Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Associated Drawings
• Circuit breaker schematic diagram—drawing no. 46040-651
• Circuit breaker wiring diagram—drawing no. 46040-652
Instruction Bulletin
• Document no. 6055-33
™
© 2014 Schneider Electric All Rights Reserved
ANSI/NEMA Vacuum Circuit Breakers 6055DB1401
5–15 kV; 1200, 2000, and 3000 A; 25–63 kA 03/2014
Dimensions The following diagram shows typical dimensions for Type VR medium voltage
vacuum circuit breakers. A 1200/2000 A circuit breaker is pictured.
29.04 24.80
Dimension taken with (ref.) ± 0.10 14.80
cage pushed against ± 0.70
11.15 9.51 4.80
copper contact. ± 0.15 (ref.) ± 0.10
28.75 8.30
(ref.) 0.42
± 0.15 (ref.)
0.62 0.30
(typ.) (ref.) 1.88 min.
travel
0.66
(typ.)
28.93
(ref.) 24.50 23.47
± 0.10 ± 0.10
12.00
± 0.10
Weights
15 kV Circuit Breaker Rating Weight (lbs.)
1200 A, 25/40 kA 380
2000 A, 25/40 kA 430
1200 A, 50 kA 450
2000 A, 50 kA 500
3000 A, 50 kA 700
1200/2000/3000 A, 63kA 800
5–15 kV Ratings
Insulation Level
Interrupting Ratings
Rated Rated Withstand
Nominal Mechanical
Continuous
Voltage Endurance
k MVA Current Power Impulse System Close and Short Short Time Interrupting Catalog
Factor Rating a Frequency 1.2x50 μs Interrupting Latch Time Duration Time Number
Operations
kV rms A rms kV rms kV peak kA rms kA peak kA rms Seconds Cycles
b
Capacitor Switching Duty Applies to single bank and back-to-back switching with de-rating factors
applied per C37.012.
Schneider Electric USA, Inc. Electrical equipment should be installed, operated, serviced, and maintained only by
1415 S. Roselle Road qualified personnel. No responsibility is assumed by Schneider Electric for any
Palatine, IL 60067 USA consequences arising out of the use of this material.
1-888-778-2733 All trademarks are owned by Schneider Electric Industries SAS or its affiliated
www.schneider-electric.us companies.