Daikin Industries, Ltd.

’s products are manufactured for export to numerous countries throughout the


PCS0626A
Warning
world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a
particular country. Prior to purchase, please therefore confirm with your local authorized importer,
distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for
use, in the region where the product will be used. This statement does not purport to exclude, restrict
or modify the application of any local legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any inquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an
outdoor unit with anti-corrosion treatment.

About ISO9001 About ISO 14001


ISO 9001 is a plant certification ISO 14001 is the standard defined by the
system defined by the International International Organization for
Organization for Standardization (ISO) Standardization (ISO) relating to
relating to quality assurance. ISO environmental management systems. Our
9001 certification covers quality group has been acknowledged by an
assurance aspects related to the internationally accredited compliance
“ design, development, manufacture, organisation as having an appropriate
installation, and supplementary programme of environmental protection
JMI-0107 JQA-1452 service” of products manufactured at EC99J2044 JQA-E-90108 procedures and activities to meet the
AIR CONDITIONING SYSTEM
Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi, COOLING ONLY [ 50 Hz ]
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
c All rights reserved
Printed in Japan 10/06/003 SW • HP • SS

Specifications, designs and other content appearing in this brochure are current as of October 2006 but subject to change without notice. Printed on 100% recycled paper with soy ink.
The match for
tastefully designed offices and stores. CEILING SUSPENDED TYPE
Simple design and quiet
operation
Auto-swing airflow brings
comfort to each and every
corner of the room.
Installation and
maintenance are easy.

DUCT CONNECTION TYPE


People are drawn to beautifully designed stores that express the latest.
The indoor unit is installed
People work best in offices imbued with functional beauty.
inside the ceiling and ducts
Daikin’s SkyAir is the choice to bring high quality air conditioning to CEILING MOUNTED CASSETTE TYPE blow the air in any direction.
stores and offices like this. Comfort is provided without
This unit is installed at center even knowing that an air
Thanks to its many advantages such as quiet operation, ease of use and
ceiling. Air is blown in four conditioner is installed.
flexible installation, the SkyAir enjoys an excellent reputation throughout directions to bring comfort.
the world wherever it is used. Operation is quiet.

Cooling only
HP 2 2.5 3 4 5 6 6.5 7

apacity *
1
Btu/h 18,000 21,000 26,000 36,000 42,000 48,000 51,000 56,000
values given for kW 5.3 6.2 7.6 10.6 12.3 14.1 15.0 16.4
–6 HP is for FHC type,
HP–7 HP is for FDMG type. kcal/h 4,560 5,290 6,550 9,100 10,600 12,100 12,900 14,100

EILING MOUNTED
ASSETTE TYPE
Indoor unit FHC18NUV1 FHC21NUV1 FHC26NUV1 FHC36NUV1 FHC42NUV1 FHC48NUV1
Outdoor unit R18NUV1 R21NUV1 R26NUV1 / Y1 R36NUV1 / Y1 R42NUY1 R48NUY1

EILING SUSPENDED TYPE


CEILING MOUNTED
CASSETTE TYPE FHC-NU Unified square panels
All models from the 18NU to 48NU
use the same size panel. Multiple
unit installations maintain a physical
Compact body and quiet operation
Indoor units use an
aerodynamically designed
Draft resistance has been reduced
by incorporating, into a single unit,

Quiet, decor-blending form and easy installation uniformity that is aesthetically


pleasing and make it easier to plan
Diffuser Turbo Fan an impeller and a diffuser to control
air flow inside the unit. The Diffuser

in new or old buildings. ceiling lighting systems and to


design interiors.
Diffus er Turbo Fan is both quiet during
operation and compact.
(220V)

Indoor unit High Low


Same for 18NU 33 dB 29 dB
all models

950 mm
B lade
21NU 35 dB 30 dB
26NU 35 dB 30 dB
36NU 42 dB 36 dB
42NU 42 dB 36 dB
950 mm
48NU 42 dB 36 dB

Optimal comfort and convenience assured by three blow modes Quick and easy to install
Blow direction Draft prevention setting Standard setting Setting to prevent soiling of ceiling
Sound level
Desired situation When drafts are unwanted For gentle drafts(Ceiling is soiled.) When ceilings must be kept spotless Just 240 mm thick. Installable

Cooling only
FHC18NU–48NU
42/ 36 High
FHC36NU
Low
dB Auto-swing

Blow direction
can be set to
Auto-s wing between
10° and 40°

S ettable to 5 different
levels between
Auto-s wing between
10° and 65°

S ettable to 5 different
levels between
Auto-s wing between
30° and 65°

S ettable to 5 different
levels between
under low-lying beams (18NU—26NU)

240 mm *1 245 mm *2
(220V) 5 levels 10° and 40° 10° and 65° 30° and 65°
Draft prevention At heating s tartup and thermo OFF*, air blow is auto- At heating startup and ther-
mo OFF*, air blow is auto-
(In heating mode) matic ally s et to a near horizontal 10˚ to prevent direc t matically set to 30˚ to prevent both direct expo-
expos ure to c ool air drafts . sure to cool air drafts and contact with ceilings.
*1 298 mm thic k with 36NU– 48NU
Auto blow The las t blow direc tion is s aved in memory and automatic ally s et the next time the unit is
direction control turned ON. (Fac tory s etting is 65˚ for heating and 30˚ for c ooling.) *2 303 mm thic k with 36NU– 48NU
Option Note: B low direc tion is s et to the s tandard pos ition when the unit is s hipped from the fac tory.
Easy height adjustment
Accessory required for indoor unit The pos ition c an be c hanged from the remote c ontroller.
*When the thermos tat turns off.
Each corner of the unit has an
Wired LCD remote controller Multi-Flow System Wide air distribution Adjuster Pocket that
lets you easily adjust
4-way blow A newly shaped air discharge
the unit's suspended
BRC1C61 1 pattern opening increases flow without
height.
increasing wind speed. Discharged
3-way blow
air reaches farther than before. Note: If the wireless remote
Note: R emote c ontroller c able not 4 pattern c ontrol option is installed,
inc luded. C ables must be Air blow distribution comparison a light rec eptor unit is
•42NU (m)
proc ured loc ally. Super Cassette 3.2
housed in one of the ad-
(m) Conventional model 3
2.7 2.5 m/sec
2.0 m/sec
2.5 m/sec All models suspended
2 2
Wireless LCD remote controller 2-way blow 1.5 m/sec 2.0 m/sec without lift
3 pattern 1 1.0 m/sec 1.5 m/sec
A s ignal rec eiver mus t be added to the indoor unit. 1.0 m/sec 1
0.5 m/sec 0.5 m/sec
BRC7C613W " " denotes piping direction. " " denotes sealing
member for air discharge outlet (option) . 4 (m) 3 2 1 0 1 2 3 4 (m)
90° rotating
Note: For 3-way or 2-way blow ins tallation, the
air intake grille
s ealing member for air dis c harge outlet
(option) mus t be us ed to c los e off the
Installable on high ceilings
Signal receiver unit
unus ed outlet(s ). Criteria for ceiling height and number of Ins talled in
(Installed type) blow outlets any direc tion.
Blow direction can be selected Number of blow outlets used
Wireles s remote c ontroller and s ignal according to installation. 18NU–26NU 36NU–48NU
rec eiver unit are s old as a s et. 4-way 3-way 2-way 4-way 3-way 2-way
blow blow blow blow blow blow
Provided with drain water
Note: Operation nois e
Standard 2.7 m 3.0 m 3.5 m 3.2 m 3.6 m 4.2 m
inc reas es when Ceiling
High ceiling 3.0 m 3.3 m 3.8 m 3.6 m 4.0 m 4.2 m
us ing 2-way
or 3-way
height
High ceiling 3.5 m 3.5 m - 4.2 m 4.2 m - lift-up mechanism
Features Note: Fac tory s ettings are for s tandard c eiling
height and 4-way blow. High c eiling s ettings
Mildew
Feature Comfort prevention Work & Servicing Control features 1 and 2 are s et with the remote
Easy installation of options
C eiling s oiling prevention

Program "Dry"
Mold res is tant treatment
High c eiling applic ation
S wing pattern s elec tion

S witc hable fan s peed

Two selectable thermo-sensors The high-performance filter and


High-effic ienc y filter

Fres h air intake kit

Dehumidification is computer
Ultra long-life filter
Drain water lift-up

other options are easily clipped into


Pre-c harged for

Both indoor unit and wired remote controlled to prevent abrupt and
Two s elec table
thermo-s ens ors

Timer s elec tor


Program "Dry"

Long-life filter

place. There is no need for a


up to 15 m

controller (option) contain thermo- uncomfortable changes in air


Auto-res tart
mec hanis m
Auto s wing

Filter s ign

screwdriver.
for filter

sensors. Temperature detection can be temperature.


Model set at the unit or, to further improve 750 mm
Switchable fan speed:
Cooling only • • • • • *1
• • • *2
• • • • • • • comfort level, closer to the target area
High/Low
*1Applic able when wired remote c ontroller is us ed at the wired remote control.
*2Applic able to R 36NU– R 48NU outdoor units
*Thermo-s ens or on indoor unit mus t be us ed
when the air c onditioner is c ontrolled from an-
other room.
(Wireles s remote c ontroller does not have a

3 4
CEILING SUSPENDED TYPE FH-NU
Upgrade to an quiet and compact system.
Spreads comfortable air throughout the room Quiet operation
Quiet operation has been
Auto-swing (up&down) Installable on ceilings emphasized even more on the
brings comfort to the room. 3.5 m high exposed ceiling suspended type unit.
(220V)

Wide air discharge openings Indoor unit High Low


produce a spreading 100° 21NU 44 dB 40 dB
air flow 26NU 44 dB 40 dB
Switchable fan speed:
36NU 46 dB 40 dB
High/Middle/Low
42NU 48 dB 42 dB
48NU 49 dB 43 dB
Sound level
Program "Dry"
Cooling only
FH21NU—48NU
46/ 40
High
FH36NU
Low
dB New model
100°
Dehumidification is computer
controlled to prevent abrupt and
uncomfortable changes in air
Uses new quiet stream fan
and other quiet
technologies.
(220V) Air is blown up to 50° in temperature.
the downward direction. Turbulent flow Straightening New quiet
is produced vane stream fan

Option
Accessory required for indoor unit 50°

Wired LCD remote controller Easier to maintain


Long-life filter lasts about half
BRC1NU61 Easier installation for greater freedom of design year * maintenance not required
* For dust concentration of 0.15 mg/m3

Uniform height and depth. All wiring and internal


Note: R emote c ontroller c able not Narrower design for small- servicing done from below Non-dew flap without bristles
inc luded. C ables must be
proc ured loc ally. capacity models to meet tighter the unit Absence of bristles minimizes clinging
dimensional constraints. dirt and simplifies
(mm) Pipes more easily rigged, too cleaning.
Wireless LCD remote controller Indoor unit 21NU 26NU 36NU 42NU 48NU
A s ignal rec eiver mus t be added to the indoor unit. Plastic panels are used to conceal Non-dew flap

Height 195 piping holes. Holes can be easily


BRC7NU66 Width 1,160 1,590 punched out without requiring Easy-clean, flat surfaces
Depth 680 special tools. It is easy to wipe dirt off the flat
Weight of all models reduc ed (down 10% side and lower surfaces of the unit.
c ompared with previous models ). Trans fer and
ins tallation work is les s arduous .
Signal receiver unit (Installed type)
Less need for edge space, For all maintenance tasks,
Wireles s remote c ontroller and s ignal
rec eiver unit are s old as a s et.
more freedom of installation access is from below.
Work is easier.
The unit fits more snugly into tight
spaces.
For 48NU indoor unit Improved-oil resistant
Features
Feature Comfort
Mildew
Work & Servicing
Control grille
prevention features
Oil-resistant plastic is used for the air
Mold res is tant treatment

30 mm 1,590 mm 30 mm
S witc hable fan s peed

or more or more discharge grille. This improves


*Water used in the test-run can now be drained from the air durability in restaurants and other
Pre-c harged for
Mildew-proofing

similar environments.
Timer s elec tor
Program "Dry"

discharge opening rather than from the side as was formerly


Long-life filter
up to 15 m

the case.
Auto-res tart
Auto s wing

drain pan

Note: Intended for use in salons, dining rooms, and


for filter

ordinary sales floors, this specification is not


Model suitable for kitchens or other harsh environments.

Cooling only • • • • • • *1
• •
*1Applic able to R 36NU– R 48NU outdoor units

5 6
DUCT CONNECTION DUCT CONNECTION
MIDDLE STATIC PRESSURE TYPE FDMG-NU LOW STATIC PRESSURE TYPE FDBG-NU
Unit can be mounted in the Ideal for quiet, beautiful living
ceiling and air can be delivered spaces
freely by duct. Suitable for condominiums and
Superior freedom of layout apartments, houses and hotels,
and similar living areas
The duct system allows the most efficient location
of discharge outlets in accordance with the room
layout Handy
Medium static pressure type, usable in a larger Small, lightweight, and easy-to-install outdoor unit.
than standard space
Duct connection is simpler with standard rear Quiet operation
intake chambers (220V)

Indoor unit High Low


Ordinary duct
(procured locally)
Air conditioner Ordinary duct
(procured locally)
FDBG18NU 41 dB 38 dB
295 mm
FDBG21NU 43 dB 40 dB
305 mm or more FDBG26NU 43 dB 40 dB
Air blow Air intake

Durable
Quiet operation
(220V)
To achieve increased durability by improved resistance to
Daikin units are salt corrosion and atmospheric pollution, coated PE fins (with
Indoor unit High LOW
among you can get. special acryl pretreatment) are used for the heat exchanger
FDMG26NU 42 dB 38 dB of the outdoor unit.
Noise is less likely
FDMG36NU 45 dB 37 dB
to detract from the
comfort provided by FDMG42NU 46 dB 37 dB
air conditioning. FDMG48NU 46 dB 37 dB
FDMG51NU 47 dB 37 dB
Sound level FDMG56NU 47 dB 37 dB Sound level or more

Cooling only
FDMG26NU—56NU 45/ 37dB
High
FDMG36NU
Low
Switchable fan speed: High/Middle/Low
Drain pipe connection can be done inside the unit. Coolant
Cooling only
FDBG18NU—26NU 43/ 40dB
High
FDBG26NU
Low
[Duc t c onnec tion]
Air filter
S uc tion c hamber

(220V) and drain pipe outlets are at the same opening. (220V) To prevent increased operation noise, avoid installing the air suction grille
directly below the suction chamber.
Option Accessory required for indoor unit Option Accessory required for indoor unit
Features
Features
Digital remote Remote Feature Comfort Work & Servicing Control features Digital remote Remote
Feature Comfort Work & Servicing Control features Others
controller controller controller controller
S witc hable fan s peed

S witc hable fan s peed

Adjus table external


Pre-c harged for

Pre-c harged for


up to 15 m

s tatic pres s ure


Auto-res tart

up to 10 m

Auto-res tart
KRC47-2 KRC47-1
Model KRC47-2A KRC47-1A Model
KRC47-4 Cooling only • *1
• KRC47-4A
*1Applic able to R 36NU– R 51NU outdoor units Cooling only • • • •

Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)
When air conditioning two rooms Door-installed Wall-installed
Under-door cutout
simultaneously, the air discharged into ventilation grille ventilation grille
each room must be circulated back to the
air conditioner. To ensure this, a
Ventilates air through
ventilation duct should be installed for Partitioning wall
the partitioning wall.
each room or one of the indicated (S ee right)

ventilation grilles should be installed on the Ventilation grille Ventilation grille Under-door c utout
partitioning wall or under the door
Note: The under-door cutout method should be used only when there is a small volume of air flow.
between the rooms.

7 8
OUTDOOR UNIT Abundance of functions that provide comfortable
air-conditioning in stores and offices.
See the list of main functions given on the page introducing each indoor unit.

C omfort W o r k a n d S e r v ic in g
Auto-swing Drain water lift-up mechanism
Delivers comfortable air- Air discharge direction angle can Steeper gradient ensures more
conditioning to all areas, be set (fixed setting) efficient wastewater drainage.
near to and far from the air- High-lift is especially useful for
conditioner. long lengths of drain piping.

Pre-charged for up to 15 meters


If refrigerant piping length does not exceed 15 m, there is no
R26NU R36NU R42NU R48/51NU Swing pattern selection need for on-site gas charging. (Applies to R36NU–51NU)
(draft prevention, standard, ceiling soiling prevention)
You can freely set 3 air flow positions by remote controller. Long-life filter
Neighbor-friendly Easily replaceable Smoother and easier (1) Air flow range in Maintenance is not required for one year (two years when a
standard position ceiling mounted cassette type is used).
Quiet Operation Compact Installation and maintenance (2) Air flow range in draft Ceiling soiling prevention function
prevention position
Fitted with wide inlet fan Slim-design and low-profile Pre-charged for up to Daikin's innovative air discharge mechanism keeps air flow
away from the ceiling. Ceiling cleaning is less frequently
(Applies to R26NU–51NU)
compact outdoor units 15 meters (Applies to R36NU–51NU) (3) Air flow range in ceiling required.
Fully shaped (Applies to R26NU–51NU) If refrigerant piping length does not exceed soiling prevention position
aerodynamic Compactly designed outdoor unit 5m (R56NU), 10m (R18NU,R21NU, R26NU), Filter sign
propellers are with interior layout optimized for the 15m (R36NU, R42NU, R48NU, R51NU),
designed to The filter sign warns you when it is time to clean the filter.
smooth flow of air. there is no need for on-site gas charging.
push air with a Allowable refrigerant pipe length and height difference
Switchable fan speed *When using a wired remote controller the sign is displayed in the LCD. When using a
wireless remote controller the filter sign lamp illuminates on the signal receiver unit.
large wing Pre-charged Max. height High setting provides maximum reach while low setting
Wide inlet fan Max. length
surface. This Curved Super Aero Grille *1 difference
minimizes drafts.
provides both high blow volume and restricts the spread of exhaust R18NU 10 m 30 m
(Equivalent length 50 m) 15 m

quiet operation with minimal gas and fits in the same space R21NU 10 m 30 m 15 m
Program "Dry" C o n t r o l fe a t u r e s
(Equivalent length 50 m)
turbulence. as previous outdoor units. Dehumidification is computer controlled to prevent abrupt and
30 m
R26NU 10 m (Equivalent length 50 m) 20m
uncomfortable changes in air temperature. Useful for reducing Auto-restart
discomforting humidity without uncomfortable cooling of the
Fitted with Super Aero Grille R36NU 15 m 30 m
(Equivalent length 50 m) 20 m
room.
If there is a power outage while the equipment is operating,
(Applies to R26NU–51NU) R42NU 15 m 30 m 20 m operations will restart in the same mode as before the power
(Equivalent length 50 m)
To suppress cut when electricity is restored.
R48NU 15 m 30 m
(Equivalent length 50 m) 20 m High-ceiling application
turbulence and Delivers air-conditioning comfort all the way down to the floor
30 m
achieve quiet 50 R51NU 15 m 20 m
in air-conditioning zones with high ceilings.
Others
(Equivalent length 50 m)

operation, the 500 (mm) R56NU 5m 50 m


(Equivalent length 70 m) 30 m
curved ribs of
the grille are
Note: 1Additional refrigerant charging is required if the
refrigerant pipe is longer than the indicated length.
PE fin
optimized to meet the outflow of air. To achieve increased durability by improved resistance to salt
4-direction piping affords corrosion and atmospheric pollution, coated PE fins (with
more freedom of layout special acryl pretreatment) are used for the heat exchanger of
the outdoor unit.
Equipped with scroll (Applies to R26NU–56NU)
Note:When units are installed on high ceilings, depending on the model, various restrictions
compressor for Piping can be run from the front, concerning maximum height, air discharge direction, and choice of options may apply.
bottom, right or rear surface
quieter operation O pt io n s
(Applies to R36NU–56NU)
according to how the unit is installed. Timer selector
Operation starts when the preset time of the ON timer elapses
Smooth running,
and stops when the preset time of the OFF timer elapses.
High-efficiency filter unit
minimal vibration, Two types are available: 65% and 90% colorimetry. Superior
low operating noise Takes installation environment into consideration filtering ratio easily meets building maintenance laws.

Even less operation noise


Durability M ild e w pr e v e n t io n Ultra long-life filter
(In case of V1: 220V, Y1: 380V)
Heat exchange fins provided with anti-corrosion treatment Mold-resistant treatment for filter Requires no maintenance for about 4 years* (10,000 h) in
Outdoor unit Sound level stores and offices. * For dust concentration of 0.15 mg/m3
To achieve increased durability by Construction Sanitary filter has mold-resistant treatment.
R36NUV1
R36NUY1 55 dB
R42NUY1 57 dB improved resistance to salt corrosion Non-treated fin Aluminium
Mildew-proofing drain pan Fresh-air intake kit
and atmospheric pollution, coated PE fin Hydrophilic film
R48NUY1 59 dB Aluminium
Mildew proofing maintains hygiene by preventing growth in You can provide air-conditioning with fresh air from outside.
PE fins (with special acryl C orrosion resistant
Convenient for places where a ventilation fan cannot be
R51NUY1 59 dB pretreatment) are used for the heat
ac rylic resin
highly humid conditions.
installed.
exchanger of the outdoor unit.

9 10
CEILING MOUNTED CASSETTE TYPE DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
18 21 26 36 42 48 26 36 42 48 51 56
Indoor unit FHC18NUV1 FHC21NUV1 FHC26NUV1 FHC36NUV1 FHC42NUV1 FHC48NUV1 Indoor unit FDMG26NUV1 FDMG36NUV1 FDMG42NUV1 FDMG48NUV1 FDMG51NUV1 FDMG56NUV1
Model Model
Name R26NUV1 R36NUV1 Name R26NUV1 R36NUV1
Outdoor unit R18NUV1 R21NUV1 R42NUY1 R48NUY1 Outdoor unit R42NUY1 R48NUY1 R51NUY1 R56NUY1
R26NUY1 R36NUY1 R26NUY1 R36NUY1
Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Cooling capacity 1a/1b Btu/h 18,100/18,000 21,200/21,000 26,300/26,000 36,500/36,000 42,700/42,000 49,100/48,000 Cooling capacity 1a/1b Btu/h 26,300/26,000 36,500/36,000 42,700/42,000 49,100/48,000 52,200/51,000 57,000/56,000
kW 5.3/5.3 6.2/6.2 7.7/7.6 10.7/10.6 12.5/12.3 14.4/14.1 kW 7.7/7.6 10.7/10.6 12.5/12.3 14.4/14.1 15.3/15.0 16.7/16.4
kcal/h 4,580/4,560 5,340/5,290 6,630/6,550 9,200/9,100 10,800/10,600 12,400/12,100 kcal/h 6,630/6,550 9,200/9,100 10,800/10,600 12,400/12,100 13,200/12,900 14,400/14,100
Power consumption 1a/1b kW 2.03/2.02 2.46/2.45 3.07/3.07 4.04/4.04 4.79/4.79 5.49/5.49 Power consumption 1a/1b kW 3.15/3.15 4.16/4.16 4.84/4.84 5.55/5.55 5.90/5.90 6.45/6.45
Colour Unit ---------- Colour ----------
Indoor Indoor
Decoration panel White Fan Air flow rate (H) m3/min 23 37 42 42 42 42
unit unit
Air flow rate (H) m3/min 15 19 19 33 33 33 cfm 811 1,306 1,482 1,482 1,482 1,482
cfm 529 670 670 1,164 1,164 1,164 Sound level (H/L) (220V) 2 dBA 42/38 45/37 46/37 46/37 47/37 47/37
Sound level (H/L) (220V) 2 dBA 33/29 35/30 35/30 42/36 42/36 42/36 Dimensions (HX WX D) mm 305X 1,350X 680 305X 1,550X 680 305X 1,550X 680 305X 1,550X 680 305X 1,900X 680 305X 1,900X 680
Dimensions Unit mm 230X 840X 840 230X 840X 840 230X 840X 840 288X 840X 840 288X 840X 840 288X 840X 840 Machine weight kg 43 52 52 52 58 58
(HX WX D) Decoration panel mm 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 Operation range °CWB 14 to 25
Unit kg 24 24 24 28 28 28 Colour Ivory
Machine weight Outdoor
Decoration panel kg 5 5 5 5 5 5
unit Compressor Type Hermetically sealed rotary type Hermetically sealed scroll type
Operation range °CWB 14 to 25 Motor output kW 2.5 3.00 3.75 4.50 4.50 4.50
Colour Ivory white Ivory Refrigerant charge (R22) kg 2.3(Charged for 10 m) 2.0(Charged for 15 m) 2.4(Charged for 15 m) 2.6(Charged for 15 m) 2.7 (Charged for 15 m) 2.8 (Charged for 5 m)
Outdoor
unit Compressor Type Hermetically sealed rotary type Hermetically sealed scroll type Sound level 2, 3 dBA 57 55 57 59 59 56
Motor output kW 1.7 2.2 2.5 3.00 3.75 4.50 Dimensions (HX WX D) mm 770X 900X 320 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320 1,345X 900X 320 1,345X 880X 370
1.20 1.50 2.3 2.0 2.4 2.6 Machine weight kg 70 (V1), 69 (Y1) 81 (V1), 79(Y1) 87 92 93 114
Refrigerant charge (R22) kg (Charged for 10 m) (Charged for 10 m) (Charged for 10 m) (Charged for 15 m) (Charged for 15 m) (Charged for 15 m) °CDB
Operation range 21 to 46
Sound level 2, 3 dBA 49 54 57 55 57 59 Piping Liquid (Flare) mm o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5
Dimensions (HX WX D) mm 540X 750X 270 685X 800X 300 770X 900X 320 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320 connections Gas (Flare) mm o/ 15.9 o/ 19.1 o/ 19.1 o/ 19.1 o/ 19.1 o/ 19.1
Machine weight kg 42 61 70 (V1), 69 (Y1) 81 (V1), 79 (Y1) 87 92 Drain Indoor unit mm 3/4B (I.Do/ 21.6X O.Do/ 27.2)
Operation range °CDB 21 to 46 Outdoor unit mm o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole)
Piping Liquid (Flare) mm o/ 6.4 o/ 6.4 o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 Max. interunit piping length m 30 (equivalent length 50 m) 50 (equivalent length 70 m)
connections Gas (Flare) mm o/ 15.9 o/ 15.9 o/ 15.9 o/ 19.1 o/ 19.1 o/ 19.1 Max. installation level difference m 20 30
Drain Indoor unit mm I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 Heat insulation Both liquid and gas piping
Outdoor unit mm o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) Note :
Max. interunit piping length m 30 (equivalent length 50 m) 1
Nominal cooling capacities are based on the following conditions:
1a
Max. installation level difference m 15 20 Return air temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
1b
Return air temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
Heat insulation Both liquid and gas piping 2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
Note : During operation these values are somewhat higher owing to ambient conditions.
3
1
Nominal cooling capacities are based on the following conditions: In case of V1: 220V, Y1: 380V.
1a
Return air temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
1b
Return air temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
In case of V1: 220V, Y1: 380V. DUCT CONNECTION LOW STATIC PRESSURE TYPE
18 21 26
Indoor unit FDBG18NUV1 FDBG21NUV1 FDBG26NUV1
Model
Name R26NUV1
CEILING SUSPENDED TYPE Outdoor unit R18NUV1 R21NUV1
R26NUY1
21 26 36 42 48 Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Indoor unit FH21NUV1 FH26NUV1 FH36NUV1 FH42NUV1 FH48NUV1 Cooling capacity 1a/1b Btu/h 18,100/18,000 21,200/21,000 26,300/26,000
Model kW 5.3/5.3 6.2/6.2 7.7/7.6
Name R26NUV1 R36NUV1
Outdoor unit R21NUV1 R42NUY1 R48NUY1 kcal/h 4,580/4,560 5,340/5,290 6,630/6,550
R26NUY1 R36NUY1
Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz Power consumption 1a/1b kW 2.12/2.11 2.73/2.72 3.33/3.33
Colour ----------
Cooling capacity 1a/1b Btu/h 21,200/21,000 26,300/26,000 36,500/36,000 42,700/42,000 49,100/48,000 Indoor
kW 6.2/6.2 7.7/7.6 10.7/10.6 12.5/12.3 14.4/14.1 Air flow rate (H) m3/min 13 18 18
unit
kcal/h 5,340/5,290 6,630/6,550 9,200/9,100 10,800/10,600 12,400/12,100 cfm 458 635 635
Fan Driving system Direct drive (2 speed)
Power consumption 1a/1b kW 2.72/2.71 3.10/3.10 4.06/4.06 4.83/4.83 5.50/5.50
Colour White Sound level (H/L) (220V) 2 dBA 41/38 43/40 43/40
Indoor Dimensions (HX WX D) mm 260X 900X 580 260X 1,300X 580 260X 1,300X 580
Air flow rate (H) m3/min 22-23 22-23 32-34 38-40 42-44
unit Machine weight kg 23 31 31
cfm 776-811 776-811 1,129-1,200 1,341-1,412 1,482-1,553
Operation range °CWB 14 to 25
Sound level (H/L) (220V) 2 dBA 44/40 44/40 46/40 48/42 49/43
Dimensions (HX WX D) mm 195X 1,160X 680 195X 1,160X 680 195X 1,590X 680 195X 1,590X 680 195X 1,590X 680 Colour Ivory white Ivory
Outdoor
Machine weight kg 26 26 35 35 35 unit Compressor Type Hermetically sealed rotary type
°CWB 14 to 25 Motor output kW 1.7 2.2 2.5
Operation range
Colour Ivory white Ivory 1.20 1.50 2.3
Outdoor Refrigerant charge (R22) kg (Charged for 10 m) (Charged for 10 m) (Charged for 10 m)
unit Compressor Type Hermetically sealed rotary type Hermetically sealed scroll type
Motor output kW 2.2 2.5 3.00 3.75 4.50 Sound level 2, 3 dBA 49 54 57
1.50 2.3 2.0 2.4 2.6 Dimensions (HX WX D) mm 540X 750X 270 685X 800X 300 770X 900X 320
Refrigerant charge (R22) kg (Charged for 10 m) (Charged for 10 m) (Charged for 15 m) (Charged for 15 m) (Charged for 15 m) Machine weight kg 42 61 70 (V1), 69 (Y1)
Operation range °CDB 21 to 46
Sound level 2, 3 dBA 54 57 55 57 59
Dimensions (HX WX D) mm 685X 800X 300 770X 900X 320 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320 Piping Liquid (Flare) mm o/ 6.4 o/ 6.4 o/ 9.5
kg 61 70 (V1), 69 (Y1) 81 (V1), 79 (Y1) 87 92 connections Gas (Flare) mm o/ 15.9 o/ 15.9 o/ 15.9
Machine weight
Operation range °CDB 21 to 46 Drain Indoor unit mm 3/4B (I.Do/ 21.6X O.Do/ 27.2)
Piping Liquid (Flare) mm o/ 6.4 o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 Outdoor unit mm o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole)
Max. interunit piping length m 30 (equivalent length 50 m)
connections Gas (Flare) mm o/ 15.9 o/ 15.9 o/ 19.1 o/ 19.1 o/ 19.1
Max. installation level difference m 15 20
Drain Indoor unit mm I.Do/ 20X O.Do/ 26 I.Do/ 20X O.Do/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26
Outdoor unit mm o/ 18.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) Heat insulation Both liquid and gas piping
Max. interunit piping length m 30 (equivalent length 50 m) Note :
1
m 20 Nominal cooling capacities are based on the following conditions:
Max. installation level difference 15 1a
Return air temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
Heat insulation Both liquid and gas piping 1b
Return air temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria.
1
Nominal cooling capacities are based on the following conditions: During operation these values are somewhat higher owing to ambient conditions.
3
1a
Return air temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal). In case of V1: 220V, Y1: 380V.
1b
Return air temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
In case of V1: 220V, Y1: 380V.

39
11 40
12
DIME N S ION S (Unit: mm)

Indoor units CEILING MOUNTED CASSETTE TYPE

CEILING MOUNTED CASSETTE TYPE C


860~890 Ceiling opening 80 2 100=200 85
Kit name Note3.
Name of option Remark 950 300 or less 680 Suspension position
FHC18NU FHC21NU FHC26NU FHC36NU FHC42NU FHC48NU 420

C
Decoration panel BYC125K-W1 9

D
E
Sealing member for air discharge outlet KDBHJ55K160 10

860~890 Ceiling opening


40

780 Suspension position


Panel spacer KDBP55H160WA Branch duct
350 connection
Fresh air intake kit Chamber Without the T-joint pipe and fan KDDP55D160
type With the T-joint pipe,without fan KDDP55D160K C view

950
Direct installation type KDDJ55X160
60
Chamber connection kit2 KKSJ55K160 4-M4 Hole
(prepared hole) 80
High-efficiency filter (Colorimetric method 65%) KAFP556D80 KAFP556D160 6 75

80
(Colorimetric method 90%) KAFP557D80 KAFP557D160
Replacement 7
(Colorimetric method 65%) KAFP552H80 KAFP552H160

160
high-efficiency filter A view 420
(Colorimetric method 90%) KAFP553H80 KAFP553H160 B
For fresh air intake kit

Adjustable(0~550)
High-efficiency filter chamber KDDFP55D160 3 B view connection
[FHC18NUV1-26NUV1] Required space (direct installation type)
Replacement long-life filter KAFJ551K160 55 840 55
295 55 840 55
Ultra long-life filter KAFP55D160 12-M4 Hole

750
80 2 100=200 85 (prepared hole) 1500mm or more
Replacement ultra long-life filter KAFJ55K160H Required space

110
Branch duct chamber KDJ55K80 KDJ55K160

95
1500mm
Remote controller Wired type1 BRC1C61 or more

200
40 A
1500mm

B
150
125
30 10
or more

Required space 165


Wireless type BRC7C613W

150
1500mm or more
Wired LCD remote controller with weekly schedule timer BRC1D61 240 260
Branch duct When the discharge grill is closeout,the required space is

1000 or more
Suspension 270 40
Central remote controller2 DCS302CA61 bolt 8 5 4 1
connection 200mm or more.
315 2 350
Unified ON/OFF controller2 DCS301BA61 4-M8 M10
Schedule timer2 DST301BA61 A
intelligent Touch Controller2 DCS601C51 A B C D E
Adaptor for wiring3 KRP1B57 FHC18NUV1-26NUV1 230 240 165 ---- ----
Wiring adaptor for electrical appendices3 KRP4A53 FHC36NUV1-48NUV1 288 298 195 165 195
[FHC36NUV1-48NUV1]
Interface adaptor for SkyAir series DTA102A52 55 840 55
Installation box for adaptor PCB KRP1B98 80 2 100=200 85 14-M4 Hole
(prepared hole)
Note:

155
165
40
50
1
Wiring for wired remote controller to be procured locally. 1 Liquid pipe connection
Notes:
2
This optional accessory requires DTA102A52. 1
Location of unit's Name Plate 2 Gas pipe connection
3
Installation box for adaptor PCB (KRP1B98) is necessary. For Main body: Switch Box Cover inside surface of suction grille. 3 Drain pipe connection

195
For decoration panel: Panel frame inside surface of suction grille. 4 Power supply connection

150
2
When installing an optional accessory, refer to the 5 Remote control code and control wiring connection
CEILING SUSPENDED TYPE installation drawings. Branch duct

Required space
6 Air discharge grille

1000 or more
40 connection
For fresh air intake kit Inspection port is necessary.
Kit name For high efficiency filter unit Inspection port is not necessary.
350 7 Air suction grille
Name of option Remark 8 Port for water supply
FH21NU FH26NU FH36NU FH42NU FH48NU 3
In case of using wireless remote controller, this position will
Replacement long-life filter Resin net be a signal receiver. Refer to the drawing of wireless remote A 9 Corner decoration cover
KAFJ501D80 KAFJ501D160
controller in detail. 10 Drain hose
L-type piping kit (for upward direction) KHFJ5F80 KHFJ5F160
Remote controller Wired type1 BRC1NU61
Wireless type BRC7NU66
Note:
CEILING SUSPENDED TYPE
1
Wiring for wired remote controller to be procured locally.

DUCT CONNECTION LOW STATIC PRESSURE TYPE FH21NUV1


A
1120 1160
B
170 12 9
Kit name 1120 1160 105
145 60
Name of option Remark FH26NUV1
FDBG18NU FDBG21NU FDBG26NU 1550 1590 90
FH36NUV1

115 60
135
Remote controller KRC47-1A 18 17 16 142 58

192 36
FH42NUV1 1550 1590
Digital remote controller KRC47-2A FH48NUV1 1550 1590

65
160

40
102

185
210
Digital remote controller for duct heater use KRC47-4A 50 60 65

85
Suction grille KDGF19A45 KDGF19A71

position)
Position slit hole for taking out in piping back

(Hanging
Drain pan cover KKD19A1 127

135 (Required space)


260
(View from the front)
10
105
8
15
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

5
A

(Required space)
(Hanging position)
Kit name
Name of option Remark
FDMG26NU FDMG36NU FDMG42NU FDMG48NU FDMG51NU FDMG56NU Hanging bolt
680 1
Remote controller KRC47-1 4-M8~M10 Position : Hole of wall for taking out in piping back
Digital remote controller KRC47-2 (View from the front)

5
5 11 80
Digital remote controller for duct heater use KRC47-4

From the floor side 2500 or more 155

195

40
90
155
(Required space)
For height installaion
55

300 or more
13
6 30 or more B 30 or more
(Service space) (Service space) 55 14
4 o/ 45

Outdoor units
Obstacle The Front
Floor side Brand name plate
1 Air discharge grille
(Note.2)
2 Air suction grille
3 Air filter
Kit name 4 Gas pipe connection
Name of option Remark Drain pipe connection VP20
6
R18NU R21NU R26NU R36NU R42NU R48NU R51NU R56NU (For left piping) 5 Liquid pipe connection
Drain piping kit ------- KIS95 ------- 6 Drain pipe conneciton
Central drain plug ------- KKPJ5F180 7 Earth terminal (inside the electric components box) (M4)

300
275
8 Suspension bracket

225
275
9 Backward piping and wiring connection opening lid
80 80 10 Upward piping and wiring connection opening lid
105 11 Right side pipe connection
3 2 7 5 4 12 Left back drain pipe connection
Notes: 170
1 13 Left side drain pipe connection
Location of unit's Name Plate: Bottom of fan housing inside the suction grille.
2 14 Right side drain pipe connection
In case of using wireless remote controller, this position will be a signal receiver.
15 Hole of wall for taking out in piping back
Refer to the drawing of wireless remote controller in detail.
3 16 Upward drain pipe connection
The remote control code is the standard <about 3 m outside the machine> attached.
17 Upward gas pipe connection
(0.5 mm2 2 wicks O.D. 5.4)
18 Upward liquid pipe connection
(It is attached to VRV.)

13 14
DIME N S ION S (Unit: mm)

DUCT CONNECTION LOW STATIC PRESSURE TYPE OUTDOOR UNIT // R18NUV1

700
A Holes for anchor bolts
B 151 (M8 or M10) 520
190 60
3-Drain outlets 170 27
300 or more

(Suspension bolt pinch)


3

10 or more
3

290
306
500

237
213
580

48

95
317

271
530 100 34

137
167
72
750 15 270
Service space
8

55
Terminal cover
C 126
(Suspension bolt pinch) Earth
terminal
D (M4)
E
F 2
4 Power intake

540
50

Name
5 plate
Gas stop valve
110
107

170
164
134

228

260

150
219
236
260

Liquid stop valve


34 105 58 27

52
16
10
G 29 6 7 H I
N
1 16 J Minimum space for air passage Service port
(All around)
O 10 K
(All around) 151 L A
M H Space A
1 Liquid pipe connection 5 Switch box Less than 1000 More than 300

150

50
2 Gas pipe connection 6 Control wiring intake (for remote controller) More than 1000 More than 600

100
3 Drain pipe connection 7 Control wiring intake (for outdoor unit)
4 Ground terminal 8 Suspension bracket Note: 1Location of unit's Name Plate: Chamber cap

H
A
A B C D E F G H I J K L M N O 50
FDBG18NUV1 900 704 755 684 664 3XP150=450 500 127 3XP150=450 674 688 704 900 10-M4 12-M4
Holes Holes

FDBG21NUV1/26NUV1 1300 1104 1155 1084 1064 6XP150=900 700 102 6XP150=900 1074 1088 1104 1300 16-M4 18-M4
Holes Holes 50

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE OUTDOOR UNIT // R21NUV1

A
B 151 300 or more Holes for anchor bolts
3 269
(Suspension bolt pinch)

(M8 or M10)

3
600

31
680

330
350
427

381
146

98
116

Service space
55

8 540 130 2-Drain outlet


C 126
(Suspension bolt pinch) [FDMG26NUV1]
1350 Outdoor
800 15 300
D 151 1153 air thermostat
E 8 1137 Earth terminal
F 2 16 1121 (M4)
4
50

51 7XP150=1050
152

5
123

Power intake
212
175
206

274
305

150
305

263
280

Name plate
Liquid

645
G H 29 stop valve

685
1 6 7 Liquid pipe
74
16
10

(All around) 20-M4 Holes


(All around) Service port
1 Liquid pipe connection [FDMG36NUV1/42NUV1/48NUV1/51NUV1/56NUV1]

70
2 Gas pipe connection I
Gas

95
151 J
3 Drain pipe connection stop valve
8 K
4 Ground terminal 16 L 75 100 Gas pipe
5 Switch box 51 M
6 Control wiring intake (for remote controller) A
7 Control wiring intake (for outdoor unit)
8 Suspension bracket
150
305

263
280

Minimum space for air passage


Note: 1Location of unit's Name Plate: Chamber cap
N
74
16
10

H
A B C D E F G H (All around)

150
FDMG26NUV1 1350 1153 1203 1134 1114 7XP150=1050 18-M4 727 I J K L M N
50

100
Holes

FDMG36NUV1/42NUV1/48NUV1 1550 1353 1403 1334 1314 7XP150=1050 18-M4 827 FDMG36NUV1/42NUV1/48NUV1 1550 1353 1337 1321 7XP150=1050 20-M4
Holes Holes

FDMG51NUV1/56NUV1 1900 1703 1753 1684 1664 9XP150=1350 22-M4 827 FDMG51NUV1/56NUV1 1900 1703 1687 1671 9XP150=1350 24-M4 H A
Holes Holes 50
50 H 1000 300

A
H 1000 600

15 16
DIME N S ION S (Unit: mm)
[Space required for outdoor unit installation] (Unit: mm)
REMOTE CONTROLLER Dimensions inside brackets [ ] indicate case where air direction adjustment guide is adjusted downward.

The values represent the case for the R26 type through R56 type.
Wireless type • Remote controller dimensions
For R26NU-56NU The dimensions in ( ) are for the R36 and R56 type (The unit values is mm. )
BRC7C613W CEILING MOUNTED CASSETTE TYPE In case of R56 model, the values in < > are those when the air discharge direction of the grille is downward.

Transmitting part
•Remote controller holder
installation procedure
•Receiver installation procedure • Receiver detail When there is an obstruction When there is an obstruction
<Installation to wall surface> Receiver
Drain piping on the inlet side on the outlet side
side
When the overhead space is open When the overhead space is open
1. For single unit
157

Liquid crystal 1. For single unit installation


remote controller
(Wireless) installation
Refrigerant When there is an
Remote controller piping side
holder obs truc tion only
on the inlet s ide 2. For series installation
62 17.5 Decoration panel ore
or m
(more than two units) 500
BRC7NU66 CEILING SUSPENDED TYPE re
mo
or
•Receiver installation procedure • Receiver detail 00)
Transmitting part Remote controller holder 0(1

5
installation procedure
The Front Receiver When there are
<Installation to wall surface>

obs truc tions on


Remote controller
(Wireless) both s ides
ore
rm
0o
115.5

100
100
Remote controller or m
holder ore
re
When there is an obstruction ss
mo or le
100
or m
ore 10
0 or in the overhead space 500

1000 or more
54 18.1 1. For single unit
installation
Receiver detail
2. For series installation

An obs truc tion


2-5x9 Slot
Service space for ceiling installation (more than two units) in the overhead s pac e
When there are
(Srevice space)
More than 90

obs truc tions on ore


or m
(Ceiling opening)

both s ides 2. For series installation 500


83.5
120

106
72

Note :
Do not install more than 3 receivers in (more than two units) or le
ss
the vicinity of one another. 500
With 4 or more units, there is always

1000 or more
the possibility of malfunction
100
0.5 0o
70 18 35 49 rm
(Ceiling opening) ore
Switch box
re An obs truc tion
(field Supplied parts) mo
200 or in the overhead s pac e
or m 0 0)
ore 0(3
20

Wired type •Remote controller dimensions


ore
rm
0o
BRC1C61 KRC47-2(A) / KRC47-4(A) KRC47-1 10 0

110 110 When there is an obstruction


25 18
in the overhead space
When there are obstructions on both
42

1. For single unit installation


120

19

the inlet and outlet sides


84

71
38

58

When there is an ss
or le

1000 or more
500 Pattern 1
120 17 18
obs truc tion on the
Cord
outlet inlet s ide When the obstruction on the outlet side is higher than
23 28
46
hole the unit itself (There is no limit to the height of the
32

27

28

An obs truc tion


obstruction on the outlet side.)
•Remote controller installation procedure
in the overhead s pac e
A EXposed body, B Exposed body, C Exposed body, ore When the overhead space is open
exposed cord embedded cord embedded code or m
100
Staple
17 Conduit 92 14 When there are obs truc tions 1. For single unit installation
on the inlet s ide and ss
or le

1000 or more
both lateral s ides 500
61
117

H
0~5

L
17 Through hole An obs truc tion
(fl12~fl16)
( Distance between in the overhead s pac e
)
remote controller
100
17
CONTROL BOX and control box ) 50( more
KRC47-1A 150
or
L H or m
ore or
Note) 1. Remote controller cord and Specifications of cord mo
re 500 1000>
staple are not attached. they are 150 ore <
Type
Vinyl cord with sheath or cable 136 or or m
field supplied parts. (Insulated thickness: 1 mm or more)
124 32
mo
re 150
Size 0.75~1.25 mm2 2. For series installation
Total length 500 m 2. For series installation (more than two units) (more than two units)
* Countries requiring EMC: Shield wire
When there are obs truc tions
81

(insulated thickness: 1 mm or more)


BRC1NU61 on the inlet s ide and
44.5 both lateral
Note)
s ides

H
25 The dimension of hole.
6

20 ss

1000 or more
or le
500
A
36

a
10

B B
22 25

An obs truc tion 0)


17 R2
119

(30
L H 200 more
13

85 in the overhead s pac e


4

B
25 20
ore or
77

A A
A
100 rm
0o >
Hole type a (mm) 0o
rm 100 1500
A 6 ore <
41 38
111 24 B 10
41.5
ore
rm
200 )o
or (3 00
mo
re 2 00

19 20
DIME N S ION S (Unit: mm)

OUTDOOR UNIT // R26NUV1/Y1 OUTDOOR UNIT // R42NUY1and R48NUY1and R51NUY1

Hole for anchor A B C D


Hole for anchor bolt 4-M12
R42NUY1 1170 54 113 579
bolt 4-M12

30
30
R48NUY1/51NUV1 1345 55 — —

(345~355)

320
350

61
48
(345~355)
350

320
41

30
55
48
96
140 620 140
40

30
96 30 900
140 620 140
30 900 3 4
2
2
1
6 6 1

5 3
5
4 4 7
770

6 7 7

A
5

55
6 6

352
329
5 5
60

223

B
84 55
54 95

54 95

53 95
143

435

55
60

410
89 19 19 80 52
28

89

223
95

95
95
142 145

84
13 67
71 16
7

54
24

89

54

53
16

C 89 19 19 80 52
58
117

D 142 145 13 67
8
70 102

71 16
4 1 Gas pipe connection

16
1 Gas pipe connection
2 Liquid pipe connection
45 376 191 2 Liquid pipe connection
3 Grounding terminal M5(in switch box)

70 102 117
3 Service port (in the unit)
4 Refrigerant piping intake

58
4 Grounding terminal M5 (in switch box)
5 Power supply wiring intake
5 Refrigerant piping intake
6 Control wiring intake
5 6 Power supply wiring intake
7 Drain connection
Note: In some circumstances, with certain machine types, 7 Control wiring intake
it may not be possible to attach the supplied piping. 45 376 191 8 Drain pipe connection

OUTDOOR UNIT // R36NUV1/Y1 OUTDOOR UNIT // R56NUY1

Hole for anchor Hole for anchor


bolt 4-M12 bolt 4-M12

30
30

84

370
396
(345~355)

38
350

320
61
48

35
30
41 146 584 150
30

96
880
140 620 140
30
30 900

4
2 4
3
1 2
3 1
7
7
7 6
6
1170

1345
7 6 5
5
6 5 7
6
5
54
435

5 5
410
60

568
538
60
223

60
84 55
95
157.5

95

148
89

95
95

144
84
24

54

54

89 19 19 80 52

49
name plate 14 67 14 90

49
24

84
142 145 13 67 90 14 115
137
8 71 16
102 11

40

61 11
16

1 Gas pipe connection


2 Liquid pipe connection 1 Gas pipe connection
58
117

3 Service port(in the unit) 2 Liquid pipe connection


275

4 Grounding terminal 3 Service port(in the unit)


70 102

5 Refrigerant piping intake 4 Grounding terminal M5(in switch box)


5 5
6 Power supply wiring intake 5 Refrigerant piping intake
7 Control wiring intake 6 Power supply wiring intake
45 376 191
8 Drain pipe connection 7 Control wiring intake
391 8 8 Drain outlet

17 18
MEMO