Sei sulla pagina 1di 1

TECHNICAL SPECIFICATION FOR

415 V MOULDED CASE CIRCUIT BREAKER


1 Installation : Switch board
2 Number of Poles : 3
3 Service Voltage : 415 V (-15% to 10%)
4 Rated current (A) : 630A, 500A, 350A, 300A, 250A, 200 A, 100A
5 Making capacity : 120 kA (peak)
6 Frequency : 50 Hz (-5% to 3%)
7 Symmetrical breaking : 50 kA (rms)
capacity
8 Short time current for 1 : 50 kA (rms)
Second
9 Settings : 500A /400A/300A/250A/200A/160A/90A
Magnetic 9 kA
10 Operating Mechanism : Manual Trip free
11 Tripping arrangement : Thermal overload and Short circuit electromagnetic release.
12 Protections to be provided : i) Short circuit
ii) Overload
13 Cable Entries :
13.1 Incoming : Suitable for PVCSWA with Aluminium conductor. Totally
shrouded to avoid risk of electric shock to operating
personnel.
13.2 Outgoing : Connected to Bus.
14 Execution : Fixed

7.4.7 SPECIFICATION FOR 415 V POWER DISTRIBUTION BOARDS (PDB)

7.4.7.1 SCOPE
This specification covers requirements for 415V PDB, metal enclosed, dust and vermin proof
conforming to the latest revision of IS: 8623-1993 except where modified or extended by the
provision of this specification.
7.4.7.2 OTHER RELEVANT STANDARDS
The other relevant Indian standards are as under :
IS : 3043 : Code of practices for earthing.
IS : 4237 : General requirements for switchgear and control gears for voltages not exceeding
1000V AC.
IS : 2551 : Danger Notice Plates
IS : 5082 : Wrought Aluminium Alloys for electrical purpose
IS : 6005 : Code of practice of phosphating iron and steel
IS : 3202 : Code of practice for climate proofing of electrical equipment
IS : 2147 : Degree of protection provided by industrial enclosures
IS : 5 : Colors for ready mixed paints and enamels.
Where Indian standards are not available International standards like British standards, ISO,
DIN, JIS or Other standards which ensures performance equivalent or superior to Indian
standard shall be followed.
The equipment covered under this specification shall comply with all the latest applicable
statutory rules, regulations, acts and safety codes which may be in force during the period of
execution and which are related with design, construction and operation of equipment in the
locality where the equipment is to be installed.
Nothing in this specification shall be construed as to relieve the supplier of the responsibility
for correctness of the design and construction of the equipment.
All the standards being followed shall be listed out in the bid. Where any foreign standard is
being followed, the copy of the same shall be provided with the bid.