 2768 CAN Parent Communication Incorrect PC 3.x
Bitmap 23 w/Cooldown
Fault Status Gas Shutdown
40453 15 2769 CAN Child Com Incorrect PC 3.x
Bitmap 23 w/Cooldown

Copyright © 2017 Cummins Inc. 442 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas
40454 0 2789 COT_Low_Error Warning PC 3.x
Bitmap 24
Fault Status Gas Shutdown
40454 1 2793 COT_Low_Serious_Error PC 3.x
Bitmap 24 w/Cooldown
Fault Status Gas
40454 2 2794 Ign Shutd Relay OOR High Warning PC 3.x
Bitmap 24
Fault Status Gas
40454 3 2795 Ign Shutd Relay OOR Low Warning PC 3.x
Bitmap 24
Fault Status Gas Partial_Engine_Overload_Warning_E
40454 4 2796 Warning PC 3.x
Bitmap 24 rror
Fault Status Gas
40454 5 2797 Inlet Gas Diff Pressure OOR High Warning PC 3.x
Bitmap 24
Fault Status Gas
40454 6 2798 Inlet Gas Diff Pressure OOR Low Warning PC 3.x
Bitmap 24
Fault Status Gas IMOP_Compressor_Outlet_Presure_ Shutdown
40454 7 2799 PC 3.x
Bitmap 24 Delta_Error w/Cooldown
Fault Status Gas IMOP_Compressor_Outlet_Pressure Shutdown
40454 8 2811 PC 3.x
Bitmap 24 _Maximum_Error w/Cooldown
Fault Status Gas Exhaust_Temp_1_(A1)_Deviation_Er
40454 9 2837 Warning PC 3.x
Bitmap 24 ror
Fault Status Gas Exhaust_Temp_3_(A2)_Deviation_Er
40454 10 2838 Warning PC 3.x
Bitmap 24 ror
Fault Status Gas Exhaust_Temp_5_(A3)_Deviation_Er
40454 11 2839 Warning PC 3.x
Bitmap 24 ror
Fault Status Gas Exhaust_Temp_7_(A4)_Deviation_Er
40454 12 2841 Warning PC 3.x
Bitmap 24 ror
Fault Status Gas Exhaust_Temp_9_(A5)_Deviation_Er
40454 13 2842 Warning PC 3.x
Bitmap 24 ror
Fault Status Gas Exhaust_Temp_11_(A6)_Deviation_E
40454 14 2843 Warning PC 3.x
Bitmap 24 rror
Fault Status Gas Exhaust_Temp_13_(A7)_Deviation_E
40454 15 2844 Warning PC 3.x
Bitmap 24 rror
Fault Status Gas Exhaust_Temp_15_(A8)_Deviation_E
40455 0 2845 Warning PC 3.x
Bitmap 25 rror
Fault Status Gas Exhaust_Temp_17_(A9)_Deviation_E
40455 1 2846 Warning PC 3.x
Bitmap 25 rror
Fault Status Gas Exhaust_Temp_2_(B1)_Deviation_Er
40455 2 2847 Warning PC 3.x
Bitmap 25 ror
Fault Status Gas Exhaust_Temp_4_(B2)_Deviation_Er
40455 3 2848 Warning PC 3.x
Bitmap 25 ror

A029X159 (Issue 19) 443 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas Exhaust_Temp_6_(B3)_Deviation_Er
40455 4 2849 Warning PC 3.x
Bitmap 25 ror
Fault Status Gas Exhaust_Temp_8_(B4)_Deviation_Er
40455 5 2851 Warning PC 3.x
Bitmap 25 ror
Fault Status Gas Exhaust_Temp_10_(B5)_Deviation_E
40455 6 2852 Warning PC 3.x
Bitmap 25 rror
Fault Status Gas Exhaust_Temp_12_(B6)_Deviation_E
40455 7 2853 Warning PC 3.x
Bitmap 25 rror

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas Exhaust_Temp_14_(B7)_Deviation_E
40455 8 2854 Warning PC 3.x
Bitmap 25 rror
Fault Status Gas Exhaust_Temp_16_(B8)_Deviation_E
40455 9 2855 Warning PC 3.x
Bitmap 25 rror
Fault Status Gas Exhaust_Temp_18_(B9)_Deviation_E
40455 10 2856 Warning PC 3.x
Bitmap 25 rror
Fault Status Gas Shutdown
40455 11 2857 Turbo_1_Overspeed_Critical_Error PC 3.x
Bitmap 25 w/Cooldown
Fault Status Gas Shutdown
40455 12 2858 Turbo_2_Overspeed_Critical_Error PC 3.x
Bitmap 25 w/Cooldown
Fault Status Gas
40455 13 2859 Alt Heater Ctrl OOR High Warning PC 3.x
Bitmap 25
Fault Status Gas
40455 14 2861 Alt Heater Ctrl OOR Low Warning PC 3.x
Bitmap 25
Fault Status Gas
40455 15 2862 Gen Alternator 1st Start Cond Exists Warning PC 3.x
Bitmap 25
Fault Status Gas Shutdown
40456 0 2863 Genset to Engine Com Incorrect PC 3.x
Bitmap 26 w/Cooldown
Fault Status Gas Shutdown
40456 1 2864 FSO_NON_High_Control_Error PC 3.x
Bitmap 26 w/Cooldown
Fault Status Gas Power Conservation Control Cond
40456 2 3364 Warning PC 3.x
Bitmap 26 Exists
Fault Status Gas
40456 3 2866 FCV_Position_High_Error Warning PC 3.x
Bitmap 26
Fault Status Gas
40456 4 2867 FCV_Position_Low_Error Warning PC 3.x
Bitmap 26
Fault Status Gas Engine_Heater_Over-
40456 5 2868 Warning PC 3.x
Bitmap 26 Temperature_Alarm_Error
Fault Status Gas
40456 6 2869 HT Cool Temp Driver OOR High Warning PC 3.x
Bitmap 26

Copyright © 2017 Cummins Inc. 444 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas
40456 7 2871 HT Cool Temp Driver OOR Low Warning PC 3.x
Bitmap 26
Fault Status Gas
40456 8 2872 HT Cool Temp Driver Cond Exists Warning PC 3.x
Bitmap 26
Fault Status Gas
40456 9 2873 LT Cool Temp Driver OOR High Warning PC 3.x
Bitmap 26
Fault Status Gas
40456 10 2874 LT Cool Temp Driver OOR Low Warning PC 3.x
Bitmap 26
Fault Status Gas
40456 11 2875 LT Cool Temp Driver Cond Exists Warning PC 3.x
Bitmap 26
Fault Status Gas Shutdown
40456 12 2876 Comp_Surge_Shutdown_Error PC 3.x
Bitmap 26 w/Cooldown
Fault Status Gas
40456 13 2877 Comp_Surge_Derate_Error Warning PC 3.x
Bitmap 26
Fault Status Gas
40456 14 2994 MC68302_Error Warning PC 3.x
Bitmap 26
Fault Status Gas Shutdown
40456 15 2995 Int Man Pressure 1 Critical High PC 3.x
Bitmap 26 w/Cooldown
Fault Status Gas
40457 0 2996 Int Man Pressure 1 Moderate High Warning PC 3.x
Bitmap 27
Fault Status Gas Shutdown
40457 1 2997 Exhaust O2 Critical Low PC 3.x
Bitmap 27 w/Cooldown
Fault Status Gas Shutdown
40457 2 3111 Excessive_Mech_Vibration_1_(A1) PC 3.x
Bitmap 27 w/Cooldown
Fault Status Gas Shutdown
40457 3 3112 Excessive_Mech_Vibration_2_(B1) PC 3.x
Bitmap 27 w/Cooldown
Fault Status Gas Shutdown
40457 4 3113 Excessive_Mech_Vibration_3_(A2) PC 3.x
Bitmap 27 w/Cooldown
Fault Status Gas Shutdown
40457 5 3114 Excessive_Mech_Vibration_4_(B2) PC 3.x
Bitmap 27 w/Cooldown
Fault Status Gas Shutdown
40457 6 3115 Excessive_Mech_Vibration_5_(A3) PC 3.x
Bitmap 27 w/Cooldown
Fault Status Gas Shutdown
40457 7 3116 Excessive_Mech_Vibration_6_(B3) PC 3.x
Bitmap 27 w/Cooldown
Fault Status Gas Shutdown
40457 8 3117 Excessive_Mech_Vibration_7_(A4) PC 3.x
Bitmap 27 w/Cooldown
Fault Status Gas Shutdown
40457 9 3118 Excessive_Mech_Vibration_8_(B4) PC 3.x
Bitmap 27 w/Cooldown
Fault Status Gas Shutdown
40457 10 3119 Excessive_Mech_Vibration_9_(A5) PC 3.x
Bitmap 27 w/Cooldown

A029X159 (Issue 19) 445 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas Shutdown
40457 11 3121 Excessive_Mech_Vibration_10_(B5) PC 3.x
Bitmap 27 w/Cooldown
Fault Status Gas Shutdown
40457 12 3122 Excessive_Mech_Vibration_11_(A6) PC 3.x
Bitmap 27 w/Cooldown
Fault Status Gas Shutdown
40457 13 3123 Excessive_Mech_Vibration_12_(B6) PC 3.x
Bitmap 27 w/Cooldown
Fault Status Gas Shutdown
40457 14 3124 Excessive_Mech_Vibration_13_(A7) PC 3.x
Bitmap 27 w/Cooldown
Fault Status Gas Shutdown
40457 15 3125 Excessive_Mech_Vibration_14_(B7) PC 3.x
Bitmap 27 w/Cooldown
Fault Status Gas Shutdown
40458 0 3126 Excessive_Mech_Vibration_15_(A8) PC 3.x
Bitmap 28 w/Cooldown
Fault Status Gas Shutdown
40458 1 3127 Excessive_Mech_Vibration_16_(B8) PC 3.x
Bitmap 28 w/Cooldown
Fault Status Gas Shutdown
40458 2 3128 Excessive_Mech_Vibration_17_(A9) PC 3.x
Bitmap 28 w/Cooldown
Fault Status Gas Shutdown
40458 3 3129 Excessive_Mech_Vibration_18_(B9) PC 3.x
Bitmap 28 w/Cooldown
Fault Status Gas
40458 4 1275 Knock Cyl 10 (B5) OORL Warning PC 3.x
Bitmap 28
Fault Status Gas
40458 5 1277 Knock Cyl 11 (A6) OORL Warning PC 3.x
Bitmap 28
Fault Status Gas
40458 6 1282 Knock Cyl 12 (B6) OORL Warning PC 3.x
Bitmap 28
Fault Status Gas
40458 7 1287 Knock Cyl 13 (A7) OORL Warning PC 3.x
Bitmap 28
Fault Status Gas
40458 8 1292 Knock Cyl 14 (B7) OORL Warning PC 3.x
Bitmap 28
Fault Status Gas
40458 9 1297 Knock Cyl 15 (A8) OORL Warning PC 3.x
Bitmap 28
Fault Status Gas
40458 10 1584 Knock Cyl 16 (B8) OORL Warning PC 3.x
Bitmap 28
Fault Status Gas
40458 11 1589 Knock Cyl 17 (A9) OORL Warning PC 3.x
Bitmap 28
Fault Status Gas
40458 12 1338 Knock Cyl 18 (B9) OORL Warning PC 3.x
Bitmap 28
Fault Status Gas HT Coolant Temperature Root Cause Shutdown
40459 0 189 PC 3.x
Bitmap 29 Unknown w/Cooldown
Fault Status Gas
40459 1 229 HT Coolant Pressure Incorrect Warning PC 3.x
Bitmap 29

Copyright © 2017 Cummins Inc. 446 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas
40459 2 334 HT Coolant Temperature Incorrect Warning PC 3.x
Bitmap 29
Fault Status Gas
40459 4 831 Spark Plug 1 (A1) OORL Warning PC 3.x
Bitmap 29
Fault Status Gas
40459 5 832 Spark Plug 2 (B1) OORL Warning PC 3.x
Bitmap 29
Fault Status Gas
40459 6 833 Spark Plug 3 (A2) OORL Warning PC 3.x
Bitmap 29
Fault Status Gas
40459 7 834 Spark Plug 4 (B2) OORL Warning PC 3.x
Bitmap 29
Fault Status Gas
40459 8 835 Spark Plug 5 (A3) OORL Warning PC 3.x
Bitmap 29
Fault Status Gas
40459 9 836 Spark Plug 6 (B3) OORL Warning PC 3.x
Bitmap 29
Fault Status Gas
40459 10 837 Spark Plug 7 (A4) OORL Warning PC 3.x
Bitmap 29
Fault Status Gas
40459 11 838 Spark Plug 8 (B4) OORL Warning PC 3.x
Bitmap 29
Fault Status Gas
40459 12 839 Spark Plug 9 (A5) OORL Warning PC 3.x
Bitmap 29
Fault Status Gas
40459 13 841 Spark Plug 10 (B5) OORL Warning PC 3.x
Bitmap 29
Fault Status Gas
40459 14 842 Spark Plug 11 (A6) OORL Warning PC 3.x
Bitmap 29
Fault Status Gas
40459 15 843 Spark Plug 12 (B6) OORL Warning PC 3.x
Bitmap 29
Fault Status Gas
40460 0 844 Spark Plug 13 (A7) OORL Warning PC 3.x
Bitmap 30
Fault Status Gas
40460 1 845 Spark Plug 14 (B7) OORL Warning PC 3.x
Bitmap 30
Fault Status Gas
40460 2 846 Spark Plug 15 (A8) OORL Warning PC 3.x
Bitmap 30
Fault Status Gas
40460 3 847 Spark Plug 16 (B8) OORL Warning PC 3.x
Bitmap 30
Fault Status Gas
40460 4 848 Spark Plug 17 (A9) OORL Warning PC 3.x
Bitmap 30
Fault Status Gas
40460 5 849 Spark Plug 18 (B9) OORL Warning PC 3.x
Bitmap 30
Fault Status Gas Spark Plug 1 (A1) Root Cause
40460 7 891 Warning PC 3.x
Bitmap 30 Unknown

A029X159 (Issue 19) 447 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas Spark Plug 2 (B1) Root Cause
40460 8 892 Warning PC 3.x
Bitmap 30 Unknown
Fault Status Gas Spark Plug 3 (A2) Root Cause
40460 9 893 Warning PC 3.x
Bitmap 30 Unknown
Fault Status Gas Spark Plug 4 (B2) Root Cause
40460 10 894 Warning PC 3.x
Bitmap 30 Unknown
Fault Status Gas Spark Plug 5 (A3) Root Cause
40460 11 895 Warning PC 3.x
Bitmap 30 Unknown
Fault Status Gas Spark Plug 6 (B3) Root Cause
40460 12 896 Warning PC 3.x
Bitmap 30 Unknown
Fault Status Gas Spark Plug 7 (A4) Root Cause
40460 13 897 Warning PC 3.x
Bitmap 30 Unknown
Fault Status Gas Spark Plug 8 (B4) Root Cause
40460 14 898 Warning PC 3.x
Bitmap 30 Unknown
Fault Status Gas Spark Plug 9 (A5) Root Cause
40460 15 899 Warning PC 3.x
Bitmap 30 Unknown
Fault Status Gas Spark Plug 10 (B5) Root Cause
40461 0 911 Warning PC 3.x
Bitmap 31 Unknown
Fault Status Gas Spark Plug 11 (A6) Root Cause
40461 1 912 Warning PC 3.x
Bitmap 31 Unknown
Fault Status Gas Spark Plug 12 (B6) Root Cause
40461 2 913 Warning PC 3.x
Bitmap 31 Unknown
Fault Status Gas Spark Plug 13 (A7) Root Cause
40461 3 914 Warning PC 3.x
Bitmap 31 Unknown
Fault Status Gas Spark Plug 14 (B7) Root Cause
40461 4 915 Warning PC 3.x
Bitmap 31 Unknown
Fault Status Gas Spark Plug 15 (A8) Root Cause
40461 5 916 Warning PC 3.x
Bitmap 31 Unknown
Fault Status Gas Spark Plug 16 (B8) Root Cause
40461 6 917 Warning PC 3.x
Bitmap 31 Unknown
Fault Status Gas Spark Plug 17 (A9) Root Cause
40461 7 918 Warning PC 3.x
Bitmap 31 Unknown
Fault Status Gas Spark Plug 18 (B9) Root Cause
40461 8 919 Warning PC 3.x
Bitmap 31 Unknown
Fault Status Gas
40461 10 1276 Knock Cyl 10 (B5) OORH Warning PC 3.x
Bitmap 31
Fault Status Gas
40461 11 1278 Knock Cyl 11 (A6) OORH Warning PC 3.x
Bitmap 31
Fault Status Gas
40461 12 1279 Knock 12 (B6) High Warning Warning PC 3.x
Bitmap 31

Copyright © 2017 Cummins Inc. 448 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas
40461 13 1283 Knock Cyl 12 (B6) OORH Warning PC 3.x
Bitmap 31
Fault Status Gas
40461 14 1284 Knock 13 (A7) High Warning Warning PC 3.x
Bitmap 31
Fault Status Gas
40461 15 1288 Knock Cyl 13 (A7) OORH Warning PC 3.x
Bitmap 31
Fault Status Gas
40462 0 1289 Knock 14 (B7) High Warning Warning PC 3.x
Bitmap 32
Fault Status Gas
40462 1 1293 Knock Cyl 14 (B7) OORH Warning PC 3.x
Bitmap 32
Fault Status Gas
40462 2 1294 Knock 15 (A8) High Warning Warning PC 3.x
Bitmap 32
Fault Status Gas
40462 3 1298 Knock Cyl 15 (A8) OORH Warning PC 3.x
Bitmap 32
Fault Status Gas
40462 4 1299 Knock 16 (B8) High Warning Warning PC 3.x
Bitmap 32
Fault Status Gas
40462 6 1339 Knock Cyl 18 (B9) OORH Warning PC 3.x
Bitmap 32
Fault Status Gas
40462 7 1352 Knock 20 (B10) High Warning Warning PC 3.x
Bitmap 32
Fault Status Gas Continuous_Light_Knock_Error_20_( Shutdown
40462 8 1353 PC 3.x
Bitmap 32 B10) w/Cooldown
Fault Status Gas Shutdown
40462 9 1354 Heavy_Knock_Error_20_(B10) PC 3.x
Bitmap 32 w/Cooldown
Fault Status Gas
40462 10 1355 Knock Cyl 20 (B10) OORL Warning PC 3.x
Bitmap 32
Fault Status Gas
40462 11 1356 Knock Cyl 20 (B10) OORH Warning PC 3.x
Bitmap 32
Fault Status Gas Continuous_Light_Knock_Error_19_( Shutdown
40462 12 1572 PC 3.x
Bitmap 32 A10) w/Cooldown
Fault Status Gas Shutdown
40462 13 1574 Heavy_Knock_Error_19_(A10) PC 3.x
Bitmap 32 w/Cooldown
Fault Status Gas
40462 14 1575 Knock Cyl 19 (A10) OORL Warning PC 3.x
Bitmap 32
Fault Status Gas
40462 15 1576 Knock Cyl 19 (A10) OORH Warning PC 3.x
Bitmap 32
Fault Status Gas
40463 0 1585 Knock Cyl 16 (B8) OORH Warning PC 3.x
Bitmap 33
Fault Status Gas
40463 1 1586 Knock 17 (A9) High Warning Warning PC 3.x
Bitmap 33

A029X159 (Issue 19) 449 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas
40463 2 1591 Knock Cyl 17 (A9) OORH Warning PC 3.x
Bitmap 33
Fault Status Gas
40463 3 1592 Knock 18 (B9) High Warning Warning PC 3.x
Bitmap 33
Fault Status Gas
40463 4 1594 Knock 19 (A10) High Warning Warning PC 3.x
Bitmap 33
Fault Status Gas
40463 6 2193 HT Coolant Level Moderate High Warning PC 3.x
Bitmap 33
Fault Status Gas
40463 7 2231 Knock Cyl 1 (A1) OORH Warning PC 3.x
Bitmap 33
Fault Status Gas
40463 8 2232 Knock Cyl 2 (B1) OORH Warning PC 3.x
Bitmap 33
Fault Status Gas
40463 9 2233 Knock Cyl 3 (A2) OORH Warning PC 3.x
Bitmap 33
Fault Status Gas
40463 10 2234 Knock Cyl 4 (B2) OORH Warning PC 3.x
Bitmap 33
Fault Status Gas
40463 11 2235 Knock Cyl 5 (A3) OORH Warning PC 3.x
Bitmap 33
Fault Status Gas
40463 12 2236 Knock Cyl 6 (B3) OORH Warning PC 3.x
Bitmap 33
Fault Status Gas
40463 13 2237 Knock Cyl 7 (A4) OORH Warning PC 3.x
Bitmap 33
Fault Status Gas
40463 14 2238 Knock Cyl 8 (B4) OORH Warning PC 3.x
Bitmap 33
Fault Status Gas
40463 15 2239 Knock Cyl 9 (A5) OORH Warning PC 3.x
Bitmap 33
Fault Status Gas
40464 0 2279 Knock 11 (A6) High Warning Warning PC 3.x
Bitmap 34
Fault Status Gas
40464 1 2431 Knock 1 (A1) High Warning Warning PC 3.x
Bitmap 34
Fault Status Gas
40464 2 2432 Knock 2 (B1) High Warning Warning PC 3.x
Bitmap 34
Fault Status Gas
40464 3 2433 Knock 3 (A2) High Warning Warning PC 3.x
Bitmap 34
Fault Status Gas
40464 4 2434 Knock 4 (B2) High Warning Warning PC 3.x
Bitmap 34
Fault Status Gas
40464 5 2435 Knock 5 (A3) High Warning Warning PC 3.x
Bitmap 34
Fault Status Gas
40464 6 2436 Knock 6 (B3) High Warning Warning PC 3.x
Bitmap 34

Copyright © 2017 Cummins Inc. 450 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas
40464 7 2437 Knock 7 (A4) High Warning Warning PC 3.x
Bitmap 34
Fault Status Gas
40464 8 2438 Knock 8 (B4) High Warning Warning PC 3.x
Bitmap 34
Fault Status Gas
40464 9 2439 Knock 9 (A5) High Warning Warning PC 3.x
Bitmap 34
Fault Status Gas
40464 10 2441 Knock 10 (B5) High Warning Warning PC 3.x
Bitmap 34
Fault Status Gas Exhaust Temperature 19 (A10) Shutdown
40464 11 2514 PC 3.x
Bitmap 34 Abnormal Rate w/Cooldown
Fault Status Gas Exhaust Temperature 20 (B10) Shutdown
40464 12 2515 PC 3.x
Bitmap 34 Abnormal Rate w/Cooldown
Fault Status Gas
40464 13 2553 Engine Oil Level Low Warning Error Warning PC 3.x
Bitmap 34
Fault Status Gas Shutdown
40464 14 2568 Gas Supply Pressure Critical High PC 3.x
Bitmap 34 w/Cooldown
Fault Status Gas Shutdown
40464 15 2569 Gas Supply Pressure Critical Low PC 3.x
Bitmap 34 w/Cooldown
Fault Status Gas
40465 0 2586 Spark Plug 1 (A1) High Warning NONE PC 3.x
Bitmap 35
Fault Status Gas
40465 1 2587 Spark Plug 2 (B1) High Warning NONE PC 3.x
Bitmap 35
Fault Status Gas
40465 2 2588 Spark Plug 3 (A2) High Warning NONE PC 3.x
Bitmap 35
Fault Status Gas
40465 3 2589 Spark Plug 4 (B2) High Warning NONE PC 3.x
Bitmap 35
Fault Status Gas
40465 4 2591 Spark Plug 5 (A3) High Warning NONE PC 3.x
Bitmap 35
Fault Status Gas
40465 5 2592 Spark Plug 6 (B3) High Warning NONE PC 3.x
Bitmap 35
Fault Status Gas
40465 6 2593 Spark Plug 1 (A1) Low Warning NONE PC 3.x
Bitmap 35
Fault Status Gas
40465 7 2594 Spark Plug 2 (B1) Low Warning NONE PC 3.x
Bitmap 35
Fault Status Gas
40465 8 2595 Spark Plug 3 (A2) Low Warning NONE PC 3.x
Bitmap 35
Fault Status Gas
40465 9 2596 Spark Plug 4 (B2) Low Warning NONE PC 3.x
Bitmap 35
Fault Status Gas
40465 10 2597 Spark Plug 5 (A3) Low Warning NONE PC 3.x
Bitmap 35

A029X159 (Issue 19) 451 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas
40465 11 2598 Spark Plug 6 (B3) Low Warning NONE PC 3.x
Bitmap 35
Fault Status Gas HT Coolant Temperature Condition
40465 12 2646 Warning PC 3.x
Bitmap 35 Exists
Fault Status Gas
40466 0 3262 Spark Plug 7 (A4) High Warning NONE PC 3.x
Bitmap 36
Fault Status Gas
40466 1 3263 Spark Plug 7 (A4) Low Warning NONE PC 3.x
Bitmap 36
Fault Status Gas
40466 2 3264 Spark Plug 8 (B4) High Warning NONE PC 3.x
Bitmap 36
Fault Status Gas
40466 3 3265 Spark Plug 8 (B4) Low Warning NONE PC 3.x
Bitmap 36
Fault Status Gas
40466 4 3266 Spark Plug 9 (A5) High Warning NONE PC 3.x
Bitmap 36
Fault Status Gas
40466 5 3267 Spark Plug 9 (A5) Low Warning NONE PC 3.x
Bitmap 36
Fault Status Gas
40466 6 3268 Spark Plug 10 (B5) High Warning NONE PC 3.x
Bitmap 36
Fault Status Gas
40466 7 3269 Spark Plug 10 (B5) Low Warning NONE PC 3.x
Bitmap 36
Fault Status Gas
40466 8 3271 Spark Plug 11 (A6) High Warning NONE PC 3.x
Bitmap 36
Fault Status Gas
40466 9 3272 Spark Plug 11 (A6) Low Warning NONE PC 3.x
Bitmap 36
Fault Status Gas
40466 10 3273 Spark Plug 12 (B6) High Warning NONE PC 3.x
Bitmap 36
Fault Status Gas
40466 11 3274 Spark Plug 12 (B6) Low Warning NONE PC 3.x
Bitmap 36
Fault Status Gas
40466 12 3275 Spark Plug 13 (A7) High Warning NONE PC 3.x
Bitmap 36
Fault Status Gas
40466 13 3276 Spark Plug 13 (A7) Low Warning NONE PC 3.x
Bitmap 36
Fault Status Gas
40466 14 3277 Spark Plug 14 (B7) High Warning NONE PC 3.x
Bitmap 36
Fault Status Gas
40466 15 3278 Spark Plug 14 (B7) Low Warning NONE PC 3.x
Bitmap 36
Fault Status Gas
40467 0 3279 Spark Plug 15 (A8) High Warning NONE PC 3.x
Bitmap 37
Fault Status Gas
40467 1 3281 Spark Plug 15 (A8) Low Warning NONE PC 3.x
Bitmap 37

Copyright © 2017 Cummins Inc. 452 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas
40467 2 3282 Spark Plug 16 (B8) High Warning NONE PC 3.x
Bitmap 37
Fault Status Gas
40467 3 3283 Spark Plug 16 (B8) Low Warning NONE PC 3.x
Bitmap 37
Fault Status Gas
40467 4 3284 Spark Plug 17 (A9) High Warning NONE PC 3.x
Bitmap 37
Fault Status Gas
40467 5 3285 Spark Plug 17 (A9) Low Warning NONE PC 3.x
Bitmap 37
Fault Status Gas
40467 6 3286 Spark Plug 18 (B9) High Warning NONE PC 3.x
Bitmap 37
Fault Status Gas
40467 7 3287 Spark Plug 18 (B9) Low Warning NONE PC 3.x
Bitmap 37
Fault Status Gas Exhaust Aft Outlet Oxygen Relay
40467 8 3288 Warning PC 3.x
Bitmap 37 OORH
Fault Status Gas Exhaust Aft Outlet Oxygen Relay
40467 9 3289 Warning PC 3.x
Bitmap 37 OORL
Fault Status Gas Exhaust Aft Inlet Oxygen Relay
40467 10 3291 Warning PC 3.x
Bitmap 37 OORH
Fault Status Gas Exhaust Aft Inlet Oxygen Relay
40467 11 3292 Warning PC 3.x
Bitmap 37 OORL
Fault Status Gas
40467 12 3293 Exhaust Oxygen Relay OORH Warning PC 3.x
Bitmap 37
Fault Status Gas
40467 13 3294 Exhaust Oxygen Relay OORL Warning PC 3.x
Bitmap 37
Fault Status Gas External Air Pressure Low Warning
40468 3 3365 Warning PC 3.x
Bitmap 38 Error
Fault Status Gas Manifold_Absolute_Pressure_2_High
40468 4 3384 Warning PC 3.x
Bitmap 38 _Error
Fault Status Gas Manifold_Absolute_Pressure_2_Low
40468 5 3391 Warning PC 3.x
Bitmap 38 _Error
Fault Status Gas Shutdown
40468 6 3392 Int Man Pressure 2 Critical High PC 3.x
Bitmap 38 w/Cooldown
Fault Status Gas
40468 7 3393 Int Man Pressure 2 Moderate High Warning PC 3.x
Bitmap 38
Fault Status Gas Low Gearbox Oil Pressure -
40468 9 3397 Shutdown PC 3.x
Bitmap 38 Condition Exists
Fault Status Gas High Gearbox Oil Temperature - Shutdown
40468 10 3398 PC 3.x
Bitmap 38 Condition Exists w/Cooldown
Fault Status Gas
40468 11 3399 Differential Fault - Condition Exists Shutdown PC 3.x
Bitmap 38

A029X159 (Issue 19) 453 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas DC Power Supply Fault - Condition
40468 12 3411 Warning PC 3.x
Bitmap 38 Exists
Fault Status Gas GIB Isolator Open Fault - Condition
40468 13 3412 Warning PC 3.x
Bitmap 38 Exists
Fault Status Gas Radiator Fan Trip Fault - Condition
40468 14 3413 Warning PC 3.x
Bitmap 38 Exists
Fault Status Gas Ventilator Fan Trip Fault - Condition
40468 15 3414 Warning PC 3.x
Bitmap 38 Exists
Fault Status Gas Louvres Closed Fault - Condition
40469 0 3415 Warning PC 3.x
Bitmap 39 Exists
Fault Status Gas
40469 1 3416 Start System Fault - Condition Exists Warning PC 3.x
Bitmap 39
Fault Status Gas Alternator Heater Trip Fault -
40469 2 3417 Warning PC 3.x
Bitmap 39 Condition Exists
Fault Status Gas
40469 4 9971 ECM Derate Fault NONE PC 3.x
Bitmap 39
Fault Status Gas
40469 5 3479 Start-Inhibit Shutdown Fault Shutdown PC 3.x
Bitmap 39
Fault Status Gas
40469 6 3481 Start-Inhibit Warning Fault Event Warning PC 3.x
Bitmap 39
Fault Status Gas High Alternator Temperature 1
40469 7 3483 Shutdown PC 3.x
Bitmap 39 Shutdown Fault
Fault Status Gas High Alternator Temperature 2
40469 8 3484 Shutdown PC 3.x
Bitmap 39 Shutdown Fault
Fault Status Gas High Alternator Temperature 3
40469 9 3485 Shutdown PC 3.x
Bitmap 39 Shutdown Fault
Fault Status Gas High Drive End Bearing Temperature
40469 10 3486 Shutdown PC 3.x
Bitmap 39 Shutdown Fault
Fault Status Gas High Non-Drive End Bearing Temp
40469 11 3487 Shutdown PC 3.x
Bitmap 39 Shutdown Fault
Fault Status Gas
40469 12 3482 Off Load Running Fault Shutdown PC 3.x
Bitmap 39
Fault Status Gas Shutdown
40470 0 3491 Oil Filter Restriction High PC 3.x
Bitmap 40 w/Cooldown
Fault Status Gas
40470 1 2313 Fuel Control Valve Error Warning PC 3.x
Bitmap 40
Fault Status Gas Engine Electronic Fuel Valve #2
40470 2 3475 Warning PC 3.x
Bitmap 40 OORH
Fault Status Gas Engine Electronic Fuel Valve #2
40470 3 3476 Warning PC 3.x
Bitmap 40 OORL

Copyright © 2017 Cummins Inc. 454 A029X159 (Issue 19)


8-2017 6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Fault
Addr. Bit# Name Event Name Response Control
Code
Fault Status Gas Shutdown
40470 4 2812 Throttle Control Actuator Error PC 3.x
Bitmap 40 w/Cooldown
Fault Status Gas
40470 5 3489 Compressor Bypass Actuator Error Warning PC 3.x
Bitmap 40
Fault Status Gas
40470 6 3458 Knock Engine Derate Warning PC 3.x
Bitmap 40
Fault Status Gas Throttle Actuator 2- Special Shutdown
40470 8 3499 PC 3.x
Bitmap 40 Instruction w/Cooldown
Fault Status Gas Shutdown
40470 9 3511 Throttle Actuator 2- Shorted High PC 3.x
Bitmap 40 w/Cooldown
Fault Status Gas Shutdown
40470 10 3512 Throttle Actuator 2- Shorted Low PC 3.x
Bitmap 40 w/Cooldown
Fault Status Gas Shutdown
40470 11 2752 Throttle Actuator - Shorted High PC 3.x
Bitmap 40 w/Cooldown
Fault Status Gas Shutdown
40470 12 3514 Throttle Actuator - Shorted Low PC 3.x
Bitmap 40 w/Cooldown
Fault Status Gas Shutdown
40470 13 3515 Throttle Actuator - Special instruction PC 3.x
Bitmap 40 w/Cooldown
Fault Status Gas
40470 14 3521 Throttle Actuator - Temperature low Warning PC 3.x
Bitmap 40
Fault Status Gas
40470 15 3522 Throttle Actuator 2- Temp low Warning PC 3.x
Bitmap 40
Fault Status Gas
40474 10 4686 Connector Cap Not Present Warning PC 3.x
Bitmap 40
Customer Faults
40757 0 1573 Configurable Input #1 None 3.X
(Modlon)
Customer Faults
40757 1 1312 Configurable Input #2 None 3.X
(Modlon)
Customer Faults
40757 2 1317 Configurable Input #13 None 3.X
(Modlon)
Customer Faults
40757 3 1318 Configurable Input #14 None 3.X
(Modlon)
Customer Faults
40757 4 5182 AUX101 0 Input 1 Fault Warning 3.X
(Modlon)
Customer Faults
40757 5 2621 AUX101 0 Input 2 Fault Warning 3.X
(Modlon)
Customer Faults
40757 6 2622 AUX101 0 Input 3 Fault Warning 3.X
(Modlon)
Customer Faults
40757 7 2623 AUX101 0 Input 4 Fault Warning 3.X
(Modlon)

A029X159 (Issue 19) 455 Copyright © 2017 Cummins Inc.


6. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# Name Event Name Response Control
Code
Customer Faults
40757 8 2624 AUX101 0 Input 5 Fault Warning 3.X
(Modlon)
Customer Faults
40757 9 2625 AUX101 0 Input 6 Fault Warning 3.X
(Modlon)
Customer Faults
40757 10 2626 AUX101 0 Input 7 Fault Warning 3.X
(Modlon)
Customer Faults
40757 11 2627 AUX101 0 Input 8 Fault Warning 3.X
(Modlon)
Customer Faults
40757 12 2882 Aux101 1 Input 1 Fault Warning 3.X
(Modlon)
Customer Faults
40757 13 2883 Aux101 1 Input 2 Fault Warning 3.X
(Modlon)
Customer Faults
40757 14 2884 Aux101 1 Input 3 Fault Warning 3.X
(Modlon)
Customer Faults
40757 15 2885 Aux101 1 Input 3 Fault Warning 3.X
(Modlon)

Fault
Addr. Bit# Name Event Name Response Control
Code
PCC300,
Fault Status Engine Friction Below Baseline -
41419 9 7548 None PCC3300V
Bitmap 38 Least Severe
2
PCC3300,
Fault Status Engine Friction Below Baseline -
41419 10 7549 Warning PCC3300V
Bitmap 38 Moderately Severe
2
PCC3300,
Fault Status Engine Friction - Above Baseline
41419 11 7551 None PCC3300V
Bitmap 38 Least Severe
2
PCC3300,
Fault Status Engine Friction Above Baseline -
41419 12 7552 Warning PCC3300V
Bitmap 38 Moderately Severe
2
PCC3300,
Fault Status Engine Friction Devn Above Baseline
41419 13 7553 Warning PCC3300V
Bitmap 38 - Mod Severity
2
PCC3300,
Fault Status Engine Friction Devn Above Baseline
41419 14 7554 Shutdown PCC3300V
Bitmap 38 - Most Severe
2
PC3300,
Fault Status
41419 15 7555 Alternator Feedback Power Loss Shutdown PCC3300V
Bitmap 38
2

Copyright © 2017 Cummins Inc. 456 A029X159 (Issue 19)


7 NFPA 110 and Extended Annunciation
Bitmap
TABLE 8. NFPA110 BITMAP

Bit Description
15 Common Alarm
14 Genset Supplying Load
13 Genset Running
12 Not in Auto
11 High Battery Voltage
10 Low Battery Voltage
9 Charger AC Failure
8 Fail to Start
7 Low Coolant Temperature
6 Pre–high Engine Temperature
5 High Engine Temperature
4 Pre–low Oil Pressure
3 Low Oil Pressure
2 Overspeed
1 Low Coolant Level
0 Low Fuel Level

See Chapter 3 Reg. 40016, Section 5.2 Reg. 40716, 40717, and Chapter 9

TABLE 9. EXTENDED ANNUNCIATION BITMAP

Bit Description
15 Check Genset
14 Ground Fault
13 High AC Voltage
12 Low AC Voltage
11 Under Frequency
10 Overload
9 Overcurrent
8 Short Circuit
7 Reverse KW

A029X159 (Issue 19) 457 Copyright © 2017 Cummins Inc.


7. NFPA 110 and Extended Annunciation Bitmap 8-2017

Bit Description
6 Reverse kVAR
5 Fail to Sync
4 Fail to Close
3 Load Demand
2 Genset Circuit Breaker Tripped
1 Utility Circuit Breaker Tripped
0 Emergency Stop

SeeChapter 3 Reg. 40017 and Chapter 9

TABLE 10. NFPA110 BITMAP

Bit Description
15 Source 1 Connected
14 Source 2 Connected
13 NA
12 Not in Auto
11 NA
10 NA
9 Charger AC Failure
8 NA
7 NA
6 NA
5 NA
4 NA
3 NA
2 NA
1 NA
0 NA

See Chapter 10

TABLE 11. EXTENDED ANNUNCIATION BITMAP

Bit Description
15 Source 1 Available
14 Source 2 Available
13 Source 1 Connected

Copyright © 2017 Cummins Inc. 458 A029X159 (Issue 19)


8-2017 7. NFPA 110 and Extended Annunciation Bitmap

Bit Description
12 Source 2 Connected
11 ATS Common Alarm
10 Not In Auto
9 Test / Exercise In Progress
8 Low Battery Voltage
7 Load Shed
6 Transfer Inhibit
5 Retransfer Inhibit
4 Fail To Close
3 Fail To Disconnect
2 Fail To Synchronize
1 Bypass to Source 1
0 Bypass to Source 2

See Chapter 10

A029X159 (Issue 19) 459 Copyright © 2017 Cummins Inc.


7. NFPA 110 and Extended Annunciation Bitmap 8-2017

This page is intentionally blank.

Copyright © 2017 Cummins Inc. 460 A029X159 (Issue 19)


8 NFPA 110 Bitmap (PS0600)
TABLE 12. NFPA110 BITMAP FOR PS0600

Bit Description
31 Check Genset
30 Ground Fault
29 High AC Voltage
28 Low AC Voltage
27 Under Frequency
26 Overload Warning OR Overload Shutdown
25 Overcurrent
24 Short Circuit
23 Reverse KW
22 Reverse KVAR
21 Fail to Sync
20 Fail to Close
19 Load Demand
18 Genset Circuit Breaker Tripped
17 Utility Circuit Breaker Tripped
16 Emergency Stop
15 Common Alarm
14 Genset Supplying Load
13 Genset Running
12 Not in Auto
11 High Battery Voltage
10 Low Battery Voltage OR Weak Battery
9 Charger AC Failure
8 Fail to Start
7 Low Coolant Temperature
6 Pre–High Engine Temperature
5 High Engine Temperature
4 Pre–Low Oil Pressure
3 Low Oil Pressure
2 Overspeed

A029X159 (Issue 19) 461 Copyright © 2017 Cummins Inc.


8. NFPA 110 Bitmap (PS0600) 8-2017

1 Low Coolant Level


0 Low Fuel Level

See Section 4.2.

NOTICE
To view 32-bit data of NFPA110 register in Modbus tool, length shall be provided as 2 for 400016
address for read/write values.

Copyright © 2017 Cummins Inc. 462 A029X159 (Issue 19)


9 DMC 1000 Modbus Parametric Data
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

Addr System Name Access Specifications Description Function

Multiplier: Unit:
1.000000000000 Lower Limit: .000 Logical address
MB Logical Read/ Offset: 0
42001 Upper Limit: to be read via Communications
Read Address Write
Size (bits): 16 65535.000 Modbus
Sign: U Default: 0
Multiplier:
Unit:
1.000000000000 Logical data to
MB Logical Read Lower Limit:
42002 Offset: 0 be read via Communications
Read Data Only Upper Limit:
Size (bits): 32 Modbus
Default:
Sign: U
Multiplier:
Unit:
1.000000000000 Hard coded
Read Lower Limit:
42009 Device Type Offset: 0 device type id = Communications
Only Upper Limit:
Size (bits): 16 52 (0x0034)
Default:
Sign: U
Multiplier:
Unit:
0.000100000000
Software Read Lower Limit: Software version Controller
42010 Offset: 0
Version Only Upper Limit: number Information
Size (bits): 16
Default:
Sign: U
Multiplier: The most
Unit:
1.000000000000 recently
Current Fault Read Lower Limit: Fault and Event
42012 Offset: 0 occurring fault
Status Only Upper Limit: Info
Size (bits): 16 which is still
Default: active
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L1N Read Lower Limit: Generator set
42018 Offset: 0 Voltage
Voltage Only Upper Limit: L1N voltage
Size (bits): 16
Default
Sign: U

A029X159 (Issue 19) 463 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

Addr System Name Access Specifications Description Function


Multiplier:
1.000000000000 Unit: Volts
Genset L2N Read Offset: 0 Lower Limit: Generator set
42019 Voltage
Voltage Only Size (bits): 16 Upper Limit: L2N voltage
Sign: U Default

Multiplier:
Unit: Volts
1.000000000000
Genset L3N Read Lower Limit: Generator set
42020 Offset: 0 Voltage
Voltage Only Upper Limit: L3N voltage
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Volts
Genset LN 1.000000000000 Generator set
Read Lower Limit:
42021 Average Offset: 0 LN average Voltage
Only Upper Limit:
Voltage Size (bits): 16 voltage
Default
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L1L2 Read Lower Limit: Generator set
42022 Offset: 0 Voltage
Voltage Only Upper Limit: L1L2 voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L2L3 Read Lower Limit: Generator set
42023 Offset: 0 Voltage
Voltage Only Upper Limit: L2L3 voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L3L1 Read Lower Limit: Generator set
42024 Offset: 0 Voltage
Voltage Only Upper Limit: L3L1 voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
Genset LL 1.000000000000 Generator set
Read Lower Limit:
42025 Average Offset: 0 LL average Voltage
Only Upper Limit:
Voltage Size (bits): 16 voltage
Default:
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Genset L1 Read Lower Limit: Generator set
42026 Offset: 0 Current
Current Only Upper Limit: L1 current
Size (bits): 16
Default
Sign: U

Copyright © 2017 Cummins Inc. 464 A029X159 (Issue 19)


8-2017 9. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier:
Unit: Amps
1.000000000000
Genset L2 Read Lower Limit: Generator set
42027 Offset: 0 Current
Current Only Upper Limit: L2 current
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Genset L3 Read Lower Limit: Generator set
42028 Offset: 0 Current
Current Only Upper Limit: L3 current
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Amps
Genset 1.000000000000
Read Lower Limit: Generator set
42029 Average Offset: 0 Current
Only Upper Limit: average current
Current Size (bits): 16
Default
Sign: U
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: Generator set
42030 Genset L1 kW Offset: 0 Current
Only Upper Limit: L1 kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: Generator set
42031 Genset L2 kW Offset: 0 Current
Only Upper Limit: L2 kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: Generator set
42032 Genset L3 kW Offset: 0 Power
Only Upper Limit: L3 kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Genset Total Read Lower Limit: Generator set
42033 Offset: 0 Power
kW Only Upper Limit: total kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Genset L1 Read Lower Limit: Generator set
42034 Offset: 0 Power
kVAR Only Upper Limit: L1 kVAR
Size (bits): 16
Default:
Sign: S

A029X159 (Issue 19) 465 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

Addr System Name Access Specifications Description Function


Multiplier:
Unit: kVAR
1.000000000000
Genset L2 Read Lower Limit: Generator set
42035 Offset: 0 Power
kVAR Only Upper Limit: L2 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Genset L3 Read Lower Limit: Generator set
42036 Offset: 0 Power
kVAR Only Upper Limit: L3 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Genset Total Read Lower Limit: Generator set
42037 Offset: 0 Power
kVAR Only Upper Limit: total kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit:
0.010000000000 Generator set
Genset Total Read Lower Limit:
42038 Offset: 0 total power Power
Power Factor Only Upper Limit:
Size (bits): 8 factor
Default:
Sign: S
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: Generator set
42039 Genset L1 kVA Offset: 0 Power
Only Upper Limit: L1 kVA
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: Generator Set
42040 Genset L2 kVA Offset: 0 Power
Only Upper Limit: L2 kVA
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: Generator set
42041 Genset L3 kVA Offset: 0 Power
Only Upper Limit: L3 kVA
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Genset Total Read Lower Limit: kVA Generator set
42042 Offset: 0 Power
kVA Only Upper Limit: kVA total kVA
Size (bits): 16
Default:
Sign: U

Copyright © 2017 Cummins Inc. 466 A029X159 (Issue 19)


8-2017 9. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier:
Unit: Hz Generator set
0.100000000000
MB Genset Read Lower Limit: Hz line frequency
42043 Offset: 0 Communications
Frequency Only Upper Limit: Hz scaled by 10 =
Size (bits): 16 1Hz for Modbus
Default:
Sign: U
Multiplier:
Unit: kWh Generator set
1.000000000000
Genset Total Read Lower Limit: kWh total negative
42044 Offset: 0 Energy
Negative kWh Only Upper Limit: kWh kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kWh Generator set
.100000000000
Genset Total Read Lower Limit: kWh total positive
42046 Offset: 0 Energy
Positive kWh Only Upper Limit: kWh kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kWh
1.000000000000 Generator set
Genset Total Read Lower Limit: kWh
42048 Offset: 0 total net kWh Energy
Net kWh Only Upper Limit: kWh
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier:
Unit: kVARh Generator set
Genset Total 1.000000000000
Read Lower Limit: kVARh total negative
42050 Negative Offset: 0 Energy
Only Upper Limit: kVARh kVARh
kVARh Size (bits): 32
Default: accumulation
Sign: U
Multiplier:
Unit: kVARh Generator set
1.000000000000
Genset Total Read Lower Limit: kVARh total positive
42052 Offset: 0 Energy
Positive kVARh Only Upper Limit: kVARh kVARh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kVARh
1.000000000000 Generator set
Genset Total Read Lower Limit: kVARh
42054 Offset: 0 total net kVARh Energy
Net kVARh Only Upper Limit: kVARh
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier:
Unit: kVAh
1.000000000000 Generator set
Genset Total Read Lower Limit: kVAh
40056 Offset: 0 total kVAh Energy
kVAh Only Upper Limit: kVAh
Size (bits): 32 accumulation
Default:
Sign: U

A029X159 (Issue 19) 467 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

Addr System Name Access Specifications Description Function


Calculated
Multiplier: Amps which
Unit: Amps
Genset 1.000000000000 represent 100%
Read Lower Limit:
42058 Available Offset: 0 generator set Current
Only Upper Limit:
Current Size (bits): 16 bus current --
Default: used by
Sign: U
barograph
Generator set
Multiplier: L1 current as
Unit: %
Genset L1 0.100000000000 percent of
Read Lower Limit:
42059 Current Offset: 0 generator set Current
Only Upper Limit:
Percent Size (bits): 16 total current
Default: capacity--used
Sign: U
by barograph
Generator set
Multiplier: L2 current as
Unit: %
Genset L2 0.100000000000 percent of
Read Lower Limit:
42060 Current Offset: 0 generator set Current
Only Upper Limit:
Percent Size (bits): 16 total current
Default: capacity--used
Sign: U
by barograph
Generator set
Multiplier: L3 current as
Unit: %
Genset L3 0.100000000000 percent of
Read Lower Limit:
42061 Current Offset: 0 generator set Current
Only Upper Limit:
Percent Size (bits): 16 total current
Default: capacity--used
Sign: U
by barograph

Multiplier: Generator set


Unit: % total kW as
0.100000000000
Genset Total Read Lower Limit: percent of total
42062 Offset: 0 Power
kW Percent Only Upper Limit: generator set
Size (bits): 16 capacity -- used
Default:
Sign: S by barograph
Generator set
Multiplier: frequency as
Unit: %
Genset 0.100000000000 percent of
Read Lower Limit:
42063 Frequency Offset: 0 system Frequency
Only Upper Limit:
Percent Size (bits): 16 frequency --
Default: used by
Sign: U
barograph
Multiplier:
Unit: %
0.100000000000
Genset L1L2 Read Lower Limit: Generator set
42064 Offset: 0 Voltage
Voltage% Only Upper Limit: L1L2 voltage%
Size (bits): 16
Default:
Sign: U

Copyright © 2017 Cummins Inc. 468 A029X159 (Issue 19)


8-2017 9. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier:
Unit: %
0.100000000000
Genset L2L3 Read Lower Limit: Generator set
42065 Offset: 0 Voltage
Voltage% Only Upper Limit: L2L3 voltage%
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: %
0.100000000000
Genset L3L1 Read Lower Limit: Generator set
42066 Offset: 0 Voltage
Voltage% Only Upper Limit: L3L1 voltage%
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L1N Read Lower Limit: Utility L1N
42118 Offset: 0 Voltage
Voltage Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L2N Read Lower Limit: Utility L2N
42119 Offset: 0 Voltage
Voltage Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L3N Read Lower Limit: Utility L3N
42120 Offset: 0 Voltage
Voltage Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U
Multiplier:
Unit: Volts
Utility LN 1.000000000000
Read Lower Limit: Utility LN
42121 Average Offset: 0 Voltage
Only Upper Limit: average voltage
Voltage Size (bits): 16
Default: 0
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L1L2 Read Lower Limit: Utility L1L2
42122 Offset: 0 Voltage
Voltage Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L2L3 Read Lower Limit: Utility L2L3
42123 Offset: 0 Voltage
Voltage Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U

A029X159 (Issue 19) 469 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

Addr System Name Access Specifications Description Function


Multiplier:
Unit: Volts
1.000000000000
Utility L3L1 Read Lower Limit: Utility L3L1
42124 Offset: 0 Voltage
Voltage Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U
Multiplier:
Unit: Volts
Utility LL 1.000000000000
Read Lower Limit: Utility LL
42125 Average Offset: 0 Voltage
Only Upper Limit: average voltage
Voltage Size (bits): 16
Default: 0
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Utility L1 Read Lower Limit:
42126 Offset: 0 Utility L1 current Current
Current Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Utility L2 Read Lower Limit:
42127 Offset: 0 Utility L2 current Current
Current Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Utility L3 Read Lower Limit:
42128 Offset: 0 Utility L3 current Current
Current Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Utility Average Read Lower Limit: Utility average
42129 Offset: 0 Current
Current Only Upper Limit: current
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit:
42130 Utility L1 kW Offset: 0 Utility L1 kW Power
Only Upper Limit:
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit:
42131 Utility L2 kW Offset: 0 Utility L2 kW Power
Only Upper Limit:
Size (bits): 16
Default
Sign: S

Copyright © 2017 Cummins Inc. 470 A029X159 (Issue 19)


8-2017 9. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier:
Unit: kW
1.000000000000
Read Lower Limit:
42132 Utility L3 kW Offset: 0 Utility L3 kW Power
Only Upper Limit:
Size (bits): 16
Default
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit:
42133 Utility Total kW Offset: 0 Utility total kW Power
Only Upper Limit:
Size (bits): 16
Default
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Utility L1 Read Lower Limit:
42134 Offset: 0 Utility L1 kVAR Power
kVARt Only Upper Limit:
Size (bits): 16
Default
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Read Lower Limit:
42135 Utility L2 kVAR Offset: 0 Utility L2 kVAR Power
Only Upper Limit:
Size (bits): 16
Default
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Read Lower Limit:
42136 Utility L3 kVAR Offset: 0 Utility L3 kVAR Power
Only Upper Limit:
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Utility Total Read Lower Limit:
42137 Offset: 0 Utility total kVAR Power
kVAR Only Upper Limit:
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit:
.010000000000
Utility Total Read Lower Limit: Utility total
42138 Offset: 0 Power
Power Factor Only Upper Limit: power factor
Size (bits): 8
Default:
Sign: S
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit:
42139 Utility L1 kVA Offset: 0 Utility L1 kVA Power
Only Upper Limit:
Size (bits): 16
Default:
Sign: U

A029X159 (Issue 19) 471 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

Addr System Name Access Specifications Description Function


Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit:
42140 Utility L2 kVA Offset: 0 Utility L2 kVA Power
Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit:
42141 Utility L3 kVA Offset: 0 Utility L3 kVA Power
Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Utility Total Read Lower Limit:
42142 Offset: 0 Utility total kVA Power
kVA Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Hz Utility line
.100000000000
MB Utility Read Lower Limit: frequency
42143 Offset: 0 Communications
Frequency Only Upper Limit: scaled by 10 =
Size (bits): 16 1Hz for Modbus
Default:
Sign: U
Multiplier:
Unit: kWh
1.000000000000 Utility total
Utility Total Read Lower Limit:
42144 Offset: 0 negative kWh Energy
Negative kWh Only Upper Limit:
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kWh
1.000000000000 Utility total
Utility Total Read Lower Limit:
42146 Offset: 0 positive kWh Energy
Positive kWh Only Upper Limit:
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kWh
1.000000000000 Utility total net
Utility Total Net Read Lower Limit:
42148 Offset: 0 kWh Energy
kWh Only Upper Limit:
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier:
Unit: kVARh
Utility Total 1.000000000000 Utility total
Read Lower Limit:
42150 Negative Offset: 0 negative kVARh Energy
Only Upper Limit:
kVARh Size (bits): 32 accumulation
Default:
Sign: U

Copyright © 2017 Cummins Inc. 472 A029X159 (Issue 19)


8-2017 9. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier:
Unit: kVARh
1.000000000000 Utility total
Utility Total Read Lower Limit:
42152 Offset: 0 positive kVARh Energy
Positive kVARh Only Upper Limit:
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kVARh
1.000000000000 Utility total net
Utility Total Net Read Lower Limit:
42154 Offset: 0 kVARh Energy
kVARh Only Upper Limit:
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier:
Unit: kVARh
1.000000000000
Utility Total Read Lower Limit: Utility total kVAh
42156 Offset: 0 Energy
kVAh Only Upper Limit: accumulation
Size (bits): 32
Default:
Sign: U
Multiplier:
Unit: kW Sum of
1.000000000000
System Total Read Lower Limit: generator set
42158 Offset: 0 Power
kW Only Upper Limit: bus and utility
Size (bits): 16 bus kW
Default:
Sign: S
Multiplier:
Unit: kVAR Sum of
1.000000000000
System Total Read Lower Limit: generator set
42159 Offset: 0 Power
kVAR Only Upper Limit: bus and utility
Size (bits): 16 bus kVAR
Default:
Sign: S

Multiplier: System total


Unit: power factor
0.010000000000
System Total Read Lower Limit: (totalized value
42160 Offset: 0 Power
Power Factor Only Upper Limit: of utility bus plus
Size (bits): 8 generator set
Default:
Sign: S bus)
Multiplier:
Unit: kVA Sum of
1.000000000000
System Total Read Lower Limit: generator set
42161 Offset: 0 Power
kVA Only Upper Limit: bus and utility
Size (bits): 16 bus kVA
Default:
Sign: U
Multiplier:
Unit: %
Utility L1 .100000000000
Read Lower Limit:
42162 Current Offset: 0 barograph Current
Only Upper Limit:
Percent Size (bits): 16
Default:
Sign: U

A029X159 (Issue 19) 473 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

Addr System Name Access Specifications Description Function


Multiplier:
Unit: %
Utility L2 .100000000000
Read Lower Limit:
42163 Current Offset: 0 barograph Current
Only Upper Limit:
Percent Size (bits): 16
Default:
Sign: U
Multiplier:
.100000000000 Unit: %
Utility L3 Offset: 0 Lower Limit:
Read
42164 Current barograph Current
Only Size (bits): 16 Upper Limit:
Percent
Sign: U Default:

Multiplier:
.100000000000 Unit: % Utility total kW
Offset: 0 Lower Limit: as percent of
Utility Total kW Read
42165 total utility Power
Percent Only Size (bits): 16 Upper Limit: capacity -- used
Sign: S Default: by barograph

Multiplier: Unit: % Utility frequency


.100000000000 Lower Limit: as percent of
Utility
Read Offset: 0 System
42166 Frequency Upper Limit: Frequency
Only Frequency --
Percent Size (bits): 16 Default: used by
Sign: U barograph
Multiplier:
Unit: %
.100000000000
Utility L1L2 Read Lower Limit: Utility L1L2
42167 Offset: 0 Voltage
Voltage% Only Upper Limit: voltage%
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: %
.100000000000
Utility L2L3 Read Lower Limit: Utility L2L3
42168 Offset: 0 Voltage
Voltage% Only Upper Limit: voltage%
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: %
.100000000000
Utility L3L1 Read Lower Limit: Utility L3L1
42169 Offset: 0 Voltage
Voltage% Only Upper Limit: voltage%
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: NA Number of
1.000000000000
Total Number Read Lower Limit: generator sets System
42200 Offset: 0
of Gensets Only Upper Limit: with non-zero Information
Size (bits): 16 ratings entered
Default:
Sign: U

Copyright © 2017 Cummins Inc. 474 A029X159 (Issue 19)


8-2017 9. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier:
Unit: kW
1.000000000000 Sum of the
Total System Read Lower Limit: System
42201 Offset: 0 generator set
Capacity Only Upper Limit: Information
Size (bits): 16 kW ratings
Default:
Sign: S
Multiplier: Sum of the
Unit: kW
1.000000000000 generator set
Total Online Read Lower Limit: System
42202 Offset: 0 kW ratings for
Capacity Only Upper Limit: Information
Size (bits): 16 generator sets
Default: which are online
Sign: S
Multiplier:
Unit: seconds Countdown
Programmed .100000000000
Read Lower Limit: value of the
42203 Transition Offset: 0 PTC Timers
Only Upper Limit: programmed
Timer Size (bits): 16
Default: transition timer
Sign: U
Multiplier:
Unit: seconds
.100000000000 Countdown
Read Lower Limit:
42204 Transfer Timer Offset: 0 value of the PTC Timers
Only Upper Limit:
Size (bits): 16 transfer timer
Default: 0
Sign: U
Multiplier:
Unit: seconds
.100000000000 Countdown
Retransfer Read Lower Limit:
42205 Offset: 0 value of the PTC Timers
Timer Only Upper Limit:
Size (bits): 16 retransfer timer
Default:
Sign: U
Multiplier:
Unit: seconds Countdown
.100000000000
Maximum Read Lower Limit: value of the
42206 Offset: 0 PTC Timers
Parallel Timer Only Upper Limit: maximum
Size (bits): 16 parallel timer
Default:
Sign: U
Multiplier:
Unit: kW kW control
1.000000000000
kW Load Read Lower Limit: reference value Master Load
42207 Offset: 0
Reference Only Upper Limit: for utility Control
Size (bits): 16 paralleling
Default:
Sign: S
Multiplier:
Unit: seconds
Active .010000000000 Countdown
Read Lower Limit:
42212 Transition Offset: 0 timer value of PTC Timers
Only Upper Limit:
Timer Size (bits): 16 active timer
Default:
Sign: U

A029X159 (Issue 19) 475 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

Addr System Name Access Specifications Description Function


Multiplier:
Unit: Indicates the
1.000000000000
Hardware Read Lower Limit: hardware
42213 Offset: 0 Discrete Inputs
Version Only Upper Limit: version of the
Size (bits): 8 board
Default:
Sign: U

Multiplier: Unit: seconds


1.000000000000 Lower Limit: 0.000 Amount of time
Controller On Read Offset: 0 in seconds Controller
42214 Upper Limit:
Time Only controller has Information
Size (bits): 32 4294967295.000 been powered
Sign: U Default: 0.000
Multiplier:
Unit: kVAR kVAR control
1.000000000000
kVAR Load Read Lower Limit: reference value Master Load
42220 Offset: 0
Reference Only Upper Limit: for extended Control
Size (bits): 16 paralleling
Default:
Sign: S
Multiplier: Engineering
kVAR Load Unit: %
.010000000000 units value for
Setpoint Engr Read Lower Limit:
42221 Offset: 0 the kVAR load Analog Inputs
Units Display Only Upper Limit:
Size (bits): 16 setpoint analog
Value Default
Sign: S input

Multiplier: Engineering
kW Load Unit: %
.010000000000 units value for
Setpoint Engr Read Lower Limit:
42222 Offset: 0 the kW load Analog Inputs
Units Display Only Upper Limit:
Size (bits): 16 setpoint analog
Value Default:
Sign: S input

Multiplier: Power factor


Unit: setpoint analog
.010000000000
Power Factor Read Lower Limit: input value
42223 Offset: 0 Analog Inputs
Setpoint Only Upper Limit: (uses kVAR load
Size (bits): 8 setpoint analog
Default:
Sign: S input)
Multiplier:
Unit: degrees Utility to
.010000000000
Sync Phase Read Lower Limit: generator set L1
42226 Offset: 0 Phase
Difference Only Upper Limit: voltage phase
Size (bits): 16 angle
Default:
Sign: S
Multiplier:
Unit:
1.000000000000
Current Add Read Lower Limit: Indicates the Load Add Shed
42250 Offset: 0
Level Only Upper Limit: next level to add Control
Size (bits): 8
Default:
Sign: U

Copyright © 2017 Cummins Inc. 476 A029X159 (Issue 19)


8-2017 9. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier:
Unit:
1.000000000000 Indicates the
Current Shed Read Lower Limit: Load Add Shed
42251 Offset: 0 next level to
Level Only Upper Limit: Control
Size (bits): 8 shed
Default
Sign: U
Multiplier: Engineering
Unit: VDC
Battery Voltage .010000000000 units value for
Read Lower Limit:
42291 Engr Units Offset: 0 the battery Analog Inputs
Only Upper Limit:
Display Value Size (bits): 16 voltage analog
Default input
Sign: U
Multiplier: Voltage level
kVAR Master Unit: VDC
.010000000000 commanded to
Load Control Read Lower Limit:
42292 Offset: 0 kVAR Master Analog Outputs
Output Only Upper Limit:
Size (bits): 16 load control
Predictor Value Default
Sign: S analog output

Multiplier: Voltage level


kW Master Unit: VDC
.010000000000 commanded to
Load Control Read Lower Limit:
42293 Offset: 0 kW Master load Analog Outputs
Output Only Upper Limit:
Size (bits): 16 control analog
Predictor Value Default
Sign: S output

Multiplier: Voltage level


Master Unit: VDC
.010000000000 commanded to
Frequency Read Lower Limit:
42294 Offset: 0 Master Analog Outputs
Bias Output Only Upper Limit:
Size (bits): 16 frequency bias
Predictor Value Default
Sign: S analog output

Multiplier: Voltage level


Unit: VDC
Master Voltage .010000000000 commanded to
Read Lower Limit:
42295 Bias Output Offset: 0 Master voltage Analog Outputs
Only Upper Limit:
Predictor Value Size (bits): 16 bias analog
Default: output
Sign: S
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 01 kW Read/ Offset: 0 Sets gen1 kW System
42305 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 1000.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 02 kW Read/ Offset: 0 Sets gen2 kW System
42306 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000

A029X159 (Issue 19) 477 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

Addr System Name Access Specifications Description Function


Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 03 kW Read/ Offset: 0 Sets gen3 kW System
42307 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 04 kW Read/ Offset: 0 Sets gen4 kW System
42308 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 05 kW Read/ Offset: 0 Sets gen5 kW System
42309 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 06 kW Read/ Offset: 0 Sets gen6 kW System
42310 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 07 kW Read/ Offset: 0 Sets gen7 kW System
42311 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 08 kW Read/ Offset: 0 Sets gen8 kW System
42312 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 09 kW Read/ Offset: 0 Sets gen9 kW System
42313 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 10 kW Read/ Offset: 0 Sets gen10 kW System
42314 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000

Copyright © 2017 Cummins Inc. 478 A029X159 (Issue 19)


8-2017 9. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 11 kW Read/ Offset: 0 Sets gen11 kW System
42315 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 12 kW Read/ Offset: 0 Sets gen12 kW System
42316 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Unit: seconds
Multiplier:
0.100000000000 Lower Limit: 0.000 Sets the
Programmed seconds
Read/ Offset: 0 programmed
42317 Transition PTC Timers
Write Upper Limit: 60 transition time
Delay (TDPT) Size (bits): 16
seconds delay
Sign: U
Default: 3.000
Unit: seconds
Multiplier:
0.100000000000 Lower Limit: 0.000
Transfer Delay Read/ seconds Sets the transfer
42318 Offset: 0 PTC Timers
(TDNE) Write Upper Limit: 120 time delay
Size (bits): 16
seconds
Sign: U
Default: 10.000
Unit: seconds
Multiplier:
0.100000000000 Lower Limit: 0.000
seconds Sets the
Retransfer Read/ Offset: 0
42319 retransfer time PTC Timers
Delay (TDEN) Write Upper Limit: 1800
Size (bits): 16 delay
seconds
Sign: U
Default: 600.000
Unit seconds
Multiplier: Sets the
0.000000000000 Lower Limit: 0.000
Maximum seconds maximum
Read/ Offset: 0
42320 Parallel Time parallel time for PTC Timers
Write Upper Limit: 1800
(TDMP) Size (bits): 16 soft load
seconds transfers
Sign: U
Default: 20.000

Multiplier: Unit: % Sets %kW


.010000000000 Lower Limit: –5.000 % generator set
Genset Bus Read/ Offset: 0 output level for Master Load
42321 Upper Limit: 105.000
%kW Setpoint Write open loop base Control
Size (bits): 16 % load extended
Sign: S Default: 80.000 paralleling
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 110.000
Genset Volts
Read/ Offset: 0 Generator set
42322 Nominal AC Setup
Write Upper Limit: nominal voltage
Voltage Size (bits): 16
45000.000 Volts
Sign: U
Default: 480.000

A029X159 (Issue 19) 479 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

Addr System Name Access Specifications Description Function


Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 110.000
Utility Nominal Read/ Volts Utility nominal
42323 Offset: 0 AC Setup
Voltage Write Upper Limit: voltage
Size (bits): 16
45000.000 Volts
Sign: U
Default: 480.000
Sets the center
Multiplier: frequency for
Unit: Hz
0.100000000000
Genset Center Read/ Lower Limit: 45.000 Hz the generator
42324 Offset: 0 set frequency PTC Sensors
Frequency Write Upper Limit: 65.000
Size (bits): 16 sensor
Default: 60.000 bandwidth
Sign: U
settings
Sets the center
Multiplier: frequency for
Unit: Hz
0.100000000000
Utility Center Read/ Lower Limit: 45.000 Hz the utility
42325 Offset: 0 frequency PTC Sensors
Frequency Write Upper Limit: 65.000 Hz sensor
Size (bits): 16
Default: 60.000 bandwidth
Sign: U
settings
Multiplier:
Unit: Hz Use to define
0.100000000000
System Read/ Lower Limit: 45.000 Hz the system System
42327 Offset: 0
Frequency Write Upper Limit: 65.000 Hz nominal Information
Size (bits): 16 frequency
Default: 60.000
Sign: U
Multiplier: Unit: kW Sets the base
1.000000000000 Lower Limit: 0.000 kW load kW setpoint
Genset Bus Read/ Offset: 0 Master Load
42330 Upper Limit: in closed loop
kW Setpoint Write Control
Size (bits): 16 32767.000 kW extended
Sign: S Default: 0.000 paralleling

Unit: kVAR Sets the base


Multiplier:
1.000000000000 Lower Limit: 0.000 load kVAR
Genset Bus Read/ kVAR setpoint in Master Load
42331 Offset: 0
kVAR Setpoint Write Upper Limit: 32767 closed loop Control
Size (bits): 16 extended
kVAR
Sign: S paralleling
Default: 0.000

Multiplier: Unit: % Sets %kVAR


.010000000000 Lower Limit: –5.000 % generator set
Genset Bus
Read/ Offset: 0 output level for Master Load
42332 %kVAR Upper Limit: 105.000
Write open loop base Control
Setpoint Size (bits): 16 % load extended
Sign: S Default: 0.000 paralleling

Multiplier: Sets the desired


Unit: generator set
Genset Bus .010000000000
Read/ Lower Limit: 0.700 bus power factor Master Load
42333 Power Factor Offset: 0
Write Upper Limit: 1.000 in closed loop Control
Setpoint Size (bits): 8
Default: 1.000 extended
Sign: S paralleling

Copyright © 2017 Cummins Inc. 480 A029X159 (Issue 19)


8-2017 9. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function

Multiplier: Unit: kW
Genset 1.000000000000 Lower Limit: Setpoint for
Read/ Offset: 0 Master Load
42334 Unloaded -32768.000 kW generator set
Write Control
Level Size (bits): 16 Upper Limit: 32767 kW unloaded level
Sign: S Default: 50.000

Multiplier: Unit: kW Sets the peak


1.000000000000 Lower Limit: shave kW
Utility Bus kW Read/ Offset: 0 -32768.000 kW setpoint in Master Load
42337
Setpoint Write closed loop Control
Size (bits): 16 Upper Limit: 32767 kW extended
Sign: S Default: 100.000 paralleling
Unit: kW
Multiplier: Sets the utility
1.000000000000 Lower Limit:
Utility Bus kW kW constraint
Read/ Offset: 0 –32768.000 kW Master Load
42338 Constraint level for base
Write Upper Limit: Control
Level Size (bits): 16 load extended
32767.000 kW paralleling
Sign: S
Default: 100.000
Unit: kVAR Sets the peak
Multiplier:
1.000000000000 Lower Limit: shave kVAR
Utility Bus Read/ 32768.000 kVAR setpoint in Master Load
42339 Offset: 0
kVAR Setpoint Write Upper Limit: closed loop Control
Size (bits): 16 extended
32767.000 kVAR
Sign: S paralleling
Default: 100.000
Multiplier: Sets the desired
Unit:
Utility Bus .010000000000 utility bus power
Read/ Lower Limit: 0.700 Master Load
42340 Power Factor Offset: 0 factor in closed
Write Upper Limit: 1.000 Control
Setpoint Size (bits): 8 loop extended
Default: 1.000 paralleling
Sign: S
Unit: kW
Multiplier:
1.000000000000 Lower Limit:
Utility –32768.000 kW Setpoint for
Read/ Offset: 0 Master Load
42341 Unloaded utility unloaded
Write Upper Limit: Control
Level Size (bits): 16 level
32767.000 kVAR
Sign: S
Default: 50.000
Unit: seconds
Multiplier:
.100000000000 Lower Limit: 10.000 Sets ramp load
Extended seconds
Read/ Offset: 0 time for Master Load
42348 Parallel Ramp
Write Upper Limit: 900.000 extended Control
Load Time Size (bits): 16
seconds paralleling
Sign: U
Default: 60.000
Unit: seconds
Multiplier:
.200000000000 Lower Limit: 10.000 Sets the fail to
Fail To seconds
Read/ Offset: 0 synchronize Master Sync
42351 Synchronize
Write Upper Limit: 900.000 diagnostic time Control
Time Size (bits):16
seconds delay
Sign: U
Default: 120.000

A029X159 (Issue 19) 481 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

Addr System Name Access Specifications Description Function


Multiplier: Sets the
Unit: Hz
.00100000000 synchronizer slip
Read/ Lower Limit: –3.000 Hz Master Sync
42354 Slip Frequency Offset: 0 frequency (used
Write Upper Limit: 3.000 Hz Control
Size (bits):16 when sync
Default: 0.100 method is slip)
Sign: S
Unit: seconds
Multiplier:
.10000000000 Lower Limit: 0.000
seconds Sets the
Start Time Read/ Offset: 0 PTC Operating
42355 generator sets
Delay (TDES) Write Upper Limit: 3600.000 Mode
Size (bits):16 start time delay
seconds
Sign: U
Default: 0.000
Unit: seconds
Multiplier:
.100000000000 Lower Limit: 0.000
seconds Sets the
Stop Time Read/ Offset: 0 PTC Operating
42356 generator sets
Delay (TDEC) Write Upper Limit: 3600.000 Mode
Size (bits):16 stop time delay
seconds
Sign: U
Default: 0.000
Unit: seconds Indicates delay
Multiplier:
1.000000000000 Lower Limit: 0.000 between add
Genset Bus seconds
Read/ Offset: 0 levels when all Load Add Shed
42364 Load Add
Write Upper Limit: 60.000 generator sets Control
Delay Size (bits): 16
seconds are online and
Sign: U no utility
Default: 1.000
Unit: seconds
Multiplier:
1.000000000000 Lower Limit: 0.000 Indicates delay
Utility Bus seconds
Read/ Offset: 0 between add Load Add Shed
42365 Load Add
Write Upper Limit: 60.000 levels when on Control
Delay Size (bits): 16
seconds utility
Sign: U
Default: 1.000
Unit: seconds
Multiplier: Lower Limit: 1.000
.100000000000 seconds Indicates delay
Load Shed Read/ Offset: 0 between shed Load Add Shed
42366 Upper Limit: 10.000
Delay Write levels when on Control
Size (bits): 8 seconds
generator sets
Sign: U Default: 1.000

Multiplier:
Unit:
1.000000000000 Indicates which
Load 1 Add Read/ Lower Limit: 1.000 Load Add Shed
42373 Offset: 0 add level load 1
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 1.000
Sign: U

Copyright © 2017 Cummins Inc. 482 A029X159 (Issue 19)


8-2017 9. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier:
Unit:
1.000000000000 Indicates which
Load 2 Add Read/ Lower Limit: 1.000 Load Add Shed
42374 Offset: 0 add level load 2
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 2.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 3 Add Read/ Lower Limit: 1.000 Load Add Shed
42375 Offset: 0 add level load 3
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 3.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 4 Add Read/ Lower Limit: 1.000 Load Add Shed
42376 Offset: 0 add level load 4
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 4.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 5 Add Read/ Lower Limit: 1.000 Load Add Shed
42377 Offset: 0 add level load 5
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 5.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 6 Add Read/ Lower Limit: 1.000 Load Add Shed
42378 Offset: 0 add level load 6
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 6.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 1 Shed Read/ Lower Limit: 0.000 Load Add Shed
42379 Offset: 0 shed level load
Level Write Upper Limit: 5.000 Control
Size (bits): 8 1 is assigned to
Default: 0.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 2 Shed Read/ Lower Limit: 0.000 Load Add Shed
42380 Offset: 0 shed level load
Level Write Upper Limit: 5.000 Control
Size (bits): 8 2 is assigned to
Default: 5.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 3 Shed Read/ Lower Limit: 0.000 Load Add Shed
42381 Offset: 0 shed level load
Level Write Upper Limit: 5.000 Control
Size (bits): 8 3 is assigned to
Default: 4.000
Sign: U

A029X159 (Issue 19) 483 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

Addr System Name Access Specifications Description Function


Multiplier:
Unit:
1.000000000000 Indicates which
Load 4 Shed Read/ Lower Limit: 0.000 Load Add Shed
42382 Offset: 0 shed level load
Level Write Upper Limit: 5.000 Control
Size (bits): 8 4 is assigned to
Default: 3.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 5 Shed Read/ Lower Limit: 0.000 Load Add Shed
42383 Offset: 0 shed level load
Level Write Upper Limit: 5.000 Control
Size (bits): 8 5 is assigned to
Default: 2.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 6 Shed Read/ Lower Limit: 0.000 Load Add Shed
42384 Offset: 0 shed level load
Level Write Upper Limit: 5.000 Control
Size (bits): 8 6 is assigned to
Default: 1.000
Sign: U
Multiplier: Unit: % Use to set the
Genset Bus 1.000000000000 Lower Limit: 80.000 % %kW threshold
Read/ Offset: 0 System
42386 %kW Overload Upper Limit: 140.000 for gen bus
Write Information
Threshold Size (bits): 8 % overload
Sign: U Default: 105.000 condition

Unit: second
Multiplier:
1.000000000000 Lower Limit: 0.000
Genset Bus second Sets the delay
Read/ Offset: 0 System
42387 kW Overload time for overload
Write Upper Limit: 120.000 Information
Delay Size (bits): 8 based on kW
second
Sign: U
Default: 60.000

Multiplier: Use to set the


Genset Bus Unit: Hz underfrequency
.100000000000
Underfrequenc Read/ Lower Limit: 0.100 Hz offset threshold System
42388 Offset: 0
y Overload Write Upper Limit: 10.000 Hz for gen bus Information
Threshold Size (bits): 16 overload
Default: 3.000
Sign: U condition
Multiplier:
Genset Bus Unit: second Sets the delay
1.000000000000
Underfrequenc Read/ Lower Limit: 0.000 Hz time for overload System
42389 Offset: 0
y Overload Write Upper Limit: 20.000 Hz based on Information
Delay Size (bits): 8 frequency
Default: 3.000
Sign: U
Unit: minute
Multiplier: Sets the initial
1.000000000000 Lower Limit: 1.000
minute delay time
Load Demand Read/ Offset: 0 Load Demand
42395 before load
Initial Delay Write Upper Limit: 60.000 Control
Size (bits): 8 demand will
minute operate
Sign: U
Default: 5.000

Copyright © 2017 Cummins Inc. 484 A029X159 (Issue 19)


8-2017 9. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function

Multiplier: Sets the load


Unit: % demand restart
Load Demand 1.000000000000
Read/ Lower Limit: 20 % threshold (make Load Demand
42396 Restart Offset: 0
Write Upper Limit: 100 % larger than Control
Percent Size (bits): 8
Default: 80.000 shutdown
Sign: U percent)

Multiplier: Unit: Hours Sets run hours


1.000000000000 Lower Limit: 1.000 differential for
Load Demand
Read/ Offset: 0 Hours restarting a Load Demand
42397 Run Hours
Write generator set Control
Differential Size (bits): 16 Upper Limit: 500 Hours stopped due to
Sign: S Default: 50.000 load demand
Unit: minute Sets the delay
Multiplier:
1.000000000000 Lower Limit: 1.000 time between
Load Demand minute
Read/ Offset: 0 stopping Load Demand
42398 Shutdown
Write Upper Limit: 60.000 generator sets Control
Delay Size (bits): 8
minute due to load
Sign: U demand
Default: 5.000

Multiplier: Sets the load


Unit: % demand
Load Demand 1.000000000000
Read/ Lower Limit: 20 % shutdown Load Demand
42399 Shutdown Offset: 0
Write Upper Limit: 100 % threshold (make Control
Percent Size (bits): 8
Default: 60.000 smaller than
Sign: U restart percent)
Unit: seconds Sets how long to
Multiplier:
1.000000000000 Lower Limit: 10.000 wait for a
Genset Fail Read/ seconds generator set to Load Demand
42400 Offset: 0
Time Delay Write Upper Limit: 900.000 come online Control
Size (bits): 16 before declaring
seconds
Sign: U it failed
Default: 60.000
Unit: seconds
Multiplier:
.020000000000 Lower Limit: 0.100
seconds Sets the utility
Util CB Fail to Read/ Offset: 0
42401 breaker fail to Breaker Control
Close Delay Write Upper Limit: 1.000
Size (bits): 16 close time delay
seconds
Sign: U
Default: 0.26
Unit: seconds
Multiplier:
.200000000000 Lower Limit: 0.200
seconds Sets the utility
Util CB Fail to Read/ Offset: 0
42402 breaker fail to Breaker Control
Open Delay Write Upper Limit: 5.000
Size (bits): 8 open time delay
seconds
Sign: U
Default: 1

A029X159 (Issue 19) 485 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

Addr System Name Access Specifications Description Function


Unit: seconds
Multiplier:
.020000000000 Lower Limit: 0.000 Sets the time to
Util CB seconds
Read/ Offset: 0 allow for utility
42403 Recharge Breaker Control
Write Upper Limit: 60 breaker
Delay Size (bits): 16
seconds recharge
Sign: U
Default: 10.000
Unit: seconds
Multiplier:
.020000000000 Lower Limit: 0.100 Sets the
Gen CB Fail to Read/ seconds generator set
42404 Offset: 0 Breaker Control
Close Delay Write Upper Limit: 1.000 breaker fail to
Size (bits): 16 close time delay
seconds
Sign: U
Default: 0.260
Unit: seconds
Multiplier:
0.200000000000 Lower Limit: 0.200 Sets the
Gen CB Fail to Read/ seconds generator set
42405 Offset: 0 Breaker Control
Open Delay Write Upper Limit: 5.000 breaker fail to
Size (bits): 8 open time delay
seconds
Sign: U
Default: 1.000
Unit: seconds
Multiplier: Sets the time to
.020000000000 Lower Limit: 0.000
Gen CB seconds allow for
Read/ Offset: 0
42406 Recharge generator set Breaker Control
Write Upper Limit: 60.000
Delay Size (bits): 16 breaker
seconds recharge
Sign: U
Default: 10.000
Unit: degrees Sets the
Multiplier:
0.01000000000 Lower Limit: 0.100 permissive +/-
Permissive Read/ degrees phase angle Master Sync
42407 0Offset: 0
Phase Window Write Upper Limit: 20.000 window for the Control
Size (bits): 16 sync check
degrees
Sign: S function
Default: 10.000
Sets the
Multiplier: permissive +/-
Unit: %
Permissive .100000000000 voltage
Read/ Lower Limit: 0.5000 % Master Sync
42408 Voltage Offset: 0 acceptance
Write Upper Limit: 10.000 % Control
Window Size (bits): 16 window for the
Default: 5.000 sync check
Sign: U
function
Unit: seconds Sets the
Multiplier:
.020000000000 Lower Limit: 0.500 permissive
Permissive Read/ seconds acceptance Master Sync
42409 Offset: 0
Window Time Write Upper Limit: 5.000 window dwell Control
Size (bits): 16 time for the sync
seconds
Sign: U check function
Default: 0.500

Copyright © 2017 Cummins Inc. 486 A029X159 (Issue 19)


8-2017 9. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function

Multiplier: Sets the


Unit: Hz maximum
Permissive .001000000000
Read/ Lower Limit: 0.001 Hz frequency Master Sync
42410 Frequency Offset: 0
Write Upper Limit: 1.000 Hz difference Control
Window Size (bits): 32
Default: 1.000 allowed for
Sign: U permissive close
Unit: degrees Sets a sync
Multiplier:
0.010000000000 Lower Limit: –50.000 phase offset to
Sync Phase Read/ degrees accommodate Master Sync
42412 Offset: 0
Offset Write Upper Limit: 50.000 sync across Control
Size (bits): 16 transformer with
degrees
Sign: S phase shift
Default: 0.000

Multiplier: Proportional
Unit: gain for kW
1.000000000000
Read/ Lower Limit: 0.000 closed loop Master Load
42414 kW Kp Offset: 0
Write Upper Limit: 1000.000 control in Control
Size (bits): 16 extended
Default: 60.000
Sign: U paralleling
Multiplier: Integral gain for
Unit:
1.000000000000 kW closed loop
Read/ Lower Limit: 0.000 Master Load
42415 kW KI Offset: 0 control in
Write Upper Limit: 255.000 Control
Size (bits): 8 extended
Default: 60.000 paralleling
Sign: U

Multiplier: Proportional
Unit: gain for kVAR
1.000000000000
Read/ Lower Limit: 0.000 closed loop Master Load
42416 kVAR Kp Offset: 0
Write Upper Limit: 1000.000 control in Control
Size (bits): 16 extended
Default: 120.000
Sign: U paralleling
Multiplier: Integral gain for
Unit:
1.000000000000 kVAR closed
Read/ Lower Limit: 0.000 Master Load
42417 kVAR KI Offset: 0 loop control in
Write Upper Limit: 255.000 Control
Size (bits): 8 extended
Default: 50.000 paralleling
Sign: U
Multiplier:
Unit: Selects which
1.000000000000
Scheduler Read/ Lower Limit: 1.000 scheduler System
42418 Offset: 0
Program Select Write Upper Limit: 12.000 program to view Scheduler
Size (bits): 8 or edit
Default: 1.000
Sign: U
Unit: hour
Multiplier:
1.000000000000 Lower Limit: 0.000 Use to adjust
Scheduler hour
Read/ Offset: 0 start hour for the System
42423 Program x
Write Upper Limit: 23.000 selected Scheduler
Start Hour Size (bits): 8
hour program
Sign: U
Default: 0.000

A029X159 (Issue 19) 487 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

Addr System Name Access Specifications Description Function


Unit: minute
Multiplier:
1.000000000000 Lower Limit: 0.000 Use to adjust
Scheduler minute
Read/ Offset: 0 start minute for System
42424 Program x
Write Upper Limit: 59.000 the selected Scheduler
Start Minute Size (bits): 8
minute program
Sign: U
Default: 0.000
Unit: hour
Multiplier:
1.000000000000 Lower Limit: 0.000 Use to adjust
Scheduler hour
Read/ Offset: 0 duration hours System
42425 Program x
Write Upper Limit: 23.000 for the selected Scheduler
Duration Hours Size (bits): 8
hour program
Sign: U
Default: 0.000
Unit: minute
Multiplier:
Scheduler 1.000000000000 Lower Limit: 0.000 Use to adjust
Program x Read / minute duration minutes System
42426 Offset: 0
Duration Write Upper Limit: 59.000 for the selected Scheduler
Minutes Size (bits): 8 program
minute
Sign: U
Default: 0.000
Multiplier:
Unit: Selects which
Scheduler 1.000000000000
Read/ Lower Limit: 1.000 scheduler System
42427 Exception Offset: 0
Write Upper Limit: 6.000 exception to Scheduler
Select Size (bits): 8
Default: 1.000 view or edit
Sign: U
Unit: month
Multiplier:
1.000000000000 Lower Limit: 1.000 Use to adjust
Scheduler month
Read/ Offset: 0 the month of the System
42430 Exception x
Write Upper Limit: 12.000 selected Scheduler
Month Size (bits): 8
month exception
Sign: U
Default: 1.000
Unit: date
Multiplier:
1.000000000000 Lower Limit: 1.000 Use to adjust
Scheduler date
Read/ Offset: 0 the date of the System
42431 Exception x
Write Upper Limit: 31.000 selected Scheduler
Date Size (bits): 8
date exception
Sign: U
Default: 1.000
Unit: hour
Multiplier:
1.000000000000 Lower Limit: 0.000 Use to adjust
Scheduler hour
Read/ Offset: 0 the start hour of System
42432 Exception x
Write Upper Limit: 23.000 the selected Scheduler
Hour Size (bits):8
hour exception
Sign: U
Default: 0.000

Copyright © 2017 Cummins Inc. 488 A029X159 (Issue 19)


8-2017 9. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Unit: minute
Multiplier:
1.000000000000 Lower Limit: 0.000 Use to adjust
Scheduler minute
Read/ Offset: 0 the start minute System
42433 Exception x
Write Upper Limit: 59.000 of the selected Scheduler
Minute Size (bits): 8
minute exception
Sign: U
Default: 0.000
Unit: days
Multiplier: Use to adjust
1.000000000000 Lower Limit: 0.000
Scheduler days the duration
Read/ Offset: 0 System
42434 Exception x days of the
Write Upper Limit: 44.000 Scheduler
Duration Days Size (bits): 8 selected
days exception
Sign: U
Default: 0.000
Multiplier: Unit: hour Use to adjust
Scheduler 1.000000000000 Lower Limit: 0.000 the duration
Read/ Offset: 0 hour System
42435 Exception x hours of the
Write Scheduler
Duration Hours Size (bits): 8 Upper Limit: 23 hour selected
Sign: U Default: 0.000 exception

Unit: minute
Multiplier: Use to adjust
Scheduler 1.000000000000 Lower Limit: 0.000
minute the duration
Exception x Read/ Offset: 0 System
42436 minutes of the
Duration Write Upper Limit: 59.000 Scheduler
Size (bits): 8 selected
Minutes minute
Sign: U exception
Default: 0.000
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 110.000
Genset PT Volts Generator Set
Read/ Offset: 0
42440 Primary PT primary AC Setup
Write Upper Limit:
Voltage Size (bits): 16 voltage
45000.000 Volts
Sign: U
Default: 480
Multiplier: Unit: Volts
Genset PT 1.000000000000 Lower Limit: 110.000 Generator set
Read/ Offset: 0
42441 Secondary Volts Upper Limit: 500 PT secondary AC Setup
Write
Voltage Size (bits): 16 Volts voltage
Sign: U Default: 120

Unit: Amp
Multiplier:
1.000000000000 Lower Limit: 5.000
Genset CT Amp Generator set
Read/ Offset: 0
42442 Primary CT primary AC Setup
Write Upper Limit:
Current Size (bits): 16 current
10000.000 Amp
Sign: U
Default: 100
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 110.000
Utility PT Volts
Read/ Offset: 0 Utility PT
42445 Primary AC Setup
Write Upper Limit: primary voltage
Voltage Size (bits): 16
45000.000 Volts
Sign: U
Default: 480

A029X159 (Issue 19) 489 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

Addr System Name Access Specifications Description Function


Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 110.000
Utility PT Volts Utility PT
Read/ Offset: 0
42446 Secondary secondary AC Setup
Write Upper Limit: 500.000
Voltage Size (bits): 16 voltage
Volts
Sign: U
Default: 120
Unit: Amps
Multiplier:
1.000000000000 Lower Limit: 5.000
Utility CT Amps
Read/ Offset: 0 Utility primary
42447 Primary AC Setup
Write Upper Limit: 10000.00 current
Current Size (bits): 16
Amps
Sign: U
Default: 100

Multiplier: Unit: kW Generator set


Load Add Shed 1.000000000000 Lower Limit: 0.000 kW kW capacity that
Required Read/ Offset: 0 must be online Load Add Shed
42449 Upper Limit:
Online Write to start timed Control
Capacity Size (bits): 16 32000.000 kW load add; 0
Sign: S Default: 0 disables this
Multiplier: Unit: kW Sets how much
Load Demand 1.000000000000 Lower Limit: 0.000 kW capacity must
Minimum Read/ Offset: 0 Load Demand
42450 Upper Limit: always be online
Online Write Control
Size (bits): 16 32767.000 kW regardless of
Capacity
Sign: S Default: 0 what the load is

Unit: seconds Sets generator


Multiplier:
0.100000000000 Lower Limit: 0.000 restart delay
Load Demand Read/ seconds time to avoid Load Demand
42451 Offset: 0
Restart Delay Write Upper Limit: 25.000 nuisance Control
Size (bits): 8 restarts due to
seconds
Sign: U load transients
Default: 1
Unit: Amps
Multiplier:
1.000000000000 Lower Limit: 1.000
Utility Available Read/ Amps
42452 Offset: 0 barograph AC Setup
Current Write Upper Limit:
Size (bits): 16
32000.000 Amps
Sign: U
Default: 1000
Multiplier: Unit: kW Use to set how
1.000000000000 Lower Limit: 1.000 kW kW = 100%
Total Utility Read/ Offset: 0
42453 Upper Limit: 32000.00 utility kW -- AC Setup
Capacity Write
Size (bits): 16 kW Used by
Sign: S Default: 1000 barograph

Unit: VDC
Multiplier:
0.010000000000 Lower Limit: 28.000
24 V High VDC Sets 24V high
Read/ Offset: 0 Battery Voltage
42455 Battery Voltage battery voltage
Write Upper Limit: 34.000 Protection
Threshold Size (bits): 16 fault threshold
VDC
Sign: U
Default: 32

Copyright © 2017 Cummins Inc. 490 A029X159 (Issue 19)


8-2017 9. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Unit: VDC
Multiplier:
0.010000000000 Lower Limit: 22.000
24 V Low VDC Sets 24V low
Read/ Offset: 0 Battery Voltage
42456 Battery Voltage battery voltage
Write Upper Limit: 26.000 Protection
Threshold Size (bits): 16 fault threshold
VDC
Sign: U
Default: 24
Unit: VDC
Multiplier:
0.010000000000 Lower Limit: 14.000
12 V High VDC Sets 12V high
Read/ Offset: 0 Battery Voltage
42457 Battery Voltage battery voltage
Write Upper Limit: 17.000 Protection
Threshold Size (bits): 16 fault threshold
VDC
Sign: U
Default: 16
Unit: VDC
Multiplier: Lower Limit: 11.000
12 V Low 0.010000000000 VDC Sets 12V low
Read/ Offset: 0 Battery Voltage
42458 Battery Voltage Upper Limit: 13.000 battery voltage
Write Protection
Threshold Size (bits): 16 VDC fault threshold
Sign: U Default: 12

Multiplier:
Unit: second
High Battery 1.000000000000
Read/ Lower Limit: 2 second Sets high Battery Voltage
42459 Voltage Set Offset: 0 battery voltage
Write Upper Limit: 60 second set time Protection
time Size (bits): 8
Default: 60
Sign: U
Multiplier:
Unit: second
Low Battery 1.000000000000
Read/ Lower Limit: 2 second Sets low battery Battery Voltage
42460 Voltage Set Offset: 0
Write Upper Limit: 60 second voltage set time Protection
Time Size (bits): 8
Default: 60
Sign: U

Multiplier: Unit: kW Sets the online


Genset Online 1.000000000000 Lower Limit: 0.000 kW kW threshold at
Capacity Read/ Offset: 0 which generator
42462 Upper Limit: PTC Sensors
Sensor Write set bus is
Threshold Size (bits): 16 32000.000 kW available for
Sign: S Default: 0 loading
Multiplier:
Unit: Bitmapped state
1.000000000000
Fault Status Read Lower Limit: of utility and Fault and Event
42500 Offset: 0
BitMap 1 Only Upper Limit: other faults - 32 Info
Size (bits): 32 bits
Default:
Sign: U
Multiplier:
Unit: Bitmapped state
1.000000000000
Fault Status Read Lower Limit: of generator set Fault and Event
42502 Offset: 0
BitMap 2 Only Upper Limit: and other faults Info
Size (bits): 32 - 32 bits
Default:
Sign: U

A029X159 (Issue 19) 491 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

Addr System Name Access Specifications Description Function


Multiplier:
Unit:
1.000000000000 Bitmapped state
Event Status Read Lower Limit: Fault and Event
42505 Offset: 0 of events - 32
BitMap 1 Only Upper Limit: Info
Size (bits): 32 bits
Default:
Sign: U

Multiplier: Bitmapped word


Unit: with status of
Genset 1.000000000000
Read Lower Limit: generator set AC Interrupt
42506 Metering Fault Offset: 0
Only Upper Limit: AC metering out Service
Status Size (bits): 16
Default: of range
Sign: U conditions
Multiplier: Bitmapped word
Unit:
1.000000000000 with status of
Utility Metering Read Lower Limit: AC Interrupt
42507 Offset: 0 utility AC
Fault Status Only Upper Limit: Service
Size (bits): 16 metering out of
Default: range conditions
Sign: U
Unit: Hours
Multiplier:
0.000277778 Lower Limit: 0.000
Gen1 Online Read Hours Total online time System
42704 Offset: 0
Time Only Upper Limit: for Gen1 Information
Size (bits): 32
1193046.000 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
0.000277778 Lower Limit: 0.000
Gen2 Online Read Hours Total online time System
42706 Offset: 0
Time Only Upper Limit: for Gen2 Information
Size (bits): 32
1193046.000 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
0.000277778 Lower Limit: 0.000
Gen3 Online Read Hours Total online time System
42708 Offset: 0
Time Only Upper Limit: for Gen3 Information
Size (bits): 32
1193046.000 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
0.000277778 Lower Limit: 0.000
Gen4 Online Read Hours Total online time System
42710 Offset: 0
Time Only Upper Limit: for Gen4 Information
Size (bits): 32
1193046.000 Hours
Sign: U
Default: 0

Multiplier: Indicates how


Unit: many of the
Total Number 1.000000000000
Read Lower Limit: defined Gen1 System
42717 of Gensets Offset: 0
Only Upper Limit: thru Gen4 Information
Online Size (bits): 8
Default: generator sets
Sign: U are online

Copyright © 2017 Cummins Inc. 492 A029X159 (Issue 19)


8-2017 9. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function

Multiplier: Difference
Unit: kW between online
Total Spare 1.000000000000
Read Lower Limit: capacity (4 System
42718 Online Offset: 0
Only Upper Limit: generator sets) Information
Capacity Size (bits): 16
Default: and Genset Bus
Sign: S Total kW

Multiplier: Indicates kW
Unit: kW threshold for
Next Gen 1.000000000000
Read Lower Limit: gen bus at Load Demand
42719 Restart Offset: 0
Only Upper Limit: which the next Control
Threshold Size (bits): 16
Default: generator set
Sign: S will restart
Indicates kW
Multiplier: threshold for
Unit: kW
Next Gen 1.000000000000 gen bus at
Read Lower Limit: Load Demand
42720 Shutdown Offset: 0 which the next
Only Upper Limit: Control
Threshold Size (bits): 16 generator set
Default: will load demand
Sign: S
stop

Multiplier: Calculated kW
Unit: kW overload
Genset Bus 1.000000000000
Read Lower Limit: threshold based System
42727 kW Overload Offset: 0
Only Upper Limit: on online Information
Threshold Size (bits): 16
Default: capacity and %
Sign: S setting
Multiplier:
Unit:
Modbus Bus 1.000000000000
Read Lower Limit: Modbus bus
42732 Message Offset: 0 Communications
Only Upper Limit: message count
Count Size (bits): 16
Default:
Sign: U
Multiplier:
Unit:
1.000000000000
Modbus CRC Read Lower Limit: Modbus CRC
42733 Offset: 0 Communications
Error Count Only Upper Limit: error count
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit:
Modbus 1.000000000000
Read Lower Limit: Modbus
42734 Exception Offset: 0 Communications
Only Upper Limit: exception count
Count Size (bits): 16
Default:
Sign: U
Multiplier:
Unit:
Modbus No 1.000000000000
Read Lower Limit: Modbus no
42735 Response Offset: 0 Communications
Only Upper Limit: response count
Count Size (bits): 16
Default:
Sign: U

A029X159 (Issue 19) 493 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

Addr System Name Access Specifications Description Function


Multiplier:
Unit:
Modbus Slave 1.000000000000
Read Lower Limit: Modbus slave
42736 Message Offset: 0 Communications
Only Upper Limit: message count
Count Size (bits): 16
Default:
Sign: U
Multiplier: Unit: year
1.000000000000 Lower Limit: .000 year Use to set or
Read/ Offset: 0
42739 Clock Year Upper Limit: 99.000 read current Real Time Clock
Write
Size (bits): 8 year year
Sign: U Default:
Unit: month
Multiplier:
1.000000000000 Lower Limit: 1.000
month Use to set or
Read/ Offset: 0
42740 Clock Month read current Real Time Clock
Write Upper Limit: 12.000
Size (bits): 8 month
month
Sign: U
Default:
Unit: date
Multiplier:
1.000000000000 Lower Limit: 1.000
date Use to set or
Read/ Offset: 0
42741 Clock Date read current Real Time Clock
Write Upper Limit: 31.000
Size (bits): 8 date
date
Sign: U
Default:
Multiplier: Unit: hour
1.000000000000 Lower Limit: .000 hour Use to set or
Read/ Offset: 0
42742 Clock Hour Upper Limit: 23.000 read current Real Time Clock
Write
Size (bits): 8 hour hour
Sign: U Default:
Unit: minute
Multiplier:
1.000000000000 Lower Limit: .000
minute Use to set or
Read/ Offset: 0
42743 Clock Minute read current Real Time Clock
Write Upper Limit: 59.000
Size (bits): 8 minute
minute
Sign: U
Default:
Unit: seconds
Multiplier:
1.000000000000 Lower Limit: .000
seconds Use to set or
Read/ Offset: 0
42744 Clock Second read current Real Time Clock
Write Upper Limit: 59.000
Size (bits): 8 seconds
seconds
Sign: U
Default:
Multiplier:
Unit: seconds Countdown
0.100000000000
Read Lower Limit: timer value for PTC Operating
42746 Start Timer Offset: 0
Only Upper Limit: generator set Mode
Size (bits): 16 start timer
Default:
Sign: U

Copyright © 2017 Cummins Inc. 494 A029X159 (Issue 19)


8-2017 9. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier:
Unit: seconds Countdown
.100000000000
Read Lower Limit: timer value for PTC Operating
42747 Stop Timer Offset: 0
Only Upper Limit: generator set Mode
Size (bits): 16 stop timer
Default:
Sign: U
Multiplier:
Unit: VDC Battery voltage
Low Battery 0.010000000000
Read Lower Limit: with respect to Battery Voltage
42748 Voltage Offset: 0
Only Upper Limit: the set low Protection
Threshold Size (bits): 16
Default: battery threshold
Sign: U
Multiplier:
Unit: VDC Battery voltage
High Battery 0.010000000000
Read Lower Limit: with respect to Battery Voltage
42749 Voltage Offset: 0
Only Upper Limit: set high battery Protection
Threshold Size (bits): 16
Default: threshold
Sign: U

A029X159 (Issue 19) 495 Copyright © 2017 Cummins Inc.


9. DMC 1000 Modbus Parametric Data 8-2017

This page is intentionally blank.

Copyright © 2017 Cummins Inc. 496 A029X159 (Issue 19)


10 DMC 1000 Modbus Enumerated Data
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

Addr. System Name Access Specifications Description Function


Save
configuration
parameters or
adjustments to
non-volatile
memory.
0: Do Nothing Perform Save
Save Read / Size (bits): 8 Controller
42004 1: Save Trims Trims after all
Adjustments Write Number of Fields: 2 Information
Default: Do Nothing configurations
have been
updated. Do
not save trims
unless a
change has
occurred.
0: Time Delay Start
1: Time Delay Stop Indicates state
Genset Run Size (bits): 8
Read of the PTC Operating
42011 Sequence 2: Stop
Only Number of Fields: 4 generator set Mode
State 3: Run run sequence
Default:
0: Unavailable Energization
Genset Bus Read Size (bits): 8 1: Dead status of the
42017 PTC Sensors
Status Only Number of Fields: 3 2: Live generator set
Default: bus

0: Unavailable
Size (bits): 8 1: Dead Energization
Utility Bus Read
42117 status of the PTC Sensors
Status Only Number of Fields: 3 2: Live utility bus
Default:
0: Not Available
Size (bits): 8 1: Not Unloaded Indicates utility
Utility Unload Read Master Load
42208 unloaded
Status Only Number of Fields: 3 2: Unloaded Control
status
Default:

A029X159 (Issue 19) 497 Copyright © 2017 Cummins Inc.


10. DMC 1000 Modbus Enumerated Data 8-2017

Addr. System Name Access Specifications Description Function


0: Not Available Indicates
Genset Unload Read Size (bits): 8 1: Not Unloaded generator set Master Load
42209
Status Only Number of Fields: 3 2: Unloaded unloaded Control
Default: status

0: Not Available
1: TD Start
2: TD Stop
3: TD Programmed
Transition
4: TD Transfer
5: TD Retransfer
6: Synchronizing
7: Sync Check OK Indicates what
Size (bits): 8 8: Inhibit
Read / state the System
42210 System State Number of Fields:
Write 9: Unassigned control is Information
18 currently in
10: Ramp Unload
11: Ramp Load
12: Manual
13: Utility Failure
14: Test
15: Standby
16: Factory Test
17: Extended Parallel
Default: Not Available
0: Manual
Size (bits): 8 1: Normal Indicates the
Number of Fields: 6 2: Normal Override current PTC
PTC Operating Read operating PTC Operating
42211 3: Test
Mode Only mode. Mode
4: Utility Fail Read/Write in
5: Extended Parallel Comp mode
Default:
Indicates
0: Not Available availability of
Genset Size (bits): 8 1: Available generator set
Read
42216 Availability for loading as Availability
Only Number of Fields: 3 2: Unknown
Status determined by
Default: generator set
sensors
Indicates
0: Not Available availability of
Utility Size (bits): 8 1: Available
Read utility for
42217 Availability Availability
Only Number of Fields: 3 2: Unknown loading as
Status
Default: determined by
utility sensors

Copyright © 2017 Cummins Inc. 498 A029X159 (Issue 19)


8-2017 10. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function


Size (bits): 8
0: Open
Number of Fields: 3 Generator set
Gen CB Read 1: Closed
42218 breaker Breaker Control
Position Status Only 2: Not Available position
Default:

Size (bits): 8
Number of Fields: 3 0: Open
Util CB Read 1: Closed Utility breaker
42219 Breaker Control
Position Status Only 2: Not Available position
Default:

0: Not Enabled
Indicates the
1: No Source connected
Connected state of the
Read Size (bits): 8 PTC State
42224 PTC State 2: Utility Connected power transfer
Only Number of Fields: 5 Machine
3: Genset Connected control
4: Paralleled Read/Write in
Comp.
Default:
Size (bits):8 Indicates
Number of Fields: 2 0: Not Allowed whether any
Sync Check Read Master Sync
42225 1: Allowed sync check
Close Allowed Only Control
Default: conditions for
have been met

Size (bits): 8
0: Synchronizer Off Indicates state
Synchronizer Read Number of Fields: 2 Master Sync
42227 1: Synchronizer On of the
Status Only Control
Default: synchronizer

Size (bits): 8 Faults have


Number of Fields: 2 0: Inactive occurred which
System Read prevent normal System
42228 1: Active
Lockout Status Only system Information
Default: operation;
reset faults
Size (bits): 8
0: Open
Number of Fields: 3 Indicates
Breaker 1 Read 1: Closed Load Add Shed
42229 position status
Position Only 2: Not Available Control
of breaker 1
Default: Not Available

0: Open
Size (bits): 8 Indicates
Breaker 2 Read 1: Closed Load Add Shed
42230 Number of Fields: 3 position status
Position Only 2: Not Available Control
of breaker 2
Default: Not Available

A029X159 (Issue 19) 499 Copyright © 2017 Cummins Inc.


10. DMC 1000 Modbus Enumerated Data 8-2017

Addr. System Name Access Specifications Description Function


0: Open
Size (bits): 8 1: Closed Indicates
Breaker 3 Read Load Add Shed
42231 position status
Position Only Number of Fields: 3 2: Not Available Control
of breaker 3
Default: Not Available
Size (bits): 8 0: Open
Number of Fields: 3 1: Closed Indicates
Breaker 4 Read Load Add Shed
42232 2: Not Available position status
Position Only Control
Default: Not Available of breaker 4

0: Open
Size (bits): 8 1: Closed Indicates
Breaker 5 Read Load Add Shed
42233 position status
Position Only Number of Fields: 3 2: Not Available Control
of breaker 5
Default: Not Available
0: Open
Size (bits): 8 1: Closed Indicates
Breaker 6 Read Load Add Shed
42234 position status
Position Only Number of Fields: 3 2: Not Available Control
of breaker 6
Default: Not Available
0: Not Available
Size (bits): 8 1: Normal Indicates trip
Breaker 1 Trip Read Load Add Shed
42235 status of
Status Only Number of Fields: 3 2: Tripped Control
breaker 1
Default: Not Available
0: Not Available
Size (bits): 8 1: Normal Indicates trip
Breaker 2 Trip Read Load Add Shed
42236 status of
Status Only Number of Fields: 3 2: Tripped Control
breaker 2
Default: Not Available
0: Not Available
Size (bits): 8 1: Normal Indicates trip
Breaker 3 Trip Read Load Add Shed
42237 status of
Status Only Number of Fields: 3 2: Tripped Control
breaker 3
Default: Not Available
Size (bits): 8
0: Not Available
Number of Fields: 3 Indicates trip
Breaker 4 Trip Read 1: Normal Load Add Shed
42238 status of
Status Only 2: Tripped Control
breaker 4
Default: Not Available

0: Not Available
Size (bits): 8 1: Normal Indicates trip
Breaker 5 Trip Read Load Add Shed
42239 status of
Status Only Number of Fields: 3 2: Tripped Control
breaker 5
Default: Not Available
0: Not Available
Size (bits): 8 1: Normal Indicates trip
Breaker 6 Trip Read Load Add Shed
42240 status of
Status Only Number of Fields: 3 2: Tripped Control
breaker 6
Default: Not Available

Copyright © 2017 Cummins Inc. 500 A029X159 (Issue 19)


8-2017 10. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function


0: Not Available
1: No Source
Connected Indicates
Read Size (bits): 8 Load Add Shed
42241 ATS 1 Position 2: Source 1 Connected position status
Only Number of Fields: 5 Control
3: Source 2 Connected of ATS 1
4: Paralleled
Default: Not Available
0: Not Available
1: No Source
Connected Indicates
Read Size (bits): 8 Load Add Shed
42242 ATS 2 Position 2: Source 1 Connected position status
Only Number of Fields: 5 Control
3: Source 2 Connected of ATS 3
4: Paralleled
Default: Not Available
0: Not Available
1: No Source
Connected Indicates
Read Size (bits): 8 Load Add Shed
42243 ATS 3 Position 2: Source 1 Connected position status
Only Number of Fields: 5 Control
3: Source 2 Connected of ATS 3
4: Paralleled
Default: Not Available
0: Not Available
1: No Source
Connected Indicates
Read Size (bits):8 Load Add Shed
42244 ATS 4 Position 2: Source 1 Connected position status
Only Number of Fields: 5 Control
3: Source 2 Connected of ATS 4
4: Paralleled
Default: Not Available
0: Not Available
1: No Source
Connected Indicates
Read Size (bits): 8 Load Add Shed
42245 ATS 5 Position 2: Source 1 Connected position status
Only Number of Fields: 5 Control
3: Source 2 Connected of ATS 5
4: Paralleled
Default: Not Available
0: Not Available
1: No Source
Connected Indicates
Read Size (bits): 8 Load Add Shed
42246 ATS 6 Position 2: Source 1 Connected position status
Only Number of Fields: 5 Control
3: Source 2 Connected of ATS 6
4: Paralleled
Default: Not Available

A029X159 (Issue 19) 501 Copyright © 2017 Cummins Inc.


10. DMC 1000 Modbus Enumerated Data 8-2017

Addr. System Name Access Specifications Description Function


0: Failed
PCCNet Size (bits): 8 1: Good Indicates
Read
42248 Communication status of Communications
Only Number of Fields: 3 2: Wait
s Status PCCNet
Default: Wait
Indicates the
Expansion 0: Disabled status of the
Board Read Size (bits): 8 SID to
42249 1: Enabled Communications
Communication Only Number of Fields: 2 expansion
s Default: Disabled board
connection
0: Do Nothing Indicates
Add Level 1 Read Size (bits): 8 Load Add Shed
42252 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 1

0: Do Nothing Indicates
Add Level 2 Read Size (bits):8 Load Add Shed
42253 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 2

0: Do Nothing Indicates
Add Level 3 Read Size (bits): 8 Load Add Shed
42254 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 3

0: Do Nothing Indicates
Add Level 4 Read Size (bits): 8 Load Add Shed
42255 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 4

0: Do Nothing Indicates
Add Level 5 Read Size (bits): 8 Load Add Shed
42256 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 5

0: Do Nothing Indicates
Add Level 6 Read Size (bits): 8 Load Add Shed
42257 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 6

0: Do Nothing Indicates
Shed Level 1 Read / Size (bits): 8 Load Add Shed
42258 1: Shed Level status of shed
Command Write Number of Fields: 2 Control
Default: Do Nothing level 1

0: Do Nothing Indicates
Shed Level 2 Read Size (bits): 8 Load Add Shed
42259 1: Shed Level status of shed
Command Only Number of Fields: 2 Control
Default: Do Nothing level 2

0: Do Nothing Indicates
Shed Level 3 Read / Size (bits): 8 Load Add Shed
42260 1: Shed Level status of shed
Command Write Number of Fields: 2 Control
Default: Do Nothing level 3

0: Do Nothing Indicates
Shed Level 4 Read Size (bits): 8 Load Add Shed
42261 1: Shed Level status of shed
Command Only Number of Fields: 2 Control
Default: Do Nothing level 4

Copyright © 2017 Cummins Inc. 502 A029X159 (Issue 19)


8-2017 10. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates
Shed Level 5 Read Size (bits): 8 Load Add Shed
42262 1: Shed Level status of shed
Command Only Number of Fields: 2 Control
Default: Do Nothing level 5

0: Do Nothing Operator input


Manual add Size (bits): 8
Read / to add loads Load Add Shed
42263 Level 1 1: Add Level
Write Number of Fields: 2 assigned to Control
Command Default: Do Nothing level 1

0: Do Nothing Operator input


Manual add Size (bits): 8
Read / to add loads Load Add Shed
42264 Level 2 1: Add Level
Write Number of Fields: 2 assigned to Control
Command Default: Do Nothing level 2

0: Do Nothing Operator input


Manual add Size (bits): 8
Read / to add loads Load Add Shed
42265 Level 3 1: Add Level
Write Number of Fields: 2 assigned to Control
Command Default: Do Nothing level 3

0: Do Nothing Operator input


Manual add Size (bits): 8
Read / to add loads Load Add Shed
42266 Level 4 1: Add Level
Write Number of Fields: 2 assigned to Control
Command Default: Do Nothing level 4

0: Do Nothing Operator input


Manual add Size (bits): 8
Read / to add loads Load Add Shed
42267 Level 5 1: Add Level
Write Number of Fields: 2 assigned to Control
Command Default: Do Nothing level 5

0: Do Nothing Operator input


Manual add Size (bits): 8
Read / to add loads Load Add Shed
42268 Level 6 1: Add Level
Write Number of Fields: 2 assigned to Control
Command Default: Do Nothing level 6

0: Do Nothing Operator input


Manual Shed Read / Size (bits): 8 to shed loads Load Add Shed
42269 1: Shed Level
Level 1 Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 1

0: Do Nothing Operator input


Manual Shed Read / Size (bits): 8 to shed loads Load Add Shed
42270 1: Shed Level
Level 2 Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 2

0: Do Nothing Operator input


Manual Shed Read / Size (bits): 8 to shed loads Load Add Shed
42271 1: Shed Level
Level 3 Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 3

0: Do Nothing Operator input


Manual Shed Read / Size (bits): 8 to shed loads Load Add Shed
42272 1: Shed Level
Level 4 Write Number of Fields:2 assigned to Control
Default: Do Nothing level 4

0: Do Nothing Operator input


Manual Shed Read / Size (bits): 8 to shed loads Load Add Shed
42273 1: Shed Level
Level 5 Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 5

A029X159 (Issue 19) 503 Copyright © 2017 Cummins Inc.


10. DMC 1000 Modbus Enumerated Data 8-2017

Addr. System Name Access Specifications Description Function

0: Do Nothing Indicates if
Restore Shed Size (bits): 8
Read / shed level 1 Load Add Shed
42274 Level 1 1: Restore Level
Write Number of Fields: 2 has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed Size (bits): 8
Read / shed level 2 Load Add Shed
42275 Level 2 1: Restore Level
Write Number of Fields: 2 has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed Size (bits): 8
Read / shed level 3 Load Add Shed
42276 Level 3 1: Restore Level
Write Number of Fields: 2 has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed Size (bits): 8
Read / shed level 4 Load Add Shed
42277 Level 4 1: Restore Level
Write Number of Fields: 2 has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed Size (bits): 8
Read / shed level 5 Load Add Shed
42278 Level 5 1: Restore Level
Write Number of Fields: 2 has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates add
Add Load 1 Read Size (bits): 8 Load Add Shed
42279 1: Add Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 1

0: Do Nothing Indicates add


Add Load 2 Read Size (bits): 8 Load Add Shed
42280 1: Add Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 2

0: Do Nothing Indicates add


Add Load 3 Read Size (bits): 8 Load Add Shed
42281 1: Add Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 3

0: Do Nothing Indicates add


Add Load 4 Read Size (bits): 8 Load Add Shed
42282 1: Add Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 4

0: Do Nothing Indicates add


Add Load 5 Read Size (bits): 8 Load Add Shed
42283 1: Add Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 5

0: Do Nothing Indicates add


Add Load 6 Read Size (bits): 8 Load Add Shed
42284 1: Add Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 6

0: Do Nothing Indicates shed


Shed Load 1 Read Size (bits): 8 Load Add Shed
42285 1: Shed Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 1

0: Do Nothing Indicates shed


Shed Load 2 Read Size (bits): 8 Load Add Shed
42286 1: Shed Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 2

Copyright © 2017 Cummins Inc. 504 A029X159 (Issue 19)


8-2017 10. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates shed
Shed Load 3 Read Size (bits): 8 Load Add Shed
42287 1: Shed Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 3

0: Do Nothing Indicates shed


Shed Load 4 Read Size (bits): 8 Load Add Shed
42288 1: Shed Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 4

0: Do Nothing Indicates shed


Shed Load 5 Read Size (bits): 8 Load Add Shed
42289 1: Shed Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 5

0: Do Nothing Indicates shed


Shed Load 6 Read Size (bits): 8 Load Add Shed
42290 1: Shed Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 6

0: Manual
1: Normal Indicates the
PTC Genset 2: Normal Override current
Read Size (bits):8 PTC Operating
42296 Operating 3: Test operating
Only Number of Fields: 6 Mode
Mode 4: Utility Fail mode of the
5: Extended Parallel generator sets
Default:
0: Manual
1: Normal Indicates the
PTC Transfer 2: Normal Override current
Read Size (bits):8 PTC Operating
42297 Pair Operating 3: Test operating
Only Number of Fields: 6 Mode
Mode 4: Utility Fail mode of the
5: Extended Parallel transfer pair
Default:

0: Open Transition Indicates the


1: Hard Closed transition type
Size (bits): 8 Transition currently
PTC Operating Read PTC Operating
42298 applicable to
Transition Type Only Number of Fields: 3 2: Soft Closed Mode
the PTC
Transition function
Default: operation
0: Master Synchronize
Only
1: Isolated Bus w/out Main setting:
GM Sets system
System Read / Size (bits): 8 2: Isolated Bus w/GM topology; Application
42300
Topology Write Number of Fields: 6 3: Common Bus control must be Configuration
4: Transfer Pair in manual to
5: Component Mode set
Default: Master
Synchronize Only

A029X159 (Issue 19) 505 Copyright © 2017 Cummins Inc.


10. DMC 1000 Modbus Enumerated Data 8-2017

Addr. System Name Access Specifications Description Function


0: Open Transition
1: Hard Closed
Transition Sets the type
Read / Size (bits):8 of transition Application
42301 Transition Type 2: Soft Closed
Write Number of Fields: 3 that will be Configuration
Transition used
Default: Open
Transition

0: Disabled Use to enable


Extended Read / Size (bits): 8 extended Application
42302 1: Enabled
Parallel Enable Write Number of Fields: 2 paralleling Configuration
Default: Disabled operation
Size (bits): 8
0: None
Number of Fields: 3
Load Demand Read / 1: Fixed Sequence Sets load Load Demand
42303
Type Write 2: Run Hours demand type Control
Default: None

0: Manual
Priority Control Read / Size (bits): 8 Sets priority
42304 1: Automatic Priority Control
Method Write Number of Fields: 2 control method
Default: Manual

0: Disabled Use to enable


Test With Load Read / Size (bits): 8 or disable load Application
42326 1: Enabled
Enable Write Number of Fields: 2 transfer during Configuration
Default: Disabled a test
selects where
0: Internal the generator
Genset Bus Size (bits):8
Read / set kW setpoint Master Load
42328 kW Setpoint 1: Analog Input
Write Number of Fields: 2 will come from Control
Source Default: Internal for extended
paralleling
Selects where
the generator
Genset Bus 0: Internal set kVAR
Read / Size (bits):8 Master Load
42329 kVAR Setpoint 1: Analog Input setpoint will
Write Number of Fields: 2 Control
Source Default: Internal come from
extended
paralleling
Selects where
0: Internal the utility kW
Utility Bus kW Size (bits):8
Read / setpoint will Master Load
42335 Setpoint 1: Analog Input
Write Number of Fields: 2 come from for Control
Source Default: Internal extended
paralleling
Selects where
0: Internal the utility kVAR
Utility Bus Size (bits):8
Read / setpoint will Master Load
42336 kVAR Setpoint 1: Analog Input
Write Number of Fields: 2 come from Control
Source Default: Internal extended
paralleling

Copyright © 2017 Cummins Inc. 506 A029X159 (Issue 19)


8-2017 10. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function

0: Inactive Use to
Clear Fault Read / Size (bits):8 completely Fault and Event
42342 1: Active
History Table Write Number of Fields: 2 clear the fault Info
Default: Inactive history table
Use to
completely
Clear Size (bits):8 0: Inactive clear the
Read / Fault and Event
42343 Occurrence Number of Fields: 2 1: Active counts in faults
Write Info
Table Default: Inactive and events
occurrence
tables
Use to
0: Do Nothing permanently
Genset Reset Size (bits):8
Read / clear all
42344 All Energy 1: Clear Counters Energy
Write Number of Fields: 2 generator set
Meters Default: Do Nothing energy meter
values

Size (bits):8 Use to


0: Do Nothing permanently
Utility Reset All Read / Number of Fields: 2
42345 1: Clear Counters clear all utility Energy
Energy Meters Write
Default: Do Nothing energy meter
values
0: Genset % Level
(Open Loop)
1: Genset Bus kW Sets how and
(Closed Loop) where the kW
Extended
Size (bits):8 will be
Paralleling kW Read / 2: Genset Bus kW Master Load
42346 controlled for
Load Control Write Number of Fields: 4 w/Utility (open Loop) Control
extended
Type 3: Utility Bus kW parallel
(Closed Loop) operation
Default: Genset Bus %
Level (Open Loop)
0: Genset Controllers
1: Genset Bus % Level
(Open Loop)
2: Genset Bus Power
Factor Sets how and
3: Genset Bus kVAR where the
Extended (Closed Loop)
Size (bits):8 kVAR will be
Paralleling Read / Master Load
42347 4: Genset Bus Power controlled for
kVAR Load Write Number of Fields: 7 Control
Factor (Closed Loop) extended
Control Type
5: Utility Bus kVAR parallel
(Closed Loop) operation
6:Utility Bus Power
Factor(Closed Loop)
Default: Genset
Controllers

A029X159 (Issue 19) 507 Copyright © 2017 Cummins Inc.


10. DMC 1000 Modbus Enumerated Data 8-2017

Addr. System Name Access Specifications Description Function

0: Disabled Enable if want


Fail To Sync Read / Size (bits):8 synchronizing Master Sync
42349 1: Enabled
Lockout Enable Write Number of Fields: 2 to stop if fail to Control
Default: Disabled sync occurs
Fail to Sync Use to enable
Open 0: Disabled or disable an
Read / Size (bits):16 PTC State
42350 Transition 1: Enabled open transition
Write Number of Fields: 2 Machine
Retransfer Default: Disabled retransfer upon
Enable a fail to sync
In manual
Size (bits):8 mode, can be
0: Closed Requested
Number of Fields: 3 used to
Gen CB Read / 1: No Command
42352 semi–manually Breaker Control
Manual Control Write 2: Open Command control the
Default: No Command generator set
breaker
In manual
0: Closed Requested mode, can be
Util CB Manual Read / Size (bits):8 1: No Command used to
42353 Breaker Control
Control Write Number of Fields: 3 2: Open Command semi–manually
Default: No Command control the
utility breaker
0: Normal Use to invert
Synchronizer Read / Size (bits):8 Master Sync
42357 1: Invert synchronizer
Polarity Write Number of Fields: 2 Control
Default: Normal polarity

0: Phase Match Sets the


Synchronize Read / Size (bits):8 Master Sync
42358 1: Slip Frequency synchronizing
Method Write Number of Fields: 2 Control
Default: Phase Match method

Allows protocol
0: PCCNet CT the
Port Protocol Read / Size (bits): 8 PCCNet port to
42359 1: MON Communications
Selection Write Number of Fields: 2 be changed to
Default: PCCNet MON for
troubleshooting

0: Disabled Use to enable


System Size (bits): 8
Read / or disable the System
42360 Scheduler 1: Enabled
Write Number of Fields: 2 system Scheduler
Enable Default: Disabled scheduler

0: Disabled Use to enable


Load Add Shed Read / Size (bits): 8 or disable the Load Add Shed
42361 1: Enabled
Enable Write Number of Fields: 2 load add shed Control
Default: Disabled feature
Use to enable
Open
0: Disabled or disable the
Transition Size (bits): 8
Read / shedding of Load Add Shed
42362 Retransfer 1: Enabled
Write Number of Fields: 2 loads during Control
Load Shed Default: Disabled open transition
Enable
retransfer

Copyright © 2017 Cummins Inc. 508 A029X159 (Issue 19)


8-2017 10. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function


Indicates
Auto/Manual Size (bits): 8 0: Auto automatic or
Read / Load Add Shed
42363 Load Add Number of Fields: 2 1: Manual manual load
Write Control
Restore Mode Default: Auto add restore
operation
Indicates type
0: None of load
Load 1 Device
Read / Size (bits): 8 1: Breaker connection to Load Add Shed
42367 Type
Write Number of Fields: 3 2: ATS load 1 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 2 Device Read / Size (bits): 8 1: Breaker connection to Load Add Shed
42368
Type Write Number of Fields: 3 2: ATS load 2 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 3 Device Read / Size (bits): 8 1: Breaker connection to Load Add Shed
42369
Type Write Number of Fields: 3 2: ATS load 3 add Control
Default: None shed control
and status I/O

Size (bits): 8 Indicates type


0: None of load
Number of Fields: 3
Load 4 Device Read / 1: Breaker connection to Load Add Shed
42370
Type Write 2: ATS load 4 add Control
Default: None shed control
and status I/O
Indicates type
Size (bits): 8 0: None of load
Load 5 Device Read / Number of Fields: 3 1: Breaker connection to Load Add Shed
42371
Type Write 2: ATS load 5 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 6 Device Read / Size (bits):8 1: Breaker connected to Load Add Shed
42372
Type Write Number of Fields: 3 2: ATS load 6 add Control
Default: None shed control
and status I/O
0: Both kW and Use to choose
Frequency method for
Genset Bus Size (bits):8 1: kW Only
Read / determining System
42385 Overload
Write Number of Fields: 3 2: Frequency Only generator bus Information
Method
Default: Both kW and overload
Frequency condition

A029X159 (Issue 19) 509 Copyright © 2017 Cummins Inc.


10. DMC 1000 Modbus Enumerated Data 8-2017

Addr. System Name Access Specifications Description Function

0: Disabled Use to enable


Load Demand Read / Size (bits):8 or disable the Load Demand
42390 1: Enabled
Enable Write Number of Fields: 2 load demand Control
Default: Disabled feature
0: Gen1
1: Gen2 Sets GenA for
Load Demand Read / Size (bits): 8 Load Demand
42391 2: Gen3 fixed sequence
GenA Write Number of Fields: 4 Control
3: Gen4 load demand
Default: Gen1
0: Gen1
1: Gen2 Sets GenB for
Load Demand Read / Size (bits):8 Load Demand
42392 2: Gen3 fixed sequence
GenB Write Number of Fields: 4 Control
3: Gen4 load demand
Default: Gen2
0: Gen1
1: Gen2 Sets GenC for
Load Demand Read / Size (bits):8 Load Demand
42393 2: Gen3 fixed sequence
GenC Write Number of Fields: 4 Control
3: Gen4 load demand
Default: Gen3
0: Gen1 Sets GenD
1: Gen2 (first to stop)
Load Demand Read / Size (bits):8 Load Demand
42394 2: Gen3 for fixed
GenD Write Number of Fields: 4 Control
3: Gen4 sequence load
Default: Gen4 demand

0: L1–L2–L3 Defines what


System Phase Read / Size (bits):8 the system System
42413 1:L1–L3–L2
Rotation Write Number of Fields: 2 phase rotation Information
Default: L1–L2–L3 sequence is

0: Disable Use to enable


Scheduler Size (bits):8
Read / or disable the System
42419 Program x 1: Enable
Write Number of Fields: 2 selected Scheduler
Enable Default: Disable program

Copyright © 2017 Cummins Inc. 510 A029X159 (Issue 19)


8-2017 10. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function


0: Once
1: Every Week
2: Every 2 Weeks
3: Every 3 Weeks
4: Every 4 Weeks
5: Every 5 Weeks
Size (bits):8 6: First Week of Month Use to adjust
Scheduler
Read / 7: Second Week of repeat interval System
42420 Program x Number of Fields:
Write Month for the selected Scheduler
Repeat Interval 11 program
8: Third Week of
month
9: Forth Week of the
Month
10: Last Week of the
Month
Default: Once
0: No Load Use to adjust
Scheduler Size (bits): 8 1: With Load
Read / run mode for System
42421 Program x Run
Write Number of Fields: 3 2: Extended Parallel the selected Scheduler
Mode
Default: No Load program

0: Sunday
1: Monday
2: Tuesday Use to adjust
Scheduler Size (bits): 8 3: Wednesday start day of
Read / System
42422 Program x week for the
Write Number of Fields: 7 4: Thursday Scheduler
Start Day selected
5: Friday program
6: Saturday
Default: Sunday

0: Disable Use to enable


Scheduler Size (bits): 8
Read / or disable the System
42428 Exception x 1: Enable
Write Number of Fields: 2 selected Scheduler
Enable Default: Disable exception
Use to adjust
Scheduler 0: Once Only the repeat
Read / Size (bits): 8 System
42429 Exception x 1: Every Year setting of the
Write Number of Fields: 2 Scheduler
Repeat Default: Once Only selected
exception

0: Disabled Enables the


Daylight Size (bits): 8
Read / daylight
42437 Saving Time 1: Enabled Real Time Clock
Write Number of Fields: 2 savings time
Enable Default: Disabled feature
Use to force a
Load Demand 0: Do Nothing
Size (bits): 8 refresh of the
Refresh Read / Load Demand
42438 1: Refresh Sequence active load
Sequence Write Number of Fields: 2 Control
Default: Do Nothing demand
Command
sequence

A029X159 (Issue 19) 511 Copyright © 2017 Cummins Inc.


10. DMC 1000 Modbus Enumerated Data 8-2017

Addr. System Name Access Specifications Description Function

Genset 0: Wye Delta or Wye


Read / Size (bits):8
42439 Connection 1: Delta for generator AC Setup
Write Number of Fields: 2
Type Default: Wye set connection

Genset CT 0: 1 Amp Generator set


Read / Size (bits): 8
42443 Secondary 1: 5 Amp CT secondary AC Setup
Write Number of Fields: 2
Current Default: 5 Amp current

Utility 0: Wye Delta or Wye


Read / Size (bits): 8
42444 Connection 1: Delta for utility AC Setup
Write Number of Fields: 2
Type Default: Wye connection

Utility CT 0: 1 Amp Utility CT


Read / Size (bits): 8
42448 Secondary 1: 5 Amp secondary AC Setup
Write Number of Fields: 2
Current Default: 5 Amp current

0: 12V DC voltage
Nominal Read / Size (bits): 8 Battery Voltage
42454 1: 24V provided to the
Battery Voltage Write Number of Fields: 2 Protection
Default: 24V control

Use to enable
Genset Online 0: Disable or disable the
Read / Size (bits): 8
42461 Capacity 1: Enable generator set PTC Sensors
Write Number of Fields: 2
Sensor Enable Default: Disable online capacity
sensor
Indicates that
0: Inactive the generator
Gen Bus Base Read Size (bits):8 System
42472 1: Active bus is on base
Load Status Only Number of Fields: 2 Information
Default: load extended
paralleling
Indicates that
0: Inactive the utility bus is
Util Bus Peak Read Size (bits): 8 System
42473 1: Active on peak shave
Shave Status Only Number of Fields: 2 Information
Default: extended
paralleling

0: Stop State of
Extended Size (bits): 8
Read / extended
42600 Parallel Start 1: Start Discrete Inputs
Write Number of Fields: 2 parallel start
Vol Default: Stop volatile input

0: inactive State of
Synchronizer Read / Size (bits): 8 synchronizer
42601 1: Active Discrete Inputs
Enable Vol Write Number of Fields: 2 enable volatile
Default: inactive input
0: inactive State of utility
Utility Source Read / Size (bits): 8
42602 1: Active source failure Discrete Inputs
Failure Vol Write Number of Fields: 2
Default: inactive volatile input

0: No Inhibit State of
Transfer Inhibit Read / Size (bits):16
42603 1: Inhibit transfer inhibit Discrete Inputs
Vol Write Number of Fields: 2
Default: No Inhibit volatile input

Copyright © 2017 Cummins Inc. 512 A029X159 (Issue 19)


8-2017 10. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function

0: No Inhibit State of
Retransfer Read / Size (bits):8 retransfer
42604 1: Inhibit Discrete Inputs
Inhibit Vol Write Number of Fields: 2 inhibit volatile
Default: No Inhibit input

0: No Inhibit State of
Gen CB Inhibit Read / Size (bits): 8 generator CB
42605 1: Inhibit Discrete Inputs
Vol Write Number of Fields: 2 inhibit volatile
Default: No Inhibit input
0: No Inhibit State of utility
Util CB Inhibit Read / Size (bits): 8
42606 1: Inhibit CB inhibit Discrete Inputs
Vol Write Number of Fields: 2
Default: No Inhibit volatile input

0: Auto State of
Auto/Manual Read / Size (bits): 8
42607 1: Manual auto/manual Discrete Inputs
Vol Write Number of Fields: 2
Default: Auto volatile input

Size (bits): 8 0: Stop State of test


Read /
42608 Test Start Vol Number of Fields: 2 1: Start start volatile Discrete Inputs
Write
Default: Stop input

0: Not Reset State of fault


Read / Size (bits): 8
42609 Fault Reset Vol 1: Reset reset volatile Discrete Inputs
Write Number of Fields: 2
Default: Not Reset input

0: No Override State of
Read / Size (bits): 8
42610 Override Vol 1: Override override Discrete Inputs
Write Number of Fields: 2
Default: No Override volatile input

0: Start State of
Extended Size (bits): 8
Read extended
42611 Parallel Start 1: Stop Discrete Inputs
Only Number of Fields: 2 parallel start
Sw Default: input
0: Inactive State of
Synchronizer Read Size (bits): 8
42612 1: Active synchronizer Discrete Inputs
Enable Sw Only Number of Fields: 2
Default: enable input

0: Inactive State of utility


Utility Source Read Size (bits): 8
42613 1: Active source failure Discrete Inputs
Failure Sw Only Number of Fields: 2
Default: input

0: No Inhibit State of
Transfer Inhibit Read Size (bits): 8
42614 1: Inhibit transfer inhibit Discrete Inputs
Sw Only Number of Fields: 2
Default: input

0: No Inhibit State of
Retransfer Read Size (bits): 8
42615 1: Inhibit retransfer Discrete Inputs
Inhibit Sw Only Number of Fields: 2
Default: inhibit input

0: No Inhibit Sate of
Gen CB Inhibit Read Size (bits): 8
42616 1: Inhibit generator CB Discrete Inputs
Sw Only Number of Fields: 2
Default: inhibit input

A029X159 (Issue 19) 513 Copyright © 2017 Cummins Inc.


10. DMC 1000 Modbus Enumerated Data 8-2017

Addr. System Name Access Specifications Description Function


0: No Inhibit
Util CB Inhibit Read Size (bits): 8 State of utility
42617 1: Inhibit Discrete Inputs
Sw Only Number of Fields: 2 CB inhibit input
Default:
0: Auto State of
Auto/Manual Read Size (bits): 8
42618 1: Manual auto/manual Discrete Inputs
Sw Only Number of Fields: 2
Default: input

0: Stop
Read Size (bits): 8 State of test
42619 Test Start Sw 1: Start Discrete Inputs
Only Number of Fields: 2 start input
Default:
0: No Reset
Read Size (bits): 8 State of fault
42620 Fault Reset Sw 1: Reset Discrete Inputs
Only Number of Fields: 2 reset input
Default:
0: No Override
Read Size (bits): 8 State of
42621 Override Sw 1: Override Discrete Inputs
Only Number of Fields: 2 override input
Default:
0: No Inhibit Indicates state
Read Size (bits): 8
42622 Master Inhibit 1: Inhibit of Master Priority Control
Only Number of Fields: 2
Default: priority inhibit

0: Inactive State of
Gen CB Read Size (bits): 8
42623 1: Active generator CB Discrete Inputs
Tripped Sw Only Number of Fields: 2
Default: tripped input

0: Inactive State of
Gen CB Read / Size (bits): 8 generator CB
42624 1: Active Discrete Inputs
Tripped Vol Write Number of Fields: 2 tripped volatile
Default: Inactive input
0: Inactive State of utility
Util CB Tripped Read Size (bits): 8
42625 1: Active CB tripped Discrete Inputs
Sw Only Number of Fields: 2
Default: input

Size (bits): 8 0: Inactive State of utility


Util Cb Tripped Read /
42626 Number of Fields: 4 1: Active CB tripped Discrete Inputs
Vol Write
Default: Inactive volatile input

0: L1–L2–L3
Genset Phase Read Size (bits): 8 Generator set
42627 1: L1–L3–L2 Phase
Rotation Only Number of Fields: 2 phase rotation
Default:
Size (bits): 8 0: L1–L2–L3
Utility Phase Read Utility phase
42628 Number of Fields: 2 1: L1–L3–L2 Phase
Rotation Only rotation
Default:
Size (bits): 8 0: Breaker Open State of Gen1
Gen1 CB Read
42629 Number of Fields: 2 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

Copyright © 2017 Cummins Inc. 514 A029X159 (Issue 19)


8-2017 10. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function


0: Breaker Open State of Gen1
Gen1 CB Read / Size (bits): 8
42630 1: Breaker Closed CB position Discrete Inputs
Position Vol Write Number of Fields: 2
Default: Open volatile input

0: Breaker Open State of Gen2


Gen2 CB Read Size (bits): 8
42631 1: Breaker Closed CB position Discrete Inputs
Position Sw Only Number of Fields: 2
Default: input

0: Breaker Open State of Gen2


Gen2 CB Read / Size (bits): 8
42632 1: Breaker Closed CB position Discrete Inputs
Position Vol Write Number of Fields: 2
Default: Open volatile input

0: Breaker Open State of Gen3


Gen3 CB Read Size (bits):16
42633 1: Breaker Closed CB position Discrete Inputs
Position Sw Only Number of Fields: 2
Default: input

0: Breaker Open State of Gen3


Gen3 CB Read / Size (bits): 8
42634 1: Breaker Closed CB position Discrete Inputs
Position Vol Write Number of Fields: 2
Default: Open volatile input

0: Breaker Open State of Gen4


Gen4 CB Read Size (bits): 8
42635 1: Breaker Closed CB position Discrete Inputs
Position Sw Only Number of Fields: 2
Default: input

0: Breaker Open State of Gen4


Gen4 CB Read / Size (bits): 8
42636 1: Breaker Closed CB position Discrete Inputs
Position Vol Write Number of Fields: 2
Default: Open volatile input

0: No Inhibit Use to
Network Read / Size (bits): 8
42637 1: Inhibit manually inhibit Priority Control
Master Inhibit Write Number of Fields: 2
Default: No Inhibit the module

0: Gen Does Not Exist


1: Offline For load
Gen1 Size (bits): 8 2: Waiting for Gen
Read demand use - Load Demand
42700 Availability
Only Number of Fields: 5 3: Online Indicates Control
State
4: Failed status of Gen1
Default:
0: Gen Does Not Exist
1: Offline For load
Gen2 Size (bits): 8 2: Waiting for Gen
Read demand use - Load Demand
42701 Availability
Only Number of Fields: 5 3: Online Indicates Control
State
4: Failed status of Gen2
Default:
0:Gen Does Not Exist
1: Offline For load
Gen3 Size (bits): 8 2: Waiting for Gen
Read demand use - Load Demand
42702 Availability
Only Number of Fields: 5 3: Online Indicates Control
State
4: Failed status of Gen3
Default:

A029X159 (Issue 19) 515 Copyright © 2017 Cummins Inc.


10. DMC 1000 Modbus Enumerated Data 8-2017

Addr. System Name Access Specifications Description Function


0:Gen Does Not Exist
1: Offline For load
Gen4 Size (bits): 8
Read 2: Waiting for Gen demand use - Load Demand
42703 Availability Number of Fields: 5
Only 3: Online Indicates Control
State
4: Failed status of Gen4
Default:
Size (bits): 8 0: Gen1 Indicates which
Number of Fields: 4 1: Gen2 generator set is
Read Load Demand
42712 GenA 2: Gen3 currently GenA
Only Control
3: Gen4 for load
Default: demand

Size (bits): 8 0: Gen1 Indicates which


Number of Fields: 4 1: Gen2 generator set is
Read Load Demand
42713 GenB 1: Gen3 currently GenB
Only Control
1: Gen4 for load
Default: demand

0: Gen1 Indicates which


1: Gen2 generator set is
Read Size (bits): 8 Load Demand
42714 GenC 1: Gen3 currently GenC
Only Number of Fields: 4 Control
1: Gen4 for load
Default: demand

0: Gen1 Indicates which


1: Gen2 generator set is
Read Size (bits): 8 currently GenD Load Demand
42715 GenD 1: Gen3
Only Number of Fields: 4 (first to stop) Control
1: Gen4 for load
Default: demand
Size (bits): 8
0: Off Indicates
Number of Fields: 3
Load Demand Read 1: Initial Delay Timing operating state Load Demand
42716
State Only 2: Load Monitor of the load Control
Default: demand control

0: Gen1
Indicates which
Size (bits): 8 1: Gen2 generator set is
Next Gen To Read Number of Fields: 5 2: Gen3 next to be Load Demand
42721
Restart Only 3: Gen4 restarted if load Control
4: None conditions are
met
Default:
0: Gen1
Size (bits): 8 Indicates which
1: Gen2 generator set is
Number of Fields: 5
Next Gen To Read 2: Gen3 next to be Load Demand
42722
Shutdown Only 3: Gen4 stopped if load Control
4: None conditions are
met
Default:

Copyright © 2017 Cummins Inc. 516 A029X159 (Issue 19)


8-2017 10. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function


Size (bits): 8
Number of Fields: 2 0: Run Status of the
Load Demand
Read load demand
42723 Gen1 Driver 1: Load Demand Stop Discrete Outputs
Only Gen1 driver
Status Default: output

0: Run Status of the


Load Demand Size (bits): 8
Read load demand
42724 Gen2 Driver 1: Load Demand Stop Discrete Outputs
Only Number of Fields: 2 Gen2 driver
Status Default: output

0: Run Status of the


Load Demand Size (bits): 8
Read load demand
42725 Gen3 Driver 1: Load Demand Stop Discrete Outputs
Only Number of Fields: 2 Gen3 driver
Status Default: output
Size (bits): 8
Number of Fields: 2 0: Run Status of the
Load Demand
Read load demand
42726 Gen4 Driver 1: Load Demand Stop Discrete Outputs
Only Gen4 driver
Status Default: output

Size (bits): 8 Indicates


Genset Bus 0: No Overload whether
Read Number of Fields: 2 System
42728 kW Overload 1: Overload generator bus
Only Information
Status Default: is overloaded
based on kW

Size (bits): 8 Indicates


Genset Bus Number of Fields: 2 0: No Overload whether
Underfrequenc Read generator bus System
42729 1: Overload
y Overload Only is overloaded Information
Status Default: based on
frequency

A029X159 (Issue 19) 517 Copyright © 2017 Cummins Inc.


10. DMC 1000 Modbus Enumerated Data 8-2017

Addr. System Name Access Specifications Description Function


0: None
1: Program 1
2: Program 2
3: Program 3
4: Program 4
5: Program 5
6: Program 6
Size (bits): 8 7: Program 7
Number of Fields: 8: Program 8 Indicates the
19 9: Program 9 currently active
Active Read System
42730 scheduler
Schedule Only 10: Program 10 Scheduler
program or
11: Program 11 exception
12: Program 12
13: Exception 1
14: Exception 2
15: Exception 3
16: Exception 4
17: Exception 5
18: Exception 6
Default:

0: Off Indicates
1: No Load current run
Scheduler Run Read Size (bits): 8 command System
42731 2: With Load
Command Only Number of Fields: 4 coming from Scheduler
3: Extended Parallel the scheduler
Default: function
0: Do Nothing Clears all the
Modbus Clear Read / Size (bits): 8
42737 1: Clear Counters Modbus Communications
Counters Write Number of Fields: 2
Default: Do Nothing counters

Size (bits): 8
0: Normal
Number of Fields: 3 Use to set
Read / 1: Set Clock
42738 Clock Mode clock and save Real Time Clock
Write 2: Save Clock setting
Default: Normal

0: Sunday
1: Monday
2: Tuesday
Size (bits): 8 3: Wednesday Indicates day
Read
42745 Clock Day of week for Real Time Clock
Only Number of Fields: 7 4: Thursday current date
5: Friday
6: Saturday
Default:

Copyright © 2017 Cummins Inc. 518 A029X159 (Issue 19)


11 DMC 1000 Modbus Bitmap Data
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table, it is not implemented.

Addr. Bit# System Name Fault Code Event Name Response


42500 0 Fault Status 1455 Utility Main Warning
Bitmap 1 Breaker Position
Contact Warning
42500 1 Fault Status 2396 Utility Main Warning
Bitmap 1 Breaker Fail To
Close Warning
42500 2 Fault Status 2397 Utility Main Warning
Bitmap 1 Breaker Fail To
Open Warning
42500 3 Fault Status 1219 Utility Main Warning
Bitmap 1 Breaker Tripped
Warning
42500 4 Fault Status 1914 Utility Bus Phase Warning
Bitmap 1 Rotation Warning
42500 5 Fault Status 1912 Utility Bus Loss Warning
Bitmap 1 Of Phase
Warning
42500 6 Fault Status 2331 Utility Bus Warning
Bitmap 1 Undervoltage
Warning
42500 7 Fault Status 2358 Utility Bus Warning
Bitmap 1 Overvoltage
Warning
42500 8 Fault Status 1223 Utility Bus Warning
Bitmap 1 Frequency
Warning
42500 24 Fault Status 2648 Remote I/O Warning
Bitmap 1 Communication
Failure Warning
42500 25 Fault Status 1689 Real Time Clock Warning
Bitmap 1 Power Interrupt
Warning

A029X159 (Issue 19) 519 Copyright © 2017 Cummins Inc.


11. DMC 1000 Modbus Bitmap Data 8-2017

Addr. Bit# System Name Fault Code Event Name Response


42500 26 Fault Status 1335 AC Metering Out Warning
Bitmap 1 Of Range
Warning
42500 27 Fault Status 1999 Maximum Parallel Warning
Bitmap 1 Time Warning
42500 28 Fault Status 343 Hardware Failure Warning
Bitmap 1 Warning
42500 29 Fault Status 1456 Synchronizer Warning
Bitmap 1 Output Limit
Warning
42500 30 Fault Status 2416 Calibration Warning
Bitmap 1 Checksum
Warning
42500 31 Fault Status 353 EEPROM Write Warning
Bitmap 1 Error Warning
42502 0 Fault Status 1454 Genset Main Warning
Bitmap 2 Breaker Position
Contact Warning
42502 1 Fault Status 1452 Genset Main Warning
Bitmap 2 Breaker Fail To
Close Warning
42502 2 Fault Status 1453 Genset Main Warning
Bitmap 2 Breaker Tripped
Warning
42502 3 Fault Status 1328 Genset Bus Warning
Bitmap 2 Phase Rotation
Warning
42502 4 Fault Status 1915 Genset Bus Warning
Bitmap 2 Phase Rotation
Warning
42502 5 Fault Status 1913 Genset Bus Loss Warning
Bitmap 2 Of Phase
Warning
42502 6 Fault Status 1225 Genset Bus Warning
Bitmap 2 Undervoltage
Warning
42502 7 Fault Status 1224 Genset Bus Warning
Bitmap 2 Overvoltage
Warning
42502 8 Fault Status 1226 Genset Bus Warning
Bitmap 2 Frequency
Warning
42502 24 Fault Status 1541 Genset Failed To Warning
Bitmap 2 Come Online
Warning

Copyright © 2017 Cummins Inc. 520 A029X159 (Issue 19)


8-2017 11. DMC 1000 Modbus Bitmap Data

Addr. Bit# System Name Fault Code Event Name Response


42502 25 Fault Status 2647 Load Demand Warning
Bitmap 2 Setup Warning
42502 26 Fault Status 1444 Genset Bus Warning
Bitmap 2 Overload Warning
42502 27 Fault Status 1989 kW Load Control Warning
Bitmap 2 Output Limit
Warning
42502 28 Fault Status 1991 kVAR Load Warning
Bitmap 2 Control Output
Limit Warning
42502 29 Fault Status 1121 Fail To Warning
Bitmap 2 Disconnect
Warning
42502 30 Fault Status 1458 Synchronizer Warning
Bitmap 2 Phase Rotation
Mismatch
Warning
42502 31 Fault Status 1457 Fail To Warning
Bitmap 2 Synchronizer
Warning
42505 0 Event Status 1222 Not in Automatic Event
Bitmap 1 Event
42505 1 Event Status 1483 Common Warning Event
Bitmap 1 Event
42505 2 Event Status 2965 Genset Bus Event
Bitmap 1 Available Event
42505 3 Event Status 2328 Utility Bus Event
Bitmap 1 Available Event
42505 4 Event Status 2333 Genset Bus Event
Bitmap 1 Connected Event
42505 5 Event Status 2332 Utility Bus Event
Bitmap 1 Connected Event
42505 6 Event Status 2971 Test / Extended Event
Bitmap 1 Parallel Event
42505 7 Event Status 1916 Synchronized Event
Bitmap 1 Event
42505 8 Event Status 1534 Load Control Event
Bitmap 1 Output Event

A029X159 (Issue 19) 521 Copyright © 2017 Cummins Inc.


11. DMC 1000 Modbus Bitmap Data 8-2017

This page is intentionally blank.

Copyright © 2017 Cummins Inc. 522 A029X159 (Issue 19)


12 DMC 1500 Communication Server 1
12.1 Modbus Address: 2 (Slave)
NOTICE
If an address or bit is not listed in this table, it is not implemented.

NOTICE
The external device can read 1-40 contiguous registers, write 1-40 contiguous registers, or read
diagnostic counters.

Modbus Address Bit # Alarm Event


40001 0 (LSB) Utility Main Breaker Position Contact Warning
40001 1 Utility Main Breaker Fail To Close Warning
40001 2 Utility Main Breaker Fail To Open Warning
40001 3 Utility Main Breaker Tripped Warning
40001 4 Utility Bus Phase Rotation Warning
40001 5 Utility Bus Loss of Phase Warning
40001 6 Utility Bus Undervoltage Warning
40001 7 Utility Bus Overvoltage Warning
40001 8 Utility Bus Frequency Warning
40001 9 Remote IO Comm Failure Warning
40001 10 Real Time Clock Power Interrupt Warning
40001 11 AC Metering Out Of Range Warning
40001 12 Maximum Parallel Time Warning
40001 13 Not Implemented
40001 14 Synchronizer Output Limit Warning
40001 15 (MSB) Calibration Checksum Warning MCM 3320

Modbus Address Bit # Alarm Event


40002 0 (LSB) EEPROM Write Error Warning MCM 3320
40002 1 Genset Main Breaker Position Contact Warning
40002 2 Genset Main Breaker Fail to Close Warning
40002 3 Genset Main Breaker Fail to Open Warning

A029X159 (Issue 19) 523 Copyright © 2017 Cummins Inc.


12. DMC 1500 Communication Server 1 8-2017

Modbus Address Bit # Alarm Event


40002 4 Genset Main Breaker Tripped Warning
40002 5 Genset Bus Phase Rotation Warning
40002 6 Genset Bus Loss of Phase Warning
40002 7 Genset Bus Undervoltage Warning
40002 8 Genset Bus Overvoltage Warning
40002 9 Genset Bus Frequency Warning
40002 10 Low Battery Voltage Warning MCM 3320
40002 11 High Battery Voltage Warning MCM 3320
40002 12 Genset Failed to Come Online Warning
40002 13 Load Demand Setup Warning
40002 14 Genset Bus Over Load Limit Warning
40002 15 (MSB) kW Load Control Output Limit Warning

Modbus Address Bit # Alarm Event


40003 0 (LSB) kVAR Load Control Output Limit Warning
40003 1 Fail to Disconnect Warning
40003 2 Synchronizer Phase Rotation Mismatch Warning
40003 3 Fail to Synchronize Warning
40003 4 Normal Operation Lockout
40003 5 Common Warning MCM 3320
40003 6 Common Server 1 to Network ATS Comm Failure
40003 7 Common Server 1 to MCM3320 Comm Failure
40003 8 Common Server 1 Battery Warning
40003 9 Common Server 1 Comm Server 2 Comm Failure
40003 10 Not Implemented
40003 11 Not Implemented
40003 12 Not Implemented
40003 13 Not Implemented
40003 14 Not Implemented
40003 15 (MSB) Not Implemented

Copyright © 2017 Cummins Inc. 524 A029X159 (Issue 19)


8-2017 12. DMC 1500 Communication Server 1

Modbus Address Bit # Alarm Event


40004 0 (LSB) Feeder Breaker 1 Trip
40004 1 Feeder Breaker 2 Trip
40004 2 Feeder Breaker 3 Trip
40004 3 Feeder Breaker 4 Trip
40004 4 Feeder Breaker 5 Trip
40004 5 Feeder Breaker 6 Trip
40004 6 Feeder Breaker 7 Trip
40004 7 Feeder Breaker 8 Trip
40004 8 Feeder Breaker 9 Trip
40004 9 Feeder Breaker 10 Trip
40004 10 Not Implemented
40004 11 Not Implemented
40004 12 Not Implemented
40004 13 Not Implemented
40004 14 Not Implemented
40004 15 (MSB) Not Implemented

NOTICE
40005 is not implemented.

Modbus Address Bit # Alarm Event


40006 0 (LSB) System in Auto-Opened Transition
40006 1 System in Auto-Hard Closed Transition
40006 2 System in Auto-Soft Closed Transition
40006 3 System Manual Mode Active
40006 4 System Automatic Mode Active
40006 5 Common Warning Event
40006 6 Genset Bus Available Event
40006 7 Utility Bus Available Event
40006 8 Genset Bus Connected Event
40006 9 Utility Bus Connected Event
40006 10 Synchronized Event
40006 11 Load Control Output Event

A029X159 (Issue 19) 525 Copyright © 2017 Cummins Inc.


12. DMC 1500 Communication Server 1 8-2017

Modbus Address Bit # Alarm Event


40006 12 Genset Source Unloaded Event
40006 13 Utility Source Unloaded Event
40006 14 Genset Bus Load Event
40006 15 (MSB) Utility Bus Peak Shave Event

Modbus Address Bit # Alarm Event


40007 0 (LSB) Extended Paralleling Enable
40007 1 Extended Paralleling Disable
40007 2 System in Extended Parallel
40007 3 System in Test with Load
40007 4 System in Test without Load
40007 5 System Test Off
40007 6 Load Demand Enable
40007 7 Load Demand Disable
40007 8 Extended Parallel Off
40007 9 Not Implemented
40007 10 Not Implemented
40007 11 Not Implemented
40007 12 Not Implemented
40007 13 Not Implemented
40007 14 Not Implemented
40007 15 (MSB) Not Implemented

12.2 Generator Set Bus Data


Generator Bus Data MB Address Data Type Multiplier Units
Generator Set L1N Volts 40009 16U 1 Volts
Generator Set L2N Volts 40010 16U 1 Volts
Generator Set L3N Volts 40011 16U 1 Volts
Generator Set LN Average Volt 40012 16U 1 Volts
Generator set L1L2 Volts 40013 16U 1 Volts
Generator Set L2L3 Volts 40014 16U 1 Volts
Generator Set L3L1 Volts 40015 16U 1 Volts
Generator Set LL Average Volts 40016 16U 1 Volts

Copyright © 2017 Cummins Inc. 526 A029X159 (Issue 19)


8-2017 12. DMC 1500 Communication Server 1

Generator Bus Data MB Address Data Type Multiplier Units


Generator Set L1 Current 40017 16U 1 Amps
Generator Set L2 Current 40018 16U 1 Amps
Generator Set L3 Current 40019 16U 1 Amps
Generator Set Average Current 40020 16U 1 Amps
Generator Set L1 kW 40021 16S 1 kW
Generator Set L2 kW 40022 16S 1 kW
Generator Set L3 kW 40023 6S 1 kW
Generator Set Total kW 40024 16S 1 kW
Generator Set L1 kVAR 40025 16S 1 kVAR
Generator Set L2 kVAR 40026 16S 1 kVAR
Generator Set L3 kVAR 40027 16S 1 kVAR
Generator Set Total kVAR 40028 16S 1 kVAR
Generator Set Total Power Factor 40029 16S 0.01
Generator Set L1 kVA 40030 16U 1 kVA
Generator Set L2 kVA 40031 16U 1 kVA
Generator Set L3 kVA 40032 16U 1 kVA
Generator Set Total kVA 40033 16U 1 kVA
MB Generator Set Frequency 40034 16U 0.1 Hz
Generator Set Total Negative kWh 40035 32U 1 kWh
40036
Generator Set Total Positive kWh 40037 32U 1 kWh
40038
Generator Set Total Net kWh 40039 32S 1 kWh
40040
Generator Set Total Negative kVARh 40041 32U 1 kVARh
40042
Generator Set Total Positive kVARh 40043 32U 1 kVARh
40044
Generator Set Total Net kVARh 40045 32S 1 kVARh
40046
Generator Set Total kVAh 40047 32U 1 kVAh
40048
Generator Set Available Current 40049 16U 1 Amps
Generator Set L1 Current Percent 40050 16U 0.1 %

A029X159 (Issue 19) 527 Copyright © 2017 Cummins Inc.


12. DMC 1500 Communication Server 1 8-2017

Generator Bus Data MB Address Data Type Multiplier Units


Generator Set L2 Current Percent 40051 16U 0.1 %
Generator Set L3 Current Percent 40052 16U 0.1 %
Generator Set Total kW Percent 40053 16U 0.1 %
Generator Set Frequency Percent 40054 16S 0.1 %
Generator Set L1L2 Voltage Percent 40055 16U 0.1 %
Generator Set L2L3 Voltage Percent 40056 16U 0.1 %
Generator Set L3L1 Voltage Percent 40057 16U 0.1 %

12.3 Utility Bus Data


Utility Bus Data MB Address Data Type Multiplier Units
Utility L1N Voltage 40059 16U 1 Volts
Utility L2N Voltage 40060 16U 1 Volts
Utility L3N Voltage 40061 16U 1 Volts
Utility LN Average Voltage 40062 16U 1 Volts
Utility L1L2 Voltage 40063 16U 1 Volts
Utility L2L3 Voltage 40064 16U 1 Volts
Utility L3L1 Voltage 40065 16U 1 Volts
Utility LL Average Voltage 40066 16U 1 Volts
Utility L1 Current 40067 16U 1 Amps
Utility L2 Current 40068 16U 1 Amps
Utility L3 Current 40069 16U 1 Amps
Utility Average Current 40070 16U 1 Amps
Utility L1 kW 40071 16S 1 kW
Utility L2 kW 40072 16S 1 kW
Utility L3 kW 40073 16S 1 kW
Utility Total kW 40074 16S 1 kW
Utility L1 kVAR 40075 16S 1 kVAR
Utility L2 kVAR 40076 16S 1 kVAR
Utility L3 kVAR 40077 16S 1 kVAR
Utility Total kVAR 40078 16S 1 kVAR
Utility Total Power Factor 40079 16S 0.01
Utility L1 kVA 40080 16U 1 kVA
Utility L2 kVA 40081 16U 1 kVA

Copyright © 2017 Cummins Inc. 528 A029X159 (Issue 19)


8-2017 12. DMC 1500 Communication Server 1

Utility Bus Data MB Address Data Type Multiplier Units


Utility L3 kVA 40082 16U 1 kVA
Utility Total kVA 40083 16U 1 kVA
MB Utility Frequency 40084 16U 0.1 Hz
Utility Total Negative kWh 40085 32U 1 kWh
40086
Utility Total Positive kWh 40087 32U 1 kWh
40088
Utility Total Net kWh 40089 32S 1 kWh
40090
Utility Total Negative kVARh 40091 32U 1 kVARh
40092
Utility Total Positive kVARh 40093 32U 1 kVARh
40094
Utility Total Net kVARh 40095 32S 1 kVARh
40096
Utility Total kVAh 40097 32U 1 kVAh
40098
System Total kW 40099 16S 1 kW
System Total kVAR 40100 16S 0.01 kVAR
System Total Power Factor 40101 16S 1
System Total kVA 40102 16U 1 KVA

12.4 ATS 1-5 DATA


ATS Raw Data ATS 1 ATS 2 ATS 3 ATS 4 ATS 5 Multiplier Units
Device Type 40257 40317 40377 40437 40497
Mode (See Table 14 on page 531) 40258 40318 40378 40438 40498
State (See Table 13 on page 531) 40259 40319 40379 40439 40499
Fault Code 40260 40320 40380 40440 40500
Fault Type (See Table 15 on page
40261 40321 40381 40441 40501
532)
Percent Amps 40262 40322 40382 40442 40502 0.5 %
Total kW 40263 40323 40383 40443 40503
NFPA 110 (See Table 10 on page
40264 40324 40384 40444 40504
458)

A029X159 (Issue 19) 529 Copyright © 2017 Cummins Inc.


12. DMC 1500 Communication Server 1 8-2017

ATS Raw Data ATS 1 ATS 2 ATS 3 ATS 4 ATS 5 Multiplier Units
NFPA Extended(See Table 11 on
40265 40325 40385 40445 40505
page 458)
Frequency Load 40266 40326 40386 40446 40506 0.1 Hz
Total pf Load 40267 40327 40387 40447 40507 0.00005 pf
Total kVA Load 40268 40328 40388 40448 40508 kVA
Total kW Load 40269 40329 40389 40449 40509 kW
Total kVAR Load 40270 40330 40390 40450 40510 kVAR
Volts ab Load 40271 40331 40391 40451 40511 Volts
Volts bc Load 40272 40332 40392 40452 40512 Volts
Volts ca Load 40273 40333 40393 40453 40513 Volts
Volts a Load 40274 40334 40394 40454 40514 Volts
Volts b Load 40275 40335 40395 40455 40515 Volt
Volts c Load 40276 40336 40396 40456 40516 Volts
Amps a Load 40277 40337 40397 40457 40517 Amps
Amps b Load 40278 40338 40398 40458 40518 Amps
Amps c Load 40279 40339 40399 40459 40519 Amps
Percent Amps a Load 40280 40340 40400 40460 40520 0.5 %
Percent Amps b Load 40281 40341 40401 40461 40521 0.5 %
Percent Amps c Load 40282 40342 40402 40462 40522 0.5 %
Frequency SRC1 40283 40343 40403 40463 40523 0.1 Hz
Total pf SRC1 40284 40344 40404 40464 40524 0.00005 PF
Total kVA SRC1 40285 40345 40405 40465 40525
Total kW SRC1 40286 40346 40406 40466 40526
Total kVAR SRC1 40287 40347 40407 40467 40527
Volts ab SRC1 40288 40348 40408 40468 40528
Volts bc SRC1 40289 40349 40409 40469 40529
Volts ca SRC1 40290 40350 40410 40470 40530
Volts a SRC1 40291 40351 40411 40471 40531
Volts b SRC1 40292 40352 40412 40472 40532 Volts
Volts c SRC1 40293 40353 40413 40473 40533
Amps a SCR1 40294 40354 40414 40474 40534 Amps
Amps b SCR1 40295 40355 40415 40475 40535
Amps c SRC1 40296 40356 40416 40476 40536
Percent Amps a SCR1 40297 40357 40417 40477 40537 0.5 %

Copyright © 2017 Cummins Inc. 530 A029X159 (Issue 19)


8-2017 12. DMC 1500 Communication Server 1

ATS Raw Data ATS 1 ATS 2 ATS 3 ATS 4 ATS 5 Multiplier Units
Percent Amps b SCR1 40298 40358 40418 40478 40538 0.5 %
Percent Amps c SCR1 40299 40359 40419 40479 40539 0.5 %
Frequency SRC2 40300 40360 40420 40480 40540 0.1 Hz
Total pf SRC2 40301 40361 40421 40481 40541 0.00005 pf
Total kVA SRC2 40302 40362 40422 40482 40542 kVA
Total kW SRC2 40303 40363 40423 40483 40543 kW
Total kVAR SRC2 40304 40364 40424 40484 40544 kVAR
Volts ab SRC2 40305 40365 40425 40485 40545 Volts
Volts bc SRC2 40306 40366 40426 40486 40546 Volts
Volts ca SRC2 40307 40367 40427 40487 40547 Volts
Volts a SRC2 40308 40368 40428 40488 40548 Volts
Volts b SRC2 40309 40369 40429 40489 40549 Volts
Volts c SRC2 40310 40370 40430 40490 40550 Volts
Amps a SRC2 40311 40371 40431 40491 40551 Amps
Amps b SRC2 40312 40372 40432 40492 40552 Amps
Amps c SRC2 40313 40373 40433 40493 40553 Amps
Percent Amps a SRC2 40314 40374 40434 40494 40554 0.5 %
Percent Amps b SRC2 40315 40375 40435 40495 40555 0.5 %
Percent Amps c SRC2 40316 40376 40436 40496 40556 0.5 %

12.5 Word Data


Reference Tables ATS 1-5 and 6-10.

TABLE 13.

Digital State
0 Neutral
1 Source 1 Connected
2 Source 2 Connected
3 Source 1 and 2 Connected

TABLE 14.

Digital Mode
0 Test
1 Utility / Genset

A029X159 (Issue 19) 531 Copyright © 2017 Cummins Inc.


12. DMC 1500 Communication Server 1 8-2017

2 Utility / Utility
3 Genset / Genset

TABLE 15.

Digital Fault Type


0 No Faults
1 Warning

12.6 ATS 6-10 DATA


ATS Raw Data ATS 6 ATS 7 ATS 8 ATS 9 ATS 10 Multiplier Units
Device Type 40557 40617 40677 40737 40797
Mode (See Table 14 on page 531) 40558 40618 40678 40738 40798
State (See Table 13 on page 531) 40559 40619 40679 40739 40799
Fault Code 40560 40620 40680 40740 40800
Fault Type (See Table 15 on page
40561 40621 40681 40741 40801
532)
Percent Amps 40562 40622 40682 40742 40802 0.5 %
Total kW 40563 40623 40683 40743 40803
NFPA 110 (See Table 8 on page
40564 40624 40684 40744 40804
457)
NFPA Extended (See Table 9 on
40565 40625 40685 40745 40805
page 457)
Frequency Load 40566 40626 40686 40746 40806 0.1 Hz
Total pf Load 40567 40627 40687 40747 40807 0.00005 PF
Total kVA Load 40568 40628 40688 40748 40808 kVA
Total kW Load 40569 40629 40689 40749 40809 kW
Total kVAR Load 40570 40630 40690 40750 40810 kVAR
Volts ab Load 40571 40631 40691 40751 40811 Volts
Volts bc Load 40572 40632 40692 40752 40812 Volts
Volts ca Load 40573 40633 40693 40753 40813 Volts
Volts a Load 40574 40634 40694 40754 40814 Volts
Volts b Load 40575 40635 40695 40755 40815 Volts
Volts c Load 40576 40636 40696 40756 40816 Volts
Amps a Load 40577 40637 40697 40757 40817 Amps
Amps b Load 40578 40638 40698 40758 40818 Amps

Copyright © 2017 Cummins Inc. 532 A029X159 (Issue 19)


8-2017 12. DMC 1500 Communication Server 1

ATS Raw Data ATS 6 ATS 7 ATS 8 ATS 9 ATS 10 Multiplier Units
Amps c Load 40579 40639 40699 40759 40819 Amps
Percent Amps a Load 40580 40640 40700 40760 40820 0.5 %
Percent Amps b Load 40581 40641 40701 40761 40821 0.5 %
Percent Amps c Load 40582 40642 40702 40762 40822 0.5 %
Frequency SRC1 40583 40643 40703 40763 40823 0.1 Hz
Total pf SRC1 40584 40644 40704 40764 40824 0.00005 PF
Total kVA SRC1 40585 40645 40705 40765 40825 kVA
Total kW SRC1 40586 40646 40706 40766 40826 kW
Total kVAR SRC1 40587 40647 40707 40767 40827 kVAR
Volts bc SRC1 40588 40648 40708 40868 40828 Volts
Volts bc SRC1 40589 40649 40709 40869 40829 Volts
Volts ca SRC1 40590 40650 40710 40870 40830 Volts
Volts a SRC1 40591 40651 40711 40871 40831 Volts
Volts b SRC1 40592 40652 40712 40872 40832 Volts
Volts c SRC1 40593 40653 40713 40873 40833 Volts
Amps a SCR1 40594 40654 40714 40874 40834 Amps
Amps b SCR1 40595 40655 40715 40875 40835 Amps
Amps c SRC1 40596 40656 40716 40876 40836 Amps
Percent Amps a SCR1 40597 40657 40717 40777 40837 0.5 %
Percent Amps b SCR1 40598 40658 40718 40778 40838 0.5 %
Percent Amps c SCR1 40599 40659 40719 40779 40839 0.5 %
Frequency SRC2 40600 40660 40720 40780 40840 0.1 Hz
Total pf SRC2 40601 40661 40721 40781 40841 0.00005 pf
Total KVA SRC2 40602 40662 40722 40782 40842 kVA
Total kW SRC2 40603 40663 40723 40783 40843 kW
Total KVAR SRC2 40604 40664 40724 40784 40844 kVAR
Volts ab SRC2 40605 40665 40725 40785 40845 Volts
Volts bc SRC2 40606 40666 40726 40786 40846 Volts
Volts ca SRC2 40607 40667 40727 40787 40847 Volts
Volts a SRC2 40608 40668 40728 40788 40848 Volts
Volts b SRC2 40609 40669 40729 40789 40849 Volts
Volts c SRC2 40610 40670 40730 40790 40850 Volts
Amps a SRC2 40611 40671 40731 40791 40851 Amps
Amps b SRC2 40612 40672 40732 40792 40852 Amps

A029X159 (Issue 19) 533 Copyright © 2017 Cummins Inc.


12. DMC 1500 Communication Server 1 8-2017

ATS Raw Data ATS 6 ATS 7 ATS 8 ATS 9 ATS 10 Multiplier Units
Amps c SRC2 40613 40673 40733 40793 40853 Amps
Percent Amps a SRC2 40614 40674 40734 40794 40854 0.5 %
Percent Amps b SRC2 40615 40675 40735 40795 40855 0.5 %
Percent Amps c SRC2 40616 40676 40736 40796 40856 0.5 %

Copyright © 2017 Cummins Inc. 534 A029X159 (Issue 19)


13 DMC 1500 Communication Server 2
13.1 Modbus Address: 1 (Slave)
NOTICE
If an address or bit is not listed in this table, it is not implemented.

NOTICE
The external device can read 1-40 contiguous registers, write 1-40 contiguous registers, or read
diagnostic counters.

Modbus Address Bit # Alarm Event


40001 0 (LSB) Neutral Earthing 1 Fail to Open Warning
40001 1 Neutral Earthing 2 Fail to Open Warning
40001 2 Neutral Earthing 3 Fail to Open Warning
40001 3 Neutral Earthing 4 Fail to Open Warning
40001 4 Neutral Earthing 5 Fail to Open Warning
40001 5 Neutral Earthing 6 Fail to Open Warning
40001 6 Neutral Earthing 7 Fail to Open Warning
40001 7 Neutral Earthing 8 Fail to Open Warning
40001 8 Neutral Earthing 1 Fail to Closed Warning
40001 9 Neutral Earthing 2 Fail to Closed Warning
40001 10 Neutral Earthing 3 Fail to Closed Warning
40001 11 Neutral Earthing 4 Fail to Closed Warning
40001 12 Neutral Earthing 5 Fail to Closed Warning
40001 13 Neutral Earthing 6 Fail to Closed Warning
40001 14 Neutral Earthing 7 Fail to Closed Warning
40001 15 (MSB) Neutral Earthing 8 Fail to Closed Warning

Modbus Address Bit # Alarm Event


40002 0 (LSB) Neutral Earthing 1 Tripped Warning
40002 1 Neutral Earthing 2 Tripped Warning
40002 2 Neutral Earthing 3 Tripped Warning
40002 3 Neutral Earthing 4 Tripped Warning

A029X159 (Issue 19) 535 Copyright © 2017 Cummins Inc.


13. DMC 1500 Communication Server 2 8-2017

Modbus Address Bit # Alarm Event


40002 4 Neutral Earthing 5 Tripped Warning
40002 5 Neutral Earthing 6 Tripped Warning
40002 6 Neutral Earthing 7 Tripped Warning
40002 7 Neutral Earthing 8 Tripped Warning
40002 8 Undergrounded Bus Warning
40002 9 Undergrounded Bus Failure - System Shutdown
40002 10 Multiple NECs Connected
40002 11 Multiple System Grounds Connected
40002 12 Not Implemented
40002 13 Not Implemented
40002 14 Not Implemented
40002 15 (MSB) Not Implemented

Modbus Address Bit # Alarm Event


40003 0 (LSB) Station Battery Power Supply Fault
40003 1 UPS Fault
40003 2 On Station Battery Warning
40003 3 System Manual Mode Active
40003 4 Utility Failure
40003 5 Utility Out of Limits for Extended Parallel
40003 6 Common Server 2 Battery Warning
40003 7 System Emergency Stop
40003 8 Hardware Failure Warning MCM 3320
40003 9 Not Implemented
40003 10 Not Implemented
40003 11 Not Implemented
40003 12 Not Implemented
40003 13 Not Implemented
40003 14 Not Implemented
40003 15 (MSB) Not Implemented

Copyright © 2017 Cummins Inc. 536 A029X159 (Issue 19)


8-2017 13. DMC 1500 Communication Server 2

Modbus Address Bit # Alarm Event


40004 0 (LSB) Illegal Genset Node Address Assignment
40004 1 Not Implemented
40004 2 Not Implemented
40004 3 Comm Server 2 to Comm Server 1 Comm Failure
40004 4 Manufacturing Test Mode Active
40004 5 Not Implemented
40004 6 Not Implemented
40004 7 Not Implemented
40004 8 Comm Server 2 to Genset 1 Comm Failure
40004 9 Comm Server 2 to Genset 2 Comm Failure
40004 10 Comm Server 2 to Genset 3 Comm Failure
40004 11 Comm Server 2 to Genset 4 Comm Failure
40004 12 Comm Server 2 to Genset 5 Comm Failure
40004 13 Comm Server 2 to Genset 6 Comm Failure
40004 14 Comm Server 2 to Genset 7 Comm Failure
40004 15 (MSB) Comm Server 2 to Genset 8 Comm Failure

NOTICE
40005 is unused.

Modbus Address Bit # Alarm Event


40006 0 (LSB) Gen 1 Breaker Closed
40006 1 Gen 2 Breaker Closed
40006 2 Gen 3 Breaker Closed
40006 3 Gen 4 Breaker Closed
40006 4 Gen 5 Breaker Closed
40006 5 Gen 6 Breaker Closed
40006 6 Gen 7 Breaker Closed
40006 7 Gen 8 Breaker Closed
40006 8 Gen 1 Breaker Open
40006 9 Gen 2 Breaker Open
40006 10 Gen 3 Breaker Open
40006 11 Gen 4 Breaker Open

A029X159 (Issue 19) 537 Copyright © 2017 Cummins Inc.


13. DMC 1500 Communication Server 2 8-2017

Modbus Address Bit # Alarm Event


40006 12 Gen 5 Breaker Open
40006 13 Gen 6 Breaker Open
40006 14 Gen 7 Breaker Open
40006 15 (MSB) Gen 8 Breaker Open

Modbus Address Bit # Alarm Event


40007 0 (LSB) Gen 1 Running
40007 1 Gen 2 Running
40007 2 Gen 3 Running
40007 3 Gen 4 Running
40007 4 Gen 5 Running
40007 5 Gen 6 Running
40007 6 Gen 7 Running
40007 7 Gen 8 Running
40007 8 Gen 1 Fault
40007 9 Gen 2 Fault
40007 10 Gen 3 Fault
40007 11 Gen 4 Fault
40007 12 Gen 5 Fault
40007 13 Gen 6 Fault
40007 14 Gen 7 Fault
40007 15 (MSB) Gen 8 Fault

Modbus Address Bit # Alarm Event


40008 0 (LSB) Gen 1 Shut Down in Load Demand
40008 1 Gen 2 Shut Down in Load Demand
40008 2 Gen 3 Shut Down in Load Demand
40008 3 Gen 4 Shut Down in Load Demand
40008 4 Gen 5 Shut Down in Load Demand
40008 5 Gen 6 Shut Down in Load Demand
40008 6 Gen 7 Shut Down in Load Demand
40008 7 Gen 8 Shut Down in Load Demand
40008 8 Gen Start Signal On MCM 3320

Copyright © 2017 Cummins Inc. 538 A029X159 (Issue 19)


8-2017 13. DMC 1500 Communication Server 2

Modbus Address Bit # Alarm Event


40008 9 Gen Start Signal Off MCM 3320
40008 10 Gen Main Breaker Closed
40008 11 Gen Main Breaker Opened
40008 12 Utility Main Breaker Closed
40008 13 Utility Main Breaker Opened
40008 14 Utility Failure
40008 15 (MSB) Return to Utility

Modbus Address Bit # Alarm Event


40009 0 (LSB) Remote Commands Enable
40009 1 Remote Commands Disable
40009 2 Remote Test On
40009 3 Remote Test Off
40009 4 Remote Extended Parallel On
40009 5 Remote Extended Parallel Off
40009 6 Remote Transfer Inhibit On
40009 7 Remote Transfer Inhibit Off
40009 8 Remote Retransfer Inhibit On
40009 9 Remote Retransfer Inhibit Off
40009 10 Auto Genset Start Inhibit in Manual Mode Enable
40009 11 Auto Genset Start Inhibit in Manual Mode Disable
40009 12 Not Implemented
40009 13 Not Implemented
40009 14 Not Implemented
40009 15 (MSB) Not Implemented

13.2 Generator Raw Data Gen 1-5


Generator Raw Data Gen 1 Gen 2 Gen 3 Gen 4 Gen 5 Multiplier Units
Device Type 40011 40066 40121 40176 40231
Control Switch (See Table 22 on
40012 40067 40122 40177 40232
page 543)
State (See Table 16 on page 541) 40013 40068 40123 40178 40233
Fault Code 40014 40069 40124 40179 40234

A029X159 (Issue 19) 539 Copyright © 2017 Cummins Inc.


13. DMC 1500 Communication Server 2 8-2017

Generator Raw Data Gen 1 Gen 2 Gen 3 Gen 4 Gen 5 Multiplier Units
Fault Type (SeeTable 21 on page
40015 40070 40125 40180 40235
543)
Percent kW Standby 40016 40071 40126 40181 40236 0.5 %
Total kW 40017 40072 40127 40182 40237
NFPA 110 (See Table 8 on page
40018 40073 40128 40183 40238
457)
NFPA Extended (See Table 9 on
40019 40074 40129 40184 40239
page 457)
Frequency 40020 40075 40130 40185 40240 0.1 Hz
Total pf 40021 40076 40131 40186 40241 0.00005 pf
Total kVA 40022 40077 40132 40187 40242 kVA
Total kW 40023 40078 40133 40188 40243 kW
Total kVAR 40024 40079 40134 40189 40244 kVAR
Volts ab 40025 40080 40135 40190 40245 Volts
Volts bc 40026 40081 40136 40191 40246 Volts
Volts ca 40027 40082 40137 40192 40247 Volts
Volts a 40028 40083 40138 40193 40248 Volts
Volts b 40029 40084 40139 40194 40249 Volt
Volts c 40030 40085 40140 40195 40250 Volts
Amps a 40031 40086 40141 40196 40251 Amps
Amps b 40032 40087 40142 40197 40252 Amps
Amps c 40033 40088 40143 40198 40253 Amps
Percent Amps a 40034 40089 40144 40199 40254 0.5 %
Percent Amps b 40035 40090 40145 40200 40255 0.5 %
Percent Amps c 40036 40091 40146 40201 40256 0.5 %
Battery Voltage 40037 40092 40147 40202 40257 0.1 Volts
Oil Pressure 40038 40093 40148 40203 40258 0.1 kPa
Oil Temp 40039 40094 40149 40204 40259 0.1 Deg K
Coolant Temp 40040 40095 40150 40205 40260 0.1 Deg K
Fuel Rate 40041 40096 40151 40206 40261 0.001 GPH
Engine RPM 40042 40097 40152 40207 40262 RPM
Engine Starts 40043 40098 40153 40208 40263 Starts
Engine Runtime High 40044 40099 40154 40209 40264
Engine Runtime Low 40045 40100 40155 40210 40265 0.1 Sec
Total kWH High 40046 40101 40156 40211 40266

Copyright © 2017 Cummins Inc. 540 A029X159 (Issue 19)


8-2017 13. DMC 1500 Communication Server 2

Generator Raw Data Gen 1 Gen 2 Gen 3 Gen 4 Gen 5 Multiplier Units
Total kWH Low 40047 40102 40157 40212 40267 KWH
Total Fuel High 40048 40103 40158 40213 40268
Total Fuel Low 40049 40104 40159 40214 40269 0.01 GAL
Bus Frequency 40050 40105 40160 40215 40270 0.1 Hz
Bus Volts ab 40051 40106 40161 40216 40271 Volts
Bus Volts bc 40052 40107 40162 40217 40272 Volts
Bus Volts ca 40053 40108 40163 40218 40273 Volts
Bus Volts a 40054 40109 40164 40219 40274 Volts
Bus Volts b 40055 40110 40165 40220 40275 Volts
Bus Volts c 40056 40111 40166 40221 40276 Volts
Customer Faults 40057 40112 40167 40222 40277
Network Faults 40058 40113 40168 40223 40278
Customer Faults 40059 40114 40169 40224 40279
ES State (See Table 17 on page
40060 40115 40170 40225 40280
542)
Load Share State (See Table 18 on
40061 40116 40171 40226 40281
page 542)
Load Govern State kW (See Table
40062 40117 40172 40227 40282
22 on page 543)
Load Govern State kVAR (SeeTable
40063 40118 40173 40228 40283
20 on page 542)

13.3 Word Data


Reference the ATS 6-1 and 6-10 tables in Section 8.

TABLE 16.

Digital State
0 Stopped
1 Start Pending
2 Warm-up at Idle
3 Running
4 Cooldown at Rated
5 Cooldown at idle

A029X159 (Issue 19) 541 Copyright © 2017 Cummins Inc.


13. DMC 1500 Communication Server 2 8-2017

TABLE 17.

Digital ES State
0 Standby
1 Dead Bus Close
2 Synchronizing
3 Load Share
4 Load Govern

TABLE 18.

Digital Load Share State


0 Not in Load Share
1 Track Load
2 Ramp Load
3 Ramp Unload
4 Load Demand Shutdown

TABLE 19.

Digital Load Govern State kW


0 NA
1 Ramp Load
2 Track Target Load
3 Ramp Unload
4 Ramp Unload Done

TABLE 20.

Digital Load Govern State kVAR


0 NA
1 Ramp Load
2 Track Target Load
3 Ramp Unload
4 Ramp Unload Done

Copyright © 2017 Cummins Inc. 542 A029X159 (Issue 19)


8-2017 13. DMC 1500 Communication Server 2

TABLE 21.

Digital Fault Type


0 Normal
1 Warning
2 Derate
3 Shutdown with Cooldown
4 Shutdown

TABLE 22.

Digital Control Switch


0 Off
1 Manual
2 Automatic

13.4 Generator Raw Data Gen 6-8


Generator Raw Data Gen 6 Gen 7 Gen 8 Multiplier Units
Device Type 40286 40341 40396
Control Switch (See Table 22 on page 543) 40287 40342 40397
State (See Table 16 on page 541) 40288 40343 40398
Fault Code 40289 40344 40399
Fault Type (See Table 21 on page 543) 40290 40345 40400
Percent kW Standby 40291 40346 40401 0.5 %
Total kW 40292 40347 40402
NFPA 110 (See Table 10 on page 458) 40293 40348 40403
NFPA Extended (See Table 11 on page
40294 40349 40404
458)
Frequency 40295 40350 40405 0.1 Hz
Total pf 40296 40351 40406 0.00005 PF
Total kVA 40297 40352 40407 kVA
Total kW 40298 40353 40408 kW
Total kVAR 40299 40354 40409 kVAR
Volts ab 40300 40355 40410 Volts
Volts bc 40301 40356 40411 Volts
Volts ca 40302 40357 40412 Volts

A029X159 (Issue 19) 543 Copyright © 2017 Cummins Inc.


13. DMC 1500 Communication Server 2 8-2017

Generator Raw Data Gen 6 Gen 7 Gen 8 Multiplier Units


Volts a 40303 40358 40413 Volts
Volts b 40304 40359 40414 Volts
Volts c 40305 40360 40415 Volts
Amps a 40306 40361 40416 Amps
Amps b 40307 40362 40417 Amps
Amps c 40308 40363 40418 Amps
Percent Amps a 40309 40364 40419 0.5 %
Percent Amps b 40310 40365 40420 0.5 %
Percent Amps c 40311 40366 40421 0.5 %
Battery Voltage 40312 40367 40422 0.1 Volts
Oil Pressure 40313 40368 40423 0.1 kPa
Oil Temp 40314 40369 40424 0.1 Deg K
Coolant Temp 40315 40370 40425 0.1 Deg K
Fuel Rate 40316 40371 40426 0.001 GPH
Engine RPM 40317 40372 40427 RPM
Engine Starts 40318 40373 40428 Starts
Engine Runtime High 40319 40374 40429
Engine Runtime Low 40320 40375 40430 0.1 Sec
Total kWH High 40321 40376 40431
Total kWH Low 40322 40377 40432 KWH
Total Fuel High 40323 40378 40433
Total Fuel Low 40324 40379 40434 0.01 GAL
Bus Frequency 40325 40380 40435 0.1 Hz
Bus Volts ab 40326 40381 40436 Volts
Bus Volts bc 40327 40382 40437 Volts
Bus Volts ca 40328 40383 40438 Volts
Bus Volts a 40329 40384 40439 Volts
Bus Volts b 40330 40385 40440 Volts
Bus Volts c 40331 40386 40441 Volts
Customer Faults 40332 40387 40442
Network Faults 40333 40388 40443
Customer Faults 40334 40389 40444
ES State (See Table 17 on page 542) 40335 40390 40445

Copyright © 2017 Cummins Inc. 544 A029X159 (Issue 19)


8-2017 13. DMC 1500 Communication Server 2

Generator Raw Data Gen 6 Gen 7 Gen 8 Multiplier Units


Load Share State (See Table 18 on page
40336 40391 40446
542)
Load Govern State kW (See Table 19 on
40337 40392 40447
page 542)
Load Govern State kVAR (See Table 20 on
40338 40393 40448
page 542)

A029X159 (Issue 19) 545 Copyright © 2017 Cummins Inc.


13. DMC 1500 Communication Server 2 8-2017

This page is intentionally blank.

Copyright © 2017 Cummins Inc. 546 A029X159 (Issue 19)


14 MCM3320 Modbus Register Map
14.1 Modbus Communications
This section defines the Modbus communications interface. Serial communications use an RTU (Remote
Terminal Unit) two-wire RS485 multi-drop network configuration described in the Modbus Protocol
Reference Guide. The Cummins control is a Slave unit.

14.2 Reference Documents


1. “Modbus Over Serial Line Specification and Implementation Guide V1.02" describes the lower levels
of Modbus protocol.
2. “Modbus Application Protocol Specification V1.1b3" describes the application layer of the Modbus
protocol.

14.3 Serial Port Configuration


The port communications occur, by default, at a baud rate of 19200 using eight data bits, one stop-bit with
even parity, and are configurable via MON and PCCNet logically.

14.4 Device Addresses


The PLC is the Master device in the Modbus network. The Modbus node address is configurable and is
set to node 1 by default.

14.5 Power-Up Time


The MCM3320 is capable of supporting communication transactions within 10 seconds following initial
power-up.

14.6 Response Time


The controller responds within 100 ms of a request for information from the Master.

14.7 Data Formatting


The format for each register is defined in the Modbus register table.
All data parameters are transmitted as registers. All registers are two 8 bit bytes in length (16 bits per
register). If a register requires more than 16 bits, then, the subsequent registers are also used. Therefore,
with a 32 bit register X and X+1, the X register contains the upper 16 bits of data and the X+1 register
contains the lower 16 bits. A register with 1 bit of data uses the least significant bit of a 16 bit register.
For all discrete data referenced a by bit number, the least significant bit for the register is numbered as 0
inch and the most significant bit as 15 inch. For all fault statuses and event statuses, a 1 inch indicates the
fault or event is active and a 0 inch indicates inactive.

A029X159 (Issue 19) 547 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

14.8 Modbus Activity LED


The Modbus activity LED is on when either the control is receiving a Modbus packet or sending a Modbus
packet. It is also on when a protocol timer is in timer mode. This precedes a protocol switch on the SCI1
port. Otherwise, the LED is off.

14.9 Supported Functions


The controller is only capable of processing the following Modbus data and control function queries from
the Master:
• Read holding registers (Function Code 03)
• Preset single register (Function Code 06)
• Diagnostics (Function Code 08)
• Preset multiple registers (Function Code 16)
The control responds to any query containing a function code, other than codes 03, 06, 08 and 16, by
sending an exception response with the exception code set to 01 (Illegal Function).
The control responds to any read of a single address that is not defined in this specification by sending an
exception response with the exception code set to 02 (Illegal Address).
The control responds to any read of a block of 2 or more addresses containing an address that is not
defined in this specification by returning data of 0xFFFF for that address.
The control responds to Preset Single Register and Preset Multiple Register functions when the data is
out of bounds by sending an exception response with the exception code set to 03 (Illegal Data Value).

14.10 Holding Register Function


The control provides the ability to read all read only and read/write registers in the Modbus Registers
Table via the Holding Register function. From 1 to 40 contiguous registers can be read at a time. If an
attempt is made to read a register that's not available, then an error is returned and none of the data will
be returned.

14.11 Preset Single/Preset Multiple Registers Function


The control provides the ability to write to (preset) Read/Write registers in the Modbus registers table via
both the preset single register (Function Code 06) and the preset multiple registers (Function Code 16). A
write to a single register can be performed by the Master using the Modbus data and control function
query preset single register (Function Code 06). For writes requiring writes to 1 to 40 contiguous registers,
the Master uses the Modbus data and control function query called preset multiple registers (Function
Code 16). If a write attempt is made and any of the data is invalid or if an attempt is made to write to a
register that's not available, then an error is returned and none of the data will be written.

14.12 Diagnostic Counters


The following diagnostic counters is also available via the Modbus diagnostic function (Function Code 08).
The following parameters are updated and available via MON and Modbus logical access. A single logical
is also available to clear all counters.
• Bus Message Count - Total Modbus packets on bus
• CRC Errors Count - Total Modbus packets received with a bad CRC

Copyright © 2017 Cummins Inc. 548 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

• Exception Count - Total Modbus packets received where an exception was sent back
• No Response Count - Total Modbus packets received where no response sent back
• Slave Message Count - Total Modbus packets on bus addressed to this node

14.13 Register Maps


Addresses were assigned to maintain compatibility with the existing Modlon gateway where applicable.
The following conventions are followed:
• 40xxx - Genset control registers
• 41xxx - Transfer switch control register
• 42xxx - Master control registers (MCM3320)
• 4x0xx - General data registers (volts, current, etc.) primarily for genset bus
• 4x1xx - General data registers (volts, current, etc.) primarily for utility bus
• 4x2xx - Configuration and status registers - Block 1
• 4x3xx - Settings - Block 1
• 4x4xx - Settings - Block 2
• 4x5xx - Bitmap
• 4x6xx - Switch I/O
• 4x7xx - Configuration and status registers - Block 2

14.14 Application Layer


The application layer processes the packet. Four functions are supported: Read Hold Registers, Set
Single Register, Modbus Loopback, and Set Multiple Registers. If the request packet specifies an
unsupported function, then an illegal function response is returned. See the "Modbus Application Protocol
Specification" to see how the request and response packets are formatted and how each function
processes the data.

14.15 Read Hold Registers


Given a starting address and the quantity of registers desired, this function gets the data, formats it if
required, and writes it to the TX buffer. If any register in the range is not supported, then an error is
returned.

14.16 Set Single Register


Given a register address and data, this function verifies that the data is within range; then if OK, writes the
data.

A029X159 (Issue 19) 549 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

14.17 Modbus Loopback


This function performs Modbus diagnostic functionality. Some of the functionality defined here is also
available via MON and PCCNet logicals. See the "Diagnostic Counters" section of this document for
details. The Loopback function supports:
• 0x00 Return Query Data
• 0x01 Restart
• 0x04 Force Listen Only Mode
• 0x0A Clear Counter
• 0x0B Return Bus Message Count
• 0x0C Return Bus Communication Error Count (bad CRC)
• 0x0D Return Bus Exception Error Count
• 0x0E Return Slave Message Count
• 0x0F Return Slave No Response Count

14.18 Set Multiple Registers


Given a starting address, the quantity of registers, and two bytes of data for each register, this function
verifies that all the data is within range; then if OK, writes all data. If any register in the range is not
supported or any of the data is out of range then an error is returned and no data is written. A 32-bit
parameter is written using "Write Multiple Register" (Command Code 16) only. Using "Write Single
Register" (Command Code 06) returns an exception code 2 - Illegal Address. If both registers are not in
the same block, the control sends an exception code 2-Illegal Address.

14.19 Modbus Register Table


NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

Copyright © 2017 Cummins Inc. 550 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function

Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Logical
MB logical Read / Offset: 0 address to be
42001 Upper Limit: Communications
Read Address Write read via
Size (bits):16 65535.000 Modbus
Sign: U Default: 0
Multiplier:
Unit: NA
1.000000000000 Logical data to
MB Logical Read Lower Limit:
42002 Offset: 0 be read via Communications
Read Data Only Upper Limit:
Size (bits): 32 Modbus
Default:
Sign: U
Save
configuration
parameters or
adjustments to
non-volatile
memory.
0: Do Nothing Perform Save
Save Read / Controller
42004 1: Save Trims Trims after all
Adjustments Write Information
Default: Do Nothing configurations
have been
updated. Do
not save trims
unless a
change has
occurred.
Multiplier:
Unit: NA
1.000000000000 Hard coded
Read Lower Limit:
42009 Device Type Offset: 0 device type id= Communications
Only Upper Limit:
Size (bits):16 52 (0x0034)
Default:
Sign: U
Multiplier:
Unit: NA
.000100000000
Software Read Lower Limit: Software Controller
42010 Offset: 0
Version Only Upper Limit: version number Information
Size (bits):16
Default:
Sign: U
0: Time Delay Start
1: Time Delay Stop Indicates state
Genset Run
Read of the PTC Operating
42011 Sequence 2: Stop
Only generator set Mode
State 3: Run run sequence
Default:
Multiplier: The most
Unit: NA
1.000000000000 recently
Current Fault Read Lower Limit: Fault and Event
42012 Offset: 0 occurring fault
Status Only Upper Limit: Information
Size (bits):16 which is still
Default: active
Sign: U

A029X159 (Issue 19) 551 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Unavailable Energization
Genset Bus Read 1: Dead status of
42017 PTC Sensors
Status Only 2: Live generator Set
Default: bus

Multiplier:
Unit: Volts
1.000000000000
Genset L1N Read Lower Limit: Volts Generator set
42018 Offset: 0 Voltage
Voltage Only Upper Limit: Volts L1N voltage
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L2N Read Lower Limit: Volts Generator set
42019 Offset: 0 Voltage
Voltage Only Upper Limit: Volts L2N voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L3N Read Lower Limit: Volts Generator set
42020 Offset: 0 Voltage
Voltage Only Upper Limit: Volts L3N voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
Genset LN 1.000000000000 Generator set
Read Lower Limit: Volts
42021 Average Offset: 0 LN average Voltage
Only Upper Limit: Volts
Voltage Size (bits): 16 voltage
Default:
Sign: U
Multiplier:
1.000000000000 Unit: Volts
Genset L1L2 Read Offset: 0 Lower Limit: Volts Generator set
42022 Voltage
Voltage Only Upper Limit: Volts L1L2 voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L2L3 Read Lower Limit: Volts Generator set
42023 Offset: 0 Voltage
Voltage Only Upper Limit: Volts L2L3 voltage
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L3L1 Read Lower Limit: Volts Generator set
42024 Offset: 0 Voltage
Voltage Only Upper Limit: Volts L3L1 voltage.
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Volts
Genset LL 1.000000000000 Generator set
Read Lower Limit: Volts
42025 Average Offset: 0 LL Average Voltage
Only Upper Limit: Volts
Voltage Size (bits): 16 voltage
Default
Sign: U

Copyright © 2017 Cummins Inc. 552 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: Amps
1.000000000000
Genset L1 Read Lower Limit: Amps Generator set
42026 Offset: 0 Current
Current Only Upper Limit: Amps L1 current
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Genset L2 Read Lower Limit: Amps Generator set
42027 Offset: 0 Current
Current Only Upper Limit: Amps L2 current
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Genset L3 Read Lower Limit: Amps Generator set
42028 Offset: 0 Current
Current Only Upper Limit: Amps L3 current
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Amps
Genset 1.000000000000 Generator set
Read Lower Limit: Amps
42029 Average Offset: 0 average Current
Only Upper Limit: Amps
Current Size (bits): 16 current
Default:
Sign: U
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: kW Generator set
42030 Genset L1 kW Offset: 0 Power
Only Upper Limit: kW L1 kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: kW Generator set
42031 Genset L2 kW Offset: 0 Power
Only Upper Limit: kW L2 kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: kW Generator set
42032 Genset L3 kW Offset: 0 Power
Only Upper Limit: kW L3 kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Genset Total Read Lower Limit: kW Generator set
42033 Offset: 0 Power
kW Only Upper Limit: kW total kW
Size (bits): 16
Default:
Sign: S

A029X159 (Issue 19) 553 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: kVAR
1.000000000000
Genset L1 Read Lower Limit: kVAR Generator set
42034 Offset: 0 Power
kVAR Only Upper Limit: kVAR L1 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Genset L2 Read Lower Limit: kVAR Generator set
42035 Offset: 0 Power
kVAR Only Upper Limit: kVAR L2 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Genset L3 Read Lower Limit: kVAR Generator set
42036 Offset: 0 Power
kVAR Only Upper Limit: kVAR L3 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Genset Total Read Lower Limit: kVAR Generator set
42037 Offset: 0 Power
kVAR Only Upper Limit: kVAR total kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: NA
1.000000000000
Genset Total Read Lower Limit: Generator set
42038 Offset: 0 Power
Power Factor Only Upper Limit: L1 power factor
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: kVA Generator set
42039 Genset L1 kVA Offset: 0 Power
Only Upper Limit: kVA L1 kVA
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: kVA Generator set
42040 Genset L2 kVA Offset: 0 Power
Only Upper Limit: kVA L2 kVA
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: kVA Generator set
42041 Genset L3 kVA Offset: 0 Power
Only Upper Limit: kVA L3 kVA
Size (bits): 16
Default:
Sign: U

Copyright © 2017 Cummins Inc. 554 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: kVA
1.000000000000
Genset Total Read Lower Limit: kVA Generator set
42042 Offset: 0 Power
kVA Only Upper Limit: kVA total kVA
Size (bits): 16
Default:
Sign: U
Multiplier: Generator set
Unit: Hz
.100000000000 line frequency
MB Genset Read Lower Limit: Hz
42043 Offset: 0 scaled by 10 = Communications
Frequency Only Upper Limit: Hz
Size (bits): 16 1Hz for
Default: Modbus
Sign: U
Multiplier:
Unit: kWh Generator set
1.000000000000
Genset Total Read Lower Limit: kWh total negative
42044 Offset: 0 Energy
Negative kWh Only Upper Limit: kWh kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kWh Generator set
1.000000000000
Genset Total Read Lower Limit: kWh total positive
42046 Offset: 0 Energy
Positive kWh Only Upper Limit: kWh kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kWh
1.000000000000 Generator set
Genset Total Read Lower Limit: kWh
42048 Offset: 0 total net kWh Energy
Net kWh Only Upper Limit: kWh
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier:
Unit: kVARh Generator set
Genset Total 1.000000000000
Read Lower Limit: kVARh total negative
42050 Negative Offset: 0 Energy
Only Upper Limit: kVARh kVARh
kVARh Size (bits): 32
Default: accumulation
Sign: U
Multiplier:
Unit: kVARh Generator set
1.00000000000
Genset Total Read Lower Limit: kVARh total positive
40052 0Offset: 0 Energy
Positive kVARh Only Upper Limit: kVARh kVARh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kVARh Generator set
1.000000000000
Genset Total Read Lower Limit: kVARh total net
42054 Offset: 0 Energy
Net kVARh Only Upper Limit: kVARh kVARh
Size (bits): 32 accumulation
Default:
Sign: S

A029X159 (Issue 19) 555 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: kVARh
1.000000000000 Generator set
Genset Total Read Lower Limit: kVARh
42056 Offset: 0 total kVAh Energy
kVAh Only Upper Limit: kVARh
Size (bits): 32 accumulation
Default:
Sign: U
Calculated
Multiplier: amps which
Unit: Amps
Genset 1.000000000000 represent 100-
Read Lower Limit: Amps
42058 Available Offset: 0 % generator Current
Only Upper Limit: Amps
Current Size (bits): 16 set bus current
Default: - used by
Sign: U
bargraph
Generator set
Multiplier: L1 current as
Unit: %
Genset L1 .100000000000 percent of
Read Lower Limit: %
42059 Current Offset: 0 generator Set Current
Only Upper Limit: %
Percent Size (bits): 16 total current
Default: capacity - used
Sign: S
by bargraph
Generator set
Multiplier: L2 current as
Unit: %
Genset L2 .100000000000 percent of
Read Lower Limit: %
42060 Current Offset: 0 generator Set Current
Only Upper Limit: %
Percent Size (bits): 16 total current
Default: capacity - used
Sign: U
by bargraph
Generator set
Multiplier: L3 current as
Unit: %
Genset L3 .100000000000 percent of
Read Lower Limit: %
42061 Current Offset: 0 generator Set Current
Only Upper Limit: %
Percent Size (bits): 16 total current
Default: capacity - used
Sign: U
by bargraph

Multiplier: Generator set


Unit: % kW as percent
.100000000000
Genset Total Read Lower Limit: % of total
42062 Offset: 0 Power
kW Percent Only Upper Limit: % generator set
Size (bits): 16 capacity - used
Default:
Sign: S by bargraph
Generator set
Multiplier: frequency as
Unit: %
Genset .100000000000 percent of
Read Lower Limit: %
42063 Frequency Offset: 0 system Frequency
Only Upper Limit: %
Percent Size (bits): 16 frequency -
Default: used by
Sign: U
bargraph

Copyright © 2017 Cummins Inc. 556 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: %
.100000000000
Genset L1L2 Read Lower Limit: % Generator set
42064 Offset: 0 Voltage
Voltage% Only Upper Limit: % L1L2 voltage%
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: %
.100000000000
Genset L2L3 Read Lower Limit: % Generator set
42065 Offset: 0 Voltage
Voltage% Only Upper Limit: % L2L3 voltage %
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: %
.100000000000
Genset L3L1 Read Lower Limit: % Generator set
42066 Offset: 0 Voltage
Voltage% Only Upper Limit: % L3L1 voltage%
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kW
1.000000000000 Generator set
Genset Total Read Lower Limit: kW
42070 Offset: 0 total kW in 32 Power
kW_32bit Only Upper Limit: kW
Size (bits): 32 bit
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000 Generator set
Genset Total Read Lower Limit: kVAR
42072 Offset: 0 total kVAR in Power
kVAR_32bit Only Upper Limit: kVAR
Size (bits): 32 32 bit
Default:
Sign: S
Multiplier:
Unit: kVA
1.000000000000 Generator set
Genset Total Read Lower Limit: kVA
42074 Offset: 0 total kVA in 32 Power
kVA_32bit Only Upper Limit: kVA
Size (bits): 32 bit
Default:
Sign: U
0: Unavailable
1: Dead Energization
Utility Bus Read
42117 status of the PTC Sensors
Status Only 2: Live utility bus
Default:
Multiplier:
Unit: Volts
1.000000000000
Utility L1N Read Lower Limit: Volts Utility L1N
42118 Offset: 0 Voltage
Voltage Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L2N Read Lower Limit: Volts Utility L2N
42119 Offset: 0 Voltage
Voltage Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U

A029X159 (Issue 19) 557 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: Volts
1.000000000000
Utility L3N Read Lower Limit: Volts Utility L3N
42120 Offset: 0 Voltage
Voltage Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
Utility LN 1.000000000000 Utility LN
Read Lower Limit: Volts
42121 Average Offset: 0 average Voltage
Only Upper Limit: Volts
Voltage Size (bits): 16 voltage
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L1L2 Read Lower Limit: Volts Utility L1L2
42122 Offset: 0 Voltage
Voltage Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L2L3 Read Lower Limit: Volts Utility L2L3
42123 Offset: 0 Voltage
Voltage Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L3L1 Read Lower Limit: Volts Utility L3L1
42124 Offset: 0 Voltage
Voltage Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
Utility LL 1.000000000000 Utility LL
Read Lower Limit: Volts
42125 Average Offset: 0 average Voltage
Only Upper Limit: Volts
Voltage Size (bits): 16 voltage
Default:
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Utility L1 Read Lower Limit: Amps Utility L1
42126 Offset: 0 Current
Current Only Upper Limit: Amps current
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Utility L2 Read Lower Limit: Amps Utility L2
42127 Offset: 0 Current
Current Only Upper Limit: Amps current
Size (bits): 16
Default:
Sign: U

Copyright © 2017 Cummins Inc. 558 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: Amps
1.000000000000
Utility L3 Read Lower Limit: Amps Utility L3
42128 Offset: 0 Current
Current Only Upper Limit: Amps current
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Utility Average Read Lower Limit: Amps Utility average
42129 Offset: 0 Current
Current Only Upper Limit: Amps current
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: kW
42130 Utility L1 kW Offset: 0 Utility L1 kW Power
Only Upper Limit: kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: kW
42131 Utility L2 kW Offset: 0 Utility L2 kW Power
Only Upper Limit: kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: kW
42132 Utility L3 kW Offset: 0 Utility L3 kW Power
Only Upper Limit: kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: kW
42133 Utility Total kW Offset: 0 Utility total kW Power
Only Upper Limit: kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Read Lower Limit: kVAR
42134 Utility L1 kVAR Offset: 0 Utility L1 kVAR Power
Only Upper Limit: kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Read Lower Limit: kVAR
42135 Utility L2 kVAR Offset: 0 Utility L2 kVAR Power
Only Upper Limit: kVAR
Size (bits): 16
Default:
Sign: S

A029X159 (Issue 19) 559 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: kVAR
1.000000000000
Read Lower Limit: kVAR
42136 Utility L3 kVAR Offset: 0 Utility L3 kVAR Power
Only Upper Limit: kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Utility Total Read Lower Limit: kVAR Utility total
42137 Offset: 0 Power
kVAR Only Upper Limit: kVAR kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: NA
1.000000000000
Utility Total Read Lower Limit: Utility L1 power
42138 Offset: 0 Power
Power Factor Only Upper Limit: factor
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: kVA
42139 Utility L1 kVA Offset: 0 Utility L1 kVA Power
Only Upper Limit: kVA
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: kVA
42140 Utility L2 kVA Offset: 0 Utility L2 kVA Power
Only Upper Limit: kVA
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: kVA
42141 Utility L3 kVA Offset: 0 Utility L3 kVA Power
Only Upper Limit: kVA
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Utility Total Read Lower Limit: kVA
42142 Offset: 0 Utility total kVA Power
kVA Only Upper Limit: kVA
Size (bits): 16
Default:
Sign: U
Multiplier: Utility line
Unit: Hz
1.000000000000 frequency
MB Utility Read Lower Limit: Hz
42143 Offset: 0 scaled by 10 = Communications
Frequency Only Upper Limit: Hz
Size (bits): 16 1Hz for
Default: Modbus
Sign: U

Copyright © 2017 Cummins Inc. 560 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: kWh
1.000000000000 Utility total
Utility Total Read Lower Limit: kWh
42144 Offset: 0 negative kWh Energy
Negative kWh Only Upper Limit: kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kWh
1.000000000000 Utility total
Utility Total Read Lower Limit: kWh
42146 Offset: 0 positive kWh Energy
Positive kWh Only Upper Limit: kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kWh
1.000000000000 Utility total net
Utility Total Net Read Lower Limit: kWh
42148 Offset: 0 kWh Energy
kWh Only Upper Limit: kWh
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier:
Unit: kVARh Utility total
1.000000000000
Utility Total Read Lower Limit: kVARh negative
42150 Offset: 0 Energy
Negative Only Upper Limit: kVARh kVARh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kVARh
1.000000000000 Utility total
Utility Total Read Lower Limit: kVARh
42152 Offset: 0 positive kVARh Energy
Positive kVARh Only Upper Limit: kVARh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kVARh
1.000000000000 Utility total net
Utility Total Net Read Lower Limit: kVARh
42154 Offset: 0 kVARh Energy
kVARh Only Upper Limit: kVARh
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier:
Unit: kVAh
1.000000000000 Utility total
Utility Total Read Lower Limit: kVAh
42156 Offset: 0 kVARh Energy
kVAh Only Upper Limit: kVAh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kW Sum of
1.000000000000
System Total Read Lower Limit: kW generator set
42158 Offset: 0 Power
kW Only Upper Limit: kW bus and utility
Size (bits): 16 bus kW
Default:
Sign: S

A029X159 (Issue 19) 561 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: kVAR Sum of
1.000000000000
System Total Read Lower Limit: kVAR generator set
42159 Offset: 0 Power
kVAR Only Upper Limit: kVAR bus and utility
Size (bits): 16 bus kVAR
Default:
Sign: S

Multiplier: System total


Unit: NA power factor
.010000000000
System Total Read Lower Limit: (totalized value
42160 Offset: 0 Power
Power Factor Only Upper Limit: of utility bus
Size (bits): 16 plus generator
Default:
Sign: S set bus)
Multiplier:
Unit: kVA Sum of
1.000000000000
System Total Read Lower Limit: kVA generator set
42161 Offset: 0 Power
kVA Only Upper Limit: kVA bus and utility
Size (bits): 16 bus kVA
Default:
Sign: U

Multiplier: Utility L1
Unit: % current as % of
Utility L1 .100000000000
Read Lower Limit: % utility total
42162 Current Offset: 0 Current
Only Upper Limit: % current
Percent Size (bits): 16
Default: capacity - used
Sign: U by bargraph

Multiplier: Utility L2
Unit: % current as % of
Utility L2 .100000000000
Read Lower Limit: % utility total
42163 Current Offset: 0 Current
Only Upper Limit: % current
Percent Size (bits): 16
Default: capacity - used
Sign: U by bargraph

Multiplier: Utility L3
Unit: % current as
Utility L3 .100000000000
Read Lower Limit: % as % of utility
42164 Current Offset: 0 Current
Only Upper Limit: % total current
Percent Size (bits): 16
Default: capacity - used
Sign: U by bargraph
Multiplier: Utility total kW
Unit: %
.100000000000 as percent of
Utility Total kW Read Lower Limit %
42165 Offset: 0 total utility Power
Percent Only Upper Limit: %
Size (bits): 16 capacity - used
Default: by bargraph
Sign: S
Utility
Multiplier: frequency as
Unit: %
Utility .100000000000 percent of
Read Lower Limit: %
42166 Frequency Offset: 0 system Frequency
Only Upper Limit: %
Percent Size (bits): 16 frequency -
Default: used by
Sign: U
bargraph

Copyright © 2017 Cummins Inc. 562 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: %
.100000000000
Utility L1L2 Read Lower Limit: % Utility L1L2
42167 Offset: 0 Voltage
Voltage % Only Upper Limit: % voltage %
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: %
.100000000000
Utility L2L3 Read Lower Limit: % Utility L2L3
42168 Offset: 0 Voltage
Voltage % Only Upper Limit: % voltage %
Size (bits): 16
Default:
Sign: U

Addr. System Name Access Specifications Description Function


Multiplier:
Unit:%
.100000000000
Utility L3L1 Read Lower Limit: % Utility L3L1
42169 Offset: 0 Voltage
Voltage % Only Upper Limit: % voltage %
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kW
1.000000000000
Utility Total kW Read Lower Limit: kW
42170 Offset: 0 Utility total kW Power
_32 bit Only Upper Limit: kW
Size (bits): 32
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Utility total Read Lower Limit: kVAR Utility total
42172 Offset: 0 Power
kVAR_32 bit Only Upper Limit: kVAR kVAR in 32 bit
Size (bits): 32
Default:
Sign: S
Multiplier:
Unit: kVA
1.000000000000
Utility total Read Lower Limit: kVA Utility total kVA
42174 Offset: 0 Power
kVA_32 bit Only Upper Limit: kVA in 32 bit
Size (bits): 32
Default:
Sign: U
Multiplier:
Unit: kW Sum of
1.000000000000
System Total Read Lower Limit: kW generator bus
42176 Offset: 0 Power
kW_32 bit Only Upper Limit: kW and utility bus
Size (bits): 32 kW in 32 bit
Default:
Sign: S
Multiplier:
Unit: kVAR Sum of
1.000000000000
System Total Read Lower Limit: kVAR generator bus
42178 Offset: 0 Power
kVAR_32 bit Only Upper Limit: kVAR and utility bus
Size (bits): 32 kVAR in 32 bit
Default:
Sign: S

A029X159 (Issue 19) 563 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: kVA Sum of
1.000000000000
System Total Read Lower Limit: kVA generator set
42180 Offset: 0 Power
kVA_32 bit Only Upper Limit: kVA and utility bus
Size (bits): 32 kVA in 32 bit
Default:
Sign: U
Multiplier:
Unit: NA Number of
1.000000000000
Total Number Read Lower Limit: generator sets System
42200 Offset: 0
of Gensets Only Upper Limit: with non–zero Information
Size (bits): 16 rating entered
Default:
Sign: U
Multiplier:
Unit: kW
1.000000000000 Sum of the
Total System Read Lower Limit: kW System
42201 Offset: 0 generator set
Capacity Only Upper Limit: kW Information
Size (bits): 16 kW ratings
Default:
Sign: U

Multiplier: Sum of the


Unit: kW generator set
1.000000000000
Total Online Read Lower Limit: kW kW ratings for System
42202 Offset: 0
Capacity Only Upper Limit: kW generator sets Information
Size (bits): 16 which are
Default:
Sign: S Online
Multiplier:
Unit: seconds Countdown
Programmed .100000000000
Read Lower Limit: seconds value of the
42203 Transition Offset: 0 PTC Timers
Only Upper Limit: seconds programmed
Timer Size (bits): 16
Default: transition timer
Sign: U
Multiplier:
Unit: seconds
.100000000000 Countdown
Read Lower Limit: seconds
42204 Transfer Timer Offset: 0 value of the PTC Timers
Only Upper Limit: seconds
Size (bits): 16 transfer timer
Default:
Sign: U
Multiplier:
Unit: seconds
.100000000000 Countdown
Retransfer Read Lower Limit: seconds
42205 Offset: 0 value of the PTC Timers
Timer Only Upper Limit: seconds
Size (bits): 16 retransfer timer
Default:
Sign: U
Multiplier:
Unit: seconds Countdown
.100000000000
Maximum Read Lower Limit: seconds value of the
42206 Offset: 0 PTC Timers
Parallel Timer Only Upper Limit: seconds maximum
Size (bits): 16 parallel timer
Default:
Sign: U

Copyright © 2017 Cummins Inc. 564 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: kW kW Control
1.000000000000
Read Lower Limit: kW reference value Master Load
42207 kW Reference Offset: 0
Only Upper Limit: kW for utility Control
Size (bits): 16 paralleling
Default:
Sign: S
0: Not Available
Utility 1: Not Unloaded Indicates utility
Read Master Load
42208 Unloaded unloaded
Only 2: Unloaded Control
Status status
Default:
0: Not Available Indicates
Genset 1: Not Unloaded
Read generator set Master Load
42209 Unloaded
Only 2: Unloaded unloaded Control
Status
Default: status

0: Not Available
1: TD Start
2: TD Stop
3: TD Programmed Transition
4: TD Transfer
5: TD Retransfer
6: Synchronizing
7: Sync Check OK
8: Inhibit Indicates what
Read state the System
42210 System State 9: Unassigned
Only control is Information
10: Ramp Upload currently IN
11. Ramp Load
12: Manual
13: Utility Failure
14: Test
15: Standby
16: Factory Test
17: Extended Parallel
Default: Not Available
0: Manual
1: Normal Indicates the
2: Normal Override Current PTC
PTC Operating Read Operating PTC Operating
42211 3: Test
Mode Only mode. Read/ Mode
4: Utility Fail Write on comp
5: Extended Parallel mode.
Default:
Multiplier:
Unit: seconds
Active .100000000000 Countdown
Read Lower Limit: seconds
42212 Transition Offset: 0 timer value of PTC Timers
Only Upper Limit: seconds
Timer Size (bits): 16 active timer
Default:
Sign: U

A029X159 (Issue 19) 565 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA Indicates the
1.000000000000
Hardware Read Lower Limit: hardware
42213 Offset: 0 Discrete Inputs
Version Only Upper Limit: version of the
Size (bits): 16 board
Default:
Sign: U
Multiplier: Unit: seconds
1.000000000000 Lower Limit: .000 sec. Amount of time
Controller On Read Offset: 0 in seconds the Controller
42214 Upper Limit:
Time Only controller has Information
Size (bits): 32 4294967295.000 sec been powered
Sign: U Default: 0
Indicates
0: Not Available availability of
Genset 1: Available generator set
Read
42216 Availability for Loading, as PTC Availability
Only 2: Unknown
Status determined by
Default: the generator
set sensors
Indicates
0: Not Available availability of
Utility 1: Available utility for
Read
42217 Availability loading as PTC Availability
Only 2: Unknown
Status determined by
Default: the utility
sensors
0: Open
1: Closed Generator set
Gen CB Read
42218 breaker Breaker Control
Position Status Only 2: Not Available position
Default:
0: Open
Util CB Read 1: Closed Utility breaker
42219 Breaker Control
Position Status Only 2: Not Available position
Default:
Multiplier:
Unit: kVAR kVAR control
1.000000000000
kVAR Load Read Lower Limit: kVAR reference value Master Load
42220 Offset: 0
Reference Only Upper Limit: kVAR for extended Control
Size (bits): 16 paralleling
Default:
Sign: S
Multiplier: Engineering
kVAR Load Unit: %
.010000000000 units value for
Setpoint Engr Read Lower Limit: %
42221 Offset: 0 the kVAR load Analog Inputs
Units Display Only Upper Limit: %
Size (bits): 16 setpoint analog
Value Default:
Sign: U Input

Copyright © 2017 Cummins Inc. 566 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Engineering
kW Load Unit: %
.010000000000 units value for
Setpoint Engr Read Lower Limit: %
42222 Offset: 0 the kW load Analog Inputs
Units Display Only Upper Limit: %
Size (bits): 16 setpoint analog
Value Default:
Sign: S input

Multiplier: Power factor


Unit: NA setpoint analog
.010000000000
Power Factor Read Lower Limit: input value
42223 Offset: 0 Analog Inputs
Setpoint Only Upper Limit: (uses kVAR
Size (bits): 16 load setpoint
Default:
Sign: S analog input)
0: Not Enabled
Indicates the
1: No Source Connected connected
Read 2: Utility Connected state of power PTC State
42224 PTC State
Only 3: Genset Connected transfer Machine
4: Paralleled control. read /
write in comp.
Default:
Indicates
0: Not Allowed whether any
Sync Check Read Master Sync
42225 1: Allowed sync check
Close Allowed Only Control
Default: conditions
have been met
Multiplier:
Unit: degrees Utility to
.010000000000
Sync Phase Read Lower Limit: degrees generator set
42226 Offset: 0 Phase
Difference Only Upper Limit: degrees L1 voltage
Size (bits): 16 phase angle
Default:
Sign: S
0: Synchronizer Off Indicates state
Synchronizer Read Master Sync
42227 1: Synchronizer On of the
Status Only Control
Default: synchronizer

Faults have
0: Inactive occurred which
System Read prevent normal System
42228 1: Active
Lockout Status Only system Information
Default: operation;
reset faults
0: Open
1: Closed Indicates the
Breaker 1 Read Load Add Shed
42229 position status
Position Only 2: Not Available Control
of breaker 1
Default: Not Available
0: Open
1: Closed Indicates the
Breaker 2 Read Load Add Shed
42230 position status
Position Only 2: Not Available Control
of breaker 2
Default: Not Available

A029X159 (Issue 19) 567 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Open
1: Closed Indicates the
Breaker 3 Read Load Add Shed
42231 position status
Position Only 2: Not Available Control
of breaker 3
Default: Not Available
0: Open
1: Closed Indicates the
Breaker 4 Read Load Add Shed
42232 position status
Position Only 2: Not Available Control
of breaker 4
Default: Not Available
0: Open
1: Closed Indicates the
Breaker 5 Read Load Add Shed
42233 position status
Position Only 2: Not Available Control
of breaker 5
Default: Not Available
0: Open
1: Closed Indicates the
Breaker 6 Read Load Add Shed
42234 position status
Position Only 2: Not Available Control
of breaker 6
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 1 Trip Read Load Add Shed
42235 status of
Status Only 2: Tripped Control
breaker 1
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 2 Trip Read Load Add Shed
42236 status of
Status Only 2: Tripped Control
breaker 2
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 3 Trip Read Load Add Shed
42237 status of
Status Only 2: Tripped Control
breaker 3
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 4 Trip Read Load Add Shed
42238 status of
Status Only 2: Tripped Control
breaker 4
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 5 Trip Read Load Add Shed
42239 status of
Status Only 2: Tripped Control
breaker 5
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 6 Trip Read Load Add Shed
42240 status of
Status Only 2: Tripped Control
breaker 6
Default: Not Available

Copyright © 2017 Cummins Inc. 568 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42241 ATS 1 Position position status
Only 3: Source 2 Connected Control
of ATS 1
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42242 ATS 2 Position position status
Only 3: Source 2 Connected Control
of ATS 2
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42243 ATS 3 Position position status
Only 3: Source 2 Connected Control
of ATS 3
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42244 ATS 4 Position position status
Only 3: Source 2 Connected Control
of ATS 4
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42245 ATS 5 Position position status
Only 3: Source 2 Connected Control
of ATS 5
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42246 Position position status
Only 3: Source 2 Connected Control
of ATS 6
4: Paralleled
Default: Not Available
0: Missing
1: Good Indicates
Read 2: Connecting status of SID1
42247 SID1 Status Communications
Only 3: No EXP Board (AUX 101 / 102
4: Not Applicable module 1)
Default:

A029X159 (Issue 19) 569 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Missing
1: Good Indicates
Read 2: Connecting status of SID0
42248 SID0 Status Communications
Only 3: No EXP Board (AUX 101 / 102
4: Not Applicable module 0)
Default:
Indicates the
Expansion 0: Disable status of SIDO
Board Read
42249 1: Enable to expansion Communications
Communication Only
Default: Disable board
s
connection
Multiplier:
Unit: NA
1.000000000000 Indicates the
Current Add Read Lower Limit: Load Add Shed
42250 Offset: 0 next level to
Level Only Upper Limit: Control
Size (bits): 16 add
Default:
Sign: U
Multiplier:
Unit: NA
1.000000000000 Indicates the
Current Shed Read Lower Limit: Load Add Shed
42251 Offset: 0 next level to
Level Only Upper Limit: Control
Size (bits): 16 shed
Default:
Sign: U
0: Do Nothing Indicates
Add Level 1 Read Load Add Shed
42252 1: Add Level status of add
Command Only Control
Default: Do Nothing level 1

0: Do Nothing Indicates
Add Level 2 Read Load Add Shed
42253 1: Add Level status of add
Command Only Control
Default: Do Nothing level 2

0: Do Nothing Indicates
Add Level 3 Read Load Add Shed
42254 1: Add Level status of add
Command Only Control
Default: Do Nothing level 3

0: Do Nothing Indicates
Add Level 4 Read Load Add Shed
42255 1: Add Level status of add
Command Only Control
Default: Do Nothing level 4

0: Do Nothing Indicates
Add Level 5 Read Load Add Shed
42256 1: Add Level status of add
Command Only Control
Default: Do Nothing level 5

0: Do Nothing Indicates
Add Level 6 Read Load Add Shed
42257 1: Add Level status of add
Command Only Control
Default: Do Nothing level 6

0: Do Nothing Indicates
Shed Level 1 Read Load Add Shed
42258 1: Add Level status of shed
Command Only Control
Default: Do Nothing level 1

Copyright © 2017 Cummins Inc. 570 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates
Shed Level 2 Read Load Add Shed
42259 1: Add Level status of shed
Command Only Control
Default: Do Nothing level 2

0: Do Nothing Indicates
Shed Level 3 Read Load Add Shed
42260 1: Add Level status of shed
Command Only Control
Default: Do Nothing level 3

0: Do Nothing Indicates
Shed Level 4 Read Load Add Shed
42261 1: Add Level status of shed
Command Only Control
Default: Do Nothing level 4

0: Do Nothing Indicates
Shed Level 5 Read Load Add Shed
42262 1: Add Level status of shed
Command Only Control
Default: Do Nothing level 5

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42263 Level 1 1: Add Level
Only to add level 1 Control
Command Default: Do Nothing

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42264 Level 2 1: Add Level
Only to add level 2 Control
Command Default: Do Nothing

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42265 Level 3 1: Add Level
Only to add level 3 Control
Command Default: Do Nothing

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42266 Level 4 1: Add Level
Only to add level 4 Control
Command Default: Do Nothing

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42267 Level 5 1: Add Level
Only to add level 5 Control
Command Default: Do Nothing

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42268 Level 6 1: Add Level
Only to add level 6 Control
Command Default: Do Nothing

0: Do Nothing Operator input


Manual Shed
Read to shed loads Load Add Shed
42269 Level 1 1: Add Level
Only assigned to Control
Command Default: Do Nothing level 1

0: Do Nothing Operator input


Manual Shed
Read to shed loads Load Add Shed
42270 Level 2 1: Add Level
Only assigned to Control
Command Default: Do Nothing level 2

0: Do Nothing Operator input


Manual Shed
Read to shed loads Load Add Shed
42271 Level 3 1: Add Level
Only assigned to Control
Command Default: Do Nothing level 3

A029X159 (Issue 19) 571 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function

0: Do Nothing Operator input


Manual Shed
Read to shed loads Load Add Shed
42272 Level 4 1: Add Level
Only assigned to Control
Command Default: Do Nothing level 4

0: Do Nothing Operator Input


Manual Shed
Read to Shed Loads Load Add Shed
42273 Level 5 1: Add Level
Only Assigned to Control
Command Default: Do Nothing Level 5

0: Do Nothing Indicates if
Restored Shed
Read shed level 1 Load Add Shed
42274 Level 1 1: Add Level
Only has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restored Shed
Read shed level 2 Load Add Shed
42275 Level 2 1: Add Level
Only has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restored Shed
Read shed level 3 Load Add Shed
42276 Level 3 1: Add Level
Only has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restored Shed
Read shed level 4 Load Add Shed
42277 Level 4 1: Add Level
Only has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restored Shed
Read shed level 5 Load Add Shed
42278 Level 5 1: Add Level
Only has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates add
Add Load 1 Read Load Add Shed
42279 1: Add Level command for
Command Only Control
Default: Do Nothing load 1

0: Do Nothing Indicates add


Add Load 2 Read Load Add Shed
42280 1: Add Level command for
Command Only Control
Default: Do Nothing load 2

0: Do Nothing Indicates add


Add Load 3 Read Load Add Shed
42281 1: Add Level command for
Command Only Control
Default: Do Nothing load 3

0: Do Nothing Indicates add


Add Load 4 Read Load Add Shed
42282 1: Add Level command for
Command Only Control
Default: Do Nothing load 4.

0: Do Nothing Indicates add


Add Load 5 Read Load Add Shed
42283 1: Add Level command for
Command Only Control
Default: Do Nothing load 5

Copyright © 2017 Cummins Inc. 572 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates add
Add Load 6 Read Load Add Shed
42284 1: Add Level command for
Command Only Control
Default: Do Nothing load 6

0: Do Nothing Indicates shed


Shed Load 1 Read Load Add Shed
42285 1: Add Level command for
Command Only Control
Default: Do Nothing load 1

0: Do Nothing Indicates shed


Shed Load 2 Read Load Add Shed
42286 1: Add Level command for
Command Only Control
Default: Do Nothing load 2

0: Do Nothing Indicates shed


Shed Load 3 Read Load Add Shed
42287 1: Add Level command for
Command Only Control
Default: Do Nothing load 3

0: Do Nothing Indicates Shed


Shed Load 4 Read Load Add Shed
42288 1: Add Level Command for
Command Only Control
Default: Do Nothing Load 4

0: Do Nothing Indicates shed


Shed Load 5 Read Load Add Shed
42289 1: Add Level command for
Command Only Control
Default: Do Nothing load 5

0: Do Nothing Indicates shed


Shed Load 6 Read Load Add Shed
42290 1: Add Level command for
Command Only Control
Default: Do Nothing load 6

Multiplier: Engineering
Unit: VDC
Battery Voltage .010000000000 units value for
Read Lower Limit: VDC
42291 Engr Units Offset: 0 the battery Analog Inputs
Only Upper Limit: VDC
Display Value Size (bits): 16 voltage analog
Default Input
Sign: U
Multiplier: Voltage level
kVAR Master Unit: VDC
.010000000000 commanded to
Load Control Read Lower Limit: VDC
42292 Offset: 0 kVAR Master Analog Inputs
Output Only Upper Limit: VDC
Size (bits): 16 load control
Predictor Value Default
Sign: S analog output

Multiplier: Voltage level


kW Master Unit: VDC
.010000000000 commanded to
Load Control Read Lower Limit: VDC
42293 Offset: 0 kW Master Analog Inputs
Output Only Upper Limit: VDC
Size (bits): 16 load control
Predictor Value Default
Sign: S analog output

Multiplier: Voltage level


Master Unit: VDC
.010000000000 commanded to
Frequency Read Lower Limit: VDC
42294 Offset: 0 Master Analog Inputs
Bias Output Only Upper Limit: VDC
Size (bits): 16 frequency bias
Predictor Value Default
Sign: S analog output

A029X159 (Issue 19) 573 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Multiplier: Voltage level
Unit: VDC
Master Voltage .010000000000 commanded to
Read Lower Limit: VDC
42295 Bias Output Offset: 0 Master voltage Analog Inputs
Only Upper Limit: VDC
Predictor Value Size (bits): 16 bias analog
Default output
Sign: S
0: Manual
1: Normal Indicates the
PTC Genset 2: Normal Override current
Read PTC Genset
42296 Operating 3: Test operating
Only Operating Mode
Mode 4: Utility Fail mode of the
5: Extended Parallel generator set
Default
0: Manual
1: Normal Indicates the
PTC Transfer 2: Normal Override current
Read PTC Genset
42297 Pair Operating 3: Test operating
Only Operating Mode
Mode 4: Utility Fail mode of the
5: Extended Parallel transfer pair
Default:
Indicates the
0: Open Transition transition type
1: Hard Closed Transition currently
PTC Operating Read PTC Genset
42298 applicable to
Transition Type Only 2: Soft Closed Transition Operating Mode
the PTC
Default: function
operation

Addr. System Name Access Specifications Description Function


Indicates the
Expansion 0: Disabled status of the
Board Read SID1 to
42299 1: Enabled Communications
Communication Only expansion
s1 Default: Disabled board
connection
0: Master Synchronize Only
1: Isolated Bus w/ out GM Main setting:
2: Isolated Bus w/GM sets system
System Read/ topology; Application
42300 3: Common Bus
Topology Write control must be Configuration
4: Transfer Pair in manual to
5: Component Mode set
Default: Master Synchronize Only
0: Open Transition Sets the type
Read/ 1: Hard Closed Transition of transition Application
42301 Transition Type
Write 2: Soft Closed Transition that will be Configuration
Default: Open Transition used

Copyright © 2017 Cummins Inc. 574 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function

0: Disabled Use to enable


Extended Read/ extended Application
42302 1: Enabled
Parallel Enable Write paralleling Configuration
Default: Disabled operation
0: None
Load Demand Read/ 1: Fixed Sequence Sets the load Load Demand
42303
Type Write 2: Run Hours demand type Control
Default: None
0: Manual
Priority Control Read/ Set the priority
42304 1: Automatic Priority Control
Method Write control method
Default: Manual
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 01 kW Read/ Offset: 0 Sets generator System
42305 Upper Limit:
Rating Write 1 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 1000
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 02 kW Read/ Offset: 0 Sets generator System
42306 Upper Limit:
Rating Write 2 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 03 kW Read/ Offset: 0 Sets generator System
42307 Upper Limit:
Rating Write 3 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 04 kW Read/ Offset: 0 Sets generator
42308 Upper Limit: PC 3.x
Rating Write 4 kW rating
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 05 kW Read/ Offset: 0 Sets generator System
42309 Upper Limit:
Rating Write 5 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 06 kW Read/ Offset: 0 Sets generator System
42310 Upper Limit:
Rating Write 6 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0

A029X159 (Issue 19) 575 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 07 kW Read/ Offset: 0 Sets generator System
42311 Upper Limit:
Rating Write 7 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 08 kW Read/ Offset: 0 Sets generator System
42312 Upper Limit:
Rating Write 8 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 09 kW Read/ Sets generator System
42313 Offset: 0 Upper Limit:
Rating Write 9 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0

Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 10 kW Read/ Offset: 0 Sets generator System
42314 Upper Limit:
Rating Write 10 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 11 kW Read/ Sets generator System
42315 Offset: 0 Upper Limit:
Rating Write 11 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0

Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 12 kW Read/ Offset: 0 Sets generator System
42316 Upper Limit:
Rating Write 12 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Unit: Seconds
Multiplier:
.100000000000 Lower Limit: .000 Set the
Programmed Seconds
Read/ Offset: 0 programmed
42317 Transition PTC Timers
Write Upper Limit: 60.000 transition time
Delay (TDPT) Size (bits): 16
Seconds delay
Sign: U
Default: 3
Unit: Seconds
Multiplier:
.100000000000 Lower Limit: .000
Seconds Sets the
Transfer Delay Read/ Offset: 0
42318 transfer time PTC Timers
(TDNE) Write Upper Limit: 120.000
Size (bits): 16 delay
Seconds
Sign: U
Default: 10

Copyright © 2017 Cummins Inc. 576 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Unit: Seconds
Multiplier:
.100000000000 Lower Limit: .000
Seconds Sets the
Retransfer Read/ Offset: 0
42319 transfer time PTC Timers
Delay (TDEN) Write Upper Limit: 1800.000
Size (bits): 16 delay
Seconds
Sign: U
Default: 600
Unit: Seconds
Multiplier: Sets the
.100000000000 Lower Limit: .000
Maximum Seconds maximum
Read/ Offset: 0
42320 Parallel Time parallel time for PTC Timers
Write Upper Limit: 1800.000
(TDMP) Size (bits): 16 soft load
Seconds transfers
Sign: U
Default: 20
Multiplier:
Unit: %
.010000000000 Generator set
Genset Bus Read/ Lower Limit: -5.000% Master Load
42321 Offset: 0 nominal
%kW Setpoint Write Upper Limit: 105.000% voltage Control
Size (bits): 16
Default: 80
Sign: S
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 100.000
Genset Volts Generator set
Read/ Offset: 0
42322 Nominal nominal AC Setup
Write Upper Limit:
Voltage Size (bits): 16 voltage
45000.000 Volts
Sign: U
Default: 480
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 100.000
Utility Nominal Read/ Volts Utility nominal
42323 Offset: 0 AC Setup
Voltage Write Upper Limit: voltage
Size (bits): 16
45000.000 Volts
Sign: U
Default: 480
Multiplier: Sets the center
Unit: Hz
.100000000000 frequency
Genset Center Read/ Lower Limit: 45.000 Hz
42324 Offset: 0 sensor PTC Sensors
Frequency Write Upper Limit: 65.000 Hz
Size (bits): 16 bandwidth
Default: 60 settings
Sign: U
Multiplier: Sets the center
Unit: Hz
.100000000000 frequency
Utility Center Read/ Lower Limit: 45.000 Hz
42325 Offset: 0 sensor PTC Sensors
Frequency Write Upper Limit: 65.000 Hz
Size (bits): 16 bandwidth
Default: 60 settings
Sign: U

0: Disable Use to enable


test With Load Read/ or disable load Application
42326 1: Enable
Enable Write transfer during Configuration
Default: Disable a Test

A029X159 (Issue 19) 577 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: Hz Use to define
.100000000000
System Read/ Lower Limit: 45.000 Hz the system System
42327 Offset: 0
Frequency Write Upper Limit: 65.000 Hz nominal Information
Size (bits): 16 frequency
Default: 60
Sign: U
Selects where
0: Internal the generator
Genset Bus
Read/ set kW setpoint Master Load
42328 kW Setpoint 1: Analog Input
Write will come from Control
Source Default Internal for extended
paralleling
Selects where
the generator
Genset Bus 0: Internal set kVAR
Read/ Master Load
42329 kVAR Setpoint 1: Analog Input setpoint will
Write Control
Source Default Internal come from for
extended
paralleling

Multiplier: Unit: kW Set the base


1.000000000000 Lower Limit: .000 kW load kW
Genset Bus Read/ Offset: 0 setpoint in Master Load
42330 Upper Limit:
kW Setpoint Write closed loop Control
Size (bits): 16 32767.000 kW extended
Sign: S Default: 0 paralleling
Unit: kVAR Sets the base
Multiplier:
1.000000000000 Lower Limit: .000 load kVAR
Genset Bus Read/ kVAR setpoint in Master Load
42331 Offset: 0
kVAR Setpoint Write Upper Limit: closed loop Control
Size (bits): 16 extended
32767.000 kVAR
Sign: S paralleling
Default: 0

Multiplier: Sets % kVAR


Unit: % generator
.010000000000
Genset Bus % Read/ Lower Limit: -5.000% output level for Master Load
42332 Offset: 0
kVAR Setpoint Write Upper Limit: 105.000% open loop base Control
Size (bits): 16 load extended
Default: 0
Sign: S paralleling
Sets the
Multiplier: desired
Unit: NA
Genset Bus .010000000000 generator set
Read/ Lower Limit: .700 Master Load
42333 Power Factor Offset: 0 bus power
Write Upper Limit: 1.000 Control
Setpoint Size (bits): 16 factor in closed
Default: 1.00 loop extended
Sign: S
paralleling

Copyright © 2017 Cummins Inc. 578 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Unit: kW
Multiplier:
1.000000000000 Lower Limit:
Genset -32768.000kW Setpoint for
Read/ Offset: 0 Master Load
42334 Unloaded generator set
Write Upper Limit: Control
Level Size (bits): 16 unloaded level
32767.000 kW
Sign: S
Default: 50
Selects where
0: Internal the utility kW
Utility Bus kW
Read/ setpoint will Master Load
42335 Setpoint 1: Analog Input
Write come from for Control
Source Default: Internal extended
paralleling
Selects where
0: Internal the utility kVAR
Utility Bus
Read/ setpoint will Master Load
42336 kVAR Setpoint 1: Analog Input
Write come from for Control
Source Default: Internal extended
paralleling
Unit: kW Sets the peak
Multiplier:
1.000000000000 Lower Limit: Shave kW
Utility Bus kW Read/ -32768.000kW setpoint in Master Load
42337 Offset: 0
Setpoint Write Upper Limit: closed loop Control
Size (bits): 16 extended
32767.000 kW
Sign: S paralleling
Default: 100
Unit: kW
Multiplier: Sets the utility
1.000000000000 Lower Limit:
Utility Bus kW -32768.000kW kW constraint
Read/ Offset: 0 Master Load
42338 Constraint level for base
Write Upper Limit: Control
Level Size (bits): 16 load extended
32767.000 kW paralleling
Sign: S
Default: 100
Unit: kW Sets the peak
Multiplier:
1.000000000000 Lower Limit: shave kVAR
Utility Bus Read/ -32768.000 kVAR setpoint in Master Load
42339 Offset: 0
kVAR Setpoint Write Upper Limit: closed loop Control
Size (bits): 16 extended
32767.000 kVAR
Sign: S paralleling
Default: 100

Multiplier: Sets the


Unit: NA desired utility
Utility Bus .010000000000
Read/ Lower Limit: .700 bus power Master Load
42340 Power Factor Offset: 0
Write Upper Limit: 1.000 factor in loop Control
Setpoint Size (bits): 16
Default: 1.00 extended
Sign: S paralleling

A029X159 (Issue 19) 579 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Unit: kW
Multiplier:
1.000000000000 Lower Limit:
Utility -32768.000kW Setpoint for
Read/ Offset: 0 Master Load
42341 Unloaded utility unloaded
Write Upper Limit: Control
Level Size (bits): 16 level
32767.000 kW
Sign: S
Default: 50

0: Inactive Use to
Clear Fault Read/ completely Fault and Event
42342 1: Active
History Table Write clear the fault Info
Default: Inactive history table
Use to
completely
0: Inactive clear the
Clear
Read/ counters in Fault and Event
42343 Occurrence 1: Active
Write faults and Info
Tables Default: Inactive events
occurrence
tables
Use to
0: Do Nothing permanently
Genset Reset
Read/ clear all
42344 All Energy 1: Clear Counters Energy
Write generator set
Meters Default: Do Nothing energy meter
values
Use to
0: Do Nothing permanently
Utility Reset All Read/
42345 1: Clear Counters clear all utility Energy
Energy Meters Write
Default: Do Nothing energy meter
values

0: Genset Bus % Level (Open Loop) Sets how and


1: Genset Bus kW (Closed Loop) where the kW
Extended
will be
Paralleling kW Read/ 2: Genset Bus kW w/ Utility Constraint Master Load
42346 controlled for
Load Control Write (Closed Loop) Control
extended
Type 3: Utility Bus kW (Closed Loop) parallel
Default: Genset Bus % Level (Open Loop) operation
0: Genset Controllers
1: Genset Bus % Level (Open Loop) Sets how and
2: Genset Bus Power Factor (Open Loop) where the
Extended
3: Genset Bus kVAR (Closed Loop) kVAR will be
Paralleling Read/ Master Load
42347 controlled for
kVAR Load Write 4: Genset Bus Power Factor (Closed Loop) Control
extended
Control Type 5: Utility Bus kVAR (Closed Loop) parallel
6: Utility Bus Power Factor (Closed Loop) operation
Default: Genset Controllers

Copyright © 2017 Cummins Inc. 580 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Unit: seconds
Multiplier:
.10000000000 Lower Limit: 10.000 Set ramp load
Extended seconds
Read/ Offset: 0 time for Master Load
42348 Parallel Ramp
Write Upper Limit: 900.000 extended Control
Load Time Size (bits): 16
seconds paralleling
Sign: U
Default:60

0:Disabled Enable if want


Fail To Sync Read/ synchronizing Master Sync
42349 1:Enabled
Lockout Enable Write to stop if fail to Control
Default: Disable sync occurs
Fail To Sync Use to enable
Open 0:Disabled or disable an
Read/ PTC State
42350 Transition 1:Enabled open transition
Write Machine
Retransfer Default: Disable retransfer upon
Enable fail to sync
Unit: seconds
Multiplier:
.200000000000 Lower Limit: 10.000 Set the fill to
Fail To seconds
Read/ Offset: 0 synchronize Master Sync
42351 Synchronize
Write Upper Limit: 900.000 diagnostic time Control
Time Size (bits): 16
seconds delay
Sign: U
Default:120
In manual
0: Closed Requested mode can be
1: No Command used to semi-
Gen CB Read/
42352 manually Breaker Control
Manual Control Write 2: Open Commanded control the
Default: No Command generator set
breaker
In Manual
0: Closed Requested Mode can be
Util CB Manual Read/ 1: No Command used to Semi-
42353 Breaker Control
Control Write 2: Open Commanded Manually
Default: No Command Control the
Utility Breaker

Multiplier: Sets the


Unit: seconds Synchronizer
.001000000000
Read/ Lower Limit: -3.000 Hz Slip Frequency Master Sync
42354 Slip Frequency Offset: 0
Write Upper Limit: 3.000 Hz (used when Control
Size (bits): 16 Sync Method is
Default:0.1
Sign: S Slip)
Unit: seconds
Multiplier:
.100000000000 Lower Limit: .000 Sets the
Start Time Read/ seconds generator set PTC Operating
42355 Offset: 0
Delay (TDES) Write Upper Limit: 3600.000 Start Time Mode
Size (bits): 16 Delay
seconds
Sign: U
Default: 0

A029X159 (Issue 19) 581 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Unit: seconds
Multiplier:
.100000000000 Lower Limit: .000 Sets the
Stop Time Read/ seconds generator set PTC Operating
42356 Offset: 0
Delay (TDEC) Write Upper Limit: 3600.000 Stop Time Mode
Size (bits): 16 Delay
seconds
Sign: U
Default: 0
0: Normal Use to Invert
Synchronizer Read/ Master Sync
42357 1: Invert Synchronizer
Polarity Write Control
Default: Normal Polarity

0: Phase Match Sets the


Synchronize Read/ Master Sync
42358 1: Slip Frequency synchronizing
Method Write Control
Default: Phase Match method

Allows protocol
0: PCCNet of the PCCNet
Port Protocol Read/ port to be
42359 1: MON Communications
Selection Write changed to
Default: PCCNet MON for
troubleshooting

0: Disabled Use to enable


System
Read/ or disable the System
42360 Scheduler 1: Enabled
Write system Scheduler
Enable Default: Disabled scheduler

0: Disabled Use the enable


Load Add Shed Read/ or disable the Load Add Shed
42361 1: Enabled
Enable Write load add shed Control
Default: Disabled feature
Use to enable
Open
0: Disabled or disable the
Transition
Read/ shedding of Load Add Shed
42362 Retransfer 1: Enabled
Write loads during Control
Load Shed Default: Disabled open transition
Enable
retransfer
Indicates
Auto/Manual 0: Auto automatic or
Read/ Load Add Shed
42363 Load Add 1: Manual manual load
Write Control
Restore Mode Default: Auto add restore
operation
Unit: second Indicates delay
Multiplier:
1.000000000000 Lower Limit: .000 between add
Genset Bus second
Read/ Offset: 0 levels when all Load Add Shed
42364 Load Add
Write Upper Limit: 60.000 generator sets Control
Delay Size (bits): 16
second are online and
Sign: U no utility
Default: 1

Copyright © 2017 Cummins Inc. 582 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Unit: second
Multiplier:
1.000000000000 Lower Limit: .000 Indicates delay
Utility Bus second
Read/ Offset: 0 between add Load Add Shed
42365 Load Add
Write Upper Limit: 60.000 levels when on Control
Delay Size (bits): 16
second utility
Sign: U
Default: 1
Unit: seconds
Multiplier:
1.000000000000 Lower Limit: 1.000 Indicates delay
Load Shed Read/ seconds between shed Load Add Shed
42366 Offset: 0
Delay Write Upper Limit: 10.000 levels when on Control
Size (bits): 16 generator sets
seconds
Sign: U
Default: 1
Indicates type
0: None of load
Load 1 Device Read/ 1: Breaker connected to Load Add Shed
42367
Type Write 2: ATS load 1 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 2 Device Read/ 1: Breaker connected to Load Add Shed
42368
Type Write 2: ATS load 2 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 3 Device Read/ 1: Breaker connected to Load Add Shed
42369
Type Write 2: ATS load 3 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 4 Device Read/ 1: Breaker connected to Load Add Shed
42370
Type Write 2: ATS load 4 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 5 Device Read/ 1: Breaker connected to Load Add Shed
42371
Type Write 2: ATS load 5 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 6 Device Read/ 1: Breaker connected to Load Add Shed
42372
Type Write 2: ATS load 6 add Control
Default: None shed control
and status I/O

A029X159 (Issue 19) 583 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA Indicates which
1.000000000000
Load 1 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42373 Offset: 0
Level Write Upper Limit: 18.000 1 is assigned Control
Size (bits): 16 to
Default: 1
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 2 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42374 Offset: 0
Level Write Upper Limit: 18.000 2 is assigned Control
Size (bits): 16 to
Default: 2
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 3 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42375 Offset: 0
Level Write Upper Limit: 18.000 3 is assigned Control
Size (bits): 16 to
Default: 3
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 4 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42376 Offset: 0
Level Write Upper Limit: 18.000 4 is assigned Control
Size (bits): 16 to
Default: 4
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 5 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42377 Offset: 0
Level Write Upper Limit: 18.000 5 is assigned Control
Size (bits): 16 to
Default: 5
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 6 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42378 Offset: 0
Level Write Upper Limit: 18.000 6 is assigned Control
Size (bits): 16 to
Default: 6
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 1 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42379 Offset: 0
Level Write Upper Limit: 17.000 1 is assigned Control
Size (bits): 16 to
Default: 1
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 2 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42380 Offset: 0
Level Write Upper Limit: 17.000 2 is assigned Control
Size (bits): 16 to
Default: 2
Sign: U

Copyright © 2017 Cummins Inc. 584 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA Indicates which
1.000000000000
Load 3 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42381 Offset: 0
Level Write Upper Limit: 17.000 3 is assigned Control
Size (bits): 16 to
Default: 3
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 4 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42382 Offset: 0
Level Write Upper Limit: 17.000 4 is assigned Control
Size (bits): 16 to
Default: 4
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 5 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42383 Offset: 0
Level Write Upper Limit: 17.000 5 is assigned Control
Size (bits): 16 to
Default: 5
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 6 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42384 Offset: 0
Level Write Upper Limit: 17.000 6 is assigned Control
Size (bits): 16 to
Default: 6
Sign: U
Use to choose
0: Both kW and Frequency method for
Genset Bus 1: kW Only
Read/ determining System
42385 Overload
Write 2: Frequency Only generator bus Information
Method
Default: Both kW and Frequency overload
condition

Multiplier: Use to set


Unit: % the % kW
Genset Bus 1.000000000000
Read/ Lower Limit: 80.000% threshold for System
42386 kW Overload Offset: 0
Write Upper Limit: 140.000% generator bus Information
Delay Size (bits): 16
Default: 105 overload
Sign: U condition
Unit: second
Multiplier:
1.000000000000 Lower Limit: .000 Sets the delay
Genset Bus second
Read/ Offset: 0 time for System
42387 kW Overload
Write Upper Limit: 120.000 overload based Information
Delay Size (bits): 16
second on kW
Sign: U
Default: 60

Multiplier: Use to set the


Genset Bus Unit: Hz underfrequency
1.000000000000
Underfrequenc Read/ Lower Limit: .1000 Hz offset threshold System
42388 Offset: 0
y Overload Write Upper Limit: 10.000 Hz for generator Information
Threshold Size (bits): 16 bus overload
Default: 3
Sign: U condition

A029X159 (Issue 19) 585 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Unit: second
Multiplier:
Genset Bus 1.000000000000 Lower Limit:.000 Sets the delay
Underfrequenc Read/ second time for System
42389 Offset: 0
y Overload Write Upper Limit: 20.000 overload based Information
Delay Size (bits): 16 on frequency
second
Sign: U
Default: 3

0: Disable Use enable or


Load Demand Read/ disable the Load Demand
42390 1: Enable
Enable Write load demand Control
Default: Disable feature
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenA
Load Demand Read/ (never stop) for Load Demand
42391 8: Gen9
GenA Write fixed sequence Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen1
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenB
Load Demand Read/ (never stop) for Load Demand
42392 8: Gen9
GenB Write fixed sequence Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen2

Copyright © 2017 Cummins Inc. 586 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenC
Load Demand Read/ (never stop) for Load Demand
42393 8: Gen9
GenC Write fixed sequence Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen3
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenD
Load Demand Read/ (never stop) for Load Demand
42394 8: Gen9
GenD Write fixed sequence Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen4
Unit: minute
Multiplier: Sets the Initial
1.000000000000 Lower Limit: 1.000
minute delay time
Load Demand Read/ Offset: 0 Load Demand
42395 before load
Initial Delay Write Upper Limit: 60.000 Control
Size (bits): 16 demand will
minute operate
Sign: U
Default: 5
Multiplier: Sets load
Unit: %
Load Demand 1.000000000000 demand restart
Read/ Lower Limit: 20.000% Load Demand
42396 Restart Offset: 0 threshold when
Write Upper Limit: 100.000% Control
Percent Size (bits): 16 method is
Default: 80 %kW
Sign: U

A029X159 (Issue 19) 587 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Unit: Hours Sets run hours
Multiplier:
1.000000000000 Lower Limit: 1.000 differential for
Load Demand Hours
Read/ Offset: 0 restart a Load Demand
42397 Run Hours
Write Upper Limit: 500.000 generator set Control
Differential Size (bits): 16
Hours stopped due to
Sign: U load demand
Default: 50
Unit: minute Sets the delay
Multiplier:
1.000000000000 Lower Limit: 1.000 time between
Load Demand minute
Read/ Offset: 0 stopping Load Demand
42398 Shutdown
Write Upper Limit: 60.000 generator sets Control
Delay Size (bits): 16
minute due to load
Sign: U demand
Default: 5

Multiplier: Unit: % Sets load


1.000000000000 Lower Limit: 20.000 % demand
Load Demand
Read/ Offset: 0 shutdown Load Demand
42399 Shutdown Upper Limit: 100.000
Write threshold when Control
Percent Size (bits): 16 % method is
Sign: U Default: 60 %kW

Unit: seconds Sets how long


Multiplier: to wait for a
1.000000000000 Lower Limit: 10.000
seconds generator set
General Fail Read/ Offset: 0 Load Demand
42400 to come online
Time Delay Write Upper Limit: 900.000 Control
Size (bits): 16 before
second declaring it
Sign: U
Default: 59 failed
Unit: seconds
Multiplier:
.020000000000 Lower Limit: .100 Sets the utility
Util CB Fail to Read/ seconds breaker fail to
42401 Offset: 0 Breaker Control
Close Delay Write Upper Limit: 1.000 close time
Size (bits): 16 delay
seconds
Sign: U
Default: 0.26
Unit: seconds
Multiplier:
.200000000000 Lower Limit: .200 Sets the utility
Util CB Fail to Read/ seconds breaker fail to
42402 Offset: 0 Breaker Control
Open Delay Write Upper Limit: 5.000 open time
Size (bits): 16 delay
seconds
Sign: U
Default: 1
Unit: seconds
Multiplier:
.020000000000 Lower Limit: .000 Sets time to
Util CB seconds
Read/ Offset: 0 allow for utility
42403 Recharge Breaker Control
Write Upper Limit: 60.000 breaker
Delay Size (bits): 16
seconds recharge
Sign: U
Default: 10

Copyright © 2017 Cummins Inc. 588 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Unit: seconds
Multiplier: Sets the
.020000000000 Lower Limit: .100
seconds generator Set
Gen CB Fail to Read/ Offset: 0
42404 breaker fail to Breaker Control
Close Delay Write Upper Limit: 1.000
Size (bits): 16 close time
seconds delay
Sign: S
Default: 0.26
Unit: seconds
Multiplier:
.200000000000 Lower Limit: .200 Sets generator
Gen CB Fail to Read/ seconds set breaker fail
42405 Offset: 0 Breaker Control
Open Delay Write Upper Limit: 5.000 to open time
Size (bits): 16 delay
seconds
Sign: U
Default: 1
Unit: seconds
Multiplier: Sets the time
.020000000000 Lower Limit: .000
Gen CB seconds to allow for
Read/ Offset: 0
42406 Recharge generator set Breaker Control
Write Upper Limit: 60.000
Delay Size (bits): 16 breaker
second recharge
Sign: U
Default: 10
Unit: degrees Sets the
Multiplier:
.010000000000 Lower Limit: .100 permissive +/-
Permissive Read/ degrees phase angle Master Sync
42407 Offset: 0
Phase Window Write Upper Limit: 20.000 window for Control
Size (bits): 16 sync check
degrees
Sign: S function
Default: 10
Sets the
Multiplier: permissive +/-
Unit: %
Permissive .100000000000 voltage
Read/ Lower Limit: .500 % Master Sync
42408 Voltage Offset: 0 acceptance
Write Upper Limit: 10.000 % Control
Window Size (bits): 16 window for
Default: 5 sync check
Sign: U
function
Unit: seconds Sets the
Multiplier:
.020000000000 Lower Limit: .500 permissive
Permissive Read/ seconds acceptance Master Sync
42409 Offset: 0
Window Time Write Upper Limit: 5.000 window dwell Control
Size (bits): 16 time for sync
seconds
Sign: U check function
Default: 0.5

Multiplier: Sets maximum


Unit: Hz frequency
Permissive .001000000000
Read/ Lower Limit: .001 Hz difference Master Sync
42410 Frequency Offset: 0
Write Upper Limit: 1.000 Hz allowed for Control
Window Size (bits): 32
Default: 1 permissive
Sign: U close

A029X159 (Issue 19) 589 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Unit: degrees Sets a sync
Multiplier:
.010000000000 Lower Limit: -50.000 phase offset to
Sync Phase Read/ degrees accommodate Master Sync
42412 Offset: 0
Offset Write Upper Limit: 50.000 sync across Control
Size (bits): 16 transformer
degrees
Sign: S with phase shift
Default: 0

0: L1-L2-L3 Defines what


System Phase Read/ the system System
42413 1: L1-L3-L2
Rotation Write phase rotation Information
Default: L1-L2-L3 sequence is

Multiplier: Proportional
Unit: NA gain for kW
1.00000000000
Read/ Lower Limit: .000 closed loop Master Load
42414 kW Kp Offset: 0
Write Upper Limit: 1000.000 control in Control
Size (bits): 16 extended
Default: 60
Sign: U paralleling
Multiplier: Integral gain
Unit: NA
1.00000000000 for kW closed
Read/ Lower Limit: .000 Master Load
42415 kW KI Offset: 0 loop control in
Write Upper Limit: 255.000 Control
Size (bits): 16 extended
Default: 60 paralleling
Sign: U

Multiplier: Proportional
Unit: NA gain for kVAR
.100000000000
Read/ Lower Limit: .000 closed loop Master Load
42416 kVAR Kp Offset: 0
Write Upper Limit: 1000.000 control in Control
Size (bits): 16 extended
Default: 120
Sign: U paralleling

Multiplier: Integral gain


Unit: NA for kVAR
1.00000000000
Read/ Lower Limit: .000 closed loop Master Load
42417 kVAR K1 Offset: 0
Write Upper Limit: 255.000 control in Control
Size (bits): 16 extended
Default: 50
Sign: U paralleling
Multiplier:
Unit: NA Selects which
1.00000000000
Scheduler Read/ Lower Limit: 1.000 scheduler System
42418 Offset: 0
Program Select Write Upper Limit: 12.000 program to Scheduler
Size (bits): 16 view or edit
Default: 1
Sign: U

0: Disable Use to enable


Scheduler
Read/ or disable the System
42419 Program 1: Enable
Write selected Scheduler
Enable Default: Disable program

Copyright © 2017 Cummins Inc. 590 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Once
1: Every Week
2: Every 2 Weeks
3: Every 3 Weeks
Scheduler 4: Every 4 Weeks use to adjust
Program x Read/ 5: Every 5 Weeks repeat interval System
42420
Repeats Write 6: First Week of the Month for the selected Scheduler
Interval 7: Second Week of the Month program
8: Third Week of the Month
9: Forth Week of the Month
10: Last Week of the Month
Default: Once
0: No Load Use to adjust
Scheduler 1: With Load
Read/ run mode for System
42421 Program x Run
Write 2: Extended Parallel the selected Scheduler
Mode
Default: No Load program

0: Sunday
1: Monday
2: Tuesday Use to adjust
Scheduler 3: Wednesday start day of
Read/ System
42422 Program x week for the
Write 4: Thursday Scheduler
Start Day selected
5: Friday program
6: Saturday
Default: Sunday
Multiplier: Unit: hour
1.00000000000 Lower Limit: .000 hour Use to adjust
Scheduler
Read/ Offset: 0 start hour for System
42423 Program x Upper Limit: 23.000
Write the selected Scheduler
Start Hour Size (bits): 16 hour program
Sign: U Default: 0
Unit: minute
Multiplier:
1.00000000000 Lower Limit: .000 Use to adjust
Scheduler minute
Read/ Offset: 0 start minute for System
42424 Program x
Write Upper Limit: 59.000 the selected Scheduler
Start Minute Size (bits): 16
minute program
Sign: U
Default: 0
Multiplier: Unit: hour
1.00000000000 Lower Limit: .000 hour Use to adjust
Scheduler
Read/ Offset: 0 duration hours System
42425 Program x Upper Limit: 23.000
Write for the selected Scheduler
Duration Hours Size (bits): 16 hour program
Sign: U Default: 0

A029X159 (Issue 19) 591 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Unit: minute
Multiplier:
Scheduler 1.000000000000 Lower Limit: .000 Use to adjust
Program x Read/ minute duration minute System
42426 Offset: 0
Duration Write Upper Limit: 59.000 for the selected Scheduler
Minutes Size (bits): 16 program
minute
Sign: U
Default: 0
Multiplier:
Unit: NA Selects which
Scheduler 1.000000000000
Read/ Lower Limit: 1.000 scheduler System
42427 Exception Offset: 0
Write Upper Limit: 6.000 exception to Scheduler
Select Size (bits): 16
Default: 1 view or edit
Sign: U

0: Disable Use to enable


Scheduler
Read/ or disable the System
42428 Exception x 1: Enable
Write selected Scheduler
Enable Default: Disable exception
Use to adjust
Scheduler 0: Once Only the repeat
Read/ System
42429 Exception x 1: Every Year setting of the
Write Scheduler
Repeat Default: Only Once selected
exception
Unit: month
Multiplier:
1.000000000000 Lower Limit: 1.000 Use to adjust
Scheduler month
Read/ Offset: 0 the month of System
42430 Exception x
Write Upper Limit: 12.000 the selected Scheduler
Month Size (bits): 16
month exception
Sign: U
Default: 1
Unit: date
Multiplier:
1.000000000000 Lower Limit: 1.000 Use to adjust
Scheduler date
Read/ Offset: 0 the start date System
42431 Exception x
Write Upper Limit: 31.000 of the selected Scheduler
Date Size (bits): 16
date exception
Sign: U
Default: 1
Multiplier: Unit: hour
1.000000000000 Lower Limit: .000 hour Use to adjust
Scheduler
Read/ Offset: 0 the start hour System
42432 Exception x Upper Limit: 23.000
Write of the selected Scheduler
Hour Size (bits): 16 hour exception
Sign: U Default: 0
Unit: minute
Multiplier:
Scheduler 1.000000000000 Lower Limit: .000 Use to adjust
Exception x Read/ minute the start minute System
42433 Offset: 0
Duration Write Upper Limit: 59.000 of the selected Scheduler
Minute Size (bits): 16 exception
minute
Sign: U
Default: 0

Copyright © 2017 Cummins Inc. 592 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Unit: days Use to adjust
Scheduler 1.000000000000 Lower Limit: .000 days the duration
Read/ Offset: 0 System
42434 Exception x Upper Limit: 44.000 days of the
Write Scheduler
Duration Days Size (bits): 16 days selected
Sign: U Default: 0 exception

Multiplier: Unit: hour Use to adjust


Scheduler 1.000000000000 Lower Limit: .000 hour the duration
Read/ Offset: 0 System
42435 Exception x Upper Limit: 23.000 hours of the
Write Scheduler
Duration Hours Size (bits): 16 hour selected
Sign: U Default: 0 exception

Unit: minute
Multiplier: Use to adjust
Scheduler 1.000000000000 Lower Limit: .000:
minute the duration
Exception x Read/ Offset: 0 System
42436 minutes of the
Duration Write Upper Limit: 59.000: Scheduler
Size (bits): 16 selected
Minutes minute
Sign: U exception
Default: 0

0: Disable Enables the


Daylight
Read/ daylight
42437 Saving Time 1: Enable Real Time Clock
Write savings time
Enable Default: Disable feature
Use to force a
Load Demand 0: Do Nothing refresh of the
Refresh Read/ Load Demand
42438 1: Refresh Sequence active load
Sequence Write Control
Default: Do Nothing demand
Command
sequence

Genset 0: Wye Delta or wye


Read/
42439 Connection 1: Delta for generator AC Setup
Write
Type Default: Wye set connection

Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 100.000
Genset PT Volts Generator set
Read/ Offset: 0
42440 Primary PT primary AC Setup
Write Upper Limit:
Voltage Size(bits): 16 voltage
45000.000 Volts
Sign: U
Default: 480
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 100.000
Genset PT Volts Generator set
Read/ Offset: 0
42441 Secondary PT secondary AC Setup
Write Upper Limit: 500.000
Voltage Size(bits): 16 voltage
Volts
Sign: U
Default: 120
Unit: Amps
Multiplier:
1.000000000000 Lower Limit: 5.000
Genset CT Amps Generator set
Read/ Offset: 0
42442 Primary CT primary AC Setup
Write Upper Limit:
Current Size(bits): 16 current
25000.000 Volts
Sign: U
Default: 100

A029X159 (Issue 19) 593 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function

Genset CT 0: 1 Amp Generator set


Read/
42443 Secondary 1: 5 Amp CT secondary AC Setup
Write
Current Default: 5 Amp current

Utility 0: Wye Delta or wye


Read/
42444 Connection 1: Delta for utility AC Setup
Write
Type Default: Wye connection

Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 100.000
Utility PT Volts
Read/ Offset: 0 Utility PT
42445 Primary AC Setup
Write Upper Limit: primary voltage
Voltage Size(bits): 16
45000.000 Volts
Sign: U
Default: 480
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 100.000
Utility PT Volts Utility PT
Read/ Offset: 0
42446 Secondary secondary AC Setup
Write Upper Limit: 500.000
Voltage Size(bits): 16 voltage
Volts
Sign: U
Default: 120
Unit: Amps
Multiplier:
1.000000000000 Lower Limit: 5.000
Utility CT Amps
Read/ Offset: 0 Utility CT
42447 Primary AC Setup
Write Upper Limit: primary current
Current Size(bits): 16
25000.000 Amps
Sign: U
Default: 100

Utility CT 0: 1 Amp Utility CT


Read/
42448 Secondary 1: 5 Amp secondary AC Setup
Write
Current Default: 5 Amp current

Generator set
Multiplier: Unit: kW kW capacity
Load Add Shed 1.000000000000 Lower Limit: .000 kW that must be
Required Read/ Offset: 0 Load Add Shed
42449 Upper Limit: online to start
Online Write Control
Size(bits): 16 32767.000 kW timed load
Capacity
Sign: S Default: 0 add : 0
disables this
Sets how much
Multiplier: Unit: kW capacity must
Load Demand 1.000000000000 Lower Limit: .000 kW always be
Minimum Read/ Offset: 0 Load Demand
42450 Upper Limit: online
Online Write Control
Size(bits): 16 32767.000 kW regardless of
Capacity
Sign: S Default: 0 what the load
is

Copyright © 2017 Cummins Inc. 594 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Unit: second Sets generator
Multiplier:
.100000000000 Lower Limit: .000 restart delay
Load Demand Read/ second time to avoid Load Demand
42451 Offset: 0
Restart Delay Write Upper Limit: 25.000 nuisance Control
Size(bits): 16 restarts due to
second
Sign: U load transients
Default: 1
Unit: Amps
Multiplier: Use to set how
1.000000000000 Lower Limit: 1.000
Amps many amps =
Utility Available Read/ Offset: 0
42452 100% utility kW AC Setup
Current Write Upper Limit:
Size(bits): 16 - used by
32000.000 Amps bargraph
Sign: U
Default: 1000
Multiplier: Unit: kW Use to set hoe
1.000000000000 Lower Limit: 1.000 kW many kW =
Total Utility Read/ Offset: 0
42453 Upper Limit: 100% utility kW AC Setup
Capacity Write
Size(bits): 16 32000.000 kW - used by
Sign: S Default: 1000 bargraph

0: 12V DC voltage
Nominal Read/ Battery Voltage
42454 1: 24V provided to the
Battery Voltage Write Protection
Default: 24V control

Unit: VDC
Multiplier:
.0100000000000 Lower Limit: 28.000
24V High VDC Sets 24V high
Read/ Offset: 0 Battery Voltage
42455 Battery Voltage battery voltage
Write Upper Limit: 34.000 Protection
Threshold Size(bits): 16 fault threshold
VDC
Sign: U
Default: 32
Unit: VDC
Multiplier:
.0100000000000 Lower Limit: 22.000
24V Low VDC Sets 24V low
Read/ Offset: 0 Battery Voltage
42456 Battery Voltage battery voltage
Write Upper Limit: 26.000 Protection
Threshold Size(bits): 16 fault threshold
VDC
Sign: U
Default: 24
Unit: VDC
Multiplier:
.0100000000 Lower Limit: 14.000
12V High VDC Sets 12V high
Read/ Offset: 0 Battery Voltage
42457 Battery Voltage battery voltage
Write Upper Limit: 17.000 Protection
Threshold Size(bits): 16 fault threshold
VDC
Sign: U
Default: 16
Unit: VDC
Multiplier:
.010000000000 Lower Limit: 11.000
12 V Low VDC Sets 12V low
Read/ Offset: 0 Battery Voltage
42458 Battery Voltage battery voltage
Write Upper Limit: 13.000 Protection
Threshold Size(bits): 16 fault threshold
VDC
Sign: U
Default: 12

A029X159 (Issue 19) 595 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Unit: second
Multiplier:
1.000000000000 Lower Limit: 2.000
High Battery second Sets high
Read/ Offset: 0 Battery Voltage
42459 Voltage Set battery voltage
Write Upper Limit: 60.000 Protection
Time Size(bits): 16 set time
second
Sign: U
Default: 60
Unit: second
Multiplier:
1.000000000000 Lower Limit: 2.000
Low Battery second Sets low
Read/ Offset: 0 Battery Voltage
42460 Voltage Set battery voltage
Write Upper Limit: 60.000 Protection
Time Size(bits): 16 set time
second
Sign: U
Default: 60
Used to enable
Genset Online 0: Disable or disable the
Read/
42461 Capacity 1: Enable generator set PTC Sensors
Write
Sensor Enable Default: Disable online capacity
sensor

Multiplier: Unit: kW Sets the online


Genset Online 1.000000000000 Lower Limit: .000 kW kW threshold
Capacity Read/ Offset: 0 at which
42462 Upper Limit: PTC Sensors
Sensor Write generator set
Threshold Size(bits): 16 32000.000 kW bus is available
Sign: S Default: 0 for loading
Use to enable
Nominal 0: Disable or disable the
Read/ Battery Voltage
42463 Battery Voltage 1: Enable nominal battery
Write Protection
Check Enable Default: Disable voltage
monitoring
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ Offset: 0 code tied to
42464 Upper Limit: Discrete Outputs
Output1 Code Write configurable
Size(bits): 16 65535.000 output 1
Sign: U Default: 1483
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ Offset: 0 code tied to
42465 Upper Limit: Discrete Outputs
Output2 Code Write configurable
Size(bits): 16 65535.000 output 2
Sign: U Default: 1457
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ Offset: 0 code tied to
42466 Upper Limit: Discrete Outputs
Output3 Code Write configurable
Size(bits): 16 65535.000 output 3
Sign: U Default: 2965

Copyright © 2017 Cummins Inc. 596 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ Offset: 0 code tied to
42467 Upper Limit: Discrete Outputs
Output4 Code Write configurable
Size(bits): 16 65535.000 output 4
Sign: U Default: 2328
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ Offset: 0 code tied to
42468 Upper Limit: Discrete Outputs
Output5 Code Write configurable
Size(bits): 16 65535.000 output 5
Sign: U Default: 1121
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ code tied to
42469 Offset: 0 Upper Limit: Discrete Outputs
Output6 Code Write configurable
Size(bits): 16 65535.000 output 6
Sign: U Default: 1916

Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ Offset: 0 code tied to
42470 Upper Limit: Discrete Outputs
Output7 Code Write configurable
Size(bits): 16 65535.000 output 7
Sign: U Default: 0
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ Offset: 0 code tied to
42471 Upper Limit: Discrete Outputs
Output8 Code Write configurable
Size(bits): 16 65535.000 output 8
Sign: U Default: 343

0: None Indicates that


1: Breaker the generator
Gen Bus Base Read/ System
42472 bus is on base
Load Status Write 2: ATS Information
load extended
Default: None paralleling

0: None Indicates that


1: Breaker the utility bus is
Util Bus Peak Read/ System
42473 on peak shave
Shave Status Write 2: ATS Information
extended
Default: None paralleling
Indicates type
0: None of load
Load 7 Device Read/ 1: Breaker connected to Load Add Shed
42474
Type Write 2: ATS load 7 add Control
Default: None shed control
and status I/O

A029X159 (Issue 19) 597 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Indicates type
0: None of load
Load 8 Device Read/ 1: Breaker connected to Load Add Shed
42475
Type Write 2: ATS load 8 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 9 Device Read/ 1: Breaker connected to Load Add Shed
42476
Type Write 2: ATS load 9 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 10 Read/ 1: Breaker connected to Load Add Shed
42477
Device Type Write 2: ATS load 10 add Control
Default: None shed control
and status I/O
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 7 Add Read/ Lower Limit: .000 add level load Load Add Shed
42478 Offset: 0
Level Write Upper Limit: 17.000 7 is assigned Control
Size (bits): 16 to
Default: 7
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 8 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42479 Offset: 0
Level Write Upper Limit: 18.000 8 is assigned control
Size (bits): 16 to
Default: 8
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 9 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42480 Offset: 0
Level Write Upper Limit: 18.000 9 is assigned control
Size (bits): 16 to
Default: 9
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 10 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42481 Offset: 0
Level Write Upper Limit: 18.000 10 is assigned control
Size (bits): 16 to
Default: 10
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 7 Shed Read/ Lower Limit: .000 shed level load Load Add Shed
42482 Offset: 0
Level Write Upper Limit: 17.000 7 is assigned control
Size (bits): 16 to
Default: 6
Sign: U

Copyright © 2017 Cummins Inc. 598 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA Indicates which
1.000000000000
Load 8 Shed Read/ Lower Limit: .000 shed level load Load Add Shed
42483 Offset: 0
Level Write Upper Limit: 17.000 8 is assigned control
Size (bits): 16 to
Default: 7
Sign: U

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA Indicates which
1.000000000000
Load 9 Shed Read/ Lower Limit: .000 shed level load Load Add Shed
42484 Offset: 0
Level Write Upper Limit: 17.000 9 is assigned control
Size (bits): 16 to
Default: 8
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 10 Shed Read/ Lower Limit: .000 shed level load Load Add Shed
42485 Offset: 0
Level Write Upper Limit: 17.000 10 is assigned control
Size (bits): 16 to
Default: 9
Sign: U
Selects
whether to
Load Demand 0: %kW shutdown /
Read/ Load Add Shed
42486 Threshold 1: kW restart
Write control
Method Default: %kW generator sets
based on %kW
or absolute kW

Multiplier: Unit: kW Sets minimum


1.000000000000 Lower Limit: .000 kW kW reserve
Load Demand
Read/ Offset: 0 capacity when Load Add Shed
42487 Restart kW Upper Limit:
Write threshold control
Threshold Size (bits): 16 32000.000 kW method is
Sign: S Default: 500 absolute kW

Multiplier: Unit: kW Sets maximum


1.000000000000 Lower Limit: .000 kW kW reserve
Load Demand
Read/ Offset: 0 capacity when Load Add Shed
42488 Shutdown kW Upper Limit:
Write threshold control
Threshold Size (bits): 16 32000.000 kW method is
Sign: S Default: 1000 absolute kW

A029X159 (Issue 19) 599 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenE for
Load Demand Read/ Load Demand
42489 8: Gen9 fixed sequence
GenE Write Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen5
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenF for
Load Demand Read/ Load Demand
42490 8: Gen9 fixed sequence
GenF Write Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen6

Copyright © 2017 Cummins Inc. 600 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenG for
Load Demand Read/ Load Demand
42491 8: Gen9 fixed sequence
GenG Write Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen7
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenH for
Load Demand Read/ Load Demand
42492 8: Gen9 fixed sequence
GenH Write Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen8
Sets how long
Unit: second to wait for
Multiplier:
.200000000000 Lower Limit: 2.000 generator set
Virtual Gen second
Read/ Offset: 0 paralleling
42494 Main Fail to Breaker Control
Write Upper Limit: 30.000 circuit breakers
Open Delay Size (bits): 16
second to open when
Sign: U no generator
Default: 5
main

A029X159 (Issue 19) 601 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 13 kW Read/ Offset: 0 Sets generator System
42495 Upper Limit:
Rating Write 13 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 14kW Read/ Offset: 0 Sets generator System
42496 Upper Limit:
Rating Write 14 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 15kW Read/ Offset: 0 Sets generator System
42497 Upper Limit:
Rating Write 15 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 16kW Read/ Offset: 0 Sets generator System
42498 Upper Limit:
Rating Write 16 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier:
Unit: NA Bitmapped
1.000000000000
Fault Status Read Lower Limit: state of utility Fault and Event
42500 Offset: 0
BitMap 1 Only Upper Limit: and other faults Info
Size (bits): 32 - 32 bits
Default: 0
Sign: U
Multiplier: Bitmapped
Unit: NA
1.000000000000 state of
Fault Status Read Lower Limit: Fault and Event
42502 Offset: 0 generator set
BitMap 2 Only Upper Limit: Info
Size (bits): 32 and other faults
Default: 0 - 32 bits
Sign: U
Multiplier:
Unit: NA
1.000000000000 Bitmapped
Event Status Read Lower Limit: Fault and Event
42505 Offset: 0 state of events
BitMap 1 Only Upper Limit: Info
Size (bits): 32 - 32 bits
Default: 0
Sign: U
Bit mapped
Multiplier: word with
Unit: NA
Genset 1.000000000000 status of
Read Lower Limit: AC Interrupt
42506 Metering Fault Offset: 0 generator set
Only Upper Limit: Service
Status Size (bits): 16 AC metering
Default: 0 out of range
Sign: U
conditions

Copyright © 2017 Cummins Inc. 602 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function

Multiplier: Bit mapped


Unit: NA word with
1.000000000000
Utility Metering Read Lower Limit: status of utility AC Interrupt
42507 Offset: 0
Fault Status Only Upper Limit: AC metering Service
Size (bits): 16 out of range
Default: 0
Sign: U conditions

0: Stop State of
Extended
Read / extended
42600 Parallel Start 1: Start Discrete Inputs
Write parallel start
Vol Default: Stop volatile input

0: Inactive State of
Synchronizer Read / synchronizer
42601 1: Active Discrete Inputs
Enable Vol Write enable volatile
Default: Inactive input
0: Inactive State of utility
Utility Source Read /
42602 1: Active source failure Discrete Inputs
Fail Vol Write
Default: Inactive volatile input

0: No Inhibit State of
Transfer Inhibit Read /
42603 1: Inhibit transfer inhibit Discrete Inputs
Vol Write
Default: No Inhibit volatile input

0: No Inhibit State of
Retransfer Read / retransfer
42604 1: Inhibit Discrete Inputs
Inhibit Vol Write inhibit volatile
Default: No Inhibit input

0: No Inhibit State of
Gen CB Inhibit Read / generator CB
42605 1: Inhibit Discrete Inputs
Vol Write inhibit volatile
Default: No Inhibit input
0: No Inhibit State of utility
Utility CB Read /
42606 1: Inhibit CB inhibit Discrete Inputs
Inhibit Vol Write
Default: No Inhibit volatile input

0: Auto State of
Auto/Manual Read/
42607 1: Manual auto/manual Discrete Inputs
Vol Write
Default: Auto volatile input

0: Stop state of test


Read/
42608 Test Start Vol 1: Start start volatile Discrete Inputs
Write
Default: Stop input

0: No Reset state of fault


Read/
42609 Fault Reset Vol 1: Reset reset volatile Discrete Inputs
Write
Default: No Reset input

0: No Override State of
Read/
42610 Override Vol 1: Override override Discrete Inputs
Write
Default: No Override volatile input

A029X159 (Issue 19) 603 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function

0: Stop State of
Extended
Read extended
42611 Parallel Start 1: Start Discrete Inputs
Only parallel start
Sw Default: input
0: Inactive State of
Synchronizer Read
42612 1: Active synchronizer Discrete Inputs
Enable Sw Only
Default: enable input

0: Inactive State of utility


Utility Source Read
42613 1: Active source failure Discrete Inputs
Failure Sw Only
Default: input

0: No Inhibit Status of
Transfer Inhibit Read
42614 1: Inhibit transfer inhibit Discrete Inputs
Sw Only
Default: input

0: No Inhibit Status of
Retransfer Read
42615 1: Inhibit retransfer Discrete Inputs
Inhibit Sw Only
Default: inhibit input

0: No Inhibit State of
Gen CB Inhibit Read
42616 1: Inhibit generator CB Discrete Inputs
Sw Only
Default: inhibit input

0: No Inhibit
Utility CB Read State of utility
42617 1: Inhibit Discrete Inputs
Inhibit Sw Only CB inhibit input
Default:
0: Auto
Auto/Manual Read State of auto /
42618 1: Manual Discrete Inputs
Sw Only manual input
Default:
0: Stop
Read State of test
42619 Test Start Sw 1: Start Discrete Inputs
Only start input
Default:
0: No Reset
Read State of fault
42620 Fault Reset Sw 1: Reset Discrete Inputs
Only reset input
Default:
0: No Override
Read State of
42621 Override Sw 1: Override Discrete Inputs
Only override input
Default:
0: No Inhibit Indicates state
Read
42622 Master Inhibit 1: Inhibit of Master Priority Control
Only
Default: priority inhibit

0: Inactive State of
Genset CB Read
42623 1: Active generator CB Discrete Inputs
Tripped Sw Only
Default: tripped input

Copyright © 2017 Cummins Inc. 604 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function

0: Inactive State of
Genset CB Read/ generator CB
42624 1: Active Discrete Inputs
Tripped Vol Write tripped volatile
Default: Inactive input
0: Inactive State of Utility
Utility CB Read
42625 1: Active CB tripped Discrete Inputs
Tripped Sw Only
Default: input

0: Inactive State of Utility


Util CB Tripped Read/
42626 1: Active CB tripped Discrete Inputs
Vol Write
Default: Inactive volatile input

0: L1-L2-L3
Genset Phase Read Generator set
42627 1: L1-L3-L2 Phase
Rotation Only phase rotation
Default:
0: L1-L2-L3
Utility Phase Read Utility phase
42628 1: L1-L3-L2 Phase
Rotation Only rotation
Default:
0: Breaker Open State of Gen1
Gen1 CB Read
42929 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: Open input

0: Breaker Open State of Gen1


Gen1 CB Read/
42630 1: Breaker Closed CB volatile Discrete Inputs
Position Vol Write
Default: Open input

0: Breaker Open State of Gen2


Gen2 CB Read
42631 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen2


Gen2 CB Read/
42632 1: Breaker Closed CB volatile Discrete Inputs
Position Vol Write
Default: Open input

0: Breaker Open State of Gen3


Gen3 CB Read
42633 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen3


Gen3 CB Read/
42634 1: Breaker Closed CB volatile Discrete Inputs
Position Vol Write
Default: Open input

0: Breaker Open State of Gen4


Gen4 CB Read
42635 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen4


Gen4 CB Read/
42636 1: Breaker Closed CB volatile Discrete Inputs
Position Vol Write
Default: Open input

A029X159 (Issue 19) 605 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: No Inhibit Use to
Network Read/
42637 1: Inhibit manually inhibit Priority Control
Master Inhibit Write
Default: No Inhibit the module

0: Breaker Open State of Gen5


Gen5 CB Read
42638 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen5


Gen5 CB Read/
42639 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen6


Gen6 CB Read
42640 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen6


Gen6 CB Read/
42641 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen7


Gen7 CB Read
42642 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen7


Gen7 CB Read/
42643 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen8


Gen8 CB Read
42644 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen8


Gen8 CB Read/
42645 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42646 ATS 7 Position position status
Only 3: Source 2 Connected Control
of ATS 7
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42647 ATS 8 Position position status
Only 3: Source 2 Connected Control
of ATS 8
4: Paralleled
Default: Not Available

Copyright © 2017 Cummins Inc. 606 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42648 ATS 9 Position position status
Only 3: Source 2 Connected Control
of ATS 9
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 10 Read Load Add Shed
42649 position status
Position Only 3: Source 2 Connected Control
of ATS 10
4: Paralleled
Default: Not Available
0: Open
1: Closed Indicates
Breaker 7 Read Load Add Shed
42650 position status
Position Only 2: Not Available Control
of breaker 7
Default: Not Available
0: Open
1: Closed Indicates
Breaker 8 Read Load Add Shed
42651 position status
Position Only 2: Not Available Control
of breaker 8
Default: Not Available
0: Open
1: Closed Indicates
Breaker 9 Read Load Add Shed
42652 position status
Position Only 2: Not Available Control
of breaker 9
Default: Not Available
0: Open
1: Closed Indicates
Breaker 10 Read Load Add Shed
42653 position status
Position Only 2: Not Available Control
of breaker 10
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 7 Trip Read Load Add Shed
42654 status of
Status Only 2: Tripped Control
breaker 7
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 8 Trip Read Load Add Shed
42655 status of
Status Only 2: Tripped Control
breaker 8
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 9 Trip Read Load Add Shed
42656 status of
Status Only 2: Tripped Control
breaker 9
Default: Not Available

A029X159 (Issue 19) 607 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Not Available
1: Normal Indicates trip
Breaker 10 trip Read Load Add Shed
42657 status of
Status Only 2: Tripped Control
breaker 10
Default: Not Available
0: Breaker Open State of Gen9
Gen9 CB Read
42658 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen9


Gen9 CB Read/
42659 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen10


Gen10 CB Read
42660 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen10


Gen10 CB Read/
42661 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen11


Gen11 CB Read
42662 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen11


Gen11 CB Read/
42663 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen12


Gen12 CB Read
42664 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen12


Gen12 CB Read/
42665 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen13


Gen13 CB Read
42666 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen13


Gen13 CB Read/
42667 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen


Gen14 CB Read
42668 1: Breaker Closed 14 CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen


Gen14 CB Read/
42669 1: Breaker Closed 14 CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

Copyright © 2017 Cummins Inc. 608 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Breaker Open State of Gen
Gen15 CB Read
42670 1: Breaker Closed 15 CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen


Gen15 CB Read/
42671 1: Breaker Closed 15 CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen


Gen16 CB Read
42672 1: Breaker Closed 16 CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen


Gen16 CB Read/
42673 1: Breaker Closed 16 CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 11 Read Load Add Shed
42674 position status
Position Only 3: Source 2 Connected Control
of ATS 11
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 12 Read Load Add Shed
42675 position status
Position Only 3: Source 2 Connected Control
of ATS 12
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 13 Read Load Add Shed
42676 position status
Position Only 3: Source 2 Connected Control
of ATS 13
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 14 Read Load Add Shed
42677 position status
Position Only 3: Source 2 Connected Control
of ATS 14
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 15 Read Load Add Shed
42678 position status
Position Only 3: Source 2 Connected Control
of ATS 15
4: Paralleled
Default: Not Available

A029X159 (Issue 19) 609 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 16 Read Load Add Shed
42679 position status
Position Only 3: Source 2 Connected Control
of ATS 16
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 17 Read Load Add Shed
42680 position status
Position Only 3: Source 2 Connected Control
of ATS 17
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 18 Read Load Add Shed
42681 position status
Position Only 3: Source 2 Connected Control
of ATS 18
4: Paralleled
Default: Not Available
0: Open
1: Closed Indicates
Breaker 11 Read Load Add Shed
42682 position status
Position Only 2: Not Available Control
of breaker 11
Default: Not Available
0: Open
1: Closed Indicates
Breaker 12 Read Load Add Shed
42683 position status
Position Only 2: Not Available Control
of breaker 12
Default: Not Available
0: Open
1: Closed Indicates
Breaker 13 Read Load Add Shed
42684 position status
Position Only 2: Not Available Control
of breaker 13
Default: Not Available
0: Open
1: Closed Indicates
Breaker 14 Read Load Add Shed
42685 position status
Position Only 2: Not Available Control
of breaker 14
Default: Not Available
0: Open
1: Closed Indicates
Breaker 15 Read Load Add Shed
42686 position status
Position Only 2: Not Available Control
of breaker 15
Default: Not Available
0: Open
1: Closed Indicates
Breaker 16 Read Load Add Shed
42687 position status
Position Only 2: Not Available Control
of breaker 16
Default: Not Available

Copyright © 2017 Cummins Inc. 610 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Open
1: Closed Indicates
Breaker 17 Read Load Add Shed
42688 position status
Position Only 2: Not Available Control
of breaker 17
Default: Not Available
0: Open
1: Closed Indicates
Breaker 18 Read Load Add Shed
42689 position status
Position Only 2: Not Available Control
of breaker 18
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 11 Trip Read Load Add Shed
42690 status of
Status Only 2: Tripped Control
breaker 11
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 12 Trip Read Load Add Shed
42691 status of
Status Only 2: Tripped Control
breaker 12
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 13 Trip Read Load Add Shed
42692 status of
Status Only 2: Tripped Control
breaker 13
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 14 Trip Read Load Add Shed
42693 status of
Status Only 2: Tripped Control
breaker 14
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 15 Trip Read Load Add Shed
42694 status of
Status Only 2: Tripped Control
breaker 15
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 16 Trip Read Load Add Shed
42695 status of
Status Only 2: Tripped Control
breaker 16
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 17 Trip Read Load Add Shed
42696 status of
Status Only 2: Tripped Control
breaker 17
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 18 Trip Read Load Add Shed
42697 status of
Status Only 2: Tripped Control
breaker 18
Default: Not Available

A029X159 (Issue 19) 611 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Disabled Indicates the
Load Add Shed Read 1: Enabled overall state of Load Add Shed
42698
Enable Status Only 2: Paused the load add Control
Default: shed function

0: No Connection Indicates
1: Connected overall state of
Read
42699 PCCNet Status the PCCNet Communications
Only 2: Connecting communication
Default: s bus
0: Gen Does Not Exist
1: Offline For load
Gen1 2: Waiting For Gen
Read demand use - Load Demand
42700 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen1
Default:
0: Gen Does Not Exist 1: Offline
2: Waiting For Gen For load
Gen2
Read demand use - Load Demand
42701 Availability 3: Online
Only indicates status Control
State 4: Failed of Gen2
Default:
0: Gen Does Not Exist 1: Offline For load
Gen3 2: Waiting For Gen
Read demand use - Load Demand
42702 Availability
Only 3: Online 4: Failed indicates status Control
State
Default: of Gen3

0: Gen Does Not Exist 1: Offline


2: Waiting For Gen For load
Gen4
Read demand use - Load Demand
42703 Availability 3: Online
Only indicates status Control
State 4: Failed of Gen4
Default:

Multiplier: Unit: Hours


.000277777780 Lower Limit:.000 Hours
Gen1 Online Read Offset: 0 Total online System
42704 Upper Limit:
Time Only time for Gen1 Information
Size (bits): 32 1193046.000 Hours
Sign: U Default: 0
Unit: Hours Lower
Multiplier: Limit: .000 Hours
Gen2 Online Read .000277777780 Total online System
42706 Upper Limit:
Time Only Offset: 0 time for Gen2 Information
1193046.000 Hours
Size (bits): 32
Default: 0
Unit: Hours Lower
Multiplier:
Limit: .000 Hours
Gen3 Online Read .000277777780 Total online System
42708 Upper Limit:
Time Only Offset: 0 time for Gen3 Information
1193046.000 Hours
Size (bits): 32
Default: 0

Copyright © 2017 Cummins Inc. 612 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Unit: Hours Lower
Multiplier:
Limit: .000 Hours
Gen4 Online Read .000277777780 Total online System
42710 Upper Limit:
Time Only Offset: 0 time for Gen4 Information
1193046.000 Hours
Size (bits): 32
Default: 0
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read currently GenA Load Demand
42712 GenA 8: Gen9
Only (never stops) Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42713 GenB 8: Gen9 currently GenB
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

A029X159 (Issue 19) 613 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42714 GenC 8: Gen9 currently GenC
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator sets
Read Load Demand
42715 GenD 8: Gen9 is currently
Only Control
9: Gen10 GenD for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Off Indicates
Load Demand Read 1: Initial Delay Timing operating state Load Demand
42716
State Only 2: Load Monitor of the load Control
Default demand control

Indicates how
Multiplier: many of the
Unit: NA
Total Number 1.000000000000 generator sets
Read Lower Limit: System
42717 of Gensets Offset: 0 are online
Only Upper Limit: Information
Online Size (bits): 16 which are
Default: sensed by CB
Sign: U
position

Copyright © 2017 Cummins Inc. 614 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function

Multiplier: Difference
Unit: kW between
Total Spare 1.000000000000
Read Lower Limit: kW sensed online System
42718 Online Offset: 0
Only Upper Limit: kW capacity and Information
Capacity Size (bits): 16
Default: generator set
Sign: S bus total kW

Multiplier: Indicates kW
Unit: kW threshold for
Next Gen 1.000000000000
Read Lower Limit: kW generator bus Load Demand
42719 Shutdown Offset: 0
Only Upper Limit: kW at which next Control
Threshold Size (bits): 16
Default: generator set
Sign: S will restart
Indicates kW
Multiplier: threshold for
Unit: kW
Next Gen 1.000000000000 generator bus
Read Lower Limit: kW Load Demand
42720 Shutdown Offset: 0 at which the
Only Upper Limit: kW Control
Threshold Size (bits): 16 next generator
Default: set will load
Sign: S
demand stop
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Next Gen Read next to be Load Demand
42721 8: Gen9
Restart Only restarted if load Control
9: Gen10 conditions are
10: Gen11 met
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

A029X159 (Issue 19) 615 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Next Gen Read next to be Load Demand
42722 8: Gen9
Shutdown Only stopped if load Control
9: Gen10 conditions are
10: Gen11 met
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

0: Run Status of the


Load Demand
Read load demand
42723 Gen1 Driver 1: Load Demand Stop Discrete Outputs
Only Gen1 driver
Status Default: output

0: Run Status of the


Load Demand
Read load demand
42724 Gen2 Driver 1: Load Demand Stop Discrete Outputs
Only Gen2 driver
Status Default: output

0: Run Status of the


Load Demand
Read load demand
42725 Gen3 Driver 1: Load Demand Stop Discrete Outputs
Only Gen3 driver
Status Default: output

0: Run Status of the


Load Demand
Read load demand
42726 Gen4 Driver 1: Load Demand Stop Discrete Outputs
Only Gen4 driver
Status Default: output

Multiplier: Calculated kW
Unit: kW overload
Genset Bus 1.000000000000
Read Lower Limit: kW threshold System
42727 kW Overload Offset: 0
Only Upper Limit: kW based on Information
Status Size (bits): 16
Default: online capacity
Sign: S and % setting
Indicates
Genset Bus 0: No Overload whether
Read System
42728 kW Overload 1: Overload generator bus
Only Information
Status Default: is overloaded
based on kW

Copyright © 2017 Cummins Inc. 616 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Indicates
Genset Bus 0: No Overload whether
Underfrequenc Read generator bus System
42729 1: Overload
y Overload Only is overloaded Information
Status Default: based on
frequency
0: None
1: Program 1
2: Program 2
3: Program 3
4: Program 4
5: Program 5
6: Program 6
7: Program 7
8: Program 8 Indicates the
9: Program 9 currently active
Active Read System
42730 scheduler
Schedule Only 10: Program 10 Scheduler
program or
11: Program 11 exception
12: Program 12
13: Exception 1
14: Exception 2
15: Exception 3
16: Exception 4
17: Exception 5
18: Exception 6
Default:

0: Off Indicates
1: No Load current run
Scheduler Run Read command System
42731 2: With Load
Command Only coming from Scheduler
3: Extended Parallel scheduler
Default: function
Multiplier:
Unit: NA
Modbus Bus 1.000000000000
Read Lower Limit: Modbus
42732 Message Offset: 0 Communications
Only Upper Limit: message count
Count Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: NA
1.000000000000
Modbus CRC Read Lower Limit: Modbus CRC
42733 Offset: 0 Communications
Error Count Only Upper Limit: error count
Size (bits): 16
Default:
Sign: U

A029X159 (Issue 19) 617 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA
Modbus 1.000000000000 Modbus
Read Lower Limit:
42734 Exception Offset: 0 exception Communications
Only Upper Limit:
Count Size (bits): 16 count
Default:
Sign: U
Multiplier:
Unit: NA
Modbus No 1.000000000000
Read Lower Limit: Modbus no
42735 Response Offset: 0 Communications
Only Upper Limit: response count
Count Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: NA
Modbus Slave 1.000000000000
Read Lower Limit: Modbus slave
42736 Message Offset: 0 Communications
Only Upper Limit: message count
Count Size (bits): 16
Default:
Sign: U
0: Do Nothing Clears all
Modbus Clear Read/
42737 1: Clear Counters Modbus Communications
Counters Write
Default: Do Nothing counters

0: Normal
1: Set Clock Use to set
Read/
42738 Clock Mode clock and save Real Time Clock
Write 2: Save Clock setting
Default: Normal
Unit: year
Multiplier:
1.000000000000 Lower Limit: .000 year
Use to set or
Read/ Offset: 0 Upper Limit: 99.000
42739 Clock Year read current Real Time Clock
Write year
Size (bits): 16 year
Default: Read from
Sign: U
RTC chip
Unit: month
Multiplier: Lower Limit: 1.000
1.000000000000 month Use to set or
Read/ Offset: 0
42740 Clock Month Upper Limit: 12.000 read current Real Time Clock
Write
Size (bits): 16 month month
Sign: U Default: Read from
RTC chip
Unit: date
Multiplier: Lower Limit: 1.000
1.000000000000 date Use to set or
Read/ Offset: 0
42741 Clock Date Upper Limit: 31.000 read current Real Time Clock
Write
Size (bits): 16 date date
Sign: U Default: Read from
RTC chip

Copyright © 2017 Cummins Inc. 618 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Unit: hour
Multiplier: Lower Limit: 1.000
1.000000000000 hour Use to set or
Read/ Offset: 0
42742 Clock Hour Upper Limit: 23.000 read current Real Time Clock
Write
Size (bits): 16 hour hour
Sign: U Default: Read from
RTC chip
Unit: minute
Multiplier: Lower Limit: 1.000
1.000000000000 minute Use to set or
Read/ Offset: 0
42743 Clock Minute Upper Limit: 59.000 read current Real Time Clock
Write
Size (bits): 16 minute minute
Sign: U Default: Read from
RTC chip
Unit: second
Multiplier: Lower Limit: .000
1.000000000000 second Use to set or
Read/ Offset: 0
42744 Clock Second Upper Limit: 59.000 read current Real Time Clock
Write
Size (bits): 16 second second
Sign: U Default: Read from
RTC chip
0: Sunday
1: Monday
2: Tuesday
3: Wednesday Indicates day
Read
42745 Clock Day of the week for Real Time Clock
Only 4: Thursday current date
5: Friday
6: Saturday
Default:
Multiplier:
Unit: seconds Countdown
.100000000000
Read Lower Limit: seconds timer value for PTC Operating
42746 Start Timer Offset: 0
Only Upper Limit: seconds generator set Mode
Size (bits): 16 start timer
Default:
Sign: U
Multiplier:
Unit: seconds Countdown
.100000000000
Read Lower Limit: seconds timer value for PTC Operating
42747 Stop Timer Offset: 0
Only Upper Limit: seconds generator set Mode
Size (bits): 16 stop timer
Default:
Sign: U
Multiplier:
Unit: VDC Battery voltage
Low Battery .010000000000
Read Lower Limit: VDC with respect to Battery Voltage
42748 Voltage Offset: 0
Only Upper Limit: VDC set low battery Protection
Threshold Size (bits): 16
Default: threshold
Sign: U

A029X159 (Issue 19) 619 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: VDC Battery voltage
High Battery .010000000000
Read Lower Limit: VDC with respect to Battery Voltage
42749 Voltage Offset: 0
Only Upper Limit: VDC set high battery Protection
Threshold Size (bits): 16
Default: threshold
Sign: U
0: Gen Does Not Exist
1: Offline For load
Gen5 2: Waiting for Gen
Read demand use - Load Demand
42750 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen5
Default:
0: Gen Does Not Exist
1: Offline For load
Gen6 2: Waiting for Gen
Read demand use - Load Demand
42751 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen6
Default:
0: Gen Does Not Exist
1: Offline For load
Gen7 2: Waiting for Gen
Read demand use - Load Demand
42752 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen7
Default:
0: Gen Does Not Exist
1: Offline For load
Gen8 2: Waiting for Gen
Read demand use - Load Demand
42753 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen8
Default:

0: Run Status of the


Load Demand
Read load demand
42754 Gen5 Driver 1: Load Demand Stop Discrete Outputs
Only Gen5 driver
Status Default: output

0: Run Status of the


Load Demand
Read load demand
42755 Gen6 Driver 1: Load Demand Stop Discrete Outputs
Only Gen6 driver
Status Default: output

0: Run Status of the


Load Demand
Read load demand
42756 Gen7 Driver 1: Load Demand Stop Discrete Outputs
Only Gen7 driver
Status Default: output

0: Run Status of the


Load Demand
Read load demand
42757 Gen8 Driver 1: Load Demand Stop Discrete Outputs
Only Gen8 driver
Status Default: output

Copyright © 2017 Cummins Inc. 620 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7 Indicates which
7: Gen 8 generator set is
Read Load Demand
42758 GenE 8: Gen 9 currently GenE
Only Control
9: Gen 10 for load
10: Gen 11 demand
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default:

A029X159 (Issue 19) 621 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7 Indicates which
7: Gen 8 generator set is
Read Load Demand
42759 GenF 8: Gen 9 currently GenF
Only Control
9: Gen 10 for load
10: Gen 11 demand
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default:
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7 Indicates which
7: Gen 8 generator set is
Read Load Demand
42760 GenG 8: Gen 9 currently GenG
Only Control
9: Gen 10 for load
10: Gen 11 demand
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default:

Copyright © 2017 Cummins Inc. 622 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7 Indicates which
7: Gen 8 generator set is
Read Load Demand
42761 GenH 8: Gen 9 currently GenH
Only Control
9: Gen 10 for load
10: Gen 11 demand
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default:
0: Do Nothing Indicates
Add Level 7 Read Load Add Shed
42762 1: Add Level status of add
Command Only Control
Default: Do Nothing level 7

0: Do Nothing Indicates
Add Level 8 Read Load Add Shed
42763 1: Add Level status of add
Command Only Control
Default: Do Nothing level 8

0: Do Nothing Indicates
Add Level 9 Read Load Add Shed
42764 1: Add Level status of add
Command Only Control
Default: Do Nothing level 9

0: Do Nothing Indicates
Add Level 10 Read Load Add Shed
42765 1: Add Level status of add
Command Only Control
Default: Do Nothing level 10

0: Do Nothing Indicates add


Add Load 7 Read Load Add Shed
42766 1: Add Level command for
Command Only Control
Default: Do Nothing load 7

0: Do Nothing Indicates add


Add Load 8 Read Load Add Shed
42767 1: Add Level command for
Command Only Control
Default: Do Nothing load 8

0: Do Nothing Indicates add


Add Load 9 Read Load Add Shed
42768 1: Add Level command for
Command Only Control
Default: Do Nothing load 9

0: Do Nothing Indicates add


Add Load 10 Read Load Add Shed
42769 1: Add Level command for
Command Only Control
Default: Do Nothing load 10

A029X159 (Issue 19) 623 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates
Shed Level 6 Read Load Add Shed
42770 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 6

0: Do Nothing Indicates
Shed Level 7 Read Load Add Shed
42771 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 7

0: Do Nothing Indicates
Shed Level 8 Read Load Add Shed
42772 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 8

0: Do Nothing Indicates
Shed Level 9 Read Load Add Shed
42773 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 9

0: Do Nothing Indicates shed


Shed Load 7 Read Load Add Shed
42774 1: Shed Load command for
Command Only Control
Default: Do Nothing load 7

0: Do Nothing Indicates shed


Shed Load 8 Read Load Add Shed
42775 1: Shed Load command for
Command Only Control
Default: Do Nothing load 8

0: Do Nothing Indicates shed


Shed Load 9 Read Load Add Shed
42776 1: Shed Load command for
Command Only Control
Default: Do Nothing load 9

0: Do Nothing Indicates shed


Shed Load 10 Read Load Add Shed
42777 1: Shed Load command for
Command Only Control
Default: Do Nothing load 10

0: Do Nothing Indicates if
Restore Shed
Read shed level 6 Load Add Shed
42778 Level 6 1: Restore Level
Only has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 7 Load Add Shed
42779 Level 7 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 8 Load Add Shed
42780 Level 8 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 9 Load Add Shed
42781 Level 9 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

Copyright © 2017 Cummins Inc. 624 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Unit: hours
Multiplier:
.000277777780 Lower Limit: .000
Gen5 Online Read hours Total online System
42782 Offset: 0
Time Only Upper Limit: time for Gen5 Information
Size (bits): 32
1193046.000 hours
Sign: U
Default: 0
Unit: hours
Multiplier:
.000277777780 Lower Limit: .000
Gen6 Online Read hours Total online System
42784 Offset: 0
Time Only Upper Limit: time for Gen6 Information
Size (bits): 32
1193046.000 hours
Sign: U
Default: 0
Unit: hours
Multiplier:
.000277777780 Lower Limit: .000
Gen7 Online Read hours Total online System
42786 Offset: 0
Time Only Upper Limit: time for Gen7 Information
Size (bits): 32
1193046.000 hours
Sign: U
Default: 0
Unit: hours
Multiplier:
.000277777780 Lower Limit: .000
Gen8 Online Read hours Total online System
42788 Offset: 0
Time Only Upper Limit: time for Gen8 Information
Size (bits): 32
1193046.000 hours
Sign: U
Default: 0

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42790 Level 7 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 7

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42791 Level 8 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 8

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42792 Level 9 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 9

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42793 Level 10 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 10

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42794 Level 6 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 6

A029X159 (Issue 19) 625 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42795 Level 7 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 7

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42796 Level 8 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 8

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42797 Level 9 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 9
0: Gen Does Not Exist
1: Offline For load
Gen9 2: Waiting For Gen
Read demand use - Load Demand
42798 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen9
Default:
0: Gen Does Not Exist
1: Offline For load
Gen10 2: Waiting For Gen
Read demand use - Load Demand
42799 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen10
Default:
0: Gen Does Not Exist
1: Offline For load
Gen11 2: Waiting For Gen
Read demand use - Load Demand
42800 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen11
Default:
0: Gen Does Not Exist
1: Offline For load
Gen12 2: Waiting For Gen
Read demand use - Load Demand
42801 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen12
Default:
0: Gen Does Not Exist
1: Offline For load
Gen13 2: Waiting For Gen
Read demand use - Load Demand
42802 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen13
Default:

Copyright © 2017 Cummins Inc. 626 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen Does Not Exist
1: Offline For load
Gen14 2: Waiting for Gen
Read demand use - Load Demand
42803 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen14
Default:
0: Gen Does Not Exist
1: Offline For load
Gen15 2: Waiting for Gen
Read demand use - Load Demand
42804 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen15
Default:
0: Gen Does Not Exist
1: Offline For load
Gen16 2: Waiting for Gen
Read demand use - Load Demand
42805 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen16
Default:

Load Demand 0: Run Status of load


Read
42806 Gen9 Driver 1: Load Demand Stop demand Gen9 Discrete Outputs
Only
Status Default: driver output

Load Demand 0: Run Status of load


Read
42807 Gen10 Driver 1: Load Demand Stop demand Gen10 Discrete Outputs
Only
Status Default: driver output

Load Demand 0: Run Status of load


Read
42808 Gen11 Driver 1: Load Demand Stop demand Gen11 Discrete Outputs
Only
Status Default: driver output

Load Demand 0: Run Status of load


Read
42809 Gen12 Driver 1: Load Demand Stop demand Gen12 Discrete Outputs
Only
Status Default: driver output

Load Demand 0: Run Status of load


Read
42810 Gen13 Driver 1: Load Demand Stop demand Gen13 Discrete Outputs
Only
Status Default: driver output

Load Demand 0: Run Status of load


Read
42811 Gen14 Driver 1: Load Demand Stop demand Gen14 Discrete Outputs
Only
Status Default: driver output

Load Demand 0: Run Status of load


Read
42812 Gen15 Driver 1: Load Demand Stop demand Gen15 Discrete Outputs
Only
Status Default: driver output

Load Demand 0: Run Status of load


Read
42813 Gen16 Driver 1: Load Demand Stop demand Gen16 Discrete Outputs
Only
Status Default: driver output

A029X159 (Issue 19) 627 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42814 GenI 8: Gen9 currently GenI
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42815 GenJ 8: Gen9 currently GenJ
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

Copyright © 2017 Cummins Inc. 628 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42816 GenK 8: Gen9 currently GenK
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42817 GenL 8: Gen9 currently GenL
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

A029X159 (Issue 19) 629 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42818 GenM 8: Gen9 currently GenM
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42819 GenN 8: Gen9 currently GenN
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

Copyright © 2017 Cummins Inc. 630 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42820 GenO 8: Gen9 currently GenO
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42821 GenP 8: Gen9 currently GenP
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Do Nothing Indicates
Add Level 11 Read Load Add Shed
42822 1: Add Level status of add
Command Only Control
Default: Do Nothing level 11

0: Do Nothing Indicates
Add Level 12 Read Load Add Shed
42823 1: Add Level status of add
Command Only Control
Default: Do Nothing level 12

0: Do Nothing Indicates
Add Level 13 Read Load Add Shed
42824 1: Add Level status of add
Command Only Control
Default: Do Nothing level 13

A029X159 (Issue 19) 631 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates
Add Level 14 Read Load Add Shed
42825 1: Add Level status of add
Command Only Control
Default: Do Nothing level 14

0: Do Nothing Indicates
Add Level 15 Read Load Add Shed
42826 1: Add Level status of add
Command Only Control
Default: Do Nothing level 15

0: Do Nothing Indicates
Add Level 16 Read Load Add Shed
42827 1: Add Level status of add
Command Only Control
Default: Do Nothing level 16

0: Do Nothing Indicates
Add Level 17 Read Load Add Shed
42828 1: Add Level status of add
Command Only Control
Default: Do Nothing level 17

0: Do Nothing Indicates
Add Level 18 Read Load Add Shed
42829 1: Add Level status of add
Command Only Control
Default: Do Nothing level 18

0: Do Nothing Indicates add


Add Load 11 Read Load Add Shed
42830 1: Add Load command for
Command Only Control
Default: Do Nothing load 11

0: Do Nothing Indicates add


Add Load 12 Read Load Add Shed
42831 1: Add Load command for
Command Only Control
Default: Do Nothing load 12

0: Do Nothing Indicates add


Add Load 13 Read Load Add Shed
42832 1: Add Load command for
Command Only Control
Default: Do Nothing load 13

0: Do Nothing Indicates add


Add Load 14 Read Load Add Shed
42833 1: Add Load command for
Command Only Control
Default: Do Nothing load 14

0: Do Nothing Indicates add


Add Load 15 Read Load Add Shed
42834 1: Add Load command for
Command Only Control
Default: Do Nothing load 15

0: Do Nothing Indicates add


Add Load 16 Read Load Add Shed
42835 1: Add Load command for
Command Only Control
Default: Do Nothing load 16

0: Do Nothing Indicates add


Add Load 17 Read Load Add Shed
42836 1: Add Load command for
Command Only Control
Default: Do Nothing load 17

0: Do Nothing Indicates add


Add Load 18 Read Load Add Shed
42837 1: Add Load command for
Command Only Control
Default: Do Nothing load 18

Copyright © 2017 Cummins Inc. 632 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates
Shed Level 10 Read Load Add Shed
42838 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 10

0: Do Nothing Indicates
Shed Level 11 Read Load Add Shed
42839 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 11

0: Do Nothing Indicates
Shed Level 12 Read Load Add Shed
42840 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 12

0: Do Nothing Indicates
Shed Level 13 Read Load Add Shed
42841 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 13

0: Do Nothing Indicates
Shed Level 14 Read Load Add Shed
42842 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 14

0: Do Nothing Indicates
Shed Level 15 Read Load Add Shed
42843 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 15

0: Do Nothing Indicates
Shed Level 16 Read Load Add Shed
42844 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 16

0: Do Nothing Indicates
Shed Level 17 Read Load Add Shed
42845 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 17

0: Do Nothing Indicates shed


Shed Load 11 Read Load Add Shed
42846 1: Shed Load command for
Command Only Control
Default: Do Nothing load 11

0: Do Nothing Indicates shed


Shed Load 12 Read Load Add Shed
42847 1: Shed Load command for
Command Only Control
Default: Do Nothing load 12

0: Do Nothing Indicates shed


Shed Load 13 Read Load Add Shed
42848 1: Shed Load command for
Command Only Control
Default: Do Nothing load 13

0: Do Nothing Indicates shed


Shed Load 14 Read Load Add Shed
42849 1: Shed Load command for
Command Only Control
Default: Do Nothing load 14

0: Do Nothing Indicates shed


Shed Load 15 Read Load Add Shed
42850 1: Shed Load command for
Command Only Control
Default: Do Nothing load 15

A029X159 (Issue 19) 633 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates shed
Shed Load 16 Read Load Add Shed
42851 1: Shed Load command for
Command Only Control
Default: Do Nothing load 16

0: Do Nothing Indicates shed


Shed Load 17 Read/ Load Add Shed
42852 1: Shed Load command for
Command Write Control
Default: Do Nothing load 17

0: Do Nothing Indicates shed


Shed Load 18 Read/ Load Add Shed
42853 1: Shed Load command for
Command Write Control
Default: Do Nothing load 18

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 10 Load Add Shed
42854 Level 10 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 11 Load Add Shed
42855 Level 11 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

Addr. System Name Access Specifications Description Function

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 12 Load Add Shed
42856 Level 12 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 13 Load Add Shed
42857 Level 13 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 14 Load Add Shed
42858 Level 14 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 15 Load Add Shed
42859 Level 15 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 16 Load Add Shed
42860 Level 16 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 17 Load Add Shed
42861 Level 17 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

Copyright © 2017 Cummins Inc. 634 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen9 Online Read Hours Total online System
42862 Offset: 0
Time Only Upper Limit: time for Gen9 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen10 Online Read Hours Total online System
42864 Offset: 0
Time Only Upper Limit: time for Gen10 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen11 Online Read Hours Total online System
42866 Offset: 0
Time Only Upper Limit: time for Gen11 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen12 Online Read Hours Total online System
42868 Offset: 0
Time Only Upper Limit: time for Gen12 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen13 Online Read Hours Total online System
42870 Offset: 0
Time Only Upper Limit: time for Gen13 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen14 Online Read Hours Total online System
42872 Offset: 0
Time Only Upper Limit: time for Gen14 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen15 Online Read Hours Total online System
42874 Offset: 0
Time Only Upper Limit: time for Gen15 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0

A029X159 (Issue 19) 635 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen16 Online Read Hours Total online System
42876 Offset: 0
Time Only Upper Limit: time for Gen16 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42878 Level 11 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 11

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42879 Level 12 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 12

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42880 Level 13 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 13

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42881 Level 14 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 14

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42882 Level 15 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 15

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42883 Level 16 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 16

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42884 Level 17 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 17

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42885 Level 18 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 18

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42886 Level 10 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 10

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42887 Level 11 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 11

Copyright © 2017 Cummins Inc. 636 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42888 Level 12 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 12

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42889 Level 13 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 13

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42890 Level 14 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 14

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42891 Level 15 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 15

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42892 Level 16 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 16

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42893 Level 17 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 17
Indicates type
0: None of load
Load 11 Read/ 1: Breaker connected to Load Add Shed
42894
Device Type Write 2: ATS load 11 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 12 Read/ 1: Breaker connected to Load Add Shed
42895
Device Type Write 2: ATS load 12 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 13 Read/ 1: Breaker connected to Load Add Shed
42896
Device Type Write 2: ATS load 13 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 14 Read/ 1: Breaker connected to Load Add Shed
42897
Device Type Write 2: ATS load 14 add Control
Default: None shed control
and status I/O

A029X159 (Issue 19) 637 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Indicates type
0: None of load
Load 15 Read/ 1: Breaker connected to Load Add Shed
42898
Device Type Write 2: ATS load 15 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 16 Read/ 1: Breaker connected to Load Add Shed
42899
Device Type Write 2: ATS load 16 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 17 Read/ 1: Breaker connected to Load Add Shed
42900
Device Type Write 2: ATS load 17 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 18 Read/ 1: Breaker connected to Load Add Shed
42901
Device Type Write 2: ATS load 18 add Control
Default: None shed control
and status I/O
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 11 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42902 Offset: 0
Level Write Upper Limit: 18.000 11 is assigned Control
Size (bits): 0 to
Default: 11
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 12 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42903 Offset: 0
Level Write Upper Limit: 18.000 12 is assigned Control
Size (bits): 0 to
Default: 12
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 13 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42904 Offset: 0
Level Write Upper Limit: 18.000 13 is assigned Control
Size (bits): 0 to
Default: 13
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 14 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42905 Offset: 0
Level Write Upper Limit: 18.000 14 is assigned Control
Size (bits): 0 to
Default: 14
Sign: U

Copyright © 2017 Cummins Inc. 638 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA Indicates which
1.000000000000
Load 15 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42906 Offset: 0
Level Write Upper Limit: 18.000 15 is assigned Control
Size (bits): 0 to
Default: 15
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 16 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42907 Offset: 0
Level Write Upper Limit: 18.000 16 is assigned Control
Size (bits): 0 to
Default: 16
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 17 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42908 Offset: 0
Level Write Upper Limit: 18.000 17 is assigned Control
Size (bits): 0 to
Default: 17
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 18 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42909 Offset: 0
Level Write Upper Limit: 18.000 18 is assigned Control
Size (bits): 0 to
Default: 18
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 11 Shed Read/ Lower Limit: .000 shed level load Load Add Shed
42910 Offset: 0
Level Write Upper Limit: 17.000 11 is assigned Control
Size (bits): 0 to
Default: 10
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 12 Shed Read Lower Limit: .000 shed level load Load Add Shed
42911 Offset: 0
Level /Write Upper Limit: 17.000 12 is assigned Control
Size (bits): 0 to
Default: 11
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 13 Shed Read Lower Limit: .000 shed level load Load Add Shed
42912 Offset: 0
Level /Write Upper Limit: 17.000 13 is assigned Control
Size (bits): 16 to
Default: 12
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 14 Shed Read Lower Limit: .000 shed level load Load Add Shed
42913 Offset: 0
Level /Write Upper Limit: 17.000 14 is assigned Control
Size (bits): 16 to
Default: 13
Sign: U

A029X159 (Issue 19) 639 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA Indicates which
1.000000000000
Load 15 Shed Read Lower Limit: .000 shed level load Load Add Shed
42914 Offset: 0
Level /Write Upper Limit: 17.000 15 is assigned Control
Size (bits): 16 to
Default: 14
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 16 Shed Read Lower Limit: .000 shed level load Load Add Shed
42915 Offset: 0
Level /Write Upper Limit: 17.000 16 is assigned Control
Size (bits): 16 to
Default: 15
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 17 Shed Read Lower Limit: .000 shed level load Load Add Shed
42916 Offset: 0
Level /Write Upper Limit: 17.000 17 is assigned Control
Size (bits): 16 to
Default: 16
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 18 Shed Read Lower Limit: .000 shed level load Load Add Shed
42917 Offset: 0
Level /Write Upper Limit: 17.000 18 is assigned Control
Size (bits): 16 to
Default: 17
Sign: U
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenI for
Load Demand Read Load Demand
42918 8: Gen 9 fixed sequence
GenI /Write Shed Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen9

Copyright © 2017 Cummins Inc. 640 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenJ for
Load Demand Read Load Demand
42919 8: Gen 9 fixed sequence
GenJ /Write Shed Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen10
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenK for
Load Demand Read Load Demand
42920 8: Gen 9 fixed sequence
GenK /Write Shed Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen11

A029X159 (Issue 19) 641 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenL for
Load Demand Read Load Demand
42921 8: Gen 9 fixed sequence
GenL /Write Shed Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen12
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenM for
Load Demand Read Load Demand
42922 8: Gen 9 fixed sequence
GenM /Write Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen13

Copyright © 2017 Cummins Inc. 642 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenN for
Load Demand Read Load Demand
42923 8: Gen 9 fixed sequence
GenN /Write Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen14
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenO for
Load Demand Read Load Demand
42924 8: Gen 9 fixed sequence
GenO /Write Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen15

A029X159 (Issue 19) 643 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenP for
Load Demand Read Load Demand
42925 8: Gen 9 fixed sequence
GenP /Write Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen16
0: Missing
1: Good Indicates
Read 2: Connecting status of SID2
42926 SID2 Status Communications
Only 3: No Exp Board (aux101/102
4: Not Applicable module 2)
Default:
0: Missing
1: Good Indicates
Read 2: Connecting status of SID3
42927 SID3 Status Communications
Only 3: No Exp Board (aux101/102
4: Not Applicable module 3)
Default:
Indicates the
Expansion 0: Disabled status of the
Board Read 1: Enabled SID2 to
42928 Communications
Communication Only 2: Connecting expansion
s2 Default: Disabled board
connection
Indicates the
Expansion 0: Disabled status of the
Board Read 1: Enabled SID3 to
42929 Communications
Communication Only 2: Connecting expansion
s3 Default: Disabled board
connection

0: After Transfer Delay PTC - point in


Utility Breaker Read time at which
42930 1: Upon Utility Failure PTC Connected
Opening Point /Write system opens
Default: After Transfer Delay utility breaker

Copyright © 2017 Cummins Inc. 644 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


PTC - sets
0: Utility Disconnect point at which
Commit To 1: Genset Start
Read system PTC Operating
42931 Transfer
/Write 2: No Commit commits to Mode
Method
Default: Utility Disconnect transfer to
generator set
PTC - indicates
0: Not Committed if system is
Commit To Read PTC Operating
42932 1: Committed committed to
Transfer State Only Mode
Default: transferring to
generator set
Multiplier:
Unit: kW Sum of the
1.000000000000
Total System Read Lower Limit: kW generator set System
42933 Offset: 0
Capacity 32bit Only Upper Limit: kW kW ratings in Information
Size (bits): 32 32bit
Default:
Sign: S
Sum of the
Multiplier: generator set
Unit: kW
1.000000000000 kW ratings in
Total Online Read Lower Limit: kW System
42935 Offset: 0 32bit for
Capacity 32bit Only Upper Limit: kW Information
Size (bits): 32 generator sets
Default: which are
Sign: S
online
Multiplier: kW control
Unit: kW
kW Load 1.000000000000 reference value
Read Lower Limit: kW Master Load
42937 Reference Offset: 0 in 32bit for
Only Upper Limit: kW Control
32bit Size (bits): 3 extended
Default: paralleling
2Sign: S
Multiplier: kVAR control
Unit: kVAR
kVAR Load 1.000000000000 reference value
Read Lower Limit: kVAR Master Load
42939 Reference Offset: 0 in 32bit for
Only Upper Limit: kVAR Control
32bit Size (bits): 32 extended
Default: paralleling
Sign: S
Unit: kW Sets the base
Multiplier: Lower Limit: .000 kW load kW
Genset Bus
Read 1.000000000000Off Upper Limit: setpoint in Master Load
42943 kW Setpoint
/Write set: 0Size (bits): 2147483647.000 32bit in closed Control
32bit
32Sign: S kW loop extended
Default: 0 paralleling

Unit: kVAR
Multiplier: Lower Limit: .000 Sets the base
1.000000000000 kVAR load kVAR
Genset Bus
Read Offset: 0 setpoint in Master Load
42945 kVAR Setpoint Upper Limit:
/Write 32bit in closed Control
32bit Size (bits): 32 2147483647.000 loop extended
Sign: S kVAR paralleling
Default: 0

A029X159 (Issue 19) 645 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function


Unit: kW
Multiplier:
1.000000000000 Lower Limit: Setpoint for
Genset -2147483648.000 kW
Read Offset: 0 generator set Master Load
42947 Unloaded
/Write Upper Limit: unloaded level Control
Level 32bit Size (bits): 32
2147483647.000 kW in 32bit
Sign: S
Default:50
Unit: kW Sets the peak
Multiplier:
1.000000000000 Lower Limit: shave kW
Utility Bus kW Read -2147483648.000 kW setpoint in Master Load
42949 Offset: 0
Setpoint 32bit /Write Upper Limit: 32bit in closed Control
Size (bits): 32 loop extended
2147483647.000 kW
Sign: S paralleling
Default: 100
Unit: kW sets the utility
Multiplier:
1.000000000000 Lower Limit: kW constraint
Utility Bus kW -2147483648.000 kW
Read / Offset: 0 level in 32bit Master Load
42951 Constraint
write Upper Limit: for base load Control
Level 32bit Size (bits): 32
2147483647.000 kW extended
Sign: S paralleling
Default: 100
Unit: kVAR
Multiplier: Lower Limit: Sets the peak
1.000000000000 -2147483648.000 shave kVAR
Utility Bus kVAR
Read / Offset: 0 setpoint in Master Load
42953 kVAR Setpoint
write Upper Limit: 32bit in closed Control
32bit Size (bits): 32
2147483647.000 loop extended
Sign: S kVAR paralleling
Default: 100
Unit: kW
Multiplier:
1.000000000000 Lower Limit:
Utility -2147483648.000 kW Setpoint for
Read / Offset: 0 Master Load
42955 Unloaded utility unload
write Upper Limit: Control
Level 32bit Size (bits): 32 level in 32bit
2147483647.000 kW
Sign: S
Default: 50

Multiplier: Unit: kW generator set


Load Add Shed 1.000000000000 Lower Limit: .000 kW kW capacity
Required Read / Offset: 0 that must be Load Demand
42957 Upper Limit:
Online write online to start Control
Capacity 32bit Size (bits): 32 2147483647.000 kW timed load add;
Sign: S Default: 0 0 disables this
Sets how much
Multiplier: Unit: kW capacity must
Load Demand 1.000000000000 Lower Limit: .000 kW always be
Minimum Read / Offset: 0 Load Demand
42959 Upper Limit: online
Online write Control
Size (bits): 32 2147483647.000 kW regardless of
Capacity 32bit
Sign: S Default: 0 what the load
is

Copyright © 2017 Cummins Inc. 646 A029X159 (Issue 19)


8-2017 14. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function

Multiplier: Unit: kW Use to set how


1.000000000000 Lower Limit: 1.000 kW many kW
Total Utility Read / Offset: 0 (32bit) =100%
42961 Upper Limit: AC Setup
Capacity 32bit write utility kW --
Size (bits): 32 2147483647.000 kW used by
Sign: S Default: 1000 bargraph

Multiplier: Unit: kW Set the online


Genset Online 1.000000000000 Lower Limit: .000 kW kW threshold
Capacity Read / 32bit at which
42963 Offset: 0 Upper Limit: PTC Sensors
Sensor write generator set
Threshold 32bit Size (bits): 32 2147483647.000 kW but is available
Sign: S Default: 0 for loading
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW Set minimum
Load Demand
Read Offset: 0 kW reserve Load Demand
42965 Restart kW Upper Limit:
/Write capacity when Control
Threshold 32bit Size (bits): 32 2147483647.000 kW kW in 32bit
Sign: S Default: 500
Sets maximum
Multiplier: Unit: kW kW reserve
Load Demand 1.000000000000 Lower Limit: .000 kW capacity when
Read / Offset: 0 Load Demand
42967 Shutdown kW Upper Limit: threshold
write Control
Threshold 32bit Size (bits): 32 2147483647.000 kw method is
Sign: S Default: 1000 absolute kW in
32bit
Difference
Multiplier: between
Unit: kW
Total Spare 1.000000000000 sensed online
Read Lower Limit: kW System
42971 Online Offset: 0 capacity and
Only Upper Limit: kW Information
Capacity 32bit Size (bits): 32 generator Set
Default: bus total kW in
Sign: S
32bit

Multiplier: Shows 32 bit


Unit: kW kW threshold
Next Gen 1.000000000000
Read Lower Limit: kW for generator Load Demand
42973 Restart Offset: 0
Only Upper Limit: kW bus at which Control
Threshold 32bit Size (bits): 32
Default: next generator
Sign: S set will restart
Shows 32 bit
Multiplier: kW threshold
Unit: kW for generator
Next Gen 1.000000000000
Read Lower Limit: kW bus at which Load Demand
42975 Shutdown Offset: 0
Only Upper Limit: kW next generator Control
Threshold 32bit Size (bits): 32
Default: set load
Sign: S demand stops
in

A029X159 (Issue 19) 647 Copyright © 2017 Cummins Inc.


14. MCM3320 Modbus Register Map 8-2017

Addr. System Name Access Specifications Description Function

Multiplier: Calculated kW
Unit: kW overload
Genset Bus 1.000000000000
Read Lower Limit: kW threshold in System
42977 kW Overload Offset: 0
Only Upper Limit: kW 32bit based on Information
Threshold 32bit Size(bits): 32
Default: online capacity
Sign: S and % setting

Copyright © 2017 Cummins Inc. 648 A029X159 (Issue 19)


15 MCM3320 Modbus Fault Status
Bitmaps
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

Fault
Addr. Bit# System Name Event Name Response
Code
Utility Main Breaker Position Contact
42500 0 Fault Status Bitmap 1 1455 Warning
Warning
42500 1 Fault Status Bitmap 1 2396 Utility Main Breaker Fail To Close Warning Warning
42500 2 Fault Status Bitmap 1 2397 Utility Main Breaker Fail To Open Warning Warning
42500 3 Fault Status Bitmap 1 1219 Utility Main Breaker Tripped Warning Warning
42500 4 Fault Status Bitmap 1 1914 Utility Bus Phase Rotation Warning Warning
42500 5 Fault Status Bitmap 1 1912 Utility Bus Loss Of Phase Warning Warning
42500 6 Fault Status Bitmap 1 2331 Utility Bus Undervoltage Warning Warning
42500 7 Fault Status Bitmap 1 2358 Utility Bus Overvoltage Warning Warning
42500 8 Fault Status Bitmap 1 1223 Utility Bus Frequency Warning Warning
42500 21 Fault Status Bitmap 1 4137 Advanced Grid Protection Warning Warning
42500 22 Fault Status Bitmap 1 3924 Utility Reverse kW Warning Warning
42500 23 Fault Status Bitmap 1 2939 Modbus Communication Failure Warning Warning
42500 24 Fault Status Bitmap 1 2648 Remote IO Communication Failure Warning Warning
42500 25 Fault Status Bitmap 1 1689 Real Time Clock Power Interrupt Warning Warning
42500 26 Fault Status Bitmap 1 1335 AC Metering Out Of Range Warning Warning
42500 27 Fault Status Bitmap 1 1999 Maximum Parallel Time Warning Warning
42500 28 Fault Status Bitmap 1 343 Hardware Failure Warning Warning
42500 29 Fault Status Bitmap 1 1456 Synchronizer Output Limit Warning Warning
42500 30 Fault Status Bitmap 1 2416 Calibration Checksum Warning Warning
42500 31 Fault Status Bitmap 1 353 EEPROM Write Error Warning Warning

A029X159 (Issue 19) 649 Copyright © 2017 Cummins Inc.


15. MCM3320 Modbus Fault Status Bitmaps 8-2017

Fault
Addr. Bit# System Name Event Name Response
Code
Genset Main Breaker Position Contact
42502 0 Fault Status Bitmap 2 1454 Warning
Warning
42502 1 Fault Status Bitmap 2 1452 Genset Main Breaker Fail To Close Warning Warning
42502 2 Fault Status Bitmap 2 1453 Genset Main Breaker Fail To Open Warning
42502 3 Fault Status Bitmap 2 1328 Genset Main Breaker Tripped Warning Warning
42502 4 Fault Status Bitmap 2 1915 Genset Bus Phase Rotation Warning Warning
42502 5 Fault Status Bitmap 2 1913 Genset Bus Loss Of Phase Warning Warning
42502 6 Fault Status Bitmap 2 1225 Genset Bus Undervoltage Warning Warning
42502 7 Fault Status Bitmap 2 1224 Genset Bus Overvoltage Warning Warning
42502 8 Fault Status Bitmap 2 1226 Genset Bus Frequency Warning Warning
42502 22 Fault Status Bitmap 2 441 Low Battery Voltage Warning Warning
42502 23 Fault Status Bitmap 2 442 High Battery Voltage Warning Warning
42502 24 Fault Status Bitmap 2 1541 Genset Failed To Come Online Warning Warning
42502 25 Fault Status Bitmap 2 2647 Load Demand Setup Warning Warning
42502 26 Fault Status Bitmap 2 1444 Genset Bus Overload Warning Warning
42502 27 Fault Status Bitmap 2 1989 kW Load Control Output Limit Warning Warning
42502 28 Fault Status Bitmap 2 1991 kVAR Load Control Output Limit Warning Warning
42502 29 Fault Status Bitmap 2 1121 Failure To Disconnect Warning Warning
Synchronizer Phase Rotation Mismatch
42502 30 Fault Status Bitmap 2 1458 Warning
Warning
42502 31 Fault Status Bitmap 2 1457 Fail To Synchronize Warning Warning
42505 0 Fault Status Bitmap 1 1222 Not In Automatic Event Event
42505 1 Fault Status Bitmap 1 1483 Common Warning Event Event
42505 2 Fault Status Bitmap 1 2965 Genset Bus Available Event Event
42505 3 Fault Status Bitmap 1 2328 Utility Bus Available Event Event
42505 4 Fault Status Bitmap 1 2333 Genset Bus Connected Event Event
42505 5 Fault Status Bitmap 1 2332 Utility Bus Connected Event Event
42505 6 Fault Status Bitmap 1 2971 Test / Extended Parallel Event Event
42505 7 Fault Status Bitmap 1 1916 Synchronized Event Event
42505 8 Fault Status Bitmap 1 1534 Load Control Output Event Event
42505 9 Fault Status Bitmap 1 2781 Genset Source Unloaded Event Event
42505 10 Event Status Bitmap 1 2779 Utility Source Unloaded Event Event
42505 11 Event Status Bitmap 1 3226 Genset Bus Base Load Event Event
42505 12 Event Status Bitmap 1 3227 Utility Bus Peak Shave Event Event

Copyright © 2017 Cummins Inc. 650 A029X159 (Issue 19)


16 MCM3320 Modbus Address 42506,
42507
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

Metering Fault Status Bitmaps


Bit (LSB = 0) Parameter Metering Fault Status Bitmaps
0 ZXA Timeout Zero Crossing cannot be detected on L1 voltage signal
1 ZXB Timeout Zero Crossing cannot be detected on L2 voltage signal
2 ZXC Timeout Zero Crossing cannot be detected on L3 voltage signal
Voltage scaling error due to incompatible combination of
3 (See Note 1) Voltage Out of Range settings for Nominal Voltage, PT Primary Voltage, and PT
Secondary Voltage
Current Input is saturated; actual current cannot be
4 (See Note 1) Current Out of Range
determined
Frequency Out of
5 Frequency input is out of range; valid range 24-80 Hz
Range
Loss Phase Out of One or more zero crossings of voltage cannot be
6
Range detected; loss phase cannot be determined
Synchronizer phase difference cannot be measured due
to any of the following: genset frequency out of range,
Sync Phase Out of
7 utility frequency out of range, genset L1 voltage zero
Range
crossing not detected, or utility L1 voltage zero crossing
not detected
kW is out of range; valid range is - 2147483648 to
8 (See Note 1) kW Out of Range
+2147483647 kW
kVAR is out of range; valid range is - 2147483648 to
9 (See Note 1) kVAR Out of Range
+2147483647 kVAR
10 (See Note 1) kVA Out of Range kVA is out of range; valid range is 0 to 4294867295 kVA
Power Factor Out of Power factor is out of range due to either kW > kVA or
11 (See Note 1)
Range kVA = 0; should not normally occur
Main processor is unable to communicate with metering
12 AC Metering Failure
processor

A029X159 (Issue 19) 651 Copyright © 2017 Cummins Inc.


16. MCM3320 Modbus Address 42506, 42507 8-2017

Metering Fault Status Bitmaps


Bit (LSB = 0) Parameter Metering Fault Status Bitmaps
13 Not Implemented
14 Not Implemented
15 Not Implemented
NOTE:
1. If any of bits are active (1), the "AC Metering Out of Range Warning" fault
will be active.
2. If Bit 12 is active (1), the "Hardware Failure Warning" fault will be active.
3. Some bits do not generate warning faults because they are a normal occurrence (e.g. if a source is dead).

Copyright © 2017 Cummins Inc. 652 A029X159 (Issue 19)


17 PC500/550 Modbus TCP Register Map
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

PC500/550 (PC5xx)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40001 U ENUM 64= PC500/PC550
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40002 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40003 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40004 U ENUM
2=Not Communicating
Communications Error Counter 40005 U
Last Successful Communication
40006 U Bitfield See Note 5
(Year, Month)
Last Successful Communication
40007 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication
40008 U Bitfield See Note 5
(Seconds, Milliseconds)
PC500/550 (Device 1)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40011 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40012 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40013 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40014 U ENUM
2=Not Communicating
Communications Error Counter 40015 U

A029X159 (Issue 19) 653 Copyright © 2017 Cummins Inc.


17. PC500/550 Modbus TCP Register Map 8-2017

Last Successful Communication


40016 U Bitfield See Note 5
(Year, Month)
Last Successful Communication
40017 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication
40018 U Bitfield See Note 5
(Seconds, Milliseconds)
PC500/550 (Device 2)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40021 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40022 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40023 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40024 U ENUM
2=Not Communicating
Communications Error Counter 40025 U
Last Successful Communication
40026 U Bitfield See Note 5
(Year, Month)
Last Successful Communication
40027 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40028 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 3)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40031 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40032 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40033 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40034 U ENUM
2=Not Communicating
Communications Error Counter 40035 U
Last Successful Communication
40036 U Bitfield See Note 5
(Year, Month)
Last Successful Communication
40037 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication
40038 U Bitfield See Note 5
(Seconds, Milliseconds)

Copyright © 2017 Cummins Inc. 654 A029X159 (Issue 19)


8-2017 17. PC500/550 Modbus TCP Register Map

PC500/550 (Device 4)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40041 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40042 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40043 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40044 U ENUM
2=Not Communicating
Communications Error Counter 40045 U
Last Successful Communication
40046 U Bitfield See Note 5
(Year, Month)
Last Successful Communication
40047 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication
40048 U Bitfield See Note 5
(Seconds, Milliseconds)
PC500/550 (Device 5)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40051 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40052 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40053 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40054 U ENUM
2=Not Communicating
Communications Error Counter 40055 U
Last Successful Communication See Note 5
40056 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40057 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40058 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 6)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40061 U ENUM 1=Genset, 2=ATS, 4=AUX101/102

A029X159 (Issue 19) 655 Copyright © 2017 Cummins Inc.


17. PC500/550 Modbus TCP Register Map 8-2017

0=N/A, 1=3300, 2=2300, 4=1301,


Device Model 40062 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40063 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40064 U ENUM
2=Not Communicating
Communications Error Counter 40065 U
Last Successful Communication See Note 5
40066 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40067 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40068 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 7)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40071 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40072 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40073 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40074 U ENUM
2=Not Communicating
Communications Error Counter 40075 U
Last Successful Communication See Note 5
40076 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40077 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40078 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 8)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40081 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40082 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40083 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40084 U ENUM
2=Not Communicating

Copyright © 2017 Cummins Inc. 656 A029X159 (Issue 19)


8-2017 17. PC500/550 Modbus TCP Register Map

Communications Error Counter 40085 U


Last Successful Communication See Note 5
40086 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40087 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40088 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 9)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40091 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40092 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40093 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40094 U ENUM
2=Not Communicating
Communications Error Counter 40095 U
Last Successful Communication See Note 5
40096 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40097 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40098 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 10)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40101 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40102 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40103 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40104 U ENUM
2=Not Communicating
Communications Error Counter 40105 U
Last Successful Communication See Note 5
40106 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40107 U Bitfield
(Day, Hour, Minutes)

A029X159 (Issue 19) 657 Copyright © 2017 Cummins Inc.


17. PC500/550 Modbus TCP Register Map 8-2017

Last Successful Communication See Note 5


40108 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 11)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40111 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40112 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40113 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40114 U ENUM
2=Not Communicating
Communications Error Counter 40115 U
Last Successful Communication See Note 5
40116 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40117 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40118 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 12)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40121 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40122 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40123 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40124 U ENUM
2=Not Communicating
Communications Error Counter 40125 U
Last Successful Communication See Note 5
40126 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40127 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40128 U Bitfield
(Seconds, Milliseconds)

Copyright © 2017 Cummins Inc. 658 A029X159 (Issue 19)


8-2017 17. PC500/550 Modbus TCP Register Map

NOTES:
1. Modbus TCP can be enabled/disabled in the PC500/550 User Interface (Setup > Modbus Settings).
2. Default Modbus TCP port is 502 and is configurable in the PC500/550 User Interface (Setup > Modbus Settings).
No more than 2 Modbus TCP sessions can be established at a time.
3. PC5xx provides READ ONLY access over Modbus TCP.
4. PC500/550 registers return details about all configured devices in PC5xx (Generator Set, ATS, AUX101/102) and
can be accessed using Modbus TCP Unit ID 255 (default for PC500/550).
5. In PC500/550 registers, Devices 1 through 12 are numbered in the same order as they are arranged in the
Interface Device Configuration grid. To access details of these devices over Modbus TCP, the user must use the
Modbus TCP Unit ID (returned by register 4xxx3) in the query.
6. Bitmap registers indicating Last Successful Communication (4xxx6, 4xxx7, 4xxx8) are formatted as below:

7. Site IOs (sensors) and AUX101/102 data cannot be accessed over Modbus TCP.

Generator Set
Modbus
Scale Sign Units Description Comments
Register
40001 1 U ENUM Switch Position 0=Off, 1=AUTO, 2=Manual
0=Stopped, 1=Pending, 2=Warm
Up, 3=Running, 4=Cool Down
40002 1 U ENUM Control State (rated),
5=Cool Down (idle)
40003 1 U Fault Code
0=Normal, 1=Warning,
2=Derate,
40004 1 U ENUM Fault Type
3=Shutdown w/Cooldown,
4=Shutdown
40005 1 U Bitfield NFPA110 See Table 8 on page 457
40006 1 U Bitfield NFPA Extended See Table 9 on page 457
40007 1 U Volts L1N Voltage
40008 1 U Volts L2N Voltage
40009 1 U Volts L3N Voltage
40010 1 U Volts L1L2 Voltage
40011 1 U Volts L2L3 Voltage
40012 1 U Volts L3L1 Voltage
40013 1 U Amps L1 Current

A029X159 (Issue 19) 659 Copyright © 2017 Cummins Inc.


17. PC500/550 Modbus TCP Register Map 8-2017

Generator Set
Modbus
Scale Sign Units Description Comments
Register
40014 1 U Amps L2 Current
40015 1 U Amps L3 Current
40016 1 S kVA Total kVA
40017 0.01 U Hz Frequency
40018 0.1 U % PercentAmps APhase
40019 0.1 U % PercentAmps BPhase
40020 0.1 U % PercentAmps CPhase
40021 1 S kW Total kW
40022 0.01 S Total Power Factor
40023 0.01 S Volts Battery Voltage
40024 0.1 S psi Oil Pressure
40025 0.1 S _F Oil Temperature
40026 0.1 S _F Coolant Temperature
40027 1 U GPH Fuel Rate
40028 0.1 U Gallons Fuel Level
40029 1 U RPM Average Engine Speed
40030 1 U Engine Starts
40031 0.1 U Hours Engine Runtime

ATS
Modbus
Scale Sign Units Description Comments
Register
0=Test 1=Utility/Genset,
40001 1 U ENUM Mode 2=Utility/Utility,
3=Genset/Genset
0=None,
1=EngineStartASource2,
2=EngineStartBSource1,
3=NormaltoEmergency (TDNE),
4=EmergencytoNormal (TDEN),
40002 1 U ENUM Active Transfer Timer 5=EngineCooldownA (TDECa),
6=EngineCooldownB (TDECb),
7=ProgramTransition (TDPT),
8=Transfer Pend./Elevator
(TDEL),
255=Unknown

Copyright © 2017 Cummins Inc. 660 A029X159 (Issue 19)


8-2017 17. PC500/550 Modbus TCP Register Map

ATS
Modbus
Scale Sign Units Description Comments
Register
40003 1 U Fault Code
40004 1 U ENUM Fault Type 0=No Faults, 1=Warning
40005 1 U Bitfield NFPA110 See Table 10 on page 458
40006 1 U Bitfield NFPA Extended See Table 11 on page 458
40007 1 U Volts L1N Voltage (Load)
40008 1 U Volts L2N Voltage (Load)
40009 1 U Volts L3N Voltage (Load)
40010 1 U Volts L1L2 Voltage (Load)
40011 1 U Volts L2L3 Voltage (Load)
40012 1 U Volts L3L1 Voltage (Load)
40013 1 U Amps L1 Current (Load)
40014 1 U Amps L2 Current (Load)
40015 1 U Amps L3 Current (Load)
40016 1 S kW Total kW (Load)
40017 0.01 S Total Power Factor (Load)
40018 1 S kVAR Total kVAR (Load)
40019 1 S kVA Total kVA (Load)
40020 0.01 U Hz Frequency (Load)
40021 0.1 U % PercentAmps APhase (Load)
40022 0.1 U % PercentAmps BPhase (Load)
40023 0.1 U % PercentAmps CPhase (Load)
40024 1 U Volts L1N Voltage Source1
40025 1 U Volts L2N Voltage Source1
40026 1 U Volts L3N Voltage Source1
40027 1 U Volts L1L2 Voltage Source1
40028 1 U Volts L2L3 Voltage Source1
40029 1 U Volts L3L1 Voltage Source1
40037 0.01 U Hz Frequency Source1
40041 1 U Volts L1N Voltage Source2
40042 1 U Volts L2N Voltage Source2
40043 1 U Volts L3N Voltage Source2
40044 1 U Volts L1L2 Voltage Source2

A029X159 (Issue 19) 661 Copyright © 2017 Cummins Inc.


17. PC500/550 Modbus TCP Register Map 8-2017

ATS
Modbus
Scale Sign Units Description Comments
Register
40045 1 U Volts L2L3 Voltage Source2
40046 1 U Volts L3L1 Voltage Source2
40054 0.01 U Hz Frequency Source2

Copyright © 2017 Cummins Inc. 662 A029X159 (Issue 19)


18 AUX101/102 Modbus Register Map
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

System
Addr. Access Specifications Comments
Name

Default: Modbus Changing the address causes no


Modbus Read As supported by Address 13 communication with the annunciator
43044
Device ID Only Modbus protocol until the Modbus Master also
Type: Trim changes its sending address.
0: 2400 Baud
1: 4800 Baud
Changing the baud rate causes no
Modbus Read 2: 9600 Baud Default: 3 communication with the annunciator
43045
Baud Rate Only 3: 19200 Baud Type: Trim until the Modbus Master also
changes its baud rate.
4: 38400 Baud
5: 57600 Baud
0: Even Changing the parity causes no
Modbus Read Default: 2 communication with the annunciator
43046 1: Odd
Parity Only Type: Trim until the Modbus Master also
2: None changes its parity.

1 Changing the stop bits causes no


Modbus Read Default: 1 communication with the annunciator
43047
Stop Bits Only 2 Type: Trim until the Modbus Master also
changes its stop bits.
Changes the communication
Read 0: RS485 Default: 0 protocol between RS485 and
43048 Protocol Modbus.
Only Type: Trim
1: Modbus

Software Read Default: NA Sends AUX101 current firmware


43049
Version Only Type: Trim version.

Device Read Default: 59


43050 AUX101 Device Type
Type Only Type: Trim

AUX 102 Read 0: Not Available Default: 0 Indicates if AUX102 expansion


43051
Available Only 1: Available Type: Trim board is available.

A029X159 (Issue 19) 663 Copyright © 2017 Cummins Inc.


18. AUX101/102 Modbus Register Map 8-2017

System
Addr. Access Specifications Comments
Name
0: Do Nothing Save configuration parameters or
adjustments to non-volatile
Read/ Do Nothing memory. Perform Save Trims after
43052 Save Trims
Write 1: Save Trims Type: Trim all configurations have been
updated. Do not save trims unless
a change has occurred.
Relay 1
Parameters to allow the Relay to be
Relay 2
turned on/off. The lower 8 bits are
Relay 3 used to store out relay values.
Relay 1 is stored in bit 0 and Relay
Relay 4 Read/ 0: Inactive 8 is stored in bit 7. The upper 8 bits
42001 Default: 0
Relay 5 Write 1: Active are 0. In the event of a power cycle
or reboot, all the output values are
Relay 6 reset to 0. This register is used as
heartbit for AUX101 and indicates a
Relay 7
secure communication.
Relay 8
Relay 9
Relay 10
Relay 11
Relay 12 Read/ 0: Inactive Parameters to allow the Relay to be
42009 Default: 0
Relay 13 Write 1: Active turned on/off.

Relay 14
Relay 15
Relay 16
Read Register that contains the value of
42017 Input 1 Default: NA
Only Input 1.
Read Register that contains the value of
42018 Input 2 Default: NA
Only Input 2.
Read Register that contains the value of
42019 Input 3 Default: NA
Only Input 3.
Read Register that contains the value of
42020 Input 4 Default: NA
Only Input 4.
Read Register that contains the value of
42021 Input 5 Default: NA
Only Input 5.
Read Register that contains the value of
42022 Input 6 Default: NA
Only Input 6.
Read Register that contains the value of
42023 Input 7 Default: NA
Only Input 7.
Read Register that contains the value of
42024 Input 8 Default: NA
Only Input 8.

Copyright © 2017 Cummins Inc. 664 A029X159 (Issue 19)


8-2017 18. AUX101/102 Modbus Register Map

System
Addr. Access Specifications Comments
Name
Bit 0 of this register is used for
Input 9
Input 9 when AUX102 is available.
Bit 1 of this register is used for
Input 10
Read Input 10 when AUX102 is available.
42025 Default: NA
Only Bit 2 of this register is used for
Input 11
Input 11 when AUX102 is available.
Bit 3 of this register is used for
Input 12
Input 12 when AUX102 is available.
Current Default: NA
Read/
42029 Source 1 mA = CS/10 Set for Analog Input 3.
Write Type: Trim
Settings
Current Default: NA
Read/
42030 Source 2 mA = CS/10 Set for Analog Input 4.
Write Type: Trim
Settings
Current Default: NA
Read/
42031 Source 3 mA = CS/10 Set for Analog Input 5.
Write Type: Trim
Settings
Current Default: NA
Read/
42032 Source 4 mA = CS/10 Set for Analog Input 6.
Write Type: Trim
Settings
0: Sender
Input 1 Read/ Default: NA
42033 1: Switch - Active Low Register to configure Input 1.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 2 Read/ Default: NA
42034 1: Switch - Active Low Register to configure Input 2.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 3 Read/ Default: NA
42035 1: Switch - Active Low Register to configure Input 3.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 4 Read/ Default: NA
42036 1: Switch - Active Low Register to configure Input 4.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 5 Read/ Default: NA
42037 1: Switch - Active Low Register to configure Input 5.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 6 Read/ Default: NA
42038 1: Switch - Active Low Register to configure Input 6.
Settings Write Type: Trim
2: Switch - Active High

A029X159 (Issue 19) 665 Copyright © 2017 Cummins Inc.


18. AUX101/102 Modbus Register Map 8-2017

System
Addr. Access Specifications Comments
Name
0: Sender
Input 7 Read/ Default: NA
42039 1: Switch - Active Low Register to configure Input 7.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 8 Read/ Default: NA
42040 1: Switch - Active Low Register to configure Input 8.
Settings Write Type: Trim
2: Switch - Active High

Copyright © 2017 Cummins Inc. 666 A029X159 (Issue 19)


power.cummins.com