Application Description  09/2014

Plant Configuration Using


WinCC Runtime Professional
Description

http://support.automation.siemens.com/WW/view/de/87054082
Warranty and Liability

Warranty and Liability


Note The Application Examples are not binding and do not claim to be complete
regarding the circuits shown, equipping and any eventuality. The Application
Examples do not represent customer-specific solutions. They are only intended
to provide support for typical applications. You are responsible for ensuring that
the described products are used correctly. These Application Examples do not
relieve you of the responsibility to use sound practices in application, installation,
operation and maintenance. When using these Application Examples, you
recognize that we cannot be made liable for any damage/claims beyond the
liability clause described. We reserve the right to make changes to these
Application Examples at any time and without prior notice. If there are any
deviations between the recommendations provided in these Application
Examples and other Siemens publications – e.g. Catalogs – the contents of the
other documents have priority.

We do not accept any liability for the information contained in this document.
Any claims against us – based on whatever legal reason – resulting from the use of
the examples, information, programs, engineering and performance data etc.,
described in this Application Example shall be excluded. Such an exclusion shall
not apply in the case of mandatory liability, e.g. under the German Product Liability
Act (“Produkthaftungsgesetz”), in case of intent, gross negligence, or injury of life,
body or health, guarantee for the quality of a product, fraudulent concealment of a
deficiency or breach of a condition which goes to the root of the contract
 Siemens AG 2014 All rights reserved

(“wesentliche Vertragspflichten”). The damages for a breach of a substantial


contractual obligation are, however, limited to the foreseeable damage, typical for
the type of contract, except in the event of intent or gross negligence or injury to
life, body or health. The above provisions do not imply a change of the burden of
proof to your detriment.
Any form of duplication or distribution of these Application Examples or excerpts
hereof is prohibited without the expressed consent of Siemens Industry Sector.

Security Siemens provides products and solutions with industrial security functions that
informa- support the secure operation of plants, solutions, machines, equipment and/or
tion networks. They are important components in a holistic industrial security
concept. With this in mind, Siemens’ products and solutions undergo continuous
development. Siemens recommends strongly that you regularly check for
product updates.
For the secure operation of Siemens products and solutions, it is necessary to
take suitable preventive action (e.g., cell protection concept) and integrate each
component into a holistic, state-of-the-art industrial security concept. Third-party
products that may be in use should also be considered. For more information
about industrial security, visit http://www.siemens.com/industrialsecurity.
To stay informed about product updates as they occur, sign up for a product-
specific newsletter. For more information, visit
http://support.automation.siemens.com.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 2
Table of Contents

Table of Contents
Warranty and Liability ................................................................................................. 2
1 Task ..................................................................................................................... 5
2 Single-User System ........................................................................................... 7
2.1 Task ...................................................................................................... 7
2.2 Solution................................................................................................. 7
2.2.1 Functional principle .............................................................................. 7
2.2.2 Hardware and software components ................................................... 8
2.3 Procedure ............................................................................................. 9
2.3.1 Installation ............................................................................................ 9
2.3.2 Project engineering ............................................................................ 10
3 Single-User System With Multiple Monitors ................................................. 12
3.1 Task .................................................................................................... 12
3.2 Solution............................................................................................... 12
3.2.1 Functional principle ............................................................................ 12
3.2.2 Hardware and software components ................................................. 13
3.3 Procedure ........................................................................................... 14
3.3.1 Installation .......................................................................................... 14
3.3.2 Project engineering ............................................................................ 16
4 Multi-User System ........................................................................................... 20
4.1 Task .................................................................................................... 20
 Siemens AG 2014 All rights reserved

4.2 Solution............................................................................................... 20
4.2.1 Functional principle ............................................................................ 20
4.2.2 Hardware and software components ................................................. 22
4.3 Procedure ........................................................................................... 23
4.3.1 Installation .......................................................................................... 23
4.3.2 Project engineering ............................................................................ 25
4.3.3 Further settings .................................................................................. 28
5 Redundant Systems ........................................................................................ 29
5.1 Task .................................................................................................... 29
5.2 Solution............................................................................................... 29
5.2.1 Functional principle ............................................................................ 29
5.2.2 Hardware and software components ................................................. 31
5.3 Procedure ........................................................................................... 33
5.3.1 Installation .......................................................................................... 33
5.3.2 Project engineering ............................................................................ 35
5.3.3 Further settings .................................................................................. 39
6 Web Access ...................................................................................................... 40
6.1 Task .................................................................................................... 40
6.2 Solution............................................................................................... 40
6.2.1 Functional principle ............................................................................ 40
6.2.2 Hardware and software components ................................................. 41
6.3 Procedure ........................................................................................... 43
6.3.1 Installation .......................................................................................... 43
6.3.2 Project engineering ............................................................................ 52
6.3.3 Working with the WebNavigator components .................................... 54
7 Access Through Office PCs ........................................................................... 57
7.1 Task .................................................................................................... 57
7.2 Solution............................................................................................... 57
7.2.1 Functional principle ............................................................................ 57

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 3
Table of Contents

7.2.2 Hardware and software components ................................................. 59


7.3 Procedure ........................................................................................... 60
7.3.1 Installation .......................................................................................... 60
7.3.2 Project engineering ............................................................................ 68
7.3.3 Working with the DataMonitor components ....................................... 71
8 References ....................................................................................................... 90
9 History............................................................................................................... 90
 Siemens AG 2014 All rights reserved

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 4
1 Task

1 Task
Introduction
Automation technology poses most diverse requirements on SCADA systems.
With WinCC Runtime Professional and the available options, you can set up both
sophisticated single-user applications and complex multi-user systems with servers
and clients. What's more, data transfer for an evaluation in the office world or
automatic sending of the production data by e-mail is also possible.
This application shows you the required hardware and software as well as the
engineering steps for setting up the different plant configurations.

Overview of the automation task


The figure below gives an overview of the automation task.

Figure 1-1
 Siemens AG 2014 All rights reserved

...
Internet

Main topics of this application


The following topics will be discussed in this application:
• Required hardware and software components of the respective scenario
• Required licenses
• Installation and expansion of the project engineering

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 5
1 Task

Assumed knowledge
This application does not contain a description of the following topics:
• Basic engineering with WinCC (TIA Portal). Only the steps required additionally
for the respective setup will be explained.
• Network configuration
• Process connection of the WinCC (TIA Portal) components
• Basics of Microsoft Windows operating systems
Basic knowledge of these topics is assumed.
 Siemens AG 2014 All rights reserved

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 6
2 Single-User System
2.1 Task

2 Single-User System
2.1 Task
Overview
Figure 2-1

Operator Station (OS) Engineering Station (ES)

LAN

Process connection
 Siemens AG 2014 All rights reserved

Description
For process monitoring, you use a single-user system – the operator station (OS).
The OS is connected to the process (e.g., via Ethernet). The engineering station
(ES) is used for project engineering. ES and OS can also be designed as one
station.

2.2 Solution
2.2.1 Functional principle

A single-user system is an independent WinCC system. The engineering and


runtime data are stored locally on the PC.
Single-user systems are usually used close to production. They are suited for
smaller applications or for operator control and monitoring of independent
subprocesses or plant sections.
Project engineering can be performed either directly at the OS or at a separate ES.
For project engineering, the license "SIMATIC WinCC Professional" is required.
For operation at runtime, the license "SIMATIC WinCC Runtime Professional" is
required. Both licenses are available in different variants, depending on the number
of power tags required in your project. Power tags are tags with process
connection.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 7
2 Single-User System
2.2 Solution

Advantages
The solution presented here offers you the following advantages:
• Consistent scalability from single-user system to client-server solution
• Investment security
• Easy expandability via power packs or options

2.2.2 Hardware and software components

Hardware components
Table 2-1
Component No. Article number Note
Programmer, e.g., 1 6ES7716-2CA10-0CD3 Engineering station
SIMATIC FIELD
PG M4
SIMATIC 1 6AG4104-3HA34-4BX0 Operator station
IPC547E 19” rack PC, optionally
available as tower
Flat Panel 1 6AV7863-3TA00-0AA0 Single-touch, alternatively with
SIMATIC IFP1900 glass front (multi-touch
capable)
Ethernet cable 1 Specialist retailers For project engineering
 Siemens AG 2014 All rights reserved

transfer from ES to OS

Software components
Table 2-2
Component No. Article number Note
SIMATIC WinCC 1 e.g.: 6AV2103-0DA03-0AA5 For installation on the ES
Professional
SIMATIC WinCC 1 e.g.: 6AV2105-0DA03-0AA0 For installation on the OS
Runtime
Professional

Licenses
Table 2-3
Component No. Article number Note
SIMATIC WinCC 1 License included in "SIMATIC
Professional WinCC Professional" software
SIMATIC WinCC 1 License included in "SIMATIC
Runtime WinCC Runtime Professional"
Professional software

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 8
2 Single-User System
2.3 Procedure

2.3 Procedure
2.3.1 Installation

Table 2-4
No. Action
1. Start the installation setup "SIMATIC WinCC Runtime Professional" at the OS.
2. Select the installation language and read the installation and product information.
3. Select the languages to be installed.
4. Select the "SIMATIC WinCC Runtime Professional V13.0" component. The
components "Documentation Viewer", "Microsoft SQL Server 2008 R2 Standard
Edition SP2", and "Automation License Manager" are selected automatically.
 Siemens AG 2014 All rights reserved

If the check box is displayed grayed out, installation is not possible. In this case,
click on the component. In the text box below the components, the reason why
installation is not possible is indicated (e.g., incompatible software).
5. Read and accept the license conditions and security information.
6. Read and accept the security settings. Start the installation.
7. Transfer the license "SIMATIC WinCC Runtime Professional" from the license
data carrier to the OS.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 9
2 Single-User System
2.3 Procedure

2.3.2 Project engineering

Table 2-5
No. Action
1. Open WinCC (TIA Portal) on the programmer and create a new project.
2. Add the OS (IPC547E).
 Siemens AG 2014 All rights reserved

3. Open the Device view of the OS.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 10
2 Single-User System
2.3 Procedure

No. Action
4. Enter the computer name of the OS set under Windows in the "Name" and
"Computer name" fields.
 Siemens AG 2014 All rights reserved

5. Add "WinCC RT Professional" via "Hardware catalog > SIMATIC HMI


Application".

6. Configure WinCC Runtime Professional (screens, runtime settings, etc.).


7. Transfer the project to the OS. To this end, click the "Download to device"
button and navigate to the network folder released for the WinCC projects at
the OS (by default: "WinCCprojects").
If you have problems in loading the OS, please regard the notes in \5\ of the
References.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 11
3 Single-User System With Multiple Monitors
3.1 Task

3 Single-User System With Multiple Monitors


3.1 Task
Overview
Figure 3-1
Operator station (OS) with multiple montiors

Engineering station (ES)

LAN
 Siemens AG 2014 All rights reserved

Process connection

Description
An OS with multiple monitors is used as SCADA system. The OS is connected to
the process (e.g., via Ethernet). The engineering station (ES) is used for project
engineering. ES and OS can also be designed as one system.

3.2 Solution
3.2.1 Functional principle

A single-user system is an independent WinCC system. The engineering and


runtime data are stored locally on the PC.
Single-user systems are usually used close to production. They are suited for
smaller applications or for operator control and monitoring of independent
subprocesses or plant sections.
The screen window technology is suited for operating the single-user system with
multiple monitors. In the project engineering you can define on which monitor a
screen window is displayed during runtime. By using screen windows you can
adapt the project engineering to your requirements. For example, an overview
screen can be displayed on one monitor while on another monitor detail screens
are shown. Or you configure independent screen selections for each monitor so
that every user can freely select which screen is to be displayed on which monitor.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 12
3 Single-User System With Multiple Monitors
3.2 Solution

Project engineering can be performed either directly on the runtime PC or at a


separate ES.
For project engineering, the license "SIMATIC WinCC Professional" is required.
For operation at runtime, the license "SIMATIC WinCC Runtime Professional" is
required. Both licenses are available in different variants, depending on the number
of power tags required in your project. Power tags are tags with process
connection.

Advantages
• Greater clarity
• Easier comparison of different data/trends
• The extended variant of the Industrial Flat Panel allows a distance of up to 30
meters between the OS and the monitor. Thus, you can set up simple
distributed systems cost-effectively.
• Up to 5 monitors can be connected to the SIMATIC IPC547E.

3.2.2 Hardware and software components

Hardware components
Table 3-1
Component No. Article number Note
 Siemens AG 2014 All rights reserved

Programmer, e.g., 1 6ES7716-2CA10-0CD3 Engineering station


SIMATIC FIELD
PG M4
SIMATIC 1 6AG4104-3HA34-4BX0 Operator station
IPC547E 19” rack PC, optionally
available as tower
Flat Panel 5 6AV7863-3TA00-0AA0 Single-touch, alternatively with
SIMATIC IFP1900 glass front (multi-touch
capable)
DisplayPort cable 2 6AV7860-0DH30-0AA0 Industry quality, 3 m
Ethernet cable 1 Specialist retailers For project engineering
transfer from ES to OS

Software components
Table 3-2
Component No. Article number Note
SIMATIC WinCC 1 e.g.: 6AV2103-0DA03-0AA5 For installation on the ES
Professional
SIMATIC WinCC 1 e.g.: 6AV2105-0DA03-0AA0 For installation on the OS
Runtime
Professional

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 13
3 Single-User System With Multiple Monitors
3.3 Procedure

Licenses
Table 3-3
Component No. Article number Note
SIMATIC WinCC 1 License included in "SIMATIC
Professional WinCC Professional" software
SIMATIC WinCC 1 License included in "SIMATIC
Runtime WinCC Runtime Professional"
Professional software

3.3 Procedure
3.3.1 Installation

Table 3-4
No. Action
1. Start the installation setup "SIMATIC WinCC Runtime Professional" at the OS.
2. Select the installation language and read the installation and product information.
3. Select the languages to be installed.
 Siemens AG 2014 All rights reserved

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 14
3 Single-User System With Multiple Monitors
3.3 Procedure

No. Action
4. Select the "SIMATIC WinCC Runtime Professional V13.0" component. The
components "Documentation Viewer", "Microsoft SQL Server 2008 R2 Standard
Edition SP2", and "Automation License Manager" are selected automatically.
 Siemens AG 2014 All rights reserved

If the check box is displayed grayed out, installation is not possible. In this case,
click on the component. In the text box below the components, the reason why
installation is not possible is indicated (e.g., incompatible software).
5. Read and accept the license conditions and security information.
6. Read and accept the security settings. Start the installation.
7. Transfer the license "SIMATIC WinCC Runtime Professional" from the license
data carrier to the OS.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 15
3 Single-User System With Multiple Monitors
3.3 Procedure

3.3.2 Project engineering

Table 3-5
No. Action
1. Open WinCC (TIA Portal) on the programmer and create a new project.
2. Add the OS (IPC547E).
 Siemens AG 2014 All rights reserved

3. Open the Device view of the OS.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 16
3 Single-User System With Multiple Monitors
3.3 Procedure

No. Action
4. Enter the computer name of the OS set under Windows in the "Name" and
"Computer name" fields.
 Siemens AG 2014 All rights reserved

5. Add "WinCC RT Professional" via "Hardware catalog > SIMATIC HMI


Application".

6. Open the "Screens" folder and add a new screen (e.g., Startscreen) via "Add
new screen".
7. For each monitor, add a screen window from the "Controls" object palette to
the screen. Under "Properties > Miscellaneous", assign names to the screen
windows (e.g., Monitor1, Monitor2,...).

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 17
3 Single-User System With Multiple Monitors
3.3 Procedure

No. Action
8. Open "Properties > General" and check the "Independent window" check box.
Select "Maximized" for Position and mode and set the monitor number.

The monitor number must be identical with the one set under Windows. It can
be found at "Start > Control Panel > Appearance and Personalization > Adjust
screen resolution". Click the "Identify" button to display the monitor number on
the respective monitor.
9. Open the Runtime settings. Check the "Hide main window" check box in order
that only the screen windows are shown during runtime.
 Siemens AG 2014 All rights reserved

10. Complete project engineering.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 18
3 Single-User System With Multiple Monitors
3.3 Procedure

No. Action
11. For a screen change, configure the event "ActivateScreenInScreenWindow".
Under "Screen name", enter the name of the screen that contains the screen
windows (e.g., "Startscreen").
Under "Screen window", enter the name of the screen window (e.g.,
"Monitor2").
Under "New screen name", enter the name of the screen that is to be
displayed in the screen window.

12. Transfer the project to the OS. To this end, click the "Download to device"
button and navigate to the network folder released for the WinCC projects at
 Siemens AG 2014 All rights reserved

the OS (by default: "WinCCprojects").


If you have problems in loading the OS, please regard the notes in \5\ of the
References.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 19
4 Multi-User System
4.1 Task

4 Multi-User System
4.1 Task
Overview
Figure 4-1
Clients

HMI network

Server
 Siemens AG 2014 All rights reserved

Process connection

Description
The SCADA system runs on a server. This server is connected to the process
(e.g., via Ethernet). Operation is to be possible from multiple different operator
stations.
This application is suited for small- to medium-sized plants in which operation is
effected from different operator stations, but distribution of the data to multiple
servers is not required.

4.2 Solution
4.2.1 Functional principle

The multi-user system consists of one central server and multiple distributed
clients.
The WinCC server features the process connection and automatically supplies the
WinCC clients with the engineering and process data. All WinCC data (e.g.,
screens, archives) are stored on the WinCC server.
The WinCC clients do not require separate project engineering, but just
configuration with some general settings. For each WinCC client you can
individually define the start screen, runtime language, toolbar, navigation keys,
locking of key combinations, and screen properties.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 20
4 Multi-User System
4.2 Solution

Depending on your requirements, the WinCC clients have either the same or
different tasks. This is configured via different users and their access rights. Thus,
you can allow for different views and operating options for the plant dependent on
the logged-in user. Adding further WinCC clients subsequently is also possible.
Since the WinCC data are stored centrally on the WinCC server, process
specifications or message acknowledgments are consistently provided at all
operator stations. Any operator intervention, e.g., a value change, is immediately
visible at all operator stations.
In the event of a system failure during runtime or when the WinCC server is
terminated, the WinCC clients are not supplied with data. In this case, the missing
connection is indicated by grayed-out fields and a corresponding display in the
controls. Once the WinCC server is available again, the WinCC clients are
reconnected.
A prerequisite for the project engineering of a multi-user system is that the WinCC
server and WinCC clients are interconnected via a network. The WinCC server and
WinCC clients can also be connected via a router.
If you have made changes to the project, you can transfer these without ending the
runtime on the WinCC server. When executing the "Load changes" function, only
the changed or added runtime objects are loaded. During project engineering, a
warning is issued whenever you make changes that do not support the "Load
changes" function.

Advantages
 Siemens AG 2014 All rights reserved

• Low engineering effort


• Low effort in the case of changes
• Cost-efficient solution for SCADA applications of medium complexity
• Expandability to up to 32 WinCC clients
• Increased availability of the WinCC server due to the "Load changes" function

Quantity framework
• Microsoft Windows 7, 3 WinCC clients max.
• Microsoft Windows Server 2008/2012, 32 WinCC clients max.
Regard the specifications in \6\ for the released operating systems.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 21
4 Multi-User System
4.2 Solution

4.2.2 Hardware and software components

Hardware components
Table 4-1
Component No. Article number Note
Programmer, e.g., 1 6ES7716-2CA10-0CD3 Engineering station
SIMATIC FIELD
PG M4
SIMATIC 1 6AG4104-3HA42-0FX0 WinCC server
IPC547E 19” rack PC, optionally
available as tower
SIMATIC 3 6AV7240-0BC05-0KA0 WinCC client
IPC477D Alternatively:
Microbox PC SIMATIC
IPC427D with SIMATIC Flat
Panel IFP1900
SCALANCE 1 6GK5204-2BB10-2AA3
X204-2
Ethernet cable 5 Specialist retailers

Software components
 Siemens AG 2014 All rights reserved

Table 4-2
Component No. Article number Note
SIMATIC WinCC 1 e.g.: 6AV2103-0DA03-0AA5 For installation on the ES
Professional
SIMATIC WinCC 1 e.g.: 6AV2105-0DA03-0AA0 For installation on the OS
Runtime
Professional

Licenses
Table 4-3
Component No. Article number Note
SIMATIC WinCC 1 License included in "SIMATIC
Professional WinCC Professional" software
SIMATIC WinCC 1 License included in "SIMATIC
Runtime WinCC Runtime Professional"
Professional software
SIMATIC WinCC 1 6AV2107-0EB00-0BB0
Server for
Runtime
Professional
SIMATIC WinCC 3 6AV2107-0DB03-0AA0 One license required per
Client for Runtime client
Professional

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 22
4 Multi-User System
4.3 Procedure

4.3 Procedure
4.3.1 Installation

WinCC server

Table 4-4
No. Action
1. Start the installation setup "SIMATIC WinCC Runtime Professional" on the
WinCC server.
2. Select the installation language and read the installation and product information.
3. Select the languages to be installed.
4. Select the "SIMATIC WinCC Runtime Professional V13.0" component. The
components "Documentation Viewer", "Microsoft SQL Server 2008 R2 Standard
Edition SP2", and "Automation License Manager" are selected automatically.
 Siemens AG 2014 All rights reserved

If the check box is displayed grayed out, installation is not possible. In this case,
click on the component. In the text box below the components, the reason why
installation is not possible is indicated (e.g., incompatible software).
5. Read and accept the license conditions and security information.
6. Read and accept the security settings. Start the installation.
7. Transfer the licenses "SIMATIC WinCC Runtime Professional" and "SIMATIC
WinCC Server for Runtime Professional" from the license data carrier to the OS.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 23
4 Multi-User System
4.3 Procedure

WinCC clients
Perform the following steps on every WinCC client:
Table 4-5
No. Action
1. Start the installation setup "SIMATIC WinCC Runtime Professional".
2. Select the installation language.
3. Select the languages to be installed.
4. Deselect the preselected components and select the component "SIMATIC
WinCC Runtime Client V13.0".
The components "Microsoft SQL Server 2008 R2 Express Edition SP2" and
"Automation License Manager" are selected automatically.
 Siemens AG 2014 All rights reserved

5. Read and accept the license conditions and security information.


6. Read and accept the security settings. Start the installation.
7. Transfer the license "SIMATIC WinCC Client for Runtime Professional" from the
license data carrier to the WinCC client.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 24
4 Multi-User System
4.3 Procedure

4.3.2 Project engineering

Table 4-6
No. Action
1. Open WinCC (TIA Portal) on the programmer and create a new project.
2. Add the WinCC server (IPC547E) and WinCC clients (IPC477D).
 Siemens AG 2014 All rights reserved

3. Open the Device view of the WinCC server.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 25
4 Multi-User System
4.3 Procedure

No. Action
4. Enter the computer name of the WinCC server set under Windows in the "Name"
and "Computer name" fields.
 Siemens AG 2014 All rights reserved

5. Add "WinCC RT Professional" via "Hardware catalog > SIMATIC HMI


Application".

6. Open the Device view of the WinCC client.


7. Enter the computer name in the "Name" and "Computer name" fields.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 26
4 Multi-User System
4.3 Procedure

No. Action
8. Add "WinCC Client" via "Hardware catalog > SIMATIC HMI Application".

9. Perform steps 6-8 for the other WinCC clients, too.


10. Change to the Network view and activate the "Relations" field.
Create an HMI relation between the WinCC server and each WinCC client using
drag and drop.
 Siemens AG 2014 All rights reserved

11. Create the users at "IPC 547E > WinCC RT Professional > User administration".
Grant the authorizations to the user groups.
To activate the WinCC project on the WinCC client, the user requires the
authorization "Enable remote control" (number 1000). With this authorization, the
user can remotely activate/deactivate also the runtime on the WinCC server.
12. Complete project engineering of the WinCC server (screens, runtime settings,
etc.).

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 27
4 Multi-User System
4.3 Procedure

No. Action
13. Open the runtime settings of a WinCC client. Define the configuration (e.g., start
screen, services, properties of the runtime window).
Perform these steps for all WinCC clients.
14. Transfer the project to the WinCC server. To this end, click the "Download to
device" button and navigate to the network folder released for the WinCC
projects on the WinCC server (by default: "WinCCprojects").
The configuration of the WinCC clients is also loaded to the WinCC server and
distributed to the WinCC clients at runtime.
If you have problems in loading the WinCC server, please regard the notes in \5\
of the References.

4.3.3 Further settings

Operating system settings


In order that the WinCC client can access the project of the WinCC server, the
following conditions must be met:
• The network must be a home or workplace network
• On both the WinCC server and WinCC client, the same Windows user with the
same password must be logged in
 Siemens AG 2014 All rights reserved

• The password must not be blank


• The Windows user must at least be a main user and a member of the
"SIMATIC HMI" group
• The project must be stored in a folder released in the network (e.g.,
WinCCProjects)

Starting the project


• Starting the project on the WinCC server
Open "Start > All Programs > Siemens Automation > Runtime Systems >
WinCC Runtime Professional > WinCC RT Start". Select the project and
activate runtime.
• Starting the project on the WinCC client
Open "Start > All Programs > Siemens Automation > Runtime Systems >
WinCC Runtime Professional > WinCC RT Start". Navigate to the project folder
on the WinCC server and select the project. Log in with the WinCC user name
and password.
• Activating the project remotely
Open the Simatic Shell on the WinCC client via "Start > Computer". Click on
the WinCC server. Right-click on the project (station name). Click on "Remote
activation". The server project can only be activated remotely from the WinCC
client if it has already been opened on the WinCC server.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 28
5 Redundant Systems
5.1 Task

5 Redundant Systems
5.1 Task
Overview
Figure 5-1

Clients

HMI network

Server Redundant partner

Process connection
 Siemens AG 2014 All rights reserved

Description
The SCADA system runs on a server. To increase plant availability, a second,
redundant server is used. Operation is to be possible from multiple, different
operator stations.
This application is suited for plants in which the downtimes are to be kept as low as
possible.

5.2 Solution
5.2.1 Functional principle

In a multi-user system you can alternatively use a redundant server pair instead of
the server. This means that two interconnected WinCC servers work in parallel,
continuously monitoring each other. In case one WinCC server fails, the connected
WinCC clients are automatically switched to the active server. During a failure, the
active WinCC server archives all messages and process data. After the failed
WinCC server has returned, these are automatically synchronized. In normal
mode, too, data such as internal messages or recipes can be synchronized.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 29
5 Redundant Systems
5.2 Solution

For redundant WinCC servers with multi-user operation, Windows Server 2008 or
Windows Server 2012 must be used. Please regard the released operating system
versions in \6\.
In normal mode, the two redundant WinCC servers work with equal priority. They
can define individually for each WinCC client with which WinCC server it is
preferably connected.

Behavior in the event of a failure


In the runtime settings of the WinCC clients you define with which WinCC server
(master or standby) the respective WinCC client preferably connects. This setting
relates to the redundancy settings in the project, not to the actual server status.

Table 5-1
Description Figure
Server1 is configured as master server,
Server2 as standby server. In the runtime
settings of the WinCC client you define the
"Master" as preferred server.

Server 1 Server 2
(Master) (Standby)
 Siemens AG 2014 All rights reserved

When runtime is activated, the WinCC client


connects with Server1.

Server 1 Server 2
(Master) (Standby)
Status: Master Status: Standby

If Server1 fails, Server2 assumes the


"Master" status. The WinCC client is
automatically connected with Server2.

Server 1 Server 2
(Master) (Standby)
Status: ------ Status: Master

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 30
5 Redundant Systems
5.2 Solution

Description Figure
After Server1 has returned, it is assigned
the "Standby" status, Server2 remains
"Master". The WinCC client nevertheless
reconnects with Server1.

Server 1 Server 2
(Master) (Standby)
Status: Standby Status: Master

Server1 is only reassigned the "Master"


status when Server2 fails.

X
Server 1 Server 2
(Master) (Standby)
Status: Master Status: ------
 Siemens AG 2014 All rights reserved

Advantages
• Automatic switchover if a server or communication to the server fails
• Increased system availability
• Continuous operation and visualization
• Automatic synchronization of all archive and message information in the
background after a failure has been rectified

5.2.2 Hardware and software components

Hardware components
Table 5-2
Component No. Article number Note
Programmer, e.g., 1 6ES7716-2CA10-0CD3 Engineering station
SIMATIC FIELD
PG M4

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 31
5 Redundant Systems
5.2 Solution

Component No. Article number Note


SIMATIC IPC547E 2 6AG4104-3HA42-2FX0 WinCC server
19” rack PC, optionally
available as tower
SIMATIC IPC477D 3 6AV7240-0BC05-0KA0 WinCC client
Alternatively:
Microbox PC SIMATIC
IPC427D with SIMATIC Flat
Panel IFP1900
SCALANCE X206-1 1 6GK5206-1BB10-2AA3
Ethernet cable 6 Specialist retailers

Software components
Table 5-3
Component No. Article number Note
SIMATIC WinCC 1 e.g.: 6AV2103-0DA03- For installation on the ES
Professional 0AA5
SIMATIC WinCC 2 e.g.: 6AV2105-0DA03- For installation on the OS
Runtime 0AA0
Professional
 Siemens AG 2014 All rights reserved

Licenses
Table 5-4
Component No. Article number Note
SIMATIC WinCC 1 License included in "SIMATIC
Professional WinCC Professional" software
SIMATIC WinCC 2 License included in "SIMATIC
Runtime WinCC Runtime Professional"
Professional software
SIMATIC WinCC 3 6AV2107-0DB03-0AA0 One license required per
Client for Runtime WinCC client
Professional
SIMATIC WinCC 1 6AV2107-0FB00-0BB0
Redundancy for
Runtime
Professional
SIMATIC WinCC 2 6AV2107-0EB00-0BB0
Server for Runtime
Professional

Note Please note that the two redundant servers must be structured identically. Install
the same licenses on both servers.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 32
5 Redundant Systems
5.3 Procedure

5.3 Procedure
5.3.1 Installation

WinCC server
Table 5-5
No. Action
1. Start the installation setup "WinCC Runtime Professional" on the WinCC server.
2. Select the installation language and read the installation and product information.
3. Select the languages to be installed.
4. Select the "SIMATIC WinCC Runtime Professional V13.0" component. The
components "Documentation Viewer", "Microsoft SQL Server 2008 R2 Standard
Edition SP2", and "Automation License Manager" are selected automatically.
 Siemens AG 2014 All rights reserved

If the check box is displayed grayed out, installation is not possible. In this case,
click on the component. In the text box below the components, the reason why
installation is not possible is indicated (e.g., incompatible software).
5. Read and accept the license conditions and security information.
6. Read and accept the security settings. Start the installation.
7. Transfer the licenses "SIMATIC WinCC Runtime Professional", "SIMATIC WinCC
Server" and "SIMATIC WinCC Redundancy" from the license data carrier to the
WinCC server.
8. Perform these steps on the second WinCC server.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 33
5 Redundant Systems
5.3 Procedure

WinCC client
Table 5-6
No. Action
1. Start the installation setup "WinCC Runtime Professional".
2. Select the installation language.
3. Select the languages to be installed.
4. Select the "SIMATIC WinCC Runtime Client V13.0" component.
The components "Microsoft SQL Server 2008 R2 Express Edition SP2" and
"Automation License Manager" are selected automatically.
 Siemens AG 2014 All rights reserved

5. Read and accept the license conditions and security information.


6. Read and accept the security settings. Start the installation.
7. Transfer the license "SIMATIC WinCC Client for Runtime Professional" from the
license data carrier to the WinCC client.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 34
5 Redundant Systems
5.3 Procedure

5.3.2 Project engineering

Table 5-7
No. Action
1. Open WinCC (TIA Portal) on the programmer and create a new project.
2. Add a WinCC server (IPC547E) and the WinCC clients (IPC477D).
 Siemens AG 2014 All rights reserved

3. Open the Device view of the WinCC server.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 35
5 Redundant Systems
5.3 Procedure

No. Action
4. Enter the computer name of the WinCC server set under Windows in the "Name"
and "Computer name" fields.
 Siemens AG 2014 All rights reserved

5. Add "WinCC RT Professional" via "Hardware catalog > SIMATIC HMI


Application".

6. Open the Device view of the WinCC client.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 36
5 Redundant Systems
5.3 Procedure

No. Action
7. Enter the computer name of the WinCC client set under Windows in the "Name"
and "Computer name" fields.

8. Add "WinCC Client" via "Hardware catalog > SIMATIC HMI Application".
 Siemens AG 2014 All rights reserved

9. Perform steps 6-8 for the other WinCC clients, too.


10. Change to the Network view and activate the "Relations" field.
Create an HMI relation between the WinCC server and each WinCC client using
drag and drop.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 37
5 Redundant Systems
5.3 Procedure

No. Action
11. Open the runtime settings of the WinCC server. Open the "Redundancy" item.
Check the "Configure redundant servers" check box.
Check the "Default master" check box if this WinCC server is to be used as
default master.
Enter the computer name of the second WinCC server at "Redundant partner".
Separate project engineering of the redundant partner is not required. When
loading the WinCC project, it is automatically transferred to both WinCC servers.
Configure the synchronization settings according to your requirements.
 Siemens AG 2014 All rights reserved

12. Create the users and user groups under "IPC 547E > WinCC RT Professional >
User administration". Grant the authorizations to the user groups.
To activate the WinCC project on the WinCC client, the user requires the
authorization "Enable remote control" (number 1000). With this authorization, the
user can remotely activate/deactivate also the runtime on the WinCC server.
13. Complete project engineering of the WinCC server (screens, runtime settings,
etc.).
14. Open the runtime settings of the WinCC client. Open the "Redundancy" item.
Define whether the WinCC client is to connect preferably with the master or
standby server.

Define the remaining configuration (e.g., start screen, services, properties of the
runtime window).
15. Transfer the project to the WinCC server. To this end, click the "Download to
device" button and navigate to the network folder released for the WinCC
projects on the WinCC server (by default: "WinCCprojects"). Project engineering
is automatically loaded to the redundant partner, too.
If you have problems in loading a WinCC server, please regard the notes in \5\ of
the References.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 38
5 Redundant Systems
5.3 Procedure

Redundancy tags
For the evaluation of the status of the redundant servers, the following system tags
are provided in project engineering:
Table 5-8
Name Description
@RM_MASTER 1 for server = master server
0 for server = standby server
With this tag you can manually define which
server is assigned the "Master" status.
@RM_MASTER_NAME Name of the master server
@RM_SERVER_NAME Name of the server

5.3.3 Further settings

Operating system settings


• On both WinCC servers and the WinCC clients, the same user with the same
password must be used.
• This user must be a member of the "SIMATIC HMI" group and at least have the
rights of the "Main user".
 Siemens AG 2014 All rights reserved

• The network must be a home or workplace network.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 39
6 Web Access
6.1 Task

6 Web Access
6.1 Task
Overview
Figure 6-1

Internet

Operator station (OS)


 Siemens AG 2014 All rights reserved

Process network

Description
The local SCADA system is designed like one of the previously described
scenarios. In addition, the plant is to be monitored through a remote station via the
Intranet or Internet.

6.2 Solution
6.2.1 Functional principle

To operate and monitor a WinCC project via the Intranet/Internet, you use the
WinCC WebNavigator option.
The functionality of WinCC WebNavigator can easily be implemented in an existing
WinCC project. The WebNavigator clients are integrated into the local user
administration. If necessary, the authorizations can be selected in such a way that

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 40
6 Web Access
6.2 Solution

the WebNavigator client can only monitor the WinCC project. On a WebNavigator
client, only those screens are displayed that are released for web access and
published on the WebNavigator server.
To this end, the WinCC WebNavigator server is installed on a WinCC single-user
system or WinCC server. At the operator stations, WinCC WebNavigator Client is
installed. They can access the project via the Internet Explorer or WinCCViewer
RT.
Access can also be gained via terminal services so that no WinCC installation is
required at the operator stations. Further information on this topic is available in \4\.
Licensing takes place on the WebNavigator server. There, the maximum number of
WebNavigator clients connected simultaneously is licensed. For that, only the
number of WebNavigator clients currently connected simultaneously is evaluated. It
is possible to access a WebNavigator server successively with any number of
different WebNavigator clients. The WebNavigator clients do not need separate
licenses.
Additionally, you can use a WebNavigator diagnostics client. In this process, no
additional WebNavigator server license is occupied. Licensing takes place on the
web diagnostics client. Thus, you can always access the WebNavigator server,
even if the licensed number of WebNavigator clients has already been reached.
This process is recommended if you want to access several different WinCC
systems or WebNavigator servers.
To ensure a higher degree of security, protect the system with a firewall. By using
the WinCCViewer RT, you can prevent the user from accessing the Internet and
 Siemens AG 2014 All rights reserved

protect the system better against viruses and trojans. By separating the WinCC
server and WebNavigator server, you can additionally increase security and at the
same time achieve higher plant availability.

Advantages
• Operator control and monitoring over great distances
• Fast update rate due to event-driven communication
• Increased security and availability due to separation of WinCC server and web
server
• Granting of access rights with plant-wide user administration

6.2.2 Hardware and software components

Hardware components
Table 6-1
Component No. Article number Note
Programmer, e.g., 1 6ES7716-2CA10-0CD3 Engineering station
SIMATIC FIELD
PG M4
SIMATIC 1 6AG4104-3HA34-0BX0 WinCC WebNavigator server
IPC547E 19” rack PC, optionally
available as tower
SIMATIC 1 6AV7881-3AA00-2DA0 WinCC WebNavigator client
IPC277D

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 41
6 Web Access
6.2 Solution

Software components
Table 6-2
Component No. Article number Note
SIMATIC WinCC 1 e.g.: 6AV2103-0DA03-0AA5 For installation on the ES
Professional
SIMATIC WinCC 1 e.g.: 6AV2105-0DA03-0AA0 For installation on the OS
Runtime
Professional

Licenses
Table 6-3
Component No. Article number Note
SIMATIC WinCC 1 License included in "SIMATIC
Professional WinCC Professional" software
SIMATIC WinCC 1 License included in "SIMATIC
Runtime WinCC Runtime Professional"
Professional software
SIMATIC WinCC 1 e.g.: 6AV2107-0KD00-0BB0 License dependent on number
WebNavigator of connected clients (see
Functional principle)
Alternatively, 1 6AV2107-0KT00-0BB0
 Siemens AG 2014 All rights reserved

WinCC
WebDiagnostics
Client

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 42
6 Web Access
6.3 Procedure

6.3 Procedure
6.3.1 Installation

WebNavigator server
Table 6-4
No. Action
1. Windows 7
Open the control panel via "Start > Control Panel".
Click on the "Programs" category or the "Programs and Features" setting.
Click on "Turn Windows features on or off".
Activate the components stated under 2.

Windows Server 2008


In the Server Manager, Roles Summary, click on "Add roles".
Select the "Web server (IIS)" entry under "Server Roles".
Select the components stated under 2. under "Role Services".
2. • Web Management Tools:
IIS Management Service, IIS Management Console, IIS Management
Scripts and Tools, IIS Metabase and IIS 6 configuration compatibility,
IIS 6 WMI Compatibility
 Siemens AG 2014 All rights reserved

• World Wide Web Services > Common HTTP Features:


Default Document, Static Content

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 43
6 Web Access
6.3 Procedure

No. Action
• World Wide Web Services > Application Development Features:
ASP, ISAPI Extensions, ISAPI Filters

• World Wide Web Services > Security


Request Filtering, Basic Authentication
 Siemens AG 2014 All rights reserved

3. Start the installation setup "WinCC Runtime Professional" on the WebNavigator


server.
4. Select the installation language and read the installation and product information.
5. Select the "Modify/Upgrade" option.
6. Select the languages to be installed.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 44
6 Web Access
6.3 Procedure

No. Action
7. Select the "Web Navigator Server" component in addition to the preselected
components. Do not deselect the preselected components as they would then be
uninstalled.
 Siemens AG 2014 All rights reserved

If the check box is displayed grayed out, installation is not possible. In this case,
click on the component. In the text box below the components, the reason why
installation is not possible is displayed (e.g., IIS services not activated).
8. Read and accept the license conditions and security information.
9. Read and accept the security settings. Start the installation.
10. Transfer the license "SIMATIC WinCC WebNavigator" from the license data
carrier to the WebNavigator server.

WebNavigator client / web diagnostics client


You can install the WebNavigator client either via the WinCC Runtime Professional
installation medium or via the Intranet/Internet. The web diagnostics client is
installed via the WinCC Runtime Professional installation medium.
Regardless of the setup type, if you want to establish the connection to the
WebNavigator server via the Internet Explorer, you have to adapt some settings in
the Internet Explorer.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 45
6 Web Access
6.3 Procedure

Adapting settings in the Internet Explorer


Table 6-5
No. Action
1. Start the Internet Explorer. Click on "Tools > Internet Options".
 Siemens AG 2014 All rights reserved

2. Change to the "Security" tab and select the relevant zone, e.g., "Local intranet".
Click the "Custom level..." button.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 46
6 Web Access
6.3 Procedure

No. Action
3. Enable the options "Script ActiveX controls marked safe for scripting", "Download
signed ActiveX controls", and "Active scripting".

Save the settings with "OK" and confirm the subsequent dialog.
4. Click on the "Trusted sites" zone and click the "Sites" button.
 Siemens AG 2014 All rights reserved

5. Enter the address of the WebNavigator server, uncheck the "Require server
verification (https:) for all sites in this zone" check box, and click on "Add".

Close the dialog.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 47
6 Web Access
6.3 Procedure

No. Action
6. Click on "Custom level..." and enable "Initialize and script ActiveX controls not
marked as safe for scripting".
 Siemens AG 2014 All rights reserved

Save the settings with "OK" and confirm the subsequent dialog.
7. Change to the "General" tab. Click the "Settings" button under Browsing history.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 48
6 Web Access
6.3 Procedure

No. Action
8. Under "Check for newer versions of stored pages", select the "Automatically"
option.

Close all opened dialogs.

Installation via the Intranet/Internet


Table 6-6
No. Action
1. To install the WebNavigator client via the Intranet/Internet, the WebNavigator
server must already be active. First follow the instructions in section 6.3.2 Project
engineering and then install the WebNavigator client.
 Siemens AG 2014 All rights reserved

2. Open the Internet Explorer and enter the address of the WebNavigator server.
3. Enter the user name and password of the web user.
4. Click the "Click here to install" link.

Click the "Save" button and select a storage location for the installation file.
5. Navigate to the installation file in the Windows Explorer and start setup with a
double-click.
6. Click the "Next" button.
7. Read and accept the license conditions and security information.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 49
6 Web Access
6.3 Procedure

No. Action
8. Select the desired setup type.
 Siemens AG 2014 All rights reserved

9. Select the language to be installed.


10. Check the settings and click the "Install" button to start installation.

Installation via the WinCC Runtime Professional installation medium


Table 6-7
No. Action
1. Start the installation setup "WinCC Runtime Professional" on the WebNavigator
client.
2. Select the installation language and read the installation and product information.
3. Select the languages to be installed.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 50
6 Web Access
6.3 Procedure

No. Action
4. Select the "Web Navigator Client" or "Diagnostics Client" component.
 Siemens AG 2014 All rights reserved

5. Read and accept the license conditions and security information.


6. Read and accept the security settings. Start the installation.
7. If required, transfer the license "WinCC WebDiagnostics Client" from the license
data carrier to the WebDiagnostics client.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 51
6 Web Access
6.3 Procedure

6.3.2 Project engineering

Table 6-8
No. Action
1. Open an existing WinCC (TIA Portal) project on the programmer or create a new
project as described in the previous chapters.
2. Right-click on a screen that you want to release for web access and select "Web
access" in the context menu.
 Siemens AG 2014 All rights reserved

You can also release all screens for web access. To this end, right-click to open
the context menu of the "Screens" folder and then click on "Web access for all".
3. Open the runtime settings of the WebNavigator server and configure the runtime
behavior under "Web access".

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 52
6 Web Access
6.3 Procedure

No. Action
4. Open the User administration and create the web users.
Set the web start screen and web language for the respective users.

5. Assign the authorization "Web access – View only" (number 1002) if the web
user must not operate the runtime project.
6. Transfer the project to the WebNavigator server. To this end, click the "Download
to device" button and navigate to the released network folder on the
WebNavigator server.
If you have problems in loading a WebNavigator server, please regard the notes
in \5\ of the References.
7. Start the WinCC WebConfigurator on the WebNavigator server via "Start > All
Programs > Siemens Automation > Options and Tools > HMI Tools > WinCC
WebConfigurator".
8. Decide whether you want to add a new default web page or virtual directory to an
 Siemens AG 2014 All rights reserved

existing web site.


9. Assign a name to the web site. Define the port and IP address of the web site. If
the WebNavigator server is to be available via the Intranet and Internet, select
"All not assigned".
Select the default web page.
Define the time after which the WebNavigator client tries to reestablish the
connection to the WebNavigator server in case of a connection failure.

Click on "Next" if you have a firewall installed. Click on "Finish" and skip step 10 if
you have no firewall installed.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 53
6 Web Access
6.3 Procedure

No. Action
10. Click the "Windows Firewall" button. Click on "Allow a program or feature through
Windows Firewall". Click the "Change settings" button. Enable "Secure World
Wide Web Services (HTTPS)" and "World Wide Web Services (HTTP)". Close
the Windows dialogs.
Click on "Finish" in the WinCC Web Configurator.
11. Restart the WebNavigator server.
12. Start the runtime of the WinCC project.

6.3.3 Working with the WebNavigator components

WinCCViewer RT

Table 6-9
No. Action
1. Start the WinCC Viewer RT via "Start > All Programs > Siemens Automation >
Options and Tools > HMI Tools > WinCCViewer RT".
2. Enter the address of the WebNavigator server at "Address" in the format
"http://IPaddress:port" or "http://servername". If you use the default port 80, this is
not necessary. Enter the web user's data at "Username" and "Password".
 Siemens AG 2014 All rights reserved

3. Define the other settings for the WebNavigator client, e.g., screen attributes, on
the "Parameters", "Graphics Runtime", and "Runtime" tabs.
4. Click on "OK" to apply the settings. The connection to the WebNavigator server is
established.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 54
6 Web Access
6.3 Procedure

No. Action
5. To change settings later, enter the hotkeys defined for the Property sheet on the
"Parameters" tab.
 Siemens AG 2014 All rights reserved

Internet Explorer

Table 6-10
No. Action
1. Open the Internet Explorer. Enter the address of the WebNavigator server in the
address line of the Internet Explorer in the format "http://IPaddress:port" or
"http://servername". If you use the default port 80, this is not necessary.
2. Enter the user name and password of the web user.
3. The connection to the WebNavigator server is established.
4. To change the WebClient's properties or to load plugins, enter
"http://servername/maincontrol.asp" in the address line of the Internet Explorer.
5. Open the Web Navigator user interface by moving the mouse pointer over the
bar highlighted in blue to the left of the Internet Explorer. Fix the Web Navigator
user interface by clicking on the respective symbol.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 55
6 Web Access
6.3 Procedure

No. Action
6. Change the settings according to your requirements.
 Siemens AG 2014 All rights reserved

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 56
7 Access Through Office PCs
7.1 Task

7 Access Through Office PCs


7.1 Task
Overview
Figure 7-1

Office-PC

Office network

Operator Station (OS)


 Siemens AG 2014 All rights reserved

Process network

Description
The local SCADA system is designed like one of the previously described
scenarios. Additionally, one or several office PC(s) is/are to generate, display, and
analyze process states, statistics, or reports.

7.2 Solution
7.2.1 Functional principle

The WinCC DataMonitor option serves for the display, analysis, evaluation, and
distribution of current and historical process data and messages. You can simply
expand an existing WinCC Runtime Professional system by the WinCC
DataMonitor function.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 57
7 Access Through Office PCs
7.2 Solution

With the WinCCViewer RT, you can monitor the WinCC project via the
Internet/Intranet. By using these so-called "View Only Clients", you increase the
protection of plant and personnel, as unwanted remote process intervention is
prevented.
Moreover, it is possible to monitor process data or screens via customer-
configurable web pages, without the need for installation on the client PC.
The Microsoft Excel add-ins "Excel Workbook Wizard" and "Excel Workbook"
facilitate the evaluation of, for example, production data, as the data are
automatically stored in a Microsoft Excel workbook according to your requirements
and are thus available for further processing.
Furthermore, you can create time- or event-controlled reports. These can be
printed, saved in PDF format, or sent by e-mail to selected recipients.
Licensing takes place on the DataMonitor server. There, the maximum number of
clients connected simultaneously is licensed. The clients are subdivided into two
groups according to their function:
• Webcenter function group: Trends & Alarms, Webcenter, and Reports
• DataMonitor function group: WinCCViewerRT and Excel Workbooks
The table below shows how many clients can be used simultaneously dependent
on the function group and number of licenses.
Table 7-1
License Webcenter function group DataMonitor function
 Siemens AG 2014 All rights reserved

group
1 client 1 3
3 clients 3 6
10 clients 10 20
25 clients 25 50
50 clients 50 100
If you use the DataMonitor function group, log off from the Internet Explorer via the
"Logout" button. If you close the Internet Explorer with the "Close" button, the
license will only be released again after 20 minutes.
On the start page of the DataMonitor server, you can use the "?" button to display
how many licenses of the DataMonitor function group are available at the
maximum and how many are currently in use.

Advantages
• No additional engineering effort, as screens from the WinCC project are used
directly
• Evaluation via centrally administrated templates for detailed analyses of the
company processes, e.g., reports, statistics
• Information from the process can be compiled individually online at runtime
and sent by e-mail to various persons
• User administration with user groups and individual access rights, e.g., to read,
write, and create WebCenter pages

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 58
7 Access Through Office PCs
7.2 Solution

7.2.2 Hardware and software components

Hardware components
Table 7-2
Component No. Article number Note
Programmer, e.g., 1 6ES7716-2CA10-0CD3 Engineering station
SIMATIC FIELD
PG M4
SIMATIC 1 6AG4104-3HA34-0BX0 WinCC DataMonitor server
IPC547E 19” rack PC, optionally
available as tower
SIMATIC 1 6AV7881-3AA00-2DA0 WinCC DataMonitor client
IPC277D

Software components
Table 7-3
Component No. Article number Note
SIMATIC WinCC 1 e.g.: 6AV2103-0DA03-0AA5 For installation on the ES
Professional
 Siemens AG 2014 All rights reserved

SIMATIC WinCC 1 e.g.: 6AV2105-0DA03-0AA0 For installation on the OS


Runtime
Professional

Licenses
Table 7-4
Component No. Article number Note
SIMATIC WinCC 1 License included in "SIMATIC
Professional WinCC Professional" software
SIMATIC WinCC 1 License included in "SIMATIC
Runtime WinCC Runtime Professional"
Professional software
SIMATIC WinCC 1 e.g.: 6AV2107-0LD00-0BB0 License dependent on number
DataMonitor of connected clients (see
Functional principle)

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 59
7 Access Through Office PCs
7.3 Procedure

7.3 Procedure
7.3.1 Installation

DataMonitor server
Table 7-5
No. Action
1. Windows 7
Open the control panel via "Start > Control Panel".
Click on the "Programs" category or the "Programs and Features" setting.
Click on "Turn Windows features on or off".
Activate the components stated under 2.

Windows Server 2008


In the Server Manager, Roles Summary, click on "Add roles".
Select the "Web server (IIS)" entry under "Server Roles".
Select the components stated under 2. under "Role Services".
2. • Web Management Tools:
IIS Management Service, IIS Management Console, IIS Management
Scripts and Tools, IIS Metabase and IIS 6 configuration compatibility,
IIS 6 WMI Compatibility
• World Wide Web Services > Common HTTP Features:
Default Document, Static Content
 Siemens AG 2014 All rights reserved

• World Wide Web Services > Application Development Features:


.NET Extensibility, ASP, ASP.NET, ISAPI Extensions, ISAPI Filters
• World Wide Web Services > Security
Request Filtering, Basic Authentication,
Windows Authentication
3. Start the installation setup "WinCC Runtime Professional" on the DataMonitor
server.
4. Select the installation language and read the installation and product information.
5. Select the "Modify/Upgrade" option.
6. Select the languages to be installed.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 60
7 Access Through Office PCs
7.3 Procedure

No. Action
7. Select the "Data Monitor Server" component in addition to the preselected
components. The components "Web Navigator Server" and "Data Monitor Client"
are selected automatically. Do not deselect the preselected components as they
would then be uninstalled.
If required, select the components "Excel WorkBook Wizard" or "Excel
WorkBook".
 Siemens AG 2014 All rights reserved

If the check box is displayed grayed out, installation is not possible. In this case,
click on the component. In the text box below the components, the reason why
installation is not possible is displayed (e.g., IIS services not activated).
8. Read and accept the license conditions and security information.
9. Read and accept the security settings. Start the installation.
10. Transfer the license "SIMATIC WinCC DataMonitor" from the license data carrier
to the DataMonitor server.

DataMonitor client
To use the "Webcenter" and "Trends & Alarms" functions, no installation on the
DataMonitor client is required. To use the "WinCCViewer RT", "Reports", or "Excel
Workbooks", installation is required. You can install the DataMonitor client either
via the WinCC Runtime Professional installation medium or via the
Intranet/Internet.
Regardless of the setup type, if you want to establish the connection to the
DataMonitor server via the Internet Explorer, you have to adapt some settings in
the Internet Explorer.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 61
7 Access Through Office PCs
7.3 Procedure

Adapting settings in the Internet Explorer


Table 7-6
No. Action
1. Start the Internet Explorer. Click on "Tools > Internet Options".
 Siemens AG 2014 All rights reserved

2. Change to the "Security" tab and select the relevant zone, e.g., "Local intranet".
Click the "Custom level..." button.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 62
7 Access Through Office PCs
7.3 Procedure

No. Action
3. Enable the options "Script ActiveX controls marked safe for scripting", "Download
signed ActiveX controls", and "Active scripting".

Save the settings with "OK" and confirm the subsequent dialog.
4. Click on the "Trusted sites" zone and then click the "Sites" button.
 Siemens AG 2014 All rights reserved

5. Enter the address of the DataMonitor server, uncheck the "Require server
verification (https:) for all sites in this zone" check box, and click on "Add".

Close the dialog.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 63
7 Access Through Office PCs
7.3 Procedure

No. Action
6. Click on "Custom level..." and enable "Initialize and script ActiveX controls not
marked as safe for scripting".
 Siemens AG 2014 All rights reserved

Save the settings with "OK" and confirm the subsequent dialog.

Installation via the Intranet/Internet


Table 7-7
No. Action
1. To install the DataMonitor client via the Intranet/Internet, the DataMonitor server
must already be active. First follow the instructions in section 7.3.2 Project
engineering and then install the DataMonitor client.
2. Open the Internet Explorer and enter the address of the DataMonitor server.
3. Enter the login information of a Windows user of the DataMonitor server with the
rights "SIMATIC Report User" or "SIMATIC Report Administrators".

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 64
7 Access Through Office PCs
7.3 Procedure

No. Action
4. Open the "Reports > SW Download" site. Next to the relevant component (e.g.,
Datamonitor Client Setup), click on the symbol in the "Install" column and save
the setup file.
 Siemens AG 2014 All rights reserved

To install the "Excel Workbook" or "Excel Workbook Wizard" components,


Microsoft Excel 2007 or higher is required.
5. Navigate to the installation file in the Windows Explorer and start setup with a
double-click.
6. Read and accept the license conditions and security information.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 65
7 Access Through Office PCs
7.3 Procedure

No. Action
7. Select the desired setup type.

8. Select the language to be installed.


9. Check the settings and click the "Install" button to start installation.

Installation via the WinCC Runtime Professional installation medium


 Siemens AG 2014 All rights reserved

Table 7-8
No. Action
1. Start the installation setup "WinCC Runtime Professional" on the DataMonitor
client.
2. Select the installation language and read the installation and product information.
3. Select the languages to be installed.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 66
7 Access Through Office PCs
7.3 Procedure

No. Action
4. Deselect the preselected components and select the "Data Monitor Client"
component. If required, select the components "Excel WorkBook Wizard" or
"Excel WorkBook". To install these components, Microsoft Excel 2007 or higher
is required.
 Siemens AG 2014 All rights reserved

5. Read and accept the license conditions and security information.


6. Start the installation.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 67
7 Access Through Office PCs
7.3 Procedure

7.3.2 Project engineering

Table 7-9
No. Action
1. Open an existing WinCC (TIA Portal) project on the programmer or create a new
project as described in the previous chapters.
2. Right-click on a screen that you want to release for web access and select "Web
access" in the context menu.
 Siemens AG 2014 All rights reserved

You can also release all screens for web access. To this end, right-click to open
the context menu of the "Screens" folder and then click on "Web access for all".
3. Open the runtime settings of the DataMonitor server and configure the runtime
behavior under "Web access".

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 68
7 Access Through Office PCs
7.3 Procedure

No. Action
4. Open the User administration and create the DataMonitor client users.
Set the web start screen and web language for the respective users.

5. Assign the authorization "Web access – View only" (number 1002). The
DataMonitor client is always a so-called "View Only Client".
6. Transfer the project to the DataMonitor server. To this end, click the "Download
to device" button and navigate to the released network folder on the DataMonitor
server.
If you have problems in loading the DataMonitor server, please regard the notes
in \5\ of the References.
7. Start the WinCC Web Configurator on the DataMonitor server via "Start > All
Programs > Siemens Automation > Options and Tools > HMI Tools > WinCC
WebConfigurator".
8. Decide whether you want to add a new default web page or virtual directory to an
existing web site.
 Siemens AG 2014 All rights reserved

9. Assign a name to the web site. Define the port and IP address of the web site. If
the DataMonitor server is to be available via the Intranet and Internet, select "All
not assigned".
Define the time after which the DataMonitor client tries to reestablish the
connection to the DataMonitor server in case of a connection failure.

Click on "Next" if you have a firewall installed. Click on "Finish" and skip step 10 if
you have no firewall installed.
10. Click the "Windows Firewall" button. Click on "Allow a program or feature through
Windows Firewall". Click the "Change settings" button. Enable "Secure World
Wide Web Services (HTTPS)" and "World Wide Web Services (HTTP)". Close
the Windows dialogs.
Click on "Finish" in the WinCC Web Configurator.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 69
7 Access Through Office PCs
7.3 Procedure

No. Action
11. Open the Computer Management. To this end, open the start menu and right-
click on "Computer". Click on "Manage" in the context menu.

12. Open "Local Users and Groups > Users". Add new "ReportUser" and
"ReportAdmin" users. Create the passwords for these users.
13. Right-click on a user and select "Properties".

14. Change to the "Member Of" tab and add the user group "SIMATIC Report
Administrators" or "SIMATIC Report Users" and the user group "SIMATIC HMI
VIEWER" via the "Add" button.
 Siemens AG 2014 All rights reserved

15. Restart the DataMonitor server.


16. Start the runtime of the WinCC project.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 70
7 Access Through Office PCs
7.3 Procedure

7.3.3 Working with the DataMonitor components

WinCCViewer RT
With the WinCCViewer RT you can monitor the WinCC screens released for web
access on a DataMonitor client. Process-relevant operator interventions are not
possible. Other operator interventions such as screen changes are possible from
the DataMonitor client.

Table 7-10
No. Action
1. Start the WinCC Viewer RT via "Start > All Programs > Siemens Automation >
Options and Tools > HMI Tools > WinCCViewerRT".
2. Enter the address of the DataMonitor server at "Address" in the format
"http://IPaddress:port" or "http://servername". If you use the default port 80, this is
not necessary. At "Username" and "Password", enter the user data of the WinCC
user with the authorization 1002.
 Siemens AG 2014 All rights reserved

3. Define the other settings for the DataMonitor client, e.g., screen attributes, on the
"Parameters", "Graphics Runtime", and "Runtime" tabs.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 71
7 Access Through Office PCs
7.3 Procedure

No. Action
4. To change settings later, enter a hotkey for the Property sheet on the
"Parameters" tab.
By default, the hotkey "Ctrl + Alt + P" is used.
 Siemens AG 2014 All rights reserved

5. Click on "OK" to apply the settings. The connection to the DataMonitor server is
established.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 72
7 Access Through Office PCs
7.3 Procedure

Administration
To work with the DataMonitor web page, some administrative settings are required.
Table 7-11
No. Action
1. Open the web page of the DataMonitor server. Log in with the "ReportAdmin"
Windows user. Open the "Administration" page.
2. On the "Connection administration" page, you create new connections or edit
existing connections. These connections are required for the "Webcenter" and
"Trends & Alarms" functions.
 Siemens AG 2014 All rights reserved

Select "New connection".


Enter the name for the connection. Enter the user name and password of the
Windows user on the DataMonitor server.
Enter the computer name and database or search for them using the "Find"
button. Check the "Automatic adaptation of the RT database" check box in order
that the database is adapted automatically in the event of a segment change.
Select the language.
Click the "Create" button.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 73
7 Access Through Office PCs
7.3 Procedure

No. Action
3. On the "Folder administration" page, new folders are created. Thus, the contents
on the DataMonitor server can be sorted better and the access rights can be
assigned.
To create a new folder, enter a name in the "Folder name" field and click the
"Create" button.

The "User administration" page is opened automatically. Define which Windows


user rights are required in order that the user can read, edit, or create the files in
 Siemens AG 2014 All rights reserved

this folder.
4. On the "Archive management" page, swapped-out archive segments can be
connected. For that, the directory must be released on the DataMonitor server.
Select the directory and assign a name. If necessary, check "Automatically
connect all archives in this directory".
If this option is not checked, connect the archives manually in the relevant
directory on the "Connect/Disconnect Archive" page.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 74
7 Access Through Office PCs
7.3 Procedure

No. Action
5. On the "Picture management" page, you can configure the process pictures for
static use in web parts.

The pictures released for web access are displayed on this page. By checking
the relevant check box, the respective picture is released for use in the web
parts. If necessary, you can define a picture detail to be displayed via the
columns "X-position", "Y-position", "Height", and "Width". In the "Language"
column you define the language in which the process graphic is displayed.
In the "Update cycle" field below the table you define in which intervals the
process graphic is refreshed. To display the last update time, check the "Time
stamp" check box.
 Siemens AG 2014 All rights reserved

Excel workbooks and reports


With the Excel Workbook Wizard, you can configure and publish Excel workbooks.
These workbooks can be used either for creating reports or for online monitoring of
process data using Excel Workbook.

Creating and publishing Excel workbooks


Table 7-12
No. Action
1. Open a blank Excel workbook. In the menu, select "AddIns > DataMonitor >
Excel Workbook Wizard...".
2. Decide whether you want to edit the current, another opened, or a new
workbook.
3. The WinCC data can be connected with Excel in different ways.
3a If you execute the Excel Workbook Wizard directly on the DataMonitor server,
the data from the WinCC project are applied automatically.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 75
7 Access Through Office PCs
7.3 Procedure

No. Action
3b If you execute the Excel Workbook Wizard on a different PC, you can establish a
connection to the DataMonitor server.
To this end, check "Establish connection to WinCC Server" and click the "Next"
button.
 Siemens AG 2014 All rights reserved

Enter the address of the DataMonitor server in the "WinCC Server" field and click
the "Connect" button. Enter the user data of the WinCC user.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 76
7 Access Through Office PCs
7.3 Procedure

No. Action
3c If you execute the Excel Workbook Wizard on a different PC not connected with
the DataMonitor server, you can load a configuration file.
Start the "WinCC DataMonitor Configurator Export" on the DataMonitor server via
"Start > All Programs > Siemens Automation > Options and Tools > HMI Tools".
Decide which tags are to be exported. Decide whether archives and messages
are to be exported. Define a path for the XML file and click the "Export" button.
Copy the XML file to the PC with which you execute the Excel Workbook Wizard.
Check the "Download configuration data from file" check box and click on "Next".

Select the XML file and click on "Next".


 Siemens AG 2014 All rights reserved

4. Click on the symbol next to "Tag tree".

Select the desired tag and drag and drop it in a cell of the Excel table.
Close the "Tag Management" window.
In the Excel table, "OV" for online variable is entered in the respective cells. The
tag name is displayed in the comment.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 77
7 Access Through Office PCs
7.3 Procedure

No. Action
5. Double-click on a tag in the Excel Workbook Wizard to adapt settings such as the
update cycle.
 Siemens AG 2014 All rights reserved

6. Click the "Next" button and execute steps 4 and 5 for the archive tags.
In the Excel table, "AV" for archive variable is entered in the respective cells. The
tag name is displayed in the comment.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 78
7 Access Through Office PCs
7.3 Procedure

No. Action
7. Click the "Next" button and click on the symbol next to "Add alarm".
Adapt the settings (e.g., filter conditions) according to your requirements.
 Siemens AG 2014 All rights reserved

8. Click the "Next" button. If necessary, check the "Files are automatically updated
when opening a workbook" check box.

9. If you work directly on the DataMonitor server, you can publish the Excel
workbook directly using the "Publish" button or provide it as a template using the
"Template" button.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 79
7 Access Through Office PCs
7.3 Procedure

No. Action
10. If you do not work directly on the DataMonitor server, open the DataMonitor web
page in the Internet Explorer. Log in with the "ReportAdmin" Windows user.
Change to the "Reports > Upload Templates" tab. Upload the Excel workbook as
report tool or template.
 Siemens AG 2014 All rights reserved

Displaying process data with Excel Workbook


Table 7-13
No. Action
1. Open the web page of the DataMonitor server in the Internet Explorer. Log in
with the "ReportUser" or "ReportAdmin" Windows user.
2. Open the "Reports > Report tools" page.
Click on the Excel icon next to the table that you want to open.

3. Select whether the table is to be opened or saved.


4. In the menu bar, open "AddIns > DataMonitor > Excel Workbook".

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 80
7 Access Through Office PCs
7.3 Procedure

No. Action
5. At "WinCC Server", the server used in the Excel workbook is entered
automatically.
If the data of several WinCC servers are to be read, check the "all server" check
box.
6. Click the "Connect" button. In the subsequent dialog, enter the user data of the
WinCC user.
7. Check the "Read cyclic" check box if the tag values are to be updated cyclically.
Click the "Read tags", "Read archives", or "Read alarms" button.
 Siemens AG 2014 All rights reserved

Creating reports
Table 7-14
No. Action
1. Enable the "Scheduled print jobs in runtime" service in the WinCC (TIA Portal)
project in the runtime settings of the DataMonitor server. Transfer the project to
the DataMonitor server.

2. Open the DataMonitor web page in the Internet Explorer. Open the "Reports >
Settings" page. Log in with the "ReportAdmin" Windows user.
3. Select a printer. Check "Enable API print" to create reports in PDF format.
4. If necessary, define the settings for e-mail sending.
5. Click on the floppy disk icon to save the settings.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 81
7 Access Through Office PCs
7.3 Procedure

No. Action
6. To create a report from an Excel workbook, open the "Reports > Excel
Workbooks" page. In the top window area you see the reports already created
for Excel workbooks. These are subdivided into time- and event-controlled
reports.

To create a new report, select an existing Excel workbook. Define in which


directory the report is stored. If necessary, enter the e-mail recipients for the
report.
 Siemens AG 2014 All rights reserved

Define the conditions for the time- or event-controlled report dependent on the
requirements and create it using the respective "Add" button.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 82
7 Access Through Office PCs
7.3 Procedure

No. Action
7. To create a report from a print job, open the "Reports > Print jobs" page. In the
top window area you see the reports already created for print jobs. These are
subdivided into time- and event-controlled reports.

To create a new report, select an existing print job. Define in which directory the
report is stored. If necessary, enter the e-mail recipients for the report.
 Siemens AG 2014 All rights reserved

Define the conditions for the time- or event-controlled report dependent on the
requirements and create it using the respective "Add" button.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 83
7 Access Through Office PCs
7.3 Procedure

No. Action
8. The published reports are shown on the "Reports > Published Reports" page.
Depending on the User administration (see Webcenter section), the reports
published in the respective directories are shown here.
 Siemens AG 2014 All rights reserved

Webcenter, Trends & Alarms


In the Webcenter, you can compile and display customized web part pages.

Table 7-15
No. Action
1. Open the DataMonitor web page in the Internet Explorer. To create pages, log in
with the "ReportUser" or "ReportAdmin" Windows user. To create customized
layouts, log in with the "ReportAdmin" Windows user.
2. Open the "Webcenter > Configuration > Create layout" page.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 84
7 Access Through Office PCs
7.3 Procedure

No. Action
3. Enter the number of columns and rows as well as a name for the layout and click
on "Continue".

4. Click on the arrows to merge neighboring cells and click on "Continue".


 Siemens AG 2014 All rights reserved

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 85
7 Access Through Office PCs
7.3 Procedure

No. Action
5. Click on the relevant symbol to set for the cells whether the web parts are to be
arranged horizontally or vertically. Click the "Save" button.
 Siemens AG 2014 All rights reserved

6. Open the "Webcenter > Configuration > Create page" page.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 86
7 Access Through Office PCs
7.3 Procedure

No. Action
7. Select the desired layout. Enter a name for the page in the "Webcenter page"
field and select the directory in which the page is to be stored.
 Siemens AG 2014 All rights reserved

8. Open the "Webcenter > Pages" page. Open the directory in which you created
the page. Click on the name of the page.

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 87
7 Access Through Office PCs
7.3 Procedure

No. Action
9. Click the "+" button to add new web parts to the page.
 Siemens AG 2014 All rights reserved

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 88
7 Access Through Office PCs
7.3 Procedure

No. Action
10. Select the web parts and the cell in which the web parts are to be displayed and
click the "Add" button. The assignment of the code designations (e.g.,
"WPZ_03_01", see figure) to the cells is indicated in the bottom part of the
window.
 Siemens AG 2014 All rights reserved

11. Click on the "Edit web part properties" symbol.

12. Define the properties of the web part and save the settings with "OK".
13. You can also use the preconfigured pages "Process value table", "Trend
(process values)", "Alarm table", "Hit list of alarms", and "Statistics functions for
process values". These are available at "Trends & Alarms".

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 89
8 References

8 References
Table 8-1
Title Link
\1\ Siemens Industry Online Support http://support.automation.siemens.com
\2\ Download page of the entry http://support.automation.siemens.com/W
W/view/de/87054082

\3\ WinCC Professional V13.0 Manual http://support.automation.siemens.com/W


W/view/en/92323076
\4\ Decentralized Operation of SIMATIC http://support.automation.siemens.com/W
WinCC with Industrial Thin Clients W/view/en/28309119

\5\ What should you watch out for when http://support.automation.siemens.com/W


downloading WinCC Runtime W/view/en/88780011
Professional from the Engineering Station
to the Operator Station?
\6\ Compatibility Tool http://www.siemens.com/kompatool

9 History
 Siemens AG 2014 All rights reserved

Table 9-1
Version Date Modifications
V1.0 08/2014 First version

Configurations WinCC Runtime Professional


Entry ID: 87054082, V1.0, 09/2014 90