Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Technical Specifications
Single, split & three phase configurations.
Service Voltage:
Product Features See Chart
50,000 Amps per phase,
50,000 Amp surge current rating ensures long Surge Current Rating:
service life 25,000 Amps per mode
Operating
-40°F - 140°F (-40°C - 60°C)
Temperature:
Applications
Maximum Humidity: 95% non-condensing
Branch Panel
3.5”Lx 2.4”W x 3.5”H
Small Disconnects and Service Panels Dimensions:
(89mm x 61mm x 89mm)
Weight: 1.2 lb. (.5kg)
Every precaution has been taken to ensure that this literature is accurate and complete. DITEK Corporation assumes no responsibility and disclaims all liability for damages resulting from the use of this information or for any errors or omissions.
One DITEK Center 1720 Starkey Road - Largo, FL 33771 Doc. Number: SPS-100073-001 Rev 5 01-16
Phone: 1-800-753-2345 Direct: 727-812-5000 ©2016 DITEK Corp.
Technical Support: 1-888-472-6100 Page 1 of 2
www.ditekcorp.com
Service Voltage Protection Rating (VPR)
Service UL In
Part Number Configuratio MCOV
Voltage Rating L-G L-L L-N N-G
n
D50-120/2401 Split Ø
120/240VAC 150V/300V 20kA 1000V 1200V 600V 600V
D50-120/240HD (3W + G)
Three Ø
D50-120/2083Y
120/208VAC Wye 150V/300V 20kA 1000V 1200V 600V 600V
D50-127/2203Y
(4W + G)
Three Ø
1000V 1200V 600V/
High Leg
D50-120/240HL 120/240VAC 150V/320V 10kA HL-G HL-L HL-N 600V
Delta
1500V 1500V 1200V
(4W + G)
D50-2401 Single Ø
240VAC 320V 10kA 1200V N/A 1200V 2000V
D50-240HW (2W + G)
D50-277/4803Y
Three Ø
D50-220/3803Y
277/480VAC Wye 320V/640V 10kA 2000V 2000V 1200V 1200V
D50-230/4003Y
(4W + G)
D50-240/4153Y
Three Ø
D50-347/6003Y 347/600VAC Wye 420V/840V 10kA 2500V 2500V 1500V 1500V
(4W + G)
Three Ø
D50-2403D 240VAC Delta 320V/640V 10kA 1200V 2000V N/A N/A
(3W + G)
Three Ø
D50-4803D 480VAC Delta 550V/1100V 10kA 1800V 4000V N/A N/A
(3W + G)
Page 2 of 2