Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
The copyright for this document and all appendices are reserved by Holcim Group Support Ltd
Part Explosion Protection
Technical AFR Manual
Version 1.0
Lukas Schwank
Beat Maier
Werner Voramwald
Michael Schmid
2/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
Introduction
Motivation
Why is Explosion protection an important issue when dealing with AFR? The easiest way to
answer this question is to imagine a situation where an explosion would have happened. Let
us assume that there is an explosion on the top of liquid tank at an AFR platform. With a loud
bang a fireball would arise on the top of the tank. What would be the consequences in such a
case for the stakeholders? What would think the people living in the neighbourhood, the public
and the media, the authorities, the waste suppliers and the people working in the platform?
For sure the loss in good-will and confidence will by far exceed the direct cost impact from the
loss of equipment and the ability to pre-process AFR. Therefore the goal must be: Never give
the explosion a chance to happen on your platform!
Objectives
Generally speaking the goal of this manual is to provide information about the threats of
explosions, the concepts of explosion protection and the required actions to minimize
explosion risks. However it is also clear that this manual will not solve all safety problems and
answer all questions, which may arise around explosions. It shall therefore primarily serve as
a reference document which on the one hand introduces the key concepts of explosion safety
and on the other hand shows how to set them in practise.
3/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
Table of Contents
1. BASIC EXPLOSION THEORY 5
1.1 What is an explosion? 5
1.2 Explosion Factors 6
1.3 Upper and Lower Explosion limits – right fuel-oxygen mixture 7
1.4 Explosion Characteristics (pmax, KG/D) 9
1.5 Gas explosions 10
1.6 Dust explosions 11
1.7 Hybrid Mixtures Explosion 13
1.8 Pipe explosion 15
2. EXPLOSION PROTECTION 18
2.1 Overview 18
2.2 Inertisation 19
2.3 Explosion Pressure Resistant Construction 20
2.4 Explosion Pressure-Shock Resistant 20
2.5 Explosion Pressure Venting Measures 20
2.6 Explosion Suppression 23
3. REGULATIONS AND EU-DIRECTIVES 25
3.1 Overview of ATEX Directives 25
3.2 What is an explosive atmosphere? 26
3.3 Summary of ATEX 95 (Directive 94/9/EC) 26
3.4 Summary of ATEX 137 (Directive 99/92/EC) 27
3.5 Zone plan and equipment selection 28
4. APPENDIX A: EQUIPMENT LABELLING AND ATEX MARKING 31
4/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
The type of chemical reaction is usually an oxidation type reaction, which means
that a substance reacts with oxygen of the air and releases energy. An explosion
can therefore also be described as a very fast fire, which spreads through a volume,
where beforehand the fuel (or better combustible) has been distributed in the air.
This is an important characteristic of the explosion: The combustible-oxygen mixture
must be prepared before the explosion can take place.
This distinction is important since detonations are far more destructive than
deflagrations. If a combustible causes a deflagration or a detonation depends on the
type of combustible, the fuel-oxygen-mixture and the geometry of the propagation.
Most explosions in technical fields are deflagrations. However, under certain
5/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
Ignition
Ignition source
source
Combustble
Combustble Oxygen
Oxygen
Figure 1: Explosion Triangle, with the 3 factors needed for an explosion
What is meant by the third factor – source of ignition? The combustible and the
oxygen must be present in the correct ratio. But this alone will not start the
explosion. It can be seen as a gun which is loaded, but not yet fired. Pulling the
trigger in this image would mean, to bring a source of ignition into the fuel-oxygen
mixture. The source of ignition gives the needed push to start the chemical reaction
in one point. Since the chemical reaction generates heat itself, the reaction will now
propagate very fast and form what we finally call an explosion. In that sense one can
say that a part of the energy released by the explosion is needed for its propagation.
However the energy given to the environment in form of pressure and temperature
exceeds this by far.
¾ Combustible
− Gas / Vapours / Mists
− Dust
¾ Oxygen
− Air (other oxidizing agents are theoretically possible, but have no
relevance in practice)
¾ Ignition Source
6/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
− Hot surfaces
− Open flames and hot gases
− Mechanical sparks (welding, cutting, grinding etc.)
− Electrical sparks
− Electrical equipment
− Electric currents
− Electrostatic charging
− Lightning
− Electromagnetic fields
− Ionizing radiation
− Ultra sonic waves
− Adiabatic compression (e.g. shock waves)
− Chemical reactions
− Self heating, Smoldering Nests and Exothermic decomposition
The two limits of combustible concentration are called LEL and UEL, lower
explosion limit and upper explosion limit. LEL and UEL are different for every type of
combustible and are also dependent on the surrounding temperature and pressure.
For values close to ambient conditions (10 – 30°C) this dependency can be
neglected, since the effect is rather weak.
Figure 2: Explosion pressure as a function of combustible in air. The maximum impact of an explosion is reached
at stoichiometric conditions.
7/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
8/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
Both values are material parameters, but also depend on the measuring setup or the
actual conditions when they occur. As already discussed, the impact of an explosion
is dependent on the combustible-air ratio. Therefore pmax and KG/D are measured
and defined at the stoichiometric or lambda 1 ratio (maximum power of explosion).
The standardized measuring-conditions specify also the volume of the test container
to 1m3. While the maximum explosion pressure pmax is almost independent of the
container’s form and size, the maximum pressure increase KG/D is dependent on the
amount of involved combustibles and therefore also from the container volume.
V = 20 m3 → (dp/dt)max = 27 bar/s
7 7 pmax
(dp/dt)max
Figure 3: Comparison of 3 explosions in different test containers (Volume = 0.001 m3, 1m3, 20m3). It shows that
the maximum reached pressure pmax remains constant, while the steepness of pressure raise varies. KG/D is
defined as the maximum pressure steepness for a container of V=1m3.
After the ignition of an explosive fuel-air-mixture the pressure increases rapidly until
it reaches the maximum explosion pressure pmax, it is more or less equal to the
9/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
moment where all combustible has reacted with oxygen. The pressure now drops,
while the shock wave propagates further and gets damped.
The steepness of the pressure raise can be calculated as the difference in pressure
divided trough the needed time-difference (=dp/dt). The maximum reached
steepness during a test explosion is defined as KG/D. This value is a measure for the
speed in which the pressure grows and plays an important role to estimate the
destructiveness of an explosion. It is expressed in bars per seconds [bar/s].
10/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
The explosion characteristics for several gases or vapours are listed in the following
table.
These table values are only valid for standard conditions (no turbulence, ideal
explosion concentrations, a starting pressure of 1 bar).
¾ It must be combustible
(Note that materials which usually burn very weak can ignite easily when they
are in the form of small particles as dust)
¾ The particles need to be fine enough
(usually in the range of 0.5 mm, however even in optically coarser dust there
is very probably a fraction of fine dust contained, which is sufficient for the
ignition)
¾ The dust must be dispersed in the air (surrounded by oxygen) in the right
concentration (see LEL)
11/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
The explosion characteristics for several gases or vapours are listed in the following
table.
Dust pmax [bar] KD [bar m s-1]
Hard Coal 85
Lignite 150
Organic Pigments 300
Animal Meal 6.9 80
Dried Sewage 6.0 130
Sludge
PetCoke 6.3 80
Aluminum dust 6.5 - 13 16 - 1'900
PE-dust 1.3 - 7.9 4 - 120
Table 3: Explosion characteristics of several dust types
All types of mineral coals as well as the majority of lignites, Petcoke and dried
sewage sludge belong to explosions class St1.
Secondary explosions are caused (in this context) when lying dust is disturbed by
the primary explosion and forms a second dust cloud which then is ignited by the
heat released from the primary explosion. The problem is that small amounts of
lying dust occupy very little space, but once disturbed can easily form dangerous
clouds.
12/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
Example: A 1 mm layer of dust of 500 kg/m3 can give rise to a 5 m deep cloud of
100 g/m3 dust.
Hybrid mixtures are therefore much more dangerous than regular dust mixtures!
13/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
[bar]
250
[g/m3]
Hybrid Mixtures: Lower Explosion Limit
PVC
100
50
Pea Meal
Cellulose
14/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
1010
Hybrid Mixtures: Minimium Ignition Temperature
9
10
Lower Explosion
Limit (LEL) of
Mono-Azo-Pigment PY1 (Hansagelb) (M-20)
108 Propane Cellulose (M-27)
¡ PE (M-125)
T PVC (M-20)
Minimum Ignition Temperature
107
S PVC (M-125)
106
M = Median - μm
105
103
102
101
1 Propane Concentration
After ignition of the vapours, it is likely that the vapours continue to flow due to
continuing pumping in operations or thermal heating taken place. In such a case, the
flame will continue to burn at the breathing opening of the tank (Endurance
burning). The flame arrester has to be designed to absorb and dissipate the
continuous input of energy due to long term burning so that the ignition temperature
beyond the flame arrester is not reached.
15/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
16/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
occurs. But the explosion process is unstable and the overdriven detonation is just a
short lived phenomenon.
17/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
2. EXPLOSION PROTECTION
This chapter focuses on the field of “explosion protection”. Since the impact of
explosion is usually so high and so destructive, the best practise is to avoid
explosions. Measures and actions, which serve the goal not to let an explosion
happen, are summarized as explosion prevention.
It becomes clear, explosion protection deals always with assessment of risks and
probabilities. Therefore the risk assessment is a crucial part of explosion protection.
Equipment and countermeasures shall be selected according to the risk of
explosions.
2.1 Overview
Explosion protecting measures can be classified as follows:
18/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
Fighting / Limiting Damage Measures that do not prevent explosion but help
to reduce their destructiveness
¾ Fire
³ Fire Extinguisher
³ External Sprinkler
³ Internal Sprinkler
³ Foam Dosage
³ ARGONITE extinguishing system
¾ Explosion
³ Explosion Pressure Resistant Construction
³ Explosion Pressure Shock Resistant
³ Explosion Pressure Venting Measures VDI Guidelines No. 3673
³ Explosion Suppression System
2.2 Inertisation
Dust and gas explosions can be effectively prevented through inertisation, i.e. the
replacement of the oxygen in the air by a non-combustible gas, particularly CO2 or
N2, if it can be ensured that the inert gas atmosphere will be maintained as long as
the combustible is present in the system.
This must not necessarily mean that all air has to be replaced. The goal is only to
prevent the presence of an ignitable fuel-oxygen mixture. The replacement of have
the air with nitrogen would lead to a final oxygen concentration of 10.5%. This
oxygen concentration is already far below most of the critical oxygen-concentrations,
which allows an explosion to happen.
Important: Inert gas operation alone can effectively prevent the occurrence of
explosions but not of smoldering.
19/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
Inertisation can e.g. be achieved by introducing hot inert gases such as the kiln
exhaust from cement kilns or hot gases from a combustion chamber.
If the inert gas atmosphere can be maintained with absolute certainty through
appropriate design and interlocking of the installation for as long as combustible is
present in the system, design related protection measures become in principle
redundant.
Inertisation is only possible in closed devices with low gas exchange rates.
All combustible conveying installation parts as well as the adjacent equipment and
sealing elements must be designed to resist the maximal explosion pressure (e.g. 9
bar expected in the case of coal or lignite dust).
20/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
but only for the reduced explosion pressure Pred. A deformation of the container may
again be acceptable, but it must not burst.
Venting Opening
Pressure in Vessel
Pred
time
The explosion pressure venting technique operates in the following manner: When
the dynamic response pressure of the pressure venting installation is reached,
predetermined breaking points, rip foils or doors open to vent the shock wave
outdoors, mainly by means of amply dimensioned discharge channels. Immediately
after the pressure venting system responds an increase in the temporal rate of
pressure rise can often be observed which is due to the higher turbulence caused
during the venting of the shock wave. The pressure rise then quickly stops at Pred..
If the method of explosion venting is applied not only the inserts of the containers
such as filter cloths etc. must be considered but the expected recoil forces as well.
All combustible dust conveying components that are not in themselves designed to
be explosion pressure resistant, such as cyclone, filters, pulverized fuel silos, etc.
are to be provided with properly dimensioned devices for explosion pressure
venting. Thereby containers and all interconnected aggregates such as bin vent
21/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
filters, etc. must be dimensioned in pressure shock resistant design to withstand the
reduced explosion pressure.
22/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
that the resulting pressures can amount to 50 times the original pressure,
accompanied by a combustion front traveling at supersonic speed, so that any relief
or suppression installation is too sluggish in action. However, such events are,
fortunately, relatively rare in coal operations.
23/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
24/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
What does that mean for Holcim group companies outside Europe? The measures
described in this chapter are not necessarily legally binding. The actual situation in
each and every country is not determinable for HGRS. However the ATEX
regulations give a guideline for good practice. Most probably the national regulations
are not as strict as the ATEX regulations. Following the ATEX- measures means
therefore being on the “safe side”. It is an HGRS recommendation to set the ATEX-
measures in place, regardless what national regulations ask for (as long as they are
not stricter).
The two directives are also named “the manufacturer directive” (ATEX 95) and “the
end user directive” (ATEX 137). This describes pretty much what they are about and
for whom they are relevant. ATEX 95 describes what conditions a piece of
equipment must fulfil to be installed in a place where an explosive atmosphere can
occur. It is therefore mainly relevant for manufacturer of equipment.
ATEX 137 describes what measures must be taken to guarantee a safe workplace
around explosive atmospheres. It is therefore relevant for companies, which have a
process that might lead to explosive atmospheres.
25/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
Scope of directive
¾ The directive applies to equipment which fulfils the following three
preconditions:
a) it has its own effective source of ignition;
b) it is intended for use in a potentially explosive atmosphere;
c) it operates under normal atmospheric conditions.
¾ Duties are placed on the manufacturer/supplier side of the equipment
¾ To place such equipment on the European market, official certification is
needed. The equipment will be marked with the standardized “Ex” symbol (see
picture). This symbol is also referred to as “ATEX” marking and is integrated in
the CE declaration of conformity.
The explosion protection concept of this directive works on the following principle:
¾ Make sure that the equipment is not producing any kind of ignition source
such as a high temperature surfaces, sparks from mechanical impact, sparks
from electrostatic effects, or others.
¾ By eliminating the ignition source from the explosive triangle, an explosion will
not occur even there is an explosive atmosphere present (due to other
circumstances, which have nothing to do with the equipment itself)
¾ There are 3 different equipment categories (1, 2 and 3) which pay respect to
the likelihood that an ignition source may occur even under malfunctioning of
the equipment. (Category 1 provides the highest safety).
¾ The 3 equipment categories are defined in agreement with the zone concept
of ATEX 137. As lower the likelihood that an explosive atmosphere is present
the higher the equipment category. (Zone 0 and 20 are the zones with the
highest risk for an explosive atmosphere and need equipment category 1)
¾ The end user can see which category the equipment fulfils by a standardised
labelling on the type plate. The code is explained in the Annex.
26/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
The specific marking on equipment, which is Warning sign for locations where explosive
explosion protected according to ATEX 95. atmospheres may occur (ATEX 137)
(Mainly meaning that this equipment will not
serve as source of ignition for an explosion)
27/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
¾ Define work orders for the particular zones to ensure the safety of the workers.
This must include:
a) instructions on special tools and procedures (for example spark proof)
b) rules when to work under supervision (for high risk work)
¾ Install warning signs where explosive atmospheres may occur (according to
the zone plan)
¾ Elaborate an explosion protection document (EPD) and keep it up to date. The
following points must be written down in the EPD:
a) considerations and results of risk assessment
b) classification of zones according to likelihood concept
c) work orders for particular zones
As described above, the ATEX 137 asks for a zone plan for endangered areas
according to the likelihood concept. According to the zone plan the right equipment
must be selected, which is certified after ATEX 95.
In the following the concept of the zone plan is described.
Every area, where an explosive atmosphere might occur must be classified as one
of three zones. The three zones differ from each other according to the likelihood
that an explosive atmosphere might occur. Safe areas, where the risk of explosive
atmospheres can be excluded, are defined as “no zone”
There are two systems of zones. Explosive atmospheres due to
¾ …gases, mists and vapors are classified into zone 0, zone 1 and zone 2
¾ …dust are classified into zone 20, zone 21 and zone 22
¾ Whereas zone 0/20 are the zones with the highest risk for an explosive
atmosphere
28/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
gas, vapor, mist 0 present continuously or for long mor than 1000 hours
periods, frequently
gas, vapor, mist 2 not likely to occur in normal less than 10 hours
operation, only shortly
Areas classified into zones must be protected from effective sources of ignition. The
equipment used in zoned areas must meet the requirements of the ATEX 95-
directive. As higher the risk of an explosion in a zone is, the better the equipment
must be protected from being a source of ignition.
¾ Zone 0 and 20 requires category 1 marked equipment
¾ zone 1 and 21 requires category 2, or lower marked equipment
¾ zone 2 and 22 requires category 3, or lower marked equipment
The difference of the 3 equipment categories can be summarized as the chance that
the equipment serves as a source of ignition. For higher categories also malfunction
of the equipment is taken into account. The following table gives an overview.
Figure 3: Requirements for equipment, which is designed for the different explosion zones
Not all equipment which is suited for explosive atmospheres from dust is
automatically suited for explosive atmospheres from gases. Therefore two classes
of equipment categories exist:
¾ G for equipment in explosive atmospheres from gas, mists and vapors (G1, G2
and G3)
29/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
gas, vapor, mist G1 0 mor than 1000 hours present continuously or for
long periods, frequently
gas, vapor, mist G3 2 less than 10 hours not likely to occur in normal
operation, only shortly
It becomes clear that the selection of equipment can only be done correctly if a
proper risk assessment has been carried out. The direct result of the risk
assessment is the zone plane, which estimates in which areas how often an
explosive atmosphere is present.
30/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
II 2G EEx ed IIC T4
Certificate Center Equipment Group Equipment Category Explosion Group
in the following called Group in the following called Category
Group II
¾ comprises equipment intended for use in other places likely to become
endangered by explosive atmospheres.
Caution: Remarks only valid for group II, group I is out of concern.
An Ex-Zone type is defined by the temporal probability for the presence of an
explosive atmosphere. In a certain Ex-zone, only equipment assigned to the specific
category, is allowed to be installed. There is a distinction between gas and dust
zones.
Gas:
¾ Ex-Zone 0 requires Category 1 G
explosive atmosphere occurs permanently or often (> 1'000 h/a)
31/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
Dust:
¾ Ex-Zone 20 requires Category 1 D
explosive atmosphere due to combustible dust occurs permanently or often (>
1'000 h/a)
¾ Ex-Zone 21 requires Category 2 D
explosive atmosphere due to combustible dust occurs periodically (10 - 1'000
h/a)
¾ Ex-Zone 22 requires Category 3 D
explosive atmosphere due to combustible dust occurs periodically (10 - 1'000
h/a)
For the assessment of the ignition by sparks two different laboratory methods are
used:
³ MIC
³ MESG
For the assessment of the ignition of the gases and vapours in a circuit 1 , a
comparative value with methane as reference in a standardized circuit is used. This
comparative value is the minimum ignition ratio, MIC. It is the means used for
classifying gases and vapours within explosion group II in the subgroups II A, II B
and II C.
An analogue value is found when the ease of ignition by a hot gas jet flowing
through a gap is used for the classification. A test apparatus 2 is specified in which a
spherical gas volume of 20 cm³ is enclosed by two hemispheres. They are equipped
with a 25 mm wide flange. This ball-shaped object is placed into a larger vessel and
both spaces are filled with the mixture for which the safe gap is to be determined.
The gap between the 25 mm wide flanges for which ten ignitions inside the ball
volume just fail to ignite the mixture in the outer vessel is a value specific to the
mixture and is called the maximum experimental safe gap, MESG. The MESG is the
1
using a device defined in IEC 60079-11
2
In IEC 60079-1A „Determination of the experimental safe gap“
32/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
width of a gap through which the propagation of a flame is not possible. Every
combustible gas / vapour / dust has its specific MESG.
The processes involved in the prevention or spread of the explosion in the gap are
very complex. Classifying the gases and vapours by the safe gap results
approximately - with a small overlap - in the same classification as that obtained with
the minimum ignition current.
Increasing Danger
II A > 0.8 > 0,90 mm
II B1 0,85 mm
II B2 0,75 mm
II B3 0,65 mm
II B 0.45 - 0.8 0,50 mm
II C < 0.45 < 0,50 mm
Table 4-1: Explosion Groups
Every device, which has been approved for a certain MESG / MIC can be used for
any product of that MESG / MIC or any other product with a larger MESG / MIC (e.g.
II C can be used in II A, II B 1-3 and II B).
The safe gap value is of considerable importance for designs of ignition protection
type „Flameproof enclosure“. The value for the minimum ignition current is important
for those of ignition protection type „Intrinsic safety“. For these two types of
protection, the subgroups II A, II B and II C for gases and vapours are relevant. The
information about gases and vapours can also be applied approximately to mists.
For dust, standards for the determination of parameters are already available or are
in preparation.
The minimum ignition energy, a parameter similar to the minimum ignition current, is
determined in accordance with IEC 61241-2-3.
Many factors such as size, shape, type and surface quality have an influence on the
ignition temperature. A standard test method is defined in such a way, that a value
very close to the lowest practically possible, is determined.
Gases and vapours are divided into temperature classes according their ignition
temperature.
33/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
Dust in its deposited form (value A) has a different ignition temperature (it is lower
due to worse isolating effects) than in its stirred. cloudy form (value B). The relevant
value is the lowest value of the calculation (A-75°C) und 2/3*B.
34/35
Part Explosion Protection
Technical AFR Manual
Version 1.0
35/35