Prepared By:
Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 1 0.600 No No
Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 C 0.400 M
Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.070 10 15
Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 0.700 0.700 1.000 1 0.000
Zone Input
Zone 1: Sala De Capacitacion (1291.2 sq.ft) (Group 0)
Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 120.00 Zone width (feet): 10.76
Lighting Watts: 2,582 Equipment Watts: 1,937
Number of people in zone: 45 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 8.00 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 220
Cooling ventilation method: Direct Cooling ventilation value: 0.000
Cooling infiltration method: Direct Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 0.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 1,291 Exposed floor slab perimeter (ft): 70
Cooling loads only are calculated for this zone.
Glass Type S.U-F. Shd C. Height Width Occur. Area Shade Tilt Ref
1 1 0.700 1.000 5.91 32.00 1 189.1 0 90 1
Check Figures
Total Building Supply Air (based on a 19° TD): 1,883 CFM
Total Building Vent. Air (0.00% of Supply): 0 CFM
Total Conditioned Air Space: 1,291 Sq.ft
Supply Air Per Unit Area: 1.4583 CFM/Sq.ft
Area Per Cooling Capacity: 287.5080 Sq.ft/Ton
Cooling Capacity Per Area: 0.0035 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 4.49 Tons
Check Figures
Total Air Handler Supply Air (based on a 19° TD): 1,883 CFM
Total Air Handler Vent. Air (0.00% of Supply): 0 CFM
Total Conditioned Air Space: 1,291 Sq.ft
Supply Air Per Unit Area: 1.4583 CFM/Sq.ft
Area Per Cooling Capacity: 287.5080 Sq.ft/Ton
Cooling Capacity Per Area: 0.0035 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 4.49 Tons
Glass - 4.09%
People - 43.17%
Equipment - 13.49%