Sei sulla pagina 1di 14

F E A T U R E A R T I C L E

Review of Condition Assessment


of Power Transformers in Service
Key Words: Transformer insulation, condition assessment, failure statistics, oil testing, dissolved gas
analysis, partial discharge (PD), power factor, dielectric spectroscopy, recovery voltage,
winding movement detection

T
ransformers are required throughout modern in- M. Wang and A.J. Vandermaar
terconnected power systems. The size of these Powertech Labs Inc.
transformers ranges from as low as a few kVA to Surrey, B.C., Canada
over a few hundred MVA, with replacement costs ranging
from a few hundred dollars to millions of dollars. Power K.D. Srivastava
transformers are usually very reliable, with a 20-35 year The University of British Columbia
design life. In practice, the life of a transformer can be as
Vancouver, Canada
long as 60 years with appropriate maintenance. How-
ever, the in-service failure of a transformer is potentially
dangerous to utility personnel through explosions and There is an increasing need for better
fire, potentially damaging to the environment through oil nonintrusive diagnostic and monitoring
leakage, is costly to repair or replace, and may result in
significant loss of revenue. In a large public power utility, tools to assess the internal condition of
the number of transformers in the subtransmission and transformers.
transmission network (excluding the lower-voltage dis-
tribution network) can be from a few hundred to over
one thousand (69 kV to 500 kV). changes occur at a time when the average age of the trans-
As transformers age, their internal condition degrades, formers in service is increasing and approaching the end of
which increases the risk of failure. Failures are usually trig- nominal design life.
gered by severe conditions, such as lightning strikes, switch- The change to condition-based maintenance has resulted
ing transients, short-circuits, or other incidents. When the in the reduction, or even elimination, of routine time-based
transformer is new, it has sufficient electrical and mechani- maintenance. Instead of doing maintenance at a regular in-
cal strength to withstand unusual system conditions. As terval, maintenance is only carried out if the condition of
transformers age, their insulation strength can degrade to the equipment requires it. Hence, there is an increasing
the point that they cannot withstand system events such as need for better nonintrusive diagnostic and monitoring
short-circuit faults or transient overvoltages. tools to assess the internal condition of the transformers. If
To prevent these failures and to maintain transformers in there is a problem, the transformer can then be repaired or
good operating condition is a very important issue for replaced before it fails.
utilities. Traditionally, routine preventative maintenance Many testing and monitoring techniques have been used
programs combined with regular testing were used. With by utilities. This article reviews the existing monitoring and
deregulation, it has become increasingly necessary to reduce diagnostic methods and future trends.
maintenance costs and equipment inventories. This has led
to reductions in routine maintenance. The need to reduce
costs has also resulted in reductions in spare transformer ca- Power Transformer Failures and Problems
pacity and increases in average loading. There is also a trend Transformer failure can occur as a result of different
in the industry to move from traditional time-based mainte- causes and conditions. Generally, transformer failures
nance programs to condition-based maintenance. These can be defined as follows [1]-[2]:

12 0883-7554/02/$17.00©2002IEEE IEEE Electrical Insulation Magazine


Table I. Typical Causes of Transformer Failures
Internal External
Insulation deterioration Lightning strikes

Loss of winding clamping System switching operations

Overheating System overload

Oxygen System faults (short circuit)

Moisture

Solid contamination in the insulating oil

Partial discharge

Design & manufacture defects

Winding resonance

● any forced outage due to transformer damage in service ● damage to the transformer bushings caused by loss of di-
(e.g., winding damage, tap-changer failure) electric strength of the internal insulation.
● trouble that requires removal of the transformer for re- An American utility reported four single-phase EHV
turn to a repair facility, or which requires extensive field autotransformer failures due to transformer winding res-
repair (e.g., excessive gas production, high moisture lev- onance [5]. All of the failures involved the breakdown of
els). the no-load tap changers immediately after the transmis-
Transformer failures can be broadly categorized as elec- sion system was energized. The utility also experienced
three 25/765 kV, 500 MVA generator step-up trans-
trical, mechanical, or thermal. The cause of a failure can
former failures and two 765 kV, 80 MVA reserve auxil-
be internal or external. Table I lists typical causes of fail-
iary transformer failures; all of the failures were dielectric
ures. In addition to failures in the main tank, failures can
in nature [6].
also occur in the bushings, in the tap changers, or in the Another survey done by a CIGRÉ working group on
transformer accessories. failures in large power transformers [1] found that about
The failure pattern of transformers follows a “bath- 41 percent of failures were due to on-load tap changers
tub” curve, as shown in Fig. 1. The first part of the curve is (OLTC) and about 19 percent were due to the windings.
failure due to infant mortality; the second part of the The failure origins were 53 percent mechanical and 31
curve is the constant failure rate; and the last part of the percent dielectric. On transformers without on-load tap
curve is failure due to old age. changers, 26.6 percent of failures were due to the wind-
In addition to normal aging, a transformer may de- ings, 6.4 percent were due to the magnetic circuit, 33.3
velop a fault that results in faster-than-normal aging, re- percent were due to terminals, 17.4 percent were due to
sulting in a higher probability of failure. the tank and dielectric fluid, 11 percent were due to other
Power transformers have proven to be reliable in nor- accessories, and 4.6 percent were due to the tap changer.
mal operation with a global failure rate of 1 – 2 percent Figure 2 shows the percentage failure distribution for
per year. The large investment in generating capacity af- power transformers with on-load tap changers.
ter the Second World War that continued into the early Another report presents transformer failure data in
1970s has resulted in a transformer population that, in South Africa [7]. This failure analysis was based on 188
theory, is fast approaching the end of life [3]. The end of
life of a transformer is typically defined as the loss of me-
chanical strength of the solid insulation in the windings.
Typical Transformer Failure Pattern
These power transformers are at the last stage of the
Number of Failures

“bathtub” curve. They are expected to have an increasing


failure rate in the next few years.
A survey [4] reports that the main causes (51 percent
of transformer failures in a five-year period) were due to
the following problems:
● moisture, contamination and aging which caused the
transformer’s internal dielectric strength to decrease,
● damage to the winding or decompression of the wind- Years in Service

ing under short circuit forces, or Figure 1. Bathtub failure curve.

November/December 2002 — Vol. 18, No. 6 13


power transformers in the voltage range of 88 kV to 765 promote the longest possible service life and to mini-
kV with ratings from 20 to 800 MVA. The failure modes mize lifetime operating costs. The importance of this is-
are shown in Fig. 3. sue [9]-[15] has led to a lot of research in this area. In
Failure statistics for large transformers that had been general, transformer life is equal to the insulation life,
in service between 15 and 25 years are shown in Fig. 4 [4]. which depends on mechanical strength and electrical in-
The above surveys and research results indicate that tegrity. Insulation degradation consists of hydrolytic,
load tap changers, windings, insulation aging, and con- oxidative, and thermal degradation. The aging and life
tamination are the key sources of transformer failures. of a transformer has been defined as the life of the paper
Another paper [8] indicates that the average number insulation [10]. Several aging mechanisms were identi-
of failures over a four-year period (1975 to 1979) was 2.6 fied as follows:
failures per year per 100 transformers. ● applied mechanical forces
The cost and time to repair and replace a power trans- ● thermal aging (chemical reactions)
former is very substantial. The repair and replacement of ● voltage stresses
a 345/138 kV transformer normally requires about 12 -
15 months. If a spare is available, the time needed for re-
● contamination.
placement of a failed unit is in the range of 8 - 12 weeks. The transformer is subjected to mechanical forces due
to transportation, electromagnetic forces caused by sys-
Transformer Life Management tem short circuits, and inrush current. Vibration and ther-
Transformer life management has gained an increas- mal forces generated by different thermal expansion rates
ing acceptance in the past 10 - 15 years, due to economic in different materials cause long-term degradation of the
and technical reasons. The fundamental objective is to paper. The eventual dielectric failure may occur when the
mechanical forces rupture the insulation. The compres-
sive mechanical forces on the cellulose paper can cause
Core material flow and cause clamping pressure to reduce.
Terminal Thus the aging of paper insulation determines the ulti-
mate life of the transformer, although other factors may
contribute to earlier failure.
Thermal aging of transformer insulating materials is
Accessories
On Load Tap associated with the chemical reactions occurring within
Changers
the materials. These chemical reactions are caused by py-
rolysis oxidation and hydrolysis, and are accelerated by
increased levels of temperature and of the oxygen and
Tank/Fluid moisture contents. Associated with the chemical reaction
of the cellulose paper is a reduction in the mechanical
properties. The paper insulation becomes brittle to the
Windings point of almost falling apart, but it still retains an accept-
able level of dielectric strength.
Figure 2. Percentage failure of power transformers
(CIGRE survey) [1].
The temperature of a transformer has a major impact
on the life of the insulation. Continuous on-line monitor-
ing of the transformer oil temperature along with a ther-
mal model of the transformer can give an estimate of the
Core
loss of life of the transformer due to overheating. Current
industry standards limit maximum allowable hot spot tem-
Aging peratures in transformers to 140 °C with conventional
oil/paper insulation.
Lightning/Switching End of life may be dictated by any one factor or by a
Transients combination of factors. Much attention has been given
to paper aging as a cause of transformer failure. While it
is undoubtedly a factor in reducing life, it does not auto-
matically lead to failure; some other influence is nor-
Others mally required, such as mechanical shock. In industry
loading guides (e.g., IEC, ANSI, and IEEE) the princi-
Tap Changer pal factor for end of life relates only to the trans-
Short Circuit
former’s thermal factor. A classical method of
Figure 3. Percentage of failures of power transformers calculating the remaining life of a transformer has been
(South Africa) [7]. the Arhennius-Dakin formula:

14 IEEE Electrical Insulation Magazine


Remaining life = AeB/T
Miscellaneous Insulation Aging

where A = initial life; B = constant, depending on the


properties of the material studied; and T = absolute tem- Overvoltage
perature in °K.
Core
A more comprehensive approach is clearly needed to Insulation Winding
evaluate the remaining life of a transformer as a whole. Failure Deformation
The other factors affecting the probability of failure are Due to
Short Circuit
not as easily quantified as thermal aging. To assess the Forces
overall condition of a transformer reliably, several moni-
toring techniques are used and are under investigation.
The most common monitoring/testing methods used for
transformer condition assessment are given in [11], Contamination of
[16]-[76]. Insulation
The traditional routine tests are: transformer ratio
measurement, winding resistance, short-circuit imped- Figure 4. Failure of transformers 15 to 25 years old [4].
ance and loss, excitation impedance, and loss dissipation
factor and capacitance, as well as applied and induced po- analysis, such as an expert system capable of providing an
tential tests. These tests usually give information on faults assessment of equipment condition and suggested ac-
in windings, winding conductor and joint problems, tions.
winding deformation, oil moisture and contamination, There are a variety of tools available to evaluate the
and dielectric problems. Special tests include partial dis- condition of transformers [25], [55], [64]-[65],
charge measurement, frequency response analysis, vibra- [77]-[81]. They can be separated into traditional diagnos-
tion analysis, infrared examination, voltage recovery, and tic methods that have seen widespread use for many years
degree of polymerization. These detect problems such as and nontraditional methods that range from methods
local partial discharge, winding looseness and displace- that are starting to be used to methods that are still in the
ment, slack winding and mechanical faults, hot spot on research stage.
connection, moisture in paper and aging of paper, as well
as insulation degradation. Traditional Diagnostic Methods
Oil tests are used extensively. They consist of dissolved
gas analysis (DGA) with ratio analysis, furan analysis, wa- OIL TESTING
ter content, resistivity, acidity, interfacial tension (IFT), Testing of the winding insulating oil is one of the most
and dissipation factor (DF). These detect oil incipient common tests used to evaluate the condition of transform-
faults, overheating, aging of paper, dryness of oil-paper, ers in service. Thermal and electrical faults in the oil lead to
and aging of oil. degradation of the oil.
Life assessment of large transformers may be per-
formed for the following reasons [12]: Dissolved Gas Analysis
● to monitor the condition of transformers and provide Insulating oils under abnormal electrical or thermal
an early warning of faults stresses break down to liberate small quantities of gases. The
● to diagnose problems when transformers exhibit signs composition of these gases is dependent upon the type of
of distress or following the operation of protection fault. By means of dissolved gas analysis (DGA), it is possible
equipment to distinguish faults such as partial discharge (corona), over-
● to determine whether a transformer is in a suitable con- heating, and arcing in a great variety of oil filled equipment.
dition to cope with unusual operating conditions A number of samples must be taken over a period of time to
● to obtain reference results to assist in the interpretation discern trends and to determine the severity and progres-
of subsequent tests sion of incipient faults. The gases in oil tests commonly
● to assist in planning the replacement strategy for a popu- evaluate the concentration of hydrogen, methane, acety-
lation of transformers lene, ethylene, ethane, carbon monoxide, carbon diox-
● to satisfy the requirements for insurance coverage. ide, nitrogen, and oxygen. The relative ratios and the
Testing and monitoring methods are reviewed in detail in amount of gas detected in the sample are used to detect
the next section. problems with the insulation structure [82]-[90].
Cellulosic Decomposition—The thermal decomposition
of oil-impregnated cellulose insulation produces carbon ox-
Monitoring and Diagnostic Methods ides (CO, CO2) and some hydrogen and methane (H2, CH4)
Generally speaking, the term “monitoring” describes a due to the oil.
basic parameter measurement with threshold alarms. The Oil Decomposition—Mineral transformer oils are mix-
term “diagnostics” indicates the addition of sophisticated tures of many different hydrocarbon molecules, and the de-

November/December 2002 — Vol. 18, No. 6 15


composition processes for these hydrocarbons in thermal or ity of the fault is established by comparison of the levels
electrical faults are complex. Heating the oil produces eth- of gases with threshold levels and their rate of generation.
ylene (C2H4) as the principal gas. At least two consecutive samples are needed to calculate
Information from the analysis of gasses dissolved in in- rates of fault generation.
sulating oil is one of the most valuable tools in evaluating A list of key gases and their related faults are shown in
the health of a transformer and has become an integral Table III. For a detailed discussion, consult IEEE Std.
part of preventive maintenance programs. Data from C57.104-1991, “IEEE Guide for the Interpretation of
DGA can provide: Gases Generated in Oil-Immersed Transformers.”
● advanced warning of developing faults
● monitoring the rate of fault development Insulating Oil Quality
● confirm the presence of faults The condition of the oil greatly affects the performance
● a means for conveniently scheduling repairs and the service life of transformers. A combination of elec-
● monitoring of condition during overload. trical, physical, and chemical tests is performed to measure
DGA data by itself does not always provide sufficient in- the change in the electrical properties, extent of contamina-
formation on which to evaluate the integrity of a trans- tion, and the degree of deterioration in the insulating oil.
former system. Information about its manufacture and the The results are used to establish preventive maintenance
history of a transformer in terms of maintenance, loading procedures, to avoid costly shutdowns and premature
practice, previous faults, and so on are an integral part of the equipment failure, and extend the service life of the equip-
information required to make an evaluation. ment. There is a multitude of tests available for insulating
Generally, there are three steps involved. The first step is oil. The most commonly used, and their significance, are
to establish whether or not a fault exists. In-service trans- listed in Table IV. Threshold levels for these tests are speci-
formers always have some fault gases dissolved in their oil. fied in ASTM D3487 for new oils and IEEE Guide
Only when these levels exceed some threshold value is a 637-1985 for service oils.
fault suspected. Several recommended safe values have been As paper degrades, a number of specific furanic com-
published. Some of these are listed Table II. pounds are produced and dissolved in the oil. The pres-
The second step is to determine the type of fault. Two ence of these compounds is related to the strength of the
methods most commonly used are the key gases and gas paper as measured by its degree of polymerization (DP).
ratios [17]-[18], [21]-[23], [27], [29]-[30], [36], [39], Furan and phenol measurement in oil is a convenient,
[45], [56], [58], [60], [76]. The first involves plotting all noninvasive method to assess the condition of the paper
the total dissolved combustible gas (TDCG) as a per- insulation. Transformer oil samples should be analyzed
centage of their total in a histogram. Each fault type will for furans and phenols when one or more of the follow-
give a distinctive pattern characterized by a key gas, gen- ing conditions exist:
erally the most abundant. For example, high levels of hy- ● overheating or overloading of the transformer
drogen with low levels of other gases are characteristic of ● high levels of carbon monoxide or carbon dioxide
partial discharge. The ratio method requires the calcula- ● rapid decrease of interfacial tension without a correspond-
tion of ratios of gases among each other, such as methane ing increase in acid number
to hydrogen. Three or four such ratios are used for diag- ● sudden darkening of the oil and a sudden increase of the
nosis. The most widely used are Roger’s ratios; the sever- moisture content of the oil

Table II. Recommend Limits of Dissolved Gases


Gas Dornenburg/Stritt IEEE Bureau of Reclamation Age Compensated

Hydrogen 200 100 500 20n + 50

Methane 50 120 125 20n + 50

Ethane 35 65 75 20n + 50

Ethylene 80 50 175 20n + 50

Acetylene 5 35 7 5n + 10

Carbon Monoxide 500 350 750 25n + 500

TDCG* (total of above) 720 110n + 710

Carbon Dioxide 6000 2500 10000 100n + 1500

n = years in service

*Total dissolved combustible gas

16 IEEE Electrical Insulation Magazine


● transformers over 25 years old. long been used as both a routine test and for diagnosis.
Furan measurement is still a relatively new technique, The acceptance value should be less than 0.5 percent.
and its interpretation is dependent on many operational Reference [60] categorizes the interwinding power factor
and historical factors. However, the guidelines in Table V as the following: dry < 0.5 percent; medium < 1.5 per-
provide some assistance. cent; and wet > 1.5 percent. The evaluation also takes ac-
The degree of polymerization (DP) estimated from count of the transformer’s power factor history. The test
furan analysis relates to the average value. Paper in trans- requires an outage and isolation of the transformer. The
formers usually does not age uniformly, and there will be tests can be done, respectively, on high-voltage winding
areas where degradation is more severe. to ground, high- to low-voltage winding, low-voltage
winding to ground, high- to tertiary-voltage winding,
POWER FACTOR TESTING low- to tertiary-voltage winding, and the tertiary-voltage
The insulation power factor is the ratio of the resistive winding to ground insulation. It is used to detect prob-
current component to the total leakage current under an lems with the transformer bushings and to evaluate the
applied voltage. Power factor measurement is an impor- condition of the oil/paper insulation structure [17]-[18],
tant source of data in monitoring transformer and bushing [22], [35], [39], [45], [56]-[57], [60], [91].
conditions. In general, power factor measurement equip-
ment comes with three basic modes of operation: a) WINDING RESISTANCE
grounded specimen test (GST); b) GST guard; and c) un- Winding resistance is used to indicate the winding con-
grounded specimen test (UST). The three measurement ductor and tap changer contact condition. The test re-
modes allow measurement of the current leaking back to quires an ohmmeter capable of accurately measuring
the test set on each lead, individually and together. In gen- resistance in the range of 20 Ω down to fractions of an Ω.
eral, a power factor of less than 1 percent is considered Winding resistance varies with oil temperature. During
good; 1-2 percent is questionable; and if it exceeds 2 per- the test, the temperature should be recorded. For future
cent, action should be taken. Practically, the evaluation is comparisons, the resistance should be converted to a ref-
not only based on a single power factor data point but is erence temperature. Measurement of transformer wind-
also based on the history of the change in power factor. ing resistance requires an outage and isolation of the
Measurement of a transformer’s capacitance and transformer. Variations of more than 5 percent may indi-
power factor at voltages up to 10 kV (at 50 or 60 Hz) has cate a damaged conductor in a winding [22].

Table III. Key Gases Generated by Particular Fault


Key Gas Characteristic Fault
H2 Partial Discharge
C2H6 Thermal Fault <300 ºC
C2H4 Thermal fault 300 ºC-<700 ºC
C2H2, C2H4 Thermal Fault > 700 ºC
C2H2, H2 Discharge of Energy

Table IV. Insulating Oil Tests


Type of Test ASTM Method Significance/Effects
Dielectric Breakdown D877, D1816 Moisture, particles, cellulose fibers/lower dielectric
strength

Neutralization Number D644, D974 Acidic products from oil oxidation/ sludge, corrosion

Interfacial Tension (IFT) D971 Presence of polar contaminants, acids, solvents, varnish

Color D1500 Darkening indicates contamination or deterioration

Water Content D1533 Excessive paper decomposition/lower dielectric strength

Power Factor D924 (100, 25 C) Dissolved metals, peroxides, acids, salts/overheating

Oxidation Inhibitor (DBPC*) D2668, D1473 Low levels results in accelerated oil aging

Metals in Oil Indicative of pump wear, arcing or sparking with metal

*DBPC—Dibutyl Paracresol

November/December 2002 — Vol. 18, No. 6 17


Table V. Guidelines for Degradation
2-Furaldehyde (ppm) Degree of Polymerization Extent of Degradation
0 – 0.1 800 – 1200 Insignificant
0.1 – 0.5 700 – 550 Significant
1.0 – 2.0 500 – 450 Cause for concern
>10 <300 End of life

WINDING RATIO There are two commonly used PD detection methods:


The winding turns ratio test is useful to determine detection of the acoustic signals and measurement of the
whether or not there are any shorted turns or open wind- electrical signals produced by the PD [27]. PD can also be
ing circuits. The measured ratio should be within 0.5 per- detected indirectly, using chemical techniques such as
cent of the ratio of the rated voltages between the measuring the degradation products produced by the PD.
windings, as noted on the transformer nameplate. All tap The acceptable PD limits for new transformers are de-
positions and all phases should be measured. The test can pendent on the voltage and size of the transformers and
be performed at a very low voltage. range from < 100 to < 500 pC.
PD pulses generate mechanical stress waves that prop-
THERMOGRAPHY
agate through the surrounding oil (in the range of 100 to
Infrared emission testing is used to check the external
300 kHz) [35]. To detect these waves, acoustic emission
surface temperature of the transformer on-line. It is use-
sensors are mounted either on the transformer tank wall
ful for detecting thermal problems in a transformer, such
as cooling system blockages, locating electrical connec- or in the oil inside the transformer tank in the oil. If multi-
tion problems, and for locating hot spots [32], [39], [42]. ple sensors are used, the PD can be located based on the
Infrared imagers “see” the surface heat radiation from arrival time of the pulses at the sensors. The sensitivity of
objects. It cannot look “inside” the transformer tank. the test is dependent on the location of the PD, since the
Black and white thermograms (heat pictures) show hot signal is attenuated by the oil and winding structure. This
areas in white and cold areas in black, unless stated other- means that the deeper inside the winding the PD is
wise. For color thermograms, white and red areas are located, the greater the attenuation. Piezoelectric sensors
usually hotter, while black and blue areas are colder. and fiber optic sensors can measure the PD. Recent research
Infrared thermography provides the heating patterns shows that optical sensors have a potential sensitivity much
for the load that was on the equipment at the time that the higher than normal external tank-mounted piezoelectric
scan was performed. Any abnormal conditions can be lo- sensors for PD detection [93]. Fiber optic sensors also could
cated from the scan. The severity of overheating from the potentially be placed inside the winding.
scan can be categorized as follows: PD causes high-frequency low-amplitude disturbances
on the applied voltage and current waveforms that can be
Classification Temperature Excess* detected electrically. Electrical PD signals can be mea-
Attention: 0 - 9°C sured at a number of different locations, including bush-
Intermediate: 10 - 20 °C ing tap current or voltage and neutral current [17]-[18],
[23]-[24], [26]-[27], [35]-[36], [39], [45], [50]-[51],
Serious: 21 - 49 °C
[55], [62], [68], [70], [73], [76]. Techniques using detec-
Critical: >50 °C tion of ultra-high-frequency signals (typically 1–2 GHz)
have been developed to detect PD in gas-insulated substa-
*Temperature excess is defined as the difference in
tions. The method has been applied to transformers and
temperature between a reference point on the trans-
shows some promise [44], [61].
former at normal temperature and a higher temperature
point. Acoustic methods of PD detection are limited by signal
attenuation, and electrical measurements are limited by
Nontraditional Transformer electromagnetic interference problems. Equipment is
Monitoring Techniques commercially available to continuously monitor and
There has been a great deal of new development in test- evaluate internal PD on-line using both acoustic and elec-
ing and monitoring techniques in recent years, and these are trical methods.
finding increasing use on transformers. Investigations are also proceeding on improving
acoustic detection of PD, as well as further work on elec-
IN-SERVICE PD TESTING trical detection for in service monitoring [94]. The goal is
PD in transformers degrades the properties of the in- to be able to detect and ideally locate PD levels with a
sulating materials and can lead to eventual failures [23]. minimum sensitivity of at least 100 pC.

18 IEEE Electrical Insulation Magazine


RECOVERY VOLTAGE MEASUREMENT rents can be monitored to obtain a signature every time the
The recovery voltage measurement (RVM) [95]-[98] tap changer moves. Changes in this signature are used to
method is used to detect the conditions of oil-paper insu- detect problems in the tap changer. Bearing monitors are
lation and the water content of the insulation. The RVM used to detect bearing wear on transformer oil pumps [26].
relies on the principle of the interfacial polarization of
composite dielectric materials; that is, the buildup of INTERNAL TEMPERATURE MEASUREMENT
space charges at the interfaces of oil-paper insulation due The traditional method to measure the temperature of
to impurities and moisture. A dc voltage is applied to the a transformer winding is to measure the transformer’s
insulation for a time. The electrodes are then short-cir- top and bottom oil temperature and estimate the hot spot
cuited for a short period of time, after which the short cir- temperature. New fiber optic equipment has been devel-
cuit is removed to examine the rate of the voltage buildup oped that is able to monitor the temperature two differ-
or the polarization profile. The time constant associated ent ways. One is a distributed temperature measurement
with this peak recovery voltage gives an indication of the along the entire length of the winding by a fiber optic ca-
state of the insulation. The main parameters derived from ble. The temperature of the complete winding could be
the polarization spectrum are the maximum value of the monitored if a fiber optic cable can be laid along the
recovery voltage, the time to peak value, and the initial transformer winding during construction of the trans-
rate of rise of the recovery voltage. former. There are drawbacks of this method, however.
The test results give an indication of the state of the High cost and high mechanical stresses on the fiber
oil/paper insulation structure of the transformer. It re- (squeezing and buckling) are a major concern. The fiber
quires a transformer outage to carry out the test [18], optic needs to be handled with extreme care. It would
[23], [40], [45], [60], [66]-[67], [99]. This method is very have to be installed during transformer construction
controversial as to its suitability for direct measurement [23], [100]. The application of the fiber optic sensor so
of the moisture content in oil, due to the strong depend- far has been mainly for laboratory research and principal
ence of the results on the geometry, and construction of design studies. The technology used in the fiber optic
the insulation system of a transformer. Figures 5 and 6 temperature sensors is capable of measuring the full
show typical RVM curves for old transformers that are in range of temperatures encountered on transformers.
good and poor condition.
The drawbacks of this test are that a long outage may
1000
be required and the unreliability in the interpretation of
the results.
100
Voltage (V)

WINDING INSULATING OIL TESTING/MONITORING


In addition to the winding insulating oil tests routinely
carried out, as already described, there are other oil tests
that can provide information on the condition of the 10

transformer. These include particle count, metals in the


oil, furan analysis, aniline point, corrosive sulfur, and oxi-
1
dation stability. 0.01 0.1 1 10 100 1000 10,000
Equipment to continuously monitor oil condition in Charge Time (Seconds)
service is increasingly being installed on transformers.
The most widely installed systems measure hydrogen Figure 5. Typical RVM curve for a transformer in good condition.
content, although systems that measure moisture and
other gases are also available. The hydrogen and compo-
sition sensors use semiconductor or fuel cell technology;
and more complex sensors, which make use of infrared 1000
technology and gas chromatography, can detect several
or all of these gases.
100
Voltage (V)

TAP CHANGER/MOTOR MONITORING


The use of oil testing has been extended to the testing
of the tap changer oil. The oil tests are used as an indica- 10
tor of contact deterioration [19], [27], [35], [39], [42],
[50]-[51], [55], [59], [62], [63]-[64], [100]. 1
Monitoring of the tap changer temperature can be used to 0.01 0.1 1 10 100 1000
detect problems, such as contact overheating, while acoustic Charge Time (Seconds)
analysis of the switching operation can detect faults in the se-
lector and diverter switches [99]. Tap changer motor cur- Figure 6. Typical RVM curve for a transformer in poor condition.

November/December 2002 — Vol. 18, No. 6 19


The other type of system uses fiber optics for point factor-frequency characteristics allow for a more com-
temperature measurement. Since the sensors and associ- plete diagnosis of the examined insulation. At the lower
ated cables are insulated, they can be installed directly at frequency range, pressboard dielectric loss is the main
the transformer hot spots. The best time to install these sen- factor; at medium frequency range, the oil conductivity is
sors is during transformer construction at the locations indi- the dominant contributor; and at the higher frequency
cated by thermal modeling of the transformer; however, range, the pressboard and the oil volume determine the
they can be retrofitted to an existing transformer, but this is dielectric loss. Different aging mechanisms can be de-
difficult to do. tected and identified at their respective frequency ranges.
Temperature systems are being installed in on-load tap
changers. Monitoring the temperature and temperature
trends has been found to be a useful indicator of degrada- WINDING MOVEMENT DETECTION
tion of tap changer contacts [23], [27], [35], [49]-[51], [53]. A very serious problem that is particularly difficult to
detect is movement or distortion of the transformer
ON-LINE POWER FACTOR MEASUREMENT winding. Forces on the winding during short circuits on
Systems to measure bushing power factor on-line are the transformer can cause winding distortion. The other
now available. Manufacturers have made available two source of winding movement is reduction or loss of wind-
systems for monitoring the condition of bushings, based ing clamping. This can result in a transformer fault that
on detecting changes in their capacitance and power fac- will cause damage to the transformer and may result in
tor. Both systems use sensors on the bushing capacitance explosive failure of the transformer. Traditionally, the
taps to measure the bushing leakage currents. One system only way to evaluate the winding condition of a large
uses an electric field sensor to measure the bus voltage power transformer is to drain the oil from the trans-
phase angle, and calculates the capacitance and dissipa- former and carry out an internal inspection.
tion factor from the measured data. The other technique Some research work has focused on using the trans-
sums the bushing currents from the three phases and plots former vibration signal to detect winding looseness and
them on a polar plot. Any shift in the resultant currents on developing the analysis techniques for interpreting the
indicates a change in capacitance or dissipation factor of vibration data [101]-[104]. The method is based on look-
one of the bushings. These measurements can give suffi- ing for changes in the transformer’s vibration signature to
cient warning of an impending bushing failure to allow detect movement in the winding. This method is not used
replacement of the bushing before a catastrophic failure as widely as frequency response analysis tests for detect-
occurs. ing winding movement.
In the frequency response analysis test (FRA), the
POWER FACTOR VS. FREQUENCY MEASUREMENT transformer is isolated from the system and the imped-
(DIELECTRIC SPECTROSCOPY) ance or admittance of the transformer is measured as a
The measurement of power factor over a broad range function of frequency (typically to at least 2 MHz). This
of frequencies from a low of 1 mHz to 1 kHz or higher gives a “fingerprint” of the transformer. The test is re-
has been used to evaluate the insulation condition [17], peated over time and the “fingerprints” from two or
[40], [48], [57]. Interference can be easily detected as an more tests are compared.
irregularity; the transformer insulation usually has a There are two different test methods commonly used
smooth power factor-frequency characteristic. Power to carry out the FRA test: the swept frequency test and the
pulse test. The swept frequency method applies a variable
frequency voltage or a white noise voltage to the
−30
high-voltage winding and records the response in an-
other winding or terminal. This technique is more widely
−40 used in Europe than in North America. A similar tech-
Magnitude (dB)(I(f)/V(f))

nique more commonly used in North America is the pulse


−50
FRA test. With this technique a pulse signal is applied to
−60
the high-voltage winding, and the response is recorded in
another winding or terminal. Research indicates that the
−70 pulse method is more sensitive to detect small winding
Reference Transformer movement and winding clamping looseness [105]. Figure
−80 Transformer Under Test 7 shows an FRA test results comparison for a transformer
−90
with some movement compared to a transformer in good
condition. In general, the greater the difference between
0.5 1 1.5 2 2.5 3 the two “signatures,” the greater movement in the trans-
Frequency (Hz) x 106 former. The test requires experienced personnel to com-
pare the two signatures and evaluate the severity of the
Figure 7. FRA test results comparison. movement.

20 IEEE Electrical Insulation Magazine


The conventional FRA test requires a transformer out- testing at reduced voltages. The use of other tests (both
age to carry out the test. Work has been carried out in Eu- off-line and on-line) is increasing but is limited by a num-
rope and North America to use the transient voltages ber of factors.
generated during switching operations as the driving sig- ● Cost: The high cost of testing and monitoring can make
nal to measure the transformer admittance [75], [106]. If it difficult to justify the tests. The purchase price of the
the on-line FRA test could be developed, it could reduce equipment is only one cost factor limiting their use. The
or eliminate the need for outages to carry out an FRA test. cost of isolating the transformer and performing the test
The FRA test has been used extensively. The drawbacks of can be substantial for off-line tests. The long outage time
the test are that it requires an outage, an initial reference required by tests, such as the recovery voltage method,
test with the transformer in good condition, great consis- can make them difficult to carry out. The installation
tency in the test setup from one test to the next, and it re- costs for on-line monitoring equipment can be a major
quires experienced personnel to interpret the data. cost factor.
Despite these drawbacks this has been found to be the ● Data interpretation: The interpretation of tests often re-
most effective test in detecting winding movement. quires experienced expert personnel. Incorrect inter-
Another technique used to detect winding displace- pretation of the data can lead to false conclusions about
ment is the frequency response of stray losses (FRSL). the transformer condition.
This test is done over a range of frequencies from 20 Hz ● Reliability: The degradation of a transformer occurs
to over 600 Hz [17]-[19], [21], [23], [25], [27], [34], over several years. Sensors and electronic equipment in-
[38], [45], [49], [52], [54], [56], [58], [72], [76], [107]. stalled on the transformers must be able to perform over
The FRSL test has not been extensively used or studied. many years with minimal maintenance.
It is thought not to be as sensitive to winding movement ● Compatibility: The compatibility of the many on-line
as the FRA test due to its lower measurement frequency monitoring systems now available is a major concern.
range. Typically systems from one supplier are completely in-
compatible with those of other suppliers.
Diagnostic Software and Expert Systems Use of nontraditional diagnostic and monitoring tech-
Diagnostic software, which gives more definite indica- niques is expected to increase on the aging transformer
tions of transformer problems than conventional analy- population. The cost of the equipment will fall and reli-
sis, is under investigation by many researchers and ability will increase with increased usage. The interpreta-
utilities [63], [71], [76]. The use of software can improve tion and understanding of the test data obtained from
the reliability and repeatability of the analysis of test data. tests such as FRA, RVM, and vibration testing will im-
It can also be used to extract information that is not avail- prove. In particular, standard analysis techniques are be-
able from the data directly. ing developed that will enable field personnel to more
A great deal of research has been done on software to easily use the test results and will reduce the need for in-
interpret transformer oil test data such as gas, moisture terpretation by experts. Multiple test software that com-
content, and dielectric strength and correlating the data bines the results of different tests and gives an overall
with the transformer insulation condition. Expert sys- assessment of condition is expected to find increasing
tems have been developed that give an alarm signal to sys- use. The use of continuous on-line monitoring of trans-
tem operators. Some systems have been developed to formers is increasing. The cost of the equipment is de-
detect PD signals in transformers [94]. Equipment using creasing and the sensors are improving. This makes it
acoustic emission sensors and specialized software has easier to justify the installation of sophisticated monitor-
been successful in detecting PD and locating the origin of ing systems on transformers. Standardization will make it
the discharge. The sensors are mounted externally on the easier to integrate systems and data from different suppli-
transformer tank wall and three-dimensional location ers. The use of wireless technologies within the substa-
techniques are applied to locate the source of the detected tion for communication between the transformer and
signals. control room will make it easier to install monitoring
The present advancement in artificial intelligence (AI) equipment.
modeling techniques has enabled power engineers and re- The ultimate goal of transformer monitoring and diag-
searchers to develop powerful and versatile AI software to nostic techniques is to have a set of devices/systems to moni-
diagnose transformer faults. The use of expert systems of- tor and anticipate the transformer failure, so that
fers the potential of reducing the manpower and financial appropriate action can be taken before forced outage oc-
overhead required by utilities to assess transformer condi- curs. The organizational culture of a power utility signifi-
tion; however, this potential has not yet been realized. cantly impacts on the operational practices in the use of
condition-based maintenance.
Discussion and Concluding Remarks
The most widely used tests to diagnose the condition M. Wang received the B.Sc. degree in electrical engineering
of transformers are still oil tests and off-line power factor from Xian Jiaotong University, Xian, China and the

November/December 2002 — Vol. 18, No. 6 21


M.A.Sc. degree in electrical engineering References
from the University of British Columbia, [1] CIGRÉ Working Group 05, “An international survey on failures in
Vancouver, Canada, in 1982 and 1991, re- large power transformers in service,” Electra, no. 88, May 1983.
spectively. From 1982 to 1988, she was [2] V.I. Kogan, et al., “Failure analysis of EHV transformers,” IEEE
with the Wuhan High Voltage Research In- Trans. Power Delivery, vol. 3, no. 2, pp. 672-683, 1988.
stitute as a research engineer. In 1991, she [3] B. Sparling, “Transformer monitoring and diagnostics,” in Proc.
joined Powertech Labs Inc. as a senior re- IEEE Power Engineering Society 1999 Winter Power Meeting, vol. 2,
search engineer. Her research interests are New York, 1999, pp. 978-980.
in transformer condition monitoring, transformer fre-
[4] O.N. Grechko and I. Kalacheva, “Current trends in the
quency response analysis, and high-voltage engineering.
development of in-service monitoring and diagnostic systems for
She is an active IEEE member and is a registered profes-
110-750 kV power transformers,” Applied Energy: Russian Journal
sional engineer in the province of British Columbia.
of Fuel, Power, and Heat Systems, vol. 34, no. 5, pp. 84-97, 1996.
[5] A.J. McElroy, “On the significance of recent EHV transformer
John Vandermaar received his B.Sc. in En-
failures involving winding resonance,” IEEE Trans. Power
gineering from the University of Manitoba
Apparatus and Systems, vol. 94, no. 4, 1975, pp. 1301-1306.
in 1975. From 1975 to 1980 he was with
the Operations and the Engineering Divi- [6] K.H. Lee and J.M. Schneider, “Rockport transient voltage
sions of BC Hydro. In 1980 he joined the monitoring system: analysis and simulation of record waveforms,”
Research and Development Division of BC IEEE Trans. Power Delivery, vol. 4, no. 3, 1989, pp. 1794-1805.
Hydro (now Powertech Labs Inc.). He has [7] M. Minhas, J.P. Reynders, and P.J. de Klerk, “Failure in power
been responsible for many research pro- system transformers and appropriate monitoring techniques,”
jects in the areas of high-voltage insulation, equipment con- presented at the 11th Int. Symp. High Voltage Engineering, London,
dition monitoring, and equipment life assessment. U.K., 1999.
Currently, he is the Manager of the High Voltage Group at [8] R. Sahu, “Optimization of the transmission and subtransmission
Powertech Labs Inc. Mr. Vandermaar is the secretary of IEC transformer spares on the AEP system,” in Proc. 42nd American
TC 42 High Voltage Test Techniques and a member of IEC Power Conf., Chicago, IL, 1980, pp. 701-705.
Working Group 12 on Voltage Measurement by Means of [9] CIGRÉ Working Group 09 of Study Committee 12, “Lifetime
Air Gaps. He is also active on various IEEE standards com- evaluation of transformers,” Electra, no. 150, pp. 39-51, 1993.
mittees. [10] L. Pettersson, “Estimation of the remaining service life of power
transformers and their insulation,” Electra, no. 133, pp. 65-71,
K.D. Srivastava (M’67-SM-81-F’85-LF’00) 1990.
received the B.E. (Honors) degree in elec- [11] M. Darveniza, et al., “Investigations into effective methods for
trical engineering from the University of assessing the condition of insulation in aged power transformers,”
Roorkee, Roorkee, India and the Ph.D. de- IEEE Trans. Power Delivery, vol. 13, no. 4, pp. 1214-1223, 1998.
gree from the University of Glasgow, Glas-
[12] J.A. Lapworth, P.N. Jarman, and I.R. Funnell, “Condition
gow, U.K. in 1952 and 1956, respectively.
assessment techniques for large power transformers,” Second
He was a Research Engineer at A. Reyrolle
International Conf. Reliability of Transmission and Distribution
and Co., Newcastle, U.K. from 1957 to
Equipment, Coventry, U.K., Conf. Publ. no. 406, pp. 85-90, 1995.
1958. From 1958 to 1960, he was with the University of
[13] M. Kazmierski, R. Sobocki, and W. Olech, “Selected elements of
Roorkee and the University of Jodhpur as a Senior Faculty
life management of large power transformers—A Polish
Member. From 1961 to 1966, he worked at Brush Electric
experience,” presented at the International Council on Large
Co., Loughborough, U.K., as a Senior Research Engineer,
Electric Systems (CIGRÉ), Paris, France, 1998.
and then at the Rutherford High Energy Laboratory,
Harwell, U.K. as a Principal Scientific Officer. In 1966, he [14] L. Pettersson, N.L. Fantana, and U. Sundermann, “Life assessment:
emigrated to Canada and was appointed Professor of elec- Ranking of power transformers using condition based
trical engineering at the University of Waterloo, Waterloo, evaluation—A new approach,” presented at the International
ON, Canada, and from 1972 to 1978, he was Chairman of Council on Large Electric Systems (CIGRÉ), Paris, France, 1998.
the Department. In 1983, he was appointed Professor and [15] P.N. Jarman, J.A. Lapworth, and A. Wolson, “Life assessment of
Head of the Department of Electrical Engineering at the 275 and 400 kV transmission transformers,” presented at the
University of British Columbia (UBC), Vancouver, BC, Can- International Council on Large Electric Systems (CIGRÉ), Paris,
ada, and from 1986 to 1994, he was Vice President of Stu- France, 1998.
dent and Academic Services at the same University. His [16] G. Breen, “Essential requirements to maintain transformers in
research interests are in gaseous insulation and high-voltage service,” presented at the International Council on Large Electric
engineering. Systems (CIGRÉ), Paris, France, 1992.

22 IEEE Electrical Insulation Magazine


[17] S. Agou, et al., “Increasing the reliability of online insulation [35] K. Feser, et al., “The transfer function method for detection of
condition assessment of MV-HV equipment,” Electricity Today, winding displacements on power transformers after transport, short
vol. 12, no. 6, pp. 22-27, 2000. circuit or 30 years service,” presented at the International Council
[18] T.H. Aschwanden, et al., “Development and application of new on Large Electric Systems (CIGRÉ), Paris, France, 2000.
condition assessment methods for power transformers,” presented [36] E. Gockenbach and H. Borsi, “Diagnostic methods for
at the International Council on Large Electric Systems (CIGRÉ), transformers on-site,” in Proc. Int. Symp. Elec. Insul. Matls.,
Paris, France, 1998. Toyohashi, Japan, 1998, pp. 2-36.
[19] A. Basak, “Condition monitoring of power transformers,” [37] P. Guuinic, “Progress report of study committee 12
Engineering Science and Education Journal, vol. 8, no. 1, pp. 41-46, (Transformers),” Electra, no. 178, pp. 17-21, 1998.
1999. [38] E. Hanique, H.F. Reijnders, and P.T.M. Vaessen, “Frequency
[20] M. Belanger, “Transformer diagnosis: Part 1: A statistical response analysis as a diagnostic tool,” J. Elektotechniek, vol. 68,
justification for preventative maintenance,” Electricity Today, vol. no. 6, pp. 549-558, 1990.
11, no. 6, pp. 5-8, 1999. [39] J.W. Harley, “CIGRÉ Working Group 12.18 TF02, ‘Survey on
[21] M. Belanger, “Transformer diagnosis: Part 2: A look at the diagnostics & monitoring techniques transformer subsystems,’”
reference data for interpreting test results,” Electricity Today, vol. presented at CIGRÉ SC 12, Sydney Colloquium, Sydney, Australia,
11, no. 7, pp. 19-26, 1999. 1997.

[22] M. Belanger, “Transformer diagnosis: Part 3: Detection techniques [40] J.W. Harley and V.V. Sokolov, “Diagnostic techniques for power
and frequency of transformer testing,” Electricity Today, vol. 11, transformers,” presented at the International Council on Large
no. 8, pp. 19-26, 1999. Electric Systems (CIGRÉ), Paris, France, 2000.
[41] X. Huang and Z. Yan, “Study on trend analysis method for on-line
[23] C. Bengtsson, “Status and trends in transformer monitoring,”
insulation diagnosing of capacitive-type equipment,” presented at
IEEE Trans. Power Delivery, vol. 11, no. 3, pp. 1379-1384, 1996.
the International Symposium on Electrical Insulating Materials,
[24] T.R. Blackburn, et al., “On-line partial discharge measurement on
Toyohashi, Japan, 1998.
instrument transformers,” presented at the International
[42] T.R. Hyde, “On-line condition monitoring technology and
Symposium on Electrical Insulating Materials, Toyohashi, Japan,
applications,” ERA Technology, Rep. No. 95-0546R, 1995.
1998.
[43] A. Jaksts, et al., “A major breakthrough in transformer
[25] L. Bolduc, et al., “Detection of transformer winding displacement
technology,” presented at the International Council on Large
by the frequency response of stray losses (FRSL),” presented at the
Electric Systems (CIGRÉ), Paris, France, 2000.
International Council on Large Electric Systems (CIGRÉ), Paris,
[44] M.D. Judd, et al., “Transformer monitoring using the UHF
France, 2000.
technique,” presented at the 11th International Symposium on High
[26] P. Boss, et al., “Economical aspects and practical experiences of
Voltage Engineering, London, U.K., 1999.
power transformers on-line monitoring,” presented at the
[45] A.J. Kachler, “Diagnostic and monitoring technology for large
International Council on Large Electric Systems (CIGRÉ), Paris,
power transformers,” presented at CIGRÉ SC 12, Sydney
France, 2000.
Colloquium, Sydney, Australia, 1997.
[27] A.J.M. Cardoso and L.M.R. Oliveira, “Condition monitoring and
[46] S.R. Kannan, M. Tech, and N. Rao, “Generator loading limits for
diagnostics of power transformers,” Int. J. COMADEM,
impulse testing low-inductance windings,” Proc. IEE, vol. 122, no.
Sunderland, U.K., 1999, pp. 5-11.
5, pp. 535-538, 1975.
[28] D. Carreau, et al., “Condition monitoring diagnostics expert
[47] J.L. Kirtley, et al., “Monitoring the health of power transformers,”
systems: A project roadmap,” Electricity Today, vol. 12, no. 4, pp.
IEEE Computer Applications in Power, vol. 9, no. 1, pp. 18-23,
8-14, 2000.
1996.
[29] T.H. Crowley, “Automated diagnosis of large power transformers
[48] M.F. Lachman, W. Walter, and P.A. von Guggenberg, “On-line
using adaptive model-based monitoring,” B.S. and M.S. thesis,
diagnostics of high-voltage bushings and current transformers using
M.I.T., Cambridge, MA, 1990.
the sum current method,” IEEE Trans. Power Delivery, vol. 15, no.
[30] J.B. DiGiorgio, et al., “Cut failures by analyzing transformer oil,” 1, pp. 155-162, 2000.
Electrical World, vol. 192, no. 7, pp. 52-54, 1979. [49] P. Leemans, et al., “Control, diagnostic and monitoring of power
[31] N. Dominelli, “Furanic and non-furanic analysis as a transformer transformers,” presented at the International Council on Large
diagnostic,” presented at the EPRI Substation Equipment Electric Systems (CIGRÉ), Paris, France, 1998.
Diagnostics Conference IV, New Orleans, LA, 1996. [50] T. Leibfried, “Online monitors keep transformers in service,” IEEE
[32] G. Duke, “Predictive maintenance a case study in infrared Computer Applications in Power, vol. 11, no. 3, pp. 36-42, 1998.
thermography,” Electrical Maintenance, pp. 11-12, 1998. [51] T. Leibfried, et al., “On-line monitoring of power
[33] R. Farquharson and K. Caird, “An overview of substation transformers—Trends, new developments and first experiences,”
equipment monitoring and diagnostics: Part 1,” Electricity Today, presented at the International Council on Large Electric Systems
vol. 12, no. 5, pp. 23-26, 2000. (CIGRÉ), Paris, France, 1998.
[34] K. Feser, et al., “General trends in condition monitoring of [52] T. Leibfried and K. Feser, “Monitoring of power transformers
electrical insulation,” in Proc. Stockholm Power Tech. Int. Symp. using the transfer function method,” IEEE Trans. Power Delivery,
Electric Power Engineering, vol. 1, Stockholm, Sweden, 1995. Paper PE-053-PWRD-1-08-1998, 1998.

November/December 2002 — Vol. 18, No. 6 23


[53] T. Leibfried, “Online monitoring of power transformers—System [70] Y. Tian, et al., “PD pattern identification using acoustic emission
technology and data evaluation,” presented at the 11th International measurement and neural networks,” presented at the 11th
Symposium on High Voltage Engineering, London, England, 1999. International Symposium on High Voltage Engineering, London,
[54] P. Macor, et al., “The short-circuit resistance of transformers: The U.K., 1999.
feedback in France based on tests, service and calculation [71] K. Tomsovic, M. Tapper, and T. Ingvasrsson, “Performance
approaches,” presented at the International Council on Large evaluation of a transformer condition monitoring expert system,”
Electric Systems (CIGRÉ), Paris, France, 2000. presented at the International Council on Large Electric Systems
[55] R. Malewski, J. Douville, and G. Belanger, “Insulation diagnostic (CIGRÉ), Berlin, Federal Republic of Germany, 1993.
system for HV power transformers in service,” presented at the [72] A.J. Vandermaar and M. Wang, “Transformer condition
International Council on Large Electric Systems (CIGRÉ), Paris, monitoring by frequency response analysis” in Proc. 10th Int. Symp.
France, 1986. High Voltage Eng., Montreal, Canada, 1997, vol. 4, pp. 119-122.
[56] R. Malewski and M. Kazmierski, “Diagnostic techniques for [73] C. Wang, et al., “Analysis and suppression of continuous periodic
power transformers,” presented at the International Council on interference for on-line PD monitoring of power transformers,”
Large Electric Systems (CIGRÉ), Paris, France, 2000. presented at the 11th International Symposium on High Voltage
[57] R. Malewski, et al., “Instruments for HV insulation testing in Engineering, London, U.K., 1999.
substations,” presented at the International Council on Large [74] M. Wang, A.J. Vandermaar, and K.D. Srivastava, “Condition
Electric Systems (CIGRÉ), Paris, France, 2000. monitoring of transformers in service by the low voltage impulse
test method,” presented at the 11th International Symposium on
[58] M. Mizokami, M. Yabumoto, and Y. Okazaki, “Vibration analysis
High Voltage Engineering, London, U.K., 1999.
of a 3-phase model transformer core,” Electrical Engineering in
Japan, vol. 119, no. 1, 1997. [75] M. Wang, A.J. Vandermaar, and K.D. Srivastava, “Transformer
condition monitoring by the low voltage impulse test method,”
[59] A. Mollmann and B. Pahlavanpour, “New guidelines for
presented at the CIGRÉ Third South African Regional Conference,
interpretation of dissolved gas analysis in oil-filled transformers,”
Johannesburg, South Africa, 1998.
Electra, no. 186, pp. 30-51, 1999.
[76] Z. Wang, Y. Liu, and P.J. Griffin, “Neural net and expert system
[60] T. Noonan, “Power transformer on-site condition assessment
diagnose transformer faults,” IEEE Computer Applications in
testing,” presented at the International Council on Large Electric
Power, vol. 13, no. 1, pp. 50-55, 2000.
Systems (CIGRÉ), Paris, France, 2000.
[77] N. Al-Khayat and L. Haydock, “Swept frequency response test for
[61] A.J.M. Pemen, et al., “On-line partial discharge monitoring of HV
condition monitoring of power transformer,” in Proc.
components,” presented at the 11th International Symposium on
Electrical/Electronics Insul. Conf., Chicago, IL, 1995.
High Voltage Engineering, London, U.K., 1999.
[78] A. Drobishevskey, E. Levitzkaya, and M. Filatova, “Application of
[62] T.D. Poyser, et al., “On-line monitoring of power transformers,”
LV impulses for diagnostics of transformers during tests and in
IEEE Trans. Power Apparatus and Systems, vol. 104, no. 1, 1985.
service,” presented at the 8th International Symposium on High
[63] J.H. Provanzana, et al., “Transformer condition Voltage Engineering, Yokohama, Japan, 1993.
monitoring—Realizing an integrated adaptive analysis system,” [79] A.J. Kachler, et al., “High voltage impulse tests on power
presented at the International Council on Large Electric Systems transformers using a digital measuring system,” in Proc. 5th Int.
(CIGRÉ), Paris, France, 1992. Symp. High Volt. Eng., Braunschweig, Stadthalle, 1987, vol. 3,
[64] L. Ruijin, et al., “On-line detection of gases dissolved in paper 72.05.
transformer oil and the faults diagnosis,” presented at the [80] E.L. White, “Monitoring transformers in service for winding
International Symposium on Electrical Insulating Materials,” displacement using the low voltage impulse method,” ERA
Toyohashi, Japan, 1998. Technology, Rep. No. 81-62R, June 1981.
[65] B.G. Rushford, “Business case development for on-line [81] P. Tantin, P.V. Goosen, and P. Christensen, “CIGRÉ SC 12 Power
equipment,” Electrical Maintenance, pp. 5-10, Oct. 1998. Transformers Special Report 1998,” presented at the International
[66] T.K. Saha, et al., “Electrical and chemical diagnostics of Council on Large Electric Systems (CIGRÉ), Paris, France, 1998.
transformers insulation—Part A: Aged transformers samples,” [82] “Guide for the Sampling of Gases and Oil from Oil-Filled Electrical
IEEE Trans. Power Delivery, vol. 12, no. 4, pp. 1547-1554, 1997. Equipment and for the Analysis of Free and Dissolved Gases,” IEC
[67] T.K. Saha, et al., “Electrical and chemical diagnostics of Publication 567, 1992.
transformers insulation—Part B: Accelerated aged insulation [83] IEEE Guide for the Interpretation of Gases Generated in
samples,” IEEE Trans. Power Delivery, vol. 12, no. 4, pp. Oil-Immersed Transformers, IEEE Std. C57.104-1991, 1991.
1555-1561, 1997. [84] R.R. Roger, “IEEE and IEC codes to interpret incipient faults in
[68] R.J. Schwabe, et al., “On-line diagnostics of oil paper insulated transformers, using gas in oil analysis,” IEEE Trans. Elec. Insul., vol.
instrument transformers,” presented at the International Council 13, no. 5, pp. 349-354, 1978.
on Large Electric Systems (CIGRÉ), Paris, France, 2000. [85] “Interpretation of the analysis of gases in transformers and other
[69] S. Tenbohlen, et al., “Enhanced diagnosis of power transformers oil-filled electrical equipment in service,” IEC Publication 599,
using on- and off-line methods: Results, examples and future 1978.
trends,” presented at the International Council on Large Electric [86] M. Duval, “Dissolved gas analysis: It can save your transformer,”
Systems (CIGRÉ), Paris, France, 2000. IEEE Electrical Insulation Mag., vol. 5, no. 6., pp. 22-27, 1989.

24 IEEE Electrical Insulation Magazine


[87] P.J. Burton, et al., “Recent developments by CEGB to improve the [97] A. Bognar, et al, “Diagnostic tests of high voltage oil-paper
prediction and monitoring of transformer performance,” presented insulating systems (in particular transformer insulation) using dc
at the International Council on Large Electric Systems (CIGRÉ), dielectrometrics,” presented at the International Council on Large
Paris, France, 1984. Electric Systems (CIGRÉ), Paris, France, 1990.
[88] B. Fallou, “Detection of and research for the characteristics of an [98] E. Nemeth, “Measuring voltage response: A non-destructive
incipient fault from analysis of dissolved gases in the oil of an diagnostic test method of HV insulation,” IEE Proc. Sci., Meas.
insulation,” Electra, no. 42, pp. 31-52, 1975. Technol., vol. 146, no. 5, pp. 249-252, 1999.
[89] A. De Pablo and A. Mollmann, “New guidelines for furans analysis [99] T. Leibfried, et al., “On-line monitoring of power
as well as dissolved gas analysis in oil-filled transformers,” presented transformers—Trends, new developments and first experiences,”
at the International Council on Large Electric Systems (CIGRÉ), presented at the International Council on Large Electric Systems
Paris, France, 1996. (CIGRÉ), Paris, France, 1998.
[90] A. Mollmann and B. Pahlavanpour, “New guidelines for [100] T. Leibfried, “Online monitors keep transformers in service,”
interpretation of dissolved gas analysis in oil-filled transformers,” IEEE Computer Applications in Power, vol. 11, no. 3, pp. 36-42,
Electra, no. 186, pp. 30-51, 1999. 1998.
[91] D. Kopaczynski, “AC dielectric-loss, power-factor and capacitance [101] M.A. Sanz-Bobi, et al., “Experiences learned from the on-line
measurements as applied to insulation systems of high-voltage internal monitoring of the behavior of a transformer,” presented at
power apparatus in the field. Part 1: Dielectric theory. Part 2: the IEEE International Electric Machines and Drives Conference,
Practical applications of Doble testing,” Doble Client Conference Milwaukee, WI, 1997.
Proceedings, Apr. 1993. [102] C.K. Mechefske, “Correlating power transformer tank vibration
[92] IEEE Standard Test Code for Liquid Immersed Distribution, characteristics to winding looseness,” Insight, vol. 37, no. 8, pp.
Power, and Regulating Transformers and IEEE Guide for 599-604, 1985.
Short-circuit Testing of Distribution and Power Transformer, IEEE [103] T. Bengtsson, et al., “Acoustic diagnosis of tap changers,”
Std. C57.12.90-1999, 1999. presented at the International Council on Large Electric Systems
[93] A. Zargari and T.R. Blackburn, “Application of optical fiber sensor (CIGRÉ), Paris, France, 1996.
for partial discharge detection in high-voltage power equipment,” [104] A. Golubev, et al., “On-line vibro-acoustic alternative to the
in Proc. CEIDP, San Francisco, CA, 1996, pp. 541-544. frequency response analysis and on-line partial discharge
[94] R. Dorr, et al., “On-line transformer monitoring: Detection of measurements on large power transformers,” presented at the Tech
partial discharges from HF measurements using FFT and time Con’99 Annual Conference of TJ/H2b, New Orleans, LA, 1999.
domain filters,” in Proc. 12th Int. Symp. High Volt. Eng., vol. 5, [105] R.J. Denis, S.K. An, J. Vandermaar, and M. Wang, “Comparison
Bangalore, India, 2001, pp. 1230-1233. of two FRA methods to detect transformer winding movement,”
[95] R.S. Brooks and G.S. Urbani, “Using the recovery voltage method presented at the EPRI Substation Equipment Diagnostics
to evaluate aging in oil-paper insulation,” in Proc. IEEE Int. Conf. Conference VIII, New Orleans, LA, 2000.
Conduc. and Breakdown in Solid Dielec., Vasteras, Sweden, 1998, [106] A.J. Vandermaar, “On-line transformer winding and dielectric
pp. 93-97. monitoring-laboratory and field test results,” EPRI, TR-113650,
[96] G. Csepés, et al., “Recovery voltage method for oil/paper Sept. 1999.
insulation diagnosis,” in Proc. CEIDP, Atlanta, GA, 1998, vol. 1, pp. [107] M. Waters, The Short-Circuit Strength of Power Transformers.
345-355. London, U.K.: Macdonald & Co. (Publishers) Ltd., 1996.

November/December 2002 — Vol. 18, No. 6 25

Potrebbero piacerti anche