Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Data Centers
in paper form without permission of ASHRAE.
T
he increasing compactness of data to the rack compared to the airflow rate be zones where all equipment within
processing equipment size and the through the rack?” and “Is the remainder that zone dissipates very high heat loads.
expanding needs of the informa- of the air supplied to the rack within ac- This arrangement of equipment may be
tion technology industry has led to more ceptable temperature limits?” required to achieve the performance de-
equipment being packed into the same Data centers, such as the one in Figure sired (cabling between computer racks
amount of space. However, the energy 1, typically are arranged into hot and may be restricted in length to achieve
efficiency of computing and storage cold aisles. This arrangement accom- performance requirements). These high
equipment has not risen at the same rate. modates most rack designs that use performance zones can provide sig-
This has resulted in a significant increase front-to-back cooling. And, it somewhat nificant challenges in maintaining an
in power density and heat dissipation. separates cold air exiting the perforated environment within the manufacturers’
Therefore, the cooling of computer and tiles (for raised floor designs) and over- temperature specifications.
telecommunications equipment rooms is head chilled airflow (for non-raised floor Airflow distribution within a data
becoming a major challenge. designs) from the hot air exhausting center has a major impact on the thermal
The problem in many data centers is from the rear of the racks. environment of the DP equipment located
that the chilled air from the air-condition- The racks are positioned so the fronts within these rooms. A key requirement
ing units cannot satisfy the local airflow of the racks face the cold aisle as in Fig- of manufacturers is that the inlet tem-
requirements of the computer and storage ure 1. Similarly, the rear of the racks face perature and humidity to the electronic
racks. This permits only a portion of each each other, and provide a hot air exhaust
About the Authors
electronic equipment rack to be cooled by region. This layout allows the chilled air
Roger Schmidt, Ph.D., is distinguished engi-
the chilled air, while other portions of the to wash the fronts of the data processing neer and chief thermal architect, and Madhu-
rack pull in air from other regions of the (DP) equipment while the hot air from the sudan Iyengar, Ph.D., is an advisory engineer
data center that is generally at a higher racks exit into the hot aisle as it returns to at the Systems & Technology Group at IBM in
Poughkeepsie, N.Y. Richard Chu is IBM fellow
air temperature. the inlet of the air-conditioning units.
and manager of the Advanced Thermal Labs
The primary questions addressed here With the arrangement of DP equipment at the Systems & Technology Group at IBM in
are: “How much chilled air is supplied in rows within a data center, there may Poughkeepsie, N.Y.
Rack
2 Local
Region
1.75 Data Center
Numerical Model
×10
1.5
×10
Measured Value
1.25
×103
×103
×102
1
×10
0.75
×10
0.5
0.25
0
Power Heat Flux dT Inlet, C Perf. Flow/ Perf. + Cable Flow/ RdT
kW kW/m2 Rack Flow Rack Flow
Figure 2: Results for measurement and modeling of a data center shown below in Figure 3.
for measurements but still capture most of the thermo-fluid The rack was modeled with blowers that force a specific
and geometric parameters and then compare the results. A airflow through these three portions of the rack with the same
representative model of a section of raised floor data center flow characteristics as the rack. The temperature of the chilled
system, depicted in Figure 4, was constructed using a com- air entering the room through the perforated tiles was fixed
mercial software tool. The model was constructed to closely at 15°C (59°F). The rack flow rate, perforated tile flow rates,
resemble the layout in Figure 3, for and cable flow rates matched those
which measurements were taken. Region 1 measured in Region 1 of Figure 3.
The model consists of four pri- The room dimensions were four
mary components; namely, the heat times that of the quarter symmetry
generating datacom equipment model shown in Figure 4, i.e., 6.05
racks, perforated tiles that supply m by 2.8 m (19.8 ft by 9.18 ft), with
chilled air, cable openings that a room height of 2.75 m (9.02 ft).
cause underfloor air to leak into The rack dimensions were 0.61 m
the hot aisle, and computer room (2 ft) wide by 1.22 m (4 ft) deep by
air-conditioning units (CRAC) 2 m (6.56 ft) tall.
that draw in hot return air from the The resulting heat flux of this
racks and exhaust chilled air into configuration is 1.6 kW/m2 (507.6
the raised floor plenum. The model Rack 1 Btu/h/ft2) (Figure 2). Thus, the heat
comprised of a quarter symmetry flux and the flow conditions are the
Local Area 1
of 16 rack sections of a data center same for the numerical model cell
arranged in a cold aisle-hot aisle Figure 3: Rack layout in a data center. as for those measured in the data
fashion. The racks were assumed to center and reported previously. One
dissipate the same heat load as the machines for which the perforated tile with dimensions of 0.61 m by 0.61 m (2 ft by
experimental results are reported. The geometry of some of 2 ft) was placed in front of each rack. The cable openings at
the racks from the field measurements was replicated in the the back of the rack were modeled as 17.8 cm (7 in.) deep
computer model. and the width of the rack.
The racks were modeled to dissipate 6.7 kW (22,870 Btu/h) The thermo-fluid interactions were numerically solved using
each (average of the racks measured in the data center), with the k-e turbulence model, which is the preferred choice for such
the heat load distributed in three portions of the rack (same as data center fluid flow modeling. The cell count for the models
those shown in the measurements of Figure 3): input/output was approximately 50,000. Temperature data was recorded for
portion at the bottom of the rack, central electronic complex the numerical simulations at nine vertical locations in front on
that includes memory and processors in the center of the rack, the rack, namely at heights of 200 to 1600 mm (7.87 to 63 in.)
and ac/dc power supplies located at the top of the rack. in increments of 200 mm (7.87 in.), and the highest point at
Summary/Conclusions References
1. Measurements in a data center showed with significantly 1. Thermal Guidelines for Data Processing Equipment. 2004.
ASHRAE Special Publication.
less flow from the perforated tiles in front of racks, compared 2. Nakao, M., H. Hayama, M. Nishioka. 1991. “Which cooling
to the rack flow, the inlet air temperatures into a rack could air supply system is better for a high heat density room: underfloor
be met. Specifically, measurements showed that for the rack, or overhead?” Thirteenth International Telecommunications Energy
local area, region and data center the ratio of perforated tile Conference, (INTELEC ’91), Paper 12-4, pp. 393 – 400.
3. Hayama, H. M. Nakao. 1989. “Air flow systems for telecommunica-
flow to rack flow ranging from 0.48 to 0.63 were acceptable tions equipment rooms.” The Eleventh International Telecommunications
to meet inlet air temperature. (The data from four data cen- Energy Conference (INTELEC ’89), Vol. 1, Paper 8.3, pp. 1–7.
ters ranged from 0.28 to 0.68). This range was similar to that 4. Hayama, H., M. Nakao, and M. Sanabe. 1990. “Airflow distribu-
reported in Reference 5, stating that if the perforated tiles tion in telecommunications equipment rooms.” Twelfth International
Telecommunications Energy Conference (INTELEC ’90), Paper 11-4,
associated with a rack exhausted one-quarter to one-half the pp. 206 – 212.
flow of the rack, then the system inlet air temperature could 5. Schmidt, R. 2004. “Thermal profile of a high density data
be maintained (given the chilled air exhaust temperature was center—methodology to thermally characterize a data center.” 2004
below approximately 15°C [59°F]). ASHRAE Annual Meeting.