ISSN 1751-8687
Abstract: In recent years, application of self turn-off devices for the HVDC transmission system is very important
for flexible and high efficient power transport and supply. However, for self turn-off devices that are applied to
high-power system, excessive switching losses due to voltage/current surges occurred on hard switching and the
current tail characteristics on turn-off lead to the considerable switching loss. Therefore switching-loss reduction
by using a soft-switching technique is very effective for improvement of the considerable switching losses. A self-
commutated HVDC circuit topology with soft-switching characteristics is discussed. The proposed topology is able
to achieve a zero-current switching in self-commutated power converters. In order to examine the effectiveness
of the proposed system, the system is analysed in terms of the characteristics of switching losses through a
theoretical approach and computer simulations.
IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 4, pp. 315 – 324 315
doi: 10.1049/iet-gtd.2008.0078 & The Institution of Engineering and Technology 2009
www.ietdl.org
Therefore ZCS is the most successful soft-switching commutation circuit, current source self-commutated
technique for application of high-power converters. converter, output capacitors, converter transformer, AC
Besides, the soft-switching technique contributes to the filter and line impedances. The function of output
reduction of EMI noise. On the other hand, ZVS controls capacitors Cac1 , Cac2 is to keep the voltage by regulating the
voltage that occurs in the terminal of devices, and the reactive power. A commutation circuit consists of two
voltage is cancelled by resonant operation. Therefore it is thyristors T1 and T2 (or T3 and T4), resonant capacitor Ccr1
difficult to decrease of the switching losses significantly (or Ccr2 ) and resonant inductors Lcr1 and Lcr2 (or Lcr3 and
caused by the current tail based on ZVS is difficult. Also Lcr4 ). By connecting the commutation circuits for the DC-
the resonant circuit is an additional circuit that increases link, it is possible to achieve a perfect ZCS in HVDC.
the costs and power losses of components. That is to say, the commutation circuits aim to intermit
icon1 and icon2 flowing to the power converters. The
This paper proposes a zero-current switched HVDC circuit operating analysis of the commutation circuit is described
topology with self-commutated converter to improve the in detail in the next section.
switching loss of HVDC. The switching losses of HVDC are
reduced by adding a commutation circuit. In order to verify
the effectiveness of the proposed system, the simulations are 2.2 Operating principle and analysis
carried on by using MATLAB/SIMULINK and for commutation circuit
SimPowerSystems based on instantaneous modelling. Fig. 2 shows equivalent circuits in each mode (Mode 1 –
Mode 6) of commutation-circuit operation. Since the
This recent paper is organised as follows. Circuit simulation results of the operated commutation circuits on
configuration and operating principle of the proposed each side are nearly the same, only the right-side one is
system are given in Section 2. Section 3 shows ZCS analysed. The commutation circuit has six operating modes
requirements for soft switching. To confirm the robustness for a changing cycle of switching devices, and the resonant-
of the proposed circuit, fault simulations for soft-switching modes occur at Modes 1, 3 and 5. It is assumed that the
HVDC are executed in Section 4. Section 5 analyses the DC current Idc1 flowing to converter is sufficiently
characteristics of switching loss and conversion efficiency smoothed by the DC reactor. A thyristor model is treated
through a theoretical approach and computer simulations. as the same as GTO thyristor model that is shown in the
Finally, conclusions are drawn in Section 6. Fig. 3. The equations needed for analysis of operation are
derived on the basis of this figure.
2 Circuit configuration and Mode 1 (t0 2 t1: Fig. 2a): As the initial state in Mode 1,
operating principle main-switches Up1 and Wn1 on the right-side converter and
2.1 Circuit configuration of the proposed thyristor T 2 on the commutation circuit are in the
conduction state as shown in Fig. 2a. Other GTO devices
system and thyristor are in off-state. In addition, the voltage vcr1 at
Replacing line-commutated devices to self turn-off devices both ends of the resonant capacitor Ccr1 , are charged up to Vco .
causes an increase in switching loss. Therefore this paper
presents a soft-switching HVDC circuit topology. By In the beginning of this mode (t ¼ t0 ), when T2 is on by a
connecting commutation circuits for DC-link part of power turn-on signal, the commutation circuit attains resonant
converters, the proposed circuit executes the soft-switching condition by capacitor Ccr1 and inductor Lcr1 . Then, the
ZCS. Fig. 1 shows the main configuration of the soft- resonant current ir1 flows in the commutation circuit. The
switching HVDC transmission system. The circuit ir1 has the resonant frequency g1 determined by resonant
configuration contains point-symmetry except the DC-line. capacitor and inductor. An equivalent circuit of Mode 1 is
The power system side consists of DC smoothing reactor, shown in Fig. 2a. The charging voltage of resonant capacitor
316 IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 4, pp. 315– 324
& The Institution of Engineering and Technology 2009 doi: 10.1049/iet-gtd.2008.0078
www.ietdl.org
IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 4, pp. 315 – 324 317
doi: 10.1049/iet-gtd.2008.0078 & The Institution of Engineering and Technology 2009
www.ietdl.org
devices, the icon1 again begins to flow to the primary side, and 2.3 Simulation key waveform on soft
the operating mode shifts to Mode 3. and hard switchings
Mode 3 (t2 2 t3: Fig. 2c): Equivalent circuit of Mode 3 is To confirm the operating characteristics of the proposed circuit
shown in Fig. 2c. The commutation circuit once again is in shown in Fig. 1, the proposed system is simulated using
resonant condition. As the voltage equation in Mode 3 is MATLAB/SIMULINK and SimPowerSystems. The
similar to (1) of Mode 1, a equation of resonant current ir3 instantaneous simulation waveforms of a model with DC-
and (2) are equivalent. In this mode, a resonant capacitor lines are shown in Figs. 4 and 5. Fig. 4 shows simulation
changes in reverse polarity by the flow of ir3 . When ir3 is results with soft-switching ZCS. To confirm effectiveness of
zero, then thyristor T2 is turned-off with ZCS, and the the method, simulation results by hard switching are shown
condition also shifts to Mode 4. in Fig. 5. From Figs. 4 and 5, it is observed that iup1 and ivp1
flowing to each device by soft switching become nearly zero
Mode 4 (t3 2 t4: Fig. 2d): Resonant current that is flowing to by operating the commutation circuit before the main devices
commutation circuit is zero, and vcr1 has reverse polarity. In Up1 and Vp1 turn-off and turn-on, respectively. However, iup1
this mode, the DC (current) Idc1 flows to the primary and ivp1 by hard switching is not zero. As a result, excessive
inverter. An equivalent circuit of Mode 4 is shown in Fig. 2d. switching losses (losses more than 100 MW on turn-off and
losses of about 1.7 MW on turn-on), occur instantaneously in
Mode 5 (t4 2 t5: Fig. 2e): To reverse the polarity of the the main devices on hard switching. On the contrary,
resonant capacitor voltage vcr1 ( ¼ Vco ), a turn-on signal switching loss on soft switching is nearly zero. Therefore the
that has time delay Tdelay later than the turn-on signal of voltage and current stresses can be reduced (more than
thyristor T2, is given to the thyristor T1. An equivalent 100 MW on turn-off and about 1.7 MW on turn-on). To
circuit of this mode is shown in Fig. 2e. By turning on T1, evaluate the instantaneous switching loss on a simulation, a
a resonant current ir5 that has reverse direction flows in the GTO arm model of converters consists of a series connected
commutation circuit, and vcr1 is charged in straight polarity. to 15 devices (the nominal voltage and current in a GTO
device are 6000 V and 6000 A, respectively).
The voltage equation of Fig. 2e is written as
dir5 Ð
Vco ¼ (RLr2 þ Ron )ir5 þ (Lon þ Lcr1 þ Lcr2 ) þ 1 i dt
dt Ccr1 r5
(3)
9
vo5 2 a5 t =
ir5 ¼ Ccr1 Vco 1 sinh g5 t
g5 (4)
;
is ¼ Idc
pffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
where a + j b ¼ a5 + j a5 2 vo5 2
RLr2 þ Ron
¼
2(Lcr1 þ Lcr2 þ Lon )
sffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
2 ffi
RLr2 þ Ron 1
+j
2(Lcr1 þ Lcr2 þ Lon ) Ccr1 (Lcr1 þ Lcr2 þ Lon )
318 IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 4, pp. 315– 324
& The Institution of Engineering and Technology 2009 doi: 10.1049/iet-gtd.2008.0078
www.ietdl.org
In case of Mode 6
RL ¼ RLr2 þ Ron
Lro ¼ Lcr1 þ Lcr2 þ Lon
IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 4, pp. 315 – 324 319
doi: 10.1049/iet-gtd.2008.0078 & The Institution of Engineering and Technology 2009
www.ietdl.org
320 IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 4, pp. 315– 324
& The Institution of Engineering and Technology 2009 doi: 10.1049/iet-gtd.2008.0078
www.ietdl.org
bigger than the direct current Idc1 and can be expressed as in Modes 1 and 3. Therefore Tdelay can be expressed as
follows
Tr1 1 p p
Tdelay ¼ ¼ ¼ pffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi (10)
2 2fr1 b1 vo1 a1 2
2
V1
Ir2peak ¼ 1a1 =b1 f1 sin f1 Idc1 (9)
b1 (Lcr1 þ 2Lon ) where Tr1 mean time that T1 is in resonant condition.
IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 4, pp. 315 – 324 321
doi: 10.1049/iet-gtd.2008.0078 & The Institution of Engineering and Technology 2009
www.ietdl.org
parameters used in this simulation are shown in Table 1, where Fig. 9a shows the characteristics of switching losses for hard-
Lcr and Ccr was derived from (6). Each arm of the three-phase switching HVDC. In Fig. 9a, the solid line and the chain
bridge is composed of 6000 V, 6000 A gate turn-off thyristor dashed line show the total losses and the turn-off losses,
and 4500 V, 800 A anti-parallel diode. While, the resonant respectively. The chain double-dashed line and the chained
circuit is composed of 3000 V inductances, 4000 V, 800 A line show the turn-on losses and the conduction losses,
thyristor, 2500 V capacitor. As for the other components, we respectively. The dot line shows the transmission power. As
employ a 6600 V, 87.5 A, high-voltage phase advance the main losses that occur in the self turn-off device are
capacitor and a 420 kVA, 6600 V, 60 Hz AC filter. generally turn-on and turn-off losses and conduction losses,
Regarding the voltage rating of the devices, it is possible to the above three switching losses are evaluated. As can be seen
reduce the voltage rating of the devices with the increment of from Fig. 9a, with the increase of DC-current Idc , such losses
the number of L-C elements and series connection of are increasing. It can be confirmed that the arising losses on
switching devicies. The simulations assume terminal and hard switching in a high-power system like HVDC system
three phase to ground faults. Fig. 6 shows HVDC model are excessive, and that the switching losses in turn-off exceed
with faults. The simulation timestep is variable step (0–3 ms), conduction losses from Fig. 9a. Besides, it is confirmed that
duration of simulation is 0.5 s and time of execution is about the increase in hard-switching losses for high-power HVDC
17 min. The simulation sequence is as follows: fault on the circuit is high, and the switching losses with turn-off are
right-side occurred at t ¼ 0.15 s, and each power converter larger than conduction loss.
stops. In addition, the fault in the power system recovers at
t ¼ 0.3 s for considering the time when the system recovers
after an accident occurred, and each converter operates. In the
fault simulations, only the left-side converter is soft switching,
while the right-side is conventional switching.
322 IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 4, pp. 315– 324
& The Institution of Engineering and Technology 2009 doi: 10.1049/iet-gtd.2008.0078
www.ietdl.org
Fig. 9b shows the proportions of such losses (turn-on and component parts with auxiliary commutation circuit and
turn-off losses and conduction losses) to total losses (turn- the improvement of high power losses attributed by
on and turn-off losses þ conduction losses) as a introducing the soft-switching technique. However, for the
percentage. In Fig. 9b, the chain dashed line and the chain reduction of switching losses confirmed from simulation
double-dashed line show the characteristics of turn-off results, the additive losses in the commutation-circuit are
losses, and turn-on losses respectively, whereas the chained generated and the voltage rating of the devise is a little
line and the dot line show conduction losses and high, but the total losses in power converters for the
transmission power, respectively. From Fig. 9b, it is proposed system is improved. It is sufficiently possible to
confirmed that the losses with turning-off indicate losses decrease the power losses in the total system with
more than 50% of total losses, and the turn-off losses with application of soft-switching technique. In addition to
switching dominate the huge percentage of total losses. the above effectiveness, the cost reduction is led by
From the above results, in large-scale power systems such decreasing the heat-radiation unit with the reduction of
as HVDC system it is confirmed that energy losses switching loss.
occurring in self turn-off devices depend a lot on
switching loss. Developments of self turn-off device technology need no
soft-switching techniques. However, there are facts that the
Fig. 9c shows total loss of HVDC circuit with hard- and above developments advance soft switching and control
soft switching, respectively. To confirm effectiveness of the technologies. Besides, there is no ideal switching device,
soft-switching technique, the total losses with hard and the switching losses with turn-on and turn-off are not
switching are compared with soft-switching HVDC at zero. For these reasons, by introducing the soft-switching
1208 conduction operation. The total loss with soft- technique for the high-power system, the cost reduction,
switching HVDC includes copper and core losses with energy saving and the mitigation of environmental
resonant-element coil, and conduction loss with thyristors. problems is largely expected.
The solid line and the dash line show the total losses
(conduction loss þ loss of commutation circuit ) with soft
switching and total losses (conduction loss þ turn-on and 7 References
turn-off loss) with hard switching, respectively. From
Fig. 9c, it is confirmed that switching losses with self turn- [1] OHASHI H.: ‘Recent power devices trend’, J. IEEJ, 2002,
off devices are significantly improved by applying the soft- 122, (3), pp. 168– 171 (in Japanese)
switching technique.
[2] TAKAO K., YATSUO T., ARAI K.: ‘High di/dt switching
characteristics of a SiC Schottky barrier diode’, IEEJ Trans.
6 Conclusion IA, 2004, 124, (9), pp. 917 – 923 (in Japanese)
This paper proposes the HVDC circuit with soft-switching
technique. The proposed circuit concludes that switching [3] TOMASIN P.: ‘A novel topology of zero-current-switching
losses with all self turn-off devices are nearly zero by voltage-source PWM inverter for high-power applications’,
connecting commutation circuits for power converters. In IEEE Trans. Power Electron., 1998, 13, (1), pp. 186 – 193
addition, it is able to execute soft-switching ZCS only by
deciding switching sequences that turn-on pulses [4] SCHONKNECHT A., DE DONCKER R.W.A.A.: ‘Novel topology for
synchronised with turn-on signals of main-devices GTO parallel connecion of soft-switching high-power high-
give thyristor of commutation circuit. With the operating frequency inverters’, IEEE Trans. Ind. Appl., 2003, 39, (2),
analysis of the proposed circuit, the analysis equations for pp. 550– 555
such operating modes and ZCS requirements for soft
switching are derived. Besides, to confirm the robustness of [5] LI Y.P., LEE F.C., BOROYEVICH D.: ‘IGBT device application
the proposed circuit, fault simulations for soft-switching aspects for 50 kW zero-current-transition inverters’, IEEE
HVDC are executed. The simulation results show that the Trans. Ind. Appl., 2004, 40, (4), pp. 1039 – 1048
proposed circuit can achieve soft-switching operation, after
faults in the power system recover. Finally, to confirm the [6] BODUR H., BAKAN A.F.: ‘An improved ZCT-PWM DC-DC
effectiveness of soft-switching technique, the proposed converter for high-power and frequency applications’, IEEE
circuit is strictly modelled using MATLAB/SIMULINK Trans. Ind. Electron., 2004, 51, (1), pp. 89– 95
and SimPowerSystems. Switching losses with 1208
conduction operation are calculated on the simulation [7] PENG F.Z., LI H., SU G., LAWLER J.S.: ‘New ZVS bidirectional
results, and total losses for soft switching are compared DC – DC converter for fuel cell and battery application’,
with them for hard-switching. As a result, it is confirmed IEEE Trans. Power Electron., 2004, 19, (1), pp. 54 – 65
that the improvement of power losses are more than 50%
of total losses for hard-switching HVDC. Therefore the [8] HAN B.M., MOON S.I.: ‘Static reactive-power compensator
voltage and current stresses can be reduced. There are the using soft-switching current-source inverter’, IEEE Trans.
trade-off relationship between the increase of circuit Ind. Electron., 2001, 48, (60), pp. 1158 – 1165
IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 4, pp. 315 – 324 323
doi: 10.1049/iet-gtd.2008.0078 & The Institution of Engineering and Technology 2009
www.ietdl.org
[9] HAN B., MOON S., PARK J., KARADY G.: ‘Static synchronous
compensator using thyristor PWM current source inverter’,
IEEE Trans. Power Deliv., 2000, 15, (4), pp. 1285 – 1290
[11] SUZUKI H., NAKAJIMA T., IZUMI K., SUGIMOTO S., MINO Y., ABE H.:
‘Development and testing of prototype models for a
high-performance 300 MW self-commutated AC/DC
converter’, IEEE Trans. Power Deliv., 1997, 12, (4), Figure 10 Turn-on and off characteristics of GTO
pp. 1589 – 1597
can be expressed. From (13), the equation of switching loss at
[12] HE X., CHEN A., WU H., DENG Y., ZHAO R. : ‘Simple passive
turn-off duration can be derived as
lossless snubber for high-power multilevel inverters’, IEEE
Trans. Ind. Electron., 2006, 53, (3), pp. 727 – 735
ð Toff þTf þTt
1
woff ¼ ic vce dt ¼ Vrms Idc 11Tf þ Tt (14)
20
8 Appendix Toff
324 IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 4, pp. 315– 324