Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
T
ransformers are required throughout modern in- M. Wang and A.J. Vandermaar
terconnected power systems. The size of these Powertech Labs Inc.
transformers ranges from as low as a few kVA to Surrey, B.C., Canada
over a few hundred MVA, with replacement costs ranging
from a few hundred dollars to millions of dollars. Power K.D. Srivastava
transformers are usually very reliable, with a 20-35 year The University of British Columbia
design life. In practice, the life of a transformer can be as
Vancouver, Canada
long as 60 years with appropriate maintenance. How-
ever, the in-service failure of a transformer is potentially
dangerous to utility personnel through explosions and There is an increasing need for better
fire, potentially damaging to the environment through oil nonintrusive diagnostic and monitoring
leakage, is costly to repair or replace, and may result in
significant loss of revenue. In a large public power utility, tools to assess the internal condition of
the number of transformers in the subtransmission and transformers.
transmission network (excluding the lower-voltage dis-
tribution network) can be from a few hundred to over
one thousand (69 kV to 500 kV). changes occur at a time when the average age of the trans-
As transformers age, their internal condition degrades, formers in service is increasing and approaching the end of
which increases the risk of failure. Failures are usually trig- nominal design life.
gered by severe conditions, such as lightning strikes, switch- The change to condition-based maintenance has resulted
ing transients, short-circuits, or other incidents. When the in the reduction, or even elimination, of routine time-based
transformer is new, it has sufficient electrical and mechani- maintenance. Instead of doing maintenance at a regular in-
cal strength to withstand unusual system conditions. As terval, maintenance is only carried out if the condition of
transformers age, their insulation strength can degrade to the equipment requires it. Hence, there is an increasing
the point that they cannot withstand system events such as need for better nonintrusive diagnostic and monitoring
short-circuit faults or transient overvoltages. tools to assess the internal condition of the transformers. If
To prevent these failures and to maintain transformers in there is a problem, the transformer can then be repaired or
good operating condition is a very important issue for replaced before it fails.
utilities. Traditionally, routine preventative maintenance Many testing and monitoring techniques have been used
programs combined with regular testing were used. With by utilities. This article reviews the existing monitoring and
deregulation, it has become increasingly necessary to reduce diagnostic methods and future trends.
maintenance costs and equipment inventories. This has led
to reductions in routine maintenance. The need to reduce
costs has also resulted in reductions in spare transformer ca- Power Transformer Failures and Problems
pacity and increases in average loading. There is also a trend Transformer failure can occur as a result of different
in the industry to move from traditional time-based mainte- causes and conditions. Generally, transformer failures
nance programs to condition-based maintenance. These can be defined as follows [1]-[2]:
Moisture
Partial discharge
Winding resonance
● any forced outage due to transformer damage in service ● damage to the transformer bushings caused by loss of di-
(e.g., winding damage, tap-changer failure) electric strength of the internal insulation.
● trouble that requires removal of the transformer for re- An American utility reported four single-phase EHV
turn to a repair facility, or which requires extensive field autotransformer failures due to transformer winding res-
repair (e.g., excessive gas production, high moisture lev- onance [5]. All of the failures involved the breakdown of
els). the no-load tap changers immediately after the transmis-
Transformer failures can be broadly categorized as elec- sion system was energized. The utility also experienced
three 25/765 kV, 500 MVA generator step-up trans-
trical, mechanical, or thermal. The cause of a failure can
former failures and two 765 kV, 80 MVA reserve auxil-
be internal or external. Table I lists typical causes of fail-
iary transformer failures; all of the failures were dielectric
ures. In addition to failures in the main tank, failures can
in nature [6].
also occur in the bushings, in the tap changers, or in the Another survey done by a CIGRÉ working group on
transformer accessories. failures in large power transformers [1] found that about
The failure pattern of transformers follows a “bath- 41 percent of failures were due to on-load tap changers
tub” curve, as shown in Fig. 1. The first part of the curve is (OLTC) and about 19 percent were due to the windings.
failure due to infant mortality; the second part of the The failure origins were 53 percent mechanical and 31
curve is the constant failure rate; and the last part of the percent dielectric. On transformers without on-load tap
curve is failure due to old age. changers, 26.6 percent of failures were due to the wind-
In addition to normal aging, a transformer may de- ings, 6.4 percent were due to the magnetic circuit, 33.3
velop a fault that results in faster-than-normal aging, re- percent were due to terminals, 17.4 percent were due to
sulting in a higher probability of failure. the tank and dielectric fluid, 11 percent were due to other
Power transformers have proven to be reliable in nor- accessories, and 4.6 percent were due to the tap changer.
mal operation with a global failure rate of 1 – 2 percent Figure 2 shows the percentage failure distribution for
per year. The large investment in generating capacity af- power transformers with on-load tap changers.
ter the Second World War that continued into the early Another report presents transformer failure data in
1970s has resulted in a transformer population that, in South Africa [7]. This failure analysis was based on 188
theory, is fast approaching the end of life [3]. The end of
life of a transformer is typically defined as the loss of me-
chanical strength of the solid insulation in the windings.
Typical Transformer Failure Pattern
These power transformers are at the last stage of the
Number of Failures
Ethane 35 65 75 20n + 50
Acetylene 5 35 7 5n + 10
n = years in service
Neutralization Number D644, D974 Acidic products from oil oxidation/ sludge, corrosion
Interfacial Tension (IFT) D971 Presence of polar contaminants, acids, solvents, varnish
Oxidation Inhibitor (DBPC*) D2668, D1473 Low levels results in accelerated oil aging
*DBPC—Dibutyl Paracresol
[22] M. Belanger, “Transformer diagnosis: Part 3: Detection techniques [40] J.W. Harley and V.V. Sokolov, “Diagnostic techniques for power
and frequency of transformer testing,” Electricity Today, vol. 11, transformers,” presented at the International Council on Large
no. 8, pp. 19-26, 1999. Electric Systems (CIGRÉ), Paris, France, 2000.
[41] X. Huang and Z. Yan, “Study on trend analysis method for on-line
[23] C. Bengtsson, “Status and trends in transformer monitoring,”
insulation diagnosing of capacitive-type equipment,” presented at
IEEE Trans. Power Delivery, vol. 11, no. 3, pp. 1379-1384, 1996.
the International Symposium on Electrical Insulating Materials,
[24] T.R. Blackburn, et al., “On-line partial discharge measurement on
Toyohashi, Japan, 1998.
instrument transformers,” presented at the International
[42] T.R. Hyde, “On-line condition monitoring technology and
Symposium on Electrical Insulating Materials, Toyohashi, Japan,
applications,” ERA Technology, Rep. No. 95-0546R, 1995.
1998.
[43] A. Jaksts, et al., “A major breakthrough in transformer
[25] L. Bolduc, et al., “Detection of transformer winding displacement
technology,” presented at the International Council on Large
by the frequency response of stray losses (FRSL),” presented at the
Electric Systems (CIGRÉ), Paris, France, 2000.
International Council on Large Electric Systems (CIGRÉ), Paris,
[44] M.D. Judd, et al., “Transformer monitoring using the UHF
France, 2000.
technique,” presented at the 11th International Symposium on High
[26] P. Boss, et al., “Economical aspects and practical experiences of
Voltage Engineering, London, U.K., 1999.
power transformers on-line monitoring,” presented at the
[45] A.J. Kachler, “Diagnostic and monitoring technology for large
International Council on Large Electric Systems (CIGRÉ), Paris,
power transformers,” presented at CIGRÉ SC 12, Sydney
France, 2000.
Colloquium, Sydney, Australia, 1997.
[27] A.J.M. Cardoso and L.M.R. Oliveira, “Condition monitoring and
[46] S.R. Kannan, M. Tech, and N. Rao, “Generator loading limits for
diagnostics of power transformers,” Int. J. COMADEM,
impulse testing low-inductance windings,” Proc. IEE, vol. 122, no.
Sunderland, U.K., 1999, pp. 5-11.
5, pp. 535-538, 1975.
[28] D. Carreau, et al., “Condition monitoring diagnostics expert
[47] J.L. Kirtley, et al., “Monitoring the health of power transformers,”
systems: A project roadmap,” Electricity Today, vol. 12, no. 4, pp.
IEEE Computer Applications in Power, vol. 9, no. 1, pp. 18-23,
8-14, 2000.
1996.
[29] T.H. Crowley, “Automated diagnosis of large power transformers
[48] M.F. Lachman, W. Walter, and P.A. von Guggenberg, “On-line
using adaptive model-based monitoring,” B.S. and M.S. thesis,
diagnostics of high-voltage bushings and current transformers using
M.I.T., Cambridge, MA, 1990.
the sum current method,” IEEE Trans. Power Delivery, vol. 15, no.
[30] J.B. DiGiorgio, et al., “Cut failures by analyzing transformer oil,” 1, pp. 155-162, 2000.
Electrical World, vol. 192, no. 7, pp. 52-54, 1979. [49] P. Leemans, et al., “Control, diagnostic and monitoring of power
[31] N. Dominelli, “Furanic and non-furanic analysis as a transformer transformers,” presented at the International Council on Large
diagnostic,” presented at the EPRI Substation Equipment Electric Systems (CIGRÉ), Paris, France, 1998.
Diagnostics Conference IV, New Orleans, LA, 1996. [50] T. Leibfried, “Online monitors keep transformers in service,” IEEE
[32] G. Duke, “Predictive maintenance a case study in infrared Computer Applications in Power, vol. 11, no. 3, pp. 36-42, 1998.
thermography,” Electrical Maintenance, pp. 11-12, 1998. [51] T. Leibfried, et al., “On-line monitoring of power
[33] R. Farquharson and K. Caird, “An overview of substation transformers—Trends, new developments and first experiences,”
equipment monitoring and diagnostics: Part 1,” Electricity Today, presented at the International Council on Large Electric Systems
vol. 12, no. 5, pp. 23-26, 2000. (CIGRÉ), Paris, France, 1998.
[34] K. Feser, et al., “General trends in condition monitoring of [52] T. Leibfried and K. Feser, “Monitoring of power transformers
electrical insulation,” in Proc. Stockholm Power Tech. Int. Symp. using the transfer function method,” IEEE Trans. Power Delivery,
Electric Power Engineering, vol. 1, Stockholm, Sweden, 1995. Paper PE-053-PWRD-1-08-1998, 1998.